Mitsubishi-Ducted
H E AT P U M P S
AIR CONDITIONING
01-02
Advanced Power Inverter
Advanced Power Inverter
Silent Control
Mitsubishi Electric’s new Power Inverter systems drastically
reduce power consumption
Fan speed during cooling operation is automatically reduced when
the outdoor temperature drops, resulting in quiet, low-noise operation.
Operating noise is reduced by 3dB, to half of the audible sound.
To better meet the needs of shops and offices, our outdoor units are
now offered in single-phase models. Select the model to best match
your needs from our expanded model range.
Suppressed to
Model RP140
(cooling)
Day
50dB
Previous R22 model
Night
47dB
Outdoor temperature: 35°C
NEW
“Silent Control”
reduces sound further
about 1/2 the audible sound
(compared to daytime use)
Outdoor temperature: 25°C
1/2
noise
DAY
NIGHT
1/3
noise
PUHZ-RP/100/125/140/
170/200
52dB
47dB
(during cooling mode)
R22
(during cooling mode)
R410A
Inverter units (PUHZ-RP)
Non-inverter units
NEW
44dB
(during cooling mode)
Normal
Low-noise Mode
71 class
52
47
44
100 class
54
49
46
125 class
55
50
47
140 class
56
50
47
*Sound pressure level (dBA)
Side-flow Outdoor Units
Operating capacities up to 20kW have been unified to the side-flow.
All operating capacities have been unified to the side-flow configuration. Even for locations requiring large capacities, the small footprint
of these outdoor units enable them to be used anywhere.
PUHZ-RP71
PUHZ-RP71
PUHZ-RP100/125/140/170/200
Longer Maximum Piping Length
PUHZ-RP250YHM-A
As a result of increasing the volume of refrigerant, piping length has
been increased to a maximum of 75m, expanding the range of layout
possibilities for unit installation.
Max. piping length can be stretched to
71
Single-phase
Three-phase
100
125
140
170
200
250
75m
Max. height difference
Max. piping length
PUHZ-RP71
30m
50m
PUHZ-RP
100/125/140/
170/200/250
30m
75m
Outdoor Line-up (PUHZ-RP series)
High Energy Efficiency
With the latest inverter technology, energy efficiency is improved in
cooling operation and heating operation from previous models. This
contributes to further reductions in product power consumption.
100 class
170 class
3.40
3.80
3.60
3.40
12%
3.54
36%
3.28
UP
3.20
UP
UP
2.79
2.60
2.60
2.40
2.41
2.40
2.33
2.20
2.20
2.00
2.00
PEA-RP
100EAQ
PUHZ-RP
100V(Y)KA
PEA-RP
100EA2
PUHZ-BP
100VHA
Cooling
PEA-RP
100EAQ
PUHZ-RP
100V(Y)KA
PEA-RP
170WHA
PUHZ-RP
170Y(V)KA
PEA-RP
100EA2
PUHZ-BP
100VHA
PEA-RP
170WGA
PUHZ-BP
170YHA
Cooling
Heating
125 class
PEA-RP
170WHA
PUHZ-RP
170Y(V)KA
PEA-RP
170WGA
PUHZ-BP
170YHA
Heating
200 class
3.80
19%
3.64
3.60
UP
3.40
3.07
22%
2.95
3.20
23%
3.19
3.12
UP
2.60
2.60
2.60
2.40
2.41
2.40
UP
3.25
2.80
UP
2.80
4%
3.40
3.00
3.20
2.20
2.20
2.00
2.00
PEA-RP
125EAQ
PUHZ-RP
125V(Y)KA
PEA-RP
125EA
PUHZ-BP
125VHA
Cooling
PEA-RP
125EAQ
PUHZ-RP
125V(Y)KA
PEA-RP
125EA
PUHZ-BP
125VHA
PEA-RP
200WHA
PUHZ-RP
200YKA
Heating
PEA-RP
200WGA
PUHZ-BP
200YHA
Cooling
PEA-RP
200WHA
PUHZ-RP
200YKA
PEA-RP
200WGA
PUHZ-BP
200YHA
Heating
250 class
140 class
4.00
13%
3.74
3.80
UP
3.60
3.40
3.30
3.20
3.00
UP
33%
3.10
2.80
2.80
19%
3.33
3.00
3.15
3.00
3.00
3.20
2.60
UP
3.00
18%
3.05
3.10
UP
2.58
2.60
2.40
2.41
2.40
3.30
3.20
2.80
20%
2.90
2.80
3.40
2.20
2.20
2.00
2.00
PEA-RP
140EAQ
PUHZ-RP
140V(Y)KA
PEA-RP
140EA2
PUHZ-BP
140VHA
Cooling
PEA-RP
140EAQ
PUHZ-RP
140V(Y)KA
PEA-RP
140EA2
PUHZ-BP
140VHA
Heating
PEA-RP
250WHA
PUHZ-RP
250YHM-A
PEA-RP
250WGA
PUHZ-BP
250YHA
Cooling
PEA-RP
250WHA
PUHZ-RP
250YHM-A
PEA-RP
250WGA
PUHZ-BP
250YHA
Heating
03-04
Advanced Power Inverter
High Power
More Power for Faster Cooling/Heating
Comparison of EER (cooling mode)
Comparison of EER between non-inverter and Power Inverter
(4-way cassette) models.
Improved Cooling/Heating Performance
The maximum operating speed and cooling/heating capacity of
the new Mr. Slim Power Inverter units have been improved by as
much as 33% (compared to conventional non-inverter models)
when operating in either low or high outdoor temperatures.
Average
EER
4.00
4.0
Cooling capacity
51%
increase
R22
Non-inverter
80%
UP
3.40
3.5
57%
UP
3.29
41%
7.7
8.1
105%
100
9.7
11.4
118%
125
12.4
14.0
113%
140
14.0
15.3
109%
Heating capacity
R22
Non-inverter
25%
UP
2.22
2.33
2.17
Outdoor Unit
71
3.08
UP
3.0
71 class
Power Inverter Model
100 class
125 class
4-way cassette
R410A
Power inverter max. (PUHZ-RP)
2.47
140 class
4-way cassette
R410A
Power inverter max. (PUHZ-RP)
71
8.4
10.2
121%
100
10.4
14.0
135%
125
14.0
16.0
114%
140
16.1
18.0
112%
Non-inverter Model
Wider Performance Range
Operation is now possible at lower speeds, thus cutting energy losses
produced by the repeated On/Off operation of non-inverter models.
Comfort is improved while power consumption is reduced.
Cooling capacity ranges
71 class 3.3-8.1 kW
100 class 4.9-11.4 kW
125 class 5.5-14.0 kW
140 class 6.2-15.3 kW
0
2
4
6
8
10
12
14
16
18kW
16
18kW
Heating capacity ranges
71 class 3.5-10.2 kW
100 class 4.5-14.0 kW
125 class 5.0-16.0 kW
140 class 5.7-18.0 kW
0
2
4
6
8
10
12
14
Advanced Energy Saving Technologies
Highly efficient fan and grille for outdoor unit
Highly efficient heat exchanger
The shapes of the fan and grille of the outdoor unit were redesigned,
realising an increase in blowing capacity and more efficient heat
exchange while maintaining the same operating noise level.
A high density and increase in surface area have improved the
heat-exchange efficiency of the heat exchanger.
Outdoor unit fan opening increased <PUHZ–RP100–200>
High-density heat exchanger <PUHZ–RP100–200>
The diameter of the opening for the fan in the outdoor unit
has been increased from 490 to 550mm. Blowing capacity
has been increased while maintaining the same fan rotation
speed.
The pipe diameter has been changed
from 9.52 to 7.94mm, resulting in a
high-density heat exchanger.
2 lines, 52 columns
2 lines, 64 columns (RP100 –170)
Opening increased
from 490 to 550cm
in diameter
Heat-exchange surface area increased
<PUHZ–RP100–200>
Heat exchanger size extended horizontally, increasing the
surface area.
Increase in heat-exchanger surface area
Grille shape changed <PUHZ–RP71–200>
The shape of the air outlet grille has been changed to
reduce pressure loss. This has helped improve heat exchange performance.
Heat exchanger
Heat exchanger
Heat Interchanger (HIC) Added <RP140>
An HIC circuit has been added to improve energy efficiency during
cooling operation. Liquid refrigerant is rerouted, transformed into a
gas state and injected back into the system to increase overall pressure of the refrigerant being sent to the compressor, thereby reducing
the load on the compressor and raising efficiency.
Cooling operation
Inflexed fan <PUHZ–RP100–200>
Indoor
HEX
Adoption of a fan with improved ventilation characteristics
and a newly designed rear edge that suppresses wind turbulence raises fan operation efficiency.
A
A
w/ HIC circuit
w/o HIC circuit
Fan rear edge
Heat
interchanger
(HIC)
Outdoor
HEX
Power
receiver
LEV A
LEV B
Heat Interchanger (HIC)
Compressor
LEV C
Increasing the pressure of the
refrigerant sent to the compressor
reduces the compression load
Advanced Power Inverter
05-06
Advanced Technology for High Efficiency
Numerous Leading-edge Technologies
Assure High Efficiency
Reluctance DC Rotary Compressor (PUHZ-RP71)
DC Fan Motor (PUHZ-RP71/100/125/140/170/200)
The reluctance DC motor has a rotor equipped with powerful
neodymium magnets. The magnetic torque produced by the neodymium
magnets and reluctance torque results in more efficient operation.
A highly efficient DC motor has been installed to drive the fan of
outdoor units, realising up to 60% higher efficiency when compared to an equivalent AC motor.
Vector-Wave Eco Inverter
DC compressor motor (rotor)
This inverter monitors the varying compressor motor frequency and
creates the most efficient waveform for the motor speed. As a result,
operating efficiency in all speed ranges is improved, less power is
used and annual electricity costs are reduced.
Smooth AC wave pattern
Neodymium magnets
Magnetic torque
+
The inverter has been made more compact by inserting the
circuitry inside a synthetic resin molding.
To ensure quiet operation, soft PWM control is used to
prevent the metallic whine associated with conventional
inverters.
Reluctance torque
Sine-wave drive soft PWM
Highly Efficient Scroll Compressor
(PUHZ-RP100/125/140/170/200)
Higher efficiency has been achieved by adding
a frame compliance mechanism to the DC scroll
compressor. The mechanism allows movement
in the axial direction of the frame supporting the
cradle scroll, thereby greatly reducing the leakage and friction loss, and ensuring extremely
high efficiency at all speeds.
Power Receiver and Twin LEV Control
(PUHZ-RP71/100/125/140/170/200)
Fixed scroll
Leaking loss : minimum
Thrust gas power: minimum
Thrust friction loss : minimum
Secondary back-pressure
chamber minimises
thrust friction loss.
Frame Cradle scroll
Primary back-pressure
chamber minimises
leaking loss.
Mitsubishi Electric has developed a power receiver and twin linear
expansion valves (LEVs) that optimise the performance of the compressor. By ensuring optimum control in response to the operating
waveform and outdoor temperature, this technology is tailored to the
characteristics of the new refrigerant to enhance operating efficiency.
Full Dot Liquid Crystal Display Adopted
Easier to read thanks to use of a full dot liquid-crystal display with
backlight, and easier to use owing to adopting a menu format that has
reduced the number of operating buttons.
Easy To Read & Easy To Use
Multi-language Display
Display Example [Operation Mode]
NEW
Full Dot LCD
Control panel operation in eight
different languages
MultiIanguage
Choose the desired language,
among the following languages.
PAR-30MAA
[English]
[Spanish]
[Italian]
[German]
[Russian]
[Portuguese]
[Swedish]
[French]
Energy-efficient Control
Operation Control Functions
Energy
Saving
Schedule
Precise control of power
consumption <PUHZ–RP71–200>
The amount of power consumed in each time period is managed so
that the demand value is not exceeded. The demand control function can be set to start and finish in 5-minute units. Additionally, the
level can be adjusted to 0, 50, 60, 70, 80 or 90% of maximum capacity, and up to 4 patterns can be set per day. Air conditioning operation is automatically controlled to ensure that electricity in
excess of the contracted volume is not consumed.
Temperature
Range
Restriction
Using a temperature that is 1°C lower/higher for heating/cooling results in a 10% reduction in power consumption.* Temperature
Range Restriction limits the maximum and minimum temperature
settings, contributing to the prevention of overheating/overcooling.
*In-house calculations
Cooling/Dry
(Setting example of minimum temp. in 25°C)
19(˚C)
 Setting pattern example
Start time
8:15
Finish time
12:00
Capacity savings
80%
12:00
13:00
17:00
13:00
17:00
21:00
50%
90%
50%
Prevents wasteful operation by
automatically returning to the
preset temperature after specified
operating time
After adjusting the temperature for initial heating in winter or cooling on a hot summer day, it is easy to forget to return the temperature setting to its original value. The Auto-return function automatically resets the temperature back to the original setting after a
specified period of time, thereby preventing overheating/overcooling.
The Auto-return activation time can be set in 10-minute units, in a
range between 30 and 120 minutes.
30(˚C)
Possible temperature range setting
25(˚C)
30(˚C)
Lower temperature limit
To prevent excessive cooling
Lower temperatures cannot
be selected
Recommended for
Auto-return
Temperature Range Restriction
prevents overheating/overcooling
Auto-off
Timer
Office
Restaurant
Turns heating/cooling off
automatically after preset time
elapses
When using Auto-off Timer, even if one forgets to turn off the unit,
operation stops automatically after the preset time elapses,
thereby preventing wasteful operation. Auto-off Timer can be set in
10-minute units, in a range between 30 minutes and 4 hours. Eliminates all anxiety about forgetting to turn off the unit.
Recommended for
Meeting room
Changing room
*Auto-return cannot be used when Temperature Range Restrictions is in use.
Night
Setback
Keep desired room temperatures
automatically
This function monitors the room temperature and automatically activates the heating mode when the temperature drops below the
preset minimal temperature setting. It has the same function for
cooling, automatically activating the cooling mode when the temperature rises above the preset maximum temperature setting.
Operation
Lock
Fixed temperature setting promotes
energy savings
In addition to operation start/stop, the operation mode, temperature
setting and airflow direction can be locked. Unwanted adjustment
of temperature settings is prevented and an appropriate temperature is constantly maintained, leading to energy savings. This feature is also useful in preventing erroneous operation or tampering.
Recommended for
Office
Hospital
School
Public hall
Computer server facility
07-08
Control Technologies
Setting Example (restaurant in summer time)
Weekly
Timer
Set up to 8 patterns per day including
temperature control
*Weekly Timer cannot be used when On/Off Timer is in use.
10%
Approximate
Temperature setting (°C)
The Weekly Timer enables the setting of operation start and finish
times and adjusting the temperature as standard features. Up to 8
patterns per day can be set, providing operation that matches the
varying conditions of each period, such as the number of customers in the store.
Preparation
26
Busy
hours
Set to lower temperature
Off-peak Set to higher temperature
hours
7
25
Opening
time
2
24
4
5
3
23
8
Closing time
6
Lunch time
Dinner time
8-pattern setting
22
0
Energy Savings
1
10
12
14
16
18
20
22
Necessary to change temperature settings for cooling/heating times.
*Joint research conducted with Japan Facility Solutions, Inc.
24 (Time)
*Based on in-house calculations
Installation/Maintenance Support Functions
Manual
Vane Angle
Setting
Outdoor unit data accessed
immediately, enabling fast
maintenance <PUHZ–RP71–200>
Smooth
Maintenance
(4-way ceiling
cassette)
Using the Stable Operation Control (fixed frequency) of the Smooth
Maintenance function, the operating status of the inverter can be
checked easily via the screen on the remote controller.
Direction of vertical airflow for
each vane can be set
Setting the vertical airflow direction for each individual vane can be
performed simply via illustrated display. Seasonal settings such as
switching between cooling and heating are easily changed as well.
 Smooth Maintenance Function Operating Procedure
Autodescending
Panel
Operation
Activate Stable
Operation
Select the
maintenance mode
Data is displayed
Easily raise/lower panels using
the remote controller
Auto-descending panel operation is available as an option. Panels
can be lowered/raised using a button on the wired remote controller. Filter cleaning can be performed easily.
Display information (11 items)
Compressor
6
OU TH4 temp. (°C)
1
COMP. current (A)
7
OU TH6 temp. (°C)
2
COMP. run time (Hr)
8
OU TH7 temp. (°C)
3
COMP. ON/OFF (times)
4
COMP. frequency (Hz)
9
IU air temp. (°C)
Outdoor Unit
10
IU HEX temp. (°C)
5
Sub cool (°C)
11
IU filter operating time* (Hr)
Indoor Unit
*IU filter operating time is the time elapsed since filter was reset.
Inspection Guidelines
The computed temperature difference is plotted as in the graph below and
operating status is determined.
Item
( 6 OU TH4 temp.) – ( 7 OU TH6 temp.)
Cooling
Temp. difference
Heating
Cooling
operation
( 9 IU air temp.) – ( 10 IU HEX temp.)
( 6 OU TH4 temp.) – ( 10 IU HEX temp.)
( 10 IU HEX temp.) – ( 9 IU air temp.)
(°C)
45
40
Heating
operation
Inspection C
35
30
9
10
25
20
15
0
35
Inspection C
Filter inspection
30
Filter inspection
Normal
10
25
20
Inspection B
Normal
10
Inspection A
5
0
10 20 30 40 50 60 70 80
(°C)
6
9
15
Inspection B
10
5
(°C)
45
40
7
Inspection A
10 20 30 40 50 60 70 80
(°C)
6
10
Result
Normal
Normal operating status.
Filter inspection
Filter may be
Inspection A
Capacity is reduced. Detailed inspection is necessary.
Inspection B
Refrigerant level is low.
Inspection C
Filter or indoor unit heat exchanger is blocked.
blocked.1
 1: Due to indoor and outdoor temperatures, “Filter inspection” may be displayed even if the filter is not blocked.
 The above graphs are based on trial data. Results may vary depending on installation/temperature conditions.
 Stable operation may not be possible under the following temperature conditions:
a) In cooling mode when the outdoor induction temperature is over 40°C or the indoor induction temperature
is below 23°C.
b) In heating mode when the outdoor induction temperature is over 20°C or when the indoor induction
temperature is over 25°C.
 If the above temperature conditions do not apply and stable operation is not achieved after 30 minutes has
passed, please inspect the units.
 The operating status may change due to frost on the outdoor heat exchanger.
Reassuring Troubleshooting
Navigation Function
Contact Details Displayed When Abnormality Occurs
Easily contact a service company when there is a problem.
