Application Engineering Bulletin

AE-1301 Issued June, 1996

Introduction

The new model family of "ZP" compressors is designed for high pressure R-410A refrigerant, a chlorine free replacement for R-22. R-410A operates at approximately 50 to 70 percent higher pressure at the same saturated temperatures than R-22. Several design changes had to be made to the scroll compressors to accommodate the operating differences between R-

22 and the new refrigerant. These will be covered later in the bulletin.

The new models include an internal pressure relief valve, an internal discharge gas temperature sensor, and a device to limit the shut down noise caused by scroll reversal. The compressor shell thickness was increased to handle the higher required pressures.

Operating principles of the Compliant Scroll are described in Copeland Application Engineering Bulletin

AE 4-1280.

Field Replacement of a "ZP" Compressor

The ZP**K*E-XXX Scroll compressor is a unique design for R-410A refrigerant and must never be replaced with a "ZR" family scroll compressor. The "P" in the model number designates that this compressor has a housing designed for the higher pressure encountered with 410A. Use of a compressor that is not specifically designed for R-410A may cause shell

rupture and personal injury. R-410A has greater enthalpy per unit volume than R-22. For this reason the displacement is smaller vs. motor power in the "ZP" scroll than an equivalent capacity R-22 compressor.

Using an R-22 compressor in a 410A system may cause the compressor to stall. Conversely using a "ZP" compressor in an R-22 system would result in a drastic system capacity reduction.

APPLICATION GUIDELINES FOR

ZP**K*E SCROLL COMPRESSORS

FOR R-410A

Application Considerations

The Compliant Scroll is a unique type of compressor, and there are a number of application characteristics which are different from the traditional reciprocating compressor. These are detailed below.

Accumulators

Due to the Compliant Scroll’s inherent ability to handle liquid refrigerant in flooded start and defrost cycle operation, no accumulator is required for durability below system charge levels listed in the Scroll Compressor Application Diagram (Table 1). However, large volumes of liquid refrigerant which repeatedly migrate to the compressor during normal off cycles or excessive liquid refrigerant floodback during steady operation can dilute the oil in any compressor to the point that bearings are inadequately lubricated and wear may occur. To test for these conditions, see the section entitled EXCES-

SIVE LIQUID REFRIGERANT FLOODBACK TESTS at the end of this Bulletin. If an accumulator is used it is recommended that it be sized to hold from 50% to 70% of the system charge. The oil return orifice in the accumulator should be around .055. See "Excessive

Liquid Floodback Tests" and Figure 1 to determine the effectiveness of the accumulator.

Crankcase Heat - Single Phase

Generally no crankcase heat is required for single phase compressors. When the system charge exceeds the recommended limit, the compressor may fill with refrigerant under certain circumstances and configurations. This may cause excessive clearing noise, or the compressor may lock up and trip on protector several times before starting. A crankcase heater may be of benefit in the initial design or as a field fix under these circumstances. See AE 22-1182 for recommendations.

© 1996 Copeland Corporation

Copeland 4-1301

Crankcase Heat - Three Phase

A crankcase heater is required for three phase compressors when the system charge exceeds 10 lbs.

and no accumulator can not be piped to provide free liquid drainage into the accumulator during the off cycle

(See Figure 2 and Table 1).

Reversing Valves

Since Compliant Scroll compressors have very high volumetric efficiency, their displacements are lower than for comparable capacity reciprocating compressors. As a result, Copeland recommends that the capacity rating on reversing valves be no more than 1.5 to

2 times the nominal capacity of the compressor in order to ensure proper operation of the reversing valve under all operating conditions.

The reversing valve solenoid should be wired so that the valve does not reverse when the system is shut off by the operating thermostat in the heating or cooling mode. If the valve is allowed to reverse at system shutoff, suction and discharge pressures are reversed to the compressor. This results in a condition of system pressures equalizing through the compressor which can cause the compressor to slowly rotate until the pressure equalizes. This condition does not affect compressor durability but can cause unexpected sound after the compressor is turned off.

Motor Protection

Conventional inherent internal line break motor protection is provided.

Oil Type

The "ZP" compressors use a polyolester (POE) oil.

If oil must be added or replaced in the field only Mobil

EAL ARCTIC 22CC or ICI EMKARATE RL32CF may be used. See nameplate for original oil charge shown in fluid ounces. A field recharge is from 2 to 4 fl. oz. less.

POE oil absorbs moisture much quicker and to a greater degree than standard mineral oil. The compressor must not be left open longer than 15 minutes during replacement. During installation the system must be swept with an inert gas such as nitrogen to keep moisture from entering the compressor and prevent the formation of oxides.

Filter Drier

Use of a filter drier is required on all systems using

POE oil. See AE 11-1297 for filter recommendations.

After a burn-out a 100% Activated Alumina filter drier may be used in the suction line for acid clean up, but the filter must be removed after 72 hours.

2

Suction and Discharge Mufflers

Flow through Compliant Scroll Compressors is semi-continuous and has relatively low pulsations. External mufflers, where they are normally applied to piston compressors today, may not be required for Compliant

Scroll. Because of variability between systems, however, individual system tests should be performed to verify acceptability of sound performance, especially heat pumps. When no testing is performed, mufflers are recommended in heat pumps.

Low Ambient Cut-Out

Low ambient cut-outs are not required to limit heat pump operation.

Single Phase Starting Characteristics

No start assist devices are ever required, even if a system utilizes non-bleed expansion valves. Due to the inherent design of the Compliant Scroll, the internal compression components always start unloaded even if system pressures are not balanced. In addition, since internal compressor pressures are always balanced at startup, low voltage starting characteristics are excellent for Compliant Scroll compressors. "ZP" Scrolls require two minutes off time to restart after shut-off to allow for internal equalization of pressure. (See later paragraph on “Shutoff Sound” and "Brief Power Interruptions" for explanation)

Fusite

The orientation of the pins on the Fusite for Compliant Scroll compressors is shown in Figure 4 and is also shown inside the terminal box.

Deep Vacuum Operation

"ZP" scrolls incorporate internal low vacuum protection, and stop pumping (unload) when the pressure ratio exceeds approximately 10:1.

Compliant Scroll compressors (as with any refrigerant compressor) should never be used to evacuate a refrigeration or air conditioning system. (See Application

Engineering Bulletin AE 24-1105 for proper system evacuation procedures.)

Nomenclature

The model numbers of Compliant Scroll compressors include the nominal capacity at standard operating conditions. Please refer to the product literature for details pertaining to other information contained in the model number.

Shell Temperature

Under rare circumstances caused by failure of system components (such as the condenser or evapo-

rator fan), or loss of charge, and depending on the type of expansion control, the top shell and discharge line can briefly but repeatedly reach temperatures above

350°F as the compressor cycles on its internal protection devices. Care must be taken to ensure that wiring or other materials which could be damaged by these temperatures do not come in contact with the shell.

IPR Valve

ZP Compliant Scroll Compressors have internal pressure relief valves which open at a discharge to suction differential pressure of 550 to 625 psi.

Shutoff Sound/Check Valve

A low mass, disc type, check valve in the discharge tube of the compressor prevents the discharge gas from equalizing through the Scroll. This valve is not designed to be used for pump down because its higher leak rate may cause the compressor to recycle too often.

The "ZP" scroll compressors incorporate a device which prevents reverse rotation and eliminates the shutoff noise associated with earlier scrolls. Since the scroll cannot reverse, it may take two minutes for the high pressure gas trapped in the dome of the compressor to bleed down before the compressor can restart.

Suction Tubes

Compliant Scroll compressors have copper plated steel suction tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other compressors. Due to the different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. See Figure 5 for suggestions for assembly line and field brazing procedures.

Three Phase Scroll Compressors

Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction. However, three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a 50-50 chance of connecting power in such a way as to cause rotation in the reverse direction, it is important to include notices and instructions in appropriate locations on the equipment to ensure proper rotation direction is achieved when the system is installed and operated. Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation results in an elevated sound level, as well as substantially reduced current draw compared to tabulated values.

Copeland 4-1301

There is no negative impact on durability caused by operating three phase Compliant Scroll compressors in the reversed direction for a short period of time. However, after several minutes of operation the compressor’s internal protector will trip. Reverse operation for over one hour may have a negative impact on the bearings.

All three phase scroll compressors are wired identically internally. As a result, once the correct phasing is determined for a specific system or installation, connecting properly phased power leads to the same Fusite terminals should maintain proper rotation direction.

Brief Power Interruptions

No time delay is required on three phase models to prevent reverse rotation due to power interruptions.

Single phase “ZP” scroll compressor incorporate a clutch that prevents backward rotation. Because of this device a time delay is no longer required on this model, however the scroll will stall and trip on protector during a brief power interruption. Should a time delay be used see Figure 3 for specification.

Assembly Line System Charging Procedure

Rapid charging only on the suction side of a scroll equipped system or condensing unit can occasionally result in a temporary no-start condition for the compressor. The reason for this is that if the flanks of the compressor happen to be in a sealed position, rapid pressurization of the low side without opposing high side pressure can cause the scrolls to seal axially. As a result, until the pressures eventually equalize, the scrolls can be held tightly together, preventing rotation. The best way to avoid this situation is to charge on both the high and low side simultaneously at a rate which does not result in axial loading of the scrolls. The maximum charging rate can be determined through simple tests.

Unbrazing System Components

If the refrigerant charge is removed from a scroll equipped unit by bleeding the high side only, it is sometimes possible for the scrolls to seal preventing pressure equalization through the compressor. This may leave the low side shell and suction line tubing pressurized. If a brazing torch is then applied to the low side while the low side shell and suction line contains pressure, the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame. To prevent this occurrence, it is important to check both the high and low side with manifold gauges before unbrazing, or in the case of repairing a unit on an assembly line, remove refrigerant from both the high and low side. Instructions should be provided in appropriate product literature and assembly (line repair) areas.

3

Copeland 4-1301

Air Conditioning System Suction Line Noise and

Vibration

Copeland Compliant Scroll compressors inherently have low sound and vibration characteristics. However, in some respects, the sound and vibration characteristics differ from reciprocating compressors and, in rare instances, could result in unexpected sound complaints.

One difference is that the vibration characteristic of the scroll compressor, although low, includes two very close frequencies, one of which is normally isolated from the shell by the suspension of an internally suspended compressor. These frequencies, which are present in all compressors, may result in a low level

“beat” frequency which can be detected as noise coming along the suction line into a house under some conditions. Elimination of the “beat” can be achieved by attenuating either of the contributing frequencies. This is easily done by using one of the common combinations of design configurations described in Table 3.

which can be damaged, it is not necessary to perform functional compressor tests where the compressor is turned on with the suction service valve closed to check how low the compressor will pull suction pressure. In fact this type of test may actually damage a Compliant

Scroll compressor (and other types of compressors, also). Rather, the following diagnostic procedure should be used to evaluate whether a Compliant Scroll compressor is functioning properly.

1.

2.

Proper voltage to the unit should be verified.

The normal checks of motor winding continuity and short to ground should be made to determine if the inherent overload motor protector has opened or if an internal short to ground has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to allow it to reset.

3.

Proper indoor and outdoor fan/blower operation should be verified.

A second difference of the Compliant Scroll is that under some conditions the normal rotational starting motion of the compressor can transmit an 'impact' noise along the suction line. It may be particularly pronounced in three phase models due to their inherently higher starting torque. This phenomenon, like the one described previously, also results from the lack of internal suspension, and can be easily avoided by using standard suction line isolation techniques as described in

Table 3.

4.

With service gauges connected to suction and

5.

discharge pressure fittings, turn on the compressor.

If suction pressure falls below normal levels the system is either low on charge or there is a flow blockage in the system.

Single Phase Compressors

The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends.

If suction pressure does not drop and discharge pressure does not rise to normal levels, either the reversing valve (if so equipped) or the compressor is faulty. Use normal diagnostic procedures to check operation of the reversing valve.

Three Phase Compressors

Hipot Testing

Compliant Scroll compressors are configured with the motor below the compressor. As a result, the motor can be immersed in refrigerant to a greater extent than hermetic reciprocating compressors when liquid refrigerant is present in the shell. In this respect, the scroll is more like semi-hermetic compressors (which have horizontal motors partially submerged in oil and refrigerant).

When Compliant Scroll compressors are Hipot tested and liquid refrigerant is in the shell, they can show higher levels of leakage current than compressors with the motor on top. However, this phenomenon can occur with any compressor when the motor is immersed in refrigerant. The level of current leakage does not present any safety issue. To lower the current leakage reading, the system should be operated for a brief period of time to redistribute the refrigerant.

6.

If suction pressure does not drop and discharge pressure does not rise to normal levels, reverse any two of the compressor power leads and reapply power to make sure the compressor was not wired to run in reverse direction. If pressures still do not move to normal values, either the reversing valve (if so equipped) or the compressor is faulty. Reconnect the compressor leads as originally configured and use normal diagnostic procedures to check operation of the reversing valve.

If the reversing valve (if so equipped) checks out satisfactorily, then the compressor current draw must be compared to published compressor performance curves at the compressor operating conditions (pressures and voltages), and significant deviations (±15%) from published values may indicate a faulty compressor.

Compliant Scroll Functional Check Excessive Liquid Floodback Tests

Since Compliant Scroll compressors do not have internal suction valves or dynamic discharge valves

4

The following tests are for those system configurations and charge levels identified in Table 1 where special testing is needed to eliminate the use of an accumulator.

To test for excessive continuous liquid refriger-

ant floodback, it is necessary to operate the system in a test room at conditions where steady state floodback may occur (low ambient heating operation). Thermocouples should be attached to the suction and discharge lines (approximately 6 inches from the shell) as well as the sump (middle of the bottom) of the compressor and insulated. If the system is designed to be field charged, it should be overcharged by 15% in this test to simulate overcharging commonly found in field installations.

The system should be operated at an indoor temperature of 70°F. and outdoor temperature extremes

(0°F. or lower in heating) which produce floodback conditions. The compressor suction and discharge pressures and temperatures should be recorded. The system should be allowed to frost up for several hours

(disabling the defrost control and spraying water on the outdoor coil may be necessary) to cause the saturated suction temperature to fall to -20°F or below. The compressor sump temperature must remain above saturated suction temperature as shown in Figure 1 or design changes must be made to reduce the amount of floodback.

Copeland 4-1301

To test for repeated excessive liquid floodback during normal system off-cycles perform the “Field

Application Test”. Obtain a sample compressor with a sight tube to measure liquid level in the compressor. Set the system up in a configuration with the indoor unit elevated several feet above the outdoor unit with twentyfive feet of connecting tubing with no traps between the indoor and outdoor units. If the system is designed to be field charged, the system should be overcharged by

15% in this test to simulate overcharging commonly found in field installations. Operate the system in the cooling mode at the outdoor ambient, on/off cycle times, and number of cycles specified in Table 2. Record the height of the liquid in the compressor at the start of each on cycle, any protector trips, or any compressor stalls during each test.

After the last test continue running the compressor if no oil shows in the sight tube. Monitor the time till the oil first reappears. Review the results with Copeland

Application Engineering to determine if an accumulator is required or changes need to be made to the system.

40

Sump Temp

Minus

Evap. Temp

30

Temp

20

10

0

-10

Safe Zone

0 10 20 30

°F Evaporating Temperature

Figure 1

40 50

5

Copeland 4-1301

Table 1

Scroll Compressor Application Diagram

6

Table 2

Field Application Test

Operate the system as It would be operated in an actual field installation, cycling the unit on and off for the times indicated at each ambient.

Outdoor Ambient (°F) 85

System On-Time (Minutes) 7

System Off-Time (Minutes) 13

Number of On/Off Cycles 5

95 105

14 54

8

5

6

4

Copeland 4-1301

Table 3

Recommended Configuration

Component Description

Tubing Configuration Shock loop

Service Valve “Angled valve” fastened

Suction muffler to unit

Not required

Alternate Configuration

Component Description

Tubing Configuration Shock loop

Service Valve “Straight through” valve

Suction muffler fastened to unit

May be required (Acts as dampening mass)

Liquid Level

Drainage In

Off Cycle

Scroll Accumulator

To prevent flooded start damage on 3 phase Scrolls due to off cycle migration, the accumulator may be configured on some systems to allow free drainage from the compressor to the accumulator during the off cycle.

When the above configuration is not possible, a crankcase heater is required.

3 Phase Scrolls

Charge Over 10 lbs.

Figure 2

7

Copeland 4-1301

Figure 3

T1

C

T

3

R

S

T

2

Motor Terminal (Fusite) Connections

Figure 4

8

Copeland 4-1301

New Installations

• The copper-coated steel suction tube on scroll compressors can be brazed in approximately the same manner as any copper tube.

• Recommended brazing materials: Any silfos material is recommended, preferable with a minimum of 5% silver. However, 0% silver is acceptable.

• Be sure suction tube fitting I.D. and suction tube

O.D. are clean prior to assembly.

• Using a double-tipped torch apply heat in Area 1.

As tube approaches brazing temperature, move torch flame to Area 2.

• Heat Area 2 until braze temperature is attained, moving torch up and down and rotating around tube as necessary to heat tube evenly. Add braze material to the joint while moving torch around joint to flow braze material around circumference.

• After braze material flows around joint, move torch to heat Area 3. This will draw the braze material down into the joint. The time spent heating Area 3 should be minimal.

• As with any brazed joint, overheating may be detrimental to the final result.

Field Service

• To disconnect: Heat joint Areas 2 and 3 slowly and uniformly until braze material softens and tube can be pulled out of suction fitting.

• To reconnect:

• Recommended brazing materials: Silfos with minimum 5% silver or silver braze material with flux.

• Reinsert tube into fitting.

• Heat tube uniformly in Area 1, moving slowly to Area 2. When joint reaches brazing temperature, apply brazing material.

• Heat joint uniformly around the circumference to flow braze material completely around the joint.

• Slowly move torch into Area 3 to draw braze material into the joint.

• Do not overheat joint.

9