V570

V570
Vision™ OPLC™
Installation Guide
V570-57-C30B and V570-57-T40B (Color)
This guide provides basic information for Unitronics’ controllers V570-57-C30B and V570-57-T40B.
General Description
Vision OPLCs are programmable logic controllers that comprise an integral operating panel.
V570-57-C30B and V570-57-T40B comprise a color touchscreen, which displays a virtual keyboard
when the application requires the operator to enter data.
Communications
2 isolated RS232/RS485 ports
Isolated CANbus port, CANopen & UniCAN
The user can order and install an Ethernet port
Communication Function Blocks include: SMS, GPRS, MODBUS serial/IP
Protocol FB enables PLC to communicate with almost any external device,
via serial or Ethernet communications
I/O Options
Vision supports up to 5121 digital,
high-speed, and analog I/Os via:
Snap-in I/O Modules
Plug into the back of the
controller to provide an onboard I/O configuration
I/O Expansion Modules
Via adaptor, local or remote I/Os
may be added via expansion port
or CANbus
Installation instructions and other data may be found in the module’s technical
specification sheet.
Information
Mode
This mode enables you to:
Calibrate the touchscreen
View & Edit operand values, COM port settings, RTC and screen
contrast/brightness settings
Stop, initialize, and reset the PLC
To enter Information Mode, press the touchscreen and maintain contact for
several seconds.
Programming
Software,
& Utilities
The Unitronics Setup CD contains VisiLogic software and other utilities
VisiLogic
Easily configure hardware and write both HMI and Ladder control
applications; the Function Block library simplifies complex tasks such
as PID. Write your application, and then download it to the controller
via the programming cable included in the kit.
Utilities
These include UniOPC server, Remote Access for remote
programming and diagnostics, and DataXport for run-time data
logging.
To learn how to use and program the controller, as well as use utilities such as
Remote Access, refer to the VisiLogic Help system.
1 Number of I/Os may vary according to I/O module selection.
Unitronics
1
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Installation Guide
Removable
Memory
Storage
An SD card enables you to store datalogs, Alarm history, Data Tables; export to
Excel/.csv, backup Ladder, HMI & OS and use this data to ‘clone’ PLCs.
For more data, refer to the SD topics in the VisiLogic Help system.
Operand Types
Memory Bits 8192; Memory Integers 4096 registers 16-bit, 512 Long Integers,
32-bit, 256; Double Word, 32-bit unsigned, 64; Memory Floats, 32-bit, 384;
Timers, 32-bit, 32; Counters, 16-bit.
Data Tables
120K (Dynamic)/ 192K (Static) enables application recipes and data logging.
Additional product documentation is in the Technical Library, located at www.unitronics.com, and on
the Unitronics’ Setup CD.
Technical support is available at the site, and from [email protected]
Standard Kit Contents
Vision controller
Battery (not installed)
3 pin power supply connector
Programming cable + RS232 adapter
5-pin CANbus connector
Mounting brackets (x4)
CANbus network termination resistor
Rubber seal
Unitronics’ Setup CD
Danger Symbols
When any of the following symbols appear, read the associated information carefully.
Symbol
Caution
Meaning
Description
Danger
The identified danger causes physical and property damage.
Warning
The identified danger could cause physical and property damage.
Caution
Use caution.
Before using this product, the user must read and understand this document.
All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance
with the standards given in the product’s technical specification sheet.
Ventilation: 10mm space required between controller’s top/bottom edges & enclosure walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Install at maximum distance from high-voltage cables and power equipment.
2
Unitronics
Installation Guide
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Inserting the Battery
In order to preserve data in case of power-off, you must insert the battery.
The battery is supplied taped to the battery cover on the rear of the controller.
1. Remove the battery cover shown on page 6. The polarity (+) is marked on the battery holder and
on the battery.
2. Insert the battery, ensuring that the polarity symbol on the battery is:
- facing up
- aligned with the symbol on the holder
3. Replace the battery cover.
Dimensions
Unitronics
3
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Installation Guide
Mounting
Before you begin, note that the mounting panel cannot be more than 5 mm thick.
1. Make a panel cut-out according to the dimensions in the next figure.
Cut-out Dimensions
2. Slide the controller into the
cut-out, ensuring that the
rubber seal is in place.
3. Push the 4 mounting brackets
into their slots on the sides of
the controller as shown in the
figure to the right.
4. Tighten the bracket screws
against the panel. Hold the
bracket securely against the
unit while tightening the screw.
5. When properly mounted, the controller is squarely situated in the panel cut-out as shown below.
4
Unitronics
Installation Guide
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Wiring: General
Do not touch live wires.
