Carlo Gavazzi DUA01CD48500V 1-phase monitoring relay Data Sheet
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Monitoring Relays
1-Phase AC/DC Over Voltage - AC Over Current
Types DUA01, PUA01
DUA01 PUA01
• AC/DC over voltage monitoring relay
• Selection of measuring range by DIP-switches
• Measuring ranges: 2 to 20 VAC/DC, 5 to 50 VAC/DC,
20 to 200 VAC/DC, 50 to 500 VAC/DC, 0.4 to 4 V p
AC
• Adjustable voltage limit on relative scale
• Adjustable hysteresis
• Programmable latching at set level
• Output: 8 A SPDT relay normally de-energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DUA01) or plug-in module (PUA01)
• 22.5 mm Euronorm housing (DUA01) or
36 mm plug-in module (PUA01)
• LED indication for relay and power supply ON
• Galvanically separated power supply
Product Description
DUA01 and PUA01 are precise AC/DC over voltage monitoring relays. They can also be used as 1-phase or
3-phase over current monitoring relays when connected with MI or MP current transformers.
Owing to the built-in latch function, the ON-position of the relay output can be maintained.
The red LED indicates the alarm status.
Ordering Key
Housing
Function
Type
Item number
Output
Power supply
Range
DUA 01 C B23 500V
Type Selection
Mounting
DIN-rail
Plug-in
Output
SPDT
SPDT
Supply: 24 to 48 VAC/DC
DUA 01 C D48 500V
PUA 01 C D48 500V
Supply: 115/230 VAC
DUA 01 C B23 500V
PUA 01 C B23 500V
Input Specifications
Input (voltage level)
DUA01
PUA01
Measuring ranges
Direct
Selectable by DIP-switches
2 to 20 VAC/DC
5 to 50 VAC/DC
20 to 200 VAC/DC
50 to 500 VAC/DC
0.4 to 4 V p
AC
Max. voltage for 1 s
MI and MP CT ranges
1-ph.: 3-ph.:
MI 5 MP 3005
MI 20 MP 3020
MI 100 MP 3100
MI 500 MP 3500
Terminals Y1, Y2
Terminals 5, 7
Int. resist.
> 500 k
Ω
> 500 k
Ω
> 500 k
Ω
> 500 k
Ω
> 500 k
Ω
AAC rms
0.5 to 5 A
2 to 20 A
10 to 100 A
50 to 500 A
Max. volt.
600 V
600 V
600 V
600 V
600 V
1000 V
Max. curr.
20 AAC
50 AAC
250 AAC
750 AAC
Note:
The input voltage cannot raise over 300 VAC/DC with respect to ground (PUA01 only)
Contact input
DUA01
PUA01
Disabled
Enabled
Latch disable
Terminals Z1, Y1
Terminals 8, 9
> 10 k Ω
< 500 Ω
> 500 ms
Output Specifications
Output
Rated insulation voltage
SPDT relay
250 VAC
Contact ratings (AgSnO
2
)
Resistive loads AC 1
µ
8 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life
Electrical life
Operating frequency
≥ 30 x 10 6 operations
≥ 10 5 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Dielectric strength
Dielectric voltage
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (08.06.10) 1
DUA01, PUA01
Supply Specifications
Power supply
Rated operational voltage through terminals:
A1, A2 or A3, A2 (DUA01)
2, 10 or 11, 10 (PUA01)
Overvoltage cat. III
(IEC 60664, IEC 60038)
D48:
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
24 to 48 VAC/DC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
2 kV
4 kV
4 kV
AC supply
4 kV
4 kV
4 kV
4 VA
2 W
General Specifications
Reaction time
Alarm ON delay
Alarm OFF delay
< 100 ms
(voltage rising from
-20% to +20% set value)
< 300 ms
(voltage decreasing from
+20% to -20% set value)
General Specifications (cont.)
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Output relay ON
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full-scale
LED, green
LED, red
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing
Dimensions
Material
Weight
(EN 60529)
IP 20
3 (DUA01), 2 (PUA01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
DUA01 22.5 x 80 x 99.5 mm
PUA01 36 x 80 x 94 mm
PA66 or Noryl
Approx. 150 g
Screw terminals
Tightening torque Max. 0.5 Nm acc. to IEC 60947
Product standard
Approvals
CE Marking
EN 60255-6
UL, CSA
L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
EMC
Immunity
Emissions
According to EN 60255-26
According to EN 61000-6-2
According to EN 60255-26
According to EN 61000-6-3
Mode of Operation
DUA01 and PUA01 monitor both AC and DC over voltage. When connected with
MI or MP current transformer (using the 0.4 - 4 V p range) they can monitor 1phase or 3-phase AC currents up to 500 A.
Example 2 (MI CT)
(no connection between terminals Z1, Y1 or 8, 9)
The relay operates when the current flowing through the
CT exceeds the set level. It releases when the current drops min. 4% below the set level (see hysteresis) or when power supply is interrupted.
Example 1
(connection between terminals Z1, Y1 or 8, 9 - latch function enabled)
The relay operates and latches in operating position when the measured value exceeds the set level. Provided that the voltage has dropped min. 4% below the set point (see hysteresis), the relay releases when the interconnection between terminals Z1, Y1 or 8, 9 is interrupted or the power supply is interrupted as well.
Example 3 (MP CT)
(no connection between terminals Z1, Y1 or 8, 9 - latch function disabled)
The relay operates when the maximum current flowing through the CT exceeds the set level. It releases when the maximum current drops min. 4% below the set level
(see hysteresis) or when power supply is interrupted.
Range - Level Setting
Adjust the measuring range setting the DIP switches 1 to
4 as shown below.
To access the DIP switches open the grey plastic cover using a screwdriver as shown below.
Centre knob:
Setting of voltage on relative scale: from 10 to 110% of the full-scale value.
Hysteresis:
Approx. 4% of set value, it can be extended by inserting a resistor between terminals Z1, Y1 or 8, 9.
Approx. resistor values:
10%: 180 k
Ω
25%:
50%:
47 k
Ω
22 k
Ω
75%: 15 k
Ω
Latch: < 500
Ω
Measuring range
OFF ON OFF OFF 0.4 to 4 V p
ON OFF OFF OFF 2 to 20 VAC/DC
OFF OFF OFF OFF 5 to 50 VAC/DC
ON OFF ON OFF 20 to 200 VAC/DC
ON OFF OFF ON 50 to 500 VAC/DC
2 Specifications are subject to change without notice (08.06.10)
DUA01, PUA01
Operation Diagrams
Wiring Diagrams
24÷48 VAC/DC
230 VAC 115 VAC
24÷48 VAC/DC
230 VAC 115 VAC
24÷48 VAC/DC
230 VAC 115 VAC
24÷48 VAC/DC
230 VAC 115 VAC
24÷48 VAC/DC
230 VAC 115 VAC
DUA01
Specifications are subject to change without notice (08.06.10)
PUA01
24÷48 VAC/DC
230 VAC 115 VAC
3
DUA01, PUA01
Dimensions
DIN-rail
22.5
99.5
Plug-in
36
28.5
94
90
28.5
4 Specifications are subject to change without notice (08.06.10)