225 kVA
Features at-a-glance
Single/Parallel in one box for modular design
Parallel Circuits in each UPS for reliability
True Online, Double-Conversion Technology
Dual Input Design (Alternate Input for bypass)
Static Bypass Switch
- Thyristor + Contactor for highest reliability
LCD Touch screen Graphic Display
IGBT Inverter – Space Vector Modulation
Output Isolation Transformer
All Digital Signal Processor (DSP) software logic using 12 bit processor
Front Access for Installation and
Maintenance.
Bottom or Side Access for Power Cables.
Input Specifications
Voltage range: 480V +15% -15%
(Optional Cabinet for 208V, 600V)
Frequency range: 60Hz, +/- 5%
Power factor: >0.98
Input current THD: less than 6% at 100% load
Surge protection: Meets ANSI C62.41
Battery Specifications
Cabinets or Racks with DC Breaker
Battery type: Sealed Valve Regulated Lead-Acid
Recharge time: 10 x discharge time to 90% capacity
DC Link: 480VDC Nominal
Environmental Specifications
Ambient temperature: 0C to +40C
Relative humidity: 5%-95% Non-Condensing
Altitude: 0 to 9000 feet without derating
Audible noise: Less than 76 dBA at 1 meter
Battery Temperature
Compensation
Generator Compatible 1.1:1
Monitoring Options
- RemotEye II (SNMP/Web)
- Memory Card w/software
- Dry Contacts
Output Specifications: 225
kVA/180 kW (0.8PF)
Voltage: 480Y/277V Standard
(Optional 600/347V)
Voltage regulation: +/- 1%
Freq. regulation: +/- 0.05% (Free running)
Dynamic response: +/-2% at 100% step load
Voltage Distortion:
(recovery in less than 1 cycle)
Less than 2% for 100% linear load
Less than 5% for 100% non-linear load
Freq. sync range:
Freq. slew rate:
+/- 5% (user selectable)
1 – 10 Hz/second (user selectable)
Voltage adjustment: +/-5% (user selectable)
Overload capacity: 1000% for 1 cycle
150% for 1 minute
Crest Factor:
125% for 10 minutes
2.3 : 1
Safety
UL/CUL 1778 Listed
All cabinets provide for seismic zone 4 mounting
Options
Input/Output Transformer Cabinet
Maintenance Bypass Cabinet
RemotEye II Network Adapter
“Security Plus” Maintenance Agreement
T8MS3K22KK6XSN rev 1.2 29 September 2009
G8000MM 225 kVA UPS Specifications
Item: T8MS3K22KK6XSN
Input Voltage
Output Voltage
Volts
Volts
Input Voltage Range
Minimum
Maximum
Frequency
AC Input Current
Nominal Amps
Maximum Amps
(1)
Bypass Input
Nominal Amps
Volts
Volts
Hz
Amps
Amps
Volts
Amps
AC Output Current
Nominal Amps Amps
10 Minutes Max. Amps
225
225kVA/180kW
480
480/277
+15% to -15%
408
552
60
(> 0.98 PF)
237
254
480/277
271
(at 0.8 PF)
271
338
Item: T8MS3K22KK6XSN
DC Link
Nominal DC Voltage Volts
Float Voltage
End of Discharge
Charger
Efficiency
Efficiency
Volts
Volts
Amps
Full Load Heat Dissipation
BTU/Hr.
kW
%
(1) Maximum Amps equals full load current plus battery recharge current.
225
225kVA/180kW
480
545
400
29.3 (Max)
93.3
44,105
12.9
T8MS3K22KK6XSN rev 1.2 29 September 2009
G8000MM 225 kVA UPS Specifications
A A
B
C
B
C
T8MS3K22KK6XSN rev 1.2 29 September 2009
G8000MM 225 kVA UPS Specifications
T8MS3K22KK6XSN rev 1.2 29 September 2009