VDW-XF Series Compact/Lightweight 2 Port Solenoid Valve for Air, Water

VDW-XF Series Compact/Lightweight 2 Port Solenoid Valve for Air, Water
VDW30-Info.qxd
10.5.31 10:51 AM
Page 1
Akihabara UDX 15F,
4-14-1, Sotokanda, Chiyoda-ku,
Tokyo 101-0021, JAPAN
URL http://www.smcworld.com
Information
©2010 SMC Corporation All Rights Reserved
09-E562
D-DN Printing OT 12450KS
Compact / Lightweight 2 Port Solenoid Valve
Series VDW30/40-XF
쎲 Compact / Lightweight resin body (PPS)
Weight: 120 g
For Air/Water
RoHS
IP65
(VDW30-XF)
30
on
.
El
e
m
m
48 mm
쎲 Power
consumption
entry d
ical sel irect
r
t
ecte i
e
c nb
d
a
c
3 W (Standard)
power-saving
0.5 W (With
circuit)
m
50 m
∗ VDW30-XF
Quick fastener
Piping labor reduced
One-touch fitting
No torque control needed, easy handling.
Quick fastener body
One-touch fitting body
Quick fastener clip
Male quick fastener
(∗ Male quick fasteners are
not included.)
Female quick fastener
One-touch fitting
Application Examples
Fuel cell cogeneration system Note)
Dispenser
Automatic faucet
Note) A portion of the design and development work for this product was conducted as part of the Peripheral Equipment Technology Development for Household Fuel
Cell Systems project sponsored by the New Energy and Industrial Technology Development Organization (NEDO). In principle, supply of the product for
household fuel cell system applications with a capacity of 3 kW or less commences in April 2010.
1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 2
Compact / Lightweight
2 Port Solenoid Valve
For Air/Water
Series VDW30/40-XF
RoHS
How to Order Valves (Single Unit)
VDW 3 1
5G
1
P7
XF
Series
3 30
4 40
Option
Nil
N
K
Valve type
N.C.
None
Bottom mounting insert type
With 2 quick fastener clips Note)
Note) Port connection type: Supports P7 and
P10 quick fasteners only.
OUT
(2)
1
Body material and coil insulation type
Symbol Body material Seal material Coil insulation
NBR
Nil
PPS
FKM
Class B
A
EPDM
B
(1)
IN
Voltage
5
6
24 VDC
12 VDC
Port connection type
Symbol
Coil type
G
Grommet
Power-saving circuit
Nil
E
Size
P7 quick fastener
P10 quick fastener
One-touch fitting for ø4
One-touch fitting for ø6
One-touch fitting for ø8
One-touch fitting for ø10
P7
P10
C4
C6
C8
C10
None
With power-saving circuit
Series
30
40
30
40
Electrical entry direction
Piping direction
45° left direction
IN
IN
L1
Nil
OUT
OUT
45° right direction
90° left direction
IN
R1
Orifice diameter
Symbol
Orifice diameter
(mm ø)
1
3
4
6
1.0
3.0
4.5
6.0
Series
30
40
Quick Fastener Clip Part No.
Series
Size
Quick fastener clip
part no. (2 pcs.)
Material
30
40
P7 quick fastener
P10 quick fastener
VDW30-CP7
VDW40-CP10
Stainless
steel
IN
∗ Ten pieces come in each set.
L2
Quick fastener clip
OUT
90° right direction
IN
OUT
Note) Cannot be reassembled in
different combinations.
Male quick fastener
(∗ Male quick fasteners are
not included.)
R2
Female quick fastener
OUT
2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 3
Compact / Lightweight 2 Port Solenoid Valve
For Air/Water
Series VDW30/40-XF
Standard Specifications
Direct operated poppet
Valve construction
Valve specifications
Normally closed (N.C.)
Valve type
Quick fastener type
Water (1 to 50°C), Air, Inert gas, Heated water (80°C) Note 3), Low vacuum (133 Pa·abs)
Fluid
One-touch fitting type Note 4) Air, Inert gas, Water (1 to 40°C) Note 5), Low vacuum (133 Pa·abs)
1.0 MPa
Withstand pressure
–10 to 50°C
Ambient temperature
1 to 50°C (No freezing)
Fluid temperature
RH85%
Ambient humidity
Location without corrosive or explosive gases
Environment
Valve leakage Note 1)
0.1 cm3/min or less (With water pressure), 1 cm3/min or less (Air)
Exterior leakage
0.1 cm3/min or less (With water pressure), 1 cm3/min or less (Air)
Mounting orientation
Upward coil
Vibration/Impact Note 2)
30 m/s2 / 90 m/s2
P7, P10 (Quick fastener)
C4, C6, C8, C10 (One-touch fitting)
Port size
Orifice diameter
ø1, ø3, ø4.5, ø6
Rated voltage
24 VDC, 12 VDC
±10% of rated voltage
Coil specifications
Allowable voltage fluctuation
Class B
Coil insulation type
500 VDC, 10 MΩ or more
Insulation resistance
1800 VAC, 1 sec., 3 mA or less
Simulation noise: 500 Vp-p
(Based on 1 µ sec. pulse width, 50 ±10 Hz frequency noise simulation)
Fast transient noise: IEC61000-4-4: 1 kV
Voltage limit
Noise tolerance Note 3)
VDW30: 3 W (With 0.5 W power-saving circuit)
VDW40: 6.5 W (With 1 W power-saving circuit)
Power consumption
IP65
Enclosure
Note 1) The amount of leakage from the OUT port when the set pressure is applied to the IN port.
Note 2) Vibration resistance ····· No malfunction when tested with one sweep of 10 to 150 Hz in the axial direction
and at a right angle to the armature, in both energized and deenergized states.
Impact resistance ········ No malfunction when tested with a drop tester in the axial direction and at a right
angle to the main armature, one time each in energized and deenergized states.
Note 3) Products with power-saving circuit only.
Note 4) When using One-touch fittings, make sure to employ tubing that is compatible with SMC fittings
(Series KQ2).
Note 5) When using One-touch fittings with water, care must be taken when handling tubing and piping
conditions to prevent water from leaking when the tubes are inserted. Soft nylon tubing cannot
be used with water.
Characteristic Specifications
Model
Port
Orifice dia.
connection
(mm ø)
type
VDW30
P7
C4, C6
VDW40
P10
C8, C10
Max. operating pressure
differential (MPa) Note 1)
Pressure port 1
1.0
3.0
4.5
6.0
Operating
Weight
Pressure range
(kg)
(MPa) Note 2) Note 3)
0.6
0.1
0.1 (With power-saving circuit)
0.05 (Without power-saving circuit)
0.1
– 0.1 to 0.6
0.23
0.05 (With power-saving circuit)
0.02 (Without power-saving circuit)
Note 1) The maximum operating pressure differential changes depending on the flow direction of the
fluid. Refer to page 7 for details.
Note 2) For low vacuum specifications, the operating pressure range is 1 Torr (1.33 x 102 Pa) to 0.6 MPa.
Please consult with SMC if using below 1 Torr (1.33 x 102 Pa).
Some leakage is permitted, so avoid use in situations where a vacuum must be maintained,
such as in leak testing.
Note 3) The surge pressure must be under the maximum operating pressure.
Flow Characteristics
Model
VDW30
Water
Air
Orifice dia.
Port
(mm ø)
connection
1→2 (IN→N.C.)
1→2 (IN→N.C.)
type
N.C.
b
Av x 10–6 m2 Cv converted C [dm3/(s·bar)]
P7, C4, C6
VDW40 P10, C8, C10
1.0
Cv
0.96
0.04
0.14
0.4
0.09
6.7
0.28
1.0
0.52
0.3
4.5
15
0.61
2.3
0.46
0.61
6.0
24
1.1
4.0
0.4
1.1
3.0
3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 4
Series VDW30/40-XF
Construction
Component Parts Materials
w
e
t
i
r
y
u
OUT
No.
1
2
3
4
5
6
7
8
9
10
q
o
!0
IN
q
Description
Material
PPS
Body
Stainless steel
Tube assembly
—
Coil assembly
Stainless steel, NBR, FKM, EPDM
Armature assembly
Stainless steel
Return spring
Flame
Iron
O-ring
NBR, FKM, EPDM
Iron
Round head combination screw
POM, Stainless steel
Cassette
NBR, FKM, EPDM
Seal
Caution
One-touch fitting
Do not disassemble.
Dimensions
VDW40-쏔G쏔쏔-쏔-P10 / P10 Quick Fastener
36
30
VDW30-쏔G쏔쏔-쏔-P7 / P7 Quick Fastener
21
Approx. 300
23
Approx. 300
10
9
P7
1 (IN) port
50
P7
2 (OUT) port
21
P10
1 (IN) port
56
P10
2 (OUT) port
VDW40-5G쏔쏔-쏔-P10-쏔-N
16
12
VDW30-5G쏔쏔-쏔-P7-쏔-N
2 x M3 x 0.5 thread depth 4
2 x M3 x 0.5 thread depth 5
Male Quick Fastener Dimensions
Quick Fastener Clip Dimensions
∗ Male quick fasteners
are not included.
6±0.15
1.6 or more
D
C
B
A
E
2 or more
Rz 3.2 or less for
sheet surface
P7
0
–0.05
P10
A
0
–0.05
A
B
C
D
E
ø7
ø9.9±0.05
ø15
2.5+0.25
0
ø13
ø10
ø12.85±0.05
ø20
2.5+0.25
0
ø17
O-ring dimentions∗
(Nominal no.)
P7
P10
Port size
(Quick fastener)
C
Port size
(Quick fastener)
9 or less
O-ring
Applicable Clip Part No./Dimentions
Male Quick Fastener Dimensions Table
D
2.5±0.1
4
ø32
ø27
56
20
48
18
12±0.1
B
P7
P10
Clip part no. VDW30-CP7 VDW40-CP10
26
28
A
7
10
B
9
10
C
14
15
D
Applicable clip Clip for P7 Clip for P10
∗ Conforms to JIS B 2401 dimensional
standard for O-rings for industrial
applications.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 5
Compact / Lightweight 2 Port Solenoid Valve
For Air/Water
Series VDW30/40-XF
Dimensions
VDW40-쏔G쏔쏔-쏔-C8
C10 /One-touch fitting for ø8, ø10
30
36
VDW30-쏔G쏔쏔-쏔-C4
C6 /One-touch fitting for ø4, ø6
21
Approx. 300
18
21
3
23
Approx. 300
10
9
3
21
C4, C6
1 (IN) port
C4, C6
2 (OUT) port
ø32
ø27
56
20
48
17.5
A
23
26
C8, C10
2 (OUT) port
A
C8, C10
1 (IN) port
Dimentions
VDW40-쏔G쏔쏔-쏔-C쏔-쏔-N
Series
A
C8
VDW40
C10
3
4
12
VDW30-쏔G쏔쏔-쏔-C쏔-쏔-N
2 x M3 x 0.5 thread depth 4
2 x M3 x 0.5 thread depth 5
For information on handling One-touch fittings and appropriate tubing, see Series KQ2 One-touch fittings
in Best Pneumatics No. 6. It can be downloaded from the SMC Web site: http://www.smcworld.com/
5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 6
Series VDW30/40
Specific Product Precautions 1
Be sure to read before handling. Refer to back cover for Safety Instructions, “Handling
Precautions for SMC Products” (M-E03-3) for Fluids Control 2 Port Valves Precautions,
and Series VDW in Best Pneumatics No. 7 for Specific Product Precautions.
Selection
Mounting
Warning
Warning
1. Fluid quality
In the case of water
The use of a fluid which contains foreign matter can cause
problems such as malfunction and seal failure by promoting
wear of the valve seat and armature, and by sticking to the
sliding parts of the armature, etc. Install a suitable filter
(strainer) immediately upstream from the valve. In general, a
mesh of about 50 to 100 is a guideline for the filter.
When using ordinary tap water, scaling and sludge from
substances in hard water such as calcium and magnesium
can cause solenoid valves to malfunction. It is therefore
necessary to install a water softener to remove such
substances and a filter (strainer) immediately before the
solenoid valve.
In the case of air
Please use ordinary compressed air where a filter of 40 µm or
less is provided on the inlet side piping. (Except dry air)
Caution
Particularly when using a resistor in parallel with a switching
element and using a C-R element (surge voltage suppressor)
to protect the switching element, take note that leakage current will flow through the resistor, C-R element, etc., creating
a possible danger that the valve may not turn off.
Switching element
Leakage voltage
OFF
Power supply
Piping
Warning
1. During use, deterioration of the tubing or damage
to the fittings could cause tubes to come loose
from their fittings and thrash about.
To prevent uncontrolled tube movement, install protective
covers or fasten tubes securely in place.
Caution
2. Connection of piping to products
1. Leakage voltage
C
1. When the valve is secured using an insert nut (part
number suffix “-N”), handle with care during
installation because the application of excessive
stress to the body could damage it (appropriate
tightening torque: 0.8 to 1.0 N·m).
• When connecting piping to a product, refer to its instruction
manual to avoid mistakes regarding the supply port, etc.
• Do not apply external force to the coil when holding it to connect piping, as the tube may deform.
• When attaching fittings to a solenoid valve, do not use fittings that do not conform to the quick fastener standard.
• Handle with care when attaching fittings because the application of excessive stress to the quick fastener portion could
damage the body.
R
Valve
Recommended Piping Conditions
Leakage current
1) Take steps to ensure that there are no problems such as
abnormal voltage drops or insufficient capacity associated
with the signal power supply used to drive the solenoid
valve.
2) Make sure the leakage current flowing through the solenoid
valve when power is not being supplied is 0.1 mA or less. If
there the leakage current is larger than this, take
appropriate measures such as connecting a bleeder
resister (models with power-saving circuit).
3) An attenuation function is provided to reduce voltage
surges produced by the solenoid valve. However, the
controller should be equipped with protection against
voltage surges as some residual surge voltage may still
reach external components.
DC coil
2% or less of rated voltage
1. When connecting tubes
using One-touch fittings,
provide some spare tube
length as shown in Fig. 1,
recommended piping configuration.
Also, do not apply external
force to the fittings when binding tubes with bands, etc. (see
Fig. 2.)
Straight
portion
Mounting
pitch A
Fig. 1 Recommended piping
configuration
Unit: mm
Tube size
Mounting pitch A
Straight
Nylon tube Soft nylon tube Polyurethane tube portion length
ø4
56 or more
30 or more
26 or more
20 or more
ø6
84 or more
39 or more
39 or more
30 or more
ø8
112 or more
58 or more
52 or more
40 or more
ø10
140 or more
70 or more
69 or more
50 or more
2. Low temperature operation
1) The valves can be used up to an ambient temperature of
–10°C, however take measures to prevent solidification of
impurities or freezing, etc.
2) When using valves for water application in cold climates,
first stop the water supply/discharge of the pump, etc., and
then take measures to prevent freezing such as draining
water in pipe. When heating by steam, be careful not to expose the coil portion to steam. Also, please take measures
to prevent freezing such as heating the body.
Recommended
Unacceptable
Fig. 2 Binding tubes with bands
6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 7
Series VDW30/40
Specific Product Precautions 2
Be sure to read before handling. Refer to back cover for Safety Instructions, “Handling
Precautions for SMC Products” (M-E03-3) for Fluids Control 2 Port Valves Precautions,
and Series VDW in Best Pneumatics No. 7 for Specific Product Precautions.
Electrical Connections
Fluid Flow Direction
Caution
Caution
1. Solenoid valves with power-saving circuits (coil
part number “-5GE”) have polarity, so follow the
wiring diagram below when making connections.
Standard coils have no polarity.
The maximum operating pressure differential differs depending
on the flow direction of the fluid. If the pressure differential at
each port exceeds the values in the table below, valve leakage
may occur.
OUT
(2)
The solenoid valve will not switch properly if the polarity is reversed.
Standard coil
Red (+)
SOL.
2 (–, +)
Black (–)
Power-saving
circuit
1 (+, –)
Coil with power-saving circuit
(1)
IN
DC circuit
2 Port Valve
SOL.
2. Apply the correct voltage.
Incorrect voltage could cause shorting of the power-saving circuit, coil burnout, or valve malfunction.
3. Do not apply a tension load of 30 N or more to the
solenoid valve lead wires.
Model
VDW30
Orifice diameter
(mm ø)
5. When connecting an induction load such as a circuit protector to the solenoid valve connection,
take measures to ensure that the current to the solenoid valve is not reduced too much.
Pressure port 1
1.0
3.0
4.5
VDW40
6.0
4. Apply voltage which is within ±10% of the rated voltage.
Also, do not use excessive power supply voltage or superimpose electrical noise such as ripple voltage on the power supply voltage as these could harm the valve.
Max. operating pressure differential
(MPa)
0.6
0.1
0.1 (With power-saving circuit)
0.05 (Without power-saving circuit)
0.05 (With power-saving circuit)
0.02 (Without power-saving circuit)
One-touch Fittings
Caution
For information on handling One-touch fittings and
appropriate tubing, see Series KQ2 One-touch fittings
in Best Pneumatics No. 6. It can be downloaded from
the SMC Web site: http://www.smcworld.com/
Maintenance
Warning
1. Do not disassemble solenoid valves.
Disassembling a solenoid valve will void its warranty.
2. Low frequency operation
Switch valves at least once every 30 days to prevent
malfunction. Also, in order to use it under the optimum state,
conduct a regular inspection once a half year.
Caution
1. Store indoors in a location away from direct sunlight and where the following conditions are maintained.
• Temperature: –10 to 50°C
• Relative humidity: 20% to 85%RH (No condensation)
• Liquid rings may not be used.
2. Storage
When not using for a long time (more than approx. one
month) after use with liquid, thoroughly remove all moisture to
prevent rust and deterioration of rubber materials, etc.
7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
VDW30-Info.qxd
10.5.31 10:51 AM
Page 8
Safety Instructions
Caution:
These safety instructions are intended to prevent hazardous situations and/or
equipment damage. These instructions indicate the level of potential hazard with
the labels of “Caution,” “Warning” or “Danger.” They are all important notes for
safety and must be followed in addition to International Standards (ISO/IEC)∗1),
and other safety regulations.
Caution indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.
Warning:
Warning indicates a hazard with a medium level of
risk which, if not avoided, could result in death or
serious injury.
Danger :
Danger indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.
Warning
1. The compatibility of the product is the responsibility of the
person who designs the equipment or decides its
specifications.
Since the product specified here is used under various operating
conditions, its compatibility with specific equipment must be decided by
the person who designs the equipment or decides its specifications
based on necessary analysis and test results. The expected performance
and safety assurance of the equipment will be the responsibility of the
person who has determined its compatibility with the product. This person
should also continuously review all specifications of the product referring
to its latest catalog information, with a view to giving due consideration to
any possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate
machinery and equipment.
The product specified here may become unsafe if handled incorrectly.
The assembly, operation and maintenance of machines or equipment
including our products must be performed by an operator who is
appropriately trained and experienced.
3. Do not service or attempt to remove product and
machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only
be performed after measures to prevent falling or runaway of the
driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures
as mentioned above are implemented and the power from any
appropriate source is cut, and read and understand the specific
product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent
unexpected operation and malfunction.
4. Contact SMC beforehand and take special consideration of
safety measures if the product is to be used in any of the
following conditions.
1. Conditions and environments outside of the given specifications, or use
outdoors or in a place exposed to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways,
air navigation, space, shipping, vehicles, military, medical treatment,
combustion and recreation, or equipment in contact with food and
beverages, emergency stop circuits, clutch and brake circuits in press
applications, safety equipment or other applications unsuitable for the
standard specifications described in the product catalog.
3. An application which could have negative effects on people, property,
or animals requiring special safety analysis.
4. Use in an interlock circuit, which requires the provision of double
interlock for possible failure by using a mechanical protective function,
and periodical checks to confirm proper operation.
∗1) ISO 4414: Pneumatic fluid power – General rules relating to systems.
ISO 4413: Hydraulic fluid power – General rules relating to systems.
IEC 60204-1: Safety of machinery – Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Manipulating industrial robots - Safety.
etc.
Caution
1. The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in
manufacturing industries.
If considering using the product in other industries, consult SMC
beforehand and exchange specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.
Limited warranty and Disclaimer/
Compliance Requirements
The product used is subject to the following “Limited warranty and
Disclaimer” and “Compliance Requirements”.
Read and accept them before using the product.
Limited warranty and Disclaimer
1. The warranty period of the product is 1 year in service or 1.5
years after the product is delivered.∗2)
Also, the product may have specified durability, running distance or
replacement parts. Please consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is
clearly our responsibility, a replacement product or necessary parts will
be provided.
This limited warranty applies only to our product independently, and not
to any other damage incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty
terms and disclaimers noted in the specified catalog for the particular
products.
∗2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is
delivered.
Also, even within the warranty period, the wear of a product due to the use of
the vacuum pad or failure due to the deterioration of rubber material are not
covered by the limited warranty.
Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass destruction (WMD) or any other weapon is
strictly prohibited.
2. The exports of SMC products or technology from one country to
another are governed by the relevant security laws and regulations of
the countries involved in the transaction. Prior to the shipment of a
SMC product to another country, assure that all local rules governing
that export are known and followed.
Safety Instructions Be sure to read “Handling Precautions for SMC Products” (M-E03-3) before using.