Bulletin F-42-AFR Series AFR Air Filter Regulator Specifications - Installation and Operating Instructions 2-19/32 [65.8] 21/32 [16.5] 3.130 [79.5] INSTALLATION Install the regulator as close as possible to the instrument or tool it is to service. For best filter drainage, orient the valve so it is at the lowest point on the dripwell housing. The words “IN” and “OUT” are cast into the body to indicate the direction of flow. OPERATION Turning the adjusting screw changes the force exerted by the range spring on the diaphragm assembly. In equilibrium of set pressure, the force exerted by the range spring is balanced by the force from the output pressure acting underneath the diaphragm. An unbalanced state between the output pressure and the set pressure causes a corresponding reaction in the diaphragm and supply valve assemblies. If the output pressure rises above the set pressure, an upward force is exerted on the diaphragm assembly causing the relief seat to lift and open. Excess pressure is vented to atmosphere until equilibrium is reached. If the output pressure drops below the set pressure, the unbalanced force of the range spring causes a downward force on the diaphragm assembly. The supply valve then opens until the pressure builds up once more to the equilibrium condition. 2-53/64 [71.6] INPUT 1/4˝ NPT 3/8 [9.6] DRAIN GAUGE PORT 1/4˝ NPT 3.130 [79.5] The Series AFR Air Filter Regulators are designed to provide clean, accurate air pressure to instruments, valves and other automatic control equipment under variable conditions. The regulators are designed for air service only. Maximum allowable inlet pressure is 250 psi. Operating temperature is 0 to 160°F. The Series AFR has a low capacity internal relief which provides very limited down stream over pressure protection. To avoid exceeding outlet pressure limits in service, a pressure relieving or pressure limiting device should be used. 7-3/4 [196.8] OUTPUT 1/4˝ NPT SPECIFICATIONS Service: Air only. Output Ranges: 0 to 10 psi (0 to 70 kPa), 0 to 30 psi (0 to 200 kPa), 0 to 60 psi (0 to 400 kPa), and 0 to 120 psi (0 to 800 kPa). Maximum Supply Pressure: 250 psig (1700 kPa). Port Size: 1/4˝ NPT(F) in, out, and gage. Mounting: Pipe or through body. Flow Capacity: 20 SCFM (33.0 m3/hr) at 100 psig (700 kPa) supply with 20 psig (140 kPa) output. Exhaust Capacity: 0.1 SCFM (0.17 m3/hr) with downstream pressure 5 psig (35 kPa) above set point. Sensitivity: 1˝ (2.5 cm) of water. Air Consumption: Less than 6 SCFH (0.17 m3/hr). Filter Size: 40 micron. Effect of Supply Pressure Variation: Less than 0.2 psig (1.4 kPa) for 25 psi (170 kPa) change. Materials of Construction: Body: Aluminum Alloy, Irridite, and baked epoxy finish; Filter: Phenolic Impregnated Cellulose; Diaphragm and Valve seat Plug: Nitrile Elastomer. Weight: 1.6 lb (725 g). Under forward flow conditions, the range spring force is balanced by the diaphragm pressure force, with the supply valve open just enough to maintain the required equilibrium pressure. When high flow occurs, a specially designed aspirator helps maintain downstream pressure and compensates for droop. Prior to turning on supply air, back off adjusting screw until there is no compression of the range spring. After turning supply pressure on, turn the adjusting screw clockwise to increase outlet pressure. PROXIMITY CONTROLS A DIVISION OF DWYER INSTRUMENTS, INC. P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Phone: 219/879-8000 Fax: 219/872-9057 www.dwyer-inst.com e-mail: [email protected] See Figures 1 and 2 below for additional performance characteristics. EFFECT OF UPSTREAM PRESSURE VARIATIONS ON REGULATED PRESSURE 100 (700) Before using these products with fluids other than air, for non-industrial applications, life-support systems, or other applications not within published specifications, contact Dwyer Instruments, Inc. 90 (620) 0-120 (0-800) 80 (560) OUTPUT PRESSURE, PSIG (kPa) WARNING The Series AFR Air Filter Regulator is intended for use in industrial compressed air systems only. Do not use these products where pressures and temperatures can exceed those listed under specifications. 70 (480) MAINTENANCE To Remove Condensate Slowly open drain valve and bleed accumulated liquid. RANGE PSIG (kPa) 60 (420) 50 (350) 0-60 (0-400) To Clean Filter Element 1) Shut off air supply. 2) Drain condensate. 3) Remove four corner bolts from bottom of unit. 4) Remove dripwell housing and filter. 5) Clean parts and reassemble in reverse order. 40 (280) 30 (200) 0-30 (0-100) 20 (140) 10 0-10 (0-65) (70) 0 50 (345) 60 (414) 70 (483) 80 (552) 100 (689) 90 (620) INPUT PRESSURE, PSIG (kPa) Figure 1 EFFECT OF CHANGES IN FLOW ON REGULATED PRESSURE 100 PSI (6.9 bar) SUPPLY 100 (700) MAINTENANCE Upon final installation of the Series AFR Air Filter Regulator, no routine maintenance is required. A periodic check of the system calibration is recommended. This Series AFR is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping. 90 (620) OUTPUT PRESSURE, PSIG (kPa) 80 (560) RANGE PSIG (kPa) 70 (480) 0-120 (0-800) 60 (420) 50 (350) 0-60 (0-400) 40 (280) 30 (200) 20 (140) 0-30 (0-100) (70) 0-10 (0-65) 10 0 2 (3.5) 4 (6.7) 6 (10.1) 8 (13.4) 10 (16.8) 14 (23.5) 12 (20.7) 16 (26.9) 18 (30.2) 20 (33.6) 3 FLOW, SCFM (M /hr) Figure 2 ©Copyright 2014 Dwyer Instruments, Inc. PROXIMITY CONTROLS A DIVISION OF DWYER INSTRUMENTS, INC. P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Printed in U.S.A. 4/14 Phone: 219/879-8000 Fax: 219/872-9057 FR# RP-440986-00 Rev. 5 www.dwyer-inst.com e-mail: [email protected]
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement