MODEL: R8-SS2 Remote I/O R8 Series

MODEL: R8-SS2 Remote I/O R8 Series
MODEL: R8-SS2
Status indicator: Bi-color (red/green) LED; Refer to the
instruction manual.
Input status indicators: Red LED; Refer to the instruction
manual.
Remote I/O R8 Series
DC CURRENT INPUT MODULE
(2 points, isolated)
Functions & Features
• 2 channels for DC current input, compact size remote I/O
module
• Isolation between channels
• Input range adjustment with DIP switch or PC configurator
INPUT
Input range: -20 – +20 mA DC configurable
Input range: -5 - +105 % (in percentage of input range)
Input resistance: 100 Ω
INSTALLATION
12 (.47)
Max. current consumption: 100 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 60 g (2.12 oz)
115 (4.53)
59 (2.32)
mm (inch)
PERFORMANCE
MODEL: R8–SS2
ORDERING INFORMATION
• Code number: R8-SS2
RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC. Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.
GENERAL SPECIFICATIONS
Connection
•Input: 4-pin e-CON connector
PWB connector XN2D-1474-S002 (Omron)
Recommended cable connector XN2A-1470 (Omron)
Applicable wire size 0.08 mm2 (AWG28) - 0.5 mm2 (AWG20)
Outer sheath diameter: max. 1.5 dia
(The cable connector is not included in the package.
Refer to the specifications of the product.)
•Excitation supply, internal bus:
Connected to internal bus connector
•Internal power: Supplied from internal bus connector
Isolation: Input 1 to input 2 to exc. supply to internal bus or
internal power
Module address: With rotary switch
Terminating resistor: Built-in (DIP Switch, default: disable)
http://www.m-system.co.jp/
Conversion accuracy (in percentage of input range)
±0.1 % (@ input range -20 - +20 mA)
Conversion accuracy is inversely proportional to input span.
Conversion accuracy computation example:
When input range is 4 - 20 mA: conversion accuracy =
nominal input span (40 mA) ÷ input span (16 mA) × 0.1(%)
= 0.25 (%).
Nominal input span is the same as the span at input range
-20 - +20 mA DC.
Conversion rate: 2 msec.
Input circuit time constant: Approx. 1 msec.
Data range: 0 – 10000 of the input range
Data allocation: 2
Module addresses in use: 1
Max. consumption current: 100 mA
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1000 V AC @ 1 minute (input 1 to input 2 to exc. supply to
internal bus or internal power to FG)
1000 V AC @ 1 minute (for modules combined with this
device)
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
R8-SS2 SPECIFICATIONS
ES-9730 Rev.0 Page 1/3
MODEL: R8-SS2
EXTERNAL VIEW
FRONT VIEW
SIDE VIEW
Module Address Setting
Rotary SW
Status Indicator LED
456
78
78
456
CARD ADD.
x10
901
23
901
456
456
78
23
Input Status Indicator LED
78
23
RUN
901
901
SW1
SW2
x1
23
Function Setting
DIP SW
Internal Bus Connector
On
SW4
12345678
Input Connectors
On
Term
SW3
AI_I1
Terminator DIP SW
AI_I2
OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW4-3 through 4-7 are unused. Be sure to turn
off unused ones.
■ MODULE ADDRESS
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Address is selected between 0 to 31.
(Factory setting: 0)
Terminator switch
Without (*)
With
SW3
OFF
ON
901
23
456
23
7 8
901
7 8
■ Terminator DIP SW
456
Module Address Setting (x1)
Module Address Setting (x10)
■ Range
Same range for all channels. Use PC Configurator to set
independent ranges per channel.
INPUT RANGE
0 − 20mA DC
4 − 20mA DC (*)
SW4-1
OFF
ON
SW4-2
OFF
OFF
■ Configuration Mode
CONFIGURATION MODE
SW4
8
DIP switch setting (*)
OFF
PC Configurator and communication
ON
http://www.m-system.co.jp/
R8-SS2 SPECIFICATIONS
ES-9730 Rev.0 Page 2/3
MODEL: R8-SS2
6 (.24) 7 (.28)
DIMENSIONS unit: mm (inch)
12 (.47) [3 (.12)]
59 (2.32)
[4 (.16)]
55 (2.17)
7 (.28) 6 (.24)
115 (4.53)
DIN RAIL
(35 mm wide)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
+24V
STATUS INPUT
IND. STATUS LED
EXC. SUPPLY*1
Isolation
+
1
NC
2
NC
3
-
4
INPUT1
0V
Communication
Circuit
A/D
Conversion
Control
Circuit
BUS CONNECTOR
INPUT CONNECTOR 1
INTERNAL
BUS
Isolation
INPUT CONNECTOR 2
+
1
NC
2
NC
3
-
4
INPUT2
ROTARY SW
DIP SW
INTERNAL
POWER
A/D
Conversion
*1. Not used
Specifications are subject to change without notice.
http://www.m-system.co.jp/
R8-SS2 SPECIFICATIONS
ES-9730 Rev.0 Page 3/3