- Industrial & lab equipment
- Electrical equipment & supplies
- Danfoss
- VACON NXP Air cooled
- User manual
- 42 Pages
Danfoss VACON NXP Air cooled User manual
Below you will find brief information for AC drives OPTC2/C8. This manual provides information on how to connect the frequency converters to the RS-485 bus using a fieldbus board. The Vacon NX frequency converter can then be controlled, monitored and programmed from the host system.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
vacon nx ac drives optc2/c8 modbus/n2 option board user manual
1.
INDEX Document code: DPD00899A
Date 19.01.2012
GENERAL ........................................................................................................................... 3
2. RS-485 OPTION BOARD TECHNICAL DATA ........................................................................ 4
2.1 General ......................................................................................................................................... 4
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS ................................................... 5
3.1 RS-485 OPTC2 option board ......................................................................................................... 5
3.2 RS-485 OPTC8 option board ......................................................................................................... 6
3.3 Grounding ..................................................................................................................................... 7
3.3.1 Grounding by clamping the cable to the converter frame .................................................7
3.3.2 Grounding only one point on the net ..................................................................................9
3.3.3 Grounding jumper X1 ....................................................................................................... 10
3.4 Bus terminal resistors................................................................................................................ 11
3.5 Bus Biasing ................................................................................................................................. 12
3.6 LED indications ........................................................................................................................... 13
4. INSTALLATION OF VACON NX RS-485 BOARD ................................................................. 14
5. COMMISSIONING .............................................................................................................. 16
5.1 Fieldbus board parameters ........................................................................................................ 16
6. MODBUS ........................................................................................................................... 19
6.1 Modbus RTU protocol, introduction ............................................................................................ 19
6.1.1 Supported functions ......................................................................................................... 21
6.1.2 Exception responses ........................................................................................................ 23
6.2 Modbus interface ........................................................................................................................ 25
6.2.1 Modbus registers ............................................................................................................. 25
6.2.2 Process data .................................................................................................................... 25
6.2.3 Process data in ................................................................................................................ 26
6.2.4 Process data out .............................................................................................................. 27
6.2.5 Parameters ...................................................................................................................... 30
6.2.6 Actual values .................................................................................................................... 30
6.2.7 Example messages .......................................................................................................... 31
6.3 Start-up test ............................................................................................................................... 33
7. METASYS N2 ..................................................................................................................... 34
7.1 Metasys N2 Protocol Introduction .............................................................................................. 34
7.2 Metasys N2 interface .................................................................................................................. 34
7.2.1 Analogue Input (AI) .......................................................................................................... 34
7.2.2 Binary Input (BI) ............................................................................................................... 34
7.2.3 Analogue Output (AO)....................................................................................................... 35
7.2.4 Binary Output (BO) ........................................................................................................... 35
7.2.5 Internal Integer (ADI) ....................................................................................................... 35
7.3 N2 POINT MAP ............................................................................................................................ 36
7.3.1 Analogue Inputs (AI) ......................................................................................................... 36
7.3.2 Binary Inputs (BI) ............................................................................................................. 37
7.3.3 Analogue Outputs (AO) ..................................................................................................... 37
7.3.4 Binary Outputs (BO) ......................................................................................................... 38
7.3.5 Internal Integers (ADI) ..................................................................................................... 38
8. FAULT TRACKING ............................................................................................................. 39
APPENDIX 1 ............................................................................................................................................ 40
general vacon • 3
1. GENERAL
Instead of sending and receiving information to and from frequency converters through I/O, you can connect them to a fieldbus.
Vacon NX frequency converters can be connected to the RS-485 bus using a fieldbus board. The converter can then be controlled, monitored and programmed from the host system.
If you purchase your RS-485 Option Board separately, please note that it shall be installed in slot E on the control board of the frequency converter.
Internal components and circuit boards are at high potential when the frequency converter is connected to the power source. This voltage is extremely dangerous and may cause death or severe injury if you come into contact with it.
WARNING!
24-hour support +358 (0)40 8371 150 • Email: [email protected]
1
4 • vacon technical data
2. RS-485 OPTION BOARD TECHNICAL DATA
2.1 General
Connections
Communications
Environment
Interface
Data transfer method
OPTC2: Pluggable connector (5.08mm)
OPTC8: 9-pin DSUB connector (female)
RS-485, half-duplex
Transfer cable Twisted pair (1 pair and shield)
Electrical isolation 500 VDC
Modbus RTU
Metasys N2
As described in document “Modicon Modbus Protocol
Reference Guide”
Find it for example at: http://public.modicon.com/
As described in Metasys N2 System Protocol Specification
Baud rate
Addresses
Ambient operating temperature
Storing temperature
300, 600, 1200, 2400, 4800, 9600, 19200 and 38400 kbaud
1 to 247
–10°C…55°C
–40°C…60°C
Humidity
Altitude
Vibration
Safety
Table 1. RS-485 technical data
<95%, no condensation allowed
Max. 1000 m
0.5 G at 9…200 Hz
Fulfils EN50178 standard
2
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
layout and connections vacon • 5
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS
Vacon RS-485 Fieldbus Board is connected to the fieldbus through either a 5-pin pluggable bus connector (board OPTC2) or a 9-pin female sub-D-connector (board OPTC8).
The communication with the control board of the frequency converter takes place through the standard Vacon Interface Board Connector.
3.1 RS-485 OPTC2 option board
3
4
5
1
2
X4
X1
Bus connector Jumpers
Grounding plate
Figure 1. Vacon RS-485 option board OPTC2
Interface board connector
Signal
NC*
VP
Connector
1*
2
Description
No connection
Supply voltage – plus (5V)
RxD/TxD –N
RxD/TxD –P
3
4
Receive/Transmit data – A
Receive/Transmit data – B
DGND 5 Data ground (reference potential for VP)
*You can use this pin (1) to bypass the cable shield to the next slave
Table 2. OPTC2 bus connector signals
24-hour support +358 (0)40 8371 150 • Email: [email protected]
3
6 • vacon
3.2 RS-485 OPTC8 option board
5 4 3 2 1
9 8 7 6 layout and connections
X4
X1
Bus connector Jumpers
Grounding plate
Figure 2. Vacon RS-485 option board OPTC8
Interface board connector
Signal
Shield
RxD/TxD-N
DGND
VP
RxD/TxD-P
Connector
1
3
5
6
8
Description
Cable shield
Receive/ A
Data ground (reference potential for VP)
Supply voltage – plus (5V)
Receive/ Transmit data/ B
Table 3. OPTC8 bus connector signals
3
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
layout and connections vacon • 7
3.3 Grounding
3.3.1
Grounding by clamping the cable to the converter frame
This manner of grounding is the most effective and especially recommended when the distances between the devices are relatively short or if the device is the last device on the net.
Note: Normally, the option board has already been installed in slot D or slot E of the control board. It is not necessary to detach the whole board for the grounding of the bus cable shield. Just detach the terminal block.
1
Strip about 5 cm of the cable and cut off the grey cable shield.
Remember to do this for both bus cables (except for the last device). See pictures below.
2
Leave no more than 1 cm of the cable outside the terminal block and strip the data cables at about 0.5 cm to fit in the terminals. See pictures below.
Note: Do this for both bus cables.
Strip this part
Cut here
Figure 3.
1 2 3 4 5
A B
Figure 4.
3
Insert the data cables of both cables into terminals #3 (Line B) and #4 (Line A).
4
Strip the cable at such a distance from the terminal that you can fix it to the frame with the grounding clamp. See
24-hour support +358 (0)40 8371 150 • Email: [email protected]
3
8 • vacon
Figure 5. layout and connections
3
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
layout and connections vacon • 9
3.3.2
Grounding only one point on the net
In this manner of grounding, the shield is connected to ground only at the last device on the net in the
same way as described in chapter 3.3.1. Other devices of the net just pass the shield.
We recommend you to use an Abico connector to fit the shields into the terminal.
1
2
Strip about 5 cm of the cable and cut off the grey cable shield. Remember to do this for both bus cables (except for the last device).
Leave no more than 1 cm of the cable outside the terminal block and strip the data cables at
about 0.5 cm to fit in the terminals. See Figure 6.
Note: Do this for both bus cables.
1 2 3 4 5
Shield A
3
Figure 6.
Fix both the cables on the frame with the clamp. See Figure 7.
B
Figure 7.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
3
10 • vacon layout and connections
3.3.3
Grounding jumper X1
The Grounding jumper X1 on the OPTC8 is used for grounding selection. If position ON is selected it means that the D-sub connector PIN1 is connected directly to ground. Selection of position OFF means that PIN1 is connected to ground via an RC-filter. Jumper X1 has no effect on OPTC2.
5 4 3 2 1
9 8 7 6
ON
OFF
Figure 8. Grounding jumper X1
X4
X1
3
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
layout and connections vacon • 11
3.4 Bus terminal resistors
If Vacon is the last device of the fieldbus line the bus termination must be set. Use jumper X4 (ON po-
sition) or external termination resistors (e.g. in DSUB-9 connector). See Figure 9.
5 4 3 2 1
9 8 7 6
ON
OFF
X4
X1
Figure 9. Using jumper X4 to set the bus termination.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
3
12 • vacon layout and connections
3.5 Bus Biasing
Bus biasing is required to ensure faultless communication between devices at RS-485 bus. Bus biasing makes sure that the bus state is at proper potential when no device is transmitting. Without biasing, faulty messages can be detected when the bus is in idle state. RS-485 bus state should be neather +0,200..+7V or –0,200..-7V. Illegal bus state is <200mV..-200mV.
Number of nodes
2-5
Bias resistance
1.8 kohm
5-10
11-20
21-30
2.7 kohm
12 kohm
18 kohm
31-40 27 kohm
Table 4. Bias resistor size vs number of node
Fail safe biasing in OPTC2 option board
Connect resistor biasing resistors between pins #2 and #4 as well as pins #3 and #5 as shown in picture.
A
B
DATA-
DATA+
1
2
3
4
5
5
Matters related to this are discussed in the application note
Failsafe Biasing of Differential Buses
847.pdf) published by National Semiconductor ( www.national.com
).
(an-
3
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
layout and connections vacon • 13
3.6 LED indications
The two LED indications next to the connector show the present statuses of the RS-485 board (yellow) and the Fieldbus Module (green).
Yellow
Green
1
2
3
4
5
X4
X1
Figure 10. LED indications on the RS-485 board
RS-485 board status LED (BS) YELLOW
LED is:
OFF
ON
Blinking fast
(once/sec)
Blinking slow
(once/5 secs)
Meaning:
Option board not activated
Option board in initialisation state waiting for activation command from the frequency converter
Option board is activated and in RUN state
• Option board is ready for external communication
Option board is activated and in FAULT state
• Internal fault of option board
Fieldbus status LED (FS) GREEN
LED is:
OFF
ON
Meaning:
Fieldbus module is waiting for parameters from the frequency converter
• No external communication
Fieldbus module is activated
• Parameters received and module activated
• Module is waiting for messages from the bus
Module is activated and receiving messages from the bus Blinking fast
(once/sec)
Blinking slow
(once/5 secs)
Module is in FAULT state
• No messages from Master within the watchdog time
• Bus broken, cable loose or Master off line
24-hour support +358 (0)40 8371 150 • Email: [email protected]
3
4
14 • vacon
4. INSTALLATION OF VACON NX RS-485 BOARD
A Vacon NX frequency converter installation
B Remove the cable cover.
C Open the cover of the control unit.
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
installation vacon • 15
D Install RS-485 option board in slot E on the control board of the frequency converter. Make sure that the grounding plate (see below) fits tightly in the clamp.
1
2
3
4
5
X4
X1
E Make a sufficiently wide opening for your cable by cutting the grid as wide as necessary.
F Close the cover of the control unit and the cable cover.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
4
5
16 • vacon modbus
5. COMMISSIONING
READ FIRST CHAPTER 8 'COMMISSIONING' IN VACON NX USER'S MANUAL (Document nr. ud00701, please visit http://www.vacon.com/925.html
).
Note! You must select Fieldbus as the active control place, if you wish to control the frequency converter through fieldbus. See Vacon NX User’s Manual, Chapter 7.3.3.1.
5.1 Fieldbus board parameters
The Vacon RS-485 board is commissioned with the control keypad by giving values to appropriate parameters in menu M7 (for locating the expander board menu see Vacon NX User's Manual, Chapter
7).
Expander board menu (M7)
The
Expander board menu
makes it possible for the user 1) to see what expander boards are connected to the control board and 2) to reach and edit the parameters associated with the expander board.
Enter the following menu level (G#) with the slots A to E with the
Browser buttons
Menu button right
. At this level, you can browse through to see what expander boards are connected. On the lowermost line of the display you also see the number of parameter groups associated with the board.
If you still press the two groups: Editable parameters and Monitored values. A further press on the
RS-485 parameters
Menu button right
takes you to either of these groups.
once you will reach the parameter group level where there are
Menu button right
To commission the RS-485 board, enter the level P7.5.1.# from the
Parameters
desired values to all RS-485 parameters (see Figure 11 and Table 5).
group (G7.5.1). Give
READY
I/Oter m
Expander Board
G1
 G5
READY
I/Oter m
Slave address
126
I/Oter m
NXOPTC5
G1
READY

G2
READY
I/Oter m
Slave address
126
READY
I/Oter m
Parameters
P1

P4
CHANGE VALUE enter CONFIRM CHANGE
Figure 11. Changing the RS-485 board commissioning parameter values
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
commissioning vacon • 17
# Name
1 COMMUNICATION
PROTOCOL
2 SLAVE ADDRESS
3 BAUD RATE
4 PARITY TYPE
5 COMMUNICATION
TIMEOUT
6 OPERATE MODE
Table 5. RS-485 parameters
Default
1
1
6
0
20
1
Range
1 – Modbus RTU
2 – N2
1…247
1 – 300 baud
2 – 600 baud
3 – 1200 baud
4 – 2400 baud
5 – 4800 baud
6 – 9600 baud
7 – 19200 baud
8 – 38400 baud
0 – None
1 – Even
2 – Odd
0—OFF
1—300 s
1 – Normal
Description
Protocol
Communication speed
When N2 protocol is used must be set to 9600.
Baudrate
Describes what kind of parity checking is used. When N2-protocol is used Parity type must be set to 0 = None
See chapter Communication timeout
below
Reserved for later use
The parameters of every device must be set before connecting to the bus. Especially the parameters
Communication Protocol
,
Slave Address
and
Baud Rate
must be the same as in the master configuration.
Communication timeout
The RS-485 board initiates a communication error if communication is broken for as long as defined by the
Communication Timeout
.
Communication Timeout
is disabled when given the value 0.
Communication status
To see the present status of the RS-485 fieldbus, enter the
(G7.5.2). See Figure 12 and Table 6 below.
Comm.Status
page from
Monitor menu
READY
I/Oter m
Monitor
V1

V1
READY
I/Oter m
Comm. status
0.841
Good messages
Error messages
Figure 12. Communication status
24-hour support +358 (0)40 8371 150 • Email: [email protected]
5
18 • vacon
Good messages
0…999 Number of messages received without communication errors
0…64
Error messages
Number of messages received with
CRC or parity errors
Table 6. RS-485 message indications modbus
5
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 19
6. MODBUS
6.1 Modbus RTU protocol, introduction
The MODBUS protocol is an industrial communications and distributed control system to integrate
PLCs, computers, terminals, and other monitoring, sensing, and control devices. MODBUS is a Master-Slave communications protocol. The Master controls all serial activity by selectively polling one or more slave devices. The protocol provides for one master device and up to 247 slave devices on a common line. Each device is assigned an address to distinguish it from all other connected devices.
The MODBUS protocol uses the master-slave technique, in which only one device (the master) can initiate a transaction. The other devices (the slaves) respond by supplying the request data to the master, or by taking the action requested in the query. The master can address individual slaves or initiate a broadcast message to all slaves. Slaves return a message (‘response’) to queries that are addressed to them individually. Responses are not returned to broadcast queries from the master.
A transaction comprises a single query and single response frame or a single broadcast frame. The transaction frames are defined below.
Master's message
Slave response
START
ADDRESS
FUNCTION
DATA
CRC
END
START
ADDRESS
FUNCTION
DATA
CRC
END
Figure 13. The basic structure of a Modbus frame
Valid slave device addresses are in the range of 0 ... 247 decimal. The individual slave devices are assigned addresses in the range of 1 ... 247. A master addresses a slave by placing the slave address in the address field of the message. When the slave sends its response, it places its own address in this address field of the response to let the master know which slave is responding.
The function code field of a message frame contains two characters (ASCII) or eight bits (RTU). Valid codes are in the range of 1 ... 255 decimal. When a message is sent from a master to a slave device the function code field tells the slave what kind of action to perform. Examples are to read the ON /
OFF states of a group of discrete coils or inputs; to read the data contents of a group of registers; to
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
20 • vacon modbus read the diagnostic status of the slave; to write to designated coils or registers; or to allow loading, recording, or verifying the program within the slave.
When the slave responds to the master, it uses the function code field to indicate either a normal (error-free) response or that some kind of error occurred (called an exception response). For a normal response, the slave simply echoes the original function code. For an exception response, the slave returns a code that is equivalent to the original function code with its most significant bit set to a logic
1.
The data field is constructed using sets of two hexadecimal digits, in the range of 00 to FF hexadecimal. These can be made from a pair of ASCII characters, or from one RTU character, according to the network's serial transmission mode.
The data field of messages sent from a master to slave devices contains additional information which the slave must use to take the action defined by the function code. This can include items like discrete and register addresses, the quantity of items to be handled, and the count of actual data bytes in the field.
If no error occurs, the data field of a response from a slave to a master contains the data requested. If an error occurs, the field contains an exception code that the master application can use to determine the next action to be taken.
Two kinds of checksum are used for standard Modbus networks. The error checking field contents depend upon the transmission method that is being used.
6
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 21
6.1.1
Supported functions
Function Code Description
03
Address range
Read Holding Registers Applies to all addresses
04
06
Read Input Registers
Write Single Register
Applies to all addresses
Applies to all addresses
16 Write Multiple Registers
Applies to all addresses
Note: Broadcasting can be used with codes 06 and 16
Table 7. Supported messages
6.1.1.1
Read Holding Registers
The query message specifies the starting register and the quantity of registers to be read. Registers are addressed starting with zero, i.e. registers 1 to 16 are addressed as 0 to 15.
Example of a request to read registers 42001-42003 from Slave device 1:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of points HI
No. of points LO
CRC HI
CRC LO
01 hex
03 hex
07 hex
D0 hex
00 hex
03 hex
05 hex
46 hex
Slave address 1 hex (= 1)
Function 03 hex (= 3)
Starting address 07d0 hex (= 2000)
Number of registers 0003 hex (= 3)
CRC field 0546 hex (= 1350)
6.1.1.2
Read Input Registers
The query message specifies the starting register and the quantity of registers to be read. Registers are addressed starting with zero, i.e. registers 1 to 16 are addressed as 0 to 15.
Example of a request to read registers 32001 from Slave device 1:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of points HI
No. of points LO
CRC HI
CRC LO
01 hex
04 hex
07 hex
D0 hex
00 hex
01 hex
31 hex
47 hex
Slave address 1 hex (= 1)
Function 04 hex (= 4)
Starting address 07d0 hex (= 2000)
Number of registers 0003 hex (= 3)
CRC field 3147 hex (= 12615)
6.1.1.3
Preset Single Register
The query message specifies the register reference to be preset. Registers are addressed starting with zero, i.e. register 1 is addressed as 0.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
6
22 • vacon modbus
Example of a request to preset register 42001 to 00001hex in Slave device 1:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
Data HI
Data LO
CRC HI
CRC LO
01 hex Slave address 1 hex (= 1)
06 hex Function 04 hex (= 4)
07 hex
Starting address 07d0 hex (= 2000)
D0 hex
00 hex
Data = 0001 hex (= 1)
01 hex
48 hex CRC field 4887 hex (= 18567)
87 hex
6.1.1.4
Preset Multiple Registers
The query message specifies the register references to be preset. Registers are addressed starting with zero, i.e. register 1 is addressed as 0.
Example of a request to preset two registers starting at 42001 to 0001hex and 0010hex in Slave device
1:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of registers HI
No. of registers LO
Byte count
Data HI
Data LO
Data HI
Data LO
CRC HI
CRC LO
01 hex Slave address 1 hex (= 1)
10 hex Function 10 hex (= 16)
07 hex
Starting address 07d0 hex (= 2000)
D0 hex
00 hex Number of registers 0002 hex (= 2)
02 hex
04 hex Byte count 04 hex (= 4)
00 hex
Data 1 = 0001 hex (= 1)
01 hex
00 hex
Data 2 = 0010 hex (= 16)
10 hex
88 hex CRC field 88CF hex (= 35023)
CF hex
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 23
6.1.2
Exception responses
Error response is given when the Slave receives a message without communication errors, but cannot handle it. Examples of such messages are an incorrect register address, data value or unsupported message. No answer is given if a CRC or parity error occurs or the message is a broadcast message.
Code Function
01 ILLEGAL FUNCTION
Description
The message function requested is not recognized by the slave.
02 ILLEGAL DATA AD-
DRESS
The received data address is not an allowable address for the slave
03
06
ILLEGAL DATA VALUE
SLAVE DEVICE BUSY
The received data value is not an allowable value for the slave.
The message was received without error but the slave was engaged in processing a long duration program command.
Table 8. Exception response codes
Example of an exception response
In an exception response, the Slave sets the most-significant bit (MSB) of the function code to 1. The
Slave returns an exception code in the data field.
Command Master – Slave:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of registers HI
No. of registers LO
CRC HI
CRC LO
01 hex Slave address 1 hex (= 1)
04 hex Function 4 hex (= 4)
17 hex Starting address 1770 hex (= 6000)
70 hex
00 hex Invalid number of registers 0005 hex (= 5)
05 hex
34 hex
66 hex CRC field 3466 hex (= 13414)
Message frame:
01 04 17 70 00 05 34 66
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
24 • vacon
Exception response.
Answer Slave – Master:
ADDRESS
FUNCTION
ERROR CODE
ERROR
CHECK
CRC HI
CRC LO
Reply frame:
01 14 02 AE C1
01 hex Slave address 1 hex (= 1)
14 hex Most significant bit set to 1
02 hex Error code 02 => Illegal Data Address
AE hex CRC field AEC1 hex (= 44737)
C1 hex modbus
6
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 25
6.2 Modbus interface
Features of the Modbus-Vacon NX interface:
• Direct control of Vacon NX ( e.g. Run, Stop, Direction, Speed reference, Fault reset)
• Full access to all Vacon NX parameters
• Monitor Vacon NX status (e.g. Output frequency, Output current, Fault code)
6.2.1
Modbus registers
The Vacon variables and fault codes as well as the parameters can be read and written from Modbus.
The parameter addresses are determined in the application. Every parameter and actual value have been given an ID number in the application. The ID numbering of the parameter as well as the parameter ranges and steps can be found in the application manual in question. The parameter value shall be given without decimals. If several parameters/actual values are read with one message, the adresses of the parameters/actual values must be consecutive.
All values can be read with function codes 3 and 4 (all registers are 3X and 4X reference). Modbus registers are mapped to drive ID’s as follows:
ID
1 … 98
99
101… 1999
2001…2099
2101…2199
Table 9. Index table
Modbus register Group
40001…40098 (30001…30098) Actual Values
40099 (30099) Fault Code
40101…41999 (30101…31999) Parameters
42001…42099 (32001…32099) Process Data In
42101…42199 (32101…32199) Process Data Out
R/W
30/1
30/1
30/1
20/20
20/20
6.2.2
Process data
The process data fields are used to control the drive (e.g. Run, Stop , Reference, Fault Reset) and to quickly read actual values (e.g. Output frequency, Output current, Fault code). The fields are structured as follows:
Process Data Slave -> Master (max 22 bytes)
ID Modbus register Name
2101 32101, 42101 FB Status Word
2102 32102, 42102
2103 32103, 42103
Range/Type
Binary coded
FB General Status Word Binary coded
FB Actual Speed 0…10000 %
2104 32104, 42104
2105 32105, 42105
2106 32106, 42106
2107 32107, 42107
FB Process Data Out 1
FB Process Data Out 2
FB Process Data Out 3
FB Process Data Out 4
See appendix 1
See appendix 1
See appendix 1
See appendix 1
2108 32108, 42108
2109 32109, 42109
2110 32110, 42110
2111 32111, 42111
FB Process Data Out 5
FB Process Data Out 6
FB Process Data Out 7
FB Process Data Out 8
See appendix 1
See appendix 1
See appendix 1
See appendix 1
Table 10.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
6
26 • vacon modbus
Process Data Master -> Slave (max 22 bytes)
ID Modbus register Name
2001 32001, 42001 FB Control Word
2002 32002, 42002
2003 32003, 42003
2004 32004, 42004
2005 32005, 42005
FB General Control Word
FB Speed Reference
FB Process Data In 1
FB Process Data In 2
Range/Type
Binary coded
Binary coded
0…10000 %
Integer 16
Integer 16
2006 32006, 42006
2007 32007, 42007
2008 32008, 42008
2009 32009, 42009
2010 32010, 42010
2011 32011, 42011
FB Process Data In 3
FB Process Data In 4
FB Process Data In 5
FB Process Data In 6
FB Process Data In 7
FB Process Data In 8
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Table 11.
The use of process data depends on the application. In a typical situation, the device is started and stopped with the ControlWord (CW) written by the Master and the Rotating speed is set with Reference (REF). With PD1…PD8 the device can be given other reference values (e.g. Torque reference).
With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value (ACT) and PD1…PD8 show the other actual values.
6.2.3
Process data in
This register range is reserved for the control of the frequency converter.
Process data in
range ID 2001…2099. The registers are updated every 10 ms. See Table 12.
is located in
ID Modbus register
2001 32001, 42001
2002 32002, 42002
2003 32003, 42003
2004 32004, 42004
2005 32005, 42005
2006 32006, 42006
2007 32007, 42007
2008 32008, 42008
2009 32009, 42009
2010 32010, 42010
2011 32011, 42011
Table 12. Fieldbus basic input table
Name
FB Control Word
FB General Control Word
FB Speed Reference
FB Process Data In 1
FB Process Data In 2
FB Process Data In 3
FB Process Data In 4
FB Process Data In 5
FB Process Data In 6
FB Process Data In 7
FB Process Data In 8
Range/Type
Binary coded
Binary coded
0…10000 %
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Integer 16
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 27
6.2.3.1
Control word
15
-
14
-
13
-
12
-
11
-
10
-
9
-
8
-
7
-
6
-
5
-
4
-
3
-
2 1 0
RST DIR RUN
In Vacon applications, the three first bits of the control word are used to control the frequency converter. However, you can customise the content of the control word for your own applications because the control word is sent to the frequency converter as such.
Bit
Value = 0
0
1
2
3….15
Table 13. Control word bit descriptions
Description
Value = 1
Stop
Clockwise
Run
Counterclockwise
Rising edge of this bit will reset active fault
Not in use Not in use
6.2.3.2
Speed reference
15
MSB
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
LSB
This is the Reference 1 to the frequency converter. Used normally as Speed reference.
The allowed scaling is –10000...10000. In the application, the value is scaled in percentage of the frequency area between the set minimum and maximum frequencies.
6.2.3.3
Process data in 1 to 8
Process Data In values 1 to 8 can be used in applications for various purposes. Update rate is 10 ms for all values. See Vacon NX Application Manual for usage of these data values.
6.2.4
Process data out
This register range is normally used to fast monitoring of the frequency converter. located in range ID 2101…2199. See Table 14.
Process data out
is
ID
2101
2102
Modbus register Name
32101, 42101 FB Status Word
32102, 42102 FB General Status Word
Range/Type
Binary coded
Binary coded
2103
2104
2105
2106
2107
2108
2109
2110
2111
32103, 42103
32104, 42104
32105, 42105
32106, 42106
32107, 42107
32108, 42108
32109, 42109
32110, 42110
32111, 42111
Table 14. Fieldbus basic output table
FB Actual Speed
FB Process Data Out1
FB Process Data Out2
FB Process Data Out3
FB Process Data Out4
FB Process Data Out5
FB Process Data Out6
FB Process Data Out7
FB Process Data Out8
0…10000 %
See appendix 1
See appendix 1
See appendix 1
See appendix 1
See appendix 1
See appendix 1
See appendix 1
See appendix 1
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
6
28 • vacon modbus
6.2.4.1
Status word
15
-
14
-
13
-
12
-
11 10
- UVFS
9
DDI
R
8
TCSPDL
7
FR
6
Z
5
ARE
F
4
W
3 2 1 0
FLT DIR RUN RDY
Information about the status of the device and messages is indicated in the
Status word
. The
Status word
is composed of 16 bits that have the following meanings:
Bit
0
5
6
7
8
1
2
3
4
9
10
11...15
Value = 0
Not Ready
-
-
STOP
Clockwise
Ref. frequency not reached
-
Flux Not Ready
TC Speed Limit Active
Detected Encoder Direction Clockwise
UV Fast Stop Active
Not In use
Table 15. Status word bit descriptions
Description
Value = 1
Ready
RUN
Counterclockwise
Faulted
Warning
Ref. Frequency reached
Motor is running at zero speed
Flux Ready
TC Speed Limit Not Active
Encoder Direction Counterclockwise
UV Fast Stop Not Active
Not In use
6.2.4.2
General status word
15 14
I/O PANEL
13
FB
12
-
11 10
- -
9
-
8
-
7
-
Bit
0...12
13
14
15
Not in use
Description
Fieldbus control, (1 = FB control active)
Panel control, (1 = Panel control active)
I/O Control, (1 = I/O control active)
Table 16. General status word bit descriptions
6
-
5
-
4
-
3
-
2
-
1
-
0
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 29
6.2.4.3
Actual speed
15
MSB
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
LSB
This is the reference 1 to the frequency converter. Used normally as Speed reference.
The allowed scaling is –10000...10000. In the application, the value is scaled in percentage of the frequency area between set minimum and maximum frequency.
6.2.4.4
Process data out 1 to 8
Process Data Out values 1 to 8 can be used in application for various purposes. Update rate is 10ms
for all values. See APPENDIX 1 for usage of these values.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
30 • vacon modbus
6.2.5
Parameters
The parameter addresses are determined in the application. Every parameter has been given an ID number in the application. The ID numbering of the parameter as well as the parameter ranges and steps can be found in the application manual in question. The parameter value shall be given without decimals. The following functions can be activated with parameters:
Function code Function
03
04
06
16
Read Holding Registers
Read Input Registers
Preset Single Register
Preset Multiple
Registers
Modbus Address
30101…31999
40101…41999
40101…41999
40101…41999
Parameter ID’s
101-1999
101-1999
101-1999
101-1999
Table 17. Parameters
6.2.6
Actual values
The actual values as well as parameter addresses are determined in the application. Every actual value has been given an ID number in the application. The ID numbering of the actual values as well as the value ranges and steps can be found in the application manual in question. The following functions can be activated with parameters:
Function code Function
03 Read Holding Registers
Actual values
30001-30098
04 Read Input Registers 40001-40098
Table 18. Actual values
6
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 31
6.2.7
Example messages
Example 1
Write the process data 42001…42003 with command
Command Master – Slave:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of registers HI
No. of registers LO
Byte count
Data HI
Data LO
Data HI
Data LO
Data HI
Data LO
CRC HI
CRC LO
16
(Preset Multiple Registers).
01 hex Slave address 1 hex (= 1)
10 hex Function 10 hex (= 16)
07 hex
Starting address 07d0 hex (= 2000)
D0 hex
00 hex Number of registers 0003 hex (= 3)
03 hex
06 hex Byte count 06 hex (= 6)
00 hex
Data 1 = 0001 hex (= 1). Setting con-
01 hex
00 hex Data 2 = 0000 hex (= 0). General con-
00 hex trol word 0.
13 hex Data 3 = 1388 hex (= 5000), Speed Reference to
88 hex 50.00%
C8 hex CRC field C8CB hex (= 51403)
CB hex trol word run bit to 1.
Message frame:
01 10 07 D0 00 03 06 00 01 00 00 13 88 C8 CB
The reply to Preset Multiple Registers message is the echo of 6 first bytes.
Answer Slave – Master:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of registers HI
No. of registers LO
CRC HI
CRC LO
01 hex
10 hex
07 hex
D0 hex
00 hex
03 hex
F1 hex
01 hex
Slave address 1 hex (= 1)
Function 10 hex (= 16)
Starting address 07d0 hex (= 2000)
Number of registers 0003 hex (= 3)
CRC F101 hex (= 61697)
Reply frame:
01 10 07 D0 00 03 F1 01
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
6
32 • vacon modbus
Example 2
Read the Process Data 42103…42104 with command
4
(Read Input Registers) .
Command Master – Slave:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Starting ddress HI
Starting address LO
No. of registers HI
No. of registers LO
CRC HI
CRC LO
01 hex Slave address 1 hex (= 1)
04 hex Function 4 hex (= 4)
08 hex Starting address 0836 hex (= 2102)
36 hex
00 hex Number of registers 0002 hex (= 2)
02 hex
93 hex
A5 hex CRC field B321 hex (= 45857)
Message frame:
01 04 08 36 00 02 93 A5
The reply to the Read Input Registers message contains the values of the read registers.
Answer Slave – Master:
ADDRESS
FUNCTION
DATA
ERROR
CHECK
Byte count
Data HI
Data LO
Data HI
Data LO
CRC HI
CRC LO
01 hex
04 hex
02 hex
13 hex
88 hex
09 hex
C4 hex
F0 hex
E9 hex
Slave address 1 hex (= 1)
Function 4 hex (= 4)
Byte count 4 hex (= 4)
Speed reference = 1388 hex (=5000 => 50.00%)
Output Frequency = 09C4 hex (=2500 =>25.00Hz)
CRC field B321 hex (= 45857)
Reply frame:
01 04 02 13 88 09 C4 F0 E9
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
modbus vacon • 33
6.3 Start-up test
Frequency converter application
Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NX User's Manual, Chapter
7.3.3).
Master software
1. Set
2. Frequency converter status is RUN.
3. Set
5. Set
FB Control Word
FB Speed Reference
4. The Actual value is 5000 and the frequency converter output frequency is 25,00 Hz.
FB Control Word
(MBaddr 42001) value to 1hex.
(MBaddr 42003) value to 5000 (=50,00%).
(MBaddr 42001) value to 0hex.
6. Frequency converter status is STOP.
If FB Status Word (Addr 42101) bit 3 = 1 Status of frequency converter is FAULT.
24-hour support +358 (0)40 8371 150 • Email: [email protected]
6
7
34 • vacon metasys n2
7. METASYS N2
7.1 Metasys N2 Protocol Introduction
The N2 communications protocol is used by Johnson Controls and others to connect terminal unit controllers to supervisory controllers. It is open to any manufacturer and based upon a simple ASCII protocol widely used in the process control industry.
The physical characteristics of the N2 bus are three wire RS-485 with a maximum of 100 devices over a 4,000 foot distance running at 9,600 bps. Logically, the N2 is a master-slave protocol, the supervisory controller normally being the master. Data is partitioned into common HVAC control objects, such as analogue input, analogue output, binary input and binary output. N2 messaging supports the reading, writing and overriding of these points. Additionally, there are messages defined to perform uploads and downloads of devices as well as direct memory reads and writes.
7.2 Metasys N2 interface
Features of the N2 Interface:
• Direct control of Drive ( e.g. Run, Stop, Direction, Speed reference, Fault reset)
• Full access to necessary parameters
• Monitor Drive status (e.g. Output frequency, Output current, Fault code )
• In standalone operation, or should the polling stop, the overridden values are released after a specified period (about 10 minutes).
7.2.1
Analogue Input (AI)
All Analogue Input (AI) points have the following features:
• Support Change of State (COS) reporting based on high and low warning limits.
• Support Change of State (COS) reporting based on high and low alarm limits.
• Support Change of State (COS) reporting based on override status.
• Always considered reliable and never out of range.
• Writing of alarm and warning limit values beyond the range that can be held by the drive’s internal variable will result in having that limit replaced by the “Invalid Float” value even though the message is acknowledged. The net result will be the inactivation of the alarm or warning
(the same as if the original out of range value was used).
• Overriding is supported from the standpoint that the “Override Active” bit will be set and the value reported to the N2 network will be the overridden value. However, the value in the drive remains unchanged. Therefore, the N2 system should be set up to disallow overriding AI points or have an alarm condition activated when an AI point is overridden.
• Overriding an AI point with a value beyond the limit allowed by the drive’s internal variable will result in an “Invalid Data” error response and the override status and value will remain unchanged.
7.2.2
Binary Input (BI)
All Binary Input (BI) points have the following features:
• Support Change of State (COS) reporting based on current state.
• Support Change of State (COS) reporting based on alarm condition.
• Support Change of State (COS) reporting based on override status.
• Always considered reliable.
Overriding is supported from the standpoint that the “Override Active” bit will be set and the value reported to the N2 network will be the overridden value. However, the value in the drive remains un-
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
metasys n2 vacon • 35 changed. Therefore, the N2 system should be set up to disallow overriding BI points or have an alarm condition activated when a BI point is overridden.
7.2.3
Analogue Output (AO)
All Analogue Output (AO) points have the following features:
• Support Change of State (COS) reporting based on override status.
• Always considered reliable.
• Overriding of the AO points is the method used to change a value. Overriding an AO point with a value beyond the limit allowed by the drive’s internal variable will result in an ”Invalid Data” error response and the override status and value will remain unchanged. If the overridden value is beyond the drive’s parameter limit but within the range that will fit in the variable, an acknowledge response is given and the value will be internally clamped to its limit.
• An AO point override copies the override value to the corresponding drive parameter. This is the same as changing the value on the keypad. The value is non-volatile and will remain in effect when the drive is turned off and back on. It also remains at this value when the N2 network "releases" the point. The N2 system always reads the current parameter value.
Note:
On some N2 systems, the system will not poll the AO point when it is being overridden. In this case, the N2 system will not notice a change in value if the change is made with the keypad. To avoid this, set the point up as a ”local control” type and release it once it has been overridden. In this way, the N2 system will monitor the value when not being overridden.
7.2.4
Binary Output (BO)
All Binary Output (BO) points have the follwoing features:
• Support Change of State (COS) reporting based on override status.
• Always considered reliable.
• Overriding BO points control the drive. These points are input commands to the drive. When released, the drive's internal value remains at its last overridden value.
7.2.5
Internal Integer (ADI)
All Internal Integer (ADI) points have the follwoing features:
• Do not support Change of State (COS) reporting.
• Can be overridden and the ”Override Active” bit will be set. However, the Internal value is unchanged (Read Only).
24-hour support +358 (0)40 8371 150 • Email: [email protected]
7
7
36 • vacon metasys n2
7.3 N2 POINT MAP
7.3.1
Analogue Inputs (AI)
AI
AI
AI
AI
AI
AI
NPT NPA Description
AI 1 Speed Setpoint
AI 2 Output Speed
AI
AI
AI
3
4
5
Motor Speed
Load (power)
Megawatt Hours
AI
AI
AI
AI
6
7
8
9
10
11
12
13
14
15
Motor Current
Bus Voltage
Motor Volts
Heatsink Temperature ° C
Motor Torque %
Operating Days (trip) Day
Operating Hours (trip)
Kilowatt Hours (trip)
Torque Reference 1)
Motor Temperature
Rise 1)
Units
Hz
Hz
Rpm
%
MWh
A
V
V
Hour kWh
%
%
AI
AI
AI
AI
AI
AI
AI
AI
16
17
18
19
20
21
22
23
FBProcessDataOut1
FBProcessDataOut2
FBProcessDataOut3
FBProcessDataOut4
FBProcessDataOut5
FBProcessDataOut6
FBProcessDataOut7
FBProcessDataOut8
2)
2)
2)
2)
2)
2)
2)
2)
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
-32768 to
+32767
Table 19.
Note
2 decimals
2 decimals
0 decimal
1 decimal
Total Counter
2 decimal
0 decimal
1 decimal
0 decimal
1 decimal
0 decimal
0 decimal
Trip Counter
1 decimal
1 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
1) Torque Reference (AI-14) and Motor Temperature Rise (AI-15) NOT supported in NXL
2) These analogue inputs are application specific.
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
metasys n2
7.3.2
7.3.3 vacon • 37
Binary Inputs (BI)
BI
BI
BI
BI
BI
BI
BI
NPT NPA Description
BI
BI
BI
BI
1
2
3
4
Ready
Run
Direction
Faulted
BI
BI
BI
BI
5
6
7
8
9
10
11
12
13
14
15
Table 20.
Warning
Ref. Frequency reached
General 0
General 1
General 2
General 3
3)
3)
3)
3)
General 4 3)
General 5 3)
General 6
General 7
3)
3)
0 =
Not Ready
Stop
Clockwise Counterclockwise
Not Faulted Faulted
Not Warning
False
Motor running zero speed False
0
0
0
0
0
0
0
0
1 =
Ready
Run
Warning
True
True
1
1
1
1
1
1
1
1
3) These binary inputs are application specific. They are read from the drives General Status
Word.
Analogue Outputs (AO)
NPT NPA Description
AO
AO
1
2
Comms Speed
Current Limit
AO
AO
AO
AO
AO
AO
AO
3
4
5
6
7
8
9
AO 10
Table 21.
Units
%
A
Minimum Speed
Maximum Speed
Accel Time
Decel Time
Hz
Hz s s
FBProcessDataIN 1 4)
FBProcessDataIN 2 4)
-32768 to +32767
-32768 to +32767
FBProcessDataIN 3 4) -32768 to +32767
FBProcessDataIN 4 4) -32768 to +32767
4) These Analogue Outputs are application specific.
Note
2 decimals
2 decimals
2 decimals
2 decimals
1 decimal
1 decimal
2 decimals
2 decimals
2 decimals
2 decimals
24-hour support +358 (0)40 8371 150 • Email: [email protected]
7
38 • vacon
7.3.4
7.3.5
Binary Outputs (BO)
BO
BO
BO
BO
BO
BO
BO
NPT NPA Description
BO
BO
BO
BO
1
2
3
4
Comms Start/Stop
Comms Forward/Reverse
0 =
Stop
Forward
Reset Fault N/A
FBFixedControlWord Bit_3 5) -
5
6
7
8
9
10
11
FBFixedControlWord Bit_4 5)
FBFixedControlWord Bit_5 5)
FBFixedControlWord Bit_6
5)
5)
FBFixedControlWord Bit_7 5)
FBFixedControlWord Bit_8 5)
FBFixedControlWord Bit_9 5)
FBFixedControlWord Bit_10
-
-
-
-
-
-
-
BO
BO
12
13
FBFixedControlWord Bit_11
5)
FBFixedControlWord Bit_12
5)
-
-
BO 14
-
BO
BO
15
16
FBFixedControlWord Bit_13
5)
FBFixedControlWord Bit_14
5)
FBFixedControlWord Bit_15
5)
-
-
Table 22.
5) These Binary Outputs are application specific.
Internal Integers (ADI)
NPT NPA
ADI 1
Table 23.
Description
Active Fault Code
Units
-
-
-
-
-
-
-
-
-
-
-
-
1 =
Start
Reverse
Reset
-
- metasys n2
7
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
metasys n2 vacon • 39
8. FAULT TRACKING
The table below presents the faults related to the RS-485 option board. For more information, see also Vacon NX User's Manual, Chapter 9.
The RS-485 option board status LEDs have been described in more detail in Chapter 3.6.
Correcting measures Fault code
Fault Possible cause
37 Device change Option board changed.
38 Device added Option board added.
39 Device removed Option board removed.
40 Device unUnknown option board. known
53 Fieldbus fault The data connection between the Modbus/
N2 Master and the RS-485 option board is broken
54 Slot fault Defective option board or slot
Reset
Reset
Reset
Check the installation.
If installation is correct contact the nearest Vacon distributor.
Check the board and slot.
Contact the nearest Vacon distributor.
Table 24. RS-485 option board faults
You can define with parameters how the frequency converter shall react to certain faults:
Code Parameter Min Max Unit Step Default ID
P2.7.23
Response to slot fault
0
0
3
3
1
1
0
0
733
734
Note
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
Table 25. Frequency converter responses to faults
24-hour support +358 (0)40 8371 150 • Email: [email protected]
7
7
40 • vacon metasys n2
APPENDIX 1
Process Data OUT (Slave to Master)
The Fieldbus Master can read the frequency converter’s actual values using process data variables.
Basic, Standard, Local/Remote Control, Multi-Step Speed Control, PID control and Pump and fan control
applications use process data as follows:
ID
2104
2105
2106
2107
2108
2109
2110
2111
Data Value
Process data OUT 1 Output Frequency
Process data OUT 2 Motor Speed
Process data OUT 3 Motor Current
Process data OUT 4 Motor Torque
Process data OUT 5 Motor Power
Process data OUT 6 Motor Voltage
Process data OUT 7 DC link voltage
Process data OUT 8 Active Fault Code
Table 26. Process data OUT variables
Unit Scale
Hz 0,01 Hz rpm 1 rpm
A
%
%
V
V
-
0,1 A
0,1 %
0,1 %
0,1 V
1 V
-
The
Multipurpose Control application
has a selector parameter for every Process Data. The monitoring values and drive parameters can be selected using the ID number (see NX All in One Application
Manual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master to Slave)
ControlWord, Reference and Process Data are used with All-inOne applications as follows:
Basic, Standard, Local/Remote Control and Multi-Step Speed Control applications
ID
2003
2001
2004–2011
Table 27.
Data
Reference
Value
Speed Reference
ControlWord Start/Stop Command
Fault reset Command
PD1 – PD8 Not used
Unit Scale
% 0.01%
- -
- -
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
metasys n2
Multipurpose Control application
ID
2003
2001
2004
2005
2006–2011
Table 28.
Data
Reference
Value
Speed Reference
ControlWord Start/Stop Command
Fault reset Command
-
Process Data IN1 Torque Reference %
Process Data IN2 Free Analogia INPUT %
PD3 – PD8 Not Used -
Unit Scale
% 0.01%
-
0.1%
0.01%
-
PID control and Pump and fan control applications
ID
2003
2001
2004
2005
2006
2007–2011
Table 29
Data
Reference
Value
Speed Reference
ControlWord Start/Stop Command
Fault reset Command
Process Data IN1 Reference for PID controller
Process Data IN2 Actual Value 1 to PID controller
Process Data IN3 Actual Value 2 to PID controller
PD4–PD8 Not Used
Unit Scale
% 0.01%
- -
%
%
%
-
0.01%
0.01%
0.01%
- vacon • 41
24-hour support +358 (0)40 8371 150 • Email: [email protected]
7
Find your nearest Vacon office on the Internet at: www.vacon.com
Manual authoring: [email protected]
Vacon Plc.
Runsorintie 7
65380 Vaasa
Finland
Subject to change without prior notice
© 2012 Vacon Plc.
Document ID:
Rev. A
advertisement
Key Features
- RS-485 communication
- Modbus RTU protocol support
- Metasys N2 protocol support
- Control and monitoring from host system
- Pluggable connector (OPTC2)
- 9-pin DSUB connector (OPTC8)
- LED indications for status and errors
- Grounding options for cable shield
- Bus termination options