2562 8-Channel Analog Output Module Specifications

2562 8-Channel Analog Output Module Specifications
2562 8-Channel
Analog Output Module
Description
Product Bulletin
2500 Series PLC System
Specifications
The 2562 is a low-cost, high-speed, 8channel analog output module designed to
be compatible with the SIMATIC® 505
programmable controllerI/O base. The 2562
translates digital words from the controller
into equivalent analog outputs. The 2562 is
fully compatible with all versions of the 545
and 555 PLCs.
Features
Replaces Siemens® 505-6208 with no
rewiring
8 analog output channels
1500V channel-to-PLC backplane isolation
Update time 4 mSec all channels
12 bits of resolution
Voltage and current outputs available
simultaneously
Bipolar or Unipolar outputs per channel
Single-wide module
Control Technology Inc.
Output Channels: 8 analog output channels
Response Time:
4 mSec total module (includes settling time)
Output Range:
Unipolar:
0 to +5.12 VDC
0 to +10.24 VDC
0 to +20 mA
Bipolar:
-5.12 to +5.12 VDC
-10.24 to +10.24 VDC
-20 to +20 mA
Resolution 12 Bits:
Unipolar 12 bits:
0 - 20 mA range = 5µA/step
0 - 5 VDC range = 1.25mV/step
0 - 10 VDC range = 2.5mV/step
Bipolar 11 bits plus sign:
-5 to +5 VDC range = 2.5mV/step
-10 to +10 VDC range = 5.0mV/step
-20 to +20 mA range = 10µA/step
Isolation:
1500 VDC channel-to-PLC
Capacitance Drive: 0.01 microfarad
Load Resistance:
Voltage: 1KΩ minimum, no maximum
Current: 0Ω to 1KΩ max. @ 24 VDC
or greater
Accuracy:
Voltage mode: 0.125% of full scale from 0o to
60oC over total load range
Current mode: 0.225% of full scale from 0o to
60oC over total load range
User Supply:
20 to 30 VDC @ 0.50 Amps max.
(maximum ripple of 0.4 V)
NOTE: Maximum load resistance for current
output drops to 600Ω @ 20 VDC user supply
Connector: Removable
Wire Gauge: 14-22 AWG
Backplane Power: 1.7 Watts
Module Size: Single-wide
Operating Temperature: 0o to 60oC
(32o to 140oF)
Storage Temperature: -40o to 85oC
(-40o to 185oF)
Relative Humidity: 5% to 95% (non-condensing)
Agency Approvals:
UL, UL-Canada
Agency Approvals Pending:
Class 1 - Div.2
Shipping Weight: 1.5 lb. (0.68 Kg)
5734 Middlebrook Pike, Knoxville, TN 37921 Phone: 865/584-0440 Fax: 865/584-5720
www.controltechnology.com
Typical Internal Circuit - Voltage Mode
Typical Internal Circuit - Current Mode
AC
24 V Common
I1 Out
V1 Out
Return 1
Not used
Not used
I2 Out
V2 Out
Return 2
Not used
Not used
I3 Out
V3 Out
Return 3
Not used
Not used
I4 Out
V4 Out
Return 4
Chassis
AR
A5
A1
A6
A2
A7
A3
A8
A4
BC
BR
B5
B1
B6
B2
B7
B3
B8
B4
CC
CR
C5
C1
C6
C2
C7
C3
C8
C4
DC
DR
D5
D1
D6
D2
D7
D3
D8
D4
24 VDC +
I5 Out
V5 Out
Return 5
Not used
Not used
I6 Out
V6 Out
Return 6
Not used
Not used
I7 Out
V7 Out
Return 7
Not used
Not used
I8 Out
V8 Out
Return 8
Chassis
2562 Wiring Connector
Copyright ©2005 Control Technology Inc.
All Rights Reserved