Errata Sheet This Errata Sheet contains corrections or changes

Errata Sheet This Errata Sheet contains corrections or changes
Errata Sheet
This Errata Sheet contains corrections or changes
made after the publication of this manual.
Date:
Product Family:
DL405
Revision and Date
4th Edition, Rev. A, March 2013
Manual Number
D4-USER-M
Changes to Chapter 2. Installation, Wiring, and Specifications
Page 2-4. Safety Guidelines; Class 1, Division 2 Approval
Delete this section. The DL405 system is NOT Class 1, Division 2 approved.
Changes to Chapter 4. System Design and Configuration
Page 4-8. Calculating the Power Budget; Module Power Requirementsl
Change the “5V Current Required (mA)” values in the table for these analog modules:
F4-04AD: Change from 85 mA to 150 mA
F4-04ADS: Change from 270 mA to 370 mA
Page 1 of 1