The telephone number of a service company and other information can be input and stored in advance. When a problem occurs,
the contact details are displayed automatically, and a call for help
can be made without delay.
Dot Liquid Crystal Display Adopted
The adoption of dot liquid-crystal display (LCD) technology and a
large display screen for the control panel optimises visibility. Operation and control status are easily read at a glance.
Easy to Read/Easy to Use
Display Example [Operation Mode]
Multi-language Display
Dot LCD
PAR-21MAA
Control panel operation in eight
different languages
MultiIanguage
Choose the desired language, among the
following languages.
[English]
[Spanish]
[Italian]
[German]
[French]
[Russian]
[Chinese]
[Japanese]
Energy-efficient Control
Operation Control Functions
Temperature
Range
Restriction
Cooling/Dry
Air conditioner operation restricted
to within a specified operating range
(Setting example of minimum temp. in 25°C)
19(˚C)
30(˚C)
Possible temperature range setting
25(˚C)
30(˚C)
Lower temperature limit
Set the upper and lower limits for the temperature range during
operation. Excessive heating or cooling is prevented, leading to
increased energy savings.
Auto-off
Timer
Automatically turns off
air conditioner
Lower temperatures cannot
be selected
To prevent excessive cooling
Recommended for
Restaurant
Office
The “Simple Timer”— starts/stops in units of 1 hour in a 72-hour
period — is set at the time of shipment from the factory. It can be
changed to the “Auto-off Timer” function using the remote controller.
Recommended for
Meeting room
Changing room
Set the time for the air conditioner to turn off automatically. The
timer can be set in the range from 30 minutes up to 4 hours in
30-minute intervals.
Operation
Lock
Prevent operation settings
from being changed
Only the administrator can change settings when using the Operation Lock mode.
Recommended for
Office
Hospital
Units can be set so that the operation mode cannot be changed.
When “Operation Lock” is activated, new temperature setting
commands are not accepted, thereby ensuring that the unit runs
in the specified (locked in) temperature range. This promotes
energy savings and prevents erroneous/ mischievous operation.
School
Public hall
Computer server facility
09-10
Control Technologies
Introduced in response to
market demand
Weekly
Timer
Setting Example (restaurant in summer time)
Control temperature on a weekly basis
Temperature settings and On/Off control can be managed over
a period of one week using the Weekly Timer. Up to eight setting
patterns per calendar day are possible.
Setting the temperature 1°C higher for
cooling and 1°C lower for heating leads to
an energy savings of approximately 10%.
10%
Temperature setting (°C)
26
Busy
hours
Off-peak
hours
Set to lower temperature
Set to higher temperature
25
6
Opening time
24
3
1
2
23
7
Closing time
5
Lunch time
4
Dinner time
7-pattern setting
22
Approximate
Energy Savings
*Based on in-house calculations
0
10
12
14
16
18
20
22
24 (Time)
(Results of cooperative study with Japan Facility Solutions, Inc.)
Rotation, Back-up and 2nd Stage Cut-in Functions (PAR-30MAA and PAR-21MAA)
(1) Rotation and Back-up Functions
Function Outline
• Main and sub units take turns operating according to
a rotation interval setting.
• If one unit malfunctions, the other unit automatically
begins operation (Back-up function)
Operation Pattern
[Back-up function only]
System Image
Main
unit
O/U-1
O/U-2
I/U-1
I/U-2
Sub
unit
Error occurs on main unit.
Main Sub
Start operation
Main
unit
I/U-1
Run
Abnormal condition
Sub
unit
I/U-2
Stop
Run
[Rotation function] & [Back-up function]
Start operation
O/U : Outdoor unit
I/U : Indoor unit
R/C : Wired remote controller
R/C
(2) 2nd Stage Cut-in Function
Function Outline
• Number of units operating is based on room temperature and predetermined settings.
• When room temperature rises above the desired
setting, the standby unit starts (2-unit operation).
• When the room temperature falls 4°C below the predetermined setting, the standby unit stops (1-unit
operation).
System Constraint
• This function is only available for rotation operation
and when the back-up function is in cooling mode.
Main
unit
I/U-1
Run
Sub
unit
I/U-2
Stop
Main
Sub
Sub
Stop
Run
Run
1–28 days
Main
Stop
Error occurs on main unit.
Main Sub
Abnormal condition
Run
1–28 days
(Ex: When the request code is “313”, each unit operates alternately in daily cycle.)
Operation Pattern
[2nd stage cut-in function]
Start operation
Main
unit
I/U-1
Run
Sub
unit
I/U-2
Stop
Room temp. >
= Set point
Sub unit starts operation
Run
Room temp. >
= Set point –4°C
Sub unit stops
Stop
Easy Maintenance Function (Mr. Slim Power Inverter only)
• Nearly maintenance-free operation
• Monitor operation data of the indoor and outdoor
units via the remote controller.
Remote controller also lets you set the operating
frequency, allowing easier inspection.
Easy Maintenance Information
Compressor
Outdoor Unit
Indoor Unit
4
Heat exchanger
temperature (˚C)
7
Intake-air
temperature (˚C)
Number of ON/OFF
times (×100 times)
5
Discharge
temperature (˚C)
8
Heat exchanger
temperature (˚C)
Operating current (A)
6
Outdoor-air
temperature (˚C)
9
Filter operating
time* (hr)
1
Accumulated
operating time (×10hr)
2
3
*The filter operating time is the time elapsed since the filter button was reset.
Refrigerant Leakage Check (Mr. Slim Power Inverter only)
The Mr. Slim Power Inverter units come equipped
with a useful new “Refrigerant Leakage Check”
function. Using a wired remote controller, it is easy
to check if refrigerant has been lost over a long
period of use. This reduces service time and gives
an added sense of safety.
Product Line-up
4-way ceiling cassette
SLZ
Compact cassette
2.5kW
3.5kW
5.0kW
SLZ-KA25VAQ (L)
SLZ-KA35VAQ (L)
SLZ-KA50VAQ (L)
PLA
Wide Power cassette
Compact bulkhead
Ceiling concealed
Ceiling suspended
6.0kW
PLA-RP60BA
SEZ
SEZ-KD35VAQ
SEZ-KD50VAQ
SEZ-KD60VAQ
PCA-RP50KAQ
PCA-RP60KAQ
SUZ-KA50VA2
SUZ-KA60VA2
PEA
PCA
Wall mounted
PKA
Outdoor unit
SUZ-KA25VA2
*SEZ/SLZ indoor units should be connected to an SUZ outdoor unit.
*PKA-RP71 and PCA-RP71HA: only for PUHZ-RP outdoor connection.
SUZ-KA35VA2
Product Line-up of
7.1kW
10.0kW
12.5kW
14.0kW
Inverter Units
17.0kW
20.0kW
25.0kW
11-12
Remote
controller
See
page
NEW
(Optional)
19
(Optional)
(SLZ-VAL)
NEW
(Optional)
13
(Optional)
PLA-RP71BA
PLA-RP100BA
PLA-RP125BA
14
PLA-RP140BA
(Optional)
NEW
(Optional)
19
SEZ-KD71VAQ
(Optional)
NEW
(Optional)
15
PEA-RP71EAQ
PEA-RP100EAQ
PEA-RP125EAQ
PEA-RP140EAQ
PEA-RP170WHA
PEA-RP200WHA
PEA-RP250WHA
(Optional)
Not available in New Zealand
Combination only
with PUHZ-RP71
NEW
(Optional)
PCA-RP71HAQ
16
PCA-RP125HAQ
(Optional)
PCA-RP100KAQ
PCA-RP71KAQ
NEW
17
PCA-RP140KAQ
PCA-RP125KAQ
(Optional)
NEW
NEW
Combination only
with PUHZ-RP71
(Optional)
18
(Optional)
PKA-RP71KAL
PKA-RP100KAL
(Standard)
NEW
NEW
NEW
PUHZ-RP100VKA
PUHZ-RP125VKA
PUHZ-RP140VKA
SUZ-KA71VA2
NEW
PUHZ-RP71VHA4
PUHZ-RP170VKA
PUHZ-RP200YKA
PUHZ-RP250YHM-A
Not available in New Zealand
13
4-way Ceiling Cassette
PLA
SERIES
Advancements in PLA Series improve
style and performance for ensured
indoor comfort
Conventional model
Wide Airflow
Wide-angle outlets distribute airflow to all corners of the room, ensuring the room is sufficiently cooled/heated. Horizontal airflow and a
fan speed reduced by 20% compared to conventional models also contribute to increased
comfort for occupants.
PLA-RP   BA
Less Cold Draft
The “Horizontal Airflow” function prevents cold drafts from striking the body
directly, thereby keeping the body from
becoming over-chilled.
Horizontal Airflow
prevents drafty feeling
Independent Vane Direction
Setting
(i-see Sensor: optional)
PLA-RP60/71
100/125/140BA
Using wired remote controller,
set airflow direction for each vane
(manual setting also possible)
Horizontal
flow
Use the wired remote controller to set
the airflow pattern of each vane independently. Easily adjust airflow to the interior layout and seasonal conditions,
and ensure an even temperature distribution all the time.
Fixed
Set by remote Vertical
flow
controller
Settings can be changed anytime
using a wired remote controller.
(Optional)
Wave Airflow Mode for Heating
The airflow direction at
each outlet changes intermittently, providing a consistent temperature throughout the room.
 “Wave Airflow” operation image
Vertical
Vertical Vertical Vertical
flow
flow
flow
flow
Simultaneous horizontal and vertical operation ensure
a comfortable room from corner to corner
 Wave control effect thermograph
Vertical flow
Swing mode
Temperature gap with uneven
temperature distribution
Temperature gap is minimised,
and room is warmed uniformly
Specifications: 4-way ceiling cassette (PLA)
Indoor unit
PLA-RP60BA
PLA-RP71BA
Outdoor unit
SUZ-KA60VA2
SUZ-KA71VA2
Function
Capacity (min.-max.)
(kW)
Input
(kW)
Cooling
Heating
Cooling
Heating
6.1 (1.1-6.3)
6.9 (0.9-8.0)
7.1 (0.9-8.1)
8.0 (0.9-10.2)
1.87
1.97
2.07
2.19
Rated EER/COP
3.26
3.50
3.43
3.65
Rated AEER/ACOP
3.21
3.45
3.38
PLA-RP60BA
Indoor unit
3.60
PLA-RP71BA
Power supply
Airflow (Lo-Mi2-Mid-Hi)
Sound pressure level
Dimensions
Weight
CMM
12-14-16-18
14-16-18-21
L/S
200-233-267-300
233-267-300-350
(dB)
28-29-31-32
28-30-32-34
Unit: 258, Panel: 35
Height
(mm)
Width
(mm)
Unit: 840, Panel: 950
Depth
(mm)
Unit: 840, Panel: 950
(kg)
Unit: 23, Panel: 6
14
4-way Ceiling Cassette
Auto Fan Speed Mode
The fan speed is adjusted automatically, thereby maintaining a comfortable room environment at all times. At the start of operation, a high
fan speed realises quick heating/cooling of the room. Once the
desired temperature is reached, the fan speed is reduced for stable
heating/cooling and greater comfort.
Mi1
Mi2
Hi
360°
Floor-level temperature
measured throughout the room.
i-see Sensor works to
ensure even temperature
distribution and save
energy (requires optional
corner panel)
Fan speed setting by remote controller (four levels)
Lo
4-way cassettes can be equipped with the i-see Sensor,
a radiation-based sensor that monitors floor-level
temperatures throughout the room to
ensure room comfort.
Auto
Special setting is required for wireless remote controller.
Quiet Operation
An improved airflow path and powerful highcapacity flow fan contribute to the realisation of
quieter operation.
Power flow fan
“Pure White” Colour
i-see Sensor improves energy efficiency and enhances room comfort
The i-see Sensor is an innovative Mitsubishi Electric technology that uses a
radiation-based sensor to monitor temperature throughout the entire room.
When connected to the air conditioner control panel, i-see Sensor works to
maximise room comfort through 360° sensing that covers the whole floor space.

Stylish, pure white-coloured panels and wired remote controller
express a clean, streamlined image that is a suitable match for any
interior.
i-see Sensor Operation
The i-see Sensor rotates 90° and takes 5-second
measurements to accurately determine floor-level
temperatures on all sides of the room.
Other Features
90°
rotation
• Stylish indoor-unit vane covers (when unit is turned off)
• Maximum upward draining of 850mm
• Wireless remote controller available
• Duct flange for Fresh-air Intake
• Branch duct
5 sec
measurement
Automatic
elevation to
four metres
Automatic Grille Lowering
Function (Option)
1.2m
1.6m
Easy to use/Simple maintenance
An automatic grille lowering
function capable of stopping
at eight different heights is
available to simplify filter mainElevating (up-down)
controller
tenance.
5 sec
measurement
90°
rotation
5 sec
measurement
5 sec
measurement
 The i-see Sensor calculates the temperature by measuring the infrared rays emanating
from the walls and floors, and measuring the floor-level temperature.
 The sensor rotates 360-degrees once every two minutes when there is significant temperature disparity and once every five minutes when a stable, even temperature has been
reached.
“I Feel” Temperature Control
The sensory temperature is calculated by measuring the air-intake temperature
and the floor temperature. This technology makes it possible to avoid overcooling or overheating.
2.0m
2.4m
Without i-see Sensor
Only intake-air temperature at the
ceiling is measured, resulting in
uneven temperature distribution.
2.8m
With i-see Sensor
Both floor-level and intake-air temperatures are measured, providing operation that creates a comfortable
room environment from ceiling to floor.
Indoor temperature
Indoor temperature
detecting
sensor
detecting sensor
3.2m
Indoor temperature
Indoor temperature
detecting
sensor
detecting sensor
3.6m
Wired remote
controller
(optional for Auto
Elevating Panel)

A receiver on the elevated
panel detects commands from
the wireless remote controller.
90°
rotation
360°
sensing
Area which the
sensor checks
4.0m
Area
Areawhich
whichthe
the
“i-see
i-see Sensor”
Sensor
checks
checks
2.7m
PLA-RP71BA
PLA-RP100BA
PLA-RP125BA
PLA-RP140BA
PUHZ-RP71VHA4
PUHZ-RP100VKA
PUHZ-RP125VKA
PUHZ-RP140VKA
Cooling
Heating
7.1 (3.3-8.1)
8.0 (3.5-10.2)
Cooling
Heating
Cooling
Heating
Cooling
2.09
2.17
2.50
2.95
3.80
3.71
4.55
4.43
3.40
3.69
4.00
3.80
3.29
3.77
3.08
3.61
3.22
3.51
3.67
3.54
3.10
3.57
2.93
3.41
PLA-RP71BA
11.5m
Heating
10.0 (4.9-11.4) 11.2 (4.5-14.0) 12.5 (5.5-14.0) 14.0 (5.0-16.0) 14.0 (6.2-15.3) 16.0 (5.7-18.0)
PLA-RP100BA
PLA-RP125BA
PLA-RP140BA
Single-phase, 50Hz, 230V
14-16-18-21
20-23-26-30
22-25-28-31
24-26-29-32
233-267-300-350
334-384-434-501
367-417-467-517
400-434-484-534
28-30-32-34
32-34-37-40
34-36-39-41
36-39-42-44
Unit: 298, Panel: 35
Unit: 840, Panel: 950
Unit: 840, Panel: 950
Unit: 25, Panel: 6
Unit: 27, Panel: 6
Heating
Heating
Set temperature: 23°C
without i-see Sensor
Set temperature: 20°C
with i-see Sensor + Auto Fan Speed
37°C
37°C
25°C
25°C
13°C
13°C
15
Ceiling-concealed
PEA
SERIES
For elegance and style, the PEA Series
compliments the room environment with
aesthetically pleasing ceiling installation
and a vast line-up of performance
functions.
Freedom in Installation
Versatile and easy installation is possible; for example, it is possible to adjust the distance between the air-intake and air-outlet
vents to create the optimal airflow configuration.
 Long rectangular room
 Room with fixed ceiling
fixtures
 L-shaped room
Flexible Duct Design Enables Use
of High-pressure Static Fan
PEA-RP71/100EAQ
A flexible duct design and 150Pa external static high-pressure are
incorporated. The increased variation in airflow options ensures
operation that best
matches virtually all
room layouts.
PEA-RP125/140EAQ
PEA-RP170/
200/250WHA
Easier Handling
The new ducted fan coil unit
(PEA-RP170/200/250WHA)
now has a two-piece construction. This allows separation of the indoor unit heat
exchanger and the fan deck
assembly for easier handling
into the roof space.
(Optional)
Must be reassembled and installed
prior to using the system.
Computerised Dehumidification
The fan speed is controlled electronically in dehumidifying mode,
increasing the range and efficiency of dehumidification.
Specifications: Ceiling-concealed (PEA)
Indoor unit
Outdoor unit
Function
PEA-RP71EAQ
PEA-RP100EAQ
PEA-RP125EAQ
PEA-RP140EAQ
PEA-RP170WHA 4
PEA-RP200WHA 4
PEA-RP250WHA 4
PUHZ-RP71VHA4
PUHZ-RP100VKA
PUHZ-RP125VKA
PUHZ-RP140VKA
PUHZ-RP170VKA
PUHZ-RP200YKA
PUHZ-RP250YHM-A
Cooling
Capacity (min.-max.)
(kW)
Input
(kW)
Heating
7.1 (3.3-8.1)
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
8.4 (3.5-10.2) 10.0 (4.9-11.4) 11.2 (4.5-14.0) 12.5 (5.5-14.0) 14.0 (5.0-16.0) 14.0 (6.2-15.3) 16.0 (5.7-18.0) 17.0 (9.0-20.0) 20.0 (9.5-22.4) 18.9 (9.0-22.4) 22.4 (9.5-25.0) 22.0 (11.2-27.0) 25.0 (12.5-29.0)
2.48
2.51
3.05
3.16
4.24
3.85
4.83
4.28
5.48
6.00
5.92
6.89
7.21
Rated EER/COP 1
2.86
3.35
3.28
3.54
2.95
3.64
2.90
3.74
3.10
3.33
3.19
3.25
3.05
3.10
Rated AEER/ACOP
2.75
3.20
3.05
3.32
2.80
3.45
2.77
3.56
2.93
3.17
2.90
2.99
3.01
3.07
3.16 (98)
AEER/ACOP (part-load %) 2
PEA-RP71EAQ
Indoor unit
PEA-RP100EAQ
Power supply
PEA-RP170WHA
PEA-RP200WHA
PEA-RP250WHA
Three-phase, 50Hz, 400V)
22-27 (Lo-Hi)
27-34 (Lo-Hi)
48-60 (Lo-Hi)
50-61-72 (Lo-Mid-Hi)
58-71-84 (Lo-Mid-Hi)
L/S
367-450 (Lo-Hi)
450-567 (Lo-Hi)
800-1000 (Lo-Hi)
833-1017-1200 (Lo-Mid-Hi)
967-1183-1400 (Lo-Mid-Hi)
52-55
54-58
51-55
38-41-44
External static pressure Pa
Weight
PEA-RP140EAQ
CMM
Sound pressure level 3 (dB)
Dimensions
PEA-RP125EAQ
Single-phase, 50Hz, 230V
Airflow
8.06
Height
(mm)
Width
(mm)
Depth
(mm)
(kg)
125
60-75-100-150
785
1,415
1,055
1,370
690
46
59
40-43-46
470
428
1,120
76
108
1
2
3
4
Rated EER/COP for PEA-RP170/200/250WHA are measured at ESP 75 Pa.
MEPS compliant at part load
Sound pressure level for PEA-RP170/200/250WHA are measured in anechoic chamber at ESP 150 Pa.
PEA-RP170/200/250WHA come equipped with a wired remote controller PAR-21MAA.
16
Ceiling-suspended for
Professional Kitchen
PCA
SERIES
High performance, easy-to-maintain
stainless steel units perfect for use in
kitchens and modern shops
Tough on Oily Smoke
A durable stainless steel casing that is resistant to oil and grease is
provided to protect the surface of the body. Grimy dirt and stains
are removed easily, enabling the unit to be kept clean at all times.
High Performance Oil Mist Filter
A high performance heavy duty oil mist filter is included as standard equipment. The filtering system is 1.5-times more efficient
than conventional filters, thereby effectively reducing the oily
smoke entering the air
conditioner. The filter is
disposable to further simplify trouble free cleaning
and maintenance.
 Oil mist filter
 Pull the handle to easily
slide the filter out
Easy Maintenance – Even for Cleaning the Fan
A separate fan casing that can be disassembled in sections is adopted to ensure
easy fan cleaning. Drain pan cleaning onsite
is also easy owing to the use of a pipe connector that can be quickly removed.
Bring in Outside Air for
Fresher Air Conditioning (Option)
The rear panel has a knock-out opening that can be used to bring
fresh air into the unit. This helps to improve ventilation in the
kitchen for more comfort.
Cosmetic Front and
Hanging Fixture Covers (Option)
PCA-RP71/125HAQ
(Optional)
Cosmetic covers are available to
prevent the collection of dust and
grime on the main body and hanging fixture sections.
Front cover
Hanging fixture
cover
Fresh Outside Air Intake
There is a knock-out opening on the
rear panel of the unit that can be
used to bring fresh air into the unit.
This helps to improve ventilation
and make the kitchen comfortable.
Knock-out opening
Fresh air knock-out opening (ø200),
RP71 pattern: 2 places; RP125 pattern: 3 places.
Flexible Duct (Procured locally)
Duct Flange
(ø200, Optional PAC-SF28OF-E)
Notes:
1) A fresh-air duct flange is required (sold separately)
2) All fresh Outdoor-air Intake option is not available.
Fresh Air Knock-out Opening (ø200)
Specifications: Ceiling-suspended (PC)
Indoor unit
Outdoor unit
Function
Capacity (min.-max.)
(kW)
Input
(kW)
PCA-RP71HAQ
PCA-RP125HAQ
PUHZ-RP71VHA4
PUHZ-RP125VKA
Cooling
Heating
Cooling
Heating
7.1 (3.3-8.1)
7.6 (3.5-10.2)
12.5 (5.5-14.0)
13.8 (5.0-16.0)
4.05
2.21
2.23
3.88
Rated EER/COP
3.21
3.41
3.22
3.41
Rated AEER/ACOP
3.02
3.25
3.01
3.24
PCA-RP125HAQ
PCA-RP71HAQ
Indoor unit
Single-phase, 50Hz, 230V
Power supply
CMM
17-19
30-38
L/S
283-317
500-633
Sound pressure level
(dB)
34-38
Height
(mm)
Width
(mm)
Depth
(mm)
Airflow (Lo-Hi)
Dimensions
Weight
(kg)
44-50
280
1,520
1,136
650
41
56
17
Ceiling-suspended
PCA
SERIES
A stylish indoor unit design and airflow
settings for both high- and low-ceiling
interiors expand installation possibilities
Stylish Indoor Unit Design
PCA-GA
A stylish square-like design is adopted for
the indoor units of all models. As a result,
the units blend in better with the ceiling.
PCA-K A
Optional Drain Pump for
Full-capacity Models
Drain pump installation
possible
Drainage outlet can
be 600mm above
ceiling surface
The pumping height of the optional drain
pump has been increased from 400mm
to 600mm, expanding flexibility in choosing unit location during installation work.
Ceiling
surface
Equipped with Automatic Air-speed Adjustment
In addition to the conventional 4-speed setting, units are now
equipped with an automatic air-speed adjustment mode. This setting automatically adjusts the air-speed to conditions that match
the room environment. At the start of heating/cooling operation,
the airflow is set to high-speed to quickly heat/cool the room.
When the room temperature reaches the desired setting, the
airflow speed is decreased automaticalStrong
Gentle
ly for stable comfortable heating/cooling
Start of
After room
cooling/heating…
temperature is stabilised…
operation.
Units are equipped with a knockout hole that enables the induction of fresh outside-air.
(Optional)
 Outside-air intake characteristics
Static pressure (Pa)
Fresh Outside-air Intake
PCA-RP50/60/71/100/125/140KAQ
50
0
–50
–100
–150
–200
–250
–300
PCA-RP100–140KA
PCA-RP60/71KA
PCA-RP50KA
0
1
2
3
4
Airflow volume (m 3/min)
Equipped with High /Low-ceiling Modes
Units are equipped with high and
low-ceiling operation modes that
make it possible to switch the airflow volume to match room
height. The ability to choose the
optimum airflow volume makes it
possible to optimise the breezy
sensation felt throughout the room.
Capacity
High Standard Low
ceiling
ceiling
ceiling
50
3.5m
2.7m
2.5m
60
3.5m
2.7m
2.5m
71
3.5m
2.7m
2.5m
100
4.2m
3.0m
2.6m
125
4.2m
3.0m
2.6m
140
4.2m
3.0m
2.6m
Specifications: Ceiling-suspended (PCA)
Indoor unit
PCA-RP50KAQ
PCA-RP60KAQ
PCA-RP71KAQ
PCA-RP71KAQ
PCA-RP100KAQ
PCA-RP125KAQ
PCA-RP140KAQ
Outdoor unit
SUZ-KA50VA2
SUZ-KA60VA2
SUZ-KA71VA2
PUHZ-RP71VHA4
PUHZ-RP100VKA
PUHZ-RP125VKA
PUHZ-RP140VKA
Cooling
Function
Heating
Cooling
Heating
Cooling
Heating
Capacity (min.-max.)
(kW) 5.0 (1.1-5.6) 5.5 (0.9-6.6) 5.7 (1.1-6.3) 6.9 (0.9-8.0) 7.1 (0.9-8.1) 7.9 (0.9-10.2)
Input
(kW)
Cooling
Heating
7.1 (3.3-8.1)
Cooling
Heating
Cooling
Heating
Cooling
Heating
8.0 (3.5-10.2) 10.0 (4.9-11.4) 11.2 (4.5-14.0) 12.5 (5.5-14.0) 14.0 (5.0-16.0) 14.0 (6.2-15.3) 16.0 (5.7-18.0)
1.66
1.71
1.77
2.02
2.06
1.96
1.96
2.21
2.63
3.02
3.88
3.88
4.36
4.43
Rated EER/COP
3.01
3.22
3.22
3.42
3.45
4.03
3.62
3.62
3.80
3.71
3.22
3.61
3.21
3.61
Rated AEER/ACOP
2.96
3.17
3.17
3.36
3.40
3.97
3.42
3.45
3.50
3.46
3.04
3.42
2.99
3.41
PCA-RP71KAQ
PCA-RP100KAQ
PCA-RP125KAQ
PCA-RP140KAQ
PCA-RP50KAQ
PCA-RP60KAQ
CMM
10-11-13-15
15-16-17-19
16-17-18-20
22-24-26-28
23-25-27-29
24-26-29-32
L/S
167-183-217-250
250-267-283-317
267-283-300-333
367-400-433-467
383-417-450-483
400-433-483-533
Sound pressure level
(dB)
32-34-37-40
33-35-37-40
35-37-39-41
37-39-41-43
39-41-43-45
41-43-45-48
Height
(mm)
Width
(mm)
Depth
(mm)
Indoor unit
Single-phase, 50Hz, 230V
Power supply
Airflow (Lo-Mi2-Mid-Hi)
Dimensions
Weight
PCA-RP71KAQ
(kg)
230
960
1,280
1,600
680
25
32
36
38
39
18
Wall-mounted
PKA
SERIES
Elegant design and compact dimensions
are ideal for offices, stores and
residential-use
Auto-flap Shutter Enhances Good Looks
The Intake Grille Filter Can be Completely
Removed Allowing Easy Cleaning
(Can be washed in water)
Filter slides out
Front grille
Filter
NEW
4-way Piping Provides More Flexibility
in Selecting Installation Sites
Wired Remote Controller Available
(Option)
A separately sold wired remote controller and a terminal block
are available to suit various installation sites.
PKA-RP71/100KAL
Drain Pump Option Available with
All Models
(Optional)
(Standard)
Installation of the drain pump enables a drain outlet as high as
800mm above the base of the indoor unit. Drain water can be
discharged easily even if the surface where the wall-mounted
unit does not have direct access outside, increasing the degree
of freedom for installation.
Drain pump
Indoor unit
800mm
Specifications: Wall-mounted (PKA)
Indoor unit
Outdoor unit
Function
Capacity (min.-max.)
(kW)
Input
(kW)
PKA-RP71KAL
PKA-RP100KAL
PUHZ-RP71VHA4
PUHZ-RP100VKA
Cooling
Heating
Cooling
Heating
7.1 (3.3-8.1)
8.0 (3.5-10.2)
10.0 (4.9-11.4)
11.2 (4.5-14.0)
1.96
2.13
2.90
3.10
Rated EER/COP
3.62
3.76
3.45
3.61
Rated AEER/ACOP
3.42
3.57
3.20
3.31
Indoor unit
PKA-RP71KAL
PKA-RP100KAL
Single-phase, 50Hz, 230V
Power supply
CMM
18-20-22
20-23-26
L/S
300-333-367
333-283-433
Sound pressure level
(dB)
39-42-45
Height
(mm)
365
Width
(mm)
1,170
Depth
(mm)
295
(kg)
21
Airflow (Lo-Mid-Hi)
Dimensions
Weight
41-45-49
19
Compact 4-way Cassette
Compact Bulkhead
SLZ
SEZ
SERIES
SLZ-KA25/35/50VAQ (L)
Compact, ultra-quiet concealed indoor
units equipped with cutting-edge control
technologies for enhanced comfort
Compact Designs
Models with capacity ranges for any room size. The dimensions of
the SLZ are perfect for 2-metre-square installations, and the SEZ
unit is a slim 200mm in height, making it ideal for tight installation
spaces.
990mm
700mm
208mm
200mm
650mm
650mm
SLZ-KA25/35/50
SEZ-KD35/50
Impressively Quiet
S Series units offer whisper quiet operation at a hushed noise
level of 23dB (SEZ-KD35), ensuring a calm and comfortable
environment. They’re so quiet that you’ll find yourself checking to
see if they’re on.
 Noise level
Subway car
interior
Quiet passenger
car interior
(40km/h)
Library interior
80dB
60dB
40dB
Human
Sound of
hearing limits
rustling leaves (Extremely quiet)
10dB
23dB
Quiet!
(Optional)
Energy Saving Operation
(Optional)
SEZ-KD35/50/
60/71VAQ
Boasting low electricity consumption, SLZ/SEZ Series air conditioners are the key to fresh, cost-effective room comfort.
Air Cleaning Filter
This built-in filter removes dust and other particulates, keeping
the air clean all the time. Maintenance is as simple as vacuuming.
The long-life filter in SLZ Series air conditioners can be used for
approximately 2,500 hours before requiring replacement.
Fresh Air Intake
Fresh-air intake
Detail drawing of fresh-air intake
25
100
A duct hole is provided in
the main body, making it
possible to intake fresh air
from outside.
73.4
Cut-out hole
0°
120
118
3- 2.8 hole
Burring hole
°
Drain pipe
Electrical box
Refrigerant pipe
Ceiling surface
12
(For SLZ)
Specifications: Compact 4-way cassette/Compact bulkhead (SLZ, SEZ)
Indoor unit
Outdoor unit
SLZ-KA25VAQ (L)
SLZ-KA35VAQ (L)
SLZ-KA50VAQ (L)
SEZ-KD35VAQ
SEZ-KD50VAQ
SEZ-KD60VAQ
SUZ-KA25VA2
SUZ-KA35VA2
SUZ-KA50VA2
SUZ-KA35VA2
SUZ-KA50VA2
SUZ-KA60VA2
Cooling
Function
Heating
Cooling
Heating
Cooling
Heating
Capacity (min.-max.)
(kW) 2.5 (0.9-3.2) 3.2 (0.9-4.5) 3.5 (1.0-3.9) 4.0 (0.9-5.0) 4.6 (1.1-5.2) 5.0 (0.9-6.5)
Input
(kW)
Cooling
Heating
Cooling
Heating
Cooling
SEZ-KD71VAQ
SUZ-KA71VA2
Heating
Cooling
Heating
3.7 (1.0-3.9) 4.2 (0.9-5.0) 5.1 (1.1-5.6) 6.4 (1.1-7.2) 5.6 (1.1-6.3) 7.4 (0.9-8.0) 7.1 (0.9-8.3) 8.1 (0.9-10.4)
0.68
0.85
1.04
1.09
1.53
1.55
1.09
1.13
1.64
1.81
1.86
2.11
2.36
2.18
Rated EER/COP
3.68
3.76
3.37
3.67
3.01
3.22
3.39
3.72
3.11
3.54
3.01
3.51
3.01
3.72
Rated AEER/ACOP
3.53
3.65
3.28
3.58
2.95
3.17
3.31
3.63
3.06
3.48
2.96
3.46
2.97
3.66
4.10 (53)
AEER/ACOP (part-load %) 
SLZ-KA25VAQ (L)
Indoor unit
SLZ-KA35VAQ (L)
SLZ-KA50VAQ (L)
SEZ-KD35VAQ
SEZ-KD50VAQ
SEZ-KD60VAQ
SEZ-KD71VAQ
Single-phase, 50Hz, 230V
Power supply
Airflow (Lo-Mid-Hi)
CMM
8-9-10
8-9-11
7-9-11
10-12.5-15
12-15-18
12-16-20
L/S
133-150-167
133-150-183
117-150-183
167-208-250
200-250-300
200-267-333
23-28-33
30-34-37
5-15-35-50
—
External static pressure Pa
Sound pressure level
(dB)
Height
(mm)
Unit: 208, Panel: 20
200
200
Width
(mm)
Unit: 570, Panel: 650
990
1,190
Depth
(mm)
Unit: 570, Panel: 650
700
(kg)
Unit: 16.5, Panel: 3
Dimensions
Weight
28-31-37
29-33-38
30-34-39
21
30-34-38
30-35-40
700
23
27
* The SLZ-KA VAL comes equipped with a wireless remote controller.
* The SLZ-KA VAQ and SEZ-KD VAQ do not include neither wired nor wireless remote controller.
MEPS compliant at part load
20
Main Features
Main features of Mr. Slim Inverter Units
Indoor unit
SLZ-VAQ SLZ-VAL SEZ-VAQ
Outdoor unit
Energy Saving
SUZ
SUZ
SUZ
Felt Temperature Control
(i-see Sensor)
PEA
PKA
PUHZ-HA
PUHZ-HM
PUHZ-KA
PUHZ
PLA
Combination
PUHZ
SUZ
Opt
Opt
Opt
Opt
PCA-KAQ
PCA-HAQ
PUHZ
SUZ
PUHZ
Opt
Opt
Opt
Opt
Opt
Opt
Pure White
Attractive
Auto Vane
Fresh Air Intake
High Efficiency Filter
Air Quality
Oil Mist Filter
Long Life filter
Filter Check Signal
Opt
Horizontal Fin (Auto Swing)
Air Distribution
High Ceiling Mode
Auto Fan Speed Mode
On/Off Operation Timer
Auto Change Over *1
*3
Auto Restart
Convenience
Low Temperature Cooling
Low Noise Operation (Outdoor Unit)
Rotation, Back-up and 2nd Stage
Cut-in Function
System Control
Opt
PAR-21MAA Control *2
Opt
Opt
Opt
Opt
Opt
Opt
PAR-30MAA Control *2
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Centralised On/Off Control *2
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
System Group Control *2
Opt
Opt
Opt
M-NET Connection *2
Opt
Opt
Opt
Reuse of Existing Wiring
Drain Pump
*4
Opt
Opt
Opt
*6
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Opt
Installation
Pump Down Switch
Flare Connection
*5
Self-Diagnosis Function
(Check Code Display)
Maintenance
Failure Recall Function
*1 When multiple indoor units connected to an MXZ outdoor unit are running at the same time,
simultaneous cooling and heating is not possible.
*2 Please refer “System Control” on page 21 for details.
*3 Indoor unit DIP SW1-9 must be “ON”.
*4 Only available between PUHZ-HM models.
*5 Not available with PEA-RP170/200WHA models.
*6 PEA-RP170/200/250WHA come equipped with a wired remote controller PAR-21MAA.
21
System Controls
System Controls ( SUZ and Mr. Slim Power Inverter only )
Versatile system controls can be realised by using optional parts, relay circuits, control panels, etc.
System examples
Wired remote controller Wireless remote controller
A
Single-remote controller
control
Details
Major optional parts required
• Either wired or wireless remote
controller can be used
Standard system
None
PAR-30MAA
PAR-21MAA
(Example of 1 : 1 system)
B
Dual Remote Controllers
Two remote controllers, one each
for local and remote control of the
system
PAR-30MAA/PAR-21MAA
* Set “Main” and “Sub”
remote controllers.
(Example of 1 : 1 system)
C
Group control
MAC-397IF-E*
One remote controller can control
multiple air conditioners simultaneously using the same setting.
* The setting of the refrigerant
address is required for outdoor unit.
D
PAR-30MAA
PAR-21MAA
(Example of 1 : 1 system×2)
Operation Control by
level signal (12VDC)
Turn on/off unit from a remote
location, prohibit/permit
operation using a local remote
controller
Relay box (to be purchased locally)
Remote
control
panel
Operation control by
pulse signal
Relay box (to be purchased locally)
Connector
cable for
remote
display
Connector
cable for
remote
display
Remote
control
panel
Wired remote
controller
(Example of 1 : 1 system×2)
Remote display of
operating status
PAR-SL97A-E
(Example of 1 : 1 system×2)
Relay box (to be purchased locally)
Remote
control
panel
F
Adapter for
remote
On/Off
Remote
control
panel
Wired remote
controller
(Example of 1 : 1 system×2)
E
Relay box (to be purchased locally)
Adapter for
remote
On/Off
• Wired remote controller
PAR-30MAA/PAR-21MAA
• Terminal block for wired remote
controller for PKA
PAC-SH29TC-E
• Wireless remote controller
PAR-SL97A-E
• Wireless remote controller kit for PCA
PAR-SL99B-E
• One remote controller can control
up to 16 refrigerant systems
• Outdoor unit can be started/
stopped (thermostat On/Off)
individually.
• Up to two remote controllers can
be connected
• MAC-397 IF-E is required for each
indoor unit if the outdoor unit is SUZ
or MXZ (if the outdoor unit is P Series,
no optional parts are required)
• Operation other than On/Off
(adjustment of temperature, fan
speed, and air direction, for
example) can be performed even
when remote controller operation
is prohibited
• Timer control is possible with
an external timer
• Adapter for remote On/Off
PAC-SE55RA-E
• Relay box
(to be purchased locally)
• Remote control panel
(to be purchased locally)
• The pulse signal can be turned
On/Off.
• Operation/Fault signal can be
received at a remote location
(12VDC signal)
• Connector cable for remote display
PAC-SA88HA-E/PAC-725AD
(10 pcs. × PAC-SA88HA-E)
• Relay box
(to be purchased locally)
• Remote control panel
(to be purchased locally)
• Operation/Fault signal can be
received at a remote location
(when channeled through the
PAC-SF40RM no-voltage signal,
when channeled through the
PAC-SA88HA-E 12VDC signal)
• Remote display panel
(to be purchased locally)
• Connector cable for remote display
PAC-SA88HA-E/PAC-725AD
(10 pcs. × PAC-SA88HA-E)
• Relay box (to be purchased locally)
• Remote operation adapter
PAC-SF40RM
PAR-SL97A-E
(Example of 1 : 1 system×2)
Remote operation adapter/
Connector cable for remote display +
relay box
Operating status can be
displayed at a remote location.
Remote
display
panel
• Up to two remote controllers can
be connected to one group
• PAR-30MAA can be used as only
main remote controller
• Both wired and wireless remote
controllers can be used in
combination
* Cannot be used with wireless remote controller
PAR-30MAA
PAR-21MAA
• Remote display panel
(to be purchased locally)
(Example of 1 : 1 system)
G
• Weekly Timer:
Standard functions of
On/Off and up to eight pattern
PAR-30MAA/PAR-21MAA
temperatures can be set for each
calendar day (initial setting)
• Simple Timer:
Unit can be set to turn on/off one
time each in a 72hr period; setting
intervals of 1hr
• Auto-off Timer:
Unit turns on/off after a specified
time elapses. Can be set in the range
from 30min to 4hr at intervals of 30min.
Timer Operation
On/Off timer enabled
* For the control by external timer,
refer to D operation control by
level signal.
PAR-30MAA
PAR-21MAA
(Example of 1 : 1 system)
*Simple Timer and Auto-off Timer cannot be
used at the same time.
*See page 7-8 for the function of PAR-30MAA
H
Centralised control
(for Power Inverter only)
Centralised control of
dispersed air conditioning
equipment allows effective
monitoring/controlling.
• Mounting the adapter for M-NET
connection to the outdoor unit
allows MELANS (M-NET system)
connection
Power supply unit
Centralised remote
controller G-50, etc.
M-NET adapter
PAC-SF80MA-E
(Connection with M-NET system)
Centralised On/Off control
(for All Outdoor Units)
MAC-821SC-E
Up to eight indoor units can be
switched On/Off with one
remote controller.
Indoor unit
Outdoor unit
I
Interlocking with
Lossnay
Lossnay can be controlled with
a remote controller.
Lossnay operation cable
Lossnay
Wired remote
controller
(Example of 1 : 1 system)
MAC-397IF-E
PAC-SF81MA-E
• Allows centralised control by
MELANS
• Centralised remote controller can be
connected to each indoor unit via
interface.
• Units can be turned on/off
independently or simultaneously
using a centralised controller
• On/Off statues of each unit can be
confirmed viewing the LED display of
the centralised controller
• MAC-397IF-E
(Interface)
• MAC-821SC-E
(Centralised remote controller)
• Lossnay can be connected to
the indoor unit
Slim-Lossnay connection cable
22
Specifications
Specifications: Outdoor Unit
Outdoor unit
SUZ-KA25VA2
SUZ-KA35VA2
SUZ-KA50VA2
SUZ-KA60VA2
External finish
Munsell 3.0Y 7.8/1.1
Power supply
Single-phase, 50Hz, 230V
(kW)
0.55
0.65
0.85
1.2
34 (568)/32 (534)
33 (551)
49 (818)
50 (835)/48 (800)
Cooling mode
46
47
53
55
Heating mode
46
48
55
55
59
61
68
69
Compressor output
Airflow (cooling/heating)
Sound pressure
level (dB)
CMM (L /S)
(dB)
Sound level
Dimensions
SUZ-KA71VA2
Height
(mm)
550
850
880
Width
(mm)
800
840
840
Depth
(mm)
285
330
330
53
53
Weight
(kg)
Chargeless piping length
(m)
Max. piping length
(m)
20
30
Breaker size
(A)
10
20
33
37
7
*Above specifications are for outdoor units only.
Outdoor unit
PUHZ-RP71VHA4
PUHZ-RP100VKA
PUHZ-RP125VKA
External finish
Munsell 3.0Y 7.8/1.1
Power supply
Single-phase, 50Hz, 230V
(kW)
Compressor output
1.6
1.9
60 (1,000)
110 (1,830)
Cooling mode
47
49
50
50
Silent mode
44
46
47
47
Heating mode
48
51
52
52
(dB)
66
69
70
70
Height
(mm)
943
1,338
Width
(mm)
950
1,050
Depth
(mm)
Airflow (cooling/heating)
Sound pressure
level (dB)
Sound level
Dimensions
PUHZ-RP140VKA
CMM (L /S)
2.4
2.9
120 (2,000)
330
Weight
(kg)
67
Chargeless piping length
(m)
30
30
Max. piping length
(m)
50
75
Protection device
118
120
Discharge thermo, HP switch
Rated running current
(cooling/heating)
(A)
9.50/9.64
Breaker size
(A)
25
12.64/13.58
16.90/16.99
32
19.68/19.23
40
*Above specifications are for outdoor units only.
23
Specifications
Specifications: Outdoor Unit
Outdoor unit
PUHZ-RP170VKA/YKA
PUHZ-RP200YKA
External finish
Munsell 3.0Y 7.8/1.1
V: Single-phase, 50Hz, 230V Y: Three-phase, 50Hz, 400V
Power supply
(kW)
Compressor output
3.6
6.7
185 (3,083)
Cooling mode
58
58
Silent mode
56
—
Heating mode
59
58
(dB)
76
—
Height
(mm)
1,338
1,650
Width
(mm)
1,050
920
Depth
(mm)
330
760
Sound level
Dimensions
3.0
Three-phase, 50Hz, 400V
140 (2,330)
Airflow (cooling/heating)
Sound pressure
level (dB)
PUHZ-RP250YHM-A
CMM (L /S)
Weight
(kg)
Chargeless piping length
(m)
30
7.5
Max. piping length
(m)
75
75
V: 127 Y: 131
136
200
Discharge thermo, HP switch
Protection device
Rated running current
(cooling/heating)
(A)
V: 23.8/24.8 Y: 8.0/8.8
8.7/10.2
10.54/11.80
Breaker size
(A)
V: 40 Y: 32
32
32
*Above specifications are for outdoor units only.
Notes for All Specifications
Rating conditions (AS/NZS 3823)
Cooling - Indoor: 27°C (80°F) DB, 19°C (66°F) WB
Outdoor: 35°C (95°F) DB
Heating - Indoor: 20°C (68°F) DB
Outdoor: 7°C (45°F) DB, 6°C (43°F) WB
Total input based on the indicated voltage (indoor/outdoor)
50Hz
Refrigerant piping length (one-way): 5m (16ft.)
Indoor
Outdoor
Single-phase, 230V
Single-phase, 230V/ Three-phase, 400V
Guaranteed Operating Range
SUZ-KA
PUHZ
PUHZ
25/35
50/60/71
71/100/125/140/170/200
250
Upper limit (DB)
46°C
43°C
46°C
43°C
Lower limit (DB)
–10°C
–15°C
–5°C (–15°C )
–5°C
Upper limit (DB)
24°C
24°C
21°C
21°C
Lower limit (DB)
–15°C
–15°C
–20°C
–11°C
Cooling
Heating
With the optional air outlet guide, the operation at –15°C outdoor temperature is possible.
Sound Pressure Level
• Sound pressure measurements were conducted in an anechoic chamber.
• The actual noise level depends on the distance from the unit and the acoustic environment.
Optional Parts
24
Optional Parts
Part name
Model name
PAC-SG59SG-E
Application name
Part name
Model name
PAC-SH88KF-E
PCA-RP50KAQ
PAC-SH89KF-E
PCA-RP60/71KAQ
PAC-SH90KF-E
PCA-RP100/125/140KAQ
High efficiency filter element
PAC-SH59KF-E
PLA-RP
i-see Sensor corner panel
PAC-SA1ME-E
PLA-RP
PUHZ-RP71
Air outlet guide
High efficiency filter
PAC-SH96SG-E
PUHZ-100/125/140/170/200
PAC-SH51SP-E
PLA-RP
PAC-SH63AG-E
PUHZ-RP71
PAC-SH95AG-E
PUHZ-RP100/125/140/170/200
Built-in wireless remote control
receiver kit
PAR-SA9FA-E
PLA-RP
L-shape connection pipe
Control / service tool
PAC-SK52ST-E
PUHZ-RP71/100/125/140/170/200
PAC-SF81KC-E
Air outlet shutter plate
Air protection guide
ø 9.52
ø 12.7
PAC-SG73RJ-E
PUHZ-RP71/100/125/140/170/200
ø 15.88
ø 19.05
PAC-SG75RJ-E
PUHZ-RP71/100/125/140
PAC-SC84PI-E
PKA-RP71
PAC-SC86PI-E
PKA-RP100
M-NET adapter
PAC-SF81MA-E
PUHZ-RP71/100/125/140/170/200
PCA-RP71HAQ
Multi-function casement
PAC-SH53TM-E
PLA-RP
PAC-SF82KC-E
PCA-RP125HAQ
Oil mist filter element
PAC-SG38KF-E
PCA-RP71/125HAQ
PAC-SG64DP-E
PUHZ-RP71
Power supply terminal kit
PAC-SG96HR-E
PUHZ-RP71/100/125/140/170/200
PAC-SC32PTA
All indoor units
(excluding PEA-RP250WHA)
PAC-SA89TA-EP
PEA-RP250WHA
Joint pipe
Decoration cover
Drain pan
Drain pump
Drain socket
Duct flange for fresh air
Filter dryer
ø 9.52 (liquid)
Flange for Fresh-air Intake
Application name
PAC-SH97DP-E
PUHZ-RP100/125/140/170/200
PAC-SE90DM-E
PKA-RP
PAC-SH83DM-E
PCA-RP50KAQ
Remote On/Off adapter
PAC-SE55RA-E
All indoor units
PAC-SH84DM-E
PCA-RP71/100/125/140KAQ
Remote operation adapter
PAC-SF40RM-E
All indoor units
(excluding PEA-RP250WHA)
PAC-SH85DM-E
PCA-RP60KAQ
Remote sensor
PAC-SE55RA-E
All indoor units
PAC-SG61DS-E
PUHZ-RP71/100/125/140/170/200
Space panel
PAC-SH48AS-E
PLA-RP
MAC-851DS
SUZ-KA25/35
MAC-811DS
SUZ-KA50/60/71
Terminal block
PAC-SH29TC-E
PKA-RP for wired remote controller
PCA-RP71/125HAQ
Wired remote controller
PAR-21MAA
PAC-SF28OF-E
PAR-30MAA
All indoor units
(excluding PEA-RP170/200/250WHA)
PAC-SG82DR-E
PCA-RP71/125HAQ
Wireless remote controller kit
PAR-SL94B-E
PCA-RP
PAC-SH65OF-E
PLA-RP
Wiring replace kit
PAC-SH52HR-E
PLA-RP
Program timer
Refrigerant Piping
Capacity
SUZ-KA25
SUZ-KA35
SUZ-KA50
SUZ-KA60
SUZ-KA71
PUHZ-RP71
PUHZ-RP100/125/140
PUHZ-RP170/200
PUHZ-RP250
Between indoor & outdoor units
Max. height difference (m)
Max. piping length (m)
12
20
12
30
30
30
30
30
30
30
20
30
30
30
50
75
75
75
Pipe size OD (mm) (in.)
Thickness (mm)
Liquid: ø6.35
t 0.8
Gas:
ø9.52
t 0.8
Liquid: ø6.35
t 0.8
Gas:
ø9.52
t 0.8
Liquid: ø6.35
t 0.8
Gas:
ø12.7
t 0.8
Liquid: ø6.35
t 0.8
Gas: ø15.88
t 1.0
Liquid: ø9.52
t 0.8
Gas: ø15.88
t 1.0
Liquid: ø9.52
t 0.8
Gas: ø15.88
t 1.0
Liquid: ø9.52
t 0.8
Gas: ø15.88
t 1.0
Liquid: ø9.52
t 0.8
Gas: ø25.4
t 1.0
Liquid: ø9.52
t 0.8
Gas: ø22.2
t 1.0
25
Amount of Necessary Refrigerant
Amount of Necessary Refrigerant ( R410A: kg)
Factory charged
Additional charged
Calculation
Piping length
7m
10m
15m
20m
25m
30m
SUZ-KA25
0.9
0.15
0.3
0.45
—
—
SUZ-KA35
1.05
0.15
0.3
0.45
—
—
SUZ-KA50
1.6
0.06
0.16
0.26
0.36
0.46
SUZ-KA60
1.8
0.06
0.16
0.26
0.36
0.46
SUZ-KA71
2.0
0.165
0.44
0.715
0.99
1.265
Xg = 30g/m × (length-5) m
Xg = 20g/m × (length-7) m
Factory charged
Xg = 55g/m × (length-7) m
Additional charged
Piping length
10 - 30m
31 - 40m
41 - 50m
51 - 60m
61 - 75m
PUHZ-RP71
3.5
0.6
1.2
—
—
PUHZ-RP100/125/140
5.5
0.6
1.2
1.8
2.4
Factory charged
Additional charged
Piping length
PUHZ-RP170/200
10 - 30m
31 - 40m
41 - 50m
51 - 60m
61 - 70m
10.5
0.9
1.8
2.7
3.6
*The above values apply in the case of 1:1 connections.
*Please refer to the service manual for PUHZ-RP250.
26
NOTICE
 Air conditioners in this brochure contain and operate with refrigerant R410A and synthetic oils.
Before attempting any installation work you must read the installation instructions.
New tools, materials and procedures are required to install these products.
Under New Zealand Law, only persons suitably licensed are permitted to install and service air conditioning units.
Refer to Country, Commonwealth, State or Territory legislation, regulations and industry codes of practice, before installation
of these products.
Recovery and disposal of waste material must comply with Council guidelines.
 Do not install indoor units in areas (e.g., mobile phone base stations) where the emission of VOCs such as phthalate
compounds and formaldehyde is known to be high as this may result in a chemical reaction.
 When installing or relocating or servicing the air conditioners, use only the specified refrigerant (R410A) to charge the
refrigerant lines.
Do not mix it with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant lines, and may
result in an explosion and other hazards.
The use of any refrigerant other than that specified for the system will cause mechanical failure or system malfunction or
unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
Constant warmth in winter and cool
comfort in summer is only a phone
call or click away.
Simply contact your nearest Mitsubishi Electric Specialist today and you can find out all there is to
know about how to enhance your living environment. Our specialists are fully qualified to give you
all the right advice on which Mitsubishi Electric Air Conditioning System is right for you.
To locate your nearest Mitsubishi Electric Specialist go to our website
http://www.mitsubishi-electric.co.nz
They will determine whether a Compact Inverter System or a Power Inverter System best suits
your needs, both in comfort and efficiency. You can either visit one of our Specialist’s Showrooms, or they will happily arrange for one of their consultants to come to your home.
All Mitsubishi Electric Compact and Power Inverter Systems are MEPS (Minimum Efficiency
Performance Standard) Compliant, so you can be sure that they will give you the performance and
efficiency that they were designed to deliver.
these products.
BLACK DIAMOND TECHNOLOGIES
http://www.bdt.co.nz
Wellington (Head Office):
Auckland:
Christchurch:
1 Parliament Street, PO Box 30-772
Lower Hutt, Wellington
Ph: (04) 560 9147 Fax: (04) 560 9133
Unit 1, 4 Walls Road,
PO Box 12-726, Penrose, Auckland
Ph: (09) 526 9347 Fax: (09) 526 9369
44 Halwyn Drive
PO Box 16904, Christchurch
Ph: (03) 341 2837 Fax: (03) 341 2838
Black Diamond Technologies Ltd
L-179-7-C7741-F
Si 1104 Printed in Japan (NLP)
AUCKLAND
Unit 1, 4 Walls Road, Penrose
PO Box 12726, Penrose, Auckland 1061
Phone (09) 526 9347, Fax (09) 526 9369
Distributed by
WELLINGTON (HEAD OFFICE)
Revised publication, effective Apr. 2011
Superseding publication L-179-7-C7741-E Jun. 2010
Specifications
CHRISTCHURCHsubject to change without notice
1 Parliament Street, Lower Hutt
PO Box 30772, Lower Hutt 5040
Phone (04) 560 9147, Fax (04) 560 9133
44 Halwyn Drive, Hornby
PO Box 16904, Hornby, Christchurch 8441
Phone (03) 341 2837, Fax (03) 341 2838
www.mitsubishi-electric.co.nz
New publication effective September 2011.
All features and specifications are subject to change and amendment at anytime.
Where specifications are critical to design or pre-build we advise that you seek confirmation of accuracy from our product management team on (04) 560 9100.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement