ENDA ET2011 PID TEMPERATURE CONTROLLER Thank you for choosing 2011 temperature controller.

ENDA ET2011 PID TEMPERATURE CONTROLLER Thank you for choosing 2011 temperature controller.
english
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
ENDA ET2011 PID TEMPERATURE CONTROLLER
Thank you for choosing ENDA ET2011 temperature controller.
* 77 x 35mm sized.
* Selectable dual-set value.
* Selectable thermocouple types or Pt100 input.(Selection must be
specified in order).
* Automatic calculation of PID parameters.(SELF TUNE).
°F
SSR
C/A2
°C
F
SET
Enter PID parameters of the system if they are known at the beginning.
Otherwise, Self-Tune should be activated.
* Soft-Start feature.
* Input offset feature.
* C/A2 Relay output can be programmable as alarm or control output.
ENDA
ET2011
* Selectable SSR control output.
* Selectable heating/cooling control.
* In the case of sensor failure periodical running or relay state can be
selected.
* CE marked according to European Norms.
TECHNICAL SPECIFICATIONS
Input type
°C
Pt 100 Resistance thermometer
Pt 100 Resistance thermometer
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt10Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple
EN 60751
EN 60751
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
Temperature range
°F
-99.9...300.0 °C
-99.9...543.0 °F
-200...600 °C
0... 600 °C
0...1300°C
0... 400°C
0...1700°C
0...1700°C
-328...1112 °F
+32... +1112 °F
+32... +2372 °F
+32... +752 °F
+32... +3092 °F
+32... +3092°F
Accuracy
0,5% (of full scale)
0,5% (of full scale)
0,5% (of full scale)
0,5% (of full scale)
0,5% (of full scale)
0,5% (of full scale)
0,5% (of full scale)
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/-25... +70°C (with no icing)
80% up to 31°C decreasing linearly 50% at 40.
Max. Relative humidity
According to EN 60529
Front panel : IP65
Rated pollution degree
Rear panel : IP20
Max. 2000m
Height
Do not use the device in locations subject to corrosive and flammable gases.
up to date: 01022014, modification reserved and can be change any time previous notice !
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
230V AC +%10 -%20, 50/60Hz or 24V AC %10, 50/60Hz
Max. 5VA
Power connector: 2.5mm²' screw-terminal, Signal connector: 1,5mm² screw-terminal conenction.
Max. 100ohm
EEPROM (minimum 10 years)
EN 61326-1: 2006
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
OUTPUTS
C/A2 output
SSR output
Life expectancy for relay
Relay : 250V AC, 8A (for resistive load), Selectable as NO+NC Control or Alarm2 output.
Relay : 250V AC, 16A (for resistive load), Selectable as NO Control or Alarm2 output.
Max 20mA 12Volt (as control output)
Withot load 30.000.000 mechanical operation; 250V AC, on the 8A resistive load 100.000
electrical switching
CONTROL
Control type
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power
Single set-point and alarm control
12 bit
100ms
Adjustable between 0% and 100%. If Pb=0%, On-Off control is selected.
Adjustable between 1 and 250 seconds
Adjustable between 1 and 50°C/F
The ratio of power at a set point can be adjusted between 0% and 100%
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting according to DIN 43 700.
W77xH35xD71mm
Approx. 200g (after packing)
Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
1./4
ET2011-E
SET
key is pressed while holding
C.typ. = Control output type
C.typ. = HEAt means heatign control.
C.typ. = CooL means cooling control.
C1.sE. 400
C2.SE. 400
A2.SE. 500
-200
600
0
2
4.0
1.00
20
0
0
0
HEat
0
-200
600
2
indE
Hi
on
Alarm2 output
parameters
TC input Pt100 input
Pt.
inp.t. FE.cn.
Unit
°C
25
Fltr.
C.o.SE.
C-A2
0
offs.
f.k.E.C.
nonE
50
m.sEt.
TC input Pt100 input
Configuration
parameters
DEFAULT PARAMETERS
a2.Er.
no
TC input Pt100 input
Self tune
parameters
m.SEt. = The percentage of manual output parameter.
Adjustable between %0 and %100.
This parameter allows manual adjustment of the output
power when the manual output selection.
m.SEt.
oFfS. = Offset value.
Offset value is added to the measurement value.
Adjusted between -100 and +100°C.The normal value is 0.
C.o.sE = Control output selection
C-A2= C/A2 (Relay) output selection
SSR = SSR output selection
SET
SET
SET
Co.sc.
A2.Sc.
Cn.Sc.
S.t.Sc.
dEf.P.
and
Co.sc.
S.Cod.
SEcu.
Security
parameters
P.yEs
P.yEs
P.yEs
P.yEs
no
TC input Pt100 input
SET
SET
SET
5
SET
6
key, the value of parameter flashes and using
6
2/4
ET2011-E
If
key is pressed and held 0.6 seconds, the value of the selected
parameter changes rapidly. If waited enough,the value increases 100 at each
step. After 1 second following the release of the key, initial condition is
returned.The same procedure is valid for the decrement key.
keys the requested value can be adjusted.
When holding
Chys
Co.sc. = Parameters of Conf.
menu security access level code.
no = Parameter settings are not
change.
yEs = Parameter setting will be
S.t.Sc. = Parameters of S.tun.
menu security access level code.
nonE = Invisible.
Co.sc. = Parameters of Conf.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
P. no = Only visible.
a.2.sc. = Parameters of al2.o.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
Cosc. = Parameters of CoN.o.
menu security access level code.
nonE = Invisible.
P.yEs = Modification can be done.
Modification Of Parameter Diagram
dEF.P.
SET
S.Cod = Security menu access
code.
It should be 2011.
SET
keys are pressing
Selt tune begins when the measurement,
a.2.sc.
PIdt. message and measurement value
are shown alternately.Self tune process
completed automatically after the stco
parameter is done no and is entered to the
working mode. Self tune process begin when
the measured temperature is expected fall
below 90% of the set value the display shows Cn.sc.
te.HImessage alternately.Expected to fall
below the temperature set point 60% evolved
and then self tune process starts automatically.
If asked to abort the self tune process,St.Co
parameter is done no and
key is
S.t.sc.
pressed.
SET
If both
keys are pressed, no
message is displayed on the screen
and self tune process is stopped.
message is displayed on the screen
and self tune process is started
automatically.
Cu = Self tune control parameter.
s.t.Co. IfSt.both
keys are pressed ,yes
S.tun.
key is pressing programming mode is entered.Then
F.kE.C. = Function key setting parameter
nonE= Function key is off.
C2.S.A.= The function key with 2.set value is used.
manu. = Manual mode can be achieved with the
function key.
dSP.o.= Only the temperature display mode is
TC input Pt100 input
0
F
fLtr.= Coefficient of digital filter.
Filter for display value.
Adjustable between 1 and 200. If this parameter is 1,
digital filter runs most quick. If the parameter is 200,
the filter run most slow. The value of parameter should
be increased in interference.
Unit = The temperature unit.
°C= °C,°F= °F
(This parameter varies when
inp.t. = Input type selection.
FE.cn.= J type ,nc.nA.= K type c.cn.= T
type p10.r.=S type , P13.r.= R type
thermocouple selection.
This parameter varies when changing
SET
key and
F.k.E.C.
Control output
parameters
A2.s.l
A2.s.H
A2Hy.
A2.tp
a2.st.
a2.Er.
A2.Er.
C.s.lO.
C.s.Hi.
C. PB
C.HyS
C. ti
C. td
C. Ct.
C.P.St.
C.EP.S.
S.s.t.S.
C.typ.
A2.Er. = State of Alarm2 output in the
case of sensor failure.
on= A2 output is probe failure (on).
Set parameters
A2.st. = The state of Alarm2 output.
Hi= If A2 output is above the set
value. (on)
lo= If A2 output is above the set
A2.St.
offs.
C.o.sE
A2.tp = Function of Alarm2 type.
Four kinds of functions can be
selected.
indE.= Independdnt alarm
(Independent)
dE. = Deviation
bAnd = Band alarm (Band)
A2.tP
fltr.
a2.Hy= Hysteresis of the Alarm2
output.
A2.HY
Unit
inp.t.
ConF.
A2.S.H
a2.s.l= Alarm2 set value lower limit.
Adjustable between 0 and A2.S.H
parameter value.
SET
Programming mode
Alternatively, the same function occurs first pressing
together,data is recorded and running mode is entered.
Entering from the programming mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the run mode is entered.
a2.s.H= Alarm2 set value upper limit.
Adjustable between A2.S.L
parameter value and upper scale
value.
A2.S.L
If co.SE parameter is different
from C-A2,this parameter is seen.
AL2.o.
key, the programming mode is enabled.
Sst.S =Sofy starter timer set value
This parameter indicates the time to reach set point
value when the device is first enegised.
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be enable and the
device reaches set point value quickly.
Setting Pb = 0, soft start feature will be disable.
C.E.P.s. = The percentage of faulty sensor
selected output power.Adjustable between
%0 and %100.
C.p.st = The ratio of output power at the
setpoint.Adjustable between %0 and %100.
C. Ct. = Period time.(for selected output)
Adjustable between 1 and 250 second.
C. Pb parameter is different is different
C. td = Derivative time.(for selected output)
Asjustable between 0.00 and 25.00 minutes.
C. td = 0.0, derivative time is disable.
C. Pb parameter is different from”0”,this
C. ti = Integral time.(for selected output)
Adjustable between 0 and 100.0 minutes.
C. ti = 0.0,integral impact is disable.
C. Pb parameter is different from “0”,this
C.Hys = Hysteresis of the output.(for
selected output)
Adjustable between 1 and 50 °C.
C. Pb = Proportional band.(for selected
output)
Adjustable between %0.0 and %100.0.
C. Pb= %0.0,On-Off control is selected.
C.s.Hi.= Control setpoint upper limit.(for
selected output)
Adjustable between C.s.Lo. and Upper scale
C.s.lo.= Control set point lower limit.(for
selected output)
Adjustable between 0 and C.s.Hi.
If
SET
While the parameter names appear,if
and F
keys are pressed together, returns to the program
mode.
C.typ
s.s.t.s.
C.E.p.s.
C.p.st
C. Ct.
C. td
C. ti
C.Hys
C. pb
C.s.Hi.
C.s.Lo.
Con.o.
SET
TERMS
(5)
°F
( 1 ) Measurement value and set value indicator Running mode)
Parameter name and value (Programming mode)
( 2 ) Value increment key (Programming mode)
If only this key is pressed in normal operation,software version
number is seen. (F.k.E.C. parameter processing)
SSR
C/A2
°C
F
SET
ENDA
( 2) Value decrement and parameter selection key.
(Programming mode)
ET2011
( 4 ) Control ve Alarm set selection key (Running mode)
Parameter set key (Programming mode)
( 1 ) PV and SV display
7 segment, 4 digits red LED display
Character heights
12 mm
( 2 ),( 3 ),( 4 ) Keypad
Mikro switch
For control, Alarm1 and SSR outputs 3 digits red LED
( 5 ) State indicator
ALARM2 OUTPUT TYPES
Independent Alarm
A2.tp.=indE
SV
Band Alarm
A2.tp.= bAnd
Deviation Alarm
A2.tp= dE.
SV
ON
SV
ON
ON
OFF
OFF A2.St.= Hi
ON
ON
ON
OFF
OFF A1.St.= Lo
OFF
A2.Hy
a2,Hy
A2.St.= lo
OFF
A2.Hy
SV-ASV
ASV
SV+ASV +300
(ASV min. = beginning of scale-300
ASV max. = end of scale)
(ASV min. =-300, ASV max. = +300)
A2.St.= Hi
A2.Hy
SV+ASV
300
300
SV =Set point of CONT output
ASV = Set point of AL2 output
(ASV min. = 0, ASV maX. = +300)
SV
= Set point of CONT output
ASV = Set point of alarm output
Band Alarm With Inhibition
A2.tp.= bAn.i
SV+ASV
SV+ASV
SV
SV
SV-ASV
SV-ASV
ON
OFF
ON
OFF
Beginning
Band alarm is possible
SV =Set point of CONT output
Beginning
Band alarm is possible
ASV = Set point of AL2 output (ASV min. = 0, ASV maks. = 300 )
MODIFICATION OF CONTROL AND ALARM SET POINTS
ERROR MESSAGES
250
3 seconds later
pfa
SET
C1.SE.
399
C2.SE.
399
a2.SE.
499
400
398
3 seconds later
Sensor is broken
----
Temperature value is
higher than the value
____
Temperature value is
lower than the scale
psC
Pt100 sensor is short circuit
3 seconds later
F.kE.C. parameter, is set to the C2.S.A. parameter,this
parameter is displayed.
3 seconds later
C.O.SE.parameter is set to the output of SSR,this
parameter is seen.
SET
500
3./4
ET2011-E
DIMENSIONS
Depth
73mm
77mm
°F
SSR
C/A2
35mm
°C
F
SET
ENDA
ET2011
Connection
cable
1
3
4
5
7
6
8
10
9
+
Flush mounting Panel
clamp
29,5mm
2
SSR OUT
C/A2
250V AC 8A
RESISTIVE LOAD
1
2
Panel cut-out
71mm
Flush
mounting
clamp
11 12
+
230V AC +10% -20%
50/60Hz 5VA
-
5mm
For removing the device from
the panel:
- While pressing both side of
the device in direction 1, push it
in direction 2.
TC
MADE IN TURKEY
642117 704086 8
ET2011-T-230
PID DIGITAL THERMOSTAT
ENDA INDUSTRIAL ELECTRONICS
SN: XXXXXXXXX
Note
1) Panel thickness should be maximum 7mm.
2) If there is no 60mm free space at back side of the device,
it would be difficult to remove it from the panel.
Order Code: ET2011-X- XXX- X
Contact current selection
Supply voltage
None......8A contact output
230VAC......230V AC
P....16A contact output
110VAC......110V AC
024VAC........24V AC
SM.......9-30VDC/7-24V AC
Input selection
RT....PT100 input
T....TC input
CONNECTION DIAGRAM
ENDA ET2011 is intended for installation in control panels. Make sure that the device is used only for intended
purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are
connected to the device must be free of energy. The device must be protected against inadmissible humidity,
vibrations, severe soiling.Make sure that the operation temperature is not exceeded. All input and output lines
that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should
not be close to the power cables or components. The installation and electrical connections must be carried on by
a qualified staff and must be according to the relevant locally applicable regulations.
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
+
-
2
3
4
5
6
7
8
9
ENDA INDUSTRIAL ELECTRONICS
10
-
11 12
SN: XXXXXXXXX
ET2011-T-230-P
PID DIGITAL THERMOSTAT
1
2
3
4
5
3
4
5
6
7
8
10
SSR OUT
Holding screw
0.4-0.5Nm
NOTE :
SUPPLY:
184-253V AC 5
50/60Hz 5VA 6
10
11 12
SN: XXXXXXXXX
8 680407 711369
230V AC +10% -20%
50/60Hz 5VA
C/A2
250V AC 16A
RESISTIVE LOAD
TC
9
9
ET2011-RT-230-P
PID DIGITAL THERMOSTAT
+
2
8
+
+
1
7
PT100
-
ENDA INDUSTRIAL ELECTRONICS
8 680407 711284
230V AC +10% -20%
50/60Hz 5VA
C/A2
250V AC 16A
RESISTIVE LOAD
6
-
11 12
1
2
3
4
5
6
7
8
SSR OUT
1
8 680407 711321
230V AC +10% -20%
50/60Hz 5VA
C/A2
250V AC 8A
RESISTIVE LOAD
TC
+
+
SSR OUT
8 680407 711246
230V AC +10% -20%
50/60Hz 5VA
C/A2
250V AC 8A
RESISTIVE LOAD
SN: XXXXXXXXX
ET2011-RT-230
PID DIGITAL THERMOSTAT
ET2011-T-230
PID DIGITAL THERMOSTAT
SSR OUT
ENDA INDUSTRIAL ELECTRONICS
PT100
9
10
11 12
Equipment is protected throughout
by DOUBLE INSULATION.
Note 1) Mains supply cords shall meet the requirements
of IEC 60227 or IEC 60245.
Switch
2) In accordance with the safety regulations, the
Phase
230V AC
power supply switch shall bring the identification of
Neutral
Supply
the relevant instrument and it should be easily
Fuse should
accessible by the operator.
be connected. Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
E-mail : [email protected]
Internet : www.suran-elektronik.de
4./4
ET2011-E