Digital SSI Converter
DIGICON/V2
Type: DK/SSS Version 2
Digitronic Automationsanlagen GmbH
Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10
Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42
Internet: http://www.digitronic.com • E-Mail: [email protected]
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
Notification
This handbook corresponds with the unit version of 22.2.1999. The company Digitronic
Automationsanlagen GmbH reserves the right to implement changes that result in an improvement of
the quality and the functions of the device at any time and without any announcements.
This instructions manual was created with a maximum of care, but mistakes are not out of the
question. We are thankful for any comments, regarding possible mistakes in the instruction manual.
UP-date
You can also obtain this instruction manual on the Internet at http://www.digitronic.com in the latest
version as PDF file.
Qualified personal only
Commissioning and operation of the device may only be carried out by qualified personal. Qualified
personal are persons, authorized with commissioning, grounding and labeling devices, systems and
electrical circuits according to the applicable standards of security
Liability
(1) The salesperson is liable for any damages for which he or the rightful owner is responsible up to
the amount of the actual salesprice. Liability concerning missed profits, failed-to-appear savings,
indirect damages and consequential damage is excluded.
(2) The liability restrictions above are not valid concerning assured characteristics and damages, which
are caused by intention or coarse negligence.
Protection
The device DIGICON/V2 and this instruction manual are protected by copyright. All rights are reserved.
Neither the device DIGICON/V2, nor this document may be copied as a whole or partially, photocopied,
reproduced, translated or transferred to electronic media of any kind or into machine readable format
without prior written permission by the company Digitronic Automationsanlagen GmbH.
Note:
The products of Digitronic are so well constructed that they will not be effected by the
millenium.
Note:
This device fulfills the following norms according to electromagneticalcompatibility:
EN 55011, EN 55022, EN 55024 Teil 2, EN 50082 Teil 2, ENV 50140, VDE 0843
Teil 2, VDE 0843 Teil 4, VDE 0871, VDE 0875 Teil 3 ("N"), VDE 0875 Teil 11,
VDE 0877 Teil 2, IEC 801 Teil 3, IEC 801 Teil 2, IEC 801 Teil 4, IEC 801 Teil 5.
Note:
This device fulfills the following norms according to electromagneticalcompatibility:
EN 55011, EN 55022, EN 55024 Teil 2, EN 50082 Teil 2, ENV 50140, VDE 0843
Teil 2, VDE 0843 Teil 4, VDE 0871, VDE 0875 Teil 3 ("N"), VDE 0875 Teil 11,
VDE 0877 Teil 2, IEC 801 Teil 3, IEC 801 Teil 2, IEC 801 Teil 4, IEC 801 Teil 5.
(c) Copyright 1992 - 2008 / Datei: DKSSSV2E.DOC
Digitronic Automationsanlagen GmbH
Auf der Langwies 1
D-65510 Hünstetten - Wallbach
Tel. (+49)6126/9453-0 Fax. (+49)6126/9453-42
Internet: http://www.digitronic.com / E-Mail: [email protected]
Version: 17.06.08
Page: 2
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
Table of content
1. Introduction .......................................................................................................................................... 3
2. Assembly ............................................................................................................................................. 4
3. Operation ............................................................................................................................................. 4
3.1. Status LED........................................................................................................................................ 4
4. Dimensions .......................................................................................................................................... 4
5. Pin allocation........................................................................................................................................ 5
5.1. Pin allocation: Supply voltage ........................................................................................................... 5
5.2. Pin allocation: SSI Input (Master) ..................................................................................................... 5
5.3. Pin allocation SSI Output 1 (Slave)................................................................................................... 5
5.4. Pin allocation SSI Output 2 (Slave)................................................................................................... 5
6. DIP Switch configuration...................................................................................................................... 6
6.1. DIP Switch 1 + 2 (Clock frequency) .................................................................................................. 6
6.2. DIP Switch 3 (Listening mode).......................................................................................................... 6
6.3. DIP Switch 4 (Error Bit)..................................................................................................................... 6
7. Connection examples .......................................................................................................................... 7
7.1. Connection example: Default............................................................................................................ 7
7.2. Connection example: Listening mode............................................................................................... 7
8. Technical Data ..................................................................................................................................... 8
1. Introduction
Measruing systems with a synchronous serial interface (SSI) cannot be simultaneously connected to
two separat controllers, both needing the position value. DIGICON makes it possible to transmit
(copying the position values) the data of the measuring system to two controllers (e.g. our digital cam
controllers and a PLC).
Features:
-
Supply voltage: 24V DC ±20%
Power absorption: 200mA in lost motion
For SSI signals up to 25BIT
Listening Mode
or optionally with incrmental in- or output
Cycle time < 1 ms
Transmitter level SSI: RS422
Connections: IP20 standard screw-pins
Assembly: clip-on assembly on symmetrical carrier rail according to EN 50 022, row assembly
Cover type: cover corresponds with IP20
Operating temperature: 0°C to + 55° C
Weight: about 500g
Version: 17.06.08
Page: 3
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
2. Assembly
The device is snapped onto the "EN carrier rail" in the switchboard (see chapter "4. Dimensions" on
page 4). The grounding pins and the cable mantling have to be put on the shortest way possible onto a
serial grounding pin next to the device. Through the grounded assembly board and its electrical
connection to the EN carrier rail, the disturbances are optimally grounded onto the cover. All cable
connections have to be realized in a cold state! Use double-wired, shielded connection cable only. Do
not lay the cable paralel to high tension power cables. If possible, lay shieldings to both sides.
3. Operation
Connect DIGICON to the measuring system and the controller according to the pin allocation. See also
chapter 5. Pin allocation on page 5. After activation DIGICON receives its voltage supply, and it, in
turn, supplies the measuring system. Which of the controllers is activated first does not matter, since
both currents are connected throug diodes in the DIGICON. DIGICON has an activation delay of about
10 sec, during witch the SSI output gives non-defined signals. Connected devices (e.g. PLC) have to
consider this !
3.1. Status LED
The status LED announces after approx.. 10 seconds ready status by continuous lights. Is the LED off
or flashes, the device has no power or is defective.
4. Dimensions
The following carrier rails can be used for the assembly of the cover:
NS 35 / 7.5 (DIN 50022)
NS 35 / 15 (DIN 50022)
NS 32 (DIN 50035)
Version: 17.06.08
Page: 4
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
5. Pin allocation
.
5.1. Pin allocation: Supply voltage
Pin
21
22
23
24
25
26
27
28
29
30
Description
0V Supply voltage
0V Supply voltage
+ 24V Supply voltage
+ 24V Supply voltage
0V
0V
Input 1
Input 2
Input 3
Input 4
5.2. Pin allocation: SSI Input (Master)
Pin
31
32
33
34
35
36
Description
0V measuring system supply
Data A (+) of the measuring system
Data B (-) of the measuring system
Clock A (+) of the measuring system
Clock B (-) of the measuring system
+ 24 VDC Supply voltage of the measuring system
5.3. Pin allocation SSI Output 1 (Slave)
Pin
1
2
3
4
5
6
7
8
Description
0V Supply voltage
Data A (+)
Data B (-)
Clock A (+)
Clock B (-)
+ 24 VDC Supply voltage
Clear (+) with incremental output option
Clear (-) with incremental output option
5.4. Pin allocation SSI Output 2 (Slave)
Pin
9
10
11
12
13
14
15
16
Note:
Description
0V Supply voltage
Data A (+)
Data B (-)
Clock A (+)
Clock B (-)
+ 24 VDC Supply voltage
Clear (+) with incremental output option
Clear (-) with incremental output option
Pins 21, 22, 25, 26, 31, 1 and 9 are interconnected.
Pins 23 and 24 are interconnected.
Version: 17.06.08
Page: 5
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
6. DIP Switch configuration
DIGICON can be configured for many different applications through the DIP switch of the device.
To change the DIP switch setting, you have to open the device. You can open the cover in the center
with a screwdriver.
Attention:
Please take care not to damage the board or the other devices with the screwdriver.
DIP switch
The factory setting (default): switch 1 - 3 = OFF and 4 = ON.
6.1. DIP Switch 1 + 2 (Clock frequency)
DIP Switch 1
OFF
ON
OFF
ON
DIP Switch 2
OFF
OFF
ON
ON
Clock
576 KHz Clock (default)
288 KHz Clock
144 KHz Clock
external Clock at pins 4 & 5 (max. 600 KHz).
DIGICON does not create the clock for the measuring system, if both DIP switches are set to ON, but it
transmitts the Clock signal on pins 4 and 5 to pins 34 and 35. This synchronizes the data of the SSI
output 1 to the data of the SSI input.
6.2. DIP Switch 3 (Listening mode)
If this DIP switch is set to ON, DIGICON produces no own Clock signals, but triggers upon an xternal
Clock signal (listening) (max. 600 KHz) on pins 34 and 35. This makes it possible to send the data of
the SSI interface to two further devices (default = OFF).
6.3. DIP Switch 4 (Error Bit)
If this DIP switch is set to ON, DIGICON generates an SSI error at the SSI outputs, as soon as an error
is detected on the SSI input (default = ON). Is the DIP switch set to OFF, the data on the SSI outputs is
frozenuntil the error at the SSI input has been corrected.
Note:
This DIP - Switch must with single turn - encoders and/or Measuring systems with less
than 25 SSI - Bits become switched OFF, there the SSI - error bit in the software is fix on
bit 26.
Version: 17.06.08
Page: 6
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
7. Connection examples
.
7.1. Connection example: Default
DIP switch 1 - 3 = OFF and 4 = ON.
SSI input (master)
SSI output 1 (slave)
SSI output 2 (slave)
7.2. Connection example: Listening mode
DIPswitch 1 + 2 = OFF and 3 + 4 = ON.
SSI input (master)
SSI output 1 (slave)
SSI output 2 (slave)
Version: 17.06.08
Page: 7
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
DIGICON
DK/SSS/V2
8. Technical Data
Supply voltage........................... 24 VDC +/- 20% via the voltage supply of the controllers, connected at
the outputs
Power absorption ...................... 100 mA without load.
Display ...................................... 1 x LED "ready for operation"
Input .......................................... 1 * synchronous serial (SSI) RS422,
optional incremental input RS422.
4 * 24V PNP inputs for options.
Output ....................................... 2 * synchronous serial (SSI) RS422,
optional incremental output RS422.
Transmitting depth .................... 25 Bit (see chapter "6.3. DIP Switch 4 (Error Bit)").
Monoflop time ........................... 25µs.
Clock SSI Input ......................... 144, 288, 576 KHz or external (max. 600KHz).
Clock SSI Output ...................... 100 - 600 KHz.
Cycle time ................................. synchronous to SSI read-in: 120µsec - 450µsec or external
Transmitting level...................... RS422, one-sided galv. separated
Cover ........................................ hardly ignitable Thermoplast plastic, continous temperature up to
100°C
Connections .............................. plug block pins
Connection cable ...................... covered cable, max. length between measuring system and DIGICON
300 meters according to set Clock frequency.
Assembly .................................. comfortable snap-on assembly onto symmetrical carrierer rail
according to EN 50 022, row assembly possible.
Dissembly ................................. by pulling back the snap clip.
Dimensions ............................... see chapter 4. Dimensions.
Cover type................................. Cover corresponds with IP20.
Operating temperature.............. 0° to + 55° C.
Weight....................................... about 500g.
Version: 17.06.08
Page: 8
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com