Kele Relays and Contactors
RELAYS & CONTACTORS
HUMIDITY
RELAYS &
CONTACTORS
Hundreds of Options in Stock, and Thousands of Options Available.
LY/MK Series | p. 1125
RV8H Series | p. 1132
G7L Series | p. 1150
RELAYS & CONTACTORS
Products manufactured
in the United States
Products that are
new to the catalog
MODEL/SERIESPAGE
Board Mounted Relays
MR Series — Air Products and Controls Multi-Voltage Control Relays . . . . . 1143
RIB M Series — Functional Devices Modular Panel Relays. . . . . . . . . . . . . . 1145
R E L AY S &
C O N TA C T O R S
Contactors
DPC Series — Definite Purpose Contactors . . . . . . . . . . . . . . . . . . . . . . . . . 1151
T30, T40, T60, T90 — EEC Definite Purpose Contactors. . . . . . . . . . . . . . . . 1152
Enclosed Relays
RIB, RIBT Pilot Series — Relay In A Box for Pump Level Switch Control. . .
RIB, RIBT Power Series — Functional Devices Relay In A Box . . . . . . . . . .
RIB01 and RIB02 Series — Functional Devices Relay in a Box Dry C
ontact Input Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PAM-1, PAM-4 — Air Products and Controls Multi-Voltage Relay Modules. .
RIB Series | p. 1133
RV8H | p. 1132
Plug-In General Purpose Relays
RH, RJ, RR Series — IDEC General-Purpose Relays. . . . . . . . . . . . . . . . . .
SH, SJ, SR Series — IDEC Relay Sockets . . . . . . . . . . . . . . . . . . . . . . . . . .
G2R-S, LY, MK Series — Omron General-Purpose Relays. . . . . . . . . . . . . .
P2RF, PF, PTF Series — Omron Relay Sockets . . . . . . . . . . . . . . . . . . . . . .
781, 782, 783, 784 Series — Magnecraft Relays. . . . . . . . . . . . . . . . . . . . . .
70-781D5-1, 70-782D-1, 70-783D-1, 70-784D-1 — Magnecraft Relay
Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RV8H Series — 6mm Interface Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20307 Series — Special Voltage Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1133
1135
1138
1147
1121
1123
1125
1127
1129
1131
1132
1155
Power Relays
KE375, KE900 Series — Power Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1148
G7L Series — Omron Power Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1150
DPC Series | p. 1151
kele.com
Specialty Relay Products
RIBL Latching Series — Relay In A Box Latching Relay Series. . . . . . . . . .
RIBTW Series — Functional Devices LonWorks Relay in a Box . . . . . . . . . .
RIBTW2401B-BC — Functional Devices BACnet Relay in a Box. . . . . . . . . .
RIBW Series — Functional Devices Wireless Control Relays . . . . . . . . . . . .
RSSDN — IDEC Solid State Relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model ALT — Alternating Relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PIL-2 — Kele Motor Starter Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1137
1139
1140
1141
1153
1155
1167
Timing Relays
RTE Series — IDEC Multifunction Electronic Timers. . . . . . . . . . . . . . . . . . .
TRU Series — Multifunction Timing Relays . . . . . . . . . . . . . . . . . . . . . . . . . .
821TD10H, TDRSOXP, TDRSRXP — Magnecraft Time Delay Relays . . . . .
438USA, 438USA-INT — Delay On Make / Interval Timers. . . . . . . . . . . . . .
TMV8000, KRDM — Delay-on-Make Timing Relays. . . . . . . . . . . . . . . . . . . .
TA, CT Series — Lockout Delay Timer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
KRDB, KSDB, TDUB — Delay-on-Break Timing Relays . . . . . . . . . . . . . . . .
1158
1160
1162
1156
1164
1165
1166
NEW!
RELAYS & CONTACTORS
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES
DESCRIPTION
IDEC general-purpose relays are available in the RH Series
blade-style relays and the RR Series pin-style relays and the
RJ Series compact relays.
The RH Series features a 10A switching capacity. They
are available in SPDT, DPDT, 3PDT, and 4PDT contact
configurations, driven by AC or DC coils, and they have blade
terminals for socket mounting.
The RR Series has a 10A contact rating. The RR Series
relays are available in SPDT, DPDT, and 3PDT configurations
driven by AC or DC coils, and they have pin or blade
terminals for socket mounting.
The RJ Series is compact to reduce space requirements.
They are available in a 12A SPDT version and an 8A DPDT
version. They are driven by AC or DC coils and have blade
terminals for socket mounting.
RJ Series RH Series
RR Series
FEATURES
• Blade style, pin style, and compact models
• Indicator light and/or check button available
• Surface or DIN rail mount
• UL recognized, CSA certified
SPECIFICATIONS
COIL RATINGS
CONTACT RATINGS
RH SERIES
12
24
AC 120
240
DC
12
24
RATED CURRENT (mA) ±15% @ 20°C
60 Hz
50 Hz
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
75 100 140 165 86 121 165 196
42 60.5 81
83
70
50
37
98
– 16.4 19.5
–
14.2 16.5 8.6
7.5
–
–
8.2 9.8
7.1 8.3 4.9
4.3
SPDT
DPDT
3PDT
4PDT
64
75
120
125
32
36.9
60
62
COIL RESISTANCE (Ω)
±10% @ 20°C
SPDT DPDT 3PDT 4PDT
165 39.3 25.3 21.2
83 153 103 84.5
– 10,800 7,360
16.5
– 12,100 9,120
8.3
SPDT DPDT 3PDT 4PDT
96
188 160 100
750 650 400 388
RR Series
RATED
VOLTAGE
12
24
AC 120
240
12
24
DC
Rated Current (mA) ±15% @ 20°C
60 Hz
50 Hz
245
210
121
105
24
20.5
12.1
10.5
120
60
COIL RESISTANCE (Ω)
±10% @ 20°C
365
182
35
18
–
–
AC
BLADE
& PCB
DC
BLADE
PCB
Rated Current (mA) ±15% @ 20°C
COIL RESISTANCE (Ω)
WITH LED1
WITHOUT LED1
±10% @ 20°C
60 Hz 50 Hz 60 Hz 50 Hz
47.5
24V
37.5
43.9
243
41.1
8.7
120V
7.5
8.8
6,400
7.4
1,080
22.1
25.7
24V
1,080
22.1
–
24V
1. LED indicator is only available on Blade relays.
Maximum continuous applied voltage
RH, RR
110% of rated voltage
RJ
140% of rated voltage
Pull-in voltage
RH, RR, RJ/AC
80% of rated voltage
RJ, RJ/DC
70% of rated voltage
Drop-out voltage
AC
30% or more of rated voltage
DC
10% or more of rated voltage
Contact material
RH
Silver cadmium oxide
RR
Silver
RJ
Silver nickel alloy
March 2014
GENERAL USE
RH1
RH2 RH3 RH4
7A 6.5A 5A
7.5A 7.5A
–
–
–
7A
–
–
–
HORSEPOWER RATING
RH1
RH4
RH3
RH2
–
1/3 hp
1/3 hp
–
1/6 hp
1/6 hp
–
–
–
–
–
–
RR SERIES (UL ratings)
VOLTAGE
RESITIVE (A)
240 AC
120 AC
30 DC
10
10
10
INDUCTIVE (A)
cos = 0.3
7
7.5
7
MOTOR LOAD (hp)
1/3
1/4
–
RJ Series (UL ratings)
Resistive Load
(Maximum)
Inductive Load
(Maximum)
RJ Series
MODELS
RH SERIES (UL ratings)
RESISTIVE
VOLTAGE RH1
RH2 RH3 RH4
240V AC 10A 7.5A 7.5A
120V AC –
10A 10A
30V DC 10A 10A
–
28V DC
–
10A
–
RELAYS & CONTACTORS
RATED
VOLTAGE
CONTACT
RJ1S
RJ2S
N.O.
N.C.
N.O.
N.C.
12A @ 250 VAC/30 VDC
12A @ 250 VAC; 6A @ 30 VDC
7.5A @ 250 VAC; 6A @ 30 VDC
7.5A @ 250 VAC; 3A @ 30 VDC
8A @ 250 VAC/30 VDC
8A @ 250 VAC; 4A @ 30 VDC
4A @ 250 VAC; 4A @ 30 VDC
4A @ 250 VAC; 2A @ 30 VDC
Contact resistance
RH
RR
RJ
Operate time
RH, RR
RJ
Release time
RH, RR
RJ
Min load
RH
RR
RJ
Operating temp
Agency approvals
Warranty
WE MAKE IT EASY.
19
50 mΩ maximum
30 mΩ maximum
50 mΩ maximum
25 ms maximum
15 ms maximum
25 ms maximum
10 ms maximum
24 VDC/30 mA, 5 VDC/100 mA
24 VDC/10 mA, 5 VDC/20 mA
5 VDC/100 mA
-22° to 158°F (-30° to 70°C)
UL-recognized component,
(RH, RR): File #E66043,
(RJ): File #E55996
CSA certified, File #LR35144;
CE certified (not RR blade style)
1 year
kele.com
888-397-5353 USA
1121
NEW!
1 .07 (2 .75)
in
(cm)
1 .07 (2 .75)
DIMENSIONS
1 .22 (3 .1)
0 .82 (2 .1)
0 .55 (1 .39)
RH1B
1 .07 (2 .75)
IDEC GENERAL-PURPOSE RELAYS
RH, RJ, RR SERIES
1 .07 (2 .75)
RELAYS & CONTACTORS
1 .60 (4 .1)
RH3B
RH2B
RH4B
RH Series Relays (blade)
1 .39 (3 .56) or less
1 .14 (2 .9)
1 .42 (3 .6)
RR2P
RR3PA
2 .19 (5 .55)
1 .42
(3 .64)
1 .87 (4 .8) or less
1 .13 (2 .38)
3
1 .418 (3 .6)
1 .418 (3 .6)
0 .2 (0 .5)
4
2
1 .42 (3 .64)
1
5
RR1BA, RR2BA, RR3B
1 .06 (2 .7)
RR Series Relays (pin)
RR Series Power Relays (blade)
0 .5 (1 .27)
RJ Series Relays (blade)
WIRING
Legend
NC
NO
1
1
4
1
2
4
1
2
3
5
5
8
5
6
8
5
6
7
8
9
9
12
9
10
12
9
10
11
12
13
(-)
RH1B
5
5
6
3
(+)14
13 (-)
6
8
4
(+)
1
9
10
2
(-)
8
RR2P
1
3
4
5
4
3
6
2
2
7
RH4B
7
3
(-)
(+)14
13 (-)
RH3B
7
2
11
(+)
RR3PA
2
1
3
1
2
3
5
4
6
4
5
6
8
9
7
A
(-)
7
9
7
B
A
B
A
(+)
(-)
(+)
(-)
RR2BA
RR1BA
1
B
RR3B
5
RJ1S
8
1
RJ2S
(+)
ORDERING INFORMATION
MODEL
RH1B
RH2B
RH3B
RH4B
DESCRIPTION
Relay, SPDT, blade (use SH1B-05 socket)
Relay, DPDT, blade (use SH2B-05 socket)
Relay, 3PDT, blade (use SH3B-05 socket)
Relay, 4PDT, blade (use SH4B-05 socket)
U
Standard relay
UL
Indicator light
ULC
Indicator light and check button
AC12V
12 VAC coil voltage
AC24V
24 VAC coil voltage
AC120V
120 VAC coil voltage
AC240V
240 VAC coil voltage
DC12V
12 VDC coil voltage
DC24V
24 VDC coil voltage
RH1B
U
MODEL
RJ1S
RJ2S
DESCRIPTION
Relay, SPDT (use SJ1S-05B socket)
Relay, DPDT (use SJ2S-05B socket)
C
No options
CL
LED indicator
A24
24 VAC coil voltage
A120
120 VAC coil voltage
D24
24 VDC coil voltage
RJ1S
C
19
AC24V
888-397-5353 USA
MODEL
RR2P
RR3PA
RR1BA
RR2BA
RR3B
DESCRIPTION
Relay, DPDT, 8 pin (use SR2P-05 or SR2P-06)
Relay, 3PDT, 11 pin (use SR3P-06 socket)
Relay, SPDT, 11 blade (use SR3B-05 socket)
Relay, DPDT, 11 blade (use SR3B-05 socket)
Relay, 3PDT, 11 blade (use SR3B-05 socket)
U
Standard relay
UL
Indicator light
ULC
Indicator light and check button
AC12V
12 VAC coil voltage
AC24V
24 VAC coil voltage
AC120V
120 VAC coil voltage
AC240V
240 VAC coil voltage
DC12V
12 VDC coil voltage
DC24V
24 VDC coil voltage
RR2P
U
AC24V
Example: RR2PUAC24V DPDT relay 8 pin with 24VAC coil
A24
DIN-3F
DIN-3F, BAM-1000
SH, SR, SJ Series
1122
(+)14
RH2B
4
Bottom View
RELAYS & CONTACTORS
13 (-)
14
(+)
4
RELATED PRODUCTS
35 mm DIN rail, steel, 39.4" (1m), RoHS compliant
DIN rail
Relay sockets
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
860
860
1123
March 2014
NEW!
RELAYS & CONTACTORS
IDEC RELAY SOCKETS
SH, SJ, SR SERIES
DESCRIPTION
The SH and SR Series of IDEC relay sockets are for use with
the IDEC RH / RR Series relays and RTE Series timers. The
SH and SR Series include both blade and pin style sockets
and are available for one, two, three and four pole relays.
The SH and SR sockets can be DIN rail or surface mounted.
The SJ Series of IDEC relay sockets are for use with the
IDEC RJ1S and RJ2S Series relays. They can be DIN rail or
surface mounted.
SJ1S, SJ2S
SH1B-05
FEATURES
•
•
•
•
Use with IDEC RH / RR / RJ relays and RTE timers
Screw terminals with captive wire clamp
Surface or DIN rail mount
UL recognized, CSA certified and CE approved
SR2P-05
SR2P-06
SH3B-05
SR3P-06
SR3B-05
SPECIFICATIONS
Socket Type
Rated
Voltage
Rated
Current
Hold Down Clip or
SpringWire Size
Wire Size
Weight
SJ1S-05B
Blade, DIN rail or surface mount
250V
12A
Lever: SJ9Z-C1 (provided)
Two 14 AWG
0.06 lb (0.03 kg)
UL recognized File #E62437,
CSA certified File #LR84913, CE
SJ2S-05B
Blade, DIN rail or surface mount
250V
8A
Lever: SJ9Z-C1 (provided)
Two 14 AWG
0.07 lb (0.034 kg)
UL recognized File #E62437,
CSA certified File #LR84913, CE
SH1B-05
Blade, DIN rail or surface mount
250V
10A
Spring: SYS-02F1;
Clip: SFA-101, SFA-202
Two 12 AWG
0.06 lb (0.03 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
SH2B-05
Blade, DIN rail or surface mount
300V
10A
Spring: SY4S-02F1;
Clip: SFA-101, SFA-202
Two 12 AWG
0.10 lb (0.05 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
Two 12 AWG
0.13 lb (0.06 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
Model
Approvals
SH3B-05
Blade, DIN rail or surface mount
300V
10A
Spring: SH3B05F1;
Clip: SFA-101, SFA-202
SH4B-05
Blade, DIN rail or surface mount
300V
10A
Spring: SH4B-02F1;
Clip: SFA-101, SFA-202
Two 12 AWG
0.16 lb (0.07 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
SR2P-05
8-Pin DIN rail or surface mount
300V
10A
Spring: SR2B-02F1 (RR2P only);
Clip: SFA-203 (RTE-P1 only)
Two 12 AWG
0.10 lb (0.05 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
SR2P-06
8-Pin, DIN rail or surface mount
300V
10A
Spring: SR2B-02F1 (RR2P only);
Clip: SFA-202 (RTE-P1 only)
Two 12 AWG
0.10 lb (0.05 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
SR3P-06
11-Pin, DIN rail or surface mount
300V
10A
Spring: SR3B-02F1 (RR only);
Clip: SFA-202 (RTE-P2 only)
Two 12 AWG
0.13 lb (0.06 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
SR3B-05
Blade, DIN rail or surface mount
300V
10A
Spring: SR3B-02F1 (RR3PA only);
Two 12 AWG
Clip: SFA-202 (RTE-P2 only)
0.14 lb (0.06 kg)
UL recognized File #E62437,
CSA certified File #LR35144e, CE
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
RELAYS & CONTACTORS
SH4B-05
SH2B-05
19
1123
NEW!
RELAYS & CONTACTORS
IDEC RELAY SOCKETS
SH, SJ, SR SERIES
DIMENSIONS
2.2 (5.6)
1.9 (4.9)
1.4 (3.5)
in
(cm)
0.1
(0.2)
1
in
(cm)
1.12
(2.85)
0.32
(0.8)
in
(cm)
0.32
0.86
(2.2)
(0.8)
5
0 .17 0 .22
(0 .44) (0 .55)
1
7
3
2
2
4
0.66
(1.7)
8
in
(cm)
0.16
dia. 1.83
(0.42) (4.8)
2.62
(6.7)
2.8
(7.1)
DIN
Rail
1.12
(2.85)
0.7
(1.88)
0 .31
(0 .79)
0.16 1.83
dia. (4.8)
(0.42) 0 .14 dia .
2.62
(6.7)
1
6
5
5
3
1.2 (2.9)
0.2 (0.4)
4
SJ1S,
SJ2S
SJ1S
0.63
(1.6)
0.78
(2.0)
0.32
(0.8)
0.98
(2.5)
DIN
Rail
0.16
dia. 1.83
(0.42) (4.8)
2.62
(6.7)
8
6
5
4
2
1
RELAYS & CONTACTORS
0.57
(1.5)
0.98
(2.5)
1.56
(4.0)
0 .31
(0 .79)
2.62
(6.7)
12
0.10
(0.25)
9
2 Mounting
Holes
0.16 dia
(0.42)
1.42
(3.6)
1.56
(4.0)
0.32
(0.8)
1.3
(3.3)
0.10
(.25)
1.97
(5.0)
(0.44)
6
4
5
3
2.34
(6.0)
DIN
Rail
0.86
(2.2)
0.31
(0.79)
1
2
8
2 Mounting Holes
0.16 dia. (0.42)
5
2
1
1.81
(4.6)
0.31
(0.79)
0.20
(0.55)
2.3
(5.9)
0.14 dia.
(0.36)
9
11 10
0.12
(0.25)
1.3
(3.3)
0.12
(0.25)
4
6
3
7
2
8
1
2 Mounting Holes
0.16 dia. (0.42)
0.78
(2.0)
1.12
(2.85)
1.14
(2.9)
7
6
5
4
0.31
(0.79)
1.14
(2.9)
2.9
(7.6)
2 Mounting Holes
0.16 dia. (0.42)
1.3
(3.3)
in
(cm)
1.12
(2.85)
6
3
0.14 dia.
(0.36)
2
M3.5
Terminal
Screw
0.16
(0.42) 2.2
(5.6)
5
2
9
.07
(0.2)
SR3P-06
1
A
B
1.45 (3.7)
1.69 (4.3)
4
DIN
Rail
3
0.57
(1.5)
0.98
(2.5)
8
1.45
(3.7)
7
2 Mounting
Holes
0.16 dia.
(0.42)
SR3B-05
ORDERING INFORMATION
19
MODEL
SH1B-05
SH2B-05
SH3B-05
SH4B-05
SJ1S-05B
SJ2S-05B
SR2P-05
SR2P-06
SR3B-05
SR3P-06
DESCRIPTION
Relay socket, SPDT blade type, DIN/surface mount
Relay socket, DPDT blade type, DIN/surface mount
Relay socket, 3PDT blade type, DIN/surface mount
Relay socket, 4PDT blade type, DIN/surface mount
Relay socket, SPDT blade type, DIN/surface mount
Relay socket, DPDT blade type, DIN/surface mount
Relay socket, DPDT pin type, DIN/surface mount
Relay socket, DPDT pin type, DIN/surface mount
Relay socket, three-pole blade type, DIN/surface mount
Relay socket, 3PDT pin type, DIN/surface mount
DIN-3F, BAM-1000
RH, RJ, RR series
RTE Series
888-397-5353 USA
kele.com
RELATED PRODUCTS
DIN rail
Relay
Time delay relay
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
0.17 0.20
(0.44) (0.55)
0.31
(0.79)
DIN
Rail
1.28 0.9
(3.3) (2.5)
1.41
0.31
(3.6)
(0.8)0.17 0.20
(0.44) (0.55)
DIN
Rail
1.3
(3.3)
5
SR2P-05
8
0.86
(2.2)
in
(cm)
0.64
(1.7)
0.32
(0.8)
1.81
(4.6)
1.0
(2.55)
0.7
(1.8)
0.16 1.05
dia. (2.5)
(0.42)
2 Mounting
Holes
0.16 dia
(0.42)
1.25
(2.85)
0.22
(0.55)
0.16
dia.
(0.42)
2 Mounting Holes
0.16 dia (0.42)
0.57
(1.5)
0.98
(2.5)
0.32
(0.8)
1.03
(2.6)
0.14 dia.
(0.36)
13
14
9 10 11 1
SR2P-06
1124
6
3
12
in
(cm) 0.17
7
0.04
(0.25)
7
4
0.17
(0.44)
SH4B-05
1.0
(2.55)
0.7
(1.8)
0.16 0.97
dia. (2.5)
(0.42)
2.34
(6.0)
8
2.03
(5.2)
0.16
dia.
(0.42)
13
10
1.40
(3.6)
DIN
Rail
1.83
(4.8)
SH3B-05
in
(cm)
1.12
(2.85)
0.7
(1.88)
0 .171.65 0 .22
(0 .44) (0 .55)
(4.2)
9
SH2B-05
in
(cm)
0 .14 dia .
(0 .36)
DIN
Rail
14
1.42
(3.6)
0.10
(0.25)
0.57
(1.5)
0.98
(2.5)
1.03
(2.6)
1.17
(3.0)
SH1B-05
0.32
(0.8)
1
12
0.63
(1.6)
in
(cm)
1.12
(2.85)
0.7
(1.88)
1.25
(3.2)
2 Mounting
Holes
0.16 dia
(0.42)
0.57
(1.5)
SJ1S, SJ2S
in
(cm)
4
0 .31
(0 .79)
14 13
9
0.10
(0.25)
SJ2S
5
(0 .36)
14 13
0.6
(1.6)
8
0 .17
(0 .44)
PAGE
860
1121
1158
March 2014
0.14 dia.
(0.36)
NEW!
RELAYS & CONTACTORS
OMRON GENERAL-PURPOSE RELAYS
G2R-S, LY, MK SERIES
DESCRIPTION
Omron general-purpose relays are available in the LY, MK,
and G2R-S Series. The LY Series is available in SPDT,
DPDT, 3PDT, and 4PDT contact configurations driven by AC
or DC coils. It has up to a 15A switching capacity and blade
terminals for socket mounting.
LY
MK
G2R-S
The MK Series is available in DPDT and 3PDT configurations
driven by AC or DC coils and has up to a 10A switch rating.
The MK Series has pin-type terminals for socket-mounting
and comes standard with a mechanical indicator and push-totest button.
P2RF
The G2R-S Series is available with SPDT or DPDT contacts
rated up to 10A and driven by AC or DC coils. They are
socket-mounted, and their small size saves space. They come
with a mechanical indicator, optional LED, and lockable test
button.
FEATURES
• Blade-style, pin-style and compact models
• DIN rail or surface mount
• UL recognized, CSA certified, CE certified
SPECIFICATIONS
COIL RATINGS
CONTACT RATINGS
LY SERIES
Contact
Form
SPDT
DPDT
MK SERIES
Rated
Voltage
24
AC
120
24
DC
Rated Current (mA)
60 Hz
88
18
56
Coil Resistance (Ω)
Rated Current (mA)
60 Hz
37.5
7.5
21.8
Coil Resistance (Ω)
68
1578
430
3PDT
4PDT
RELAYS & CONTACTORS
LY SERIES
Rated Current (mA)
Coil Resistance (Ω)
60 Hz
50 Hz
SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT SPDT DPDT 3PDT 4PDT
80 93.6 180 180 100
54
54
80
67
46
46
78
24
AC
9.2 14.8 16.4 10.8 10.8 17.3 19 4430 4430 2450 2200
120 9.2
36.9
36.9
DC 24
58.6 69
58.6 69 650 650 410 350
Rated
Voltage
UL Contact Ratings
15A @ 240 VAC (inductive)
15A @ 28 VDC (resistive)
1/2 hp @ 120 VAC (motor)
13A @ 120 VAC (resistive)
12A @ 240 VAC (inductive)
10A @ 28 VDC (resistive)
1/2 hp @ 120 VAC (motor)
10A @ 240 VAC (inductive)
10A @ 28 VDC (resistive)
1/2 hp @ 240 VAC (motor)
G2R-S SERIES
Rated
Voltage
24
AC
120
24
DC
Min operating voltage
Max continuous applied voltage
Drop-out voltage
AC
DC
Contact material
LY, G2R-S
MK
Contact resistance
Operating time
Release time
Min load
LY, G2R-S
MK
Agency approvals
Warranty
March 2014
MK SERIES
253
7,286
1,100
Contact
Form
DPDT
80% of rated voltage AC/DC
110% of rated voltage AC/DC
3PDT
30% or more of the rated voltage
10% (LY), 15% (MK, G2R-S) or more of
the rated voltage
Silver cadmium oxide
Silver
100 mΩ maximum
30 ms maximum
25 ms maximum
UL Contact Rating
10A @ 250 VAC (resistive)
10A @ 28 VDC (resistive)
7A @ 250 VAC (inductive)
10A @ 120 VAC (resistive)
10A @ 28 VDC (resistive)
10A @ 250 VAC (resistive)
7A @ 250 VAC (inductive)
19
G2R-S SERIES
Contact
Form
SPDT
100 mA/5 VDC
10 mA/1 VDC
UL-recognized component,
File #E41643 (LY, G2R-S), #E41515 (MK);
CSA certified, File #LR31928 (LY, G2R-S);
#LR41408 (MK); CE certified
1 year
WE MAKE IT EASY.
DPDT
kele.com
UL Contact Rating
10A @ 30 VDC (resistive)
10A @ 250 VAC (general purpose)
5A @ 30 VDC (resistive)
5A @ 250 VAC (general purpose)
888-397-5353 USA
1125
NEW!
RELAYS & CONTACTORS
OMRON GENERAL-PURPOSE RELAYS
G2R-S, LY, MK SERIES
DIMENSIONS
0 .51
(1 .3)
1 .14
(2 .9)
in
(cm)
1 .10
(2 .79)
1 .10
(2 .79)
1 .42
(3 .60)
0 .85
(2 .15)
1 .24
(3 .14)
LY
LY1/LY2
LY3
1 .14
(2 .9)
1 .4
(3 .5)
1 .63
(4 .14)
LY4
1 .36
(3 .45) max
0 .03
(0 .08)
G2R-1, G2R-2
2 .07
(5 .25) max
1 .36
(3 .45) max
MK2/MK3
WIRING
RELAYS & CONTACTORS
4
2
1
1
2
4
3
1
5
4
3
4
5
6
5
6
7
7
8
7
8
10
LY1
2
LY2
8
1
3
5
6
9
9
11
13
LY3
2
3
6
10
7
11
4
8
12
5
3
6
2
7
1
8
5
6
7
4
8
3
9
2
1
MK2
4
5
4
3
6
2
2
7
1
8
1 11 10
14
LY4
3
5
G2R-1
MK3
G2R-2
ORDERING INFORMATION
LY SERIES
MK SERIES
MODEL DESCRIPTION
LY
LY Series
1 SPDT contact configuration
2 DPDT contact configuration
3 3PDT contact configuration
4 4PDT contact configuration
I4 Push-to-test button (optional)
(two- and four-pole only when
combined with N option)
N LED indicator (optional)
AC24 24 VAC
DC24 24 VDC
AC120 120 VAC
19
LY
MODEL DESCRIPTION
MK
MK Series
2 DPDT contact configuration
3 3PDT contact configuration
P—
N LED indicator (optional)
— Two-pole
5 Three-pole
S Push-to-test button (standard)
AC24 24 VAC
DC24 24 VDC
AC120 120 VAC
2 I4 N AC24
MK
3 P N 5 S AC24
Example: LY2I4NAC24 DPDT relay with push-totest button, LED indicator, and 24 VAC coil.
Example: MK3PN5SAC24 3PDT relay with LED
indicator, push-to-test button, and 24 VAC coil.
Use with PTF Series sockets
Use with PF Series sockets
DINRSTL, DINRALU
PF, PTF, PRF Series
1126
888-397-5353 USA
kele.com
G2R-S SERIES
MODEL DESCRIPTION
G2R
G2R Series
1 SPDT contact configuration
2 DPDT contact configuration
S No options
SNI LED indicator, test button
AC24(S) 24 VAC
DC24(S) 24 VDC
AC120(S) 120 VAC
G2R
1
S
AC24(S)
Example: G2R1SAC24(S) SPDT relay with
24 VAC coil.
Use with P2RF Series sockets
RELATED PRODUCTS
DIN rail
Relay sockets
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
860
1127
March 2014
NEW!
RELAYS & CONTACTORS
OMRON RELAY SOCKETS
P2RF, PF, PTF SERIES
DESCRIPTION
The PTF and PF Series of Omron relay sockets are for use
with the Omron LY / MK Series Relays. The P2RF is for use
with the G2R-S relays. The PTF and PF Series include both
blade and pin style sockets and are available for one, two,
three, and four pole relays. The P2RF comes with a built-in
relay hold down mechanism. All of these sockets can be DIN
rail or surface mounted.
GENERAL SPECIFICATIONS
Rated Voltage
Rated Current
Terminals
250V
10A, 5A, 15A
M3.5 screws with captive wire
clamps
Dielectric Strength
1500V
Wire Size
Up to two 12 AWG
Materials Of Construction
Polyphenylene
Hold Down Clip or Spring
PFC-A1, PYC-A1
Mounting
DIN rail or surface mount
Approvals
UL-recognized component, File
#E87929; CSA certified, File
#LR31928; CE certified
FEATURES
•
•
•
•
Use with Omron LY / MK / G2R-S relays
Screw terminals with captive wire clamp
Surface or DIN rail mount
UL recognized, CSA certified and CE approved
GENERAL SPECIFICATIONS (IN (CM))
Two Mounting Holes
0.18 (0.46) dia
2 1
4
3.09
(7.84)
max
3
2.68
(6.80)
1.39
(3.53)
5
6
8 7
0.31
(0.78)
1.12
(2.84)
0.75
(1.90)
1.18
(2.99)
Two Mounting Holes
0.18 (0.46) dia
PTF11A for use with relay LY3
Hold-down clip: PYC-A1
Weight: 0.13 lb (0.06 kg)
3.09
(7.84)
max
3
2
1
6
5
4
2.68
(6.80)
1.39
(3.53)
9
8
19
7
10
11
0.31
(0.78)
1.46
(3.70)
RELAYS & CONTACTORS
PTF08A-E for use with relay LY1, LY2
Hold-down clip: PYC-A1
Weight: 0.1 lb (0.05 kg)
1.08
(2.74)
1.18
(2.99)
Two Mounting Holes
0.18 (0.46) dia
PTF14A-E for use with relay LY4
HoId-down clip: PYC-A1
Weight: 0.15 lb (0.07 kg)
3.09
(7.84)
max
4
3
2
1
8
7
6
5
2.68
(6.80)
1.39
(3.53)
12
11
14
10
9
13
0.31
(0.78)
1.79
(4.55)
March 2014
1.42
(3.60)
1.18
(2.99)
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1127
NEW!
RELAYS & CONTACTORS
OMRON RELAY SOCKETS
P2RF, PF, PTF SERIES
GENERAL SPECIFICATIONS CONT'D (IN (CM))
0 .28
(0 .7)
PF083A-E for use with relay MK2
HoId-down clip: PFC-A1
Weight: 0.05 lb (0.02 kg)
2 .05
(5 .2)
7
Two Mounting Holes
0 .18 (0 .45) dia
1 .39
(3 .54)
Two Mounting Holes
0 .17 dia (0 .42)
1 .3
(3 .3)
3
0 .16
(0 .4)
8
1
2
5
4
6
0 .83
(2 .1)
1 .61
(4 .1)
PF113A-E for use with relay MK3
HoId-down clip: PFC-A1
Weight: 0.1 lb (0.05 kg)
0 .28
(0 .7)
1 11
2
10
9
3
2 .05
(5 .2)
Two
Mounting Holes
0 .18 (0 .45) dia
1 .39
(3 .54)
1 .3
(3 .3)
4
5 6
0 .16
(0 .4)
P2RF-05-E for use with relay G2R-1
Weight: 0.07 lb (0.03 kg)
1 .69
(4 .28)
Five M3 .5
7 8
1 .22
(3 .1)
2 .40
(6 .1) max
4
2
RELAYS & CONTACTORS
3
3 .37
(8 .6)
max .
0 .14 (0 .36)
dia hole
1 .40
(3 .6)
5
M3 or
0 .14 (0 .36)
dia hole
1
0 .20
(0 .5)
P2RF-08-E for use with relay G2R-2
Weight: 0.07 lb (0.03 kg)
Eight M3 .5
3 .37
(8 .6)
max .
Terminal
Arrangement
2 .40
(6 .1) max
0 .61
(1 .5) max
2 .48
(6 .3) max
6
3
7
2
5
4
1 .40
(3 .6)
0 .14 (0 .36)
dia hole
M3 or
0 .14 (0 .36)
dia hole
8
1
0 .16
(0 .4)
19
0 .63
(1 .60) max
Mounting
Holes
2 .40
(6 .1) max
Terminal
Arrangement
Mounting
Holes
ORDERING INFORMATION
MODEL
P2RF-05-E
P2RF-08-E
PF083A-E
PF113A-E
PTF08A-E
PTF11A
PTF14A-E
DIN-3F, BAM-1000
NBS Series
1128
888-397-5353 USA
kele.com
DESCRIPTION
SPDT relay socket, DIN rail/surface mount (G2R-1 relay)
DPDT relay socket, DIN rail/surface mount (G2R-2 relay)
2PDT pin relay socket, DIN rail/surface mount (MK2 relays)
3PDT pin relay socket, DIN rail/surface mount (MK3 relays)
SPDT and DPDT blade relay socket, DIN rail/surface mount (LY1 and LY2 relays)
3PDT blade relay socket, DIN rail/surface mount (LY3 relays)
4PDT blade relay socket, DIN rail/surface mount (LY4 relays)
RELATED PRODUCTS
DIN rail
Block spades
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
860
March 2014
NEW!
RELAYS & CONTACTORS
MAGNECRAFT RELAYS
781, 782, 783, 784 SERIES
DESCRIPTION
The Magnecraft 781, 782, 783, and 784 Series are SPDT,
DPDT, 3PDT, and 4PDT plug-in style relays available with
common AC and DC coil voltages. They are equipped with a
mechanical flag indicator to show relay status in the manual
or powered condition. Full-featured versions of these relays
also include a bi-polar LED to show coil "on" or "off" status, a
push button that allows momentary manual operation without
the need for coil power, and a removable lock-down door that
can hold the push button and relay contacts in the operate
position.
784
783
FEATURES
782
• SPDT, DPDT, 3PDT, 4PDT configurations
• Flag indicator
• Optional LED and momentary/maintained pushbutton
• DIN rail/surface mount sockets
• Mating sockets:
781: 70-781D5-1A 783: 70-783D11-1
782: 70-782D8-1
784: 70-784D14-1
781
SPECIFICATIONS
781
782
783
784
≤85% of nominal
≤80% of nominal
≥10% of nominal
110% of nominal
0.9VA
0.7W
Continuous
≤85% of nominal
≤80% of nominal
≥10% of nominal
110% of nominal
1.2VA
0.9W
Continuous
≤85% of nominal
≤80% of nominal
≥10% of nominal
110% of nominal
1.5VA
1.7W
Continuous
≤85% of nominal
≤80% of nominal
≥10% of nominal
110% of nominal
1.5VA
2.0W
Continuous
Silver alloy
20A @ 277 VAC
10A @ 240 VAC Gen. Purp.
15A @ 28 VDC
1/2 hp @ 120 VAC
1 hp @ 250 VAC
100 mA @ 5 VDC or 0.5W
Silver alloy
15A @ 120 VAC
12A @ 277 VAC
12A @ 28 VDC
1/2 hp @ 120 VAC
1 hp @ 250 VAC
100 mA @ 5 VDC or 0.5W
Silver alloy
15A @ 120 VAC
12A @ 277 VAC
20A @ 28 VDC
1/2 hp @ 120 VAC
3/4 hp @ 250 VAC
100 mA @ 5 VDC or 0.5W
Silver alloy
15A @ 120 VAC
12A @ 277 VAC
15A @ 28 VDC
1/2 hp @ 120 VAC
3/4 hp @ 250 VAC
100 mA @ 5 VDC or 0.5W
Coil To Contacts
2500 Vrms
1600 Vrms
1600 Vrms
1600 Vrms
Across Open Contacts
1600 Vrms
1600 Vrms
1600 Vrms
1600 Vrms
Pole to Pole
—
1600 Vrms
2500 Vrms
2500 Vrms
20 msec
20 msec
100,000 operations
10,000,000 operations
Any
-40° to 131°F (-40° to 55°C)
0.064 lb (0.029 kg)
UL-recognized component
File #E43641, CSA certified
File 40787, CE: IEC 61810-1
1 year
25 msec
20 msec
100,000 operations
10,000,000 operations
Any
-40° to 131°F (-40° to 55°C)
0.08 lb (0.036 kg)
UL-recognized component
File #E43641, CSA certified
File 40787, CE: IEC 61810-1
1 year
25 msec
20 msec
20 msec
20 msec
100,000 operations
100,000 operations
10,000,000 operations
10,000,000 operations
Any
Any
-40° to 131°F (-40° to 55°C) -40° to 131°F (-40° to 55°C)
0.13 lb (0.06 kg)
0.18 lb (0.08kg)
UL-recognized component
UL-recognized component
File #E43641, CSA certified
File #E43641, CSA certified
File 40787, CE: IEC 61810-1 File 40787, CE: IEC 61810-1
1 year
1 year
CONTACTS
Contact Material
Contact Rating
Minimum load
DIELECTRIC STRENGTH
GENERAL
Operate Time
Release Time
Electrical Life @ Rated Load
Mechanical life @ No Load
Operating Position
Operating Temperature
Weight
Agency Approvals
Warranty
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
RELAYS & CONTACTORS
MODEL
COIL
Pull-in Voltage AC (50/60 Hz)
Pull-in Voltage DC
Dropout Voltage AC/DC
Maximum Voltage
Coil Power AC (60 Hz)
Coil Power DC
Duty
19
1129
NEW!
RELAYS & CONTACTORS
MAGNECRAFT RELAYS
781, 782, 783, 784 SERIES
DIMENSIONS
in (cm)
0.83 max
(2.10)
0.53
(1.4)
1.1 max
(2.79)
1.1 max
(2.79)
1.1 max
(2.79)
1.60 max (4.1)
781
1.2
(3.08)
1.6 max
(4.06)
1.1 max
(2.79)
782
783
784
WIRING
Bottom
View
Legend
NO
NC
1 (12)
1 (12)
4 (42)
1 (12)
2 (22)
4 (42)
1 (12)
2 (22)
3 (32)
4 (42)
5 (14)
5 (14)
8 (44)
5 (14)
6 (24)
8 (44)
5 (14)
6 (24)
7 (34)
8 (44)
9 (11)
9 (11)
12 (41)
9 (11)
10 (21)
12 (41)
9 (11)
10 (21)
11 (31)
12 (41)
13 (A1)
14 (A2)
13 (A1)
14 (A2)
781
782
13 (A1)
14 (A2)
13 (A1)
783
14 (A2)
784
RELAYS & CONTACTORS
Numbers correspond to Magnecraft socket terminals. Numbers in parentheses correspond to other brand socket terminals.
ORDERING INFORMATION
Model Description
KIT
Includes relay and mating socket. Leave blank to order the relay only.
781XAXC SPDT relay with flag indicator (requires 70-781D5-1A socket)
782XBXC DPDT relay with flag indicator (requires 70-783D11-1 socket)
783XCXC 3PDT relay with flag indicator (requires 70-783D11-1 socket)
784XDXC 4PDT relay with flag indicator (requires 70-784D14-1 socket)
12D 12 VDC coil (782XBXC only)
24D 24 VDC coil
24A 24 VAC coil
120A 120 VAC coil
240A 240 VAC coil (782XBXC only)
KIT - 781XBXC - 24A
19
Model
781XAXM4L
782XBXM4L
783XCXM4L
784XDXM4L
Description
SPDT relay with flag, LED, momentary/maintained push button (requires 70-781D5-1A socket)
DPDT relay with flag, LED, momentary/maintained push button (requires 70-782D8-1 socket)
3PDT relay with flag, LED, momentary/maintained push button (requires 70-783D11-1 socket)
4PDT relay with flag, LED, momentary/maintained push button (requires 70-784D14-1 socket)
12D 12 VDC coil
24D 24 VDC coil
24A 24 VAC coil
120A 120 VAC coil
240A 240 VAC coil
782XBXM4L - 24A
1130
888-397-5353 USA
Example: KIT-782XBXC-24A DPDT relay with 24 VAC
coil and 70-782D8-1 socket included.
Example: 782XBXM4L-24A DPDT relay with 24 VAC coil, LED, and push button
(socket not included).
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
MAGNECRAFT RELAY SOCKETS
70-781D5-1, 70-782D-1, 70-783D-1, 70-784D-1
DESCRIPTION
These Relay Sockets are for use with the Magnecraft
781, 782, 783, and 784 Series relays. These sockets have
fingersafe screw terminals and can be DIN rail or surface
mounted.
SPECIFICATIONS
70-782D8-1
70-781D5-1A
Voltage Rating
300V
Current Rating
15A
Terminals
M3.5 zinc-plated steel
Dielectric Strength
2000 Vms minimum
Wire Size
20-12 AWG
Operating Temperature-40° to 176°F (-40° to 80°C)
Mounting
DIN rail or surface mount
Flammability Rating
UL 94V-0
Approvals
UL-recognized component, File
#E70550, CSA certified File #4078
Weight
781D5
0.07 lb (0.032 kg)
782D
0.12 lb (0.055 kg)
783D
0.14 lb (0.062 kg)
784D
0.17 lb (0.077 kg)
Warranty
1 year
70-784D14-1
70-783D11-1
Hold-down clip
WIRING
SOCKET ACCESSORY MODULES*
1.18
(3.0)
0.67
(1.7)
1.10
(2.8)
in
(cm)
3.14
(8.0)
0.19 (0.51)
0.82
(2.1)
1.06
(2.6)
1.45 (3.7)
1.57 (4.0)
1.18
(3.0)
5
1
14 13
9
Socket: 70-781D5-1A
Hold-down clip*: 16-781SC
8
5
4
1
14
13
12
9
2.67
(6.8)
2.67
(6.8)
2.67
(6.8)
70-782D8-1
16-782SC
8
4
14
6
2
1.81 (4.6)
1.96 (5.0)
5
8
4
1
7
6
5
3
2
1
14
13
13
12 11 10 9
12 10 9
70-783D11-1
16-783SC
70-784D14-1
16-784SC
*Order metal hold-down clip and accessory modules separately.
For use with 70-783D11-1, 70-784D14-1
MOV suppressors
70-ASMM-24
24 VAC/VDC
70-ASMM-120
120 VAC/VDC
70-ASMM-240
240 VAC/VDC
Protection diodes
70-ASMD-250
6-250 VDC
Green LEDs
70-ASMLG-24
24 VAC/VDC
70-ASMLG-120/240 120/240 VAC/VDC
For use with 70-781D5-1A, 70-782D8-1
MOV suppressors
70-BSMM-24
24 VAC/VDC
70-BSMM-120
120 VAC/VDC
70-BSMM-240
240 VAC/VDC
Protection diodes
70-BSMD-250
6-250 VDC
Green LEDs
70-BSMLG-24
24 VAC/VDC
70-BSMLG-120/240 120/240 VAC/VDC
RELAYS & CONTACTORS
Plugging an accessory module into the
socket adds additional features to the
relay.
1.41 (3.6)
19
ORDERING INFORMATION
MODEL
70-781D5-1A
70-782D8-1
70-783D11-1
70-784D14-1
DINRALU
DINRSTL
NBS Series
March 2014
DESCRIPTION
Relay socket, SPDT, use with 781 Series relays
Relay socket, DPDT, use with 782 Series relays
Relay socket, 3PDT, use with 783 Series relays
Relay socket, 4PDT, use with 784 Series relays
RELATED PRODUCTS
DIN rail, aluminum, 39.4" (1m)
DIN rail, steel, 39.4" (1m)
Block spades
WE MAKE IT EASY.
PAGE
860
860
kele.com
888-397-5353 USA
1131
NEW!
RELAYS & CONTACTORS
6MM INTERFACE RELAYS
RV8H SERIES
DESCRIPTION
The RV8H Series 6mm interface relays provide a compact
solution for general purpose relay requirements. The RV8H
series Interface relays are ideal for HVAC and energy
management controllers, PLC and electronic systems,
industrial automation, panel builders, assembly machine
applications and other applications that require a high
switching capability in a compact space. Installation time is
greatly reduced with pre-assembled relays and sockets.
FEATURES
•
•
•
•
Class I, Division 2 and Class I, Zone 2 hazardous locations
Gold plated contacts
Pre-assembled relay and DIN mount socket
Lever for easy locking and removal of relay
RV8H-S-AD24
RV8H-L-AD24
SPECIFICATIONS
Allowable Switching Power
1500 VAC, 180W DC
Minimum Applicable Load6 VDC / 10mA
Mechanical Life
Over 10,000,000 operations
Operating Temperature -40 to 158°F (-40 to 70°C)
Operating Humidity
5 to 85% non-condensing
Weight
RV8H-L
0.07 lbs (0.03 kg)
RV8H-S
0.06 lbs (0.02 kg)
DIMENSIONS
RV8H-L Screw Terminal
A1(+) Coil
A1
A2
12
11
(13+)
14
14 NO
14 NO
A1(+) Coil
11 (13+) COM
2.92”
(74.2)
Internal Connection (bottom view)
RV8H-S Spring Clamp Terminal
A2(-) Coil
11 (13+) COM
2.74”
(69.6)
in
(mm)
2.74”
(69.6)
WIRING
2.92”
(74.2)
RELAYS & CONTACTORS
Number of Poles
1 pole
Contact Configuration
Form C, SPDT
Max. Allowable Contact Power
1500 VAC, 180W DC
Rated Load
250 VAC 6A, 30 VDC 6A
Contact Rating
6A
Allowable Switching Voltage
400 VAC, 125 VDC
A2(-) Coil
12 (NC)
12 NC
1.38”
(35)
3.46” (88)
1.38”
(35)
3.67” (93.4)
.24”
(6.1)
.24”
(6.1)
ORDERING INFORMATION
19
SCREW
TERMINALS
RV8H-L-D6
SPRING CLAMP
TERMINALS
RV8H-S-D6
6V
RATED
CURRENT
±15% (mA)
35
RV8H-L-D9
RV8H-S-D9
9V
RV8H-L-D12
RV8H-S-D12
12V
RV8H-L-D18
RV8H-S-D18
RV8H-L-D24
COIL VOLTAGE
CIRCUIT RESISTANCE
±10%(Ω)
AC
DC
POWER
CONSUMPTION
(W)
-
170
0.21
18.6
-
485
0.2
14.6
-
820
0.2
18V
11.6
-
1550
0.2
RV8H-S-D24
24V
10.6
-
2270
0.25
RV8H-L-AD12
RV8H-S-AD12
12V
15.5
755
800
0.2
RV8H-L-AD18
RV8H-S-AD18
18V
13.3
1365
1345
0.25
RV8H-L-AD24
RV8H-S-AD24
24V
RV8H-L-AD48
RV8H-S-AD48
48V
RV8H-L-AD60
RV8H-S-AD60
RV8H-L-AD110
RV8H-L-AD220
DC
13.7
1730
1790
0.33
4
11880
12230
0.2
60V
3.4
17600
17910
0.2
RV8H-S-AD110
110V - 125V
3.4 - 3.9
31790 - 31890 32450 - 32900
0.5
RV8H-S-AD220
220V - 240V
3.3 - 3.6
65670 - 66070 65940 - 68570
0.85
AC/DC
OPERATING CHARACTERISTICS
PICKUP
VOLTAGE
DROPOUT
VOLTAGE
MAXIMUM
VOLTAGE
90% MAX
7% MAX
110%
Note: To order Class 1 Division 2 RV8H Relays, add -C1D2 at the end of the part number.
1132
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES RELAY IN A BOX
RIB, RIBT PILOT SERIES
DESCRIPTION
The Relay In A Box (RIB) Pilot Series controls most BAS,
HVAC, low-horsepower motor and lighting applications. The
relays come mounted and pre-wired in a housing, saving the
installer the time, trouble, and expense of buying separate
components (relay, socket, mounting rail, and enclosure) and
assembling them on the job or at the shop.
The RIB Pilot Series has a protruding 1/2" or 3/4" NPT
nipple from which all wires exit (except T series). To install,
remove a conduit knockout in the equipment, insert the wires
and nipple through the hole, tighten the locknut, and connect
the wires.
RIB Pilot Series - 10A Relays
The RIB Pilot Series has relay contacts rated for 10A and
is used to control light electrical loads, drive power relays/
contactors, or sense the voltage being fed to electrical loads.
The RIB Pilot Series requires a low coil-drive current and is
provided with circuitry to allow powering the relay coil from a
wide range of AC or DC voltages.
RIBU1S
FEATURES
• Convenient and economical to use
• Relay status indicator via LED
• Coil uses low current and accepts a wide range of AC
and DC voltages
• Closed/Open/Auto switch option available
• Nipple- or screw-mountable
• Compact, gray plastic enclosure
• Color-coded wires for eliminating errors
• UL listed for UL916 Energy Management and UL864
Fire
• Made in the USA
RELAYS & CONTACTORS
RIBT Series - High/Low Voltage Separation
The RIBT Series is designed to provide physically separate
entrances for connections to the relay input coil and output
contacts. Relay contact wires exit the housing through a
1/2" or 3/4" NPT nipple. The cover of the RIBT Series is
removable, and the coil drive wires can enter the housing
through one of two convenient openings with star bushings
or 1/2" conduit. The coil drive wires are secured to screw
terminals within a separate wiring compartment in the
RIBT Series. Most of the RIB's in the Pilot Series are also
available in the RIBT Series.
RIBU1C
SPECIFICATIONS - GENERAL
Frequnecy
Wire Length
Life Rating
50/60 Hz
16" (40.6 cm)
10 million cycles minimum
mechanical
Relay Status
LED, ON - relay activated
Operating Temperature-30° to 140°F (-34° to 60°F)
Operating Humidity
5-95% RH non-condensing
Housing Type
Plenum rated, NEMA 1, NEMA 4
Conduit Hub
1/2" NPT, 3/4" NPT
Dimensions
A size enclosures 1.7" H x 2.8" W x 1.5" D
(4.32 x 7.11 x 3.81 cm)
B size enclosures
4.0" H x 4.0" W x 1.8" D
(10.16 x 10.16 x 4.57 cm)
G size enclosures 2.3" H x 3.2"W x 1.8" D
(5.84 x 8.13 x 4.57 cm)
March 2014
Approvals
UL listed, UL 916 Energy
Management UL 864 Fire, cUL listed,
CSFM, UL File S7312
1 year
Warranty
19
Coil pull-in/drop-out (nominal values)
COIL DRIVE
10-30 VAC/VDC
24 VAC/VDC
120 VAC
208-277 VAC
WE MAKE IT EASY.
PULL-IN DROP-OUT
DC AC DC AC
10
9
2.8
2.1
20 18
3.8
3
– 102
–
9
– 176
–
13
kele.com
888-397-5353 USA
1133
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES RELAY IN A BOX
RIB, RIBT PILOT SERIES
SPECIFICATIONS - PILOT SERIES
MODEL
TYPE
RIBU1C*
RIBU1C-N4†
1-SPDT
RIBU2C*
2-SPDT
RIBH1C*
RIBH1C-N4†
1-SPDT
RIBH2C*
2-SPDT
RIBU1SC*
1-SPDT
RIBH1SC*
1-SPDT
RIBU1S*
1-SPST-NO**
RIBU2SC
1-SPST-NO**
RIBU2S2
RIBU1SM
2-SPST-NO**
RIBH1S*
1-SPST-NO**
RELAYS & CONTACTORS
1-SPDT
RIBH1SM
1-SPST-NO**
1-SPST-NO**
COIL
DRIVE
10-30 VAC/VDC
120 VAC
50/60 Hz
10-30 VAC
208-277 VAC
50/60 Hz
10-30 VAC
208-277 VAC
50/60 Hz
G-1/2
–
–
–
–
10A resistive
10A resistive
480 VA pilot duty
480 VA ballast
600W tungsten
240W tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
10-30 VAC/VDC
208-277 VAC
50/60 Hz
Yes-2
N.C. - Closed
Open
N.O. - Closed
24 VAC/VDC
208-277 VAC
50/60 Hz
10-30 VAC/VDC
50/60 Hz
Status
G-1/2
Yes
–
A-1/2
B-1/2
–
B-1/2
–
A-1/2
Relay #2 of RIBU2SC
(gray)
NC
COM
(purple)
NO
(brown)
STATUS = 2nd Pole of
switch of RIBU1SM, RIBH1SM
Closed
Open
Auto
19
SPDT
Manual
Switch
Auto
Status
A-1/2
Yes
10A resistive
10A resistive
1/2 hp for N.O.
1/3 hp for N.C.
10A resistive
10A resistive
180 VA pilot duty
1/8 hp for N.C.
30 VDC
277 VAC
120/240 VAC
120/240 VAC
30 VDC
277 VAC
120 VAC
120 VAC
10A resistive
10A resistive
480 VA pilot duty
480 VA ballast
600W tungsten
240W tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
120-277 VAC
28 VDC
240-277 VAC
277 VAC
120 VAC N.O.
120 VAC N.C.
120-240 VAC
120-240 VAC
277 VAC
277 VAC
Switch ratings
20A
Wiring
Relay #1
Common - White/Yellow wire
10-30 VAC/VDC - White/Blue wire
120 VAC - White/Black wire
208-277 VAC - White/Brown wire
(yellow)
Relay #2 (if present)
Common
Common - White/Purple wire
(blue) N.C.
10-30 VAC/VDC - Gray/White wire
(orange) N.O. 120 VAC - White/Red wire
208-277 VAC - White/Orange wire
277 VAC
Relay #1
277 VAC
(orange)
Closed
277 VAC
(orange)
Open
120 VAC N.O.
Auto
120 VAC N.C.
120-240 VAC
Relay #2 of RIBU2S2
120-240 VAC
Closed
(brown)
277 VAC
Open
(brown)
277 VAC
Status Contact
on RIBU1SM and RIBH1SM:
Yes + 5A max @ 277 VAC
–
RELAY COIL
DRIVE DATA
120/240/277 VAC Relay #1
(blue)
NC
28 VDC
240/277 VAC
COM
(yellow)
277 VAC
NO
(orange)
120 VAC N.O.
120 VAC N.C.
Relay #2 (if present)
120/240 VAC
NC
(gray)
120/240 VAC
COM
(purple)
277 VAC
NO
277 VAC
(brown)
Auto
Manual
G-1/2
G-1/2
RELAY
CONTACT WIRING
Yes-2
10A resistive
480 VA pilot duty
G-1/2
480 VA ballast
600W tungsten
Yes
10-30 VAC/VDC
240W tungsten
G-3/4
120 VAC
1/3 hp for N.O.
50/60 Hz
B-3/4 Yes-2 1/6 hp for N.C.
1/4 hp for N.O.
Yes +
1/8 hp for N.C.
1-DPDT
SIB02S
RELAY
CONTACT RATINGS
Yes
RIB2402D
RIB2402D-N4†
3-SPST-NO
1-SPDT
A-1/2
G-1/2
24 VAC/VDC
120 VAC
50/60- Hz
RIBL4C
G-3/4
10-30 VAC/VDC
120 VAC
50/60 Hz
1-DPDT
3-SPST-NO
A-1/2
G-3/4
RIB2401D*
RIB2401D-N4†
RIBL3C
SIZE/ OVR
HUB SW
(blue)
(yellow)
(orange)
NC
COM
NO
(gray)
(purple)
(brown)
Relay #2
(black)
(black)
(blue)
(blue)
Relay #3
(yellow)
(yellow)
Relay #4 (if present)
(gray)
NC
(purple)
COM
NO
(brown)
277 VAC
30 mA @ 10 VAC
32 mA @ 12 VAC
42 mA @ 24 VAC
50 mA @ 30 VAC
25 mA @ 120 VAC
35 mA @ 208-277 VAC
12 mA @ 10 VDC
14 mA @ 12 VDC
16 mA @ 24 VDC
18 mA @ 30 VDC
(brown)
(purple)
(gray)
NC
COM
NO
Relay #1
Input Current
(blue)
(yellow)
(orange)
Wiring
Common - White/Yellow wire
24 VAC/VDC - White/Blue wire
120 VAC - White/Black wire
208-277 VAC - White/Brown wire
Input Current
24 mA @ 18 VAC
20 mA @ 20 VDC
32 mA @ 24 VAC
24 mA @ 30 VDC
40 mA @ 30 VAC
36 mA @ 30 VDC
31 mA @ 120 VAC (RIB2401D)
36 mA @ 208-277 VAC (RIB2402D)
Wiring
Common - White/Red wire
Relay#1 - White/Black wire
Relay#2 - White/Blue wire
Relay#3 - White/Yellow wire
Relay#4 - White/Brown wire
(if present)
Input Current
30 mA @ 10 VAC
12 mA @ 10 VDC
32 mA @ 12 VAC
14 mA @ 12 VDC
42 mA @ 24 VAC
16 mA @ 24 VDC
50 mA @ 30 VAC
18 mA @ 30 VDC
No Relay
Switch Only
ORDERING INFORMATION
Order by model number
* Models may be ordered in RIBT Series with high/low voltage separation.
** Can be ordered normally closed by adding - NC after model number.
† N4 has NEMA 4 housing
1134
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES RELAY IN A BOX
RIB, RIBT POWER SERIES
DESCRIPTION
The Relay In a Box (RIB) Power Series controls most BAS,
HVAC, low-horsepower motor and lighting applications. The
relays come mounted and pre-wired in a housing, saving the
installer the time, trouble and expense of buying separate
components (relay, socket, mounting rail, and enclosure) and
assembling them on the job or at the shop.
The RIB Power Series has a protruding 1/2" or 3/4" NPT
nipple from which all wires exit (except T series). To install,
remove a conduit knockout in the equipment, insert the wires
and nipple through the hole, tighten the locknut, and connect
the wires.
RIB Power Series - 20, 30A Relays
The RIB Power Series has relay contacts rated for 20 and
30A. They require modest coil drive current and are used for
direct switching and control of heavy electrical circuits, such
as large resistive, motor, and lighting loads.
FEATURES
• Convenient and economical to use
• Relay status indicator via LED
• Coil uses low current and accepts a wide range of AC
and DC voltages
• Closed/Open/Auto switch option available
• Nipple or screw mountable
• Compact, gray plastic enclosure
• Color-coded wires for eliminating errors
• UL listed for UL916 Energy Management and UL864
Fire
• Made in the USA
19
SPECIFICATIONS - GENERAL
Frequency
Wire Length
Life Rating
50/60 Hz
16" (40.6 cm)
10 million cycles minimum
mechanical
Relay Status
LED, ON - relay activated
Operating Temperature-30° to 140°F (-34° to 60°C)
Operating Humidity
5% to 95% non-condensing
Housing Type
NEMA 1, plenum rated
Conduit Hub
1/2" NPT, 3/4" NPT
Dimensions
A and G size
enclosures 2.3" H x 3.2" W x 1.8" D
(5.84 x 8.13 x 4.57 cm)
B size enclosures 4" H x 4" W x 1.8" D
(10.16 x 10.16 x 4.57 cm)
March 2014
RELAYS & CONTACTORS
RIBT Series - High/Low Voltage Separation
The RIBT Series is designed to provide physically separate
entrances for connections to the relay input coil and output
contacts. Relay contact wires exit the housing through
a 1/2" or 3/4" NPT nipple. The cover of the RIBT Series
is removable and, with star bushings or 1/2" conduit, the
coil drive wires can enter the housing through one of two
convenient openings. The coil drive wires are secured to
screw terminals within a separate wiring compartment in
the RIBT. Most of the RIBs in the Power Series are also
available in the T Series.
RIB, RIBT Power Series
Approvals
UL listed, UL 916 Energy
Management, UL 864 Fire, cUL
listed, CSFM, UL File S7312
1 year
Warranty
Coil pull-in/drop-out (nominal values)
COIL DRIVE
24 VAC/VDC
120 VAC
208-277 VAC
480 VAC
WE MAKE IT EASY.
PULL-IN DROP-OUT
DC
AC
DC AC
22
18
3.8
3
–
85
–
35
–
160
–
60
–
340
–
140
kele.com
888-397-5353 USA
1135
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES RELAY IN A BOX
RIB, RIBT POWER SERIES
SPECIFICATIONS - POWER SERIES
TYPE
COIL
DRIVE
RIB2401B*
1-SPDT
24 VAC/VDC
120 VAC
RIB2402B*
1-SPDT
24 VAC/VDC
208 - 277 VAC
MODEL
SIZE- OVR
HUB SW
G-1/2
–
–
G-1/2
RIB2401SB*
1-SPST-NO
24 VAC/VDC
120 VAC
G-1/2
Yes
RIB2402SB*
1-SPST-NO
24 VAC/VDC
208 - 277 VAC
G-1/2
Yes
120 VAC
B-1/2
–
RIB01P
1-DPDT
RIB02P
1-DPDT
208-277 VAC
B-1/2
–
RIB04P
1-DPDT
480 VAC
B-1/2
–
RIB24P*
1-DPDT
24 VAC/VDC
G-1/2
RELAY
CONTACT RATINGS*
20A resistive
1 hp
2 hp
20A ballast N.O.
10A ballast N.C.
10A tungsten N.O.
770 VA pilot duty
1110 VA pilot duty
277 VAC
120 VAC
277 VAC
120/277 VAC
120/277 VAC
120 VAC
120 VAC
277 VAC
20A resistive
1 hp
2 hp
20A ballast N.O.
10A ballast N.C.
10A tungsten N.O.
770 VA pilot duty
1110 VA pilot duty
277 VAC
120 VAC
277 VAC
120/277 VAC
120/277 VAC
120 VAC
120 VAC
277 VAC
20A resistive
20A resistive
15A resistive
1 hp
2 hp
3 hp
20A ballast
770 VA pilot duty
1,158 VA pilot duty
1,110 VA pilot duty
1,640 VA pilot duty
300 VAC
28 VDC, 15 VDC
600 VAC
120 VAC
240-277 VAC
480-600 VAC
277-480 VAC
120 VAC
240 VAC
277 VAC
480 VAC
RELAY
CONTACT WIRING
(blue)
(yellow)
(orange)
(orange)
(orange)
N.C.
Common
N.O.
Closed
Open
Auto
For normally closed, add -NC after
model number when ordering.
(blue)
(yellow)
(orange)
N.C.
Common
N.O.
(gray)
(purple)
(brown)
N.C.
Common
N.O.
–
RELAY COIL
DRIVE DATA
Wiring
Common - White/Yellow wire
24 VAC/VDC - White/Blue wire
120 VAC - White/Black wire
208-277 VAC - White/Brown wire
Input Current
75 mA @ 24 VAC
32 mA @ 24 VDC
42 mA @ 120 VAC
62 ma @ 208/277 VAC
Wiring
120 VAC - White/Black wires
208-277 VAC - White/Brown wires
480 VAC - White/Green wires
Input Current
100 mA @ 120-480 VAC
Wiring
24 VAC
White/Yellow wires
Input Current
RELAYS & CONTACTORS
125 mA @ 24 VAC
RIB2401SBC*
1-SPDT
24 VAC/VDC
120 VAC
RIB2402SBC*
1-SPDT
24 VAC/VDC
208 - 277 VAC
RIB24S2*
RIB02S2
120 VAC
277 VAC
120 VAC
240-277 VAC
120 VAC
277-480 VAC
120 VAC
277 VAC
G-1/2
Yes-2
208-277 VAC
RIB04S2
20A resistive
1 hp
2 hp
10A tungsten
20A ballast
Yes
Double 770 VA pilot duty
Pole 1,110 VA pilot duty
Yes-2
B-1/2
1-DPST-NO
277 VAC
120 VAC
277 VAC
120/277 VAC
120/277 VAC
120 VAC
120 VAC
277 VAC
G-1/2
24 VAC/VDC
RIB01S2
20A resistive
1 hp
2 hp
20A ballast N.O.
10A ballast N.C.
10A tungsten N.O.
770 VA pilot duty
1110 VA pilot duty
B-1/2
–
RIB243P*
RIB013P
1-3PST-NO
120 VAC
B-1/2
–
RIB023P
1-3PST-NO
208-277 VAC
B-1/2
–
RIB043P
1-3PST-NO
480 VAC
B-1/2
–
19
RIB24P30
1-DPDT
24 VAC/VDC
A-3/4
–
20A resistive
20A resistive
15A resistive
1 hp
2 hp
3 hp
5 hp
7.5 hp
20A ballast
1466 VA
2112 VA
30A resistive
25A resistive
15A resistive
1 hp
2 hp
3 hp
20A ballast
770 VA pilot duty
1,158 VA pilot duty
1,110 VA pilot duty
1,640 VA pilot duty
Double Pole Switch
Relay Pole #1
Relay Pole #2
(orange)
(brown)
Closed
(orange)
(brown)
Open
Auto
For normally closed, add -NC after
model number when ordering.
480 VAC
24 VAC/VDC
1-3PST-NO
(yellow)
Common
(blue)
N.C.
(orange)
N.O.
Auto
Manual
N.C. - Closed
Open
N.O. - Closed
300 VAC
28 VDC
600 VAC
120 VAC, 1 PH
240-277 VAC, 1 PH
480-600 VAC 1 PH
240 VAC, 3 PH
480 VAC 3 PH
277-480 VAC
240 VAC, 3 PH
480 VAC, 3 PH
(blue)
(blue)
N.O.
(yellow)
(yellow)
N.O.
(orange)
(orange)
N.O.
For normally closed, add -NC after
model number when ordering.
300 VAC
28 VDC
600 VAC
120 VAC
240-277 VAC
480-600 VAC
277-480 VAC
120 VAC
240 VAC
277 VAC
480 VAC
50 mA @ 24 VDC
Wiring
Common - White/Yellow wire
24 VAC/VDC - White/Blue wire
120 VAC - White/Black wire
208-277 VAC - White/Brown wire
Input Current
75 mA @ 24 VAC
42 mA @ 120 VAC
32 mA @ 24 VDC
Wiring
24 VAC/VDC White/Yellow wires
120 VAC White/Black wires
208-277 VAC White/Brown wires
480 VAC White/Green wires
Input Current
125 mA @ 24 VAC
50 mA @ 24 VDC
75 mA @ 120 VAC
95 mA @ 208-277 VAC
95 mA @ 480 VAC
Wiring
24 VAC/VDC - White/Yellow wires
120 VAC - White/Black wires
208-277 VAC - White/Brown wires
480 VAC - White/Green wires
Input Current
190 mA @ 24 VAC
140 mA @ 30 VDC
140 mA @ 120 VAC
170 mA @ 208-277 VAC
120 mA @ 480 VAC
(blue)
(yellow)
(orange)
N.C.
Common
N.O.
Wiring
24 VAC/VDC - White/Yellow wires
(gray)
(purple)
(brown)
N.C.
Common
N.O.
125 mA @ 24 VAC
Input Current
50 mA @ 24 VDC
*Not rated for electronic ballast
ORDERING INFORMATION
Order by model number
* Models may be ordered in RIBT Series with high/low voltage separation.
** Can be ordered normally closed by adding - NC after the model number.
† N4 has NEMA 4 housing
1136
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
RELAY IN A BOX LATCHING RELAY SERIES
RIBL LATCHING SERIES
DESCRIPTION
The RIBL Latching Series relays are activated by pulse
commands from a controller. The relay contacts are
mechanically latched in the closed position and the load will
remain on in the event of a control panel failure period. If
power is completely lost the contacts will remain in their last
state and the load will activate upon the return of normal
power or emergency power.
RIBL12B
FEATURES
•
•
•
•
•
•
NEMA 1 Plastic enclosure
UL Listed
Energy efficient (no coil draw when relay is active)
Optional override switch
Optional status LED
Optional auxilary contacts for status control
RIBL24SBM
WIRING
SPECIFICATIONS
50 ms
30 seconds (maximum)
50/60 Hz
16" (46 cm) 600 v
1 million cycles minimum
mechanical
Operating Temperature-30° to 140°F (-34° to 60°C)
Operating Humidity
5 to 95% RH non-condensing
Housing Type
NEMA 1, plenum rated
Conduit Hub
0.5" NPT nipple
Dimensions
B, SB
1.7" x 2.8" x 1.5"
(4.32 x 7.11 x 3.81 cm)
BM, SBM
2.3" x 3.2" x 1.8"
(5.84 x 8.13 x 4.57 cm)
Approvals
UL listed, UL508, C-UL, CE, RoHS
Warranty
1 year
Wht/Blu
24 Vac/dc (–)
LATCH
RELAYS & CONTACTORS
Operate Time
Pulse Length
Frequency
Wire Type
Life Rating
Org
Line
Wht/Yel
24 Vac/dc (+)
Org
Load
Wht/Red
24 Vac/dc (–)
UNLATCH
ORDERING INFORMATION
Model
Coil
Voltage
Coil Current
Latch / Unlatch
Voltage
Contact
Arrangement
Contact Rating
None
RIBL12B
RIBL12BM
RIBL12SB
12 VAC / DC
RIBL12SBM
182mA @ 10 VAC,
250mA @ 12 VAC,
165mA @ 10VDC,
198mA @ 12 VDC,
250mA @ 15VDC
Latch / Unlatch:
10 VDC / 11
VAC Minimum
One SPST
latching relay,
dual coil
RIBL24B
RIBL24BM
RIBL24SB
RIBL24SBM
March 2014
LED Indication
24 VAC / DC
175mA @ 20 VAC,
210mA @ 24 VAC,
92mA @ 20VDC,
110mA @ 24 VDC,
138mA @ 30 VDC
Latch / Unlatch:
20 VDC / 22
VAC Minimum
20A resistive @ 120277 VAC, 20A ballast
@ 120-277 VAC, 16A
electronic ballast @
120-277 VAC, 5540 W
tungsten @ 277 VAC,
720 VA @ 120-277
VAC, 2 hp @ 277 VAC,
3 hp @ 240 VAC, 1.5
hp @ 120 VAC
19
ON = Voltage detected
(contact closed)
None
ON = Voltage detected
(contact closed)
None
ON = Voltage detected
(contact closed)
None
ON = Voltage detected
(contact closed)
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1137
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES RELAY IN A BOX DRY CONTACT INPUT SERIES
RIB01BDC, RIB01SBDC, RIB02BDC, RIB02SBDC, RIB21CDC
DESCRIPTION
The dry contact input RIB Series is controlled by Class 2
circuits with a dry contact from a BAS controller, thermostat,
switch, another relay, or a solid-state switch. The power
to energize the RIB Series comes from the load being
controlled or a local power source near the relay. The relay
contacts are isolated from the input power and the dry contact
input.
FEATURES
•
•
•
•
RIB01SBDC
RIB21CDC
Remote power input, dry contact control
LED indication
UL listed
Optional override switch
SPECIFICATIONS
Coil Rating
RELAYS & CONTACTORS
Contact Rating
Frequency
Controlling Contact
120 VAC @ 42 mA, 208-277 VAC @
62 mA, 120-277 VAC @ 50 mA
20A resistive @ 277 VAC 1110 VA
pilot duty @ 277 VAC 770 VA pilot
duty @ 120 VAC 20A ballast 277
VAC N.O. 10A ballast 277 VAC N.C
240W tungsten 120 VAC N.C. 2 hp
277 VAC 1 hp 120 VAC, 10A general
use @ 250 VAC 10A resistive @ 30
VDC 1/2 hp 125-250 VAC 470 VA
pilot duty 120-240 VAC
50/60 Hz
SPST, 7 VDC, 1µA minimum
INSTALLATION
WIRING
RIB21CDC
120-277 VAC
Black
Neutral or phase red
Contact Output
(orange)
N.O.
POWER INPUT
RIB01BDC
RIB02BDC
120 VAC
208-277 VAC
Black
Black
Neutral white Neutral or phase red
RIB
Dry Contact
Input (Class 2)*
(white/red)
(white/blue)
19
Output Type
SPDT, SPST-NO
Wire Length
16" (40.6 cm)
Operating Temperature-30° to 140°F (-34.4° to 60°F)
Operating Humidity
5% to 95% non-condensing
Housing Type
NEMA 1, plemum, NEMA 1, plenum
Conduit Hub
1/2" NPT
Dimensions
RIB01, RIB02
2.3" H x 3.2" W x 1.8" D
(5.8 x 8.1 x 4.6 cm), RIB21CDC
1.7" H x 2.8" W x 1.5" D
(4.3 x 7.1 x 3.8 cm)
Approval
UL File E68805
Warranty
1 year
POWER INPUT
RIB02SBDC
RIB01SBDC
208-277 VAC
120 VAC
Black
Black
Neutral white Neutral or phase red
Dry Contact
Input (Class 2)*
RIB
Power
208-480 VAC
(yellow)
Common
Low-Voltage
Class 2 Wiring
(blue)
N.C.
Closed
Auto
•
•
•
Open
•
orange
orange
(white/red)
(white/blue)
* If more than one dry contact RIB is used in common, connect all white/blue wires together
BAS Controller,
Thermostat, or
Other Dry Contact
Switch
Minimum rating
7 VDC, 1µA
Power
Input
Relay
Contact
RIB located at
RTU or Load
Starter
RTU or
Other Load
ORDERING INFORMATION
MODEL
RIB01BDC
RIB01SBDC
RIB02BDC
RIB02SBDC
RIB21CDC
RIB21CDC-N4
1138
888-397-5353 USA
DESCRIPTION
Dry contact input RIB, 120 VAC, SPDT, 20A
Dry contact input RIB, 120 VAC, SPST-NO, 20A, override switch
Dry contact input RIB, 208-277 VAC, SPDT, 20A
Dry contact input RIB, 208-277 VAC, SPST-NO, 20A, override switch
Dry contact input RIB, 120-277 VAC, SPDT, 10A
Dry contact input RIB, 120-277 VAC, SPDT, 10A, NEMA 4 housing
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES LONWORKS RELAY IN A BOX
RIBTW SERIES
DESCRIPTION
The RIBTW Series of general-purpose power relays are
controlled from a remote location using a LONWorks network.
The relay is powered locally and communication with the
network is over a twisted pair of wires. Using standard
network variables (SNVTs) the relay can be commanded on
and off over the network and the relay state is communicated.
A separate digital input is provided to conveniently allow the
state of a status feedback signal from a current switch (or
other switched feedback device) to be communicated on the
LONWorks network.
FEATURES
RIBTW2401B
• Enclosed LonWorks relay with 20A contacts
• Additional dry contact input (powered by Class 2
circuit)
• Models with manual override switch
• LED indication of network status, relay status and
service status
• UL listed and LonMark certified, CE
WIRING
SPECIFICATIONS
Coil Rating
Contact Rating
Frequency
Relay Type
Duty
Transceiver Type
LED Indication
Green
Network status
Red
Relay status
Yellow
Service status
Operating Temperature-30° to 140°F (35° to 60°C)
Operating Humidity
5% to 95% non-condensing
Housing Type
NEMA 1, plenum rated
Conduit Hub
1/2' NPT
Dimensions
4"H x 4"W x 1.8"D (10.2 x 10.2 x
4.6 cm) with ½" NPT Nipple
Approvals
UL listed file #E68805, CE certified,
LonMark 3.3 certified, FCC, ROHS
Weight
0.82 lb (0.38 Kg)
Warranty
1 year
LON
LON
24 VAC/VDC
Common
Dry contact input
Class 2 circuit
LON
LON
24 VAC/VDC
Common
Dry contact input
Class 2 circuit
Closed Open
(white/yellow) (white/black) (blue) (yellow) (orange)
Neutral
120 VAC N.C. Comm N.O.
or (white/brown)
208-270 VAC
RIBTW2401B, RIBTW2402B
Auto
(white/yellow) (white/black) (orange) (orange)
Neutral
120 VAC
or (white/brown)
208-270 VAC
RIBTW2401SB, RIBTW2402SB
NOTE: When using 120, 200, or 277 VAC, there will be residual voltage on 24V terminals;
this is not intended to power external devices.
APPLICATION
NODE OBJECT
NV1
nvi
Request
NV2
nvo
Status
DESCRIPTION
Command to open/close relay
SNVT NAME
nvi Value
SNVT TYPE
Command status of relay
nvo Fb Value
SNVT_switch
nci Default
SNVT_switch
CLOSED LOOP ACTUATOR
Default state of relay on/off
NV1 nvi
Value
Invert status of Digital-In
NV2
nvo
Value Fb
nci Default
nci Max Receive T
OPEN LOOP SENSOR OBJECT
NV1 nvo
Value
nci Invert
nci Max Send T
nci Min Send T
Communication timer
Max time between updates
RELAYS & CONTACTORS
24 VAC @ 111 mA, 24 VDC @ 81
mA, 120 VAC @ 96 mA, 208-277
VAC @ 105 mA
20 A resitive @ 277 VAC,
20 A ballast N.O. @ 120/277 VAC,
10 A ballast N.C. @120/277 VAC,
10 A tungsten N.O. @ 120 VAC,
1110 VA piot duty @ 277 VAC,
770 VA pilot duty @ 120 VAC,
2 hp @ 277 VAC, 1 hp @ 120 VAC
50/60 Hz
SPDT, SPST-NO
Continous
FTT-10A
SNVT_switch
nci Max Receive T SNVT_elapsed_tm
nci Invert
SNVT_lev_disc
nci Max Send T
SNVT_elapsed_tm
Min time between updates
nci Min Send T SNVT_elapsed_tm
The relay will go to the default state when the communication
timer times out. Setting the timer value to zero will cause the
communication to never time out.
19
ORDERING INFORMATION
MODEL
RIBTW2401B-LN
RIBTW2402B-LN
RIBTW2401SB-LN
RIBTW2402SB-LN
March 2014
DESCRIPTION
LonWorks RIB relay, SPDT, 24 VAC/VDC or 120 VAC power input
LonWorks RIB relay, SPDT, 24 VAC/VDC or 208-277 VAC power input
LonWorks RIB relay, SPST-NO with manual override switch, 24 VAC/VDC or 120 VAC power input
LonWorks RIB relay, SPST-NO with manual override switch, 24 VAC/VDC or 208-277 VAC power input
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1139
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES BACNET RELAY IN A BOX
RIBTW2401B-BC
DESCRIPTION
The Model RIBTW2401B-BC is an open-protocol relay controlled
from a remote location using a BACnet network. These are also
available in the LonWorks protocol. The relay is powered locally, and
communication with the network is over a twisted pair of wires. Using
standard BACnet or LonWorks objects, the relay can be commanded
on and off over the network and the relay state communicated back.
A separate digital input is provided to conveniently allow the state
of a status feedback signal from a current switch (or other switched
feedback device) to be communicated on the network. Click on the
related parts and pricing tab for a more complete listing of available
models.
FEATURES
• Enclosed BACnet relay with 20A contacts
• Additional dry contact input (powered by Class 2
circuit)
• LED indication of network status and relay status
• UL listed and BACnet compatible, CE
Relay
override
MSTP
0 1 1 2 3 4 5 6 7 8 9 10 1112
LSB
Dry contact input (Class 2 circuit)
Baud
rate
24 VAC/VDC
BACnet®
Compatible Relay
MSB
Network
Dry contact
Digital input
REF
A(–)
B(+)
WIRING
APPLICATION
RELAYS & CONTACTORS
RIBTW2401B-BC
MS/TP ADDRESS
Connect jumper for terminating
resistor. Disconnect for no
terminating resistor.
*24 V or 120 V required but not both
24 VAC/VDC
Common
Occupancy sensor
Line
Neutral
(orange)
(yellow)
(white/yellow) (white/black) (blue)
Neutral
120 VAC
N/C
Load
(yellow)
Comm
(orange)
N/O
NOTE: When using 120 VAC, there will be residual voltage on 24V terminals;
this is not to be used for powering external devices.
SPECIFICATIONS
Supply Voltage
Contact Rating
19
Frequency
Relay Type
Duty
Life Expectancy
Baud Rate
24 VAC @ 11 mA, 24 VDC @ 81 mA,
120 VAC @ 96 mA
20A resistive @ 277 VAC, 20A ballast
N.O. @ 120/277 VAC, N.C. @ 277
VAC, 10A tungsten N.O. @ 120 VAC,
1110 VA pilot duty @ 277 VAC, 770
VA pilot duty @ 120 VAC, 2 hp @
277 VAC, 1 hp @ 120 VAC
50/60 Hz
SPDT
Continuous duty
10 million cycles minimum
9600, 19200, 38400, 57600, 76800,
and 115200
Green: network status,
Red: relay status
Operating Temperature-30° to 140°F (35° to 60°C)
Operating Humidity
5% to 95% non-condensing
Housing Type
NEMA 1, plenum rated
Conduit Hub
1/2" NPT
Dimensions
4" H x 4" W x 1.8" D
(10.2 x 10.2 x 4.6 cm);
1/2" NPT nipple
Approvals
UL listed file #E68805, CE certified,
BACnet certified
Weight
0.83 lb (0.38 Kg)
Warranty
1 year
LED Indication
ORDERING INFORMATION
MODEL
RIBTW2401B-BC
RIBTW2402B-BC
1140
888-397-5353 USA
kele.com
DESCRIPTION
BACnet RIB relay, SPDT, 24 VAC/VDC or 120 VAC power input
BACnet RIB relay, SPDT, 24 VAC/VDC or 208/277VAC power input
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES WIRELESS CONTROL RELAYS
RIBW SERIES
DESCRIPTION
The RIBW Series wireless control relays are enclosed and
offer easy installation without the expense of traditional
hard wiring. The control relays are used in tandem with the
wireless transmitter Model RIBWE24TDC-EN. Relays can be
mounted up to 100 ft (30 m) from the transmitter.
FEATURES
•
•
•
•
RIBW01B-EN2
Enclosed wireless relay with 20A contacts
Eliminates hard wiring
LED indication of relay status
Continuous duty coil
RIBW277B-EN2
Relay Type
Coil Rating
RIBW01B-EN
RIBW227B-EN Frequency
Contact Rating
SPDT, continuous duty
120 VAC @ 73 mA
277 VAC @ 80 mA
50/60 Hz
20A resistive @ 120/277 VAC, 20A
ballast N.O. @ 120/277 VAC, 10A
ballast N.C. @120 VAC, 1110 VA pilot
duty @ 120 VAC, 2 HP @ 277 VAC,
1 HP @ 120 VAC
Life Expectancy
10 million cycles minimum
LED Indication
Red: on = energized
Operating Temperature-30° to 140°F (35° to 60°C)
Operating Humidity
5% to 95% non-condensing
Dimensions
2.3"H x 3.2"W x 1.8"D
(5.8 x 8.1 x 4.6 cm) with 0.5"
(1.27 cm) NPT nipple
Housing Type
NEMA 1, plenum rated
Wire Length
16" (46CM) 600 v
Approvals
UL Listed File E68805, CE, Rohs
Warranty
1 year
March 2014
TRANSMITTER
Supply Voltage
24 VAC @ 42 mA; 24 VDC @ 38 mA,
50/60 Hz
Frequency
315 mHz
Transmission Power 10mW EIRP, maximum
LED Indication
On: input activated; slow blink: input
deactivated; fast blink: transmitting
Operating Temperature-30° to 140°F (35° to 60°C)
Operating Humidity
5% to 95% non-condensing
Dimensions
1.7"H x 2.8"W x 1.5"D
(4.3 x 7.1 x 3.8)
Housing Type
NEMA 1, plenum rated
Wire Length
16" (46 cm) 600V
Warranty
1 year
WE MAKE IT EASY.
kele.com
888-397-5353 USA
RELAYS & CONTACTORS
SPECIFICATIONS
19
1141
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES WIRELESS CONTROL RELAYS
RIBW SERIES
WIRING
(blue)
(white/yellow)
24 VAC/VDC
(white/yellow)
24 VAC/VDC
(black)
120 or
277 VAC
(white)
Neutral
Wireless
receiver
control
unit
Dry contact
input
(white/blue)
Wireless
transmitter
control unit
Wireless
transmission
(white/red)
(orange)
Low voltage control input
(white/black)
(white/black)
Relay Wiring
Transmitter Wiring
RELAYS & CONTACTORS
ORDERING INFORMATION
MODEL
RIBW01B-EN2
RIBW24B-EN2
RIBW208B-EN2
RIBW240B-EN2
RIBW277B-EN2
RIBWE24TDC-EN2
DESCRIPTION
2-way wireless encl relay dry-contact, 20A 120 VAC
2-way wireless encl relay dry-contact, 20A 24 VAC
2-way wireless encl relay dry-contact, 20A 208 VAC
2-way wireless encl relay dry-contact, 20A 240 VAC
2-way wireless encl relay dry-contact, 20A 277 VAC
Wireless trasmitter for RIB relays
RELATED PRODUCTS
PAGE
WWS Series
Wireless switch transmitter679
WWS Series switch cover WWS Series swtich cover plates
679
19
1142
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
AIR PRODUCTS AND CONTROLS MULTI-VOLTAGE CONTROL RELAYS
MR SERIES
DESCRIPTION
The MR Series multi-voltage control relays offer SPDT or
DPDT contacts which may be operated by multiple input
control voltages.Each relay section contains a red LED,
which indicates the relay coil is energized. Relay sections
may be snapped apart from standard four- or eight-section
assemblies and used independently.These relays are ideal
for applications where local or remote contacts are required
for control of electrical loads and general-purpose switching.
They are suitable for use with HVAC, temperature control,
fire alarm, security, building automation, and lighting control
systems.
MR-101/T
MR-601/T
MR-801/S
FEATURES
• Multi-voltage input, SPDT or DPDT control relays
• LED indication when relay is energized
• Snap-apart relay sections from standard four or eightsection assemblies
• Track, spacer, or enclosed mounting options
• Dust-proof housing with LED viewing holes on
enclosed models
• Relays rated for 10 million mechanical operations
MR-101/C
MR-104/T
SERIES
MR-100
Relay sections (snap-apart)
Voltage input
MR-600
24 VDC @ 18 mA
24 VAC @ 18 mA
120 VAC @ 18 mA
230 VAC @ 18 mA
24 VDC @ 40 mA
24 VAC @ 40 mA
120 VAC @ 40 mA
230 VAC @ 40 mA
SPDT
DPDT
10A resistive @ 120 VAC
7A resistive @ 230 VAC/28 VDC
N.O.: 1/6 hp @ 120 VAC
N.C.: 1/8 hp @ 120 VAC
10A @ 120 VAC
7A @ 24 VDC
32° to 120°F (0° to 49°C)
Indication
Mounting
Wiring
Enclosure option
24 VDC @ 22 mA
24 VAC @ 60 mA
120 VAC @ 20 mA
24 VAC, 24 VDC
@15 mA
SPDT
Temperature
MR-800
1, 4, or 8
1 or 4
Contact type
Contact rating
Manual override
Dimensions
Enclosure dimensions
MR-200
RELAYS & CONTACTORS
SPECIFICATIONS
10A @ 120 VAC
7A @ 30 VDC/277 VAC
1/4 hp @ 120 VAC
1/3 hp @ 230 VAC
19
32° to 120°F (0° to 49°C)
LED
Track or enclosed
18-gauge metal back, ABS-94VO plastic cover
1/2" knockouts
–
3.25"H x 2.13"W x 1.5"D (8.25 x 5.39 x 3.81 cm)
5.13"H x 3.13"W x 2.5"D (13 .46 x 7.95 x 6.35 cm) or
5.13"H x 9.5"W x 2.5"D (13.46 x 24.13 x 6.35 cm)
Agency approvals
Track or spacer
Track
Solid or stranded, 12 to 22 AWG terminals
–
–
On/Auto/Off Switch
3.5"H x 2.13"W x 1.38"D (8.9 x 5.4 x 3.5 cm)
UL-recognized component, File #S3403
Enclosed model UL listed, File #S3403
–
UL-recognized component,
File #S3403
* Specifications are for each relay section.
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1143
NEW!
RELAYS & CONTACTORS
AIR PRODUCTS AND CONTROLS MULTI-VOLTAGE CONTROL RELAYS
MR SERIES
WIRING
DPDT Contacts
10A @
120 VAC
SPDT Contacts
10A @
120 VAC
NC C NO
NC C
NO NC C NO
Relay
Energized
Indicator
NC
Relay
Energized
Indicator
SPDT Contacts
10A @
120 VAC
C NO
NC
Relay
Energized
Indicator
C NO
ON
AUTO
OFF
Relay
Energized
Indicator
SPDT Contacts
10A @
120 VAC
Input
Control
Voltage
24 VDC
24 VAC
Ø 18/24
(–)
Input
Control
Voltage
115 230
(+)
N
230 VAC
L2
(–)
24 VDC
A.C. A.C.
120 VAC
Ø 18/24
24 VAC
H
L1
120 VAC
N
230 VAC
L2
Ø
Common
H
Note:
L1
MR-201, -204
24
115
Input
Control
Voltage
24 VAC/VDC
Control
Input
(+)
Terminal strip connections
MR-101, -104
24 VDC
(–)
(+)
24 VAC
AC
AC
120 VAC
Multisection relays MR-604
and MR-608 have all supply
and all common terminals
factory jumpered together.
N
H
Terminal strip connections
MR-601, -604, -608
MR-801, -804, -808
ORDERING INFORMATION
1144
888-397-5353 USA
X
X
X
X
X
X
kele.com
1
4
8
1
1
4
4
8
8
X
X
X
X
X
X
X
X
X
X
X
X
Recognized
Listed
Recognized
Listed
Recognized
Listed
Recognized
Listed
Recognized
Recognized
Recognized
Recognized
Recognized
Recognized
Recognized
Recognized
Recognized
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
X
X
X
X
CSFM
MEA
UL
Manual
Override
On/Auto/Off
1
1
4
4
X
X
X
X
X
X
X
X
X
X
X
X
1
1
4
4
SWITCH AGENCY APPROVALS
Enclosure
(included)
X
X
X
X
X
X
X
X
Spacers
(included)
X
X
X
X
X
X
X
X
Track
(included)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
MOUNTING
DPDT (10A)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
230 VAC
24 VAC
MR-101/T
MR-101/C
MR-104/T
MR-104/C
MR-201/T
MR-201/C
MR-204/T
MR-204/C
MR-601/T
MR-604/T
MR-608/T
MR-801/T
MR-801/S
MR-804/T
MR-804/S
MR-808/T
MR-808/S
120 VAC
MODEL
SPDT (10A)
SECTIONS
COIL VOLTAGE
24 VDC
RELAYS & CONTACTORS
230
A.C. A.C.
Terminal strip connections
19
115
SUP CTL COM
Supply
24 VAC
24 VDC
X
X
X
X
X
X
X
X
March 2014
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES MODULAR PANEL RELAYS
RIB M SERIES
DESCRIPTION
The RIB M Series modular relay system allows the installer
to mount a combination of relays in an attractive metal
enclosure. Models are available to control most BAS, HVAC,
low-horsepower motors and lighting applications. The relay
modules snap into a 4" (10.16 cm) wide plastic track. This
system provides a convenient and cost-saving method of
mixing and matching relays of different ratings to suit the
requirements of the application.Connections to the modules
are made by wiring to screw terminals. Input connections
can be grouped on one side of the enclosure and output
connections on the other to separate high-voltage and lowvoltage wires. Plenty of room is provided within the enclosure
for wire runs, and the housings can be stacked vertically or
horizontally. The relay modules can be snap-track mounted
inside the housing as pictured or mounted into an available
space in other equipment. The track is available in 2" (5.08
cm) lengths for mounting one module or in 12" (30.5 cm)
lengths for mounting several modules.
RIBM Power Series - 30A modular relays
The power modular relays have contacts rated up to 30A.
They require modest coil drive current and are used for direct
switching and control of heavy electrical circuits such as large
resistive, motor, or lighting loads.
RIB M Series
(shown in optional
enclosure)
FEATURES
• Convenient and economical to use
• Handy, track-mounted modules
• Attractive, stackable metal enclosure
• Relay status indicator via LED
• Coil uses low current and accepts wide range of AC &
DC voltages
• Closed/Open/Auto switch option available
• High density relay packaging
• UL listed enclosure and relay modules
SPECIFICATIONS
Frequency
Life Rating
50/60 Hz
10 million cycles minimum
mechanical
Relay Status
LED, ON - relay activated
Operating Temperature-30° to 140°F (-34° to 60°C)
Operating Humidity
5% to 95% non-condensing
Dimensions
C
1.75"H x 4"W x 1.25"L
(4.45 x 10.16 x 3.18 cm)
D
1.75"H x 4"W x 2"L
(4.45 x 10.16 x 5.08 cm)
F
1.75"H x 4"W x 2.45"L
(4.45 x 10.16 x 6.22 cm)
H
1.75"D x 2.75"W x 1.25"L
(4.45 x 6.99 x 3.18 cm)
I
1.75"D x 2.75"W x 1.7"L
(4.45 x 6.99 x 4.32 cm)
J
1.75"D x 4"W x 1.5"L
(4.45 x 10.16 x 3.85 cm)
K
1.75"D x 2.75"W x 2.5"L
(4.45 x 6.99 x 6.35 cm)
March 2014
L
MH1000
MH3500
MH38000
Approvals
1.75"D x 2.75"W x 1.25"L
(4.45 x 6.99 x 8.64 cm)
14.5"H x 7.7"W x 3.9"D
(36.83 x 19.56 9.91 cm)
24.5"H x 10.25"W x 3.9"D
(62.23 x 26.04 x 9.91 cm)
24.5"H x 12.5"W x 6.5"D
(62.23 x 31.75 x 16.5 cm)
UL listed, UL 916 Energy
Management, UL 864 Fire, cUL
listed, CSFM. UL FIle E68805
1 year
Warranty
RELAYS & CONTACTORS
RIBM Pilot Series - 10A, 15A modular relays
These pilot modular relays have contacts rated up to 15A and
are used to control light electrical loads, drive power relays/
contactors or to sense the voltage fed to electrical loads. The
pilot modular relays require a low coil drive current and are
provided with circuitry to allow powering the relay coil from a
wide range of AC or DC voltages.
19
Coil pull-in/drop-out (nominal values)
PULL-IN
COIL DRIVE
DC
AC
10-30 VAC/VDC 10
9
24 VAC/VDC
22
18
120 VAC
–
85
208-277 VAC
–
160
WE MAKE IT EASY.
kele.com
DROP-OUT
DC
AC
2 .8
2 .1
3 .8
3
–
35
–
60
888-397-5353 USA
1145
NEW!
RELAYS & CONTACTORS
FUNCTIONAL DEVICES MODULAR PANEL RELAYS
RIB M SERIES
SPECIFICATIONS - PILOT RELAY MODULES
MODEL
TYPE
RIBM24C
C
1-SPDT
RIBMN24C
RIBM24S
1-SPST
RIBMN24S
RIBMU1C
RIBMU1SC
RIBMNU1C
RIBMU2C
RIBMH1C
RIBMH1SC
RIBMNH1C
RIBMH2C
RIBMU1S
RIBMNU1S
RIBMU1SM
RIBMNU1SM
RIBMH1S
RIBMNH1S
RIBMH1SM
RIBMNH1SM
COIL DRIVE SIZE* OVR
1-SPDT
2-SPDT
1-SPDT
2-SPDT
1-SPST-NO
1-SPST-NO
1-SPST-NO
1-SPST-NO
C
H
C
J
I
F
C
J
I
F
10-30 VAC/VDC
120 VAC
50-60 Hz
10-30 VAC/VDC
208-277 VAC
50-60 Hz
C
K
D
L
C
K
D
L
10-30 VAC/VDC
120 VAC
50-60 Hz
10-30 VAC/VDC
208-277 VAC
50-60 Hz
15A general use
10A general use
10A resistive
1/2 hp
470 VA pilot duty
–
H
24 VAC/VDC
50-60 Hz
CONTACT RATINGS
Yes
125 VAC
250 VAC
30 VDC
125/250 VAC
120/240 VAC
RELAYS & CONTACTORS
COIL DRIVE DATA
Wiring
24 VAC/VDC
24S
NC
Closed
Open
Auto
COM
NO
*
*Cut appropriate jumper to
select N.C. or N.O.
Current Input
24 mA @ 20 VAC
13 mA @ 20 VDC
28 mA @ 24 VAC
16 mA @ 24 VDC
44 mA @ 35 VAC
25 mA @ 35 VDC
Relay Without Override Switch
–
Yes-2
–
10A resistive
15A resistive
15A inductive
480 VA pilot duty
480 VA ballast
600W tungsten
240W tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
–
–
Yes-2
–
–
Yes
Yes +
Status
Yes
Yes+
Status
10A resistive
15A resistive
480 VA pilot duty
480 VA ballast
600W tungsten
240W tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
120/240/277 VAC
150 VAC, 28 VDC
150 VAC
240/277 VAC
277 VAC
120 VAC N.O.
120 VAC N.C.
120/240 VAC
120/240 VAC
277 VAC
277 VAC
277 VAC
150 VAC
277 VAC
277 VAC
120 VAC N.O.
120 VAC N.C.
120/240 VAC
120/240 VAC
277 VAC
277 VAC
* See Specification on previous page for dimensions.
Relay #2
(if present)
NC
COM
NO
Relay #1
NC
COM
NO
Wiring
Relay #1 (and #2 if present)
either
or
Relay With Override Switch
Auto
Manual
Common
208-277 VAC
120 VAC
10-30 VAC/VDC
Common
N.C.
N.C. - Closed
Open
N.O. - Closed
N.O.
Closed
U1S and H1S
**For normally closed Open
contacts, specify NC Auto
after model number
**
U1SM and H1SM
Closed
Open
Auto
Current Input
30 mA @ 10 VAC
12 mA @ 10 VDC
32 mA @ 12 VAC
14 mA @ 12 VDC
42 mA @ 24 VAC
16 mA @ 24 VDC
50 mA @ 30 VAC
18 mA @ 30 VDC
25 mA @ 120 VAC
35 mA @ 208-277 VAC
Closed
Open
Auto
STATUS 50 VAC/VDC max and
0.25 A max
SPECIFICATIONS - POWER RELAY MODULES
RIBM2401B
24 VAC/VDC
120 VAC
50/60 Hz
RIBM2401SBC
C
–
F
Yes-2
C
–
F
Yes-2
1-SPDT
RIBM2402B
24 VAC/VDC
208-277 VAC
50/60 Hz
RIBM2402SBC
RIBM2401SB
1-SPST-NO
RIBM2402SB
19
CONTACT WIRING
24C
24 VAC/VDC
120 VAC
D
Yes
24 VAC/VDC
F
–
24 VAC/VDC
F
–
24 VAC/VDC
208-277 VAC
RIBM24PL
DPST-NO
RIBM24ZL
DPST-NO
RIBM24ZN
DPDT
Wiring
Relay Without Override Switch
20A resistive
1 hp
2 hp
20A ballast N.O.
10A ballast N.C.
10A tungsten N.O.
770 VA pilot duty
1,110 VA pilot duty
277 VAC
120 VAC
277 VAC
120-277 VAC
120-277 VAC
120 VAC
120 VAC
277 VAC
NC
COM
NO
either - 208-277 VAC
or 120 VAC
24 VAC/VDC
Common
Relay With Override Switch
Auto
Manual
Common
N.C.
N.C. - Closed
Open
N.O. - Closed
Closed
Open
Auto
20A resistive
300 VAC, 28 VDC
15A resistive
600 VAC
1 hp
120 VAC
2 hp
240-277 VAC
3 hp
480-600 VAC
20A ballast
277-480 VAC
770 VA pilot duty
120 VAC
1,158 VA pilot duty
240 VAC
1,110 VA pilot duty
277 VAC
1,640 VA pilot duty
480 VAC
24ZL and 24ZN: 30A [email protected] 300 VAC
N.O.
Position of yellow jumper
selects N.O. vs N.C.
Current Input
45 mA @ 18 VAC
30 mA @ 22 VDC
75 mA @ 24 VAC
32 mA @ 24 VDC
42 mA @ 120 VAC
42 mA @ 30 VDC
62 mA @ 208-277 VAC
Wiring
NO
NC
COM
NO
24 VAC/VDC
COMMON
Current Input
100 mA @ 20 VAC 50 mA @ 24 VDC
125 mA @ 24 VAC 70 mA @ 30 VDC
ORDERING INFORMATION
1146
MH1000
MH3500
MH3800
MT212-12
MT212-2
MT4-12
MT4-2
888-397-5353 USA
kele.com
ACCESSORIES
Screw-cover housing
Hinge-cover housing
Hinge-cover housing
Relay track, 12" x 2.75" (30.48 x 6.99 cm)
Relay track, 2" x 2.75" (5.08 x 6.99 cm)
Relay track, 12" x 4" (30.48 x 10.16 cm)
Relay track, 2" x 4" (5.08 x 10.16 cm)
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
AIR PRODUCTS AND CONTROLS MULTI-VOLTAGE RELAY MODULES
PAM-1, PAM-4
DESCRIPTION
PAM Series relays are small encapsulated multi-voltage
modules that provide 10A Form C contacts.These devices
are ideal for applications where remote relays are required
for control or status feedback. They are suitable for use with
HVAC, temperature control, fire alarm, security, building
automation, and lighting control systems.
PAM Series relays may be mounted by using double-sided
adhesive tape (provided), a self-drilling screw, or they may be
loosely placed in a handy box.
PAM-1
FEATURES
•
•
•
•
•
Multi-voltage input
Small size
Multiple mounting options
Wirenuts, mounting screw, and tape included
LED indication (PAM-1 only)
PAM-4
SPECIFICATIONS
Dimensions
24 VAC @ 31 mA, 24 VDC @ 15 mA,
120 VAC @ 19 mA
PAM-4
9-40 VDC @ 15 mA
Contact Rating
SPDT, Form C, 10A @120 VAC, 7A
@ 24 VDC, 250µA @ 5 VDC
Wire Size
12" (30.5 cm), 18 AWG
Operating Temperature-58° to 185°F (-50° to 85°C)
Mounting
Pre-drilled mounting screw hole and
mounting screw provided; doublesided tape also provided
1.5"H x 1"W x 0.9"D
(3.81 x 2.54 x 2.2 cm)
UL listed File #S3403, CSFM, MEA
0.15 lb (0.068 kg)
1 year
Approvals
Weight
Warranty
RELAYS & CONTACTORS
Coil Rating
PAM-1
WIRING
(–) (white)
24 VAC/
VDC
120V*
Relay Energized LED
Mounting Hole
(blue)
(black)
C
(yellow) N.C.
(+) (red)
(orange) N.O.
(+)
10A
Contacts
(red)
(blue)
9-40 VDC
@ 15 mA
(yellow)
(-)
PAM-1
N.C.
(orange)N.O.
(black)
Mounting Hole
C
10A
Contacts
19
PAM-4
* May not be suitable for continuous duty use at 120 VAC for extended periods of time.
ORDERING INFORMATION
MODEL
PAM-1
PAM-4
PAM-2
PAM-SD
March 2014
DESCRIPTION
Multi-voltage relay module, 24 VAC/VDC, 120 VAC
Multi-voltage relay module, 9-40 VDC
Multi-voltage relay module, 12 or 24 VDC
Multi-voltage relay module, 20-32 VDC
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1147
NEW!
RELAYS & CONTACTORS
POWER RELAYS
KE375, KE900 SERIES
DESCRIPTION
The KE375 and KE900 Series of 30A relays are heavy
duty power relays commonly used for energy management,
refrigeration, and HVAC control applications. High power
handling capability and small size make these power
relays particularly suited for motor control, heater loads,
and lighting control. The KE900 Series features an open
frame construction, and the KE375 is encased in a clear
polycarbonate cover.
KE900D
FEATURES
•
•
•
•
Small size
High-power handling capability
One-, two-, and three-pole models
24 VAC, 24 VDC & 120 VAC coils
KE900S
RELAYS & CONTACTORS
KE375
SPECIFICATIONS
KE900
Coil voltage
24 VAC/60 Hz, 120 VAC/60 Hz, or 24 VDC
Coil power
AC: 4.6 VA
DC: 2.6W
AC: 9.5 VA sealed
DC: 2.0W
Pull-in voltage
Contact ratings
19
AC: 85% or less of nominal
DC: 75% or less of nominal
30A or 1-1/2 hp @ 120 VAC / 240 VAC
20A or 2 hp @ 600 VAC
30A @ 28 VDC, resistive
3600W @ 120 or 240V (ballast)
2 hp @ 240 VAC
20A @ 600 VAC
20A @ 125 VDC (D models only)
Mounting
Terminals
Contact material
Dielectric strength
3/16" dia mounting holes
Screw terminals
Weight
Agency approvals
888-397-5353 USA
30A @ 300 VAC, 80% PF
15A @ 600 VAC, 80% PF
30A @ 28 VDC
1 hp @ 120 VAC
2 hp @ 240 VAC / 277 VAC
3 hp @ 480/600 VAC, 100,000 cycles
20A @ 277/480 VAC ballast, 6000 cycles
Top-mount cover with slotted tabs
0.25" x 0.032" quick connects
Silver cadmium oxide
2200V RMS between contacts
2200V RMS between contacts
2200V RMS between other elements
3750V RMS between other elements
Operate/Release
time
1148
KE375
30 ms
15 ms
10 oz (283g)
3.5 oz (99g)
UL/cUL listed, File #E37066
kele.com
UL/cUL-recognized component, File #E37066;
CE certified
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
POWER RELAYS
KE375, KE900 SERIES
DIMENSIONS
in
(cm)
8-32 Screw
(2) Contact Terminals
Two Mounting Holes 0 .19 (0 .48) dia
2 .50
(6 .35)
1 .88
(4 .76)
0 .81
(2 .08)
1 .88
(4 .76)
3 .32
(8 .43)
8-32 Screw
(6) Contact Terminals
6-32 Screw
(2) Coil Terminals
2 .35
(5 .97)
2 .50
(6 .35)
1 .66
(4 .22)
2 .50
(6 .35)
0 .06
(0 .16)
3 .16
(8 .03)
6-32 Screw (2) Coil Terminals
Two Holes
0 .19 (0 .48) dia
2 .75
(6 .99)
1 .40
(3 .56)
2 .38
(6 .04)
2 .2
(5 .59)
1
2
4
5
6
7
8
9
3
A
0 .17
(0 .43)
B
2 .13
(5 .41)
KE900S
KE375T
KE900D
6
8
NC
5
3
2
NO
C
1
KE900S
7
1
2
3
5
4
5
6
3
7
8
9
NC
6
4
NO
C
2
1
KE900D
A
NC
NO
C
B
KE375T
19
ORDERING INFORMATION
MODEL
KE375T120VAC
KE375T24VAC
KE375T24VDC
KE900S120VAC
KE900S24VAC
KE900S24VDC
KE900D120VAC
KE900D24VAC
KE900D24VDC
March 2014
RELAYS & CONTACTORS
WIRING
DESCRIPTION
3PDT Power relay 120 VAC coil
3PDT Power relay 24 VAC coil
3PDT Power relay 24 VDC coil
SPDT Power relay 120 VAC coil
SPDT Power relay 24 VAC coil
SPDT Power relay 24 VDC coil
DPDT Power relay 120 VAC coil
DPDT Power relay 24 VAC coil
DPDT Power relay 24 VDC coil
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1149
NEW!
RELAYS & CONTACTORS
OMRON POWER RELAYS
G7L SERIES
DESCRIPTION
G7L Series relays are heavy duty power relays commonly
used for controlling refrigeration, HVAC equipment, heater
loads, and lighting controls. High-power handling capability
up to 30A, small size, and low cost characterize these relays.
They are available in single and double pole models and
are surface mounted or DIN rail mounted with the PL7F-06
socket.
FEATURES
•
•
•
•
•
High power capability
Small size
Low cost
Push-to-test button
Optional DIN rail screw terminal socket
G7L Series
SPECIFICATIONS
RELAYS & CONTACTORS
Coil Voltage
19
24V, 26.4V maximum,120V 50/60
Hz.132V maximum
Coil Power
AC:2.5 VA, DC: 2.0W
Pull In Voltage 18V, 75V
Drop Out Voltage
3.6V, 18V, 20V
Contact Rating
G7L-1A: Resistive: 30A, 277 VAC
General purpose: 25A, 277 VAC
30A 120 VAC Tungsten: 1.5 kW,
120 VAC Horsepower: 1.5 hp,
120 VAC 3 hp, 277 VAC, G7L-2A:
Resistive: 25A, 277 VAC General
purpose: 25A, 277 VAC 25A 120
VAC Tungsten 1.3 kW, 120 VAC
Horsepower 1 hp, 120 VAC 2 hp,
277 VAC
Contact Resistance
50 mΩ maximum
Terminals
0.25" x 0.031" quick connects
Contact Material
Silver cadmium oxide
Dielectric Strength
2000 VAC between contacts, 4000
VAC between coil and contacts
Operate Time
30 ms maximum
Release Time
30 ms maximum
Operating Temperature -13° to 140°F (-25° to 60°C)
Mounting
Top-mount cover with slotted tabs
or DIN rail surface-mount socket
with screw terminals
Approvals
UL-recognized component, File
#E41643: CSA certified, File
#LR35535: CE certifed
Weight
0.2 lb (0.091 kg)
Warranty
1 year
DIMENSIONS
2.69
(6.85) max
2.36(6.0)
1.99 (5.05) max
in
(cm)
0.25 (0.64) max
1.32
(3.35) max
0.031
(0.08)
0.078
(0.2)
0.43
(1.1)
1.85
(4.7)
max
0.12
(0.3)
G7L-1A, -2A
0.177
(0.45)
G7L-1A, 2A
Depth: 1.0 (2.54)
Two Mounting Holes
0.177 (0.45) dia
or M4 tapped holes
2.1
(5.3)
2.36 ±.007
(6.0 ±0.02)
2.2 (5.6)
G7L-1A, -2A
P7LF-06
WIRING
1
0
4
6
G7L-1A-TUBJ-CB
1
0
2
4
6
8
G7L-2A-TUBJ-CB
ORDERING INFORMATION
MODELDESCRIPTION
G7L-1A-TUBJ-CB-24VAC
SPST-N.O. Power relay 24 VAC
G7L-1A-TUBJ-CB-24VDC
SPST-N.O. Power relay 24 VDC
G7L-1A-TUBJ-CB-120VAC SPST-N.O. Power relay 120 VAC
G7L-2A-TUBJ-CB-24VAC
DPST-N.O. Power relay 24 VAC
G7L-2A-TUBJ-CB-24VDC
DPST-N.O. Power relay 24 VDC
G7L-2A-TUBJ-CB-120VAC DPST-N.O. Power relay 120 VAC
P7LF-06
1150
888-397-5353 USA
RELATED PRODUCTS
DIN rail/surface mount socket
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
DEFINITE PURPOSE CONTACTORS
DPC SERIES
DESCRIPTION
The DPC Series is an economical line of definite-purpose
contactors designed to control electrical loads such as air
conditioning, refrigeration compressor, motors, and resistance
heaters.
FEATURES
• Two-, three-, and four-pole models
• Contact ratings from 30-60 FLA
• Optional auxiliary contacts on select models
Two-pole
Three-pole
Four-pole
IEC 60947-4-1
SPECIFICATIONS
Line Load Terminals
Coil Terminals
Auxiliary Contacts
Wire Size
Operating Temperature-40° to 149°F (-40° to 65°C)
Approvals
UL recognized, File #E246810,
CE certified
Weight
1.5 lbs (0.68 kg)
Warranty
1 year
Box lug or dual 0.25” quick connects
Dual 0.25” quick connects
10A, 1/3 hp @ 120/250 VAC 4A @
120 VAC for lamp load
14-4 AWG
CONTACT RATINGS
MODEL
LOCKED-ROTOR AMP (LRA)
2
DPST-N .O .
30 FLA @ 240-600 VAC
40A @ 240-600 VAC
2 hp @ 120 VAC
3 hp @ 240 VAC
2
DPST-N .O .
40 FLA @ 240-600 VAC
180 LRA @ 240/277 VAC
150 LRA @ 480 VAC
120 LRA @ 600 VAC
240 LRA @ 240/277 VAC
200 LRA @ 480 VAC
160 LRA @ 600 VAC
50A @ 240-600 VAC
2 hp @ 120 VAC
3 hp @ 240 VAC
DPC24A3C30
DPC01A3C30
3
3PST-N .O .
30 FLA @ 240-600 VAC
180 LRA @ 240/277 VAC
150 LRA @ 480 VAC
120 LRA @ 600 VAC
40A @ 240-600 VAC
2 hp @ 120 VAC
5 hp @ 240/277 VAC
DPC24A3C40
DPC01A3C40
3
3PST-N .O .
40 FLA @ 240-600 VAC
240 LRA @ 240/277 VAC
200 LRA @ 480 VAC
160 LRA @ 600 VAC
50A @ 240-600 VAC
3 hp @ 120 VAC
7 .5 hp @ 240/277 VAC
DPC24A3B50
DPC01A3B50
3
3PST-N .O .
50 FLA @ 240-600 VAC
300 LRA @ 240 VAC
250 LRA @ 480 VAC
200 LRA @ 600 VAC
65A @ 240-600 VAC
3 hp @ 120 VAC
7 .5 hp @ 200/208 VAC
10 hp @ 240 VAC
10 hp @ 200/208 VAC
10 hp @ 240/277 VAC
15 hp @ 480 VAC
20 hp @ 600 VAC
10 hp @ 200/208 VAC
10 hp @ 240/277 VAC
20 hp @ 480 VAC
25 hp @ 600 VAC
15 hp @ 200/208 VAC
15 hp @ 240 VAC
25 hp @ 480/600 VAC
DPC24A3B60
DPC01A3B60
3
3PST-N .O .
60 FLA @ 240-600 VAC
360 LRA @ 240 VAC
300 LRA @ 480 VAC
240 LRA @ 600 VAC
75A @ 240-600 VAC
3 hp @ 120 VAC
7 .5 hp @ 200/208 VAC
10 hp @ 240 VAC
25 hp @ 200/208 VAC
25 hp @ 240 VAC
30 hp @ 480/600 VAC
DPC24A4A30
DPC01A4A30
4
4PST-N .O .
30 FLA @ 240-600 VAC
180 LRA @ 240/277 VAC
150 LRA @ 480 VAC
120 LRA @ 600 VAC
40A @ 240-600 VAC
2 hp @ 120 VAC
5 hp @ 240/277 VAC
10 hp @ 200/208 VAC
10 hp @ 240/277 VAC
15 hp @ 480 VAC
DPC24A4A40
DPC01A4A40
4
4PST-N .O .
40 FLA @ 240-600 VAC
240 LRA @ 240/277 VAC
200 LRA @ 480 VAC
160 LRA @ 600 VAC
50A @ 240-600 VAC
3 hp @ 120 VAC
7 .5 hp @ 240/277 VAC
10 hp @ 200/208 VAC
10 hp @ 240/277 VAC
10 hp @ 480 VAC
MODEL
DPC24A2D30
DPC24A2D40
DPC01A2D30
DPC01A2D40
DPC02A2D30
DPC24A3C30
DPC24A3C40
DPC01A3C30
DPC01A3C40
DPC24A3B50
DPC24A3B60
DPC01A3B50
DPC01A3B60
DPC24A4A30
DPC24A4A40
DPC01A4A30
DPC01A4A40
CN1C
March 2014
POLES
COIL
VOLTAGE
(VAC)
24
24
120
120
208/240
24
24
120
120
24
24
120
120
24
24
120
120
NRUSH
I
@ 50 Hz
(VA)
31
31
31
31
35
65
65
65
65
140
140
140
140
68
68
68
68
SEALED
@ 50 Hz
(VA)
6
6
6
6
7
7.5
7.5
7.5
7.5
20
20
20
20
14
14
14
14
RESISTIVE
ORDERING INFORMATION
INRUSH
@ 60 Hz
(VA)
28
28
28
28
32
60
60
60
60
132
132
132
132
60
60
60
60
SEALED
@ 60 Hz
(VA)
5
5
5
5
6
6
6
6
6
14
14
14
14
9
9
9
9
PULL-IN
(VAC)
18
18
88
88
177
18
18
88
88
18
18
93
93
19.2
19.2
88
88
DROP-OUT
RANGE
(VAC)
6-15
6-15
20-70
20-70
40-140
6-15
6-15
20-70
20-70
6-15
6-15
20-70
20-70
6-15
6-15
20-70
20-70
HP, SINGLE PHASE
DIMENSIONS
LENGTH
3.29 (8.36)
3.29 (8.36)
3.29 (8.36)
3.29 (8.36)
3.29 (8.36)
3.30 (8.38)
3.30 (8.38)
3.30 (8.38)
3.30 (8.38)
4.06 (10.3)
4.06 (10.3)
4.06 (10.3)
4.06 (10.3)
3.42 (8.69)
3.42 (8.69)
3.42 (8.69)
3.42 (8.69)
WIDTH
2.00 (5.08)
2.00 (5.08)
2.00 (5.08)
2.00 (5.08)
2.00 (5.08)
2.90 (7.37)
2.90 (7.37)
2.90 (7.37)
2.90 (7.37)
3.19 (8.10)
3.19 (8.10)
3.19 (8.10)
3.19 (8.10)
2.75 (7.00)
2.75 (7.00)
2.75 (7.00)
2.75 (7.00)
(
HP, THREE PHASE
—
—
—
—
—
—
)
HEIGHT
2.61 (6.63)
2.61 (6.63)
2.61 (6.63)
2.61 (6.63)
2.61 (6.63)
3.00 (7.62)
3.00 (7.62)
3.00 (7.62)
3.00 (7.62)
3.56 (9.04)
3.56 (9.04)
3.56 (9.04)
3.56 (9.04)
3.03 (7.70)
3.03 (7.70)
3.03 (7.70)
3.03 (7.70)
APPROX. OPTIONAL
WEIGHT
AUX.
lb (kg)
SWITCH
0.6 (0.27)
No
0.6 (0.27)
No
0.6 (0.27)
No
0.6 (0.27)
No
No
0.6 (0.27)
1.0 (0.45)
Yes
1.0 (0.45)
Yes
Yes
1.0 (0.45)
Yes
1.0 (0.45)
No
1.0 (0.91)
No
1.0 (0.91)
No
1.0 (0.91)
No
1.0 (0.91)
1.5 (0.68)
Yes
1.5 (0.68)
Yes
Yes
1.5 (0.68)
Yes
1.5 (0.68)
RELAYS & CONTACTORS
FULL-LOAD AMP (FLA)
DPC24A2D30
DPC01A2D30
DPC02A2D30
DPC24A2D40
DPC01A2D40
19
RELATED PRODUCTS
Auxiliary contact, (1) SPDT
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1151
NEW!
RELAYS & CONTACTORS
EEC DEFINITE PURPOSE CONTACTORS
T30, T40, T60, T90
DESCRIPTION
The T30, T40, T60 and T90 Series of definite purpose contactors
can be used in air conditioning, compressors, refrigeration, heaters
and HVAC applications. They are rated for 200,000 electrical
operations and 2 million mechanical operations. The coils are rated
80 to 105% voltage, 65VA inrush and 7.5VA sealed. These contactors
are available in 1, 2 or 3 pole configurations up to 100 Amps.
FEATURES
• 1, 2, or 3 Pole styles
• FLA up to 90A
• Coil voltage up to 480V
T40A3
SPECIFICATIONS
Electrical Life
200,000 electrical operations
Mechanical Life
2,000,000 mechanical operations
Operating Temperature-40° to 149°F (-40° to 65°C)
Approvals
Warranty
CE, CSA, UL Listed #E309604
1 year
ORDERING INFORMATION
MODEL
RELAYS & CONTACTORS
FULL LOAD
19
T30A1-G
T30A1-A
T40A1-G
T40A1-A
T30A2-G
T30A2-A
T30A2-B
T30A2-C
T40A2-G
T40A2-A
T40A2-B
T40A2-C
T40A2-E
T40A2-G
T40A2-H
T40A3-G
T40A3-A
T40A3-B
T40A3-C
T40A3-H
T40A3-E
T60A3-G-AUX-C11
T60A3-A-AUX-C11
T60A3-B-AUX-C11
T60A3-C-AUX-C11
T60A3-H-AUX-C11
T60A3-E-AUX-C11
T90A3-G-AUX-C11
T90A3-A-AUX-C11
T90A3-B-AUX-C11
T90A3-C-AUX-C11
T90A3-H-AUX-C11
T90A3-E-AUX-C11
30
30
40
40
30
30
30
30
40
40
40
40
40
40
40
40
40
40
40
40
40
60
60
60
60
60
60
90
90
90
90
90
90
AUX-11-DP
1152
COIL
NUMBER VOLTAGE
RESISTIVE OF POLES
(VAC)
40
1
24
40
1
120
50
1
24
50
1
120
40
2
24
40
2
120
40
2
208
40
2
240
50
2
24
50
2
120
50
2
208
50
2
240
50
2
480
50
2
24
50
2
277
50
3
24
50
3
120
50
3
208
50
3
240
50
3
277
50
3
480
75
3
24
75
3
120
75
3
208
75
3
240
75
3
277
75
3
480
100
3
24
100
3
120
100
3
208
100
3
240
100
3
277
100
3
480
DIMENSIONS in (cm)
CONTACT AMP RATING
888-397-5353 USA
HEIGHT
WIDTH
DEPTH
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
3.78 (9.6)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
5.24 (13.3)
5.24 (13.3)
5.24 (13.3)
5.24 (13.3)
5.24 (13.3)
5.24 (13.3)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.64 (6.7)
2.66 (6.75)
2.66 (6.75)
2.66 (6.75)
2.66 (6.75)
2.66 (6.75)
2.66 (6.75)
3.5 (8.9)
3.5 (8.9)
3.5 (8.9)
3.5 (8.9)
3.5 (8.9)
3.5 (8.9)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
2.68 (6.8)
3.11 (7.9)
3.11 (7.9)
3.11 (7.9)
3.11 (7.9)
3.11 (7.9)
3.11 (7.9)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
4.53 (11.5)
INCLUDES 1 N.O. & 1
N.C. AUX. CONTACT
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ACCESSORIES
1 NO and 1 NC auxiliary for T30A3, T40A3 only
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
IDEC SOLID STATE RELAY
RSSDN
DESCRIPTION
The Model RSSDN is a photo-isolated solid state relay.
The 4-32 VDC input voltage allows the relay to be used on
analog or digital outputs. While solid-state relays provide
reliable switching and long-life operation, careful application
is required as excessive temperature, high inrush currents, or
induced currents can affect solid state relay operation.
FEATURES
•
•
•
•
•
•
Photo isolation
4000V optical isolation
Zero voltage turn-on
Input status LED
High surge capability
Dual SCR output
RSSDN
SPECIFICATIONS
WIRING
4000 rms minimum
1-Cycle 150A, 1-Second 30A,
1-Cycle 300A, 1-Second 75A,
1-Cylce 750A, 1-Second 150A
Reverse Voltage Protection
Yes (-32 VDC)
Zero Voltage SwitchingYes
Turn Off Time
1/2 cycle @ 60 Hz
Turn On Time
1/2 cycle @ 60 Hz
Dimensions
2.25" H x 1.75" W x 0.95" D
(5.72 x 4.45 x 2.41 cm)
Approvals
UL-recognized component,
File #E194577: CE certified
Weight
0.22 lb (0.10 kg)
Warranty
1 year
19
30 40
50
60 70 80 90 100
Relay Base Temp (°C)
WE MAKE IT EASY.
kele.com
RMS On-State Current (amps)
e Air
Free Air
at
50A Heatsink
50
90A Unit-
20
k
Free Air
50A Free Air
20
sin
k
in
10A Unit-
75A Mounted on H
e
65
ts
ea
-H
on
nit-Fre
ink
80
d
ats
90A
e
nt
ou
20
25A U
nk
5
10A H
e
50A, 75A, 90A
100
M
10
tsi
Observe the polarity of input terminals . Failure to do so may cause
damage to the solid-state relays .
15
ea
-H
LOAD
20
on
1
AC Line
48-660 VAC
ed
nt
4 –
or
10A, 25A
25
ou
RSSDN-10A
LOAD
M
Control Voltage
4-32 VDC
2
RMS On-State Current (amps)
FIGURE 1. CURRENT DERATING CURVES
3 +
March 2014
Dielectric Strength
Surge Current
RELAYS & CONTACTORS
Input Current
Regulated 10 mA
Frequency Range
47-80 Hz
Pick Up Voltage
4 VDC
Drop Out Voltage
1 VDC
Voltage Range
4-32 VDC
Contact Type
1 Form A, SPST-N.O.
Off State Leakage
20 mA @ rated voltage (maximum)
Minimum Current
10A, 25A models
(Holding) 50 mA,
50A, 75A, 90A models (Holding) 100 mA
Output Current Limit 10 A, 25 A, 50 A, 75 A, 90 A
Output Voltage
48-660 VAC
Over Voltage Rating
1200 PIV
Voltage Drop
1.6V (maximum) @ rated current
Capacitance
8 pF
30 40
50
60 70 80 90 100
Relay Base Temp (°C)
888-397-5353 USA
1153
NEW!
RELAYS & CONTACTORS
IDEC SOLID STATE RELAY
RSSDN
INSTALLATION
•
•
•
•
Install solid-state relays in dry, well-ventilated areas away from excessive heat.
Use #6-32 screws, flat washers, and lock washers to secure mounting on heat sinks.
Vertical mounting is recommended to allow air to flow unimpeded.
A small-capacity load may not turn off due to the leakage current present after the solid-state relay has turned off. In this
case, use a resistor in parallel with the load to shunt the leakage current.
• When the input signal contains a ripple voltage, the lowest ripple amplitude should exceed the minimum pick-up voltage of
4V.
Heat sinks are required to achieve the full output current rating. The recommended heat sink dimensions and materials are
shown in the Table 1 below.
TABLE 1. RECOMMENDED HEAT SINK DIMENSIONS / MATERIALS
Output Rating
Dimensions in (cm)
Material
10A
25A
50A
75A
90A
12 x 12 x 1/8 (30.5 x 30.5 x 0.3)
15 x 15 x 1/8 (38.1 x 38.1 x 0.3)
15 x 15 x 1/8 (38.1 x 38.1 x 0.3)
17 x 17 x 1/8 (43.2 x 43.2 x 0.3)
17 x 17 x 1/8 (43.2 x 43.2 x 0.3)
Aluminum (black anodized)
Aluminum (black anodized)
Aluminum (black anodized)
Aluminum (black anodized)
Aluminum (black anodized)
RELAYS & CONTACTORS
It is recommended to use a thermal compound (for example, Kele part number TCC-12) between the base of the solid-state
relay and the heat sink for heat dissipation.
APPLICATION INFORMATION
Heater Loads
Lamp Loads
When using solid-state relays for driving heaters where the load is Zero-voltage switching is ideal for driving incandescent lamps since the
switched on and off rapidly and continuously, severe thermal stress cold fillament will not be subjected to a large inrush current. Using a zerowill result. In such cases, use an solid-state relay at no more than
switched solid-state relay will reduce inrush current and prolong lamp life.
75% of the rating.
RECOMMENDED HEATER LOADS
SSR Rating @ 120 VAC @ 240 VAC
10A
1 kW
2 kW
25A
2 kW
4 kW
50A
3 kW
6 kW
RECOMMENDED LAMP LOADS
SSR Rating @ 120 VAC @ 240 VAC
10A
1 kW
2 kW
25A
2 kW
4 kW
50A
3 kW
6 kW
Solenoid Valves and Contactors
Motor Loads
RECOMMENDED LOADS
SSR Rating @ 120 VAC @ 240 VAC
10A
900W
1800W
25A
2100W
4200W
50A
3800W
7500W
UL MOTOR LOAD RATINGS (hp)
SSR Rating @ 120 VAC @ 240 VAC @ 480 VAC
10A
1/2
3/4
3/4
25A
1/2
3/4
3/4
50A
3/4
1-1/2
1-1/2
75A
3/4
5
5
90A
3/4
5
5
Solid-state relays use high-noise immunity circuitry with a snubber
to handle the electrical noise generated by inductive loads.
19
ORDERING INFORMATION
MODEL
RSSDN-10A
RSSDN-25A
RSSDN-50A
RSSDN-75A
RSSDN-90A
1154
888-397-5353 USA
kele.com
DESCRIPTION
Solid-state relay, 10A continuous output current
Solid-state relay, 25A continuous output current
Solid-state relay, 50A continuous output current
Solid-state relay, 75A continuous output current
Solid-state relay, 90A continuous output current
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
SPECIAL VOLTAGE RELAYS
20307 SERIES
DESCRIPTION
The 20307 Series plug-in style relays offer the flexibility of
using 208 VAC or 277 VAC single-phase voltages for relay
control. These relays are DPDT and plug into a standard
three-pole general purpose relay socket.
20307
FEATURES
• 208 VAC and 277 VAC coils • Socket mounting
• Heavy-duty construction
• 13A contact rating
• UL recognized
SR3B-05
WIRING
SPECIFICATIONS
Coil Rating
208 VAC @ 60 Hz,
277 VAC @ 60 Hz
Coil Power
2.2 VA
Relay Type
DPDT (2 form C)
Contact Rating 13A, 1/3 hp @ 120 VAC;
13A, 1/2 hp @ 277 VAC;
3A, 3/4 hp @ 600 VAC;
10A @ 28 VDC NOTE: SR3B-05
socket is rated for 10A, 300 V max
Dimensions
Approvals
Weight
Warranty
2.2"H x 1.5"W x 1.37"D
(5.6 x 3.8 x 3.5 cm)
UL recognized File #E7443
0.5 lb (0.23 kg)
1 year
3
1
4
6
7
9
A
B
(-)
(+)
Bottom View
ORDERING INFORMATION
MODEL
20307-86
20307-87
RELATED PRODUCTS
Relay socket, three-pole blade type, DIN/surface mount
PAGE
1123
RELAYS & CONTACTORS
SR3B-05
DESCRIPTION
Relay, 208 VAC coil, DPDT
Relay, 277 VAC coil, DPDT
ALTERNATING RELAY
MODEL ALT
DESCRIPTION
The Model ALT alternating relay is commonly used to
alternate between two loads to equalize run-time. When
an external control switch opens, the Model ALT’s output
contacts transfer from one state to the other. When an
external control switch closes, the output contacts remain
in their current state. The SW option offers an override
potentiometer switch on top of the relay that allows manual
override control of either load or automatic operation.
FEATURES
•
•
•
•
Alternation between two loads to equalize run time
Two LEDs to indicate the energized load
Override switch
Debounce time delay
19
WIRING
N.C.
C
N.O.
March 2014
20-26 VAC/VDC, 95-125 VAC
40 mA
SPDT, 480 VA @ 240 VAC
115 VAC, 2 mA, 24 VAC/VDC, 2 mA
-4° to 122°F (-20° to 50°C)
0.5 sec
UL File E68520, CSA
0.35 lb (0.16 Kg)
5 years
8
2 3
7 6
4
5
Supply Voltage
24 VAC/VDC
or 115 VAC
Control
Switch
Bottom View
SPECIFICATIONS
Supply Voltage
Supply Current
Contact Rating
Control Signal
Operating Temperature Debounce Time Delay
Aprroval
Weight
Warranty
1
ORDERING INFORMATION
MODEL
DESCRIPTION
ALT-115-S-SW Alternating relay, 115 VAC, override switch
ALT-24-S-SW Alternating relay, 24 VAC/VDC, override switch
OT08PC
WE MAKE IT EASY.
RELATED PRODUCTS
Octal Relay Socket for Model ALT
kele.com
888-397-5353 USA
PAGE
1155
NEW!
RELAYS & CONTACTORS
DELAY ON MAKE / INTERVAL TIMERS
438USA, 438USA-INT
DESCRIPTION
The Model 438USA universal switch-adjustable time capsule
is an all solid state timer that provides delay on make
(ON-Delay) control of a load device operating from 19-288
VAC/DC. The Model 438USA controls up to a 1A load, such
as a relay or solenoid.
The Model 438USA-INT universal switch-adjustable time
capsule is an all solid-state timer that provides interval timing
control of a load device operating from 24 to 240 VAC. The
438USA-INT controls up to a 1A load, such as a relay or
solenoid.
438USA
FEATURES
•
•
•
•
•
Encapsulated digital-timing circuitry
Switch-selectable delay
Low cost
Transient protected
1A output rating
438USA-INT
RELAYS & CONTACTORS
OPERATION
General
Timing is set via a binary-coded DIP switch and is adjustable
from 1 to 1024 seconds. With all switches closed, there is an
internal, one-second delay; with all switches open, there is a
1024-second delay time. Prior to applying power to the timer,
set the switches to the correct position for the desired time.
438USA - Delay-on-Make (ON-Delay)
When power is applied, the Model 438USA remains in the off
state, allowing only leakage current to flow. Once the preset
time period elapses, the unit switches on, allowing full current
to flow and the load to energize. The load remains energized
as long as power is applied. When power is removed, the unit
resets and is ready for another timing period.
438USA-INT - Interval
When voltage is applied, the Model 438USA-INT turns on,
permitting full load current to flow. At the end of the preset
timing period, the unit turns off and permits only leakage
current to flow through the load. To recycle, the operating
voltage must be removed and reapplied.
SPECIFICATIONS
19
Coil Rating
24-240 VAC (50/60 Hz), 19-288 VAC
(50/60 Hz) or VDC
Leakage Current
438USA-INT
438USA Output
Range
Transient Protection
Voltage Drop
Accuracy
Adjustments
1156
Off State: 1 mA maximum @ 240V,
Off State: 0.6 mA @ 24V, 1.8 mA
@ 48 V, 5.4 mA @ 120V, 11.4 mA
@240 V
10 mA to 1A inductive; inrush current
to 25A for 8 ms
1 to 1024 seconds, 1-second
increments
6000V for 8.3 ms
4V maximum, ON state
±10% of setpoint
10-position DIP switch
888-397-5353 USA
kele.com
Recycle Time
Repeatability
Timing
100 ms, 50 ms after timing cycle,
200 ms during timing cycle
±1% nominal
Interval timer, Delay on make
(ON-Delay)
Operating Temperature-4° to 185°F (-20° to 85°C)
Storage Humidity
95% non-condensing
Approvals
UL-recognized component, File
#E47858; CSA certified, File
#LR31931-3
Weight
0.2 lb (0.091 kg)
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
DELAY ON MAKE / INTERVAL TIMERS
438USA, 438USA-INT
DIMENSIONS / WIRING
in
(cm)
19-288 VAC/VDC
Input
LOAD
Four 20 AWG wire (two for operating
voltage and two for load circuit)
1 2 3 4 5 6 7 8 9 10
LOAD*
24 - 240 VAC
Terminals
0.25 Spade
(white)
(black)
1
2
(yellow)
3
4
5
6
7
8
9
10
1.7
(4.31)
0.90
(2.29)
0.27
(.69)
* Do not apply voltage to load wires .
The load is powered from the input
voltage .
1 .7
(4 .32)
0 .90
(2 .29)
2.25
(5.71)
Four Mounting Holes
0.16 (0.41) dia
2.65
(6.73)
2 .25
(5 .72)
Four Mounting Holes
0 .16 (0 .3962) dia
2 .65
(6 .731)
0 .20
(0 .51)
0.20
(0.51)
0.76
(1.93)
0.36
(0.91)
(white)
0 .76
(1 .93)
438USA
438USA-INT
TIME SETTINGS
To delay 60-second interval
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
OPEN
OPEN
32
16
512
16
FIGURE 1. TIMING
Power
8
2
1
59
+1*
60 sec
8
2
1
539
+1*
540 sec
Power
Time
Delay
Timing
Interval
Load
Load
438USA
RELAYS & CONTACTORS
To delay 540-second interval
19
438USA-INT
ORDERING INFORMATION
MODEL
438USA-INT
438USA
March 2014
DESCRIPTION
Universal switch-adjustable time capsule, interval timer
Universal switch-adjustable time capsule, delay on make (ON-delay) timer
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1157
NEW!
RELAYS & CONTACTORS
IDEC MULTIFUNCTION ELECTRONIC TIMERS
RTE SERIES
DESCRIPTION
The RTE Series multi-function electronic timers are socketmounted adjustable time delay relays available in two function
groups. The timer functions and time ranges are easily
selected by setting external switches. The knob on the front
of the timer is used to set the precise delay period within the
selected time range.
Timer Functions
RTE-B1/RTE-P1 (Power-Triggered)
-ON-Delay, Interval, OFF-Cycle, ON-Cycle
RTE-B2/RTE-P2 (Signal-triggered)
-ON-Delay, OFF-Cycle, OFF-Delay, ON-Cycle, Single-Shot
RTE
19
•
•
•
•
•
•
•
•
Selectable 10 timing functions and 20 time ranges
Time delay settings from 0.1 second to 600 hours
Two Form C delayed output contacts
Space-saving package
High repeat accuracy of ±0.2%
On and timing out LED indicators
Standard 8-pin, 11-pin, or 11-blade relay socket
UL Listed, CE certified
SR2P-06
DIMENSIONS
in
(cm)
1 .57
(4 .0)
RELAYS & CONTACTORS
FEATURES
SPECIFICATIONS
Time Delay Settings
0.1 sec to 600 hours
Contact Configuration 2 Form C, DPDT (delay outputs)
Load Type
10A resistive @ 240 VAC, 30 VDC;
7A inductive @ 240 VAC, 30 VDC;
1/6 hp @ 120 VAC; 1/3 hp @ 240
VAC
Input
AD models
24 VAC/VDC (3.5 VA/1.7W)
AF models
120VAC (6.6 VA)
Operating Temperature-4° to 149°F (-20° to 65°C)
Operating Humidity
35% to 85% RH
Reset Time
100 ms maximum
Accuracy
±0.2%, ±20 ms
Setting Error
±10% maximum
Insulation Resistance 100 MΩ minimum (500 VDC)
Dielectric Strength
Between power and output
terminals: 2000 VAC, 1 minute
Between contacts of different poles:
2000 VAC, 1 minute
Between contacts on the same
pole: 1000 VAC, 1 minute
Electrical Life
500,000 operations (resistive)
Mechanical Life
50 million operations
Weight
0.2 lb (0.091 kg)
Approvals
UL listed, File #E66043, CE
Warranty
1 year
1 .40
(3 .6)
A
RTE-P 8/11 Pin:
RTE-B 11 Blade:
A = 3 .06 (7 .79)
A = 2 .95 (7 .49)
WIRING
Bottom View
Delay
Delay
4
5
3
6
2
7
Delay
2
3
5
6
7
8
Delay
9
A
8
1
1
4
B
Power
(AC or DC)
Power
(AC or DC)
RTE-B1/RTE-P1
Control
Signal Switch
Delay
5
6
Control
Signal Switch
Delay
7
4
Delay
8
3
9
1
2
3
4
5
6
7
8
Delay
9
10
2
1
11
A
B
Power
(AC or DC)
Power
(AC or DC)
Do not apply voltage
to terminals 5 and 6 .
Do not apply voltage
to terminals 2 and 5 .
RTE-B2/RTE-P2
1158
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
IDEC MULTIFUNCTION ELECTRONIC TIMERS
RTE SERIES
OPERATION
RTE-P1, -B1
B: Interval (power start)
A: ON-Delay 1 (power start)
Set timer for desired delay, apply power to coil . Contacts transfer after preset time
has elapsed, and remain in transferred position until timer is reset . Reset occurs
with removal of power .
Set timer for desired delay, apply power to coil . Contacts transfer immediately, and
return to original position after preset time has elapsed . Reset occurs with removal
of power .
ITEM
ITEM
Power
Delayed
Contact
Indicator
TERMINAL NO.
(1)2-7
(2)A-B
(1)1-4,5-8
(2)1-7,3-9
(1)1-3,6-8
(2)4-7,6-9
OPERATION
Power
(NC)
Delayed
Contact
(NO)
PWR
Indicator
OUT
Set Time
Set timer for desired delay, apply power to coil . First transfer of contacts occurs
after preset delay has elapsed, after the next elapse of preset delay contacts return
to original position . The timer now cycles between on and off as long as power is
applied (duty ratio 1:1) .
Power
Delayed
Contact
Indicator
TERMINAL NO.
(1)2-7
(2)A-B
(1)1-4,5-8
(2)1-7,3-9
(1)1-3,6-8
(2)4-7,6-9
(NO)
PWR
OUT
(NC)
Delayed
Contact
(NO)
PWR
Indicator
OUT
T
Functions in same manner as Mode C, with the exception that first transfer of
contacts occurs as soon as power is applied . The ratio is 1:1 . Time On = Time Off
Power
TERMINAL NO.
(1)2-7
(2)A-B
(1)1-4,5-8
(2)1-7,3-9
(1)1-3,6-8
(2)4-7,6-9
OPERATION
(NC)
(NO)
PWR
OUT
Set Time
T
T
(NC)
D: Cycle 3 (power start, ON first)
ITEM
OPERATION
Set Time
OPERATION
Set Time
T
C: Cycle 1 (power start, OFF first)
ITEM
TERMINAL NO.
(1)2-7
(2)A-B
(1)1-4,5-8
(2)1-7,3-9
(1)1-3,6-8
(2)4-7,6-9
T
T
RTE-P2, -B2
B: Cycle 2 (signal start, OFF first)
A: ON-Delay 2 (signal start)
When a preset time has elapsed after the start input turned on while power is on,
the NO output contact goes on .
When the start input turns on while power is on, the output oscillates at a preset
cycle (duty ratio 1:1), starting while the NO contact off .
ITEM
ITEM
Power
Start
Delayed
Contact
Indicator
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(B)1-7,3-9 (NC)
(A)1-3,9-11
(B)4-7,6-9 (NO)
Power
Start
Delayed
Contact
PWR
Indicator
OUT
Set Time
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(B)1-7,3-9 (NC)
(A)1-3,9-11
(B)4-7,6-9 (NO)
PWR
OUT
Set Time
T
C: Cycle 4 (signal start, ON first)
T
T
T
T
T
T
T
T
T
Ta
D: Signal ON/OFF-Delay
When the start input turns on while power is on, the NO output contact goes on .
When a preset time has elapsed while the start input remains on, the output contact
goes off . When the start input turns off, the NO contact goes on again . When a
preset time has elapsed after the start input turned off, the NO contact goes off .
ITEM
ITEM
Power
Start
Delayed
Contact
Indicator
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(NC)
(B)1-7,3-9
(A)1-3,9-11
(NO)
(B)4-7,6-9
Power
Start
Delayed
Contact
PWR
Indicator
OUT
Set Time
T
T
T
T
T
T
T
T
Ta
E: Signal OFF-Delay
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(B)1-7,3-9 (NC)
(A)1-3,9-11
(B)4-7,6-9 (NO)
PWR
OUT
Set Time
T
T
Ta
T
T
Ta
F: One-Shot (signal start)
When power is turned on while the start input is on, the NO output contact goes
on . When a preset time has elapsed after the start input turned off, the NO output
contact goes off .
When the start input turns on while power is on, the NO output contact goes on .
When a preset time has elapsed, the NO output contact goes off .
ITEM
ITEM
Power
Start
Delayed
Contact
Indicator
Set Time
RELAYS & CONTACTORS
When the start input turns on while power is on, the NO contact goes on . The
output oscillates at a preset cycle (duty ratio 1:1) .
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(B)1-7,3-9 (NC)
(A)1-3,9-11
(B)4-7,6-9 (NO)
Power
Start
Delayed
Contact
PWR
Indicator
OUT
T
Ta
T
Ta
TERMINAL NO.
OPERATION
(A)2-10
(B)A-B
(A)5-6
(B)2-5
(A)1-4,8-11
(B)1-7,3-9 (NC)
(A)1-3,9-11
(B)4-7,6-9 (NO)
PWR
OUT
Set Time
T
Ta
Note: T = Set Time, Ta = Shorter than set time, (1): RTE-P1, (2): RTE-B1, (A): RTE-P2, (B): RTE-B2
19
ORDERING INFORMATION
March 2014
MODEL
RTE-B1AD24
RTE-B1AF20
RTE-B2AD24
RTE-B2AF20
RTE-P1AD24
RTE-P1AF20
RTE-P2AD24
RTE-P2AF20
RTE-P1D12
RTE-P2D12
DESCRIPTION
11 Blade 24 VAC/VDC On-delay, interval, off-cycle, on-cycle SR3B-05
11 Blade 100-240 VAC On-delay, interval, off-cycle, on-cycle SR3B-05
11 Blade 24 VAC/VDC On-delay, off-cycle, off-delay, on-cycle, single shot SR3B-05
11 Blade 100-240 VAC On-delay, off-cycle, off-delay, on-cycle, single shot SR3B-05
8 Pin 24 VAC/VDC On-delay, interval, off-cycle, on-cycle SR2P-06
8 Pin 100-240 VAC On-delay, interval, off-cycle, on-cycle SR2P-06
11 Pin 24 VAC/VDC On-delay, off-cycle, off-delay, on-cycle, single shot SR3P-06
11 Pin 100-240 VAC On-delay, off-cycle, off-delay, on-cycle, single shot SR3P-06
8 pin 12 VDC On- Delay, interval, off-cycle, on-cycle SR3P-05C
11 pin 12 VDC On-delay, off-cycle, off-delay, on-cycle, single shot SR3P-05C
SR2P-06
SR3B-05
SR3P-05C
SR3P-06
RELATED PRODUCTS
Relay socket, DPDT pin type, DIN/surface mount
Relay socket, three-pole blade type, DIN/surface mount
Relay socket, SPDT, DPDT, or 3PDT blade type, DIN/surface mount
Relay socket, 3PDT pin type, DIN/surface mount
WE MAKE IT EASY.
kele.com
PAGE
1123
1123
1123
1123
888-397-5353 USA
1159
NEW!
RELAYS & CONTACTORS
MULTIFUNCTION TIMING RELAYS
TRU SERIES
DESCRIPTION
The TRU Series is a multifunction, knob adjustable, universal
time delay relay. It includes six of the most popular timing
functions selected by a slide switch. The time delay is knob
adjustable and the time delay range is switch selectable.
The repeat accuracy is ± 0.1%. Both function and time range
can be selected on the top face of the unit. In addition to
multifunctioning and multiple time ranges, the TRU Series
features universal input voltage; 19 to 264VAC and 19 to
30VDC and full 10A output relay. The TRU Series can directly
replace up to 1000 competitive time delay relay models.
FEATURES
• Microcontroller ±0.1% repeat accuracy
• Six timing functions are switch selectable
• 0.1s - 1000m in six ranges
TRU Series
SPECIFICATIONS
RELAYS & CONTACTORS
Input Voltage
Frequency
Output Type
Contact Configuration
Load Type
Electrical Life
Mechanical Life
19 to 264 VAC and 19 to 30 VDC
50/60 Hz
Electromechanical relay
SPDT & DPDT, isolated
10A resistive @ 120/240 VAC, 28
VDC; 1/3 HP @ 120/240 VAC
1 million operations
10 million operations
Accuracy
±0.1%
Adjustments
4 position DIP switch
Operating Temperature-4° to 149°F to (-20° to 65°C)
Storage Temperature -22° to 185°F (-30° to 85°C)
Mounting
Plug-in socket
Approvals
CE, CSA, UR File #E57310
Weight
0.38 lb (0.17kg)
Warranty
10 years
DIMENSIONS
19
≤2.39
(60.7)
≤1.78
(45.2)
≤2.91 (73.9)
≤3.44 (87.3)
1160
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
MULTIFUNCTION TIMING RELAYS
TRU SERIES
WIRING
L1
8-pin DPDT
Delay-on-Make
Interval
Recycling
N/L2
8-pin SPDT
Delay-on-Make
Interval
Single Shot
RELAYS & CONTACTORS
Recycling (ON Time First,
Equal Recycle Delays)
L1
N/L2
Delay-on-Break
Retriggerable Single Shot
11-pin DPDT
L1
N/L2
19
S1 = Initiate Switch
ORDERING INFORMATION
March 2014
MODEL
TRU1
TRU2
TRU3
DESCRIPTION
Multifunction tming relay, 24-240VAC, 24VDC, DPDT, adjustable 8 pin plug-in
Multifunction timing relay, 24-240VAC, 24VDC, SPDT, adjustable 8 pin plug-in
Multifunction timing relay, 24-240VAC, 24VDC, DPDT, adjustable 11 pin plug-in
NDS-11
NDS-8
RELATED PRODUCTS
11 pin socket base, 300VAC, surface or DIN mount
8 pin socket base, 300VAC, surface or DIN mount
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1161
NEW!
RELAYS & CONTACTORS
MAGNECRAFT TIME DELAY RELAYS
821TD10H, TDRSOXP, TDRSRXP
DESCRIPTION
The Magnecraft 821TD10H, TDRSOXP, and TDRSRXP are
adjustable time delay relays available with various timing
functions. The 821TD10H is a DIN rail mounted product
offering multiple timing functions, multiple timing scales,
and universal voltage input. The TDRSOXP and TDRSRXP
are dual function, low cost time delay relays used with DIN/
surface mount sockets.
Timing Functions
821TD10H - On-delay, Interval, Off-delay, One-shot, Repeat
cycle, Pulse, On & Off-delay, Memory latch
TDRSOXP - On-delay, Interval
TDRSRXP - Off-delay, Retriggerable One-shot
FEATURES
RELAYS & CONTACTORS
• Adjustable timing ranges from 0.1 second to 10 days
(821TD10H)
• Selectable timing functions
• Indication LEDs show power, timing (821TD10H) and
relay energized
• The compact model 821TD10H DIN rail mounts without
a socket
• Models TDRSOXP and TDRSRXP DIN rail or surface
mount with industry standard sockets
19
821TD10H, TDRSOXP, TDRSRXP
SPECIFICATIONS
Coil Rating
821
TDR
12 to 240 VAC/VDC (-15%, + 10%),
3 VA
12/24/120 VAC/VDC (-20%, +10%),
5 VA
Relay Type
821SPDT
TDR, 822DPDT
Contact Rating
821
15A @ 240 VAC, 15A @ 24 VDC
(resistive)
TDR
12A @ 240 VAC, 12A @ 24 VDC
(resistive)
Input Pulse Time
50 ms minimum; 821, SRXP only
Minimum Load
100 mA
Transient Protection Yes
Contact Material
Silver alloy
Electrical Life
821
70,000 operations @ full load
TDR
100,000 operations @ full load
Reverse Polarity
Protected
Wire Size
821
14 AWG maximum
TDR
20-12 AWG with socket
Mechanical Life
10 million operations @ no load
Setting Error
821, 822
±5% of mechanical setting
TDR
±10% of mechanical setting
Time Delay Adjust
Potentiometer, Removeable knob
Time Range
821, 822
0.1 sec to 10 days
TDR
0.1 sec to 10 hours
1162
888-397-5353 USA
kele.com
Repeatability
Reset Time
Timing Functions
0.2%
150 ms maximum
On-delay, interval, Off-delay, Oneshot, Repeat cycle, Pulse, On and
Off-delay, Retriggerable memory
latch, On-delay, interval , Off-delay,
one-shot, On-delay, interval
LED Indication
Green Input Red Blinks = timing, on
= energized
Operating Temperature-4° to 131°F (-20° to 55°C)
Mounting
821DIN rail/surface mount
TDRDIN rail/surface mount socket
Dimensions
TDRSOXP w/socket 2.02" x 1.6" x 0.83"
(5.1 x 4.1 x 2.1 cm)
TDRSRXP w/socket 2.05" x 2.32" x 0.97"
(5.2 x 5.0 x 2.5 cm)
821TD10H
3.5" x 0.69" x 2.55"
(9 x 1.8 x 6.5 cm)
TDRSOXP/TDRSRSP 1.73" x 1.42" x 2.8"
(4.5 x 3.6 x 7.1 cm)
Approvals
821
UL File E234203, RoHS
TDR
UL File E43641, RoHS
Weight
821
0.1 lb (0.05 Kg)
TDR
0.3 lb (0.13 Kg)
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
MAGNECRAFT TIME DELAY RELAYS
821TD10H, TDRSOXP, TDRSRXP
WIRING
External
Control
Switch
3
2
5
4
1
8
4
6
3
7
24 or 120V
Power
(AC or DC)
Non-polarity Sensitive
12-240V Power (AC or DC)
+
6
5
2
1
7
11
8
–
A1 S A2
+
–
Control switch ignored
functions “A” to “E”
Control switch required
functions “F” to “J”
9
10
24 or 120V
Power
(AC or DC)
Non-polarity Sensitive
TDRSOXP
CONTROL
SWITCH
15 16 18
COM NC NO
TDRSRXP
821TD10H
Use shielded wire for external trigger.
Dry switch only.
Use shielded wire for external trigger.
Dry switch only.
OPERATION
S
P
P
t
R
t
t
t
t
Repeat Cycle: OFF First
821 Function: B
t
R
Interval
821 Function: C
TDRSOXP: SW1 ON
S
P
R
t
t
t
Repeat Cycle: ON First
821 Function: F
P - Power
Green
Input
LED
P
R
R - Relay Output
Fine Adjust Knob
On
Output
Red
Relay
LED
45 67
3
8
9
2
1
10
I
II
III
IV
Function
Time
Time
Time
off on
Digital Switches
TDRSOXP
TDRSRXP
t
Pulse
t
Pulse
Pulse (0.5 sec)
821 Function: G
S - Control Switch
Time Range
0.1sec-1sec
1sec-10sec
10sec-100sec
0.1min-1min
1min-10min
10min-100min
0.1hr-1hr
1hr-10hr
t
*
R
S
P
R
R
R
P
P
t - Time Delay
t
t
t
t
t
t
Retriggerable One Shot
821 Function: E
S
t
R
On and Off Delay
S make/break
821 Function: I
P
Memory Latch - S make
821 Function: J
* Retriggerable: time delay period restarts any time the control switch is opened and closed.
Digital Switch Position
II
III
IV
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
TDRSOXP/TDRSRXP
Time Range Selection
OFF-Delay S break
821 Function: D
TDRSRXP: SW1 OFF
S
One-Shot - S make
821 Function: H
TDRSRXP: SW1 ON*
P
Green Input
LED
A1 S A2
+
–
Time Scale
Select
Function
Select
821TD10H
15 16 18
Time Scale
Selection
1 sec
Red Timing/
10 sec
Output LED
1 min
10 min
Time
Adjust
1 hr
Multiplier
10 hr
1 day
10 day
Always ON
Always OFF
Time Adjust
Multiplier
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
RELAYS & CONTACTORS
On-Delay
821 Function: A
TDRSOXP: SW1 OFF
R
P
t
19
ORDERING INFORMATION
MODEL
821TD10H-UNI
TDRSOXP-120
TDRSOXP-24
TDRSRXP-120
TDRSRXP-24
70-464-1
70-465-1
March 2014
DESCRIPTION
Time-delay relay, SPDT, multifunction, 12-240 VAC/VDC, 0.1 sec to 10 days
Time-delay relay, on-delay/interval, 120 VAC/VDC, 0.1 sec to 10 hours
Time-delay relay, on-delay/interval, 24 VAC/VDC, 0.1 sec to 10 hours
Time-delay relay, off-delay/single-shot, 120 VAC/VDC, 0.1 sec to 10 hours
Time-delay relay, off-delay/single-shot, 24 VAC/VDC, 0.1 sec to 10 hours
Relay socket, eight-pin, use with TDRSOXP time delay relay
Relay socket, 11-pin, use with TDRSRXP time delay relay
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1163
NEW!
RELAYS & CONTACTORS
DELAY-ON-MAKE TIMING RELAYS
TMV8000, KRDM
DESCRIPTION
These Delay-on-Make timers cover all the popular voltages
and time delays. These are a cost effective approach for
applications that require small size, isolation, reliability and
long life. Encapsulation protects against shock, vibration and
humidity.
FEATURES
• Onboard adjust time delay
• Compact 2" x 2" size
• Adjustable timing ranges
TMV8000
KRPSA2M
KRDM421
SPECIFICATIONS
RELAYS & CONTACTORS
Operating Temperature
TMV8000
-4° to 158°F (-20° to 70°C)
KRPS
-40° to 140°F (-40° to 60°C)
KRDM
-4° to 140°F (-20° to 60°C)
Storage Temperature
TMV8000
-22° to 185°F (-30° to 85°C)
KRPS/KRDM
-40° to 185°F (-40° to 85°C)
Operating Humidity
Power Consumption
Mounting
Dimensions
Approvals
Warranty
95% RH non-condensing
≤ 2VA for AC; ≤ 2W for DC
Surface mount with one #10 screw
2"W x 2"H x 1.21"D
(5.08 x 5.08 x 3.07 cm)
CE, CSA, UR File #E57310
10 years
WIRING
TMV8000
L1
L1
N/L2
N/L2
Load may be connected
to terminal 3 or 1.
TMV8000 has knob
adjustment.
KRPS Series
V = Voltage
C = Common, Transfer Contact
NC = Normally Closed
NO = Normally Open
S1 = Initiate Switch
UTL = Untimed Load
L1
KRDM Series
N/L2
V = Voltage
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
A knob is supplied for
adjustable units, or RT
terminals 4 & 5 for external
adjust. See external
adjustment vs time delay chart.
Relay contacts are isolated.
A knob is supplied for adjustable
units, or RT terminals 4 & 5 for
external adjust. See external
adjustment vs. time delay chart.
The untimed load is optional. S1
is not used for some functions.
ORDERING INFORMATION
SPECIFICATIONS
TMV8000
KRPSA24M
KRDM221* / KRDM421**
Supply Voltage
24-240 VAC/DC, 50/60 Hz
24-240 VAC/DC, 50/60 Hz
24 VAC/DC* / 120 VAC**, 50/60 Hz
Output Type
Solid State
Isolated Relay Contacts
Isolated Relay Contacts
Output Form
NO, open during timing
SPDT
SPDT
Output Rating (@ 40°C)
1A steady state, 10A inrush @ 55°C
10A @ 125VAC; 5A @ 230VAC; 1/4
hp @ 125VAC
10A @ 125VAC; 5A @ 230VAC &
28VDC; 1/4 hp @ 125VAC
19
Timing Range
0.1 to 8 min adjustable
0.1 to 10 min adjustable
1 - 100 seconds adjustable
Repeat Accuracy
±2%
±0.5% or 20ms, whichever is greater
±0.5% or 20ms, whichever is greater
Timing Tolerance
≤ ± 10%
≤ ± 2%
≤ ± 5%
Reset Time
≤ 100ms
≤ 150ms
≤ 150ms
Circuitry Protection
Encapsultated
Encapsultated
Encapsultated
Isolation Voltage
-
≥ 1500V RMS input to output
≥ 1500V RMS input to output
Insulation Resistance
≥ 100 M Ω
≥ 100 M Ω
≥ 100 M Ω
Termination
.25 in. (6.35mm) male quick
connect terminals
.25 in. (6.35mm) male quick
connect terminals
.25 in. (6.35mm) male quick
connect terminals
Weight
0.15 lb (0.07kg)
0.16 lb (0.08kg)
0.16 lb (0.08kg)
1164
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
LOCKOUT DELAY TIMER
TA, CT SERIES
DESCRIPTION
The TA Series prevents rapid recycling of a compressor. A lockout
delay is started when the thermostat opens, or input voltage is lost.
Eliminates tripped circuit breakers or blown fuses caused by a locked
rotor during short cycling. The TA will not allow the compressor to
start when the line voltage is low. Because of the fast initiate time,
bounce of the thermostat will not be transmitted to the compressor
relay coil. A 30 second delay provides anti-reversing protection for
scroll compressors. The CT Series combines a delay-on-make and
delay-on-break time delay into one unit and may be used to control
fan delays in heating and/or cooling equipment.
CT1S30
FEATURES
T2D120A15M
TA24A3
• Lockout delay prevents rapid recycling of compressor
• Low voltage brownout protection
• Circuitry to activate the cooling anticipator (24VAC models)
SPECIFICATIONS
Operating Temperature
TA / CT Series
-40° to 140°F (-40° to 60°C)
T2D Series
-4° to 140°F (-20° to 60°C)
Storage Temperature -40° to 185°F (-40° to 85°C)
Operating Humidity
95% RH non-condensing
Terminations
0.25 in. (6.35 mm) male quick
connect terminals
Surface mount with one #10 screw
2"W x 2"H x 1.21"D
(5.08 x 5.08 x 3.07cm)
CE, CSA, UR File #E57310
10 years
Mounting
Dimensions
Approvals
Warranty
L1
CT1S30
N
T2D120A15M
L1
TA24A3
N/L2
L1
N
S1 = Initiate Switch,
Contact, or Thermostat
CR = Compressor Relay (Load)
CR = Compressor Relay
THMS = Wall Thermostat
1
Random Start
Plus Lockout
CA = Optional Cooling
Anticipator
V = Voltage
L = Load
S1 = Initiate Switch or Thermostat
V = Voltage
RELAYS & CONTACTORS
WIRING
ORDERING INFORMATION
March 2014
SPECIFICATIONS
CT1S30
T2D120A15M
TA24A3 / TA24A5
Function
DOM & DOB
Lockout
Lockout
Supply Voltage
24 VAC
24 VAC or 120/230 VAC in 2 ranges
12 or 24 VDC, 24 VAC
Output Type
Solid State
Solid State
Solid State
Output Form
NO
NO
NO
Output Rating
0.75A steady state, 5A inrush @ 55°C
1A steady state, 10A inrush @ 60°C
75mA, 1A @ 60°C
Timing Range
1 to 600s
-
-
Lockout Time
-
1s - 100m in 4 adjustable ranges or fixed
fixed 0.5, 1, 2, 3, or 5m
Repeat Accuracy
± 5%
± 1% or 20ms, whichever is greater
-
Timing Tolerance
± 20%
± 30%
-15% to 35%
Circuitry Protection
Encapsultated
Encapsultated
Encapsultated
Anticipator Resistor
≥ 3000 Ω
≥ 3000 Ω
≥ 1800 Ω
Insulation Resistance
≥ 100 MΩ
≥ 100 MΩ
≥ 100 MΩ
Voltage Drop
˜= 1.25V
˜= 2.5V @ 1A
˜= 1.25V
Weight
0.15lb (0.07kg)
0.15lb (0.07kg)
0.15lb (0.07kg)
WE MAKE IT EASY.
kele.com
888-397-5353 USA
19
1165
NEW!
RELAYS & CONTACTORS
DELAY-ON-BREAK TIMING RELAYS
KRDB, KSDB, TDUB
DESCRIPTION
The KRDB Series is a compact time delay relay measuring
only 2 in. (50.8 mm) square. Its microcontroller timing circuit
provides excellent repeat accuracy and stability. The KSDB
Series is designed for general purpose commercial and industrial
applications where a small, cost effective, reliable solid-state timer
is required. This series is designed for popular AC and DC voltage.
The TDUB Series combines digital timing circuitry with universal
voltage operation and offers DIP switch selectable time delays
ranging from 0.1 seconds to 102.3 minutes in three ranges.
FEATURES
KSDB421
KRDB421
• External or onboard adjustment knob
• 1A solid state or Isolated 10Aoutput
• Compact 2 x 2" time delay relay
TDUB3000A
SPECIFICATIONS
Operating Temperature-40° to 140°F (-40° to 60°C)
Storage Temperature
KRDB/TDUB
-40° to 185°F (-40° to 85°C)
KSDB
-40° to 176°F (-40° to 80°C)
Operating Humidity
95% RH non-condensing
Mounting
Dimensions
Approvals
Warranty
Surface mount with one #10 screw
2"W x 2"H x 1.21"D
(5.08 x 5.08 x 3.07 cm)
CE, CSA, UR File #E57310
10 years
RELAYS & CONTACTORS
WIRING
19
L1
N/L2
KRDB421
L1
V = Voltage
S1 = Initiate Switch
C = Common, Transfer Contact
NO = Normally Open
NC = Normally Closed
UTL = Untimed Load (optional)
N/L2
(Positive Switching)
(Negative Switching)
KSDB Series
L1
TDUB3000A
N/L2
UTL = Optional Untimed Load
L = Load
S1 = Initiate Switch
RT is used when external adjustment
is ordered.
UTL = Optional Untimed Load
S1 = Initiate Switch
L = Timed Load
A knob is supplied for
adjustable units. The
untimed load is optional.
Relay contacts are isolated.
ORDERING INFORMATION
SPECIFICATIONS
KRDB421
KSDB421 / KSDB431*
TDUB3000A
Supply Voltage
12, 24, or 110 VDC; 24, 120, or 230 VAC
12, 24, or 110 VDC; 24, 120, or 230 VAC
24 to 240 VAC, 12 to 24 VDC
Output Type
Isolated Relay Contacts
Solid State
Solid State
Output Form
SPDT
NO, closed before & during timing
NO, closed before & during timing
Output Rating (@ 40°C)
10A resistive @ 125VAC; 5A resistive @
230VAC & 28VDC; 1/4 hp @ 125VAC
1A steady state, 10A inrush @ 60°C
1A steady state, 10A inrush @ 60°C
Timing Range
0.1s-1000m in 6 adjustable ranges
or fixed
0.1s-1000m in 6 adjustable ranges
or fixed
0.1-102.3s in 0.1s increments; 1-1023s
in 1s increments
Repeat Accuracy
±0.5% or 20ms, whichever is greater
±0.5% or 20ms, whichever is greater
±0.5% or 20ms, whichever is greater
.
Timing Tolerance
≤ ±5%
≤ ±5%
≤ ±5%
Reset Time
≤ 150ms
≤ 150ms
≤ 150ms
Circuitry Protection
Encapsulated
Encapsulated
Encapsulated
Isolation Voltage
≥1500V RMS input to output
≥2000V RMS terminals to mounting
surface
≥2000V RMS terminals to mounting
surface
Insulation Resistance
≥100 MΩ
≥100 MΩ
≥100 MΩ
Termination
0.25 in (6.35mm)
Male quick connect terminals
0.25 in (6.35mm)
Male quick connect terminals
0.25 in (6.35mm)
Male quick connect terminals
Weight
0.16lb (0.08kg)
0.15lb (0.07kg)
0.15lb (0.07kg)
1166
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
RELAYS & CONTACTORS
KELE MOTOR STARTER INTERFACE
PIL-2
DESCRIPTION
The PIL-2 is designed to provide momentary contact closures
to control motor starters with momentary start/stop push
buttons. The PIL-2 acts as a remote start/stop station using a
single maintained contact from a controller, switch, or relay.
OPERATION
The Model PIL-2 is operated by a single maintained N.C.
or N.O. contact from a switch, relay, or controller. Closing
the input contact causes the N.O. latch output to close
momentarily for 300 ms to start a motor. Opening the input
contact causes the N.C. unlatch output to open momentarily
for 300 ms to stop a motor. A power-up feature allows the
selection of either an immediate pulse out (PUP position),
based on the current state of the input contact, or a pulse out
only when the input contact changes state. LEDs indicate
input state and output latch or unlatch pulses.
PIL-2
SPECIFICATIONS
Supply Voltage
Input
Output
FEATURES
Output Pulse Time
• LED indicators: Pulse out: latch/unlatch, Command
in: off/on
• 24 VAC/DC power
• Selectable power-up state (PUP)
• Snap-track mounting for easy installation
Weight
Warranty
DIMENSIONS
in
(cm)
3
(7.62)
Power-up
jumper
(shown in PUP
position)
PUP
PULSE OUT
UL L
LED Indication
PULSE OUT - UL
PULSE OUT - L
CMD IN - OFF
CMD IN - ON
PIL-2
CMD IN
OFF ON
ON only during unlatch (stop) pulse
ON only during latch (start) pulse
ON only when command contact is open
ON only when command contact is closed
RELAYS & CONTACTORS
24 VAC/VDC @ 50 mA
SPST switch or relay
One N.O. contact rated 120 VAC,
5A; one N.C. contact rated 120
VAC, 5A
300 ms (contact Kele for special
pulse time requiements, 5 sec
maximum)
0.25 lb (0.11 kg)
18 months
2.25
(5.72)
PWR PWR CMD
IN
+ –
+
24 VAC/VDC
–
19
UL L
Latch (start)
Power
Starter coil
Unlatch
(stop)
Power
Command
contact
Local start (push button)
Command
M
L1
Local stop
(push button)
L2
Starter hold-in contact
ORDERING INFORMATION
MODEL
PIL-2
PIL-2-C
March 2014
DESCRIPTION
Motor starter interface, 300 ms pulse
Motor starter interface, special pulse (specify when ordering)
WE MAKE IT EASY.
kele.com
888-397-5353 USA
1167
NEW!
RELAYS & CONTACTORS
MOTOR LOAD SIZING
A resistive load is one that offers simple resistance to the
flow of current. An example would be an electric heater.
An inductive load would be found in a motor,
transformer, solenoid, or other device that has
magnetizing coils. Inductive loads are often rated in amps
with a separate motor rating in horsepower. They are
characterized by high inrush current when contacts close,
and by resistance to the stopping of current flow when
contacts open (arcing).
A pilot duty load is another specific type of inductive load
that often has a separate rating. Pilot duty ratings come
into play when relay contacts control the coils of other
relays or contactors.
FULL LOAD CURRENT (AMPS) VS HP
THREE PHASE
SINGLE PHASE
Volts
115V
230V
460V
115V
230V
HP
1/6
4.4
2.2
1/4
5.8
2.9
1/3
7.2
3.6
1/2
4
2
1
9.8
4.9
3/4
5.6
2.8
1.4
13.8
6.9
1
7.2
3.6
1.8
16
8
1-1/2
10.4
5.2
2.6
20
10
2
13.6
6.8
3.4
24
12
5
15.2
7.6
56
28
7-1/2
22
11
80
40
10
28
14
100
50
15
38
19
20
52
26
25
64
32
30
77
39
40
101
51
RELAYS & CONTACTORS
A lighting load can be ballast type (fluorescent and
HID lighting) or tungsten (incandescent). Ballasts are
somewhat inductive, particularly the non-electronic types.
Tungsten lighting presents a very low resistance at startup (high starting current) when the filaments are cold, but
behaves like a resistive load once the lamps are bright
and hot. Tungsten loads can be the most destructive of all
to a relay’s contacts unless they are specifically designed
to handle such an inrush.
MOTOR LOAD SIZING
19
1168
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
Was this manual useful for you? yes no
Thank you for your participation!