Unused pins should not be connected. Ignoring this directive may damage the device.
Caution
To avoid damaging the wire, do not exceed a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
Use crimp terminals for wiring; use 26-14 AWG wire (0.13 mm 2–2.08 mm2).
1. Strip the wire to a length of 7±0.5mm (0.250–0.300”).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Power Supply
The controller requires an external 24VDC power supply. The permissible input voltage range is
20.4-28.8VDC, with less than 10% ripple.
A non-isolated power supply can be used if a 0V signal is connected to the chassis.
You must use an external circuit protection device.
Install an external circuit breaker. Guard against shortcircuiting in external wiring.
Double-check all wiring before turning on the power
supply.
Do not connect either the ‘Neutral or ‘Line’ signal of the
110/220VAC to device’s 0V pin.
In the event of voltage fluctuations or non-conformity to
voltage power supply specifications, connect the device
to a regulated power supply.
To maximize system performance, avoid electromagnetic interference by:
Mounting the controller on a metal panel.
Earthing the controller’s power supply: connect one end of a 14 AWG wire to the chassis
signal; connect the other end to the panel.
Note: The wire used to earth the power supply must not exceed 10 cm in length.
If your conditions do not permit this, do not earth the power supply
Unitronics
5
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Installation Guide
Communication Ports
This series comprises 2 RS232/RS485 serial ports and a CANbus port.
Turn off power before making communications connections.
Caution
Always use the appropriate port adapters.
Serial Communications
The serial ports are type RJ-11 and may be set to either RS232 or RS485 via DIP switches, in
accordance with the table shown on page 6.
Use RS232 to download programs from a PC, and to communicate with serial devices and
applications, such as SCADA.
Use RS485 to create a multi-drop network containing up to 32 devices.
Pinouts
The pinouts below show the signals between the adapter and port.
To connect a PC to a port that is set to RS485, remove the RS485 connector, and connect the PC
to the PLC via the programming cable. Note that this is possible only if flow control signals are not
used (which is the standard case).
RS232
RS485**
Controller Port
Pin #
Description
Pin #
Description
1*
DTR signal
1
A signal (+)
2
0V reference
2
(RS232 signal)
3
TXD signal
3
(RS232 signal)
4
RXD signal
4
(RS232 signal)
5
0V reference
5
(RS232 signal)
6*
DSR signal
6
B signal (-)
Pin #1
*Standard programming cables do not provide connection points for pins 1 and 6.
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,
and Pin 6 (DSR) signal is used for signal B.
RS232 to RS485: Changing DIP Switch Settings
The ports are set to RS232 by factory default.
To change the settings, first remove the Snap-in I/O Module, if one is installed, and then set the
switches according to the following table.
RS232/RS485: DIP Switch Settings
The settings below are for each COM port.
Switch Settings
1
2
3
4
5
RS232*
ON
ON
ON
OFF
ON
6
OFF
RS485
OFF
OFF
OFF
ON
OFF
ON
RS485 with
termination**
ON
ON
OFF
ON
OFF
ON
*Default factory setting
**Causes the unit to function as an end unit in an RS485 network
6
Unitronics
Installation Guide
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Removing a Snap-in I/O Module
1. Locate the four buttons on the sides of the controller, two on either side.
2. Press the buttons and hold them down to open the locking mechanism.
3. Gently rock the module from side to side, easing the module from the controller.
Re-installing a Snap-in I/O Module
1. Line the circular guidelines on the controller up with the guidelines on the Snap-in I/O Module as
shown below.
2 Apply even pressure on all 4 corners until you hear a distinct ‘click’. The module is now installed.
Check that all sides and corners are correctly aligned.
Unitronics
7
Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Installation Guide
CANbus
These controllers comprise a CANbus port. Use
this to create a decentralized control network
using one of the following CAN protocols:
CANopen: 127 controllers or external
devices
Unitronics’ proprietary UniCAN: 60
controllers, (512 data bytes per scan)
-V
The CANbus port is galvanically isolated.
PE
CANbus Wiring
-
24V Power
Supply
+
Circuit
protection
device
121
terminating
resistor
L
H
+V
Use twisted-pair cable. DeviceNet® thick
shielded twisted pair cable is recommended.
Network terminators: These are supplied with the
controller. Place terminators at each end of the
CANbus network.
Resistance must be set to 1%, 121S, 1/4W.
-V
L
PE
H
+V
Connect ground signal to the earth at only one
point, near the power supply.
The network power supply need not be at the
end of the network
CANbus Connector
-V
L
PE
H
+V
121
terminating
resistor
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them.
DIG-V570-CT 04/08
8