B215HT029 TFRX24-MFT-S

B215HT029 TFRX24-MFT-S
B215HT029, 1/2”, High Temperature CCV
Stainless Steel Ball and Stem
Application
This valve is typically used in air handling units on heating or cooling coils, and
fan coil unit heating or cooling coils. Some other common applications include
Unit Ventilators, VAV box re-heat coils and bypass loops. This valve is suitable
for use in a hydronic sysyem with variable flow.
This valve is designed to fit in compact areas where on/off or floating point
control is required using 24 VAC.
Suitable Actuators
Non-Spring
TR, LR
B215HT029
Spring
TFR
Dimensions (Inches [mm])
Date created, 01/23/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.
1691
Flow Characteristic
Controllable Flow Range
Size [mm]
End Fitting
Body
Body Finish
Ball
Stem
Stem Packing
Seat
Seat O-ring
Characterized Disc
Body Pressure Rating [psi]
Max Inlet Pressure (Steam)
Media Temperature Range
(Water)
Media Temperature Range
250°F [120°C]
(Steam)
Maximum differential pressure
15 psi
(steam)
Max Differential Pressure (Water) 60 psi partially open ball, 116 psi full open
(#B215HT455)
Closing pressure ∆ps
200 psi
Leakage
0%
Cv
0.29 Servicing
maintenance free
C
High temperature hot water/low pressure
steam, up to 60% glycol
A-port equal percentage
75°
0.5” [15]
NPT female ends
brass (DZR) P-CuZn35Pb2
nickel plated
stainless steel
stainless steel
Vition O-ring
ETFE
EPDM (lubricated)
ETFE
600
15 psi
60°F to 266°F [16°C to 130°C]
D
Technical data
Service
E
F
B
A
TR
A
B
C
D
4.16” [106] 3.33” [85] 5.44” [138] 4.91” [125]
E
1.3” [33]
F
Flow Pattern
Flow direction
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
B215HT029, 1/2”, High Temperature CCV
Stainless Steel Ball and Stem
E
H1
C
D
Dimensions (Inches [mm])
B
F
A
H2
LRB, LRX
A
8.32”
[211]
B
3.33”
[85]
C
5.8”
[147]
D
5.3”
[135]
E
F
1.3” [33]
H1
1.18”
[30]
H2
0.5” [15]
E
Date created, 01/23/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.
C
D
Dimensions (Inches [mm])
B
F
A
TFRB, TFRX
A
B
7.32” [186] 3.33” [85]
C
5.8” [147]
800-543-9038 USA
D
5.3” [135]
E
1.52” [39]
F
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
TFRX24-MFT-S
Modulating, Spring Return, Multi-Function Technology®
Date created, 01/23/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.
Technical Data
Power Supply
Power Consumption Running
Power Consumption Holding
Transformer Sizing
Shaft Diameter
Electrical Connection
100162
24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%
2.5 W 1 W 4 VA (class 2 power source)
1/4” to 1/2” round, centers on 1/2”
(2) 3 ft, 18 GA appliance cables with 1/2”
conduit connectors
Overload Protection
electronic throughout 0° to 95° rotation
Electrical Protection
actuators are double insulated
Operating Range Y
2 to 10 VDC, 4 to 20 mA (w/ 500 Ω, 1/2 W
resistor) ZG-R01
Input Impedance
100 k Ω for 2 to 10 VDC (0.1 mA), 500 Ω for
4 to 20 mA, 1500 Ω for PWM, floating point
and On/Off
Feedback Output U
2 to 10 VDC, 0.5 mA max, VDC variable
Angle of Rotation
max. 95°, adjustable with mechanical stop
Direction of Rotation (Motor)
reversible with built-in switch
Direction of Rotation (Fail-Safe) reversible with CW/CCW mounting
Position Indication
visual indicator, 0° to 95° (0° is full spring
return position)
Manual Override
No
Running Time (Motor)
150 seconds
150 seconds (default), variable (75 to 300
seconds)
Running Time (Fail-Safe)
<25 seconds
Angle of Rotation Adapation
Off (default)
Override Control
min. position = 0% , mid. Position = 50% ,
max. position = 100% (Default)
Humidity
max. 95% RH non-condensing
Ambient Temperature Range
-22°F to 122°F [-30°C to 50°C]
Storage Temperature Range
-40°F to 176°F [-40°C to 80°C]
Housing
NEMA 2, IP42, UL enclosure type 2
Housing Material
UL94-5VA
Agency Listings†
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC and
2006/95/EC
Noise Level (Motor)
<35 dB (A) Noise Level (Fail-Safe)
<62 dB (A) Servicing
maintenance free
Quality Standard
ISO 9001
Weight
2 lbs [0.9 kg]
Auxiliary Switch
1 x SPDT, 3A resistive (0.5A inductive) @ 250
VAC, adjustable 0° to 95°
*Variable when configured with MFT options.
†Rated Impulse Voltage 800V, Type of action 1.AA, Control Pollution Degree 3
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
TFRX24-MFT-S
Modulating, Spring Return, Multi-Function Technology®
Wiring Diagrams
24 VAC Transformer
INSTALLATION NOTES
A
Actuators with appliance cables are numbered.
A
1
3
Blk (1)
Common
Red (2)
Hot +
(–)
Wht (3)
Y Input
Actuators may also be powered by 24 VDC.
Position
Feedback VDC (+)
Org (5)
U Output
Two built-in auxiliary switches (2x SPDT), for end position indication,
interlock control, fan startup, etc.
On/Off
Line
Volts
Provide overload protection and disconnect as required.
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.
11
Only connect common to negative (-) leg of control circuits.
Control signal may be pulsed from either the Hot (Source) or Common
(Sink) 24 VAC line.
For triac sink the Common connection from the actuator must be
connected to the Hot connection of the controller. Position feedback
cannot be used with a triac sink controller; the actuator internal
common reference is not compatible.
Actuators may be connected in parallel if not mechanically linked. Power
consumption and input impedance must be observed.
IN4004 or IN4007 diode. (IN4007 supplied, Belimo part number
40155).
44
One built-in auxiliary switch (1x SPDT), for end position indication,
interlock control, fan startup, etc.
APPLICATION NOTES
Meets cULus requirements without the need of an electrical ground
connection.
!
24 VAC Transformer (AC Only)
Line
Volts
Blk
12
Position (–)
Feedback VDC (+)
1
10
(1)
11
Common
Red (2)
Hot +
Wht (3)
Y Input
Org
U Output
(5)
Floating Point
24 VAC Transformer
Line
Volts
Control Signal (–)
1
3
5
Blk (1)
Common
Red (2)
Hot +
Wht (3)
Y Input
Org (5)
U Output
11
Ω 500 Ω
1/4 watt
VDC / mA (+)
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to
live electrical components could result in death or serious injury.
A
7
VDC/mA Control
24 VAC Transformer (AC Only)
Line
Volts
Position (–)
Feedback VDC (+)
1
8
11
Blk (1)
Common
Red (2)
Hot +
Wht (3)
Y Input
Org (5)
U Output
PWM Control
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Date created, 01/23/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2
to 10 VDC.
TFRX24-MFT-S
Modulating, Spring Return, Multi-Function Technology®
24 VAC Transformer (AC Only)
Line
Volts
A
B
Ω
Control Signal
VDC/mA
(–)
(+)
C
7
Functions
Min
0%
Mid
50%
Max
Normal
a
b
12
A
1
5
Blk (1)
Common
Red (2)
Hot +
Wht (3)
Y Input
Org (5)
U Output
c
100%
Control mode acc. to Y
Override Control
1
44
S1
S2
S3
NC
NO
0° to 95°
Date created, 01/23/2016 - Subject to change. © Belimo Aircontrols (USA), Inc.
Auxiliary Switches
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement