Liebert DataMate 1.5 to 3 Tons (5 to 10.5kW) Precision Cooling Technical Data Manual
The Liebert DataMate 1.5 to 3 Tons (5 to 10.5kW) Precision Cooling systems are split-system evaporators combined with remote air, water- or glycol-cooled condensing units, or close-coupled water/glycol-cooled condensing units, or self-contained chilled water units. The DataMate provides complete control on an around-the-clock basis and the high sensible heat ratio required by sensitive electronic equipment.
Advertisement
Advertisement
Precision Cooling
For Business-Critical Continuity™
Liebert
®
DataMate
™
–1.5 to 3 Tons (5 to 10.5kW) Capacity
Technical Data Manual– Air, Water/Glycol and Chilled Water Units, 50 & 60Hz
TABLE OF CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.0
C ONDENSING U NITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Optional Configurations—Indoor Remote Water/Glycol Condensing Units. . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Remote Monitoring, Autochangeover and Leak Detection Equipment. . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
1.0
G
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2.0
P
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.0
E
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
i
FIGURES
Figure 1
ii
TABLES
Table 17
60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with
common power feed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
iii
iv
Introduction
1.0
I
NTRODUCTION
1.1
Designed to Match Computer and Electronic Equipment Needs—From Installation to Operation
Installed on the floor or on the wall, Liebert DataMate Precision Cooling systems control the cooling, humidity and air distribution required by sensitive electronic equipment. A range of sizes and configurations is available to meet varying sites’ needs.
The Liebert DataMate is also easy to use. Advanced microprocessor technology allows easy, precise control and menu-driven monitoring keeps you informed of system operation through the LCD readout.
These features, combined with Emerson quality construction and reliable components, guarantee satisfaction from installation through operation.
Liebert Precision Cooling
Liebert Precision Cooling systems are designed to control the environment required for computers and other sensitive electronic equipment. The Liebert DataMate provides complete control on an around-the-clock basis and the high sensible heat ratio required by sensitive electronic equipment.
Easy Installation
The Liebert DataMate is a split-system evaporator combined with a remote air-, water- or glycolcooled condensing unit or a close-coupled water/glycol-cooled condensing unit or is a self-contained, chilled water unit.
Each split system has thermostat-type wiring to controls and condensing unit. System components are pre-charged with refrigerant using quick-connect fittings and can be easily connected together.
Optional pre-charged line sets or sweat adapters for field refrigerant piping are available for remote condensing units.
Easy to Service
The Liebert DataMate is designed for front service access. Routine maintenance and service can be performed quickly and easily. Spare parts are always in Emerson inventory and available on short notice.
Advanced Control Technology
A menu-driven microprocessor control system provides precise temperature and humidity control and accurate alarm setpoints. Using touch-sensitive buttons, the wall-mounted monitor/control panel allows you to select and display temperature and other monitored parameters.
High Efficiency
High sensible heat ratio, scroll compressor and precise microprocessor control allow the system to operate efficiently.
Space Saving Design
Models available to fit any room without disrupting workstation layout. Requires 5 ft 2 of floor space or can be mounted on a wall.
(0.5m
2 ) or less
Reliable
The Liebert DataMate installed base is a testimony to the system reliability.
Agency Listed
Standard 60Hz units are CSA certified to the harmonized U.S. and Canadian product safety standard, CSA C22.2 No 236/UL 1995 for “Heating and Cooling
Equipment” and are marked with the CSA c-us logo. The units are also MEA listed for New York City applications.
C US
1
2.0
S
TANDARD
F
EATURES
—1.5-
TO
3-T
ON
S
YSTEMS
Standard Features—1.5- to 3-Ton Systems
2.1
Evaporator Section—Split-Systems
The Liebert DataMate is available as a split system air, water/glycol-cooled unit or self-contained chilled water unit.
Split-System Evaporator Section includes the evaporator coil, 2-speed centrifugal blower assembly, filter-drier, galvanized steel drain pan, R-407C refrigerant charge, cleanable filters and microprocessor control with wall-mounted display panel. The unit construction is galvanized steel with powder-coated, removable exterior panels. A reversible discharge grille provides the ability to redirect airflow. The evaporator can be floor- or wall-mounted.
2.2
Condensing Unit Section—Remote Split-Systems
2.2.1 Indoor Centrifugal Fan Condensing Units
Indoor Air-Cooled Centrifugal Fan Condensing Units include scroll compressor, factory-mounted disconnect switch, condenser coil, R-407C unit charge, belt-driven centrifugal blower assembly, highpressure switch, Liebert Lee-Temp head pressure control system, hot gas bypass and liquid-line solenoid valve. Unit must be mounted indoors. Condensing unit is designed to use outdoor air with temperatures ranging from -30°F to 95°F (-34°C to 35°C). Available in 2- & 3-Ton models.
2.2.2 Outdoor Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units include scroll compressor, condenser coil, R-407C unit charge, prop fan, liquid-line solenoid valve, high pressure switch, Liebert Lee-Temp head pressure control and hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients ranging from -30°F to 95°F (-34°C to 35°C).
2.2.3 Indoor Remote Water/Glycol Condensing Units
Indoor Remote Water/Glycol Condensing Units include scroll compressor, R-407C unit charge, factory-mounted disconnect, coaxial condenser, hot gas bypass, high head pressure switch and two-way water regulating valve designed for 150psi (1034.3kPa). Condensing units can be used on either a water or glycol cooling loop. Available in 2- and 3-ton models.
2.3
Condensing Unit Section—Close-Coupled
The Close-Coupled Water/Glycol Condensing Unit is designed to attach to the split-system evaporator to become a single wall- or floor-mounted unit.
Indoor close-coupled water/glycol condensing units include reciprocating compressor, brazed plate condenser, R-407C refrigerant charge and 2-way water regulating valve. Unit is available in 60Hz models only. Design pressure is 150psi (1034kPa).
2.4
Chilled Water Units
Self-Contained Chilled Water Models include a chilled water coil, a two-way, solenoid open, slowclose (On/Off) spring-return valve, two-speed centrifugal blower assembly, cleanable filters and microprocessor control with wall-mounted display panel. Design pressure is 125psi (862kPa).
2
Standard Features—1.5- to 3-Ton Systems
2.5
System Controls
System controls include a microprocessor control board mounted in the evaporator/chilled water unit and a wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key, membrane keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the LCD screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities, fan speed and alarm conditions.
The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also includes common alarm terminals and shutdown terminals. The unit automatically restarts after a power outage.
Figure 1 Wall-box
2.5.1 Other Standard Control Features
• Adjustable auto restart
• 5 day/2 day setback
• Password protection
• Alarm enable/disable
• Self-diagnostics
• Calibrate sensors
• Predictive humidity control
• Common alarm output
• Remote shutdown terminals
3
Optional Factory-Installed Features—Evaporator/Chilled Water & Condensing Units
3.0
O
PTIONAL
F
ACTORY
-I
NSTALLED
F
EATURES
—E
VAPORATOR
/C
HILLED
W
ATER
&
C
ONDENSING
U
NITS
3.1
Electric Reheat
Electric low watt tubular reheat element with non-corrosive metal sheath provides one stage of nonionizing reheat to maintain room dry bulb temperature.
3.2
Humidifier/Electric Reheat Package
The humidifier and electric reheat are available as a package for complete humidity control. The canister humidifier includes a steam-generating type humidifier with automatic flushing circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem alarm annunciates at the wall-mounted display panel. Maximum humidifier water supply pressure is 150psi
(1034kPa).
3.3
Optional Configurations—Prop Fan Condensing Units
Outdoor Prop Fan Condensing Units are also available in the following optional configurations:
• High ambient models for providing catalog capacities at ambient temperatures up to 105°F (40°C)
- 2- and 3-ton models only.
• Quiet-Line models for low noise level conditions (below 56 dBA) and for providing catalog capacities at ambient temperatures up to 95°F (35°C) - 2- and 3-ton models only.
• Condenser coils can be phenolic-coated for extended coil life in coastal areas.
3.4
Optional Configurations—Indoor Remote Water/Glycol Condensing Units
Indoor Remote Water/Glycol Condensing Units are also available with the following piping options:
• Two-way water regulating valve with 350psi (2413kPa) design pressure.
• Three-way water regulating valve with 150psi (1034kPa) design pressure.
• Three-way water regulating valve with 350psi (2413kPa) design pressure.
4
Ship-Loose Accessories—Field-Installed
4.0
S
HIP
-L
OOSE
A
CCESSORIES
—F
IELD
-I
NSTALLED
The Condensate Pump is field-mounted internal to the unit and wired to the unit power block or is field-mounted external to the unit with power from unit or external power supply. Pump is complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float can be field-wired to shut down the unit upon high condensate level.
The Canister Humidifier Kit can be field-installed to customize cooling only or reheat only units.
The kit includes full installation instructions and are designed to be added to the evaporator unit before it is mounted on its wall or floor location.
The 277V Step-Down Transformer is available for units needing 277-1-60 input power; one each for evaporator section and remote condensing section (37.5A max. each). Use one 37.5A transformer for 1-1/2 or 2-ton self-contained water/glycol systems; use 50A transformer for 3-ton self-contained water/glycol systems. Epoxy-encapsulated, transformer is suitable for either indoor or outdoor service.
Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m) and
30-foot (9m) sections for interconnection of evaporator to remote condensing unit without brazing.
Maximum recommended combined line set length is 45 ft.(13.7m).
The Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that allow field-supplied refrigerant piping between the evaporator and condensing unit.
A Remote Temperature and Humidity Sensor package includes sensors in an attractive case with 30 ft. (9 m) of cable. Can be wall or duct mounted. Remote sensors should be used when the wall box is not located in the space to be conditioned.
NOTE
Installing the remote sensors disables the sensors included in the wall box.
5
Ship-Loose Accessories—Field-Installed
4.1
Remote Monitoring, Autochangeover and Leak Detection Equipment
The Liebert RCM4
™
is a four-point, normally open, dry contact monitoring panel. One Form-C, dry contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires a 24VAC or 24VDC power source. Power supply is not included.
The Liebert AC4
™
Autochangeover Controller provides autochangeover and autosequence control for up to four Liebert DataMate units within a room. The Liebert AC4 will enable redundant units in an alarm condition, balance usage and test standby units at programmed intervals. Two common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product. The Liebert AC4 requires
24VAC input power.
The Liebert AC8 ™ is ideal for coordinated control of systems with redundant units. The Liebert AC8 enables redundant devices during an alarm condition, balances usage of devices and tests standby devices at programmable intervals. Supports four zones and can use the 4-20mA temperature sensor
(TW420) for temperature staging in each zone. Two programmable output control relays are available for auxiliary control such as humidity lockout. Emergency power operation input provided for device control during an emergency. Two common alarm relay outputs are available. A built-in LCD and
RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product.
The Liebert ENV-DO ™ interface card provides 16 discrete outputs, corresponding to status and major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two Environmental DO interface cards in one enclosure for installation external to the Liebert DataMate. The self-contained kit includes an external 120VAC-to-24VAC power transformer. Wiring harnesses are not provided. Power and communication wiring is field-provided.
The Liebert Liqui-tect
®
410 Point Leak Detection Sensor detects the presence of conductive liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external
24VAC or 24VDC power source.
Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of LT500xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips. The
Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.
Liebert SiteScan ® is a monitoring solution that gives you decision-making power to effectively manage the equipment critical to your business.
Liebert SiteScan enables communication from Liebert environmental and power units, as well as many other pieces of analog or digital equipment, to a front-end software package that provides real-time status and alarms so you can react quickly to changing situations.
Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such as those in computer rooms, telecommunications facilities or industrial process control rooms. Contact your local Emerson representative for assistance with a Liebert SiteScan system.
6
5.0
F
LEXIBLE
C
ONFIGURATIONS
Figure 2 Flexible configurations—All systems
Air-Cooled Systems
L ie be rt
Lieber t
Flexible Configurations
OUTDOOR, AIR-COOLED CONDENSING UNIT
Suitable for installation on a roof or at ground level.
INDOOR AIR-COOLED CONDENSING UNIT
For applications where roof or ground level locations are impractical.
Water/Glycol-Cooled Systems
L ie be rt
Liebe rt
WATER/GLYCOL-COOLED CLOSE-COUPLED
A single power and water supply connection puts the unit in operation.
WATER/GLYCOL-COOLED REMOTE
Condensing unit is installed under raised floor or above dropped ceiling.
Chilled Water Systems
Liebe rt
CHILLED WATER
Connects to a chilled water loop for quick and easy installation.
7
Air-Cooled Systems—Capacities and Dimensions
6.0
A
IR
-C
OOLED
S
YSTEMS
—C
APACITIES AND
D
IMENSIONS
Table 1 60Hz capacities & typical specifications, air-cooled applications
Evaporator Model DME020E DME027E DME037E
Condensing Unit Type PFH - Outdoor PFH - Outdoor MCD - Indoor PFH - Outdoor MCD - Indoor
DX EvaporatorNet Capacity Data - kW (Btuh) @ High Speed CFM
Total 5.40 (18,500) 7.10 (24,200) 6.85 (23,300) 10.1 (34,600) 9.60 (32,700) 80°F DB, 62.8°F WB
(26.7°C DB, 17.1°C
WB) 38 %RH
75°F DB, 61°F WB
(23.9°C DB, 16.1°C
WB) 45 %RH
Sensible 5.40 (18,500)
Total 5.05 (17,200)
Sensible 4.90 (16,700)
7.10 (24,200)
6.60 (22,500)
6.50 (22,200)
6.85 (23,300)
6.35 (21,700)
6.35 (21,600)
9.70 (33,100)
9.75 (33,200)
8.60 (29,400)
9.40 (32,000)
9.15 (31,300)
8.35 (28,500)
6.35 (21,700) 6.10 (20,800) 9.50 (32,400) 8.95 (30,600) 72°F DB, 60°F WB
(22.2°C DB, 15.5°C
WB) 50 %RH
Total
Sensible
Fan Data - Evaporator
CFM (CMH) - High Speed
4.85 (16,500)
4.50 (15,400)
870 (1478)
6.05 (20,600) 5.90 (20,100)
1230 (2090)
7.95 (27,100) 7.70 (26,200)
CFM (CMH) - Low Speed 750 (1274) 1050 (1784)
0.20 (150)*
1320 (2243)
1175(1996 )
0.27 (200)** Fan Motor hp (W) 0.16 (120)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
) 2.44 (0.23)
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
4
356 (1.8)
4 (0.11)
Unit Operating Weight, lb. (kg) 230 (104)
Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)
Input Voltage 230-1-60 2.7 (9215)
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr) 3 (1.4)
Electrical Input Power - kW 1
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip
Coupling Size, - #6 Female
Suction Line Diameter - Aeroquip
Coupling Size, #11 Female
Humidfier Supply,
OD Cu Compression Fitting
Humidifier Drain, Barb Fitting
Evaporator Drain
3/8"
1/2"
1/4"
1/2"
3/4" OD
3.92 (0.36)
3
313 (1.6)
5 (0.14)
330 (150)
5.3 (18080)
3 (1.4)
1
3/8"
7/8"
1/4"
1/2"
3/4" OD
3.92 (0.36)
4
336 (1.7)
6.5 (0.18)
365 (165)
5.5 (18765)
3 (1.4)
1
3/8"
7/8"
1/4"
1/2"
3/4" OD
Filter Washable Polypropylene/Aluminum
Condensing Unit Model Number PFH020A-_L7 PFH027A-_L7 MCD24AL_H7 PFH037A-_L7 MCD36AL_H7
Condensing Unit Rating Conditions
Coil Face Area ft
2
(m
2
) 4.1 (0.38) 4.1 (0.38)
95°F (35°C) Ambient
4.6 (0.43) 7.7 (0.72) 4.6 (0.43)
Rows of Coil 2 2 4 2 4
CFM (CMH) 2200 (3738) 2200 (3738) 1000 (1699) 3000 (5097) 1430 (2490)
Motor, hp (W)
External Static Pressure, in wg.
