GE XMT 868 flowmeter User manual
Below you will find brief information for flowmeter XMT 868. The XMT868 is a Foundation Fieldbus-enabled flowmeter, which provides data for network communication. You can configure the meter's analog inputs to provide velocity, totalizer time, power, volumetric flow, energy, and temperature readings.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
7
GE Sensing 913-326A November 2005 Foundation Fieldbus Communications for the XMT868 Network Connection and Factory Reset Fieldbus network connections are made at J8, pins 1 and 2 (see Figure 1 below). Optionally, a shield can be connected to J8 pin 3, depending on the network wiring. No connections are made to J9 under normal operation. If it is desired to reset the network board to factory defaults: 1. Connect a jumper between J9 pin 2 and J9 pin 3. 2. Power cycle the instrument. Ne et t( +) hi (–) • • eld • 3 J9 sN lS 1 na • • J8 J8 bu s bu • 3 ld ld ti o R Re TN se t N/ C 1 F ie Fie ry 2 Op to 2 Fa c J9 3. Ten seconds after the power has been restored to the unit, remove the jumper to return the network board to normal operation. Figure 1: Model XMT868 Rear View - Network Connection and Factory Reset November 2005 Foundation Fieldbus Communications Foundation Fieldbus provides a means of communicating with the XMT flowmeter. The patent numbers which apply are 5,909,363 and 6,424,872. This Foundation Fieldbus device supports 2 Analog Input (AI) blocks, which can be configured to supply the following measurements on the network. Table 1: Available Measurements Description Units Description Units Description Units Ch1 Velocity ft/s or m/s* Ch2 Totalizer Time seconds Ch1 Power POWER_U Ch1 Volumetric VOL_U Ch2 Error Value none Ch1 +Energy ENERGY_U Ch1 +Totals TOT_U Ch2 SSUP none Ch1 –Energy ENERGY_U Ch1 -Totals TOT_U Ch2 SSDN none Ch1 TempS Deg F or C* Ch1 Tot Digits** none Ch2 SNDSP ft/s or m/s* Ch1 TempR Deg F or C* Ch1 Totalizer Time seconds Avg Velocity ft/s or m/s* Ch1 TS-TR Deg F or C* Ch1 Error Value none Avg Volumetric VOL_U Ch1 DELTH Btu/lb J/gm Ch1 SSUP none Avg +Totals TOT_U Ch2 Power POWER_U Ch1 SSDN none Avg -Totals TOT_U Ch2 +Energy ENERGY_U Ch1 SNDSP ft/s or m/s* Avg Tot Digits** none Ch2 –Energy ENERGY_U Ch2 Velocity ft/s or m/s* Avg Totalizer Time seconds Ch2 TempS Deg F or C* Ch2 Volumetric VOL_U Avg Error Value none Ch2 TempR Deg F or C* Ch2 +Totals TOT_U Avg SSUP none Ch2 TS-TR Deg F or C* Ch2 –Totals TOT_U Avg SSDN none Ch2 DELTH Btu/lb J/gm Ch 2 Tot Digits** none Avg SNDSP ft/s or m/s* *Metric or English units are determined by the setup of the XMT868 flow meter. **Totalizer digits are available for informational purposes only. Respective totals are automatically scaled by the Tot Digits value selected in the XMT flow meter setup. VOL_U, TOT_U, POWER_U and ENERGY_U are determined by the units chosen for these measurements in the setup for the XMT868 flow meter. See the instrument User's Manual for the setup of these parameters. 913-326A 2 of 7 November 2005 Configuration Utility Setup The following is an example setup using National Instruments Configuration Utility v3.1. Figure 2 below shows the Configuration Utility with an XMT868 flow meter on the network (GE Flow-XMT). Figure 2: Configuration Utility Setup Example Note: The following procedures assume that the device has been placed in the OOS (out-of-service) mode before executing. Selecting the Desired Measurements To set the measurement unit for each AI: 1. Double click on the FLOW Transducer Block (in the tree under GEFlow-XMT). 2. Select the Others tab and open the drop down list for the PRIMARY_SELECTOR and SECONDARY_SELECTOR (see Figure 3 on page 4). 3. Choose the unit from the list (see Figure 3 on page 4). This unit will correspond to the unit that is available in the AI block for network connection. The PRIMARY_SELECTOR unit will correspond to ANALOG_INPUT_1 and the SECONDARY_SELECTOR will correspond to ANALOG_INPUT_2. 913-326A 3 of 7 November 2005 Selecting the Desired Measurements (cont.) 4. After the desired measurements have been selected for the PRIMARY and SECONDARY SELECTOR, choose the unit system (UNIT_SELECTOR above the PRIMARY_SELECTOR) that has been programmed in the XMT868 (English or SI). Figure 3: Primary Selector Drop Down List 913-326A 4 of 7 November 2005 Selecting Units for AI Blocks To select the units for the individual AI blocks: 1. Double click on the AI block for which you wish to set the units (ANALOG_INPUT_1 or ANALOG_INPUT_2 in the tree under GEFlowXMT; see Figure 2 on page 3). 2. Select the Scaling tab and set the unit for the measurement based on the XMT868 flow meter settings. For example, if the XMT868 was set to use the metric unit system and the PRIMARY_SELECTOR was set to use VELOCITY you would choose m/s for the unit as shown in Figure 4 below. Figure 4: Units Index Drop Down List 913-326A 5 of 7 November 2005 Resetting Instrument Totalizers To reset the instrument totalizers: 1. Double click on the FLOW transducer block (in the tree under GEFlowXMT; see Figure 2 on page 3). 2. Select the Others tab and scroll down to the CLEAR_TOTALIZERS listing. 3. Select Clear from the drop down list box (see Figure 5 below). 4. After the totals have been reset, select Normal from the drop down list box to resume total accumulation. Figure 5: Clear Totalizers Drop Down List 913-326A 6 of 7 November 2005 Function Block Application Figure 6 below is an example setup using the Function Block Application editor. The XMT868 AI blocks, along with the AO and PID of another device on the network, are displayed. We have connected the AI_1 OUT of the XMT868 to the CAS IN of the AO block. We have also connected the AI_2 OUT of the XMT868 to the CAS IN of the PID block. Figure 6: Function Block Application 913-326A 7 of 7
advertisement
Key Features
- Foundation Fieldbus Communication
- Network connection
- Analog inputs
- Totalizer reset
- Factory reset
Frequently Answers and Questions
How do I connect the XMT868 flowmeter to the network?
The network connections are made at J8, pins 1 and 2. Optionally, a shield can be connected to J8 pin 3.
How do I reset the network board to factory defaults?
Connect a jumper between J9 pins 2 and 3, power cycle the instrument, and remove the jumper 10 seconds after power is restored.
What measurements can I get from the XMT868 flowmeter?
The XMT868 provides velocity, totalizer time, power, volumetric flow, energy, and temperature readings.
How do I configure the units for the analog input blocks?
Double-click on the AI block, select the Scaling tab, and choose the unit based on the XMT868 settings.
How do I reset the instrument totalizers?
Double-click on the FLOW transducer block, select the Others tab, and choose Clear from the CLEAR_TOTALIZERS drop-down list.