Condair ME Control Adiabatic air humidification/air cooling system Operation Manual

Condair ME Control Adiabatic air humidification/air cooling system Operation Manual

Below you will find brief information for Adiabatic air humidification/air cooling system ME Control. The Condair ME Control is a system for humidifying and cooling air in AHU's or air ducts. It features a touch screen control unit, evaporative cassettes, and a hydraulic module. The system can be equipped with a variety of options, including droplet separators, evaporative module blanking, and remote operation and fault indication. The Condair ME Control is designed for use in a variety of applications, including commercial buildings, industrial plants, and data centers.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Condair ME Control Operation Manual | Manualzz
2577874 EN 1412
READ AND SAVE THESE INSTRUCTIONS
OPERATION MANUAL
Adiabatic air humidification/air cooling system
Condair ME Control
Humidification and Evaporative Cooling
Thank you for choosing Condair
Installation date (MM/DD/YYYY):
Commissioning date (MM/DD/YYYY):
Location ref.:
Model:
Serial number:
Manufacturer
Condair Plc
Artex Avenue, Rustington,
Littlehampton, West Sussex.
BN16 3LN (UK)
TEL: +44(0)1903 850 200
FAX: +44(0)1903 850 345
www.condair.co.uk
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Plc. Neither this document, nor
the information contained herein shall be reproduced, used, or disclosed to others without the written authorization
of Condair Plc, except to the extent required for installation or maintenance of recipient's equipment.
Liability Notice
Condair Plc does not accept any liability due to incorrect installation or operation of the equipment or due to the
use of parts/components/equipment that are not authorized by Condair Plc.
Copyright Notice
Copyright 2014, Condair Plc All rights reserved.
Technical modifications reserved
Contents
1
1.1
1.2
Introduction5
General
5
Notes on the operation manual
5
2
For your safety
3
3.1
3.2
3.3
3.3.1
3.3.2
3.4
3.4.1
3.4.2
Product Overview
Model overview
Product designation / Which model do you have
Construction of the system components
Construction of the evaporative module
Construction of the hydraulic module
System overviews / Functional description
Typical system Condair ME Control (internally mounted)
Typical system Condair ME Control (externally mounted)
7
10
10
11
12
12
13
14
14
15
4Operation
4.1
Important notes on operation
4.2
Initial commissioning
4.3
Display and operating elements
4.4
Start up for daily operation
4.5
Notes on operation
4.5.1
Important notes on operation
4.5.2
Remote operating and fault indication
4.5.3
Recommended regular checks during operation
4.5.4
Manual draining of the water tank
4.5.5
Performing a matrix wash over
4.6
Decommissioning the system
18
18
19
21
22
23
23
23
23
24
25
26
5
5.1
5.1.1
5.1.2
5.2
5.3
5.3.1
5.3.2
5.4
5.4.1
5.4.2
5.4.3
5.4.4
5.4.5
27
27
28
29
30
31
31
31
34
34
34
36
38
39
Operating the Condair ME control software
Standard operating display
Operating status indication
Maintenance and malfunction indications
Navigating/operating the Condair ME control software
Information functions
Accessing support information
Accessing system information
Configuration
Accessing the “Configuration” submenu
Configuring dilution and drain cycle functions – “Features” submenu
Control settings – “Control Settings” submenu
Basic settings – “General” submenu
Communication settings – “Communication” submenu
Contents
3
5.5
5.5.1
5.5.2
5.5.2.1
5.5.2.2
5.5.2.3
5.6
5.6.1
5.6.2
4
Service functions
Accessing the “Service” submenu
Performing maintenance functions – “Service” submenu
Input diagnostic functions – “Input Diagnostics” submenu
Output diagnostic functions – “Output Diagnostics” submenu
Relay diagnostic functions – “Relay Diagnostics” submenu
Administration settings
Accessing “Administrator” submenu
Administration settings – “Administrator” submenu
40
40
40
44
47
48
49
49
49
6Maintenance
6.1
Important notes on maintenance
6.2
Maintenance intervals
6.3
Maintenance guide
6.4
Dismantling and installation of components for maintenance
6.4.1
Dismantling and installation of the evaporative module
6.5
Consumables guide
6.6
Health and safety requirements
6.7
Routine water sampling and testing
6.8
Cleaning and disinfection
6.9
Cleaning and disinfection method statement
6.10
Resetting the maintenance indication on Condair ME Control
6.11
Performing software updates
51
51
52
52
54
54
55
55
56
57
58
60
61
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
Fault elimination
Fault indication on Condair ME Control control unit
Malfunction list
Saving fault and service histories to a USB memory stick
Malfunctions without indication
Notes on fault elimination
Replacing the fuses and backup battery in the control unit
Resetting the fault status on Condair ME Control
62
62
63
68
68
69
70
71
8
8.1
8.2
Taking out of service/Disposal
Taking out of service
Disposal/Recycling
72
72
72
9
9.1
Product specifications
Technical data
73
73
10Appendix
10.1
Wiring diagram Condair ME Control
74
74
Contents
1
Introduction
1.1
General
We thank you for having purchased the Condair ME Control Evaporative Humidifier and Cooler
(Condair ME Control for short).
The Condair ME Control incorporates the latest technical ad­van­ces and meets all recognized safety
standards. Nevertheless, improper use of the Condair ME Control may result in danger to the user or
third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the Condair ME Control, please observe and
comply with all information and safety instructions contained in the present documentation as well as in
the separate documentations of the components installed in the humidification system.
If you have questions after reading this documentation, please contact your Condair representative.
They will be glad to assist you.
1.2
Notes on the operation manual
Limitation
The subject of this operation manual is the Condair ME Control Evaporative Humidifier and Cooler.
The various options and accessories are only described insofar as is necessary for proper operation of the
equipment. Further information on options and accessories can be obtained in the respective instructions.
This operation manual is restricted to the operation, the maintenance and troubleshooting of the
Condair ME Control and is meant for well trained personnel being sufficiently qualified for their
respective work.
Please note, some illustrations in this manual may show options and accessories which may not be
supplied as standard or available in your country. Please check availability and specification details with
your Condair representative.
The operation manual is supplemented by various separate items of documentation (such as the installation manual), which are included in the delivery as well. Where necessary, appropriate cross-references
are made to these publications in the operation manual.
Introduction
5
Symbols used in this manual
CAUTION!
The catchword “CAUTION” used in conjunction with the caution symbol in the circle designates notes
in this operation manual that, if neglected, may cause damage and/or malfunction of the unit or
other material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol designates safety
and danger notes in this operation manual that, if neglected, may cause injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol designates safety and
danger notes in this operation manual that, if neglected, may lead to severe injury or even death
of persons.
Safekeeping
Please safeguard this operation manual in a safe place, where it can be immediately accessed. If the
equipment changes hands, the operation manual must be passed on to the new operator.
If the operation manual gets mislaid, please contact your Condair representative.
Language versions
This operation manual is available in various languages. Please contact your Condair representative
for information.
6
Introduction
2
For your safety
General
Every person working with the Condair ME Control must have read and understood the operation manual
of the Condair ME Control before carrying out any work.
Knowing and understanding the contents of the operation manual is a basic requirement for protecting
the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and
correctly.
All ideograms, signs and markings applied to the components of the Condair ME Control must be observed and kept in readable state.
Qualification of personnel
All work described in this operation manual may only be carried out by specialists who are well
trained and adequately qualified and are authorized by the customer.
For safety and warranty reasons any action beyond the scope of this manual must be carried out only
by qualified personnel authorised by the manufacturer.
It is assumed that all persons working with the Condair ME Control are familiar and comply with the
appropriate local regulations on work safety and the prevention of accidents.
The Condair ME Control may not be used by persons (including children) with reduced physical, sensory
or mental abilities or persons with lacking experience and/or knowledge, unless they are supervised by
a person responsible for their safety or they received instructions on how to operate the system.
Children must be supervised to make sure that they do not play with the Condair ME Control.
Intended use
The Condair ME Control is intended exclusively for air humidification and air cooling in AHU's or
air ducts within the specified operating conditions. Any other type of application, without the written
consent of the manufacturer, is considered as not conforming with the intended purpose and may lead
to the Condair ME Control becoming dangerous.
Operation of the equipment in the intended manner requires that all the information contained in this
operation manual are observed (in particular the safety instructions).
For your safety
7
Danger that may arise from the Condair ME Control
DANGER!
Risk of electric shock!
The Condair ME control unit (and the optional submerged UV system) contain live mains
voltage. Live parts may be exposed when the control unit (or the terminal box of the optional
submerged UV system) is open. Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work on the Condair ME Control switch off the control unit, disconnect it from the mains via the electrical isolator and secure the electrical isolator in “Off” position
against inadvertent power-up.
DANGER!
Health risk because of inadequate hygiene!
Inadequately operated and/or poorly maintained evaporative humidification/cooling systems may endanger health. When inadequately operated and/or poorly maintained micro-organisms (including the
bacterium which causes Legionnaire’s disease) may grow in the evaporative module, the water tank
and the water system of the Condair ME Control and may affect the air in the AHU/air duct.
Prevention: the Cond­air ME Control must strictly be operated and maintained in accordance with this
manual.
WARNING!
Some type of evaporative material is manufactured from glass fibre. Though this material is not classified as hazardous, it is recommended that Personal Protection Equipment such as gloves, protective
clothing and eye protection are used during handling to protect the user from fibres or dust. If dust is
generated during handling it is recommended that respiratory protection is worn.
Correct lifting and handling
Lifting or handling of components must only be carried out by trained and qualified personnel. Ensure
that the lifting operation has been properly planned and risk assessed, and that all equipment has been
checked by a skilled and competent Health & Safety representative.
It is the customer's responsibility to ensure that operators are trained in handling heavy goods and to
enforce the relevant lifting regulations.
8
For your safety
Preventing unsafe operation
If it is suspected that safe operation is no longer possible, then the Condair ME Control should immediately be shut down and secured against accidental power-up according to chapter 4.6 – Decommissioning the system. This can be the case under the following circumstances:
– if the Condair ME Control is damaged
– if the Condair ME Control is contaminated
– if the electrical installations are damaged
– if the Condair ME Control is no longer operating correctly
– if connections and/or piping are leaking
All persons working with the Condair ME Control must report any alterations to the system that may
affect safety to the owner without delay.
Prohibited modifications to the unit
No modifications must be undertaken on the Condair ME Control without the express written consent
of the manufacturer.
For the replacement of defective components use exclusively original accessories and spare parts
available from your Condair representative.
For your safety
9
3
Product Overview
3.1
Model overview
As standard the Condair ME Control consist of:
– Evaporative module (75%, 85 % or 95 % efficiency depending on the cassette type)
– Hydraulic module (mounted internal or external to the duct)
– Control unit with integrated controller with touch panel
According to your order the Condair ME Control can be equipped with the following options:
– Droplet separator
– Evaporative module blanking
– Hydraulic module cover
– Remote operation and fault indication
– BMS connectivity
– Freeze protection stat
– Leak detection
– Conductivity monitoring
– Submerged UV or In-Line UV
– PureFlo Ag+
– Dosing pump
– Electrical isolator
10
Product Overview
3.2
Product designation / Which model do you have
The product designation and the most important unit data (e.g. serial number, evaporative module
product, etc.) are found on the rating plate fixed on the left side of the evaporative module and on the
right side of the control unit.
Rating Plate
Fig. 1: Position of rating plate
Evaporative module product key
Example:
ME-1-0900-1125-F95
Product idenfication
ME (media evaporator)
Product version (consecutive version number):
Width evaporative module in mm
Height evaporative module in mm
Material type and efficiency evaporative cassettes:
F75= Glass fibre 75 %
F85= Glass fibre 85 %
F95= Glass fibre 95 %
P85= Polyester 85 %
P95= Polyester 95 %
Product Overview
11
3.3
Construction of the system components
3.3.1
Construction of the evaporative module
7
6
8
5
4
3
2
air flow direction
1
1
2
3
4
9
Upstands
Tank connector ø54 mm (2.125")
Rating plate
Droplet separator, mandatory for face velocity
>3.5 m/s (>689 fpm)
Fig. 2: Construction of the evaporative module
12
Product Overview
5
6
7
8
9
Evaporative cassettes (F75, F85, F95, P85 or P95)
Distribution heads
Blanking plates (option)
Mounting frame for evaporative cassettes
Water tank
3.3.2
Construction of the hydraulic module
8
9
10
11
12
13
7
6
5
4
3
14
15
2
1
1
2
3
4
5
6
7
8
9
Drain valve (normally open)
Drain pump
Stage pump 5 with push-fit connector ø15 mm (0.625")
Stage pump 3 with push-fit connector ø15 mm (0.625")
Stage pump 1 with push-fit connector ø15 mm (0.625")
Stage pump 2 with push-fit connector ø15 mm (0.625")
Stage pump 4 with push-fit connector ø15 mm (0.625")
Level sensor
Conductivity sensor (option)
10 Fixing bracket
11 Push-fit connector ø15 mm (0.625") pressure equalisation (only used when mounted outside of AHU)
12 Water supply push-fit connector ø15 mm (0.625")
13 Inlet valve (normally closed)
14 Drain connector ø28 mm (1.125")
Note: drain connector can be turned 180° to drain
through the left or the right duct wall
15 Interconnecting cable hydraulic module
Fig. 3: Construction of the hydraulic module (figure shows layout for 2-stage control)
Product Overview
13
3.4
System overviews / Functional description
3.4.1
Typical system Condair ME Control (internally mounted)
Blanking plates
Electrical
isolator
Control unit
Evaporative module
Hydraulic module (with
supply valve, drain valve
and stage pumps)
Shut-off valve
Water supply line
Air flow direction
Vent drain pipe
Inter connecting cable
hydraulic module
Tank drain with trap
AHU drain
with trap
Fig. 4: Typical system Condair ME Control (internally mounted)
14
Product Overview
3.4.2
Typical system Condair ME Control (externally mounted)
Blanking plates
Electrical
isolator
Control unit
Evaporative module
Water supply line
Shut-off valve
Inter connecting cable
hydraulic module
Air flow direction
Pressure equalisation
Hydraulic module (with
supply valve, drain valve
and stage pumps)
AHU drain
with trap
Vent drain pipe
Tank drain with trap
Fig. 5: Typical system Condair ME Control (externally mounted)
Product Overview
15
Schematic flow diagram
AHU
Shut-off
valve with
strainer
Hydraulic module
Inlet solenoid
valve (NC)
Evaporative cassettes
Drain vent
to duct
4
2
1
3
5
Water tank
Level
sensor
Drain
pump
Stage pumps 2... max. 5)
Gravity solenoid
drain valve (NO)
Drain trap
(building side)
Tundish
(building side)
Fig. 6: Schematic flow diagram Condair ME Control (internally mounted)
AHU
Hydraulic module
Evaporative cassettes
Pressure
equalisation
Shut-off
valve with
strainer
Inlet solenoid
valve (NC)
4
2
1
3
5
Water tank
Level
sensor
Drain
pump
Stage pumps 2... max. 5)
Drain vent
to duct
Gravity solenoid
drain valve (NO)
Drain trap
(building side)
Tundish
(building side)
Fig. 7: Schematic flow diagram Condair ME Control (externally mounted)
16
Product Overview
Functional description
The water tank is filled up to a preset upper level via the level-controlled inlet solenoid valve (NC). When
the water level in the water tank drops below a certain limit, the level-controlled inlet solenoid valve opens
until the upper limit is reached again.
The Condair ME Control provides On/Off or stage control by means of the Condair ME Control control
unit and the stage pumps. The Condair ME Control control unit processes analog sensor/control signals
and uses them to control the stage pumps.
In case of a humidification/cooling request with activated On/Off control the inlet solenoid valve (NC)
opens and all stage pumps start and the water flows to the distribution header above the evaporative
cassettes.
In case of a humidification/cooling request with activated stage control the inlet solenoid valve (NC)
opens, then one, two, three, four or all five stage pumps start (depending on the demand signal and
evaporative module size) and the water flows to the distribution header above the evaporative cassettes.
The distribution pipes inside the distribution header evenly supply the water to the entire surface of the
evaporative cassettes where it flows down and humidifies the air flowing through the evaporative cassettes. The excess water not used for humidification flows to the water tank.
To prevent accumulation of mineral residues and the formation of germs in the water tank, the tank is
completely drained periodically (interval or time controlled). Additionally further hygiene functions can
be activated: Operation-dependent draining of the water tank (fill cycle, conductivity, temperature or
time controlled).
Product Overview
17
4
Operation
4.1
Important notes on operation
Qualification of personnel
The Condair ME Control must be commissioned and op­erated only by personnel familiar with the system and adequately qualified for the respective tasks. It is the owner’s responsibility to verify proper
qualification of the operating personnel.
General notes
The instructions and details regarding commissioning and operation must be followed and upheld.
The initial commissioning of the Condair ME Control requires appropriately trained technical personnel.
It is strongly recommended that your Condair representative commissions your system. Part of this initial
commissioning process is a disinfection of the water tank, and if required the evaporative cassettes.
Please read this document in full before commencing any work.
Please pay attention to local regulations regarding working at heights and electrical work.
Safety and hygiene
DANGER!
The Condair ME Control must be operated in accordance with this manual. Failure to do so
could result in contamination that might cause Legionnaires’ disease, which can be fatal.
WARNING!
The Condair ME control unit should not be electrically isolated for periods exceeding 24 hours
as automatic drain and purge cycles will be disabled.
18
Operation
4.2
Initial commissioning
The initial commissioning of the Condair ME Control requires appropriately trained technical personnel.
We strongly recommend that your Condair representative commissions your system.
Inspections
Prior to initial commissioning the complete system must be inspected for correct execution of the installations. Proceed as follows:
1. Switch off AHU.
2. Evaporative module installation: Check correct selection of evaporative module on rating plate if
multiple units on site. Check that the evaporative module has been installed level in all planes with
secure blanking plates to prevent air bypass. Check that there is sufficient access for cassette removal during maintenance. Ensure assembly is securely fixed, and that there is no visible damage.
Check that the evaporative module is installed in a waterproof section. Check evaporative module
(including tank) is free of dirt/ debris and clean as necessary.
3. Control unit installation: Check that the control unit is mounted in a convenient dry location
4. Supply water Installation: Ensure the water system in the building has been subject to a Risk
Assessment. The Condair ME Control must be connected to a clean, wholesome mains water
supply. It is the responsibility of the user to ensure that the water system complies with local regulations and bylaws, particularly those for the control of Legionella microbes. The use of mains water
fed tanks and reservoirs is only permitted as part of a managed water treatment system. Check that
the evaporative module has a feed water supply in excess of 2 bar (29 psi) connected to the supplied approved filling hose. Ensure that any hygiene options have been correctly installed. Check
all joints and fittings for leaks.
5. Drain installation: Check that the drain line is made according to the corresponding instructions
given in the installation manual. Ensure the drain line is connected to the main building drain and
that drain pipework is trapped to a suitable level for the applicable working duct pressure. Check all
joints and fittings. Ensure that the drain connection includes an air gap.
6. Distribution pipework: Check all water distribution pipework between the hydraulic module and
the distribution headers are securely fitted.
7. Electrical wiring: Check all electrical connections with reference to the corresponding wiring diagram
in this manual. Check that a 100...240V / 10A single phase supply is connected to the control unit.
Ensure that this power supply is isolated with an electrical isolator within 1 m (39") of the control unit.
8. Optional controls: Check that appropriate controls connections have been made to the control unit.
Refer to the controls wiring section of the installation manual.
9. Flush water supply and test supply water quality: Disconnect water supply pipe from connector
on the hydraulic module. Fix hose to free end of supply pipe and lead hose to a drain. Carefully flush
supply pipe a suitable amount of time without creating splashing or aerosols.
Take a water quality sample to ensure that supply water meets the requirements specified in the
water quality guide. The sample should be tested using a dip slide to indicate the total number of
colony forming units per ml (cfu/ml). Generally, levels of 1x103 cfu/ml may be considered acceptable
for this type of humidifier provided the species of microbes and/or fungi involved are themselves not
considered to be harmful. If you are unsure of the quality of your water please consult your Condair
distributor for advice.
Then reconnect the water supply pipe to the supply connector on the hydraulic module.
Operation
19
10.Perform pressure test: Turn on water supply and check for leaks. Ensure double check valve is
installed correctly.
After the system has been inspected and found correct proceed with the initial commissioning:
1. Ensure AHU is switched off.
2. Switch on electrical isolator, and then the <Humdification/Cooling On/Off> and the <Control unit
On/Off> switch on the control unit.
3. Enter the activation code (see chapter 5.5.2 – Performing maintenance functions – “Service” submenu).
4. Perform a matrix wash over cycle (see chapter 5.5.2 – Performing maintenance functions – “Service”
submenu).
5. Check correct water level and pump activation.
6. Check water can flow to drain correctly.
7. Allow system to flush until water is clean.
8. Simulate full demand and check components are operating correctly.
9. Test correct flow of water to distribution header.
10.Test any fitted options (see relevant option addendum manual).
11. If evaporative cassettes have become dirty or damp, follow the disinfection procedure described in
sections 6.3 and 6.9 of this manual.
12.Switch on fan of AHU and test operation with fans running and validate air conditions against the
design data.
13.From full saturation – time drain cycle (with fan in design condition).
14.Test control devices.
15.Correctly configure Condair ME control unit (setpoints, control settings, etc.) according to the situation on site (see chapter 5.4 – Configuration).
16.Drain tank, wipe tank clean, re-fill tank and add DISIFIN XL chemical according to tank volume.
17.If commissioning has not been completed by an approved Condair representative, it is recommended
that records are kept of commissioning date and software settings.
18.Demonstrate system to customer and highlight hygiene and maintenance requirements.
19.Raise any installation concerns.
20.Issue commissioning documentation.
The system is now ready for normal operation.
20
Operation
4.3
Display and operating elements
r
ifie
mid
Hu
1
Electrical isolator
Note: the electrical isolator (supplied by the customer) must be installed in the mains supply line!
2
Touch screen
3
Status LED
– green: Condair ME Control is
humidifying/cooling
– green pulsing: No demand or humidification/cooling is switched off
– orange: Warning present or maintenance
due
– red: Fault present
4
<Humdification/Cooling On/Off> switch
Note: with this switch the humidification/cooling
function can be activated and deactivated. The
hygiene functions (regular flushing of the water
system) remain still active even with deactivated
humidification/cooling function.
5
<Control unit On/Off> switch (located on
the bottom of the control unit)
Note: with this switch you can switch on and off
the control unit. If the control unit is switched off
all functions (including hygiene functions) of the
Condair ME Control are deactivated.
Fig. 8: Display and operating elements Condair ME
DANGER!
Risk of electric shock!
Since mains supply to the control unit is not interrupted by switching off the <Humdification/Cooling
On/Off> switch and there is still mains voltage inside the control unit even when you switch off the
<Control unit On/Off> switch too, the electrical isolator must be switched off before open the
control unit.
Operation
21
4.4
Start up for daily operation
It is assumed that initial commissioning has been carried out properly by the service technician of your
Condair representative.
If the Condair ME Control has been out of operation for a prolonged period of time, a complete
system service has to be performed prior to the start up.
The following description outlines the start up procedure for daily operation. Proceed as follows to prepare the Condair ME Control for operation:
1. Switch off AHU.
2. Examine the Condair ME Control for possible damage and faulty installation. Ensure tank is empty.
DANGER!
Damaged systems or systems with damaged components or faulty installations may present danger
to human life or cause severe damage to material assets.
Damaged systems and/or systems with damaged or faulty installation must not be operated.
3. Close doors of AHU if open, then switch on AHU if switched off.
4. Open shut-off valve in the water supply line.
5. Make sure the front panel of the control unit is mounted and fixed with the retaining screw.
6. Switch on the electrical isolator in the mains supply line (mains supply to control unit).
7. Switch <Control unit On/Off> and <Humdification/Cooling On/Off> switch on the control unit to
“On”, and activate control unit via the external enable switch if necessary. Check for any fault or
service message.
8. If Condair ME Control has been disconnected from the mains for more than 48 hours the message
“Out of Commissioning” appears. If this is the case proceed as follows:
•
Switch off control unit via the <Control unit On/Off> switch.
•
Risk assess the system and check the need for disinfection.
•
Close shut-off valve in the water supply line.
•
Disconnect water supply line from the connector on the hydraulic module. Caution should be
taken to ensure no splashing is created.
•
Connect hose to the open end of the water supply line and lead the hose into open tundish
outside the AHU.
•
Open shut-off valve in the water supply line and flush water supply line an appropriate length of
time. Then, close shut-off valve again, remove hose and reconnect supply line to the connector
on the hydraulic module.
•
Switch on control unit via the <Control unit On/Off> switch.
Note: After switching on the control unit the “Out of Commissioning” message appears again, however the message is reset automatically after 1 minute and the Condair ME Control continues with
normal operation.
The Condair ME Control is now in normal operating mode and the standard operating display is shown.
Note: further information on the operation of the Condair ME control software can be found in chapter 5
– Operating the Condair ME control software.
22
Operation
4.5
Notes on operation
4.5.1
Important notes on operation
– For hygiene reasons the supply valve opens in standby mode every 12 hours for approximately
20 seconds in order to flush water supply line.
– If no demand is present for more than 23 hours the tank will be drained.
4.5.2
Remote operating and fault indication
The relays on the remote operating and fault indication board indicate the following operating system
status:
4.5.3
Activated
remote indication relay
When?
“Error”
An error is present, operation is stopped or further operation is possible for a limited period
of time only.
“Service”
One of the maintenance counter has elapsed. The corresponding maintenance must be
performed.
“Running”
Demand present/system is humidifying/cooling
“Unit on”
The humidification system is switched on and under voltage
Recommended regular checks during operation
During operation the Condair ME Control has to be checked periodically in accordance with the table
below.
Operations Checks
Daily
Weekly
Monthly
Quarterly
Monitor humidity/temperature control




Check for any low humidity/temperature concerns




Check any alarms on BMS




Visible check for:

– Units switched on with no fault lights
– No water leakage (air on and air off side)
– No water flow to drain (water may flow to drain during
drain cycle and when unit losses humidity demand)
– system components for correct fixing and any damage
– electric installation for any damage.



All UV bulbs are active (with water level), if applicable



Matrix media is saturated (relative to demand signal)


Condition of tanks and air on matrix is clean


Inspect and determine replacement frequency of sediment filter


Add DisifinXL chemical (1 sachet per 2 m (6.6 ft) width
of tank)


Operation
23
Operations Checks
Daily
Weekly
Monthly
Quarterly
Conductivity (reading below set point)


Correct software settings


Condition of tanks are clean (clean as required)

Water level is correct (ensure unit Is not in drain cycle)

If the checks reveal any irregularities (e.g. leakage, error indication) or any damaged components take
the Condair ME Control out of operation as described in chapter 4.6 – Decommissioning the system.
Then, have the malfunction eliminated or the damaged component replaced by a well trained specialist
or a service technician from your Condair representative.
4.5.4
Manual draining of the water tank
If a manual draining of the water tank is required proceed as follows:
1. Close shut-off valve in the water supply line.
2. Press on the <Drain> button in the standard operating display.
3. Press on the menu item <Drain>. The drain confirmation dialogue appears.
4. Press on the <Yes> button to start draining of the water system. A possible running humidification/
cooling process is interrupted. The progress bar in the display shows the current status of the drain
process. After the tank is drained the control unit returns to the “Manual” submenu.
Note: in order to stop the drain process press the <Cancel> button in the progress window. The
drain process is stopped and the control unit returns to the “Manual” submenu.
24
Operation
4.5.5
Performing a matrix wash over
At initial commissioning when the “Matrix Wash Over” (W49) message appears or any time new evaporative cassettes have been installed, a matrix wash over cycle has to be performed. If a matrix wash over
cycle is required proceed as follows:
Password: 8808
Condair ME Control is in normal operation mode.
1. Select the “Service” submenu (displays 1-3)
2. Select “Matrix Wash Over” function in the “Service” submenu. The matrix wash over confirmation
dialogue appears.
3. Press on the <Yes> button to start the matrix wash over. A possible running humidification/cooling
process is interrupted. The progress bar in the display shows the current status of the matrix wash
over process. After the matrix wash over process is finished the control unit returns to the “Service”
submenu.
Note: in order to stop the matrix wash over process press the <Cancel> button in the progress window. The matrix wash over process is stopped and the control unit returns to the “Service” submenu.
Operation
25
4.6
Decommissioning the system
In order to decommission the Condair ME Control (e.g. to perform maintenance works, to eliminate a
malfunction, etc.) perform the following steps:
1. If the system has to be switched off because of a malfunction, please note the Warning and Fault
code(s) of the actual error message(s) shown in the fault history.
2. Close the shut-off valve in the water supply line.
3. Empty the water tank with the manual drain function (see chapter 4.5.4 – Manual draining of the
water tank).
4. Switch off <Humdification/Cooling On/Off> and <Control unit On/Off> switch on the control unit,
and if necessary deactivate control unit via the external enable switch.
5. Disconnect control unit from the mains: switch off the electrical isolator in the mains supply to
the control unit and secure switch in “Off” position against accidentally being switched on, or clearly
mark the switch.
6. Let the fan of the ventilation system run until the evaporative module is dry.
7. If work has to be carried out on the evaporative module or the hydraulic module mounted inside the
duct, switch off the AHU and secure the system against accidentally being switched on.
Important Notes!
– For reasons of hygiene, we recommend that the control unit should be left powered on even if the
Condair ME Control is not being used for a longer period of time. Only the <Humdification/Cooling
On/Off> switch should be switched off. This keeps the hygiene functions (e.g. periodical flushing of
water supply pipe) active and hence the build-up of germs is opposed.
– If the Condair ME system is isolated from the mains for prolonged periods, water stagnation
might occur in supply pipework and microbial contamination result, therefore the system,
including any storage tanks or vessels should be drained and left dry. Before putting the system
back into operation, a full risk assessment should be undertaken to ensure safe operation, with
particular attention paid to water supply quality. Additionally a complete system service has to
be performed prior to putting the system back to operation.
26
Operation
5
Operating the Condair ME control software
5.1
Standard operating display
After switching on the control unit and the automatic system test the control unit is in normal operating
mode and the standard operating display is shown.
Note: the appearance of the standard operating display depends on the current operating status and
the configuration of the humidity/temperature regulation of the system and can deviate from the display
shown below.
The standard operating display is structured as follows:
Current operating status
(see chapter 5.1.1 – Operating status indication)
Humidity/temperature regulation information
Maintenance/malfunctions indication field
(see chapter 5.1.2 – Maintenance and malfunction indications)
Access Help screen
Drain tank
Access system information
Access main menu
Fig. 9: Standard operating display
Operating the Condair ME control software
27
5.1.1
Operating status indication
The following operation status indications may appear during operation:
Operating status indication
Description
The control is initialising.
No humidity demand for more than 60 minutes the humidification system is in standby mode. The
water system is flushed automatically for 300 seconds before the next humidification takes place.
The Condair ME is humidifying.
The Condair ME is cooling.
The Condair ME holds the current water level in the tank to be ready for operation.
The Condair ME is draining the tank.
If the water conductivity is not decreasing after a dilution, a water refresh cycle will be carried
out (refill of the full tank). Note: This message appears only, if the system is equipped with the
conductivity monitoring option.
The Condair ME is filling the tank.
The water in the tank is being diluted to minimise limescale.
After the demand has dropped to zero, the system drains a small amount of water to give space
to the rest water held in the matrix.
During operation the stage pumps are stopped periodically to bleed any air out of the pumps
by the water flowing back from the distribution pipes.
The Condair ME is ramping up the water duty to the matrix.
The operation is manually switched off.
The Condair ME was stopped via the external enable switch.
The inlet pipework is being purged.
The ME is in diagnostic mode, e.g. wash over activation through BMS.
The humidification system is stopped due to a malfunction which obviates further operation.
Additionally “Warning” or “Fault” is displayed in the maintenance and malfunction field.
28
Operating the Condair ME control software
5.1.2
Maintenance and malfunction indications
The following maintenance and malfunction indications may appear during operation:
Operating status indication
Description
No malfunction present. By pressing on the indication field the service menu can be accessed.
The system service is due. If the system service is not performed within 30 days a fault message is triggered. The system remains operable.
The external liquid container of the dosing pump is empty.
The lifetime of the PureFlow Ag+ cartridge has expired and must be replaced.
The lifetime of the UV bulb has expired and must be replaced.
As new matrix has been installed, a matrix wash over cycle needs to be carried out.
This message appears after switching on, if the control unit has been isolated from the mains
supply for more than 48 hours. The humidification system is blocked for 5 minutes. Before operation the RO water supply line to the central unit must be flushed. The commissioning warning
is reset automatically after 5 minutes or you can reset the warning in the “Service” submenu
(see chapter 5.5.2 – Performing maintenance functions – “Service” submenu).
The device specific activation code needs to be entered to get the system running.
A malfunction with status “Warning” is active. Additionally the yellow LED lights. Depending on
the malfunction the humidification system is either be stopped or stays operable for a certain
period of time.
A malfunction with status “Fault” is active. Additionally the red LED lights. Depending on the
malfunction the humidification system is either be stopped or stays operable for a certain
period of time.
Operating the Condair ME control software
29
5.2
Navigating/operating the Condair ME control software
Navigation element
Action
Accessing main menu
Accessing system information
Performing manual drain
Accessing Help screen
If you press on a field with a blue arrow symbol a new screen with additional
information or settings appears.
This symbol on the left side of the operating status field and of the maintenance/malfunctions indication field indicates, that the system is working ok.
This symbol on the left side of the maintenance/malfunctions indication
field indicates, that a Warning is present. Press on the field to get further
information.
This symbol on the left side of the operating status field and of the maintenance/malfunctions indication field indicates, that a Fault is present (additionally the LED lights red). Press on the field to get further information.
Jumps back to previous screen (cancel and back)
Scroll up/down
Increase/decrease value
Delete shown value
Confirm set value or selected option
30
Operating the Condair ME control software
5.3
Information functions
5.3.1
Accessing support information
In the standard operating display press the <Help>
button.
The screen with the support information appears.
5.3.2
Accessing system information
In the standard operating display press the <About> button.
The system information screen appears. Use the arrow buttons to scroll up and down within the system
information screen.
Operating data
– Actual Stage: Actual number of currently operating stages of the system.
– Max Stage: Number of maximum stages set to operate.
– Max. Capacity: Maximum evaporating capacity in kg/h or lb/hr.
Operating the Condair ME control software
31
Maintenance
– Hours of Operation: Operating hours since initial commissioning of the
system.
– Next ME Service: Remaining time until next maintenance of the system
must be performed.
– Next UV Bulb: Remaining time until the UV bulb of the optional UV device
must be replaced.
– Next PureFlo: Remaining time until the cartridge of the PureFlo Ag+ option must be replaced.
Evaporator Conditions
The content of the “Evaporator Conditions” information section depends on the set dilution mode.
Dilution mode set to “Fill Cycle”:
– Dillution Fill cycle: Actual set fill cycles for periodical tank draining depending on the fill cycles.
– Drain Interval: Actual set tank drain interval time.
Dilution mode set to “Dilution µS Limit”:
– Conductivity: Actual conductivity of the water in the tank in µS (µS/cm).
– Water Temperature: Actual temperature of the water in the tank in °C
or °F.
– Dillution µS Limit: Actual set conductivity limit value if exceeded a dilution
cycle is triggered.
– Drain Interval: Actual set tank drain interval time.
Dilution mode set to “Dilution H2O Temp”:
– Water Temperature: Actual temperature of the water in the tank in °C
or °F.
– Dilution H2O Temp: Actual set temperature limit value Actual temperature
of the water in the tank in °C or °F if exceeded a dilution cycle is triggered.
– Drain Interval: Actual set tank drain interval time.
Dilution mode set to “Dilution Interval”:
– Dillution Interval: Actual set dilution interval time, for periodic dilution of
the water in the tank.
– Drain Interval: Actual set tank drain interval time.
32
Operating the Condair ME control software
General
– Humidifier Model: Designation of the humidifier model.
– Software Version: Actual version of the control software.
– Driver A.DB.A Version: Actual software version of the driver board.
– Ext. A.DB.A 1 Version: Actual software version of the conductivity monitoring board.
– Serial number: Serial number of the Condair ME Control.
Operating the Condair ME control software
33
5.4
Configuration
5.4.1
Accessing the “Configuration” submenu
Password: 8808
5.4.2
Configuring dilution and drain cycle functions – “Features” submenu
In the “Features” submenu you set the parameters for the dilution and drain cycle functions.
Dilution
The process of evaporative humidification/cooling leads to a build up of dissolved solids in the water
tank. To control the degree of dissolved solids in the tank, the Condair ME Control will trigger a dilution
cycle according to the set fill cycles, interval time, water temperature or conductivity limit. During the
Dilution Cycle the Condair ME Control will open the gravity drain solenoid valve until a certain level is
reached to drain dissolved solids away and replenish the tank with fresh water. The Dilution Cycle does
not interrupt normal system operation.
– Mode: select the desired dilution cycle control mode.
Factory setting:
Options:
Fill Cycle
Fill Cycle (fill cycle controlled dilution cycle)
Condu Limit (conductivity controlled dilution cycle)
H2O Temp (temperature controlled dilution cycle)
Interval (time controlled dilution cycle)
Depending on the selected dilution cycle control mode additionally the parameters “Fill Cycle”, ”Condu Limit”, “H2O Temp” or “Interval” must be set.
– Dilution Fill Cycle: set the desired fill cycles after which a dilution
cycle is triggered. The number of fill cycles to be set depends on the
water quality.
Factory setting:
Setting range:
34
Operating the Condair ME control software
10
1...200 (fill cycles)
– Dilution Condu Limit: set the desired conductivity limit in µS/cm. A
dilution cycle is triggered as soon as the conductivity of the water in
the tank exceeds the set conductivity limit.
Factory setting:
Setting range:
600 µS
10...5000 µS
– Dilution H2O Temp: set the desired water temperature in °C or °F.
A dilution cycle is triggered as soon as the water temperature in the
tank exceeds the set temperature.
Factory setting:
Setting range:
30 °C (86 °F)
0...50 °C (32... 122 °F)
– Dilution Interval: set the desired interval time in minutes. A dilution
cycle is triggered as soon as the interval time has elapsed.
Factory setting:
Setting range:
60 minutes
1...2160 minutes
Drain
The drain cycle function is designed to drain the water tank periodically to prevent conditions which favour the growth of bacterias in the tank (e.g. legionella). The drain cycle can be initiated at a fixed time
of day or after a interval time has elapsed. If a drain cycle is triggered the stage pumps will be stopped
and the tank is completely drained via the drain pump (the drain pump is stopped when a preset level
is reached) and the gravity drain solenoid valve. If a demand is present the gravity drain solenoid valve
is closed and the tank is refilled otherwise the tank remains empty until the next demand.
– Mode: select the desired drain cycle control mode.
Factory setting:
Options:
Interval
Interval (interval time controlled drain cycle)
Time (time of day controlled drain cycle)
Depending on the selected drain cycle control mode additionally the parameters “Interval” or ”Time” must be set.
– Drain Interval: set the desired interval time in hours. A drain cycle is
triggered as soon as the set interval time has elapsed.
Factory setting:
Setting range:
12 hours
1...24 hours
– Drain Time: set the desired time of day time (according to set time
format) at which a drain cycle is triggered.
Factory setting:
Setting range:
12:00 am
according to set time format
Operating the Condair ME control software