(mm)
0.20 (149)
N/A
0.20 (149)
N/A
0.33 (246)
0.50 (13)
0.20 (149)
N/A
0.5 (373)
0.50 (13)
Condensing Unit Refrigerant
Charge, oz. (kg)
134 (3.8) 134 (3.8) 134 (3.8) 213 (6.0) 213 (6.0)
Unit Operating Weight, lb. (kg) 200 (91) 351 (159) 449 (204) 351 (159) 449 (204)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* DME027 has two motors - 0.08 & 0.12 HP
** DME037 has two motors - 0.11 & 0.16 HP
8
Air-Cooled Systems—Capacities and Dimensions
Table 2 50Hz capacities & typical specifications, air-cooled applications
Evaporator Model DME020E DME027E DME037E
Condensing Unit Type PFH - Outdoor PFH - Outdoor MCD - Indoor PFH - Outdoor MCD - Indoor
DX EvaporatorNet Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C
DB, 17.1°C WB) 38 %RH
75°F DB, 61°F WB (23.9°C
DB, 16.1°C WB) 45 %RH
72°F DB, 60°F WB (22.2°C
DB, 15.5°C WB) 50 %RH
Total 5.15 (17,500) 6.50 (22,200) 6.40 (21,800) 9.90 (33,800) 9.45 (32,300)
Sensible 5.05 (17,200) 6.50 (22,200) 6.40 (21,800) 8.85 (30,200) 8.65 (29,500)
Total 4.80 (16,400) 6.15 (20,900) 6.00 (20,500) 9.55 (32,500) 9.10 (31,100)
Sensible 4.50 (15,300) 5.90 (20,100) 5.80 (19,800) 7.90 (26,900) 7.70 (26,300)
Total 4.65 (15,900) 5.95 (20,300) 5.80 (19,800) 9.30 (31,800) 8.90 (30,400)
Sensible 4.10 (14,000) 5.40 (18,500) 5.35 (18,300) 7.30 (24,900) 7.10 (24,300)
Fan Data - Evaporator
CFM (CMH) - High Speed 725 (1232)
CFM (CMH) - Low Speed 625 (1062)
Fan Motor HP (W) 0.16 (120)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
) 2.44 (0.23)
1025 (1741)
875 (1487)
0.20 (150)*
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb. (kg)
4
356 (1.8)
4 (0.11)
230 (104)
Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)
Input Voltage 230-1-50 2.7 (9215)
Humidifier Data - Steam Generator Type
Steam capacity - lb/hr (kg/hr)
Electrical Input Power - kW
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip
Coupling Size, #6 Female
Suction Line Diameter - Aeroquip
Coupling Size, - #11 Female
3 (1.4)
1
3/8"
1/2"
3.92 (0.36)
3
313 (1.6)
5 (0.14)
330 (150)
5.3 (18080)
3 (1.4)
1
3/8"
7/8"
1100 (1869)
980 (1665 )
0.27 (200)**
3.92 (0.36)
4
336 (1.7)
6.5 (0.18)
365 (165)
5.5 (18765)
3 (1.4)
1
3/8"
7/8"
Humidfier Supply,
OD Cu Compression Fitting
Humidifier Drain, Barb Fitting
Evaporator Drain, OD
Filter
Condensing Unit Model Number
1/4"
1/2"
3/4"
PFH019A-_L7
1/4"
1/2"
3/4"
Washable Polypropylene/Aluminum
PFH026A-_L7 MCD23AL_H7
1/4"
1/2"
3/4"
PFH036A-_L7
Condensing Unit Rating Conditions
Coil Face Area ft
2
(m
2
)
Rows of Coil
4.1 (0.38)
2
4.1 (0.38)
2
95°F (35°C) Ambient
4.6 (0.43)
4
7.7 (0.72)
2
CFM (CMH) 1800 (3058) 1800 (3058) 1000 (1699) 2500 (4248)
Motor Hp (W) 0.20 (149) 0.20 (149) 0.33 (246) 0.20 (149)
External Static Pressure, in wg. (mm) N/A N/A 0.50 (13) N/A
Condensing Unit Refrigerant Charge, oz. (kg)
134 (3.8) 134 (3.8) 134 (3.8) 213 (6.0)
MCD35AL_H7
4.6 (0.43)
4
1430 (2430)
0.5 (373)
0.50 (13)
213 (6.0)
Unit Operating Weight, lb. (kg) 200 (91) 351 (159) 449 (204) 351 (159) 449 (204)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* DME027 has two motors - 0.08 & 0.12 HP
** DME037 has two motors - 0.11 & 0.16 HP
9
Figure 3 General arrangement, air-cooled split systems
Air-Cooled Systems—Capacities and Dimensions
10
Figure 4 Dimensions, evaporator unit
Air-Cooled Systems—Capacities and Dimensions
Table 3 Evaporator section dimensions—air-cooled applications
Model
Weight lb (kg)
Width - A in. (mm)
Depth in. (mm)
Height in. (mm)
DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813)
DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813)
DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813)
Table 4 Evaporator unit refrigerant connections—pipe size/coupling number
Model
DME020E
DME027E
DME037E
Liquid Line A
3/8" / #6
3/8" / #6
3/8" / #6
Suction Line B
1/2" / #11
7/8" / #11
7/8" / #11
11
Air-Cooled Systems—Capacities and Dimensions
Figure 5 Cabinet and floor planning dimensions—Outdoor air-cooled condensing units
Fan Rotation
CCW (left side)
A
Removable (right) panel for access to refrigeration component
Right Air
Discharge
Left Air
Intake
B
Shaded area indicates a minimum clearance of
18" (457mm) for proper airflow
Shaded area indicates a minimum clearance of
18" (457mm) for proper airflow
Removable panel for access to high voltage & low voltage connections, and refrigeration components
Shaded area indicates a recommended clearance of 24" (610mm) for component access and removal
DPN000130_Rev0
Table 5
Model Numbers
60Hz
Propeller fan, air-cooled condensing unit dimensions, inches (mm)
50Hz
Dimensional Data, inches (mm)
A B C
Module Net
Weight lb (kg)
PFH020A-L PFH019A-L
PFH027A-L PFH026A-L
PFH027A-H PFH026A-H
PFHZ27A-L PFHZ26A-L
PFH037A-L PFH036A-L
PFH037A-H PFH036A-H
PFHZ37A-L PFHZ36A-L
40 (1016) 23 1/2 (597) 18 (457)
48 (1219) 31 (787) 18 (457)
53 (1343) 36 1/4 (918) 18 (457)
200 (91)
241 (109)
351 (159)
12
Figure 6 Dimensions, indoor air-cooled condensing units
Air-Cooled Systems—Capacities and Dimensions
Table 6
Model
MC*23A
MC*24A
MC*35A
MC*36A
Remote centrifugal fan, air-cooled condensing, weight and dimensions
Weight lb (kg) A
Dimensions, in (mm)
B C
230 (104)
240 (109)
1-7/16 (37) 11-7/16 (290) 1/2 (13)
D
20-7/16 (519)
13
Water/GlycolSystems—Capacities and Dimensions
7.0
W
ATER
/G
LYCOL
S
YSTEMS
—C
APACITIES AND
D
IMENSIONS
Table 7 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications
Evaporator Model
Condensing Unit Type
Water-
Cooled
Glycol-
Cooled
DX EvaporatorNet Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38 %RH
DME020E DME027E
Water-
Cooled
Glycol-
Cooled
DME037E
Water-
Cooled
Glycol-
Cooled
Total 5.90 (20,100) 5.15 (17,600) 7.95 (27,200) 6.75 (23,000) 11.4 (38,900) 9.65 (32,900)
Sensible 5.80 (19,800) 5.15 (17,600) 7.90 (27,000) 6.75 (23,000) 10.3 (35,300) 9.40 (32,100)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45 %RH
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50 %RH
Total 5.50 (18,800) 4.80 (16,300) 7.55 (25,800) 6.25 (21,300) 11.0 (37,400) 9.20 (31,400)
Sensible 5.15 (17,600) 4.75 (16,200) 7.10 (24,200) 6.25 (21,300) 9.20 (31,400) 8.35 (28,500)
Total 5.35 (18,100) 4.60 (15,700) 7.35 (25,000) 6.00 (20,500) 10.7 (36,600) 8.95 (30,600)
Sensible 4.75 (16,200) 4.35 (14,900) 6.55 (22,300) 5.85 (19,900) 8.55 (29,100) 7.70 (26,300)
Fan Data - Evaporator
CFM (CMH) - High Speed 870 (1478) 1230 (2090)
CFM (CMH) - Low Speed
Fan Motor hp (W)
750 (1274)
0.16 (120)
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
) 2.44 (0.23) 2.44 (0.23)
1050 (1784)
0.20 (150)*
1320 (2243)
1175(1996 )
0.27 (200)**
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb. (kg)
4
356 (1.8)
4 (0.11)
230 (104)
3.92 (0.36)
3
313 (1.6)
5 (0.14)
330 (150)
3.92 (0.36)
4
336 (1.7)
6.5 (0.18)
365 (165)
Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)
Input Voltage 230-1-60 2.7 (9215)
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power - kW
Evaporator Connection Sizes
3 (1.4)
1
Liquid line Diameter - Aeroquip Coupling Size, #6
Female
3/8"
Suction Line Diameter - Aeroquip Coupling Size,
#11 Female
1/2"
5.3 (18080)
3 (1.4)
1
3/8"
7/8"
5.5 (18765)
3 (1.4)
1
3/8"
7/8"
Humidfier Supply
Humidifier Drain, Barb Fitting
Evaporator Drain, OD
Filter
Close-Coupled DMC Condensing Unit Model
1/2"
3/4"
DMC022WG
1/4" OD Copper Compression Fitting
1/2"
3/4"
Washable Polypropylene/Aluminum
DMC029WG
10.4 (31.1)
N/A
8.4 (25.1)
105 (40.6 )
7/8 (22.2)
1/2"
3/4"
DMC040WG
Condenser Fluid Requirements, °F (°C)
85 (29.4)
EWT
110 (43.3)
EGT - 40%
PG
85 (29.4)
EWT
110 (43.3)
EGT - 40%
PG
85 (29.4)
EWT
110 (43.3)
EGT - 40%
PG
THR - kW (Btuh) @ 75F/45%RH 7.30 (24,900) 7.10 (24,200) 9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100)
Flow Rate - GPM (l/m) 4.0 (15.2) 5.9 (22.4) 4.6 (17.4) 6.9 (26.2) 7.8 (29.6) 9.1 (34.5)
Pressure Drop - ft. of H
2
0 (kPa) 7.0 (20.9)
Water-Cooled Condensing Temperature, °F (°C) 105 (40.6 )
Connection Sizes, in. (mm) OD
17.0 (50.8)
5/8 (15.9)
N/A
4.4 (13.2)
105 (40.6 )
13.6 (40.7)
N/A
Unit Volume - Gal (l)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb. (kg)
Remote MCD Condensing Unit Model # —
0.25 (0.95)
47 (1.33)
169 (77)
—
0.40 (1.5)
59 (1.67)
169 (77)
MCD26W
0.50 (1.9)
61 (1.72)
172 (78)
MCD38W
Condenser Fluid Requirements, °F (°C)
THR - kW (Btuh) @ 75F/45%RH
Flow Rate - GPM (l/m)
Pressure Drop - ft. of H
2
0 (kPa)
Water-Cooled Condensing Temperature
Connection Sizes, in. (mm) OD
Unit Volume - Gal (l)
Unit Refrigerant Charge, oz. (kg)
—
—
—
—
—
—
—
N/A
—
—
—
—
—
—
—
85 (29.4)
EWT
110 (43.3)
EGT - 40 %
PG
9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100)
7.7 (24.2) 8.9 (33.7) 6.5 (24.6) 12.1 (45.9)
16.6 (49.6)
105°F
(40.6°C)
110 (43.3)
EGT - 40 %
PG
26.0 (77.7)
N/A
85 (29.4)
EWT
11.6 (34.7)
105°F
(40.6°C)
44.7 (133.7)
N/A
7/8 (22.2)
1.2 (4.5)
41 (1.16)
7/8 (22.2)
1.2 (4.5)
54 (1.54)
Unit Operating Weight, lb. (kg) — — 175 (79) 220 (100)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* DME027 has two motors - 0.08 & 0.12 HP; ** DME037 has two motors - 0.11 & 0.16 HP
14
Water/GlycolSystems—Capacities and Dimensions
Table 8 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications
Evaporator Model
Condensing Unit Type
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor HP (W)
DME027E
Water-Cooled Glycol-Cooled
DX EvaporatorNet Capacity Data - kW (Btuh) @ High Speed CFM
80°F DB, 62.8°F WB (26.7°C DB,
17.1°C WB) 38 %RH
Total
Sensible
7.55 (25,700)
7.20 (24,600)
6.15 (21,000)
6.15 (21,000)
75°F DB, 61°F WB (23.9°C DB,
16.1°C WB) 45 %RH
72°F DB, 60°F WB (22.2°C DB,
15.5°C WB) 50 %RH
Total
Sensible
Total
Sensible
7.20 (24,500)
6.45 (22,000)
7.00 (23,900)
5.95 (20,300)
5.75 (19,600)
5.65 (19,300)
5.55 (19,000)
5.20 (17,800)
1025 (1741)
875 (1487)
0.20 (150)*
DME037E
Water-Cooled Glycol-Cooled
11.3 (38,700)
9.55 (32,600)
11.0 (37,400)
8.55 (29,200)
10.7 (36,600)
7.95 (27,200)
9.30 (31,800)
8.60 (29,300)
8.95 (30,500)
7.60 (26,000)
8.75 (29,900)
7.05 (24,000)
1100 (1869)
980 (1665 )
0.27 (200)**
Evaporator Coil - Copper Tube/Aluminum Fin
Face Area ft
2
(m
2
)
Coil Rows
Max Face Velocity-fpm (m/s)
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb. (kg)
3.92 (0.36)
3
313 (1.6)
5 (0.14)
330 (150)
Electric Reheat Capacities (Includes Fan Motor)-kW (Btu/H)
Input Voltage 230-1-50 5.3 (18080)
3.92 (0.36)
4
336 (1.7)
6.5 (0.18)
365 (165)
5.5 (18765)
Humidifier Data - Steam Generator Type
Steam capacity - lbs/hr (kg/hr)
Electrical Input Power - kW
3 (1.4)
1
3 (1.4)
1
Evaporator Connection Sizes
Liquid line Diameter - Aeroquip Coupling Size
Suction Line Diameter - Aeroquip Coupling
Size
Humidfier Supply
Humidifier Drain Barb Fitting
Evaporator Drain
Filter
3/8" - #6 Female
7/8" - #11 Female
3/8" - #6 Female
7/8" - #11 Female
1/4" OD Cu Compression Fitting
1/2"
1/4" OD Cu Compression Fitting
1/2"
3/4" OD 3/4" OD
Washable Polypropylene/Aluminum
MCD25W MCD37W Remote MCD Condensing Unit Model #
Condenser Fluid Requirements
85°F (29.4°C)
EWT
THR - kW (Btuh) @ 75F/45%RH
Flow Rate - GPM (l/m)
9.10 (31,000)
7.9 (29.9)
Pressure Drop - ft. of H
2
0 (kPa) 17.3 (51.7)
Water-Cooled Condensing Temperature 105 °F (40.6 °C)
Connection Sizes, in. (mm) OD
Unit Volume - Gal (l)
110°F (43.3°C)
EGT - 40% PG
8.45 (28,900)
9.0 (34.1)
7/8 (22.2)
1.2 (4.5)
26.5 (79.2)
N/A
85°F (29.4°C)
EWT
13.7 (46,700)
6.4 (24.3)
11.7 (35.0)
105 °F (40.6 °C)
110°F (43.3°C)
EGT - 40% PG
12.9 (44,000)
13.5 (51.2)
55.8 (166.8)
7/8 (22.2)
1.2 (4.5)
N/A
Unit Refrigerant Charge, oz. (kg)
Unit Operating Weight, lb. (kg)
41 (1.16)
175 (79)
54 (1.54)
220 (100)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
* DME027 has two motors - 0.08 & 0.12 hp
** DME037 has two motors - 0.11 & 0.16 hp
15
Figure 7 General arrangement, water/glycol, split systems
Water/GlycolSystems—Capacities and Dimensions
Figure 8 General arrangement, water/glycol systems, close-coupled condensing unit
16
Figure 9 Dimensions, evaporator unit
Water/GlycolSystems—Capacities and Dimensions
Table 9 Evaporator section dimensions—water/ glycol-cooled applications
Model
Weight lb (kg)
Width - A in. (mm)
Depth in. (mm)
Height in. (mm)
DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813)
DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813)
DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813)
Table 10 Evaporator unit refrigerant connections—pipe size/coupling number
Model
DME020E
DME027E
DME037E
Liquid Line A
3/8" / #6
3/8" / #6
3/8" / #6
Suction Line B
1/2" / #11
7/8" / #11
7/8" / #11
17
Water/GlycolSystems—Capacities and Dimensions
Figure 10 Dimensions, close-coupled water/glycol condensing unit
Table 11 Net weight, water/glycol condensing units
Model Tons Weight
DMC022WG
DMC029WG
DMC040WG 3 170lb (77kg)
For refrigerant and water/glycol piping connection sizes,
18
Water/GlycolSystems—Capacities and Dimensions
Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules
Table 12 Net weight, indoor water/glycol-cooled condensing unit
60Hz
Model #
50Hz
Weight lb (kg)
19
Chilled Water Systems
8.0
C
HILLED
W
ATER
S
YSTEMS
Table 13 Chilled water data, 50/60Hz
DME044C
CW Model, 60 Hz 208/230-1-60 200/220-1-50
Net Capacity Data - kW (Btuh) based on 45°F (7.2°C) EWT & 10°F (5.6°C) temperature rise
Total
80°F DB, 62.8°F WB (26.7°C DB, 17.1°C WB) 38 %RH
10.5 (36,000) 9.1 (31,100)
Sensible 9.65 (32,900) 8.3 (28,200)
Flow Rate, GPM (l/m) 7.3 (27.7) 6.3 (23.9)
Pressure Drop, ft. water (kPa)
Total
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45 %RH
Sensible
Flow Rate, GPM (l/m)
Pressure Drop, ft. water (kPa)
Total
72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50 %RH
Sensible
Flow Rate, GPM (l/m)
Pressure Drop, ft. water (kPa)
Fan Data - Evaporator
CFM (CMH) - High Speed
CFM (CMH) - Low Speed
Fan Motor, hp (W)
CW Coil - Copper Tube/Aluminum Fin
Face Area, ft
2
(m
2
)
Coil Rows
Max Face Velocity-fpm (m/s)
12.0 (35.9)
8.45 (28,900)
7.95 (27,100)
6.1 (23.1)
8.7 (26.0)
7.65 (26,100)
6.90 (23,500)
5.3 (20.1)
6.9 (20.6)
1320 (2243)
1175 (1996 ) 980
0.27 (200)**
9.3 (27.8)
7.6 (25,900)
6.8 (23,200)
5.3 (20.1)
6.7 (20.0)
6.6 (22,600)
5.9 (20,200)
4.6 (17.4)
5.3 (15.8)
1100 (1869)
0.27 (200)
3.92 (0.36)
4
336 (1.7) 281 (1.4)
Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)
Input Voltage 230-1-60/50
Humidifier Data - Steam Generator Type
5.5 (18,765)
Steam capacity, lb/hr (kg/hr)
Electrical Input Powe, kW
Unit Connection Sizes
CW supply and return connections, in (mm) OD
3 (1.4)
1
7/8 (22.2)
Humidfier Supply 1/4" OD Copper Compression Fitting
Evaporator/Condensate Drain 3/4" NPT-Female
Unit Valve Types
Unit Internal Fluid Volume, gal (l) 1.0 (3.8)
Filter Washable Polypropylene/Aluminum
Unit Operating Weight, lb. (kg.) 365 (165)
On/Off Slow Close, 2-Way
Valve Size
Valve Cv
Max. Water Static Operating Pressure, psi (kPa)
Close-Off Pressure, psi (kPa)
3/4"
8
125 (862)
8 (55)
The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75°F (23.9 °C),
45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be ± 5%.
** DME044C has two motors - 0.11 & 0.16 HP
20
Chilled Water Systems
Table 14 Chilled water capacity correction factors based on 10°F (5.6°C) water rise
EWT
42°F (5.6°C)
43°F (6.1°C)
44°F (6.7°C)
45°F (7.2°C)
46°F (7.8°C)
47°F (8.3°C)
48°F (8.9°C)
49°F (9.4°C)
72°F (22.2°C) 50% 75°F (23.9°C) 45%RH
TCC SCC TCC SCC
1.27
1.17
1.08
1.00
0.93
0.86
0.79
0.74
1.14
1.09
1.04
1.00
0.96
0.92
0.88
0.83
1.23
1.15
1.07
1.00
0.94
0.88
0.82
0.77
1.11
1.07
1.04
1.00
0.96
0.93
0.89
0.85
Figure 12 General arrangement—Chilled water systems
21
Figure 13 Dimensions—Chilled water unit
Chilled Water Systems
Table 15 Net weights and dimensions, chilled water units
Model
DME044C
Dimensions
W x D x H, in (mm)
64-1/8 x 11-7/8 x 32
(1628 x 302 x 813)
Weight lb (kg)
364 (165)
Water Connection Sizes
7/8" (22.2mm) OD Cu
22
Electrical Data—All Units
9.0
E
LECTRICAL
D
ATA
—A
LL
U
NITS
Table 16 Electrical data, split system evaporator or chilled water unit, 60/50Hz
Base Evaporator/
Chilled Water
Cooling Only
FLA
WSA
OPD
DME020E
1.4
1.8
15
With Reheat
FLA
WSA
OPD
11.8
14.8
15
With Reheat & Humidifier
FLA 18.8
WSA
OPD
23.5
25
208/230V-1ph-60Hz
DME027E
DME037E
DME044C
1.5
1.9
15
22.3
27.9
30
29.3
36.6
40
2.2
2.8
15
23.0
28.8
30
30.0
37.5
40
DME020E
1.4
—
—
11.8
—
—
18.8
—
—
200/220V-1-50
DME027E
1.5
—
—
22.3
—
—
29.3
—
—
DME037E
DME044C
2.2
—
—
23.0
—
—
30.0
—
—
Table 17 60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with common power feed
Nominal Capacity, Tons 1.5
2 3
Evaporator Model DME020E DME027E DME037E
Condensing Model DMC022WG DMC029WG DMC040WG
Volt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60
Cooling Only
FLA
WSA
OPD
15.0
18.4
30
With Reheat or With Reheat & Humidifier
FLA 25.4
WSA
OPD
31.4
40
15.1
18.5
30
35.9
44.5
50
20.1
24.6
40
40.9
50.6
60
23
Electrical Data—All Units
Table 18 60Hz electrical data, outdoor air-cooled condensing unit
Nom. Capacity, Tons 1.5
2
Standard 95°F (35°C) Propeller Fan Condensing Unit
3 3 3 3
Model PFH020A-PL7 PFH027A-PL7 PFH037A-PL7 PFH037A-YL7 PFH037A-AL7 PFH037A-BL7
Volt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60
FLA
WSA
OPD
12.1
14.8
25
13.5
16.5
25
High Ambient Propeller Fan Condensing Unit
19.3
23.8
40
12.8
15.7
25
6.4
7.8
15
5.9
7.1
15
Model
Volt-Ph-Hz
FLA
WSA
OPD
N/A
N/A
N/A
N/A
N/A
PFH027A-PH7 PFH037A-PH7 PFH037A-YH7 PFH037A-AH7 PFH037A-BH7
208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60
15.5
18.5
30
21.3
25.8
40
14.8
17.7
25
7.4
8.8
15
5.9
7.1
15
Quiet-Line Propeller Fan Condensing Unit
Model
Volt-Ph-Hz
FLA
WSA
OPD
N/A
N/A
N/A
N/A
N/A
PFHZ27A-PL7 PFHZ37A-PL7 PFHZ37A-YL7 PFHZ37A-AL7
208/230-1-60 208/230-1-60 208/230-3-60
13.0
16.0
25
18.8
23.3
40
12.3
15.2
25
460-3-60
6.4
7.8
15
—
—
—
—
—
Table 19 50Hz electrical data, outdoor air-cooled condensing unit
Nominal Capacity, Tons 1.5
2
Standard 95°F (35°C) Propeller Fan Condensing Unit
Model PFH019A-SL7 PFH026A-SL7
Volt-Ph-Hz
FLA
220-1-50
10.9
220-1-50
12.7
High Ambient Propeller Fan Condensing Unit
Model N/A PFH026A-SH7
Volt-Ph-Hz
FLA
N/A
N/A
Quiet-Line Propeller Fan Condensing Unit
Model N/A
220-1-50
14.8
Volt-Ph-Hz
FLA
N/A
N/A
PFHZ26A-SL7
220-1-50
12.3
2
PFH026A-ML7
380/415-3-50
4.9
PFH026A-MH7
380/415-3-50
6.0
PFHZ26A-ML7
380/415-3-50
4.8
3
PFH036A-SL7
220-1-50
18.4
PFH036A-SH7
220-1-50
20.5
PFHZ36A-SL7
220-1-50
18.0
3
PFH036A-ML7
380/415-3-50
7.0
PFH036A-MH7
380/415-3-50
8.1
PFHZ36A-ML7
380/415-3-50
6.9
24
Electrical Data—All Units
Table 20 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz
Model
60 Hz 50 Hz
208/230-1ph-60Hz 277-1ph-60Hz 208/230-3ph-60Hz 460-3ph-60Hz 220-1ph-50Hz 380/415-3ph-50Hz
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
MC*24A
13.7
16.6
25
MC*36A
19.4
23.3
35
MC*26W
11.4
14.3
25
MC*38W
FLA
WSA
OPD
15.7
19.6
35
* Specify disconnect or no disconnect
MC*24A
11.9
14.3
20
MC*36A
16.6
20.2
30
MC*26W
9.6
12.0
20
MC*38W
14.3
17.9
30
MC*24A
N/A
N/A
N/A
MC*36A
15.1
18.0
25
MC*26W
N/A
N/A
N/A
MC*38W
11.4
14.3
25
MC*24A
N/A
N/A
N/A
MC*36A
7.1
8.5
15
MC*26W
N/A
N/A
N/A
MC*38W
5.7
7.1
15
MC*23A
13.2
16.1
N/A
MC*35A
20.1
24.4
N/A
MC*25W
11.4
14.3
N/A
MC*37W
17.1
21.4
N/A
MC*23A
5.7
6.8
N/A
MC*35A
7.8
9.4
N/A
MC*25W
4.3
5.4
N/A
MC*37W
6.4
8.0
N/A
Figure 14 Stepdown transformer for 277V input power applications
.281" (7mm) Dia.
For wall-mounting purposes
.31" (8mm) Dia.
For rigid mounting and shipping purposes
1D18214P1
10.3" (262mm)
1D18214P2
11.68" (297mm)
1/4-20 (2 screws & lock washers) use for rigid mounting and shipping purposes
Remove screws
& attach bracket
5.5"
(140mm)
4.92"
(125mm) Access to electrical connections from bottom
RIGID MOUNTING
WALL MOUNTING
Notes:
1. 1D18214P1 = Acme catalog no. T-1-37921 for all small systems except 3-ton Liebert DataMate
with integral condenser.
2. 1D18214P2 = Acme catalog no. T-1-37922 for 3-ton DataMate with integral condenser.
3. Epoxy encapsulated. Suitable for indoor/outdoor service. Horizontal or vertical mount.
Totally enclosed, non-ventilated.
4. Both brackets are shipped loose with transformer.
DPN000647
Rev0
25
Refrigerant Piping
10.0 R
EFRIGERANT
P
IPING
Table 21 Refrigerant charge
60 Hz
DME020E
DME027E
DME037E
50 Hz
DME020E
DME027E
DME037E
MC*24AL_H7 MC*23AL_H7
MC*36AL_H7 MC*35AL_H7
MC*26W__H7 MC*25W__H7
MC*38W__H7 MC*37W__H7
DMC022WG
DMC029WG
N/A
N/A
DMC040WG N/A
PFH020A-_L7 PFH019A-_L7
PFH027A-_L7 PFH026A-_L7
PFH027A-_H7 PFH026A-_H7
PFHZ27A-_L7 PFHZ26A-_L7
PFH037A-_L7 PFH036A-_L7
PFH037A-_H7 PFH036A-_H7
PFHZ37A-_L7 PFHZ36A-_L7
Charge R-407C, oz (kg)
4 (0.11)
5 (0.14)
6.5 (0.18)
134 (3.80)
213 (6.04)
41 (1.16)
54 (1.54)
47 (1.33
59 (1.67
61 (1.72)
134 (3.80)
134 (3.80)
213 (6.04)
213 (6.04)
213 (6.04)
426 (12.08)
426 (12.08)
Table 22 Recommended refrigerant line sizes
Equivalent
Length, ft (m)
1.5-Ton
Suction Liquid
2-Ton
Suction Liquid
3-Ton
Suction Liquid
50 (15.2
100 (30.5)
5/8"
7/8"
3/8"
3/8"
7/8"
7/8"
3/8"
1/2"
7/8"
1-1/8"
1/2"
1/2"
150 (45.7) 7/8" 1/2" 7/8" 1/2" 1-1/8" 1/2"
* Suction line and liquid line sizing based on < 3 psi pressure drop in each and suction line refrigerant velocities >700FPM (3.6m/s).
Table 23 Pipe length and condenser elevation relative to evaporator
Nominal
System Size
Tons
Max. Equiv.
Pipe Length ft. (m)
Maximum PFH
Level Above
Evaporator, ft. (m)
Maximum PFH
Level Below
Evaporator, ft. (m)
1.5 & 2 150 (45) 40 (12) 15 (4.6)
3 150 (45) 50 (15) 15 (4.6)
Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require additional specialty items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than 15 ft. (4.6m) below the evaporator. Contact
Emerson Application Engineering for assistance.
Table 24 Refrigerant charge in Liebert pre-charged R-407C line sets
Line Size, in.
3/8 liquid
5/8 or 7/8 suction
Length, ft. (m)
15 (4.5)
30 (9)
15 (4.5)
30 (9)
Charge R-407C, oz (kg)
5 (0.14)
10 (0.28)
5 (0.14)
10 (0.28)
26
Refrigerant Piping
Table 25 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube
Line Size,
O.D., in.
3/8
1/2
5/8
3/4
7/8
1-1/8
1-3/8
R-407C, lb/100 ft. (kg/30m)
Liquid Line Suction Line
3.7 (1.7)
6.9 (3.1)
11.0 (5.0
15.7 (7.1)
23.0 (10.4)
—
—
—
—
0.4 (0.2)
0.6 (0.3)
1.0 (0.4)
1.7 (0.7)
2.7 (1.1)
Figure 15 Refrigerant piping diagram
Pitch down 1/2" (13mm) per 10 ft. (3m)
Evaporator
Suction Line Piping
Condensing Unit
Below Evaporator
NOTE
When installing remote condensing units below the evaporator, the suction gas line should be trapped with an inverted trap to the height of the evaporator . This prevents refrigerant migration to the compressors during off cycles . Maximum recommended vertical level drop to condensing unit is 15 ft. (4.6m) .
Condensing
Unit
maximum vertical rise above evaporator/maximum vertical fall below evaporator.
Condensing
Unit
Evaporator
Suction Line Piping
Condensing Unit Above Evaporator
Traps recommended at the base of riser exceeding
5 ft (1.5m) and every 20 feet (6m) of vertical rise.
Pitch down 1/2" (13mm) per 10 ft. (3m)
Table 26 Equivalent lengths for various pipe fittings, ft (m)
Copper Pipe
OD, in.
1/2
5/8
3/4
90 Degree
Elbow Copper
0.8 (0.24)
0.9 (0.27)
1.0 (0.3)
90 Degree
Elbow Cast
1.3 (0.39)
1.4 (0.42)
1.5 (0.45)
45 Degree
Elbow Tee
Gate
Valve
0.4 (0.12) 2.5 (0.76) 0.26 (0.07)
0.5 (0.15) 2.5 (0.76) 0.28 (0.08)
0.6 (0.18) 2.5 (0.76) 0.3 (0.09)
Globe
Valve
7.0 (2.13)
9.5 (2.89)
12.0 (3.65)
Angle
Valve
4.0 (1.21)
5.0 (1.52)
6.5 (1.98)
7/8
1-1/8
1-3/8
1-5/8
1.45 (0.44)
1.85 (0.56)
2.4 (0.73)
2.9 (0.88)
1.8 (0.54)
2.2 (0.67)
2.9 (0.88)
3.5 (1.06)
0.8 (0.24)
1.0 (0.3)
1.3 (0.39)
1.6 (0.48)
Refrigerant trap = Four times equivalent length of pipe per this table
3.6 (1.09)
4.6 (1.4)
6.4 (1.95)
7.2 (2.19)
0.36 (0.1)
0.48 (0.14)
0.65 (0.19)
0.72 (0.21)
17.2 (5.24)
22.5 (6.85)
32.0 (9.75)
36.0 (10.97)
9.5 (2.89)
12.0 (3.65)
16.0 (4.87)
19.5 (5.94)
27
Glycol Loop Piping
11.0 G
LYCOL
L
OOP
P
IPING
Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer
Figure 16 Heat rejection loop, multiple drycoolers and multiple indoor units
Expansion Tank
______ Gal. (L)
HP GPM (l/s) ft.
____(kW) ____ Per Pump @ ____(kPa)
PUMP PACKAGE
Drycooler No. 1 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
FS
Total
GPM
(L/s): _____
Pipe
Diam.: _____ In. (mm)
P: _____ Ft. (kPa)
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
See Note 3
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Drycooler No. 2 Model ______
GPM (l/s) ____ P: ___ ft (kPa)
LEGEND
Gate Valve
Check Valve
Butterfly Valve
Relief Valve
Union
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
FS
P:
Cooling Unit #
Model
GPM (l/s)
P ft (kPa): Ball or Flow Control Valve
Flow Switch
Pressure Drop
Strainer/Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are
recommended to monitor component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied
by others and located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more
pumps may be considered; consult supplier
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
Cooling Unit #
Model
GPM (l/s)
P ft (kPa):
DPN000991
Rev. 0
28
Model Number Nomenclature—All Systems
12.0 M
ODEL
N
UMBER
N
OMENCLATURE
—A
LL
S
YSTEMS
Figure 17 Model number nomenclature—Evaporator units
DME 037 E P H 7
DME = Liebert DataMate
Evaporator Unit
Nominal capacity
(kBTUH)
E = Evaporator
C = Chilled Water
H = With Humidifier & Reheat
0 = Reheat Only
C = Cooling Only
P = 208/230 1ph, 60Hz
W = 200/220, 1ph, 50Hz
7 = R-407C Refrigerant
Figure 18 Model number nomenclature—Outdoor air-cooled condensing units
PFH 0 37 A — P L 7
PFH = Prop Fan
Condensing
Unit with Hot
Gas Bypass
Nominal Capacity
(kBtuh)
- = Std. Coil
C = Coated Coil
L = 95 F Ambient.
H = 105 F Ambient
0= Std. Sound Level
Z= Quiet-Line
* Not all combinations are possible.
A = Air-Cooled P=208/230/1/60
Y=208/2303/60
A=460/3/60
B=575/3/60
S=220-1-50
M=380/415/3/50
R-407C
Refrigerant
Figure 19 Model number nomenclature—Indoor air-cooled condensing units
MC = Liebert Mini-Mate2 Style Indoor Condensing Units
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity
23 = 2-ton, 50Hz
24 = 2-ton, 60Hz
35 = 3-ton, 50Hz
36 = 3-ton, 60Hz
Supply Power
P = 208/230V - 1 ph - 60 Hz
X = 277V - 1 ph - 60 Hz
S = 220V - 1 ph - 50 Hz
A = 460V - 3 ph - 60 Hz (3-ton only)
Y = 208/230V - 3 ph - 60 Hz (3-ton only)
M = 380/415V - 3ph - 50Hz
Refrigerant
7 = R-407C
MC D 36 A
Cooling Method
A = Air-Cooled
L A H 7
Head Pressure Controls
L = Liebert Lee-Temp Receiver
H = Hot Gas
Bypass
29
Model Number Nomenclature—All Systems
Figure 20 Model number nomenclature, close-coupled water/glycol condensing units—60Hz only
Liebert DataMate Evaporator Section
Nominal Capacity (kBtuH)
WG = Water/Glycol
P = 208/230/1/60
DMC 040 WG P 07
07 = R-407C
Refrigerant
Figure 21 Model number nomenclature—Indoor remote water/glycol-cooled condensing units
MC = Liebert Mini-Mate2
Style Indoor Condensing
Units
D = Disconnect Switch
0 = No Disconnect Switch
Nominal Capacity
25 = 2-ton, 50Hz
26 = 2-ton, 60Hz
37 = 3-ton, 50Hz
38 = 3-ton, 60Hz
Cooling Method
W = Water/Glycol
Supply Power
P = 208/230V - 1 ph - 60 Hz
X = 277V - 1ph - 60 Hz
S = 220V - 1ph - 50 Hz
A = 460V - 3ph - 60 Hz (3-ton only)
Y = 208/230V - 3ph - 60 Hz (3-ton only)
M = 380/415V – 3ph-50Hz
MC D 38 W 2 A H 7
Head Pressure Controls
2 = 2-Way Standard Pressure Water Reg Valve
3 = 3-Way Standard Pressure Water Reg Valve
D = 2-Way High-Pressure Water Reg Valve
T = 3-Way High-Pressure Water Reg Valve
Refrigerant
7 = R-407C
H = Hot Gas Bypass
Figure 22 Model number nomenclature—Chilled water units
Liebert DataMate Cooling Unit
Nominal Capacity (kBtuH)
C— = Chilled Water
P = 208/230/1/60
W = 200/220/1/50
DME 044 C— P H 7
H = With Humidifier and Reheat
0 = Reheat only
C = Cooling only
(no RH or HUM)
7 = Unit Revision
Level
30
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
G
UIDE
S
PECIFICATIONS
—F
OR
L
IEBERT
D
ATA
M
ATE
1.5-
TO
3-T
ON
(5
TO
10.5
K
W)
1.0
G
ENERAL
1.1
Summary
These specifications describe requirements for an environmental control system. The system shall be designed to maintain temperature and relative humidity conditions within the room.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the site.
System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and marked with the CSA c-us logo (60 Hz only).
1.2
Design Requirements
The environmental control system shall be a Liebert DataMate factory assembled unit. The refrigeration system shall be split, with the compressor located in a remote or close-coupled condensing unit.
The evaporator section shall be specifically designed for floor or wall-mounted installation and serviceable from the front of the system. Condensing units shall be designed for outdoor or indoor mounting, below the raised floor, above-dropped-ceiling, or in room installation. Refer to Guide
Specifications Section 2.3, Standard Features/Individual Systems.
Each system shall be capable of delivering ______ CFM. The circulating-air fan shall be two-speed for precise dehumidification control. The fan motor(s) shall total ______hp (kW) . The system shall be designed for blow-through air arrangement.
The system shall have a total cooling capacity of ______ Btu/hr (kW), and a sensible cooling capacity of
_____ Btu/hr (kW). based on the entering air condition of ____ °F (°C) dry bulb, and ____ °F (°C) wet bulb. These units are to be supplied with ____ Volt, ____ PH, ____ HZ power supply.
1.3
Submittals
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical, and Capacity data: Piping and Electrical Connection Drawings.
1.4
Quality Assurance
The specified system shall be factory tested before shipment. Testing shall include, but shall not be limited to: Quality Control Checks, “HiPot” Test (two times rated voltage plus 1000 volts, per NRTL agency requirements), and Metering Calibration Tests. The system shall be designed and manufactured according to world class quality standards. The manufacturer shall be ISO 9001 certified.
2.0
P
RODUCT
2.1
Standard Features/All Systems
2.1.1 Evaporator Cabinet and Frame Construction
The cabinet and chassis shall be constructed of heavy gauge, painted furniture steel. The cabinet shall be designed for easy installation and service access from the front only.
2.1.2 Air Distribution
The air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with multiple double-inlet blowers, self-aligning sleeve bearings, and lifetime lubrication. Fan motor(s) shall be permanent-split capacitor, high efficiency type, equipped with two speeds for air flow modulation. Dehumidification shall utilize the lower fan speed.
Air filter shall be a cleanable polypropylene monofilament type over expanded aluminum with aluminum frame. It shall be easily removable from the front of the system by means of quarter-turn fasteners and shall not require system shutdown for service.
31
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
2.1.3 Microprocessor Control System
The control system shall be microprocessor-based, factory-wired into the system and tested prior to shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/ program control, fan speed selection and unit On/Off shall be located below the display. The control display shall be field-wired to the control board using 4-conductor field-supplied thermostat wire.
Temperature and humidity sensors shall be located in the wall box, which shall be capable of being located up to 300 ft (91.4m) from the evaporator unit.
2.1.3.1
Monitoring
The LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying, dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable) indication. The monitoring system shall be capable of relaying unit operating parameters and alarms to the Liebert SiteScan monitoring system.
2.1.3.2
Control Setpoint Parameters
• Temperature Setpoint: 65-85°F (18 to 29°C)
• Temperature Sensitivity: 1 to 9.9°F (1 to 5°C)
• Humidity Setpoint: 20-80% RH
• Humidity Sensitivity: 1 to 30% RH
The microprocessor can be set within these ranges; however, the unit may not be able to control to extreme combinations of temperature and humidity.
2.1.3.3
Unit Controls
2.1.3.3.1 Compressor Short-Cycle Control
The control system shall prevent compressor short-cycling by a 3-minute timer from compressor stop to the next start.
2.1.3.3.2 Common Alarm and Remote On/Off
A common alarm relay shall provide a contact closure to a remote alarm device. Two (2) terminals shall also be provided for remote On/Off control. Individual alarms shall be “enabled” or “disabled” from reporting to the common alarm.
2.1.3.3.3 Setback Control
The control shall be user-configurable to use a manual setpoint control or a programmable, timebased setback control. The setback control will be based on a 5 day/2 day programmed weekly schedule with capability of accepting 2 events per program day.
2.1.3.3.4 Temperature Calibration
The control shall include the capabilities to calibrate the temperature and humidity sensors and adjust the sensor response delay time from 10 to 90 seconds. The control shall be capable of displaying temperature values in °F or °C.
2.1.3.3.5 System Auto Restart
For startup after power failure, the system shall provide automatic restart with a programmable (up to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the wallmounted controller or from the central, site-monitoring system.
32
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
2.1.4 Alarms
2.1.4.1
Unit Alarms
The control system shall monitor unit operation and activate an audible and visual alarm in the event of the following factory preset alarm conditions.
• High Temperature (max 90°F, 32.2°C)
• Low Temperature (min 35°F, 1.7°C)
• High Humidity (max 85% RH)
• Low Humidity (min 15% RH)
• High Water Alarm - Lockout Unit Operation
• High Head Pressure
• Loss of Power
• Compressor Short Cycle
2.1.4.2
Custom Alarms (2x)
• Humidifier Problem
• Filter Clog
• Water Detected
• Smoke Detected
• Custom Alarm (1)
• Custom Alarm (2)
User-customized text can be entered for the two (2) custom alarms
2.1.4.3
Alarm Controls
Each alarm (unit and custom) shall be individually enabled or disabled (except for high head pressure and high water in condensate pan) and can be programmed for a time delay of 0 to 255 seconds of continuous alarm condition to be recognized as an alarm. Each alarm shall also be enabled or disabled to activate the common alarm (except high head pressure and high water in condensate pan).
2.1.4.4
Audible Alarm
The audible alarm shall annunciate at the LCD wall box any alarm that is enabled by the operator.
2.1.4.5
Common Alarm
A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.
2.1.4.6
Remote Monitoring
All alarms shall be communicated to the Liebert site monitoring system with the following information: date and time of occurrence, unit number, and present temperature and humidity.
2.2
Chilled Water System Components
2.2.1 Chilled Water Control
The water circuit shall include a 2-way slow close On/Off solenoid valve. Design pressure shall be
125psi (862kPa). Valve shall be spring return.
2.2.2 Chilled Water Coil
The cooling coil shall have a minimum of 2.6 ft.
2 (.24m
2 ) face area, 3 rows deep. It shall be constructed of copper tubes and aluminum fins and be mounted in a galvanized condensate drain pan. The coil shall be designed for a maximum face velocity of _____FPM (m/s) at ___ CFM (CMH). The water circuit shall be designed to distribute water into the entire coil face area. The coil shall be supplied with
___ °F (°C) entering water temperature, with a ___°F (°C) temperature rise. The coil shall be supplied with ___ GPM (l/s) of chilled water and the pressure drop shall not exceed ______ psi (kPa).
33
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
2.2
Direct Expansion System Components
2.2.1 Direct Expansion Coil
The evaporator section shall include an evaporator coil, thermostatic expansion valve and filter-drier.
The evaporator coil shall have ___ ft.
2 (m 2 ) face area, ___ rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of ___ FPM (m/s) at _____ CFM (CMH).
An externally equalized thermostatic expansion valve shall control refrigerant flow. The evaporator coil shall be factory-charged with R-407C refrigerant and sealed. The coil shall be provided with a galvanized steel drain pan. The evaporator unit can be coupled directly with a water/glycol condensing unit or mounted remote to the indoor or outdoor condensing unit.
2.3
Indoor Air-Cooled Centrifugal Fan Condensing Unit
Condensing unit components shall include condenser coil, scroll compressor, high-pressure switch,
Liebert Lee-Temp refrigerant receiver, head pressure control valve, hot gas bypass system and liquid line solenoid valve. The hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. Units available for [(2-ton)(3-ton)] systems.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34°C). The condensing unit can be mounted directly to the evaporator or can be mounted remote to the evaporator.
The condensing coil shall be constructed of copper tubes and aluminum fins. The condenser fan shall be centrifugal type, double inlet, direct drive and shall operate at 1050 rpm (890 rpm @ 50 Hz). The fan and motor shall be mounted on vibration isolators. The condenser fan shall be designed for
____CFM (CMH) at ____" (mm) w.g. external static pressure.
2.3
Outdoor Air-Cooled Prop Fan Condensing Unit
Condensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a scroll compressor, high-pressure switch, Liebert Lee-Temp receiver and head pressure control valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass system shall be provided to reduce compressor cycling and improve operation under low load conditions.
All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for
95°F (35°C) ambient and be capable of operation to -30°F (-34.4°C).
The condenser coil shall be constructed of copper tubes and aluminum fins.
(Option) The 2- or 3-ton condensing unit shall be designed to operate at a sound level less than
58dBA.
(Option) The 2- or 3-ton condensing unit shall be designed for design ambient operation of 105°F
(40.6°C).
(Option) The condenser coil shall be phenolic-coated for extended coil life in coastal areas.
2.3
Indoor Close-Coupled Water/Glycol Condensing Unit
The water/glycol-cooled condensing unit shall include a hermetic compressor and a water/glycol cooled condenser, and shall be capable of being close-coupled to the evaporator module. The water/glycol cooled condenser shall be designed to balance the heat rejection at ______ °F (°C) entering water/glycol temperature with a flow rate of ___ GPM (l/s) and have a total system pressure drop of
_____ ft of water (kPa). An adjustable two-way water regulating valve shall be included. The condenser water/glycol circuit shall be designed for a static operating pressure of 150psi (1034kPa).
All components shall be factory assembled, charged with R-407C refrigerant, sealed and be capable of being connected to the evaporator section using quick connect refrigerant couplings and integral wiring harness for single point power connection for close-coupled system. No refrigeration piping, brazing, dehydration or charging shall be required.
34
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
2.3
Indoor Remote Water/Glycol-Cooled Condensing Unit
The water/glycol condensing unit shall include a scroll compressor, high-pressure switch, coaxial condenser, water-regulating valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing dehydration or charging shall be required. Units available for [(2-ton)(3-ton)] systems.
The water/glycol condensing unit shall be equipped with a coaxial condenser having a total system pressure drop of ______ ft. of water (kPa) and a flow rate of ______ GPM (l/s) with ______ °F (°C) entering water/glycol temperature.
The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve which is head-pressure actuated.
The condenser water/glycol circuit shall be designed for a static operating pressure of [(150psi
(1034kPa)) (350 PSI (2413 kPa))].
2.4
Factory-Installed Options
2.4.1 Electric Reheat
The electric reheat shall be low-watt density, tubular element and shall include agency approved safety switch to protect the system from overheating. The capacity of the reheat coil shall be ______
BTU/HR, ____ KW, controlled in 1 stage.
2.4.2 Steam Generating Humidifier
The environmental control system shall be equipped with a steam generating humidifier that is controlled by the microprocessor control system. It shall be complete with disposable canister, all supply and drain valves, 1" (25.4mm) air gap on fill line, inlet strainer, steam distributor, and electronic controls. The need to change canister shall be annunciated on the microprocessor wallbox control panel.
The humidifier shall have a capacity of 3 lb./hr. (1.4kg/h). An LED light on the humidifier assembly shall indicate cylinder full, overcurrent detection, fill system fault, and end of cylinder life conditions.
2.5
Ship-Loose Accessories
2.5.1 Remote Sensors
The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be connected to the unit by a 30 ft. (9m) shielded cable.
2.5.2 Condensate Pump
The condensate pump shall have the capacity of _____ GPH (___ l/h) at ___ ft. head (___ kPa). It shall be complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float switch shall be provided to permit field wiring to the unit control to shut down the evaporator upon a high water level condition.
2.5.3 Refrigerant Line Sets
Pre-charged refrigerant line sets shall be provided by Emerson in proper lengths for application. Line set length shall be [(15 ft. (4.5m)) (30 ft. (9m))].
2.5.4 Refrigerant Line Sweat Adapter Kit
Provide a sweat adapter kit to permit field brazing of refrigerant line connections.
2.5.5 Step-Down Transformer
A step-down transformer shall be provided for [(Indoor Evaporator) (Close-Coupled Water/Glycol Condensing Unit) (Outdoor Air-Cooled Condensing Unit)] needing 277V input power voltage. The transformer shall be coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable mounting brackets, suitable for [(indoor)(outdoor)] mounting.
35
Guide Specifications—For Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)
2.5.6 Liebert Local Monitoring Systems, Autochangeover and Leak Detection
Provide indicated quantities of the following:
• ______ Leak Detection System(s) Model __________________________________
• ______ Remote Monitor(s) Model ________________________________________
• ______ Auto Changeover Control(s) Model ________________________________
2.5.7 Liebert SiteScan Site Monitoring System
A Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote monitoring of the Liebert DataMate unit and monitoring of other Liebert support equipment. The Liebert SiteScan shall have the capability to monitor and change (at the user direction) the temperature and humidity setpoints and sensitivities of each unit. The printer shall provide the user with chronological alarm information. It shall also be capable of being programmed to print out environmental conditions or operating modes at each unit.
2.5.8 Drycooler
The Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil, and one or more direct drive fans. All electrical connections and controls shall be enclosed in an integral, NEMA
3R rated electrical panel section of the drycooler. The drycooler shall be quiet and corrosion resistant.
The drycooler shall be designed for _____°F (°C) ambient.
2.5.9 Glycol Pump Package
The system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The pump shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and operate on _____ volt, ____ phase,
______ Hz.
3.0
E
XECUTION
3.1
Installation of Air Conditioning Units
3.1.1 General
Install Air Conditioning units in accordance with manufacturer's installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's recommended clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor.
3.1.4 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer's instructions and local codes require.
3.2
Field Quality Control
Startup airconditioning units in accordance with manufacturer's start up instructions. Test controls and demonstrate compliance with requirements.
36
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2009 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-11035_REV2_05-10
Technical Support / Service
Web Site www.liebert.com
Monitoring [email protected]
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets [email protected]
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
Emerson Network Power.
The global leader in enabling Business-Critical Continuity ™
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets
Services
Surge Protection
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies.
©2009 Emerson Electric Co.