Below you will find brief information for PT Transmitter M5 PT. The M5 PT is a PT Transmitter designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet. The unit is calibrated at the factory to meet the ordered specifications. It is designed for indoor use and must be installed in areas with sufficient ventilation, away from heat sources and vibration.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
M5PT
INSTRUCTION MANUAL
PT TRANSMITTER
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
MODEL
M5PT
COMPONENT IDENTIFICATION
Body
Terminal Cover
Spec. Marking
Power LED
■ PACKAGE INCLUDES:
Signal conditioner.......................................................... (1)
Span Adj.
Zero Adj.
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
85 – 264V AC rating: 85 – 264V, 47 – 66 Hz, approx. 2 – 3VA
24V DC rating: 24V ±10%, approx. 2W
■ GENERAL PRECAUTIONS
•Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 0 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
•Install lightning surge protectors for those wires connected to remote locations. For 24V DC power supply line,
choose a surge protector with its maximum surge voltage
40V or less between lines. Recommended M-System model: MDP-D24.
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom.
■ MOUNTING THE UNIT ON A DIN RAIL
A)Hang the upper hook at the rear side of unit on the DIN
rail.
B)Push in the lower in keeping pressing the unit to the
DIN rail.
DIN Rail
A
B
■ REMOVING THE UNIT
A)Push down the DIN rail adaptor using a minus screwdriver.
B)Pull out the lower part of the unit.
C)Remove the upper part from the DIN rail.
C
B
Spring Loaded
DIN Rail Adaptor
A
■ AND ....
•The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
EM-2488 Rev.4
P. / 2
M5PT
TERMINAL CONNECTIONS
CHECKING
Connect the unit as in the diagram below or refer to the connection diagram on the front of the unit.
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input signal is within 5 – 120% of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
■ EXTERNAL DIMENSIONS unit: mm (inch)
7.3 (.29)
8–M3.5 SCREW
1 2
DIN RAIL
35mm wide
94 (3.70)
35.4 (1.39)
3 4
5 6
3 (.12)
7 8
25 (.98)
41 (1.61)
[3.3 (.13)]
• When mounting, no extra space is needed between units.
■ CONNECTION DIAGRAM
SOURCE
FUSE U VT u
V
LOAD
v
(V)
(±)
3
5 +
4
6 –
7 U(+)
8 V(–)
OUTPUT
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 10% input and adjust output to 10%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 10% input.
4) When ZERO value is changed, repeat the above procedure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
POWER
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 10%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUSTMENT PROCEDURE” explained earlier.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship
during the 36-month period following the date that such product was originally purchased if such product has been used under
normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this
warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is
defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the
defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES
OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 66598510, E-mail: [email protected]
EM-2488 Rev.4
P. / 2
Hang the upper hook at the rear side of the unit on the DIN rail and push in the lower in keeping pressing the unit to the DIN rail.
What is the power input rating for the M5 PT?
The power input rating is 85 – 264V AC or 24V DC. For the 85 – 264V AC rating, the operational range is 85 – 264V, 47 – 66 Hz, with an approximate power consumption of 2 – 3VA. For the 24V DC rating, the operational range is 24V ±10% with an approximate power consumption of 2W.
How do I calibrate the output signal of the M5 PT?
Apply 10% input and adjust the output to 10% to set the zero point. Then apply 100% input and adjust the output to 100% to set the span. Check the zero adjustment again with 10% input. If the zero value changes, repeat the process.