35
5.4.3
Control settings – “Control Settings” submenu
In the “Control Settings” submenu you determine the control settings for the Condair ME Control. The
control settings available depend on the selected signal source and the control mode.
Basic
– Source: with this setting you determine whether the control signal comes
from an analogue source (signal of a humidity sensor or demand signal
from an external humidity controller) or via Modbus.
Factory setting:
Analog
Options:
Analog or Modbus
– System Mode: with this setting you determine whether the Condair ME
Control is configured as an air humidifier (“Humidifying”) or as an air cooler
(“Cooling”).
Factory setting:
Options:
Humidifying
Humidifying (configured as air humidifier)
Cooling (configured as air cooler)
– Control Mode: with this setting you determine the type of controller used
with the Condair ME Control.
Factory setting:
Options:
Demand
On/Off (external On/Off humidistat)
Demand (external continuous controller)
RH P (internal P controller)
RH PI (internal PI controller)
– Signal type Channel 1 / Signal type Channel 2: with this setting you
determine the control signal type for Channel 1 (if System Mode is set to
humidifying) or Channel 2 (if System Mode is set to cooling).
Note: this setting appears only if signal source is set to “Analog” and
Control Mode is set to “Demand”, “RH P” or “RH PI”.
Factory setting:
Options:
0-10 V
0-5V, 1-5V, 0-10V, 2-10V, 0-20V, 0-16V, 3.2-16V,
0-20mA, 4-20mA
– Temperature Min: with this setting you determine the minimum temperature of the measuring range of the temperature sensor used.
Note: this setting appears only if System Mode is set to “Cooling” and
Control Mode is set to “RH P” or “RH PI”.
Factory setting:
Setting range:
0.0 °C (32 °F)
–50.0 ... +100 °C (–58 ... 212 °F)
– Temperature Max: with this setting you determine the maximum temperature of the measuring range of the temperature sensor used.
Note: This setting appears only if signal source is set to “Analog” and
control mode is set to “Demand”, “RH P” or “RH PI”.
Factory setting:
Setting range:
36
Operating the Condair ME control software
50.0 °C (122 °F)
–50.0 ... +100 °C (–58 ... 212 °F)
PI Control Parameters
– Setpoint: with this setting you set the humidity setpoint in %rh (if System
Mode is set to “Humidifying”) or the temperature setpoint in °C or °F (if
System Mode is set to “Cooling”).
Note: this setting appears only if the Control Mode is set to “RH P” or
“RH PI”.
Factory setting:
Options:
40 % or 20 °C (68 °F)
0 ... 95 % or 5 ... 40 °C (41... 104 °F)
– P-Band Channel 1 / P-Band Channel 2: with this setting you set the proportional range of channel 1 in %rh (if System Mode is set to humidifying)
or of channel 2 in °C or °F (if System Mode is set to cooling).
Note: this setting appears only if the Control Mode is set to “RH P” or
“RH PI”.
Factory setting:
Options:
15 %rh or 10 °C (50 °F)
6 ... 65 %rh or 1.0 ... 50.0 °C (34 ... 122 °F)
– Integral time Channel 1 / Integral time Channel 2: with this setting you
set the integral time of channel 1 (if System Mode is set to humidifying)
or channel 2 (if System Mode is set to cooling) in minutes.
Note: this setting appears only if the Control Mode is set to “RH PI”.
Factory setting:
Options:
5 minutes
1 ... 60 minutes
Stage switching
– Threshold 1: With this setting you determine the set point at which the
pump of stage 1 will switch on or off in % of the demand signal.
Factory setting:
Options:
5%
1 ... 99 %
– Threshold 2: With this setting you determine the set point at which the
pump of stage 2 will switch on or off in % of the demand signal.
Factory setting:
Options:
20 %
1 ... 99 %
– Threshold 3: With this setting you determine the set point at which the
pump of stage 3 will switch on or off in % of the demand signal.
Factory setting:
Options:
40 %
1 ... 99 %
– Threshold 4: With this setting you determine the set point at which the
pump of stage 4 will switch on or off in % of the demand signal.
Factory setting:
Options:
60 %
1 ... 99 %
– Threshold 5: With this setting you determine the set point at which the
pump of stage 5 will switch on or off in % of the demand signal.
Factory setting:
Options:
80 %
1 ... 99 %
Operating the Condair ME control software
37
5.4.4
Basic settings – “General” submenu
In the “General” submenu you determine the basic settings for operating the Condair ME Control control
unit.
Basic
– Date: With this setting you determine the current date in the set format
(”MM/DD/YYYY” or “DD/MM/YYYY”).
Factory setting:
00/00/0000
– Time: With this setting you set the current hour of the day in the set time
format (”12H” or “24H”).
Factory setting:
12:00
– Language: With this setting you determine the dialogue language.
Factory setting:
Options:
depending on the country
different dialogue languages
– Units: With this setting you determine the desired unit system.
Factory setting:
Options:
depending on the country
Metric or Imperial
– Contrast: With this setting you determine the desired value for the display
contrast.
Factory setting:
Options:
8
1 (weak contrast) ... 31 (strong contrast)
– Brightness: With this setting you determine the desired value for the
display brightness.
Factory setting:
Options:
52
1 (dark) ... 100 (white)
Time/Date
– Date Format: With this setting you determine the desired date format.
Factory setting:
Options:
depending on the country
DD/MM/YYYY or MM/DD/YYYY
– Clock Format: With this setting you determine the desired time format.
Factory setting:
Options:
38
Operating the Condair ME control software
depending on the country
24H (24 hours, display 13:35) or
12H (12 hours, display: 01:35 PM)
5.4.5
Communication settings – “Communication” submenu
In the “Communication” submenu you determine the parameters for the communication.
Modbus Parameters
– Modbus: With this setting you can activate (“On”) or deactivate (“Off”)
communication via a Modbus network.
Factory setting:
Off
Options:
Off or On
The following parameters appear only if the Modbus function is activated.
– Modbus Address: With this setting you determine the Modbus address for the adiabatic air humidification system Condair ME for the
communication via a Modbus network.
Factory setting:
Setting range:
10
1 ... 247
– Parity: With this setting you set the parity bit for the data transfer.
Factory setting:
Options:
Even
None, Even or Odd
– Baudrate: With this setting you set the Baudrate for the data transfer.
Factory setting:
Options:
9600
9600, 19200, 39400, 115200
– BMS Timeout: With this setting you set the timeout time for the data
transfer.
Factory setting:
Setting range:
300 Seconds
0 ... 300 Seconds
Remote Fault Board
– Indication: With this setting you determine whether only maintenance
messages (“Service”) or all Warning messages (“Warning”) are outputted
via the service relay of the remote operating and fault indication board.
Factory setting:
Service
Options:
Service or Warning
– Safety Chain Indication: With this setting you determine whether an Fault
(“On”) or a Warning (“Off”) is triggered when the external safety chain is
open.
Factory setting:
Off
Options:
Off or On
Operating the Condair ME control software
39
5.5
Service functions
5.5.1
Accessing the “Service” submenu
Password: 8808
5.5.2
Performing maintenance functions – “Service” submenu
In the “Service” submenu you can enter the activation code, accessing and resetting the fault and maintenance history and performing different input and output diagnostic functions.
General Service
– Activation Code:
Note: this menu item appears only if the activation code message is
shown at system startup.
Via the “Activation Code” function you can unlock the Cond­air ME if it is
locked ex factory with an activation code. Once the activation code has
been entered and confirmed the menu item is not shown anymore.
After pressing on the “Activation Code” button a confirmation window appears where you have to confirm the activation. Afterwards you can enter
the four-digit activation code and confirm it.
Note: contact your Condair representative to get the activation code.
40
Operating the Condair ME control software
– Commissioning Reset: with this function you can reset the “Out of
Commissioning” message, which appears if the control unit has been
disconnected from the mains for more than 48 hours. After pressing on
the “Commissioning Reset” button a confirmation window appears where
the resetting must be confirmed.
Note: after resetting the control unit must be connected to the mains for
at least 15 minutes, otherwise the “Out of Commissioning” message appears on the next startup again.
– Matrix Wash Over: with this function you can wash over the evaporative
cassette matrix. After pressing on the “Matrix Wash Over” button the wash
over cycle is automatically started.
Note: Use this function to wash over newly installed evaporative cassettes
to remove any dust and glue left after the manufacture of evaporative cassette material. The wash over is mandatory for newly installed systems
with glass fibre type evaporative cassettes.
– UV Bulb Reset: with this function you can reset the UV Bulb replacement
message after having replaced the UV bulb. This menu item appears only,
if this option is installed and activated..
Note: Resetting the UV Bulb replacement message without having replaced
the UV Bulb may lead to contamination of the system.
– PureFlo Ag+ Reset: with this function you can reset the PureFlo Ag+
replacement message after having replaced the PureFlo Ag+ cartridge.
This menu item appears only, if this option is installed and activated.
Note: Resetting the PureFlo Ag+ replacement message without having
replaced the PureFlo Ag+ cartridge may lead to contamination of the system.
– ME Service Reset: with this function you can reset the System Service
message after having performed a system service.
Note: Resetting the System Service replacement message without having
performed a system service may lead to contamination of the system.
Disifin
– Disifin: when DISIFIN XL sachet(s) are added to the tank for disinfection, the conductivity in the tank will increase. This would cause a fault on
systems equipped with the optional conductivity monitoring.
With the function “Disifin” you can override the conductivity monitoring for
1 hour once you have added DISIFIN XL sachet(s).
Operating the Condair ME control software
41
Fault/Service History
Note: the fault and maintenance events stored can be correctly analysed only
if the data and the time of day are correctly set.
– Fault History: with this function you can access the fault history list where
the last 40 fault events are stored. After pressing on the “Fault History”
button the fault history list appears.
– Service History: with this function you can access the service history list
where the last 40 service events are stored. After pressing on the “Service
History” button the service history list appears.
– Reset Fault History: with this function you can reset the fault history list.
After pressing on the “Reset Fault History” button a confirmation window
appears where the resetting of the fault history list must be confirmed.
– Reset Service History: with this function you can reset the service history
list. After pressing on the “Reset Service History” button a confirmation
window appears where the resetting of the service history list must be
confirmed.
– Export History: with the function “Export History” you can export the fault
and service history list to a USB memory stick via the USB port on the
control board (see chapter 7.3 – Saving fault and service histories to a
USB memory stick)
42
Operating the Condair ME control software
Diagnostics
– Input Diagnostics: with this function you can access the “Input Diagnostics” submenu where you can view different current input values the
control system is receiving. Detailed information can be found in chapter
5.5.2.1 – Input diagnostic functions – “Input Diagnostics” submenu.
– Output Diagnostics: with this function you can access the “Output Diagnostics” submenu where you can activate or deactivate different system
functions for diagnostic reason. Detailed information can be found in chapter
5.5.2.2 – Output diagnostic functions – “Output Diagnostics” submenu.
Note: By accessing the “Output Diagnostics” submenu the humidification
system is automatically switched to standby operation.
CAUTION!
The operation of the “Output Diagnostics” submenu requires wide knowledge of the control software and must be operated only by authorised
and trained personnel, since false operation may lead to damage of
system components.
– Relay Diagnostics: with the “Relay Diagnostics” function you can access
the “Relay Diagnostics” submenu where you can activate or deactivate
the relays of the optional remote operating and fault indication board.
Detailed information on the individual relay diagnostic functions can be
found in chapter 5.5.2.3 – Relay diagnostic functions – “Relay Diagnostics”
submenu.
Note: By accessing the “Relay Diagnostics” submenu the humidification
system is automatically switched to standby operation.
Operating the Condair ME control software
43
5.5.2.1 Input diagnostic functions – “Input Diagnostics” submenu
The following input values can be viewed after accessing the “Input Diagnostics” submenu.
Note: the input values can be accessed and viewed too, via the “Service Info” selection field in the
standard operating display.
Control
– Humidity control: Actual demand signal in %
– Temperature control: Temperature of area being controlled.
– Safety Chain: Actual status of the safety chain (“Open”= Safety chain
open, “Closed”= Safety chain closed)
– Enable: Actual status of the external enable switch, if present (“Off”=
switch open, “On”= switch closed).
ME Conditions
The ME Conditions section shows operating parameters of options, if installed:
– Incoming Air Temperature: Actual air temperature of the incoming air in
°C or °F if optional duct temperature sensor is installed.
– Water Temperature: Actual temperature of the water in the tank in °C or
°F if optional temperature sensor is installed.
– Conductivity: Actual conductivity of the water in the tank in µS/cm if
optional conductivity sensor is installed.
Level Floats
– Level: Actual level (1 to 6) in the tank of the evaporative module captured
by the level sensor.
– Dosing Pump Level Float: Actual level (“Empty”= Tank is empty or
“OK”=Level in the tank is OK) in the liquid tank of the optional system for
enhancing polyester media water absorbtion.
44
Operating the Condair ME control software
Hygiene & Safety
– 24V External Supply: Actual voltage of the external 24 V supply for
devices outside the control unit, such as humidistat, safety chain, etc.
– 10V External Supply: Actual voltage of the external 10 V supply for devices outside the control unit, such as humidity sensors, humidistat, etc.
– 5V Peripheral Supply: Actual voltage of the peripheral 5 V supply for
options fitted inside the control unit.
Valve Feedback
– Inlet Valve: Actual status of inlet solenoid valve (“Open” or “Closed”).
– Drain Valve: Actual status of gravity drain solenoid valve (“Open” or
“Closed”).
– Drain Pump: Actual status of drain pump (“On” or “Off”).
Pump Speed
– Speed Pump 1: Actual speed of stage pump 1 in % of the maximum
speed.
– Speed Pump 2: Actual speed of stage pump 2 in % of the maximum
speed.
– Speed Pump 3: Actual speed of stage pump 3 in % of the maximum
speed.
– Speed Pump 4: Actual speed of stage pump 4 in % of the maximum speed.
– Speed Pump 5: Actual speed of stage pump 5 in % of the maximum speed.
– Speed Pump 6: Actual speed of stage pump 6 in % of the maximum speed.
Note: only Condair ME XL systems have pump 6.
– Speed Pump 7: Actual speed of stage pump 7 in % of the maximum speed.
Note: only Condair ME XL systems may have pump 7.
Operating the Condair ME control software
45
Pump Feedback
– Stage Pump 1: Actual flow rate of stage pump 1 in kg/h or lb/hr.
– Stage Pump 2: Actual flow rate of stage pump 2 in kg/h or lb/hr.
– Stage Pump 3: Actual flow rate of stage pump 3 in kg/h or lb/hr.
– Stage Pump 4: Actual flow rate of stage pump 4 in kg/h or lb/hr.
– Stage Pump 5: Actual flow rate of stage pump 5 in kg/h or lb/hr.
– Stage Pump 6: Actual flow rate of stage pump 6 in kg/h or lb/hr.
Note: only Condair ME XL systems have pump 6.
– Stage Pump 7: Actual flow rate of stage pump 7 in kg/h or lb/hr.
Note: only Condair ME XL systems may have pump 7.
46
Operating the Condair ME control software
5.5.2.2 Output diagnostic functions – “Output Diagnostics” submenu
CAUTION!
The operation of the “Output Diagnostics” submenu requires wide knowledge of the control software
and must be operated only by authorised and trained personnel, since false operation may lead to
damage of system components.
The following diagnostic functions are available after accessing the “Output Diagnostics” submenu.
Hydraulic
– Inlet Valve: with this function you can open and close the inlet solenoid
valve.
– Drain Valve: with this function you can open and close the gravity drain
solenoid valve.
– Drain Pump: with this function you can start and stop the drain pump.
– Stage Pump 1: with this function you can set the speed of stage pump 1
in % of the maximum revolution speed.
– Stage Pump 2: with this function you can set the speed of stage pump 2
in % of the maximum revolution speed.
– Stage Pump 3: with this function you can set the speed of stage pump 3
in % of the maximum revolution speed.
– Stage Pump 4: with this function you can set the speed of stage pump 4
in % of the maximum revolution speed.
– Stage Pump 5: with this function you can set the speed of stage pump 5
in % of the maximum revolution speed.
– Stage Pump 6: with this function you can set the speed of stage pump 6
in % of the maximum revolution speed.
Note: only Condair ME XL systems have pump 6.
– Stage Pump 7: with this function you can set the speed of stage pump 7
in % of the maximum revolution speed.
Note: only Condair ME XL systems may have pump 7.
Operating the Condair ME control software
47
Hygiene & Safety
– UV Lamp: With this function you can switch on and off the optional UV
Lamp.
– Dosing Pump: With this function you can switch on and off the dosing
pump of the optional system for enhancing polyester media water absorbtion.
Control
– Control Select: With this function you switch the humidity or demand
control signal between voltage and current signal.
– Temp. Select: With this function you switch the temperature control signal
between voltage and current signal.
5.5.2.3 Relay diagnostic functions – “Relay Diagnostics” submenu
The following diagnostic functions are available after accessing the “Relay Diagnostics” submenu.
General
– Running: with this function you can activate (“On”) and deactivate (“Off”)
the relay “Running” on the remote operating and fault indication board,
which indicates that the unit is humidifying/cooling.
– Service: with this function you can activate (“On”) and deactivate (“Off”)
the relay “Service” on the remote operating and fault indication board,
which indicates that a service is due.
– Fault: with this function you can activate (“On”) and deactivate (“Off”) the
relay “Fault” on the remote operating and fault indication board, which
indicates that a fault is present.
48
Operating the Condair ME control software
5.6
Administration settings
5.6.1
Accessing “Administrator” submenu
Password: 8808
5.6.2
Administration settings – “Administrator” submenu
In the “Administrator” submenu you can:
– activate or deactivate password protection for main menu and setpoint adjustment access.
– perform software updates via a USB memory medium connected to the USB port
– reset user settings to factory defaults.
Password Settings
– Setpoint Password: with the function “Setpoint Password” you can
protect the setpoint input screen with the user password “8808” against
unauthorised access (“Yes”) or not (“No”).
– Main Menu Password: with the function “Main Menu Password” you
can protect the access to the main menu with the user password “8808”
against unauthorised access (“Yes”) or not (“No”).
Operating the Condair ME control software
49
Software Settings
– Software-Update: with the function “Software Update” you can update the
control software of the integrated controller (see chapter 6.11 – Performing
software updates).
– Ext.A.DB.A Update: with the function “Ext.A.DB.A Update” you can update the driver board software (see chapter 6.11 – Performing software
updates).
– Ext.A.DB.A.1 Update: with the function “Ext.A.DB.A.1 Update” you can
update the control board software (see chapter 6.11 – Performing software
updates).
– Restore Factory Defaults: with the function “Restore Factory Defaults”
you can reset all user settings to factory defaults.
50
Operating the Condair ME control software
6
Maintenance
6.1
Important notes on maintenance
Qualification of personnel
All maintenance work must be carried out only by well qualified and trained personnel authorised by
the owner. It is the owner’s responsibility to verify proper qualification of the personnel.
General notes
The instructions and details for maintenance work must be followed and upheld. Only carry out the
maintenance work described in this documentation.
The Condair ME Control must be maintained in the prescribed intervals, the cleaning work must be
carried out correctly.
Only use original spare parts from your Condair representative to replace defective parts or parts which
have elapsed their lifetime.
Safety and hygiene
Some maintenance work requires removal of the unit cover. Please note the following:
DANGER!
Danger of electric hazard!
Before carrying out any maintenance work take the Condair ME Control out of operation as
described in chapter 4.6 – Decommissioning the system and secure the system against inadvertent power-up. In addition take AHU out of operation as described in the operations instructions of the
AHU and secure the AHU against inadvertent power-up.
CAUTION!
The electronic components inside the control unit are very sensitive to electrostatic discharge.
Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of
the control unit, appropriate measures must be taken to protect the respective components against
damage caused by electrostatic discharge (ESD protection).
DANGER!
Health risk by inadequate maintenance!
Inadequately operated and/or poorly maintained adiabatic humidification/cooling systems may
endanger health. When inadequately operated and/or poorly maintained, micro-organisms
(including the bacterium which causes Legionnaire’s disease) may grow in the water system
and in the area of the humidification unit and may affect the air in the AHU/air duct.
Prevention: the adiabatic air humidification /air cooling system Cond­air ME must be correctly operated
as described in chapter 4 – Operation, and must be correctly maintained and cleaned in the prescribed
intervals as described in chapter 6 – Maintenance.
Maintenance
51
6.2
Maintenance intervals
In order to maintain operational safety and hygienic demands the Condair ME Control must be serviced
at regular intervals. The time interval for the complete system service is to be adapted to the operating
conditions. The hygiene status depends mainly on the quality of the humidifier water but also on the
adherence to the exchange intervals of the upstream air filter, the air velocity and the micro-biological
and chemical composition of the supply air. Therefore the service intervals must be determined for each
system separately.
The interval time for a complete system service is to be determined at commissioning. The default is
2000 hours of operation.
Depending on the encountered hygiene status when performing a complete system service the interval
time must be decreased or increased.
In any case the Condair ME Control system should receive a complete service at least once annually.
Note: We recommend to perform a minor service between two complete system service.
The interval time for complete system service can be programmed on the control unit. To determine the
interval time for a complete system service the above described procedure can be used. As soon as
the maintenance time has elapsed, a maintenance message is displayed to draw your attention to the
pending service.
6.3
Maintenance guide
The Condair ME unit will form part or your hot and cold water system and as such require you to undertake certain duties with regards to local regulations and bylaws concerning the control of Legionella
microbes in water systems. Your water sampling / testing and disinfection regime must be based on
results of a site specific risk assessment.
If any further assistance is required or you are interested in a planned maintenance quote, please contact
your Condair distributor.
Note: routine water sampling and testing is not included as part of a Condair service contract.
Please note that the information given in the table below is only to act as a guide which shows the work
to be carried out on “Minor Service” and “Complete System Service”.
Correct maintenance is vital to ensure optimum output, reliability and safety.
Operations
Minor
Service
Complete
System Service
Yes
Yes
Check Ag element of PureFlo Ag+ (if applicable)
Yes
Yes
Replace Ag element of PureFlo Ag+ (if applicable)
–––
Yes
Check water inlet solenoid valve
Yes
Yes
Clean water inlet solenoid valve
–––
Yes
Replace inlet flow restrictor
–––
Yes
Check all hoses and connectors
Yes
Yes
Clean inlet valve strainer
–––
Yes
Replace inlet water filter if applicable
52
Maintenance
Operations
Minor
Service
Complete
System Service
–––
Yes
Check distribution headers
Yes
Yes
Clean distribution headers
–––
Yes
Clean pumps
–––
Yes
Clean front section of tank
Yes
Yes
Clean internal of hydraulic module (use soft cloth only)
Yes
Yes
Check operation of level float and conductivity sensor (if applic­able)
Yes
Yes
Clean level float and conductivity sensor
–––
Yes
Check droplet separator (if applicable) and evaporator cassettes in suitable condition
Yes
Yes
Lightly brush evaporator cassettes if necessary, replace if heavily soiled
–––
Yes
Remove evaporator cassettes and clean all sections of tank and frame
structure
–––
Yes
Check and secure frame structure and seal
–––
Yes
Run unit and check for correct water level
Yes
Yes
Check all media for full saturation
Yes
Yes
Check drain pump operation and correct flow
Yes
Yes
Check operation of all distribution pumps
Yes
Yes
Measure flow rates to distribution headers
–––
Yes
Check water temperature and conductivity is within calibration
Yes
Yes
Check and secure all electrical connections
Yes
Yes
Check overall installation for leaks and damage
Yes
Yes
Check software settings
Yes
Yes
Check operation of submerged UV lamps
Yes
Yes
Replace UV kits
–––
Yes
Check any options as per relevant documentation
Yes
Yes
Complete disinfection as described in this manual
Yes
Yes
Check safety interlock and humidity/temperature control devices
–––
Yes
Check air velocity at face of evaporative cassettes matrix
–––
Yes
Reset all appropriate maintenance counters
Yes
Yes
Update service log book
Yes
Yes
Add DISIFIN XL disinfection sachet(s) to tank
Yes
Yes
Replace all feed hose
Maintenance
53
6.4
Dismantling and installation of components for maintenance
6.4.1
Dismantling and installation of the evaporative module
1. Take the Condair ME Control out of operation as described in chapter 4.6 – Decommissioning the
system and allow to drain and dry.
2. Switch the AHU off, and isolate the power and water supply to the AHU.
3. Disconnect distribution hoses from the connectors on the distribution heads, the wall feed-throughs
(if applicable) and the hydraulic module.
4. Remove droplet separator boxes (column by column):
•
Remove upper separator brackets.
•
Remove bank of separator boxes.
•
Remove lower separator brackets.
5. Remove evaporative cassettes (column by column):
•
Push box upwards and remove.
6. Remove distribution headers assemblies from topmost evaporative cassettes:
•
Remove plastic rivets fixing the distribution header assembly to the evaporative cassette.
•
Carefully lift off the distribution header assembly.
7. Remove optional UV lamp (if applicable).
8. Remove the cross bar (remember position).
Clean dismantled components, water tank, frame structure, blanking plates and air duct as described
in chapter 6.3 – Maintenance guide. If all components have been cleaned and dried, assemble the
evaporative module in the reverse dismantling order. Replace any defective components with new ones.
54
Maintenance
6.5
Consumables guide
Common consumables
Description
Standard Frequency (month)
DISIFIN XL
1
Disinfection chemical (sourced locally)
6
Descaling chemical (sourced locally)
as required
Inlet flow restrictor
24
Distribution header feed hose
24
Evaporative matrix cassette
– Wholesome mains water
– RO water
36 - 60
60 - 84 +
Option consumables
Description
Standard Frequency (month)
PureFlo Ag+ sediment filter
6
PureFlo Ag+ antimicrobial filter
12
UV bulb kit
12
Contact your Condair distributor for consumables list/order codes.
To help us ensure that the correct spares parts are sent, please confirm your unit serial and model
number with your order.
6.6
Health and safety requirements
In accordance with local regulations, users must take water samples for Legionella analysis. Samples
should be taken from the same places as described in chapter 6.7 – Routine water sampling and testing,
and the analysis carried out by an accredited laboratory which is part of an appropriately certified Legionella testing scheme. In the event that the Legionella content exceeds 102 cfu/l, the humidifier should
be switched off and specialist advice sought regarding its disinfection.
1. If biofilm (a slimy or gel-like deposit when wet, which might be dry and crisp in a dry system) is found
during any inspection of the humidifier or water system, the humidifier MUST be switched off and
not put back into operation until the system has been taken apart, scrubbed and thoroughly cleaned
with a suitable biocide with biofilm penetrating qualities such as 50 ppm chlorine dioxide solution.
This work should only be carried out by fully trained specialist organisations or individuals.
2. The control unit of the Condair ME Control must be left powered on to allow automatic flushing
and cleaning cycles to occur. If the control unit Condair ME Control is powered off for prolonged
periods, water stagnation might occur and contamination result, so the system, including any storage tanks or vessels should be drained and left dry. Before putting the system back into service, the
water pipework supplying the Condair ME Control should be purged carefully, avoiding the creation
of aerosols by splashing, and a water sample should be taken to ensure cleanliness. In the event
that the humidifier pipework contains any residual water or has remained damp, and the temperature
exceeded 20 °C (68°F), the Condair ME Control should be disinfected using an appropriate solution.
Contact your Condair representative for advice on water sampling and analysis, disinfection of systems,
service and maintenance.
Maintenance
55
6.7
Routine water sampling and testing
Hygiene
Your attention is drawn to local regulations and bylaws regarding the control of Legionellosis in water
systems. If inadequately maintained, water systems, of which any humidifier is a part, can support the
growth of micro-organisms, including the bacterium that causes Legionnaires’ disease. Condair Plc has
considered all aspects of this equipment to reduce as far as possible the risk of Legionnaires’ disease
and other similar conditions, but it is important that users are aware of their responsibilities under local
regulations in reducing the risk of Legionellosis.
To prevent the growth of Legionella, users are required to:
1. Carry out a risk assessment of the water system using a competent person, and implement an appropriate monitoring and control regime.
2. Avoid water temperatures which favour the growth of Legionella.
3. Avoid water stagnation.
4. Clean and disinfect the system in accordance with local regulations and bylaws, and the instructions
in this manual.
5. The Condair ME Control system must be connected to a clean, wholesome mains water supply and it is recommended that the supply water is chlorinated. It is the responsibility of the user to
ensure that the water system complies with local regulations and bylaws, particularly those for the
control of Legionella microbes. The use of mains water fed tanks and reservoirs is only permitted
as part of a managed water treatment system.
On commissioning and at regular intervals thereafter, test for possible water contamination using dipslides.
Take samples from the water supply, the evaporative cassettes and from the tank. Check for biofilm.
The dipslides should be incubated for 2 days at 30°C (86°F).
1. If the microbial count from the tank exceeds 103 cfu/ml, the system should be turned off, any biofilm
scrubbed clean and then disinfected using a 50 ppm chlorine solution for one hour before being put
back into use.
2. If the microbial count in the water supply to the evaporative module exceeds 103 cfu/ml, this suggests contamination of the water system within the building. The system should be turned off and
you should seek specialist advice on cleaning your water supply.
3. If the water temperature anywhere in the system regularly exceeds 20°C, (68°F) increase the frequency of water sampling. The frequency may be reduced if successive tests show a consistent
level below 103 cfu/ml.
56
Maintenance
6.8
Cleaning and disinfection
Before commencing cleaning and disinfection:
At initial commissioning we recommend the use of DISIFIN XL disinfection chemical. 1 sachet per 2 m
(6.6 ft) width of tank should be placed in the tank, allowed to dissolve and circulated around the system.
DISIFIN XL is 100% biodegradable, non-toxic and environmentally friendly and may be left to dissolve
and naturally flush away from the Condair ME Control after commissioning.
Note: If your system is equipped with the optional conductivity monitoring the conductivity measuring must
be deactivated via “Disifin” function in the service menu (see chapter 5.5.2 – Performing maintenance
functions – “Service” submenu). Otherwise you may get a conductivity fault message, since DISIFIN XL
disinfection chemical increase the conductivity in the tank.
For systems in operation or where the water quality or air quality is poor, it is recommended to dismantle
and scrub the system clean, to carry out a disinfection with a minimum of 50ppm chlorine or an appropriate disinfection solution circulated for 1 hour minimum or appropriate time. Please refer to the cleaning
and disinfection and method statement section to ensure that the relevant chemicals, equipment and
Personal Protective Equipment are available to carry out disinfection.
1. Risk assess the situation. This should include but is not limited to observance of local regulations
and the use of PPE, working from heights and ensuring a full understanding of the Condair ME
Control.
2. Coordinate with relevant responsible persons.
3. Check records (i.e sample results of microbiological control) for system history.
4. If possible, disinfection should be carried out when the building is unoccupied, with air flow off.
Evaporative humidifiers must be regularly cleaned and maintained, to prevent contamination especially
in industrial environments.
All surfaces requiring disinfection or cleaning must be in contact with the appropriate concentration of
disinfection solution for the correct contact period. The method statement for disinfection may need to
be adapted depending on the layout of the humidifier pipework. Additional procedures will be required
for supply water system pipework or water treatment systems prior to the humidifier.
Condair Plc recommends that routine disinfection should take place in the following situations:
•
At initial commissioning (for brand new systems use DISIFIN XL disinfection chemical).
•
At six monthly intervals as part of the maintenance regime.
•
If the system or part of it has been shutdown and/or substantially altered creating a risk of contamination.
•
During or following any increase of bacterial activity (as per recommendations in chapter 6.7 – Routine water sampling and testing) or outbreak or suspected outbreak of Legionellosis.
Maintenance
57
Recommended disinfection equipment
– Disinfection solution in accordance with manufacturers guidelines.
– Disinfection neutraliser (only if necessary).
– Disinfection solution test kit (to measure strength).
– Bucket of fresh water.
– Cleaning equipment.
– Mixing vessel / Measuring container.
– Risk assessment / test record sheets. Appropriate report/record
– Standard tools
– Appropriate PPE
– COSHH risk assessment / MSDS
6.9
Cleaning and disinfection method statement
Step 1 - Refer to the risk assessment
• Refer to the Manufacturers instructions and safety advice.
• Ensure the area is well ventilated.
• Ensure the Condair ME system is OFF and isolated from external controls.
• If the unit is already in operation there is low risks, check for correct operation before cleaning
and dismantling.
Note: if there are concerns over condition of unit, drain unit, flush water supply, and disinfect
tank before starting cleaning work.
• Drain system, dismantle unit and scrub tank fully. For complete disinfection remove droplet
separator banks (if applicable) and the evaporative cassettes to allow a full clean (refer to
maintenance section).
•
Consider appropriate maintenance requirements at this time including parts replacement i.e.
replacing distribution hoses to ensure that these are also disinfected.
•
Re-assemble the Condair ME system (refer to installation manual).
Step 2 - Mix disinfection solution
• Mix disinfection solution following the manufacturers instructions. Recommended 50ppm Chlorine
solution circulated for 1 hour minimum or appropriate time. NB: For larger or particularly unclean
systems this process may need to be repeated.
• Calculate the total water volume of the system using wet and dry weight values (see rating plate).
• Note: Solution loses strength over time and the solution may need to be increased through the
process or the disinfection process may need to be repeated.
Step 3 - Run the unit
• *Note the various control settings in case it is necessary to override them.
• Disable drain cycles or activate conductivity drain cycles to ensure solution will not be drained
unnecessary.
• Switch the control unit to the on and allow the tank to refill.
• Place the unit into a RUN condition (*control settings may need to be overridden, refer to the
configuration section of this manual).
• Check for correct operation and evaporative cassettes are full saturated.
58
Maintenance
Step 4 - Add disinfection solution
• Add the solution to the water sump tray and allow to flow through the evaporative cassettes.
• Measure the strength of the disinfection solution and check it is the correct strength in accordance with manufacturers guidelines.
• Note the strengths of the disinfection solution at 15 minute intervals and record on a record appropriately.
• Adjust solution strength as required.
Step 5 - Circulate disinfection solution
• Check all surfaces are wetted for desired time and correct solution.
Step 6 - Neutralise the disinfection solution – if required based on chemical used
WARNING!
If a neutralising solution is required, always ensure that the neutralising solution is used in accordance with the manufacturer’s guidance. Failure to follow the manufacturer’s guidance with regard
to neutralising the disinfection chemical may present a risk to health.
•
•
•
Mix neutralising agent as manufacturers instructions.
Allow the neutralising agent to disperse over the matrix and circulate in the sump tray.
Drain and measure the strength as per MSDS until the disinfection solution is down to desired
strength.
Step 7 - Drain the unit into foul drain
• Turn Off any fill cycle.
• Drain unit until empty into appropriate drain (depending on Risk Assessment) and rinse the tank
if necessary.
• Fill and drain unit including flushing over the evaporative cassettes and test to ensure that the
chemical is removed to the appropriate level.
• Wipe tank clean.
• *Where required, reset to original setting and put unit back into operation. Test for correct operation as per commissioning section of the manufacturers manual.
• Check for and complete maintenance requirements as per manufacturers instructions.
• Add DISIFIN XL chemical to the tank.
• Always leave work area clean, dry and tidy.
Step 8 - Re-start the Condair ME system
• Refer to the commissioning section of this manual.
If in doubt always contact your Condair distributor.
Maintenance
59
6.10
Resetting the maintenance indication on Condair ME Control
After completing maintenance work, the maintenance indication or the maintenance counter, respectively
must be reset. Proceed as follows to reset the maintenance counter:
1. Select in the “Service” submenu the function “System Service Reset”
Password: 8808
2. The reset dialogue appears in the display:
60
•
If the maintenance work has been completed, press the <Yes> button to reset the maintenance counter or the maintenance indication, respectively. The maintenance counter and
the maintenance indication are reset and the control unit is restarted.
•
if the maintenance work has not been completed, press the <No> button and you want abort the
reset procedure. The control unit returns to the “Service” submenu.
Maintenance
6.11
Performing software updates
To perform a software update of the control software of the Condair ME Control or one of its electronic
boards, proceed as follows:
1. Switch off the voltage supply to the control unit via the electrical isolator and secure switch in the off
position to prevent it from inadvertent power up.
2. Unlock the front door of the control unit and remove it.
3. Open control unit inner door.
4. Connect USB memory stick (max. length 75 mm/3") holding the update software to the USB port of
the control board.
5. Close control unit inner door.
6. Relocate the front door of the control unit and lock it with the screw.
7. Switch on power supply to the control unit via the electrical isolator.
8. Select in the “Administrator” submenu the desired software update function (e.g. “Control Software
Update”). Then, follow the instructions in the display of the control unit.
9. The update dialogue appears in the display:
•
Press the <Yes> button to start the update.
•
Press the <No> button to abort the update procedure.
10.During update a progress bar is shown in the display. If the update has completed the control unit
returns to the standard operating display.
11. Repeat steps 1 to 6 to remove USB memory stick.
Maintenance
61
7
Fault elimination
7.1
Fault indication on Condair ME Control control unit
Malfunctions during operation detected by the control software are indicated by a corresponding Warning message (operation still possible) or Fault message (operation not longer possible) in the operating
status field in the standard display of the control unit:
Warning
Temporary problems (e.g. water supply interrupted for a short time) or malfunctions which cannot cause damage to the system are indicated with a
warning message. If the cause of the malfunction disappears of its own accord
within a certain period of time, the alarm message will automatically switch
off otherwise an fault message is triggered.
Note: If warning indication has been switched off in the configuration menu,
malfunctions with warning character will not be indicated by the optional remote
operating and fault indication.
Fault
Malfunctions where further operation is not possible any longer or malfunctions
which can damage the system are indicated with a fault message, additionally the red LED below the touch panel light up. If such a malfunction occurs
the operation of the system is limited only or the system will be switched off
automatically.
By pressing on the maintenance and malfunction indication field in the standard operating display the
error list shown with all active warning and fault messages. By pressing on the corresponding Warning or
Fault entry additional information regarding the malfunction are displayed (see display on the far-right).
62
Fault elimination
7.2
Malfunction list
Important! Most operational malfunctions are not caused by faulty equipment but rather by improper
installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves
a thorough examination of the entire system. Often, the installation of the evaporative module has not
been properly executed, or the fault lies with the humidity/temperature control system.
Code
Message
Warning
Fault
–––
E18
–––
W20
E19
E20
Possible causes
Air Temp Snsr
Freeze Prot
Safety Chain
Note: depending on
the configuration
either Warning or
Fault is indicated
W21
–––
Information
High Water
Remedy
Condair ME Control stopped operation as the incoming temperature signal of the
optional anti freeze protection has failed.
Note: If – at any time – the temperature signal reading is correct again, the system
will continue with normal operation.
Sensor wiring broken or sensor defective
Check wiring, replace sensor if necessary
Sensor not connected
Correctly connect sensor to driver board
The ME stopped operating as the temperature of the incoming air fell below the
preset limit of the optional anti freeze protection.
Note: If – at any time – the air temperature of the incoming air rises above the limit
value again, the system will continue with normal operation.
Temperature too low for safe operation
of the Condair ME Control
No remedy
Temperature limit set wrong
Contact your Condair representative.
The Condair ME Control stopped operating as an external device opened the safety
chain. E.g. ventilation Interlock, safety humidistat, etc..
Note: If – at any time – the safety chain is closed again, the system will continue
with normal operation.
Ventilation interlock open.
If applicable, check/turn on ventilation
system.
Air flow monitor triggered.
Check ventilator/filter of the ventilation
system.
Safety humidistat triggered.
Wait. If applicable, check safety humidistat
Water overflow detected. Current operation status not affected.
Note: If – at any time – the normal operating water level is reached, the system will
continue with normal operation.
Inlet solenoid valve blocked in open
position or defective.
Check/replace inlet solenoid valve.
Gravity drain solenoid valve blocked in
closed position.
Check/replace gravity drain solenoid
valve.
Drain piping/drain trap clogged.
Check/Clean drain piping and drain trap.
Backpressure in drain trap.
Check drain trap venting to duct.
Assisted drain function not activated.
Contact your Condair representative.
Fault elimination
63
Code
Message
Warning
Fault
W22
E22
___
W28
E23
E28
Information
Possible causes
Water Inlet
Pump Error
ME Service
Water supply blocked: shut-off valve
closed/clogged, water pressure too low.
Check water supply (filter, pipes, etc.),
Check/open shut-off valve, Check water
pressure.
Water pressure too low.
Check water supply system.
Water treatment unit (fully demineralised
water) is regenerating.
Wait.
Inlet solenoid valve blocked or defective.
Check/replace Inlet solenoid valve.
Gravity drain solenoid valve open,
blocked in open position or not electrically connected (currentless open).
Check, electrically connect or replace
gravity drain solenoid valve.
Leakage in the water drain system.
Check/seal water drain system.
Control was not able to activate one or more stage pumps. Condair ME Control
automatically stopped operation. The fault message must be reset after elimination of malfunction.
Stage fault detection option not correctly
installed.
Contact your Condair representative.
Electrical pump connection broken.
Electrically connect or replace respective pump.
Pump defective.
Replace defective pump.
A warning is triggered if system service interval has exceeded. If the system service
is not performed and the system service counter is not reset within 30 days a fault
message is triggered.
Note: Condair ME Control continuous with normal operation.
System service is due.
W29
E29
UV Service
–––
64
Fault elimination
E31
No UV lamp
UV lamp OC
Perform system service and reset system
service maintenance counter.
A warning is triggered if UV service interval (replacement of UV bulb) has exceeded.
If the UV bulb is not replaced and the UV service counter is not reset within 30 days
a fault message is triggered.
Note: Condair ME Control continuous with normal operation.
Lifetime of UV bulb(s) (option) expired.
E30
Remedy
Tank (re)fill timeout. The Condair ME Control stopped operation as the tank could
not be (re)filled within a preset time. The Condair ME Control periodically tries to
fill the tank.
Note: If – at any time – the required water level is reached, the system will continue
with normal operation.
Replace UV bulb(s) and reset UV service
counter.
The Condair ME Control indicates fault as no UV lamp has been detected. Depending on the configuration of the “Shut Down” function (factory level) the Condair
ME Control stops or continuous operation. The fault message must be reset after
elimination of malfunction.
UV bulb defective
Replace UV bulb. Reset UV service
counter, if all bulbs are replaced.
UV bulb not wired or wiring broken.
Check wiring/Reconnect UV bulb.
Current consumption of UV lamp too high. Depending on the configuration of the
“Shut Down” function (factory level) the Condair ME Control stops or continuous
operation. The fault message must be reset after elimination of malfunction.
UV bulb broken.
Replace UV bulb. Reset UV service
counter, if all bulbs are replaced.
Short circuit on UV option.
Check wiring.
Code
Message
Warning
Fault
–––
E32
–––
–––
–––
–––
–––
W49
E44
E45
E46
E47
E48
–––
Information
Possible causes
Demand Snsr
Water Temp
Water Condu
Water Outlet
Level Sensor
Water Temp Snsr
Matrix Wash
Over
Remedy
Demand signal failed, Condair ME Control automatically stopped operation.
Note: If – at any time – the reading of the demand signal is correct again, the system
will continue with normal operation.
Sensor not connected.
Correctly connect sensor.
Incorrect sensor configuration.
Correctly configure sensor.
Sensor defective.
Replace Sensor.
Water supply temperature is too high, Condair ME Control changed to “Fill Cycle”
mode dilution. The fault message must be reset after elimination of malfunction.
Standing Water in inlet system.
Check water supply system.
Insufficient thermal insulation of inlet
pipework.
Insulate supply water pipe.
Water temperature limit set too low.
Check/adjust water temperature limit.
Temperature sensor of conductivity sensor configured incorrectly.
Contact your Condair representative.
Water supply conductivity is too high, Condair ME Control changed to “Fill Cycle”
mode dilution. The fault message must be reset after elimination of malfunction.
Water treatment defective/needs service.
Check/service water treatment system.
Conductivity limit set too low.
Check/adjust Conductivity limit.
Conductivity sensor configured incorrectly.
Contact your Condair representative.
Conductivity sensor defective.
Replace conductivity sensor.
Tank drain timeout. The Condair ME Control stopped operation as the tank could
not be drained within a preset time.
Note: If – at any time – the drain level is reached again, the system will continue
with normal operation.
Drain pump blocked/defective.
Check/replace drain pump.
Drain piping or drain trap clogged.
Check/clean drain piping and drain trap.
Level sensor stucked or short circuited.
Check/replace level sensor.
Backpressure in drain pipe.
Check drain pipe venting.
Water level sensor signal failed. The Condair ME Control stopped operation.
Note: If – at any time – the reading of the level sensor is correct again, the system
will continue with normal operation.
Level sensor not connected.
Correctly connect level sensor.
Level sensor defective.
Replace level sensor.
Water temperature sensor signal failed, Condair ME Control changed to “Fill Cycle”
mode dilution. The fault message must be reset after elimination of malfunction.
Water temperature sensor not connected.
Correctly connect water temperature
sensor.
Incorrect water temperature sensor configuration.
Correctly configure water temperature
sensor.
Water temperature sensor defective.
Replace water temperature sensor.
After installation of new evaporative cassettes a wash over procedure needs to
be carried out. The wash over is mandatory for evaporative cassettes with glass
fibre as evaporator media.
Condair ME Control is commissioned
first time.
Evaporative cassettes matrix must be
washed over with the Matrix wash over
function in service submenu.
Fault elimination
65
Code
Message
Warning
Fault
–––
E50
Information
Possible causes
Out of
Commissioning
Condair ME Control not energised for
more than 48 hours.
–––
–––
E51
E54
Dosing Level
Standing WTR
E55
Ag+ Service
Liquid used up during normal operation.
Refill liquid.
Incorrect floater connection.
Check/correctly connect floater.
Floater defective.
Replace floater sensor.
Standing water outside the tank detected. The Condair ME Control stopped operating as a leak of the tank or pipework has been detected.
Check system and seal any leaky components.
PureFlo Ag+ silver ion cartridge replacement interval exceeded, current operation
status not affected.
Lifespan of PureFlo Ag+ silver ion cartridge exceeded.
Replace PureFlo Ag+ silver ion cartridge.
PureFlo Ag+ silver ion cartridge replacement interval counter not reset after
replacement of cartridge.
Reset PureFlo Ag+ silver ion cartridge
replacement interval counter.
–––
E57
Activation
Activation code not yet entered. Normal operation not possible.
–––
E70
Water Condu
Snsr
Water conductivity sensor signal failed, Condair ME Control changed to “Fill Cycle”
mode dilution. The fault message must be reset after elimination of malfunction.
Activation code not yet entered.
–––
–––
E74
E82
Keep Alive
Driver Missing
–––
E83
Slave Address
Enter activation code.
Water conductivity sensor not connected.
Correctly connect water conductivity
sensor.
Incorrect water conductivity sensor configuration.
Contact your Condair representative.
Water conductivity sensor defective.
Replace water conductivity sensor.
Faulty communication, Condair ME Control automatically stopped operation. The
fault message must be reset after elimination of malfunction.
Driver board not connected.
Correctly connect driver board.
Wrong driver board connected.
Connect correct driver board.
Driver board defective.
Replace driver board.
Communication with driver board failed, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
RS485 Bus to driver board interrupted.
Contact your Condair representative.
Slave address changed during operation, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
Wrong driver address.
Check that each driver board connected
to one controller has a different address.
–––
E84
Driver faulty
Unspecific driver board fault, Condair ME Control automatically stopped operation.
The fault message must be reset after elimination of malfunction.
–––
E85
Driver ID Wrong
Driver board ID wrong, Condair ME Control automatically stopped operation. The
fault message must be reset after elimination of malfunction.
Driver board defective.
Wrong driver board connected or SAB
address wrong.
66
Disconnect water supply pipe and flush
supply pipe. Reconnect water supply
pipe and manually flush the entire water
system.
Level in the liquid tank of the optional system for enhancing polyester media water
absorbtion too low. Current operation status not affected.
Water leakage on evaporative module or
water piping inside the duct.
–––
Remedy
The water held in the supply pipework needs to be fully drained. Any contact with
the Condair ME Control has to be avoided.
Fault elimination
Replace driver board.
Contact your Condair representative.
Code
Message
Warning
Fault
–––
E86
–––
–––
E87
E88
Information
Possible causes
Driver Incompatible
Local 24V Supply
Local 5V Supply
Remedy
Version of driver board doesn't match, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.
Check fuses on driver board and replace.
Short circuit in control panel.
Check control panel.
Switched power supply unit defective.
Check/replace switched power supply
unit.
Local 24V supply out of valid range, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.
Check fuses on driver board and replace.
Short circuit in control panel.
Check control panel.
Switched power supply unit defective.
Check/replace switched power supply
unit.
Local 5V supply out of valid range, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
Fuses on driver board defective.
Check fuses on driver board and replace.
Short circuit in control panel.
Check control panel.
Switched power supply unit defective.
Check/replace switched power supply
unit.
–––
E89
Local Ref Supply
Local reference supply out of valid range, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
–––
E96
Peri. 5V Supply
Peripheral 5V supply out of valid range, Condair ME Control automatically stopped
operation. The fault message must be reset after elimination of malfunction.
Driver Board defective.
–––
E100
E103
to
E109
E110
E111
IO Inlet
IO Stage x
(e.g. IO Stage 1)
IO Drain
IO Drain Pump
Replace driver board.
Fuses on driver board defective.
Check fuses on driver board and replace.
Short circuit in control panel.
Check control panel.
Switched power supply unit defective.
Check/replace switched power supply
unit.
The smart output driver detected short circuit or open load on the output of the
inlet valve.
Inlet valve defective.
Replace inlet valve.
Distribution board defective.
Replace distribution board.
Inlet valve not connected.
Correctly connect inlet valve
The smart output driver detected short circuit or open load on the output of the
corresponding stage pump.
Corresponding stage pump defective.
Replace corresponding stage pump.
Distribution board defective.
Replace distribution board.
Corresponding stage pump not connect­
ed.
Correctly connect corresponding stage
pump.
The smart output driver detected short circuit or open load on the output of the
drain valve.
Drain valve defective.
Replace corresponding drain valve.
Distribution board defective.
Replace distribution board.
Drain valve not connected.
Correctly connect drain valve.
The smart output driver detected short circuit or open load on the output of the
drain pump.
Drain pump defective.
Replace drain pump.
Distribution board defective.
Replace distribution board.
Drain pump not connected.
Correctly connect drain pump.
Fault elimination
67
7.3
Saving fault and service histories to a USB memory stick
The fault and service histories of the Condair ME Control can be saved to a USB memory stick for
journaling and further analysis.
To save the fault and service histories to a USB memory stick, proceed as follows:
1. Disconnect power supply to control unit by switching off electrical isolator in the mains supply line.
Secure electrical isolator against inadvertent power-up.
2. Unlock retaining screw of front cover of control unit, then remove front cover.
3. Open control unit inner door.
4. Connect USB memory stick (max. length 75 mm/3") to the USB port of the control board.
5. Close control unit inner door.
6. Relocate front cover on control unit and lock it with the retaining screw.
7. Switch on power supply to control unit.
8. Select “Export History” function in the “Service” submenu. The data are saved as excel spreadsheet
on the USB memory stick.
9. When the data have been saved repeat steps 1 to 5 to remove USB memory stick.
7.4
Malfunctions without indication
Malfunction
Cause
Remedy
Residual water in the section
of the duct downstream of the
evaporative module.
Face velocity is too high. Systems
without droplet separator max
3.5 m/s (689 fpm), systems with
a droplet separator max. 4.5 m/s
(886 fpm).
Install droplet separator or reduce air
velocity in the duct.
Water tank, water piping or hydraulic Check/seal water tank, water piping
module is leaking.
and hydraulic module.
Water flow to media too high.
Check duty and software is correct.
Evaporative cassettes have become Check set up, replace evaporative
blocked with minerals.
cassettes, perform system service.
Humidity/cooling demand present however the Condair ME
Control does not humidify.
68
Fault elimination
Uneven or non laminar air flow.
Check design conditions of AHU.
Install perforated plate on the air
supply side.
Air on temperature is too low.
Check design conditions of AHU. and
increase temperature.
Shut-off valve in the water supply Open shut-off valve.
line closed.
Site control are not correct.
Prove controls and control module.
Malfunction
Cause
Maximum humidification/cooling Insufficient water supply capacity.
capacity is not reached.
Remedy
Check water supply, increase water
pressure.
Evaporative cassettes have become Check set up, replace evaporative
blocked with minerals.
cassettes, perform system service.
7.5
Notes on fault elimination
– For the elimination of faults set the Cond­air ME out of operation as described in chapter 4.6 – Decommissioning the system, disconnect control unit from the mains and close shut-off valve in the
water supply line.
DANGER!
Make sure the control unit is separated from the mains (check with voltage detector) and the shutoff valve in the water supply line is closed.
– The elimination of faults must be carried out by qualified and well trained professionals only.
Malfunctions relating to the electrical installation (e.g. replacement of the backup battery, replacement
of fuses) must be repaired by authorized personnel (e.g. licensed electrician). or by your Condair
representative’s service technician only.
CAUTION!
Electronic components are very sensitive to electrostatic discharge. When carrying out repairs
to the control unit, appropriate measures (ESD-protection) must be taken to prevent damage to
electronic components.
– Repair work and the replacement of faulty components must be carried out by your Condair representative’s service technician only!
Fault elimination
69
7.6
Replacing the fuses and backup battery in the control unit
The fuses of the control unit must be replaced by authorized personnel only (e.g. electrician).
Replace fuses of the control unit only with fuses matching the specifications below with the appropriate
nominal current capacity .
Never use refurbished fuses. Do not bridge the fuse holder.
To replace the fuses or the backup battery proceed as follows:
1. Disconnect control unit from the mains by switching off the electrical isolator and secure electrical
isolator in “Off” position against inadvertent switching on.
2. Undo the screw of the front cover of the control unit, then remove the front cover.
3. Open control unit inner door.
4. Replace desired fuse or the backup battery.
DANGER!
Fuse contact protection must be relocated after the fuse has been replaced.
5. Close control unit inner door.
6. Relocate front cover on control unit and lock it with the retaining screw.
7. Reconnect control to the mains by switching on the electrical isolator.
Contact protection
F2= 630 mA, slow acting
Backup battery 3V (CR 2032)
F1= 6,3 A, slow acting
Contact protection
70
Fault elimination
7.7
Resetting the fault status on Condair ME Control
To reset the error indication:
1. Disconnect the control unit of the Cond­air ME Control from the mains.
2. Wait approx. 5 seconds, then reconnect the control unit to the mains.
Note: If the fault has not been eliminated, the fault indication reappears after a short while.
Fault elimination
71
8
Taking out of service/Disposal
8.1
Taking out of service
If the Condair ME Control must be replaced or if the humidification system is not needed any more,
proceed as follows:
1. Take the Condair ME Control out of operation as described in chapter 4.6 – Decommissioning the
system.
2. Have the system components unmounted by a qualified service technician.
8.2
Disposal/Recycling
Components not used any more must not be disposed of in the domestic waste. Please dispose of the
individual components in accordance with local regulations at the authorised collecting point.
If you have any questions, please contact the responsible authority or your local Condair representative.
Thank you for your contribution to environmental protection.
72
Taking out of service/Disposal
9
Product specifications
9.1
Technical data
 
Condair ME Control
Supply voltage control unit
Supply voltage circulation pumps
Power consumption 1)
Control signals
Control accuracy
Max. admissible matric face velocity
Water supply
Water drain (outside diameter)
Admissible water supply pressure
Admissible water temperature
Water quality
100...240 VAC/50...60 Hz
24 Vdc/50...60 Hz
< 278 W (5 stages, no options fitted)
0...5 VDC
1...5 VDC
0..10 VDC
2...10 VDC
0...16 VDC
3.2...16 VDC
0..20 mA
4..20 mA
On/Off (via volt-free contact)
Control accuracy depends on air conditions, control
distance, water quality and on the number of On/Off
cycles
3.5 m/s (689 fpm)
4.5 m/s (886 fpm) with droplet separator
ø15mm (0.625") compression fitting
ø 54 mm (2.125") - Tank /
ø 28 mm (1.125") - Hydraulic module
2...5 bar (29...72.5 psi)
5...20 °C (41...68 °F)
Tap water, softened or fully demineralised water with a
max. of 100 cfu/ml
Admissible operating air temperature
10...60 °C (50...140 °F)
Admissible ambient temperature (Control unit)
1...40 °C (33.8...104 °F)
Admissible ambient humidity (Control unit)
Degree of protection of Control unit
Degree of protection of Hydraulic module
Conformity
Fire classification of evaporative media
1)
max. 75 %rh
IP21
IP42
CE marking
glass fibre media: A2-S2,-D0 (UL Class 1)
polyester media: DIN EN 53438 Class F1
Power consumption depending on the number of vertical evaporative cassettes banks and the options fitted
Product specifications
73
A1
A2
B1
B2
B3
B4
B5
B6
B7
B8
B9
BAT
UV
L N
F4
SUPPLY
PE L N
100...240 V/1~/50..60 Hz
U.V.
Q
X5
1 2 3 4 5 6 7 8 9 10 11 12 13 14
J1
CS
D.LVL
D.PUMP
F1
F2
F3
F4
H1
K2
PMC-24V100W1AA
X4
T2
PMC-24V100W1AA
T3
J3
JP4
JP5
JP/TR
K1
K2
LS1
LS2
M1
NF
J2
PMC-24V100W1AA
J2
J3
min.
°C
B9
B5
24/10 V
TMP
HUM
GND
24V E
Enable
J1
GND
24V IC
D–
D+
GND
D–
D+
GND
24V E
24V E
GND
GND
B8
B7
Y
Cable bridge demand signal
(for commisioning only)
Cable bridge if no safety chain is connected
Jumper fitted= 24 V on X16 (JP5 removed)
Jumper fitted= = 10 V on X16 (JP4 removed)
Jumper fitted on the last driver board
External safety chain
Cable harness from hydraulic module
Leakage monitoring board (option)
Sensor leakage monitoring (option)
Dosing pump (option)
Mains filter
B1
B2
B3
K1
X1
SF
X2
Current sensor (UV lamp)
Terminal level switch dosing liquid tank
Terminal dosing pump
Fuse mains supply (1 A slow acting)
Fuse 10/24 VDC supply(630 mA slow acting)
Internal fuse mains supply (6.3 A fast acting)
External fuse mains supply (10 A slow acting)
Remote operating and fault indication board
(option)
Cable bridge if no external On/Off switch is
connected
T1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Driver board
Control board
Ventilation interlock
Max. humidity monitor
Air flow monitor
Temperature and conductivity measuring
Sensor temperature and conductivity measuring
Level sensor dosing pump (option)
Demand or humidity/temperature signal
External On/Off switch (external enable)
Air temperature monitoring duct (option)
Backup battery (CR2032, 3V)
B6
M1
M
D.PUMP
D.LVL
F3
A A B B
X3
X4
X19
S1
B4
F2 (630 mAT)
X12
X11
UV
U.V.
X4
T1..T3
Q
S1
S3
SD
SUPPLY
SF
3V
Ethernet
RJ45
24V+
GND
–
+
GND
–
+
GND
–
+
GND
J14
J12
J10
J6
RS485
Electrical isolator
Humidification On/Off switch
On/Off switch control unit
Memory card
Terminal mains supply voltage
Snap feritte
(wrap cable 3 times through ferrite)
24V power supply (T3 for systems with 4 or 5
stages only )
UV lamp (option)
Terminal UV lamp
Terminal cable harness hydraulic module
LS2
CR2032
LS1
USB
BAT
SD
J2
Wiring diagram Condair ME Control
L N
N
L1
S3
X20
X10
A2
10.1
L N
N
L1
H1
X9
PE
N/GND
L/24V P
F1 (1 AT)
GND
24V P
X8
A1
Appendix
1 2
N
L
GND
LEVEL/T
PS3
PS2
PS1
24V P
L PE N
Y3
Y4
Y11
24V P
NF
CS
GND
GND
GND
24V 1
24V 2
24V 3
X7
Service Running Unit On
Control unit
Cnd bn
Cnd wh
Tmp bk
Tmp bu
Shield
SC1
SC2
GND
PS4
PS5
24V P
5V P
Y2
Y1
Y10
Y9
Y8
Y7
Y6
Y5
JP5: 10V
JP4: 24V
SHIELD
AIRT–
AIRT+
24V P
ERR FQ
N FQ1
N FQ2
GND
FQ+
GND
24V P
24V P
24V SCA
24V SCB
24V E
LVL DP
24V E
CS1
24V E
LEAK
24V E
GND
X13
X14
JP/TR
X15.1
X15.2
X16
PE
PE
PMP N
PMP L
PE
UV–
UV+
PE
DOSP–
DOSP+
Error
Appendix
1 2 3 4 5 6 7 8 9 10
74
10
CONSULTING, SALES AND SERVICE:
Condair Plc
Artex Avenue, Rustington,
Littlehampton, West Sussex.
BN16 3LN (UK)
TEL: +44(0)1903 850 200
FAX:
+44(0)1903 850 345
www.condair.co.uk

advertisement

Key Features

  • Touch screen control unit
  • Evaporative cassettes
  • Hydraulic module
  • Droplet separators
  • Remote operation and fault indication
  • Stage control
  • Hygiene functions
  • Conductivity monitoring
  • UV disinfection system
  • Dosing pump

Frequently Answers and Questions

What is the Condair ME Control?
The Condair ME Control is an adiabatic air humidification and air cooling system designed for use in AHU's or air ducts.
What are the key features of the Condair ME Control?
The Condair ME Control features a touch screen control unit, evaporative cassettes, and a hydraulic module. It can be equipped with a variety of options, including droplet separators, evaporative module blanking, and remote operation and fault indication.
How does the Condair ME Control work?
The Condair ME Control uses the principle of adiabatic humidification to cool and humidify air. Water is sprayed onto evaporative cassettes, which then cool and humidify the air as it passes through them.
What are the hygiene functions of the Condair ME Control?
The Condair ME Control includes a number of hygiene functions, including automatic flushing of the water system, periodic draining of the tank, and UV disinfection.
What are the options available for the Condair ME Control?
The Condair ME Control can be equipped with a variety of options, including droplet separators, evaporative module blanking, remote operation and fault indication, conductivity monitoring, UV disinfection, and dosing pumps.

Related manuals

Download PDF

advertisement