03-2009:C

03-2009:C
Product data sheet
Sheet No.: 1.604.08 - Rev: C, Page 1 of 4
Date:
March, 2009
FieldQ
Integrated Base Control Module
QC21, QC22 and QC23 (Moulded Ex d e mb, Ex ia/ib e mb)
Pilot valve specifications
The pilot valve inside the Control Module sends the actuator to its open or closed position. The following moulded pilot
valves are available:
Module
QC21
QC22
QC23
Voltages
24VDC (±10%)
115 VAC (±10%)
230 VAC (±10%)
Power
3W
5W
5W
Wiring diagram:
- Pilot valves
FieldQ Control Module
Unclassified or Non Hazardous or
Hazardous Location Classified Location
Description:
These FieldQ conventionally wired control modules with the
moulded pilot valve, offer an integrated concept for valve
automation. Its compact and robust construction incorporates
basic control and feedback functionality. These modules are
certified for use in Zone 1, 2, 21 and 22 and are suitable for
all gas and dust groups.
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside, wiring
terminals are available for connecting control and feedback
signals. Three cable entries are available.
Features:
- Basic actuator functions for fail safe (spring return) or
double acting applications.
- Robust IP65/NEMA4X enclosure, protecting the IPT
system, the pilot valve’s coil, the feedback switches and
terminals, suitable for indoor and outdoor use.
- All the control and feedback connections can be wired to
the Control Module.
- IPT-technology.
- Easy to set feedback signals.
- Control module can be easily plugged in the pneumatic
module.
- ATEX Zone 1, 2, 21 and 22 approvals.
General specifications:
Material housing
: Aluminium alloy
Electrical connections : Internal 9 pole terminal strip.
Cable entries
: 3x M20x1.5 or 3x 1/2”NPT
Operating media
: Air or inert gasses, filtered at 50μm
Switch point
: Factory set at 15° before each end of
travel (open and closed position).
- Adjustable range
: Between -3° to 15° and +75° to +93°
of the end position.
Enclosure
: IP65 / NEMA 4X
Finish
: Polyester non-TGIC based powder
coating.
Temperature
: Depends on the applied switches and
or Hazardous Area approvals
(See section Feedback switches
QC21, QC22 & QC23)
Dimensions
: See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
1
2
COM NO
3
4
5
NC COM NO
6
NC
8
9
GND (-)
(+)
7
N
Switch specifications:
- See section “Feedback
switches”
Cable range : 0.2 - 2.5mm2 or 24-14AWG
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
L
Pilot valve voltages:
QC21 24VDC
3W
QC22 115 VAC 5W
QC23 230 VAC 5W
Product data sheet
Sheet No.: 1.604.08 - Rev: C, Page 2 of 4
Date:
March, 2009
FieldQ
Feedback switches QC21, QC22 and QC23 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
Hermetically sealed switches
Option code
D
Type
Hermetically sealed V3
Voltage
250 VAC or VDC (maximum)
Contacts
Gold plated, NO and NC
Mechanical life
107 operations (depends on electrical load).
Temperature
-20°C to +60°C (-4°F to +140°F)
Maximum currents:
Load :
125 VAC
250 VAC
30 VDC
125 VDC
250 VDC
Non Inductive
5A
5A
5A
0.5 A
0.25 A
The hermetically sealed switches have gold contacts. For
applications where the benefits of gold contacts are required,
the maximum current is 100mA. When the current is higher
than 100mA, the gold plating will evaporate.
Inductive
5 A (Cos φ ≥ 0.9)
5 A (Cos φ ≥ 0.9)
5A
0.06 A
0.03 A
Hazardous area executions:
The Conventional Modules QC21, QC22 and QC23, in combination with the Hermetically sealed switches, have ATEX
approvals for use in Zone 1, 2, 21 or 22 and for all gas and
dust groups.
Wiring diagram:
- Mechanical switches
- Hermetically sealed switches
- ATEX
FieldQ Control Module
Unclassified or Hazardous or
Non Hazardous Location Classified Location
Important
:
:
0344
II 2 G Ex d e mb IIC T4/T5
II 2 D Ex tD A21 T85°C IP65
: Certificate : TÜV 07 ATEX 553927X
Temperature range
T4 @ Ta = -20°C(-4°F) to +60°C (140°F)
T5 @ Ta = -20°C(-4°F) to +40°C (104°F)
1
2
COM NO
3
4
5
NC COM NO
6
NC
8
9
GND (-)
(+)
7
N
Open
Close
Switch Connections
L
Pilot valve1
Cable range : 0.2 - 2.5mm2 or 24-14AWG
1 See secton “Pilot valve specifications”
2 For Zone 1 or 21 hazardous area applications, see Installation Guide :
DOC.IG.QC21.1
3 Wiring diagram is shown in the actuators mid-stroke position.
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.08 - Rev: C, Page 3 of 4
Date:
March, 2009
FieldQ
Feedback switches QC21, QC22 and QC23 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
2-Wire NAMUR proximity switches
Option code
N
Type
2-wire inductive, normally closed
Voltage
8 VDC nominal
Ouput
Unswitched , > 3mA
Switched , < 1mA
Temperature
-20°C to 60°C (-4°F to +140°F)
Compliant to
DIN EN 60947-5-6 (NAMUR)
QC14 Intrinsically Safe Entity Parameters Feedback switches
Switch
Terminal
Ui
Ii
Pi
Ci
Li
Type N
1 – 2, 4 - 5 16Vdc 25mA 64mW 100nF 100μH
* a cable length of 10 m is considered.
Hazardous area executions:
The Conventional Modules QC21, QC22 and QC23, in
combination with the NAMUR proximity switches, have ATEX
approvals for use in Zone 1, 2, 21 or 22 and for all gas and
dust groups.
Wiring diagram:
Unclassified or
Non Hazardous Location
1
L-
2
IS
barrier3
(+)
L
(-)
N
L+
3
4
L-
5
IS
barrier3
(+)
L
(-)
N
6
7
8
9
N(+)
L+
- ATEX :
0344
: II 2 G Ex ia/ib e mb IIC T4/T5
II 2 D Ex tD A21 T85°C, IP65
: Certificate : TÜV 07 ATEX 553927X
L(-)
Hazardous or
Classified Location
2-Wire NAMUR proximity switches
Temperature range:
T4 @ Ta = -20°C(-4°F) to +60°C (140°F)
T5 @ Ta = -20°C(-4°F) to +40°C (104°F)
Pilot valve1
Open
Close
Switch Connections1
Cable range : 0.2 - 2.5mm2 or 24-14AWG
1 See secton “Pilot valve specifications”
2 For Zone 1 or 21 hazardous area applications, see Installation Guide :
DOC.IG.QC21.1
3 IS Approved barrier
4 Wiring diagram is shown in the actuators mid-stroke position.
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.08 - Rev: C, Page 4 of 4
Date:
March, 2009
FieldQ
Feedback switches QC21, QC22 and QC23 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
Mechanical switches
Option code
Type
Voltage
Contacts
Mechanical life
Temperature
M or G
Mechanical V4
250 VAC or 250 VDC (maximum)
NO and NC (G = Goldplated)
107 operations (depends on electrical load).
-20°C to +60°C (-4°F to +140°F)
Safety parameters Mechanical switches
M type
Voltage Ui
30 V
Maximum Li
300 mA
Power Pi
1.2 W
Capacity Ci
0 nF
Inductivity Li
0 mH
G type
30 V
100 mA
1.2
0 nF
0 mH
Hazardous area executions:
The Conventional Modules QC21, QC22 and QC23, in
combination with the mechanical or gold plated mechanical
switches have ATEX approvals for use in Zone 1, 2, 21 or 22
and for all gas and dust groups.
Wiring diagram:
- Mechanical switches
- Hermetically sealed switches
Unclassified or Non Hazardous or ClasHazardous Location sified Location
- ATEX :
0344
: II 2 G Ex ia/ib e mb IIC T4/T5
II 2 D Ex tD A21 T85°C, IP65
: Certificate : TÜV 07 ATEX 553927X
1
2
COM NO
3
NC
4
5
COM NO
6
NC
7
NC
8
9
+
-
Temperature range
T4 @ Ta = -20°C(-4°F) to +60°C (140°F)
T5 @ Ta = -20°C(-4°F) to +40°C (104°F)
Pilot valve1
Open
Close
Switch Connections
Cable range : 0.2 - 2.5mm2 or 24-14AWG
1 See secton “Pilot valve specifications”
2 For Intrinsically Safe (Cl. I Div1 or Zone 1 or 21) hazardous area applications, see Installation Guide : DOC.IG.QC21.1
3 Wiring diagram is shown in the actuators mid-stroke position.
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement