Master-Fit® Spec Sheet (Canada)(CANCG10000)

Master-Fit® Spec Sheet (Canada)(CANCG10000)
Commercial Gas
Water Heaters
Master-Fit®
FULLY TESTED FOR SAFETY AND PERFORMANCE
• Design certified by Underwriters Laboratories for 180°F (82°C) hot water service
• Certified for use on combustible flooring
• 80% thermal efficiency
FULLY AUTOMATIC CONTROLS WITH SAFETY SHUTOFF
• Accurate, dependable control system
• Manual reset gas shutoff device for added safety
• Maximum inlet gas pressure is 13.8” w.c. for natural gas and propane, and minimum gas pressure is 4.5” w.c. for
natural gas and 11” w.c. for propane
BTRC 120-500A
WATER CONNECTIONS
• For ease of installation, most models feature water connections on the top, front, and rear
GLASS-LINED TANK
• PermaGlas® Ultra Coat™ is the proprietary liquid glass coating developed by A. O. Smith
• Applied after tank construction, the tank is mechanically maneuvered to ensure the liquid glass covers all surfaces
for superior protection
Eliminator™ SELF CLEANING DEVICE DIRECTS INCOMING COLD WATER TO SWEEP
THE BOTTOM OF THE TANK SO SEDIMENT DOES NOT ACCUMULATE
FOAM INSULATION SAVES FUEL AND HELPS REDUCE STANDBY HEAT LOSS
HEAVY GAUGE STEEL JACKET WITH BAKED ENAMEL FINISH OVER A BONDERIZED UNDERCOAT
HANDHOLE CLEANOUT ALLOWS FOR EASY CLEANING
INTERMITTENT IGNITION DEVICE
• Eliminates standing pilot
• Provides flame failure response in less than one second
• Power ON/OFF switch
EASY-TO-INSTALL
• Completely factory-assembled - only gas, water, vent and electric connections need be made
• Provided with drain valve
FACTORY-INSTALLED AND TESTED DRAFT DIVERTER
• Low-profile draft hood with automatic motorized flue damper to minimize standby losses
CoreGard™ LONG-LIFE, STAINLESS STEEL CORE ANODE RODS
COMPLIANCE
• All models comply with ANSI Z21.10.3 - CSA 4.3 standards and meet or excced NRCan thermal
efficiency and/or standby loss requirements and current edition of ASHRAE/IESNA 90.1
OTHER FEATURES
• Equipped with gas pressure regulator and pilot filter
• Integral automatic gas shutoff system prevents excessive water temperature
• CSA Certified and ASME Rated T&P relief valve
• Maximum working pressure is 160 psi (1103 kPa) standard
• Adjustable thermostat with a 120-180°F (49°C-82°C) range
OPTIONS
• Power vent kits for side wall venting (see back page for details)
• Meets NSF Standard 5 with optional leg kit (part number 9003425205)
WARRANTY
• 3 year limited tank warranty
• 1 year limited parts warranty
• For complete information, consult the written warranty or A. O. Smith
© A. O. Smith Enterprises Ltd. All Rights Reserved
www.hotwater.com | 888-599-2837 Toll-Free Canada | A. O. Smith Enterprises Ltd. | 599 Hill Street West | Fergus, ON N1M 2X1
LOW LEAD CONTENT
ASME
on selected models.
Approved to NSF
Standard 5
with Optional Leg Kit
Page 1 of 4
CANCG10000
Commercial Gas
Water Heaters
ROUGH-IN DIMENSIONS - SIDE VIEW
Models BTRC 120-500A
CLEARANCE TO
COMBUSTIBLES
MODEL
SIDES & REAR
CLEARANCE TO
NON-COMBUSTIBLES
TOP COVER
SIDES & REAR
TOP COVER
BTRC-120
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-154
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-180
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-197
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-199
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-200A
1” (2.54 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-250A
2” (5.08 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-251(A)
2” (5.08 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-275A
2” (5.08 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-305(A)
2” (5.08 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-365(A)
4” (10.16 cm)
4” (10.16 cm)
4” (10.16 cm)
12” (30.48 cm)
BTRC-400A
3” (7.62 cm)
12” (30.48 cm)
0” (0 cm)
12” (30.48 cm)
BTRC-500A
5” (12.7 cm)
24” (60.96 cm)
0” (0 cm)
12” (30.48 cm)
Gas Connection
WATER CONNECTIONS IN INCHES (NPT)
Top View of BTRC
MODEL
BTRC-120
INLET
OUTLET
TOP
FRONT
REAR
TOP
FRONT
REAR
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
BTRC-154
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
BTRC-180
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
BTRC-197
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
BTRC-199
1.5”
1.5”
1.5”
1.5”
1.5”
BTRC-200A
1.5”
2”
2”
1.5”
2”
2”
BTRC-250A
1.5”
2”
2”
1.5”
2”
2”
BTRC-251(A)
N/A
1.5”
1.5”
N/A
1.5”
1.5”
BTRC-275A
1.5”
2”
2”
1.5”
2”
2”
BTRC-305(A)
N/A
1.5”
2”
N/A
2”
1.5”
BTRC-365(A)
N/A
1.5”
1.5”
N/A
1.5”
1.5”
BTRC-400A
1.5”
2”
2”
1.5”
2”
2”
BTRC-500A
1.5”
1.5”
1.5”
1.5”
1.5”
1.5”
GAS PRESSURE REQUIREMENTS
ELECTRICAL SPECIFICATIONS
NATURAL GAS
PROPANE GAS
Max. Supply Pressure
13.8” w.c.
13.8” w.c.
Min. Supply Pressure
4.5” w.c.
11” w.c.
Manifold Pressure
3.5” w.c.
10” w.c.
VOLTS
AMPS
BTRC
120VAC
.7
BTRC with Power Venter
120VAC
3.0 FLA
© A. O. Smith Enterprises Ltd. All Rights Reserved
www.hotwater.com | 888-599-2837 Toll-Free Canada | A. O. Smith Enterprises Ltd. | 599 Hill Street West | Fergus, ON N1M 2X1
Page 2 of 4
CANCG10000
Commercial Gas
Water Heaters
DIMENSION TABLES FOR BTRC
MODELS 120-500A
MODEL
INPUT
RATING
A
IN (CM)
B
IN (CM)
C
IN (CM)
D
IN (CM)
E
IN (CM)
F
IN (CM)
G
IN
H
IN (CM)
I
IN (CM)
J
IN (CM)
SHIPPING WEIGHT
LB (KG)
BTU/h
kW/h
CAPACITY
USG (L)
BTRC-120
120,000
35
71 (268)
69 ¾ (177)
4 ¼ (11)
59 ½ (151)
50 7/8 (129)
19 ¾ (50)
19 (48)
½
51 7/8 (132)
5 (13)
27 ¾ (71)
512 (232)
N/A
BTRC-154
154,000
45
81 (307)
73 (185)
4 ¼ (11)
66 ½ (169)
57 7/8 (147)
19 ¾ (50)
19 (48)
½
59 (150)
6 (15)
27 ¾ (71)
552 (250)
N/A
BTRC-180
180,000
53
76 (288)
67 ½ (171)
4 ½ (12)
62 (157)
53 5/8 (136)
20 ½ (52)
21 (53)
½
54 5/8 (139)
6 (15)
27 ¾ (71)
576 (261)
N/A
BTRC-197
199,000
58
95 (360)
75 (191)
4 ½ (12)
70 (178)
61 /8 (157)
20 ½ (52)
21 (53)
½
62 5/8 (159)
6 (15)
27 ¾ (71)
645 (293)
N/A
BTRC-199
199,000
58
76 (288)
67 ½ (171)
4 ½ (12)
62 (157)
53 5/8 (136)
20 ½ (52)
21 (53)
½
54 5/8 (139)
6 (15)
27 ¾ (71)
592 (269)
N/A
BTRC-200A
199,000
58
100 (379)
72 (183)
4 ½ (12)
65 1/8 (165)
55 7/8 (142)
19 ¾ (50)
23 (58)
½
56 3/8 (143)
6 (15)
30 ¼ (77)
N/A
715 (324)
BTRC-250A
250,000
72
100 (379)
72 (183)
4 ½ (12)
65 1/8 (165)
55 7/8 (142)
19 ¾ (50)
23 (58)
½
56 3/8 (143)
8 (20)
30 ¼ (77)
N/A
715 (324)
BTRC-251(A)
251,000
73
65 (246)
75 (191)
4 ½ (12)
65 ¾ (167)
57 ¼ (145)
20 (51)
N/A
½
58 ¾ (149)
8 (20)
27 ¾ (71)
660 (299)
661 (300)
BTRC-275A
275,000
80
100 (379)
72 (183)
4 ½ (12)
65 1/8 (165)
55 7/8 (142)
19 ¾ (50)
23 (58)
½
56 3/8 (143)
8 (20)
30 ¼ (77)
N/A
721 (327)
BTRC-305(A)
305,000
89
65 (246)
75 (191)
4 ½ (12)
65 ¾ (167)
57 ¼ (145)
20 (51)
N/A
½
58 ¾ (149)
8 (20)
27 ¾ (71)
659 (299)
672 (305)
BTRC-365(A)
360,000
105
65 (246)
79 ½ (202)
4 ½ (12)
70 ¼ (178)
62 ½ (159)
22 ½ (57)
23 (58)
¾
63 (160)
8 (20)
27 ¾ (71)
670 (304)
661 (300)
BTRC-400A
390,000
117
100 (379)
75 ½ (192)
4 ½ (12)
67 ½ (171)
58 ¼ (148)
26 ¾ (68)
23 (58)
¾
59 (150)
8 (20)
30 ¼ (77)
N/A
844 (383)
BTRC-500A
500,000
147
85 (322)
81 ½ (207)
4 ½ (12)
77 ¼ (187)
67 ½ (171)
25 ½ (65)
21 (53)
1
67 ½ (171)
8 (20)
27 ¾ (71)
N/A
824 (374)
5
STD.
ASME
“A” suffix identifies ASME only.
“(A)” suffix identifies optional ASME model available. Contact A. O. Smith Enterprises for dimensions of ASME versions of the BTRC- 251, 305 & 365
Models available in both natural gas and propane, as well as sea level and high altitude.
MODEL
INPUT
RATING
CAPACITY
USG (L)
THERMAL
EFFICIENCY
RECOVERY RATING CAPACITIES
GPH (LPH)
30°F
(17°C)
40°F
(22°C)
50°F
(28°C)
60°F
(33°C)
70°F
(39°C)
80°F
(45°C)
90°F
(50°C)
100°F
(56°C)
110°F
(61°C)
120°F
(67°C)
130°F
(72°C)
140°F
(78°C)
80%
388
(1469)
291
(1102)
233
(882)
194
(734)
166
(628)
145
(549)
129
(488)
116
(439)
106
(401)
97
(367)
90
(341)
83
(314)
81 (307)
80%
498
(1885)
373
(1412)
299
(1132)
249
(943)
213
(806)
187
(708)
166
(628)
149
(564)
136
(515)
124
(469)
115
(435)
107
(405)
53
76 (288)
80%
579
(2192)
434
(1643)
347
(1314)
289
(1094)
248
(939)
217
(821)
193
(731)
174
(659)
158
(598)
145
(549)
134
(507)
124
(469)
199,000
58
95 (360)
80%
643
(2434)
482
(1825)
386
(1461)
322
(1219)
276
(1045)
241
(912)
214
(810)
193
(731)
175
(662)
161
(609)
148
(560)
132
(500)
BTRC-199
199,000
58
76 (288)
80%
643
(2434)
482
(1825)
386
(1461)
322
(1219)
276
(1045)
241
(912)
214
(810)
193
(731)
175
(662)
161
(609)
148
(560)
132
(500)
BTRC-200A
199,000
58
100 (379)
80%
643
(2434)
482
(1825)
386
(1461)
322
(1219)
276
(1045)
241
(912)
214
(810)
193
(731)
175
(662)
161
(609)
148
(560)
132
(500)
BTRC-250A
250,000
72
100 (379)
80%
808
(3059)
606
(2294)
485
(1836)
404
(1529)
346
(1310)
303
(1147)
269
(1018)
242
(916)
220
(833)
202
(765)
186
(704)
173
(655)
BTRC-251(A)
251,000
73
65 (246)
80%
811
(3070)
608
(2301)
487
(1843)
406
(1537)
348
(1317)
304
(1151)
270
(1022)
243
(920)
221
(837)
203
(768)
187
(708)
174
(659)
BTRC-275A
275,000
80
100 (379)
80%
889
(3365)
667
(2525)
533
(2018)
444
(1681)
381
(1442)
333
(1261)
296
(1120)
267
(1011)
242
(916)
222
(840)
205
(776)
190
(719)
BTRC-305(A)
305,000
89
65 (246)
80%
986
(3732)
739
(2797)
592
(2241)
493.
(1866)
423
(1601)
370
(1401)
329
(1245)
296
(1120)
269
(1018)
246
(931)
228
(863)
211
(799)
BTRC-365(A)
360,000
105
65 (246)
80%
1164
(4406)
873
(3304)
698
(2642)
582
(2203)
499
(1888)
436
(1650)
388
(1468)
349
(1321)
317
(1199)
291
(1105)
269
(1018)
249
(942)
BTRC-400A
390,000
117
100 (379)
80%
1290
(4883)
967
(3660)
774
(2930)
645
(2442)
553
(2093)
484
(1832)
430
(1628)
387
(1465)
352
(1332)
322
(1219)
298
(1128)
276
(1045)
BTRC-500A
500,000
147
85 (322)
80%
1596
(6041)
1197
(4531)
958
(3626)
798
(3021)
684
(2589)
598
(2264)
532
(2014)
479
(1813)
435
(1647)
399
(1510)
368
(1393)
342
(1295)
BTU/h
kW/h
BTRC-120
120,000
35
71 (268)
BTRC-154
154,000
45
BTRC-180
180,000
BTRC-197
© A. O. Smith Enterprises Ltd. All Rights Reserved
www.hotwater.com | 888-599-2837 Toll-Free Canada | A. O. Smith Enterprises Ltd. | 599 Hill Street West | Fergus, ON N1M 2X1
Page 3 of 4
CANCG10000
Commercial Gas
Water Heaters
POWER VENT KITS FOR BTRC
FEATURES
DESIGNED FOR FLEXIBILITY - Easy to install sidewall power vent system. Use
these kits where gas is the preferred choice, but conventional venting is costly.
Allows conversion from electric to gas or upgrading to units with higher inputs
without having to do costly venting system upgrades. Easy to install and wire.
Approved for use on all A. O. Smith water heaters listed below. Allows the use of
smaller diameter vent pipe than allowed with conventional venting.
POWERFUL 115 VOLT POWER VENTER - Allows venting up to 100 (30.48m)
equivalent feet away. Each model sized for a perfect match with A. O. Smith water
heaters. Power Venters have one or more of the following depending on the
heater’s requirements. Built in 24/115 volt relay to interface with control systems.
Combination 24 volt relay and adjustable post-purge timer control in lieu of relay
on some models. Installed diaphragm draft proving switch. Vibration isolation
mount works with common plumber’s strap and helps keep operation quiet. All
controls factory mounted and wired for simple installation.
ALUMINUM VENT HOOD - Mounts on outside of wall. Features telescoping
vent pipe connection sleeve, rust free construction, outside wall condensate shield,
1” air space provides clearance for combustibles, special heat shield protects
building exterior. Mounting hardware included.
COLOUR CODED WIRING HARNESS - Eliminates need for electrician (check
codes). Simple 24 volt connections and a 40 ft. (12.2m) low voltage cable.
MODEL
PART
NUMBER
MOTOR
WATT
MOTOR
AMPS
MAX
LENGTH
OF VENT
FT (M)
BTRC-120-200A
197515-000
95
1.26
100 (30.48)
BTRC-250A - 500A
197515-001
224
2.0
100 (30.48)
VENT
DIAMETER
SIZE
IN (CM)
DIMENSIONS
IN (CM)
C
VENT
ASSEMBLY
HEIGHT
D
VENT
ASSEMBLY
DEPTH
E
VENT
ASSEMBLY
WIDTH
F
VENT
TERMINATION
SQUARE
G
H
ROUGH
IN
4 (10.1)
7 7/8 (20)
7 (17.7)
11 (27.9)
9 (22.9)
8 7/8 (22.5)
7 ½ sq. (19.1)
8 sq. (20.3)
6 (15.2)
9 ¼ (23.5)
8 ½ (21.6)
11 ½ (29.2)
10 1/8 (25.7)
9 ½ (24.1)
8 ½ dia. (21.6)
9 dia (22.9)
* Vent pipe/vent hood connection based on Class B vent pipe sizes. Calculated using total pipe length, plus 5 ft. (1.524m) for every 90° elbow and 2 ½ ft. (0.762m) for every 45° elbow.
SUGGESTED SPECIFICATION
Water Heater(s) shall be Model ________________ as manufactured by A. O. Smith, or equal. Water heater(s) shall be of glass-lined design, and
gas-fired, equipped to burn ________________ gas and design certified by Underwriters Laboratories under Volume III tests for commercial heaters for delivery of 180°F (82°C) water, and meet of exceed the thermal efficiency and/or standby loss requirements of NRCan and current edition of
ASHRAE/IESNA 90.1. Heaters shall have an input rating of ________and a recovery rating of __________ GPH (LPH) at a temperature rise of 100°F
(38°C) with a storage capacity of _________ gallons (liters). Heaters shall be equipped with 1 ½” (38.1mm) water inlet and outlet openings, a 2
¾” (69.85mm) x 3 ¾” (95.25mm) boiler-type hand hole clean out and shall have a maximum working pressure of 160 psi (1103.1 kPa). Water heater(s)
shall be equipped with an integrated control system consisting of a 180°F (82°C) adjustable thermostat with upper and lower sensing bulbs, which average the water temperatures at the top and bottom of the tank for maximum water temperature control. Heater(s) shall be provided with a manual reset
gas shutoff device, a gas pressure regulator set for the type of gas supplied, coated steel burners, an approved draft hood, anodes for cathodic protection,
flue damper and IID system. A CSA Certified and ASME Rated T&P relief valve shall be furnished and installed by the factory. The heater shall be insulated
with foam insulation or equal. The outer jacket shall have a baked enamel finish over a bonderized undercoating. All internal surfaces of the
heater(s) exposed to water shall be glass-lined with an alkaline borosilicate composition that has been fused-to-steel by firing at a temperature
range of 1400° (760°C) to 1600°F (871°C). Heater tank shall have a 3-year limited warranty against corrosion or sediment buildup as outlined in the written
warranty. Fully illustrated instruction manual to be included.
For Technical Information call 888-599-2837. A. O. Smith Enterprises Ltd. reserves the right to make product changes or improvements without prior notice.
Revised April 2015
www.hotwater.com | 888-599-2837 Toll-Free Canada
Page 4 of 4
CANCG10000
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement