Panasonic 1736 Operating instructions
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Fire alarm systems
Alert annunciation units
1735 and 1736
• Control and indicating unit for alert annunciation
• Compact size
Alert annunciation unit
When the Alert Annunciation function shall be used in the systems EBL512 & EBL128 an AA unit is required to present the AA alarms and for the related manoeuvres, i.e. to acknowledge / reset the alarms. For a detailed description of the AA function, see
Planning and Operating instructions for the system respectively.
Point or zone alarm presentation is as in the c.i.e. it is connected to. When there are queued alarms in the system, you can scroll amongst them. All or selected alarms will be presented in the unit's display (LCD,
2x40 characters with back-light). A user definable text message will be presented together with each alarm, if programmed in the c.i.e. Furthermore, > 617 texts can for selected alarms be stored in the unit and will in that case be shown, instead of the texts sent from the c.i.e. for these alarms. A builtin buzzer will sound to indicate a not acknowledged AA alarm. The unit is power supplied via the c.i.e. or ext. power supply.
• Acknowledge, indicating that the AA alarm has been acknowledged.
The unit has the following push buttons:
• Alarms queued, used to scroll amongst the alarms.
• Acknowledge, used to acknowledge an
AA alarm and hereby also silence the buzzer.
• Reset, used to reset an AA alarm.
1735 has the designation texts in Swedish.
1736 has a neutral front for other languages, see the opposite side of this page. (This front also holds one extra LED & two extra push buttons.)
Compact size
The compact size enclosure is made of grey high impact ABS. Fitted with a supplementary "O" ring gasket, it will comply with
IP61, in respect of dust and moisture. The unit has no door, i.e. the front is accessed directly, when required. The push buttons are disabled until they are supposed to be used. The unit shall be wall mounted. Two compression glands are attached.
LEDs, push buttons etc.
The unit has the following LEDs:
• Fire and Alarms queued, indicating fire alarm / AA alarm.
• Operation, indicating that the AA function is enabled in the system.
Normally a time channel is used to enable this function.
• Fire brigade alerted, indicating that the
"Fire brigade tx" output is activated in the c.i.e. because:
- the activated alarm is not an AA alarm
- the AA function has been ended, e.g. the acknowledge or investigation time has run out, etc.
SW mode and address setting
The display and the push buttons are used to set the SW mode and address.
The SW modes are described on the opposite side of this page.
Product application
The units are intended for indoor use and in dry premises. They are intended to be used in the systems EBL512 & EBL128. An
External FBP / DU interface board 1587 is required in the EBL512 c.i.e. and a 4552
Transceiver component in the EBL128 c.i.e.
Panasonic Electric Works Fire & Security Technology Europe AB
Citadellsvägen 23, SE-211 18 Malmö, Sweden
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 [email protected] • www.panasonic-fire-security.com
1735
1736
1587
4552
Type numbers
Alert annunciation unit. Swedish designation texts.
Alert annunciation unit. Designation texts in any language.
External FBP / DU interface board in EBL512, for connection of the 1735 and
1736 units in system EBL512. (Software version > 2.2 is required.)
RS485 transceiver component, for connection of up to four display units, e.g.
Alert Annunciation Units 1735 / 1736 in system EBL128.
NOTE! The number of units that can be power supplied via the c.i.e. (or an external power supply) is depending on all other units connected to the same c.i.e. / external power supply. Up to 1200 m cable can be used.
The 1736 unit has a neutral front where the designation texts, by production, are made separately and put into a transparent "text slot" for the LED and push button respectively.
1735 succeeds the Display unit (with alert annunciation) 2235SE but not as a spare part, since
2235SE is connected to a COM loop and 1735 requires an Ext. FBP / DU interface board 1587 in the c.i.e.
(2235SE = Swedish designation texts.)
1736 succeeds the Display unit (with alert annunciation) 2235xx but not as a spare part, since
2235xx is connected to a COM loop and 1736 requires an Ext. FBP / DU interface board 1587 in the c.i.e.
(2235xx = Designation texts in another language than Swedish.)
The AA unit 1735 and AA unit 1736 shall run in SW mode 1735 – 1587 and SW mode 1736 –
1587 respectively.
Voltage (V DC)
rated
allowed
normal (in the system)
normal (in the system by battery back-up)
Current consumption at norm. volt. (mA)
AA unit 1735 / 1736
quiescent / active
Ambient temperature (
°C)
operating
storage
Ambient humidity (% RH)
Ingress Protection rating (estimated)
Size W x H x D (mm)
Weight (g)
1735
1736
Colour (high impact ABS)
Approvals
Technical data
24
12-30
24
21-27
26 (at 24 V), 48 (at 12 V) / 42 (at 24 V), 79 (at 12 V)
0 to +40
-40 to +70 max. 90, non condensing
IP61 (with the "O" ring gasket)
220 x 145 x 50
687
691
Grey (RAL 7035)
CE; Conforms with EN54-2 and –4 whenever applicable.
Conforms with SBF 110:6.
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision