Thermozone AD Corinte W - ADCS
125
125
Fig 2
2200/2450
500
350
Fig 3
2
1
2
Ø22 Cu
Ø22 Cu
3
1
80
60
PH2 /
1/4”
60
80
Thermozone AD Corinte W - ADCS
3
Thermozone AD Corinte W - ADCS
6
3
1
2
B
C
A
5
7
10
9
4
Fig 4
4
8
Thermozone AD Corinte W - ADCS
Fig 5
5
Thermozone AD Corinte W - ADCS
1700/2200
75
1670/2170
Wall
Right connection
100
126
Left connection
Ø31.5 (2x)
Ø20 (3x)
Fig 6a
Min 180 mm
Min 180 mm
50
75
376
Fig 6b
6
Thermozone AD Corinte W - ADCS
35
80
180
35
ø1
2
25
40
Fig 6c
Fig 6d
360
0
Ø22
5
15
10
243
Ø1
Fig 7
7
Thermozone AD Corinte W - ADCS
ADCEH
Ø8
Ø12 (2x)
}
2 alternatives for securing at the
top.*1
A
B
C
Ø8 for securing at the air curtain.*2
A
B
C
SE / NO / FR / RU / DE / NL / ES / PL / FI / IT / DK
*1) 2 alt. för stagning i toppen. / 2 muligheter for
montering på toppen. / 2 possibilités de fixation par le
haut. / 2 варианта крепления верхней части / Zwei Befestigungsmöglichkeiten an der Oberseite / 2 alternatieven voor bevestiging aan de bovenkant. / 2 opciones de sujeción a la parte superior. / 2 opcje montażu w
części górnej. / 2 vaihtoehtoista kiinnitystapaa. /
2 alternative per il montaggio sulla parte superiore. /
2 alternativer til fastgørelse foroven.
*2) Ø8 för stagning i luftridån. / Ø8 for montering
på luftporten. / Ø8 pour fixation du rideau d’air. /
Для крепления к завесе / Ø 8 zur Befestigung am
Luftschleier / Ø8 voor bevestiging aan het luchtgordijn. / Ø8 para sujeción a la cortina de aire. / Ø8 do
zamocowania kurtyny powietrznej. / Ø8 ilmaverhokojeen kiinnitykseen. / Ø8 per il montaggio sulla barriera
d’aria. / Ø8 til fastgørelse af lufttæppet.
8
Thermozone AD Corinte W - ADCS
ADCS - SIRe
Fig 8
SIRe
9
Thermozone AD Corinte W - ADCS
Regulations alternatives
This aircurtain is supplied with an intelligent
and well designed low voltage control
system SIRe which can be customized for
each unique application and environment.
The control system is pre-installed in the
aircurtain with an integrated control card.
Type
SIReB
SIReAC
SIReAA
SIReRTX
SIReUR*
SIReWTA
SIReCJ4
SIReCJ6
SIReCC603
SIReCC605
SIReCC610
SIReCC615
SIReCC403
SIReCC405
SIReCC410
SIReCC415
RSK-nr
673 09 22
673 09 21
673 09 23
673 09 24
673 09 25
673 09 26
673 09 27
673 09 28
673 09 29
673 09 30
SIRe is supplied pre-programmed with quickrelease connections and is very easy to use
and install. There are three different levels
with different functionality to choose from,
Basic, Competent or Advanced.
Description
Control system Basic
Control system Competent
Control system Advanced
External room temperature sensor
Kit for recessed installation
Clamp-on sensor
Joint piece for two pcs. RJ11 (4p/4c)
Joint piece for two pcs. RJ11 (6p/6c)
Modular cable RJ11 (6p/6c)
Modular cable RJ11 (6p/6c)
Modular cable RJ11 (6p/6c)
Modular cable RJ11 (6p/6c)
Modular cable RJ11 (4p/4c)
Modular cable RJ11 (4p/4c)
Modular cable RJ11 (4p/4c)
Modular cable RJ11 (4p/4c)
HxWxD
[mm]
L
[m]
70x33x23
114x70x50
3
5
10
15
3
5
10
15
Water regulation
Type
Description
VOS15LF
VOS15NF
VOS20
VOS25
VOSP15LF
VOSP15NF
VOSP20
VOSP25
VMO15LF
VMO15NF
VMO20
VMO25
VMOP15LF
VMOP15NF
VMOP20
VMOP25
VOT15
VOT20
VOT25
VMT15
VMT20
VMT25
VAT
Valve kit on/off
Valve kit on/off
Valve kit on/off
Valve kit on/off
Pressure independent valve kit
Pressure independent valve kit
Pressure independent valve kit
Pressure independent valve kit
Modulating valve kit
Modulating valve kit
Modulating valve kit
Modulating valve kit
Pressure independent and modulating valve kit
Pressure independent and modulating valve kit
Pressure independent and modulating valve kit
Pressure independent and modulating valve kit
Three way valve and actuator on/off
Three way valve and actuator on/off
Three way valve and actuator on/off
Three way valve and modulating actuator
Three way valve and modulating actuator
Three way valve and modulating actuator
Adjustment tool for valve kit VOS, VOSP, VMO, VMOP
10
Voltage
[V]
230 V
230 V
230 V
230 V
230 V
230 V
230 V
230 V
24 V
24 V
24 V
24 V
24 V
24 V
24 V
24 V
230 V
230 V
230 V
24 V
24 V
24 V
Connection
DN15
DN15
DN20
DN25
DN15
DN15
DN20
DN25
DN15
DN15
DN20
DN25
DN15
DN15
DN20
DN25
DN15
DN20
DN25
DN15
DN20
DN25
Thermozone AD Corinte W - ADCS
Wiring diagrams
Internal wiring diagram
ADCS W 230V~
SIReB1
C2
Internal Motor
sensor protection
Yellow
Orange
Red
Brown
Black
Green
Blue
230V
200V
170V
145V
120V
100V
N
Transformer
ROOM
Transformer
C1
230V
200V
170V
145V
120V
100V
N
Blue
Actuator
230V~
Black
Supply
230V~
N L
230V~
11
Thermozone AD Corinte W - ADCS
Wiring diagrams
Basic
SIReB1
SIReRTX
(optional)
SD230
Pot.
Unit ID
C2
X5
C1
X4
ROOM
X3
230V~
SIReUB1
ACTUATOR SUPPLY
N L PE PE N L
C
Basic - parallell
SIReB1
C2
Pot.
X5
Unit ID
SD230
C1
X4
ROOM
X3
230V~
ACTUATOR SUPPLY
N L
PE PE N
L
SIReB1
C2
Pot.
X5
Unit ID
SD230
C1
X4
ROOM
X3
230V~
ACTUATOR SUPPLY
N L PE PE N L
SIReB1
C2
Pot.
X5
Unit ID
SD230
C1
X4
ROOM
X3
230V~
ACTUATOR SUPPLY
N L PE PE N L
12
SIReRTX
(optional)
SIReUB1
Thermozone AD Corinte W - ADCS
15 161718
1112
+ -
EXTERNAL RPM 0-10V DC IN
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
COM 1
COM 2
EXTERNAL ALARM IN
(potential free contact)
C2
Pot.
X5
Unit ID
SIReB1
C1
X4
ROOM
X3
~
N L L
PE N
L
230V~
SD230
SIReC1X
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF
5-30V AC/DC
7 8 9 10
ROOM
19 20
SIReRTX
(optional)
SIReDC
SIReUA1
Competent
13
14
C2
X5
Pot.
Unit ID
SIReB1
C2
X5
C2
Pot.
X5
Unit ID
SIReB1
Pot.
Unit ID
SIReB1
C1
X4
C1
X4
C1
X4
ROOM
X3
ROOM
X3
ROOM
X3
~
N L L PE N L
ACTUATOR SUPPLY
~
N L L PE N L
ACTUATOR SUPPLY
~
N L L PE N L
ACTUATOR SUPPLY
230V~
230V~
230V~
SD230
SD230
SD230
COM 1
SIReC1X
COM 2
7 8 9 10
15 161718
EXTERNAL ON/OFF, 5-30V AC/DC
1112
ROOM
19 20
SIReUA1
SIReRTX
(optional)
Thermozone AD Corinte W - ADCS
Competent - parallell
ALARM OUT (BMS)
(potential free contact,max 3A, 230V)
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
Thermozone AD Corinte W - ADCS
21 22
19 20
111213 1415 161718
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
1 2 3 4 5 6 7 8 9 10
COM 1
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
Black
Grey
Red
RPM INDICATION
0-10V DC out (max 5 mA)
Black
Grey
Red
SIReST23024
Pot.
Unit ID
SIReB1
C2
X5
C1
X4
ROOM
X3
~
ACTUATOR SUPPLY
N L L PE N L
230V~
SIReSDM24
SIReWTA
(optional)
SIReA1X
COM 2
BUS
ROOM
SIReDC
SIReRTX
(optional)
SIReOTX
SIReUA1
Advanced
15
Thermozone AD Corinte W - ADCS
SIReOTX
21 22
19 20
111213 1415 161718
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
Black
Grey
Red
RPM INDICATION
0-10V DC out (max 5 mA)
Black
Grey
Red
SDM24
1 2 3 4 5 6 7 8 9 10
COM 1
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
Black
Grey
Red
16
SIReWTA
(optional)
230V~
~
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
C1
X4
C2
Pot.
X5
Unit ID
SIReB1
C1
X4
C2
Pot.
X5
Unit ID
SIReB1
C2
Pot.
X5
Unit ID
SIReB1
C1
X4
ROOM
X3
ROOM
X3
~
~
ACTUATOR SUPPLY
N L L PE N L
ACTUATOR SUPPLY
N L L PE N L
230V~
230V~
ST23024
Black
Grey
Red
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
SDM24
SDM24
SIReA1X
COM 2
BUS
ROOM
SIReDC
SIReRTX
(optional)
SIReUA1
Advanced - parallell
Thermozone AD Corinte W - ADCS
AD Corinte W - ADCS Low temperature coil
Type
ADCS17
ADCS22
ADCS25
Type
ADCS17
ADCS22
ADCS25
Type
ADCS17
ADCS22
ADCS25
Type
ADCS17
ADCS22
ADCS25
In- / outlet water temperature 70/40 °C
Inlet air temp. +15 °C
Incoming air temp. +20 °C
Air temp. Water
Output
Air temp.
Water
Fan
Airflow Output
out
flow
flow
position
out
[l/s]
[kW]
[l/s]
[m3/h] [kW]
[°C]
[°C]
max
3000
21.8
36
0.17
18.5
38
0.14
min
1400
13.5
43
0.10
11.5
44
0.09
max
4000
30.7
37
0.24
26.2
39
0.20
min
1800
18.4
45
0.14
15.8
45
0.12
max
4500
35.1
38
0.27
30.0
39
0.23
min
2050
21.2
45
0.16
18.2
46
0.14
Incoming / outgoing water temperature 60/40 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp. Water
Fan
Airflow Output
flow
flow
position
out
out
[l/s]
[kW]
[l/s]
[m3/h] [kW]
[°C]
[°C]
max
3000
19.4
34
0.23
16.2
36
0.19
min
1400
12.0
40
0.14
10.1
41
0.12
max
4000
27.0
35
0.32
22.8
37
0.27
min
1800
16.1
41
0.19
13.7
42
0.16
max
4500
30.8
35
0.36
26.0
37
0.31
min
2050
18.5
42
0.22
15.7
43
0.18
Incoming / outgoing water temperature 60/30 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp.
Water
Fan
Airflow Output
out
flow
out
flow
position
[l/s]
[kW]
[°C]
[l/s]
[m3/h] [kW]
[°C]
max
3000
14.4
29
0.11
10.9
31
0.08
min
1400
9.2
34
0.07
7.1
35
0.05
max
4000
20.7
30
0.16
15.9
32
0.12
min
1800
12.8
36
0.10
10.0
36
0.07
max
4500
23.8
31
0.18
18.5
32
0.14
min
2050
14.8
36
0.11
11.6
37
0.09
Incoming / outgoing water temperature 55/35 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp.
Water
Fan
Airflow Output
out
flow
out
flow
position
[l/s]
[kW]
[°C]
[l/s]
[m3/h] [kW]
[°C]
max
3000
16.1
31
0.19
12.9
33
0.15
min
1400
10.0
36
0.11
8.1
37
0.09
max
4000
22.6
32
0.27
18.2
33
0.21
min
1800
13.6
37
0.16
11.1
38
0.13
max
4500
25.9
32
0.30
21.0
34
0.25
min
2050
15.7
38
0.18
12.8
38
0.15
17
Thermozone AD Corinte W - ADCS
AD Corinte W - ADCS High temperature coil
In- / outlet water temperature 130/65 °C
Inlet air temp. +15 °C
Incoming air temp. +20 °C
Air temp. Water
Output
Air temp.
Water
Type
Fan
Airflow Output
out
flow
flow
position
out
[l/s]
[kW]
[l/s]
[m3/h] [kW]
[°C]
[°C]
ADCS17
max
3000
30.8
45
0.11
28.6
48
0.10
min
1400
20.0
57
0.07
18.6
59
0.06
ADCS22
max
4000
42.8
46
0.15
39.7
49
0.14
min
1800
27.1
59
0.09
25.2
61
0.09
ADCS25
max
4500
48.8
47
0.17
45.3
49
0.16
min
2050
31.1
59
0.11
29.0
61
0.10
Type
ADCS17
ADCS22
ADCS25
Type
ADCS17
ADCS22
ADCS25
Type
ADCS17
ADCS22
ADCS25
18
Incoming / outgoing water temperature 90/70 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp.
Water
Fan
Airflow Output
flow
flow
position
out
out
[l/s]
[kW]
[l/s]
[m3/h] [kW]
[°C]
[°C]
max
3000
26.4
40
0.31
24.3
43
0.28
min
1400
16.8
50
0.20
15.4
52
0.18
max
4000
36.0
41
0.43
33.1
44
0.39
min
1800
22.3
51
0.26
20.6
53
0.24
max
4500
40.8
41
0.48
37.6
44
0.44
min
2050
25.5
51
0.30
23.5
53
0.28
Incoming / outgoing water temperature 82/71 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp.
Water
Fan
Airflow Output
out
flow
out
flow
position
[l/s]
[kW]
[°C]
[l/s]
[m3/h] [kW]
[°C]
max
3000
25.4
40
0.55
23.3
42
0.50
min
1400
16.0
48
0.34
14.7
51
0.31
max
4000
34.5
40
0.74
31.7
43
0.68
min
1800
21.2
49
0.46
19.5
51
0.42
max
4500
39.1
40
0.84
35.9
43
0.77
min
2050
24.2
49
0.52
22.2
52
0.48
Incoming / outgoing water temperature 80/60 °C
Incoming air temp. = +15 °C
Incoming air temp. = +20 °C
Air temp.
Water
Output
Air temp.
Water
Fan
Airflow Output
out
flow
out
flow
position
[l/s]
[kW]
[°C]
[l/s]
[m3/h] [kW]
[°C]
max
3000
22.0
36
0.26
19.9
39
0.23
min
1400
14.0
44
0.16
12.7
46
0.15
max
4000
30.1
37
0.35
27.3
40
0.32
min
1800
18.7
45
0.22
17.0
47
0.20
max
4500
34.2
37
0.40
31.0
40
0.36
min
2050
21.4
45
0.25
19.4
47
0.23
Thermozone AD Corinte W - ADCS
Technical specifications | Thermozone AD Corinte WL with water heat, coil for low tempered water < 80/60 °C  2
Type
Output*4 Airflow
∆t*3,4
Water Sound Output Voltage
volume level*5 motor motor
ADCS17WL*1
ADCS22WL
ADCS25WL*2
[kW]
33
46
52
[°C]
42/32
43/33
43/34
[l]
2,8
3,6
4,0
[m3/h]
1400/3000
1800/4000
2050/4500
[dB(A)]
39/59
42/60
42/61
[W]
670
990
1150
[V]
230V~
230V~
230V~
Amperage Length Weight
motor
[A]
2,9
4,3
5,0
[mm]
1700
2200
2450
[kg]
85
110
125
Technical specifications | Thermozone AD Corinte WH with water heat, coil for high tempered water ≥80/60 °C   2
Type
Output*4 Airflow
[kW]
1
ADCS17WH* 22
ADCS22WH
30
ADCS25WH*2 34
[m3/h]
1400/3000
1800/4000
2050/4500
∆t*3,4
Water Sound
volume level*5
[°C]
30/22
31/22
31/22
[l]
2,8
3,6
4,0
[dB(A)]
39/59
42/60
42/61
Output Voltage Amperage Length Weight
motor motor motor
[W]
670
990
1150
[V]
230V~
230V~
230V~
[A]
2,9
4,3
5,0
[mm]
1700
2200
2450
[kg]
85
110
125
*1) ADCS17 is available only for horizontal mounting.
*2) ADCS25 is available only for vertical mounting.
*3) Applicable at water temperature 80/60 °C, air temperature in + 15 °C.
*4) Dt= temperature rise of passing air at maximum heat output and lowest/highest airflow.
*5) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2.
Protection class: IP20.
CE compliant.
19
AD Corinte W - ADCS
GB
Mounting and operating instructions
General Instructions
Read these instructions carefully before
installation and use. Keep this manual for
future reference.
The guarantee is only valid if the units
are used in the manner intended by the
manufacturer and in accordance with the
Frico mounting and operating instructions.
Application
The Thermozone AD Corinte W - ADCS air
curtain is supplied with a water coil and is
intended for permanent installation above or
beside entrance doors and other openings up
to 3,5 metres in height. Protection class: IP20.
Operation
Air is drawn in at the top/rear of the unit and
blown out downwards/outwards so that it
shields the door opening and minimizes heat
loss. To achieve the optimum curtain effect
the unit must extend the full height/width of
the door opening.
The grille for directing exhaust air is
adjustable and is normally angled outwards to
achieve the best protection against incoming
cold air.
The efficiency of the air curtain depends
on the air temperature, pressure differences
across the doorway and any wind pressure.
NOTE! Negative pressure in the building
considerably reduces the efficiency of the air
curtain. The ventilation should therefore be
balanced.
Vertical mounting
The unit is mounted vertically on the floor
with the exhaust opening facing outwards.
Before installation, decide whether any
electrical connections or water connections
are to be made from below.
Leave the protective plastic in place during
installation. Take care to avoid damaging the
surfaces. For installation see Figure 4.
1.Remove the two screws that secure the
intake grille (A) and remove this.
2.Undo the screws holding the front panel (C)
on the exhuast side (B).
3.Undo the two screws in the front panel and
remove it.
4.Place the edging in level on the floor and
secure it through the countersunk holes
(see Fig. 7). Place the air curtain on the
edging.
5.A flat bar is included for securing the air
curtain. Fixate the air curtain through the
square-shaped hole. Make sure that the flat
bar is not bent when fixing.
6.Secure the top with an angle bracket or
similar to prevent the air curtain from
toppling over. There is a hole in the centre
of the top of the air curtain with an internal
M8 thread for securing the bracket.
7.Hook the front panel (C) onto the edge on
the intake side (A), close and press it into
the slot on the exhaust side (B).
8.Fasten the two screws in the front panel.
9.Secure the front panel on the exhaust side.
10. Replace the intake grille. (A)
To remove dirt and finger prints, polish the
panels with a suitable cleanser. Any print
that may be on the panels is removed with a
suitable solvent.
Horizontal mounting
The unit is mounted horizontally with the
outlet facing downwards. Do not remove
the protecting plastic until mounting is
completed. Be careful so the surfaces are not
damaged.
Mounting less than 180 mm from the ceiling
is not recommended since it will reduce the
flow through the unit.
Two brackets are delivered with the unit
for mounting on the wall or hanging from the
ceiling.
Horizontal mounting on the wall
1.Mount the brackets on the wall according to
measures in Fig. 6a and 6b.
2.Put the unit in place and lock it with an
hexagon key and the included M8 screws.
23
GB
AD Corinte W - ADCS
Horizontal mounting on the ceiling
1.Mount pendulums or similar (not included
on delivery) on the ceiling with c-c distance
according to Fig. 6a and 6b.
2.Mount the brackets on the unit with an
hexagon key and the included M8 screws.
3. Put the unit in place and fix the brackets to
the pendulums.
Note! The unit needs to be secured if hung
from wires.
Electrical installation
The installation, which should be preceded by
an omnipolar switch with a contact separation
of at least 3 mm, should only be wired by a
competent electrician and in accordance with
the latest edition of IEE wiring regulations.
The electrical connection may be done from
above or below when mounted vertically, and
from left or right when mounted horizontally,
according to ordering key. Control (230V~)
should be connected to a terminal block.
The control system is pre-installed in the
aircurtain with an integrated control card,
(see fig 8).
SIRe is supplied pre-programmed with
quick-release connections.
Modular cables are connected to the control
board Base, by opening the front plate, as
shown in Figure 4 and 5. See manual for SIRe.
Connection of water coil
The air curtain has a heating coil with copper
tubes suitable for connection to a closed
water heating system. The heating coil must
not be connected to a mains pressure water
system or an open water system.
The unit is connected from above or below
to Ø22 mm copperpipes, by compression
fitting or through welding the pipe work to the
unit.
The upper side of the heating coil is
equipped with ventilating valve in the unit.
The heating coil should be ventilated before
operation to prevent air locks.
When mounting the unit vertically, water
connection can be carried out from the top or
bottom. The connection from below can be
done the following way:
24
• Flexible hoses may be drawn through
drilled holes in the floor and connected to
the air curtain pipes. The flexible hoses are
connected to the system beneath the floor.
Note! At connection from below, avoid placing
hoses or pipes so that they obstruct the air
flow to the fans. If necessary, secure them to
avoid vibrations and prevent them from being
sucked into the fans.
When mounting the unit horizontally, water
connection can be carried out from the left
or right. The lid on the top side of the unit
is sliding to be adjustable to the water pipe
dimension. (see Fig 6a).
Adjustment of air flow
The direction and speed of the air flow
should be adjusted considering the load on
the opening. Compressive forces affect the
air stream and make it bend inwards into the
premises (when the premises are heated and
the outdoor air is cold). The air stream should
therefore be directed outwards to withstand
the load. (Generally speaking, the higher the
load, the bigger the angle needed.)
With an hexagon key, loosen the three
screws supporting the outlet grille. Angle the
grille outwards to obstruct the incoming cold
air.
Overheating
The over heat protection maintains the
exhaust temperature at +40 °C. If the
temperature should exceed anyway there is
an over heating alarm. For more information
see the manual for SIRe.
Maintenance
To ensure performance and reliability of the
air curtain inspection should be carried out
regularly, at least twice a year, but this can
vary depending on local conditions. This is to
secure the performance of the air curtain.
A clogged filter doesn’t present a risk, but
will reduce the efficiency of the air curtain.
The inlet grille works as a filter and should
be vacuumed regularly. The water battery
should be cleaned when necessary in the
following way:
1.Disconnect the power supply.
AD Corinte W - ADCS
GB
2.Loosen the two screws of the air intake
grille with a hexagon key and remove the
grille.
3.Carefully wipe the fins of the heating coil
with a wet cloth.
5.Remount the air intake grllle.
6.Connect the power.
Filter cassettes, that the unit may be
equipped with, cannot be cleaned but need to
be changed when they are soiled or when the
airflow is reduced. The basic filter is cleaned
with water and a gentle cleaning agent.
Since fan motors and other components are
maintenance free, no maintenance other than
cleaning is necessary, undertake cleaning at
least twice a year.
Safety
• Ensure that the area around the intake
and exhaust grille is kept free from
material wich could prevent the air to flow
through the unit!
• During operation the surfaces of the unit
are hot!
• This appliance is not intended for use by
persons (including children) with reduced
physical or mental capabilities, or lack
of experience and knowledge, unless they
have been given supervision or instruction
concerning use of the appliance by
a person responsible for their safety.
Children should be supervised to ensure
that they do not play with the appliance.
25
Tel: +46 31 336 86 00
Fax: +46 31 26 28 25
[email protected]
www.frico.se
For latest updated information and information
about your local contact: www.frico.se
Art nr: 208033, 2013-04-05 SA/HH
Main office
Frico AB
Box 102
SE-433 22 Partille
Sweden
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement