- Industrial & lab equipment
- Noise Reduction Machine
- Emerson Climate Technologies
- Variable Frequency Drives
- User manual
- 4 Pages
Emerson Climate Technologies Variable Frequency Drives, Discus, Scroll, ZB, ZS, ZF, ZP, ZR, ZRHV72KJE, ZBHV45KJE Compressor Application Engineering Bulletin
Below you will find brief information for Variable Frequency Drives, Compressor Discus, Compressor Scroll, Compressor ZB, Compressor ZS, Compressor ZF, Compressor ZP, Compressor ZR. This document provides technical guidelines for using Variable Frequency Drives (VFDs) with Copeland Discus and Scroll Compressors in refrigeration systems. It covers topics such as the operation of a VFD, its effect on compressor capacity, and the necessary precautions to ensure successful operation.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
4
AE21-1369 R1 November 2011 AE21-1369 R1 Use of Variable Frequency Drives (VFDs) with Copeland Scroll® and Discus® Compressors INDEX PAGE • Low starting current obviates the need for assisted start devices 1. Introduction........................................................ 1 2. Operation of a Variable Frequency Drive........... 1 3. Evaluation and Important Considerations.......... 1 4. Limits of Use with Copeland® Compressors ...... 2 5. Approved Frequency Ranges with Standard Motors................................................. 2 6. Minimum Speed................................................. 2 7. Effect of the VFD on Performance and Power Input ....................................................... 2 8. Control of VFD Frequency................................. 2 9. Start Contactor Positioning ............................... 2 10. Starting and Ramp Up ....................................... 2 11. Electrical Shielding and Voltage Rise................. 2 12. Vibration............................................................. 3 13. Recommended VFD Range............................... 3 14. Typical VFD Parameter Set Up for Discus (Scroll) Compressors......................................... 3 • With gradual speed increase from standstill there is less risk of sudden liquid or oil return to the compressor on start up The objective of this bulletin is to provide technical guidelines to developers, designers or installers that intend to use VFDs on Copeland Discus compressors in their refrigeration systems. The operation of a VFD, the effect on compressor application range, performance and power, precautions and some implications on system design are discussed. 2. Operation of a Variable Frequency Drive A VFD works by converting the input mains alternating current to direct current and, from this, generating a simulated A.C. signal at varying frequencies. A compressor driven by a squirrel cage induction motor will run at a speed corresponding to the frequency. The speed will be in direct proportion to the frequency. 1. Introduction Variable frequency drives (VFDs) are used to vary the speed of motors and in this way can be used to control the capacity of a compressor. For refrigeration users they can be an effective method of accurately matching compressor capacity to a load requirement. A method of reducing compressor output is needed in almost every application. With the emphasis today on saving energy by reducing head pressures, an effective capacity control method can bring enormous benefits. Without the means to run efficiently at low capacity, compressor cycling by switching on/off is most commonly used. This method introduces large fluctuations and high power consumption due to heavily loaded heat exchangers. Multiple compressor solutions overcome this problem to some extent and stepping by means of cylinder unloading is used with piston compressors. 3. Evaluation and Important Considerations The advantages of varying compressor speed are: The power absorbed by a compressor operating with a VFD will always be more than for a direct connected compressor running at the same speed. It is important to choose a high quality VFD because the VFD absorbs a certain amount of power and also the nature of the electrical waveform at the motor is disjointed, resulting in increased motor losses. Investigations carried out by Emerson Climate Technologies have included computer simulations, variable speed compressor performance testing, reliability testing, and refrigeration system field data comparisons. Most VFDs are capable of generating frequencies from 2.5 Hz to over 300 Hz. This is well outside the range of any refrigeration compressor, therefore part of the investigation has been focused on assessing practical limits. Limits arise due to the capability of the oil pump to maintain lubrication at low speed and motor cooling. Increased losses at higher speeds can result in less efficient operation and compressor overheating (high discharge temperatures). • The load is more closely matched with minimal variation in evaporating pressure and fluctuations in load temperature are minimized • Better system efficiency at part load • Extended lifetime of equipment due to continuous operation instead of cycling © 2011 Emerson Climate Technologies Printed in the U.S.A. When considering a VFD, the following points should be taken into account: 1 AE21-1369 R1 6. Minimum Speed • Loss of efficiency unless care is taken with system design and control The minimum allowable frequency of 25 Hz for Discus and 45 Hz for scroll is governed by the lowest speed at which the lubrication system can operate effectively. • Conventional capacity control methods may not be used with a VFD (i.e. blocked suction, or Copeland Digital) on the same compressor 7. Effect of the VFD on Performance and Power Input • Vibration resonance may occur at certain speeds and these are very difficult to predict The capacity can be calculated as being in direct proportion to the speed. A compressor is designed to have optimum pumping efficiency at its nominal speed, usually 1750 RPM for discus and 3500 RPM for scroll. When operating at speeds other than the nominal the efficiency will change because of the behaviour of the valve reeds and the change in pressure drop through the valve plate. However, as these tend to balance out, the change in volumetric efficiency is small. • Restrictions on operating envelope may be necessary • Risk of electrical disturbance to control signals 4. Limits of Use with Copeland® Compressors With many VFDs it is very easy to alter the maximum and minimum output frequencies and the frequency range, so care must be taken to ensure the frequencies are correctly adjusted to prevent damage to the compressor. 8. Control of VFD Frequency The signal necessary to control the VFD depends on the type of VFD used. They are commonly controlled by an analog 4 to 20 mA signal. This signal should respond to changes in the system's control variable, for example changes in suction pressure or room temperature. Emerson strongly recommends controlling off of suction pressure because a response to a temperature signal may lag. Note! In most variable frequency drives, you can also program "skip" frequencies to avoid vibration resonance that may occur at certain speeds. 5. Approved Frequency Ranges with Standard Motors See Table 1 below. Normally the ratio of voltage/frequency (V/f) is kept constant, and it is only when the required voltage is above the supply voltage that the amps increase. For example, a 380V 60Hz motor will only require 320V at 50 Hz according to the constant V/f rule, and can therefore be safely operated at all conditions up to 60 Hz with a suitable drive. See Figure 1 below. 9. Start Contactor Positioning If a contactor is used to disconnect the VFD from the motor it should be interlocked to only switch when the VFD is off. The VFD should not be allowed to operate with the output from the drive to the motor as an open circuit. There should be a contactor on each side of the drive, ie, between the drive and the supply and between the drive and the compressor motor. They should be interlocked to break the supply side first. When switching on, the motor side contactor should be made first. Note! Output voltage from the drive can not exceed the input voltage to the drive. Table 1 – Approved Operating Range for Copeland® Compressors Speed Range 3D, 4D, & 6D 25 - 60 Hz Refrigeration Scroll (ZB,ZS,ZF) 45 - 60 Hz Air Conditioning Scroll (ZP,ZR) 45 - 70 Hz Notes Contact your Emerson Climate Technologies representative for extended operating ranges. Voltage Model Family Note: Application Engineering Bulletin AE4-1343 should be referenced when applying the ZRHV72KJE and ZBHV45KJE variable speed horizontal Copeland Scroll compressors. © 2011 Emerson Climate Technologies Printed in the U.S.A. 500 450 400 350 300 250 200 150 100 50 0 ine 0V L ge a Volt 46 ltage ine Vo 230V L 20 25 30 35 40 45 Frequency Figure 1 2 50 55 60 65 AE21-1369 R1 below the minimal speed as called out in Table 1 could lead to vibration problems during start up. Spring mounts should not be used as they have a natural frequency below 65 Hz. As a rule of thumb, the system should be designed or the VFD control should be configured (skip frequencies programmed), such that there is no operation at resonant frequencies between 20 and 70Hz. When using a VFD bypass, care should be taken to ensure there can be no voltage feedback to the VFD. Therefore when the bypass contactor is closed and the bypass is in operation, the contactors on either side of the VFD must be open. See Figure 2 for an example of an approved optional VFD wiring bypass. 10. Starting and Ramp Up A VFD is capable of delivering a soft start, but at the same time care must be taken to ensure that stalling does not occur. The VFD must be able to deliver sufficient power at the lower frequencies to ensure that the compressor accelerates to nominal speed in approximately 3 seconds or less. Only general guidance can be given here, because the exact torque requirements will depend on system pressures at the time of start up. Longer ramp up times could result in inadequate lubrication. 13. Recommended VFD Range Emerson Climate Technologies recommends the use of the Control Techniques® brand of VFDs with Copeland Discus® compressors. Control Techniques VFDs have been tested with the compressors and include vector control algorithms for optimum torque generation, EMC filters for electrical noise reduction, and all of the necessary VFD features required for successful compressor operation. VFD selection tables are available on request. 11. Electrical Shielding and Voltage Rise 14. Typical VFD Parameter Set Up for Discus (Scroll) Compressors Wiring of the electrical enclosure and the installation must be carefully conducted in accordance with EMC recommendations. High quality, high reliable pressure sensors must be used and it is necessary to follow EMC measures to ensure that the VFD does not disturb the signals from pressure transducers. Suction and high pressure sensors signals must be noise-free to the controller input. For best results select a VFD with a built-in EMC filter or add the manufacturer's recommended optional filter if it is not a standard component. The following is a list of some control parameters for configuring a Control Techniques® Commander SK VFD. Par01 = 25 Hz Minimum Frequency (45 Hz for scroll) Par02 = 60Hz Maximum frequency (70 HZ for air conditioning scroll products) Par03 = 5 sec Acceleration ramp Par04 = 10 sec Deceleration ramp Because the waveform generated by the VFD is built up from pulses, there is a danger that the rate of voltage rise on an individual pulse can damage the motor windings. In order to minimize the risk of motor problems it is suggested that the VFD be operated at its lowest switching frequency and that the distance between the VFD and the compressor be as short as possible. Par06 = Motor rated current (A) Par07 = 1750 Motor Rated Speed (3500 for scroll) Par08 = 460 Motor rated voltage Par37 = 3kHz Switching frequency Par39 = 60 Motor rated frequency 12. Vibration Par41 = Ur_I Vector control mode A compressor running at fixed speed imposes vibrations on its associated framework at a set group of frequencies. The framework can of course be designed such that its natural frequencies differ from the imposed frequencies. Note that other parameters will need to be adjusted to match the control method and frequency set point input type used. A compressor driven at variable speed will impose different frequencies at each speed, so the framework design to eliminate vibration throughout the speed range is more complex. The framework structure should be stiff enough such that its resonant frequencies are above the maximum frequency, ie, 60 Hz. Designing with natural frequencies © 2011 Emerson Climate Technologies Printed in the U.S.A. 3 Figure 2 Example of Optional VFD Bypass Wiring Diagram AE21-1369 R1 © 2011 Emerson Climate Technologies Printed in the U.S.A. 4
advertisement
Key Features
- VFD operation
- Compressor capacity control
- VFD frequency range
- VFD bypass
- VFD parameter setup
- Compressor vibration
- Recommended VFD brand
- Starting and ramp up
- Electric Shielding and Voltage Rise
Frequently Answers and Questions
How does a VFD work?
A VFD converts the input mains alternating current to direct current and from this, generates a simulated A.C. signal at varying frequencies. A compressor driven by a squirrel cage induction motor will run at a speed corresponding to the frequency. The speed will be in direct proportion to the frequency.
What are the benefits of using a VFD with Copeland Discus and Scroll compressors?
The use of a VFD offers greater control of compressor capacity, better system efficiency at part load, extended equipment lifetime, and reduced motor vibration.
What are the limitations of using a VFD with Copeland Discus and Scroll compressors?
There are limitations to the operating speed range of the compressors with a VFD. Operating below the minimum speed can lead to lubrication issues and operating above the maximum speed can lead to overheating.
How to choose the right VFD for my application?
Emerson Climate Technologies recommends using Control Techniques® VFDs with Copeland Discus® compressors. These VFDs have been tested with the compressors and include vector control algorithms, EMC filters for electrical noise reduction, and all of the necessary features for successful compressor operation.