Do-more T1H PLC Technical Specs

Do-more T1H PLC Technical Specs
Prices as of April 15, 2015. Check Web site for most current prices.
Do-more T1H Series PLC System
Specifications
General Specifications
General Specifications
Ambient Operating Temperature
32°F to 131°F (0°C to 55°C)
Storage Temperature
-4°F to 158°F (-20°C to 70°C)
Ambient Humidity
5% to 95% (Non-condensing)
Atmosphere
No corrosive gases. The level of environmental
pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand (Dielectric)
1500 VAC, 1 minute
Insulation Resistance
500 VDC, 10 Mq
Noise Immunity
NEMA ICS3-304
Impulse noise 1µs, 1000 V
FCC class A
RFI (144 MHz, 430 MHz 10 W, 10 cm)
Agency Approvals
UL E185989, CE, FCC class A, NEC Class 1 Division 2
Book 1 (14.3)
eDT-14
Do-more T1H PLCs
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
Do-more T1H Series PLC System
Specifications
Module Placement and
I/O Usage Tables
There are no I/O module placement
restrictions with the Do-more T1H Series
PLC family. In general, any mix of up to 16
analog and discrete I/O module types can
be used in any local or Ethernet I/O base.
Specialty modules can also be used in any
local or Ethernet I/O base. Reference the
Module Placement Restrictions table to
the right for the Do-more T1H Series PLC.
Company
Information
Control Systems
Overview
CLICK PLC
Module Placement Restrictions
Do-More
PLCs
Module/Unit
Local CPU Base
Ethernet I/O Base
CPUs
Discrete I/O
Analog I/O
CPU slot only
3
3
3
3
Do-More T1H
PLC
CPU slot only
DirectLOGIC
PLCs Overview
3
DirectLOGIC
DL05/06
Base Controller
T1H-EBC100
Specialty Module
T1H-CTRIO
3
Do-More H2
PLC
DirectLOGIC
DL105
Analog I/O in the Ethernet I/O
bases
When using an analog module in an
Ethernet I/O base, the analog update
time to the CPU will be asynchronous to
the scan time. Critical analog I/O should
be located in the local base.
I/O point usage
The table to the right indicates the number
of I/O points consumed by each module.
These X (discrete input), Y (discrete
output), WX (analog input) and WY
(analog output) addresses are automatically assigned by Do-more Designer.
DirectLOGIC
DL205
DirectLOGIC
DL305
I/O Module Point Usage
DC INPUT
T1K-08ND3
T1K-16ND3
8X
16 X
RELAY OUTPUT
SPECIALTY MODULES
T1K-08TR
T1K-16TR
T1K-08TRS
T1H-CTRIO
8Y
16 Y
8Y
None
Productivity
Controller
Productivity
3000
AC INPUT
T1K-08NA-1
T1K-16NA-1
8X
16 X
DC OUTPUT
T1K-08TD1
T1K-16TD1
T1K-08TD2-1
T1K-16TD2-1
T1H-08TDS
AC OUTPUT
T1K-08TA
T1K-16TA
T1K-08TAS
Universal
Field I/O
ANALOG
8Y
16 Y
8Y
16 Y
8Y
8Y
16 Y
8Y
DirectLOGIC
DL405
T1F-08AD-1
T1F-08AD-2
T1F-16AD-1
T1F-16AD-2
T1F-16RTD
T1F-14THM
T1F-08DA-1
T1F-08DA-2
T1F-16DA-1
T1F-16DA-2
T1F-8AD4DA-1
T1F-8AD4DA-2
Software
8 X, 8 WX
8 X, 8 WX
16 X, 16 WX
16 X, 16 WX
16 X, 16 WX
16 X, 16 WX
8 Y, 8 WY
8 Y, 8 WY
8 Y, 16 WY
8 Y, 16 WY
8 X, 8 WX/8 Y, 4 WY
8 X, 8 WX/8 Y, 4 WY
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
Book 1 (14.3)
www.automationdirect.com/do-more-plcs
Do-more T1H PLCs
eDT-15
Prices as of April 15, 2015. Check Web site for most current prices.
Do-more T1H Series PLC System
Specifications
Power supplies
Power requirements
The T1H Series PLC offers two power
supply options: AC or DC. More than one
power supply can be installed in a T1H
series PLC system with each power supply
positioned to the left of the modules they
supply power to.
Module
5VDC 24VDC
CPU Modules
DC Output Modules
$111.00
200
0
T1F-08AD-1
75
­50*
T1H-DM1E
275
0
T1K-08TD1
100
200*
T1F-08AD-2
75
50*
T1K-16TD1
200
400*
T1F-16AD-1
75
50*
T1K-08TD2-1
100
0
T1F-16AD-2
75
50*
T1K-16TD2-1
200
0
T1F-14THM
60
70*
T1F-16RTD
150
0
300
0
T1K-08ND3
35
0
AC Output Modules
T1K-16ND3
70
0
T1K-08TA
250
0
Analog Output Modules
T1K-16TA
450
0
T1F-08DA-1
75
150*
300
0
T1F-08DA-2
75
150*
AC Input Modules
T1K-08NA-1
35
0
T1K-08TAS
T1K-16NA-1
70
0
Relay Output Modules
75
150*
350
0
T1F-16DA-2
75
150*
T1K-16TR
700
0
Combination Analog Modules
T1K-08TRS
400
0
T1F-8AD4DA-1
75
60*
T1F-8AD4DA-2
75
70*
Specialty Module
T1K-01DC
T1K-01AC
T1F-16DA-1
T1K-08TR
T1H-CTRIO
Calculating the power budget
Input Frequency
50/60 Hz
N/A
Maximum Power
50 VA
30 W
To calculate the power budget, read the
available power (current rating) from the
Power Supply Specifications table and
subtract the power consumed by each
module to the right of the power supply.
Do not include modules to the right of an
additional power supply.
10 A
Insulation
Resistance
> 10 Mq @ 500 VDC
Voltage Withstand
1 min. @ 1500 VAC between
primary, secondary and field
ground
Voltage
5.25 VDC
5.25 VDC
mA max
5VDC Current Rating 2000
(see the table 2000 mA max
PWR
below)
Ripple
5% max.
5% max.
Voltage
24 VDC
N/A
mA max.
24VDC Current Rating 500
(see the table N/A
PWR
below)
Ripple
10% max.
400
0
* Use either internal or external source
for 24VDC
Input Voltage Range 110/220 VAC 12/24 VDC
Max. Inrush Current 20 A
Analog Input Modules
T1H-08TDS
Power supply
specifications
Power Supply
Specifications
5VDC 24VDC
0
DC Input Modules
$116.00
Module
250
T1H-EBC100
T1K-01DC
5VDC 24VDC
T1H-DM1
Interface Module
T1K-01AC
Module
Adding additional
power supplies
Each power supply furnishes power only to
the modules to its right. Inserting a second
power supply closes the power loop for
the power supply to the left, while also
powering the modules to its right. Perform
a power budget calculation for each
power supply in the system.
* Use either internal or external source
for 24VDC
Power Budget Example
Module
5VDC
24VDC
T1K-01AC
+2000 mA
+300 mA
T1H-DM1E
-275 mA
-0 mA
T1K-16ND3
-70 mA
-0 mA
T1K-16TD2-1
-200 mA
-0 mA
T1F-08AD-1
-75 mA
-50 mA
Remaining
+1380 mA
+250 mA
Accessories available for
Terminator I/O are listed in the
Terminator Field I/O section of the
Price List
N/A
Fuse 1 (primary), not replaceable
MVSTBW
MVSTBW
Replacement
2.5/4-ST-5.08 2.5/6-ST-5.08
Terminal Block
BK
BK
(Phoenix Contact)
T1H-DM1E
TERM
RUN
I/O
ERR
RUN
STOP
USB
TX
RX
USB
PGM
PORT
T1K-01AC Current Output
5VDC PWR
2000 mA
1500 mA
24VDC PWR
300 mA
500 mA
Note: 500 mA @ 24VDC can be achieved by lowering the
5 VDC from 2000 mA to 1500 mA.
Book 1 (14.3)
eDT-16
Do-more T1H PLCs
This power supply powers the CPU module and the next two
I/O modules
This power supply powers these three I/O
modules
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
CPU Modules
Company
Information
Control Systems
Overview
CLICK PLC
Specifications
Feature
Total Memory (bytes)
Ladder Memory (instruction words)
V-Memory (words)
Non-volatile V Memory (words)
D-memory (DWORDs)
Non-volatile D Memory (DWORDs)
R-memory (REAL DWORDs)
Non-volatile R Memory (REAL DWORDs)
Boolean execution
Stage Programming
T1H-DM1
$359.00
262,144 bytes
65,536 instruction words
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
Configurable up to 65536 (4096 default)
50 uSec
Yes
128 per Program code-block; number of code-blocks configurable to
memory limit
Handheld Programmer
Programming Software for Windows
No
FREE Do-more Designer version 1.2 or newer
USB, RS-232,
USB, RS-232
Ethernet (10/100 Base-T)
Flash ROM
X, Y, each configurable up to 65536 (2048 default); WX, WY (analog
in/out) each configurable up to 65536 (256 default)
Built-In communications ports
Program Memory
Total I/O points available
16
256
131,072
32,768
32,768
Configurable up to 65536 (2048 default)
ASCII
PID Loop Control, Built In
Time of Day Clock/Calendar
Run Time Edits
Supports True Force
Internal Diagnostics
Password security
System error log
User error log
Battery backup
>170
1024
512
Configurable up to 65536 (256 default)
Configurable up to 65536 (256 default)
8
Configurable up to 65536 (32 default)
Configurable up to memory limit (192 default)
Yes, configurable up to memory limit, default 1024 input bits, 1024
coil bits, 2048 input registers, 2048 holding registers
Up to memory limit, default 512 X, 512 Y, 512 C, 2048 V
No
No
Program and Task code-blocks, up to memory limit
Yes, up to memory limit
Yes
FOR/NEXT, WHILE/WEND, REPEAT/UNTIL loops
>60 operators and functions: Integer, Floating Point, Trigonometric,
Statistical, Logical, Bitwise, Timing
Yes, IN/OUT, Serial, Ethernet TCP and UDP; 11 output script commands
Yes, configurable to memory limit (over 2,000)
Yes
Yes
Yes
Yes
Multi-user, credentialed, session-based security
Yes
Yes
Yes (Battery included)
Book 1 (14.3)
www.automationdirect.com/do-more-plcs
Do-more T1H PLCs
DirectLOGIC
PLCs Overview
DirectLOGIC
DL105
DirectLOGIC
DL205
DirectLOGIC
DL305
DirectLOGIC
DL405
Universal
Field I/O
8/16
Control relays
Special relays (system defined)
Special registers (system defined)
Timers
Counters
System Date/Time structures
User Date/Time structures
ASCII String/Byte buffer structures
Math
Do-More T1H
PLC
Productivity
3000
16
>160
DL Classic Client memory
Immediate I/O
Interrupt input (hardware / timed)
Subroutines
Drum Timers
Table Instructions
Loops
Do-More H2
PLC
Productivity
Controller
Number of instructions available
Modbus Client memory
Do-More
PLCs
DirectLOGIC
DL05/06
Number of Stages
Max Number of Local I/O Modules
Local I/O points available
Ethernet I/O Discrete points
Ethernet I/O Analog I/O Channels
Max Number of Ethernet slaves per PLC
I/O points on Ethernet I/O
Discrete I/O Module Point Density
T1H-DM1E
$459.00
T1H-DM1E
T1H-DM1
eDT-17
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Other HMI
Communications
Appendix
Book 1
Terms and
Conditions
Prices as of April 15, 2015. Check Web site for most current prices.
CPU Modules
T1H-DM1
T1H-DM1E
USB 2.0 Port (Type B)
- Programming
RS 232 Serial Port (RJ12)
- Programming
- Multipurpose Serial
Communications Port
10/100 MB Ethernet Port (RJ45)
- Programming
- Modbus TCP Client and Server
- Ethernet I/O Master
ACTIVITY
Y
RS232
SERIAL PORT
RS232
SERIAL PORT
)
er
er
100
MBIT
10/100 BASE-T
ETHERNET PORT
LED
Status Indicators
T1H-DM1E
LED Indicators
Indicator
RUN
ROM
ACTIVITY
Y
100
MBIT
ERR
USB
RS232
SERIAL PORT
10/100 BASE-T
ETHERNET PORT
TX
RX
ACTIVITY
100 MBIT
Status
Description
Green
CPU is in RUN Mode
Yellow
Forces are Active
Yellow
Red
Yellow
CPU is updating Non-volatile Memory
CPU Fatal Error
Low Battery
Green
Status OK (good)
Green
USB Receive Activity
Yellow
USB Transmit Activity
Green
RS-232 Transmit Activity
Green
RS-232 Receive Activity
Green
Ethernet Port Activity
Yellow
Ethernet Port communicating at 100 MBIT Rate
PLC Mode Switch
T1H-DM1E
Mode Switch Functions
Mode Switch Position
CPU Action
RUN (Run Program)
CPU is forced into RUN Mode if no errors are encountered.
TERM (Terminal)
RUN, PROGRAM and DEBUG modes are available. In this
switch position, the mode of operation can be changed
through the Programming Software.
STOP (Stop Program)
CPU is forced into STOP Mode.
Book 1 (14.3)
eDT-18
Do-more T1H PLCs
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
CPU Modules
Company
Information
Control Systems
Overview
CLICK PLC
Communication Ports
Do-More
PLCs
USB Port
Do-More H2
PLC
Used exclusively for programming and monitoring via a PC running
Do-more Designer.
Do-More T1H
PLC
USB Port Specifications
DirectLOGIC
PLCs Overview
Description
Standard USB 2.0 Slave input for programming and online
monitoring, with built-in surge protection. Not compatible
with older full speed USB devices.
DirectLOGIC
DL05/06
Cables
USB Type A to USB Type B:
DirectLOGIC
DL105
(ADC part #)
USB-CBL-AB3 (3 ft.)
DirectLOGIC
DL205
USB-CBL-AB6 (6 ft.)
USB-CBL-AB10 (10 ft.)
USB-CBL-AB15 (15 ft.)
DirectLOGIC
DL305
Pin
DirectLOGIC
DL405
Description
1
2
3
4
5V
Bus Voltage Sense
D-
Data -
D+
Data +
0V
Ground
Productivity
Controller
Productivity
3000
Universal
Field I/O
RS-232 Port
RJ-12 style connector used for:
• Connection to a PC running Do-more
Designer
• Modbus RTU Master connections
• Modbus RTU Slave connections
• ASCII Incoming and Outgoing
communications
• Custom Protocol Incoming and Outgoing
communications
Software
RS-232 Port Specifications
Description
Non-isolated, full duplex RS-232 DTE port used for programming, online
monitoring or can connect the CPU as a Modbus RTU or ASCII master or
slave to a peripheral device. Includes ESD and built-in surge protection.
1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Baud Rates
+5V Cable Power
Source
Maximum Output
Load (TXD/RTS)
Minimum Output
Voltage Swing
Output Short Circuit
Protection
Cable Options
220 mA maximum at 5V, +/- 5%. Reverse polarity and overload protected.
(ADC part #)
USB-RS232 with D2-DSCBL
3 KV, 1,000 pf
+/-5V
Other HMI
+/-15 mA
Communications
D2-DSCBL
Appendix
Book 1
Terms and
Conditions
FA-ISOCON for converting RS-232 to isolated RS-422/485
EA-MG-PGM-CBL
1
2
3
4
5
6
C-More Micro
HMI
ViewMarq
Industrial
Marquees
FA-CABKIT
Pin
C-More
HMI
Description
0V
Power (-) connection (GND)
5V
Power (+) connection (220 mA max.)
RXD
Receive Data (RS-232)
TXD
Transmit Data (RS-232)
RTS
Request to Send (RS-232)
CTS
Clear to Send (RS-232)
For a list of protocols supported by each port, please refer to the Communications topic
of the Do-more T1H Series PLC Overview in this section.
Book 1 (14.3)
www.automationdirect.com/do-more-plcs
Do-more T1H PLCs
eDT-19
Prices as of April 15, 2015. Check Web site for most current prices.
CPU Modules
Ethernet Port
RJ-45 style connector used for:
• Connection to a PC running Do-more
Designer
• Modbus TCP Client connections (Modbus
requests sent from the CPU)
• Modbus TCP Server connections (Modbus
requests received by the CPU)
• Ethernet I/O Master
Ethernet Port Specifications
Description
Standard transformer isolated Ethernet port with built-in surge
protection for programming, online monitoring, Modbus/TCP
client/server connections (fixed IP or DHCP) and Ethernet
I/O capabilities.
Transfer Rate
10/100 Mbps
Cables
Use a Patch (Point to Point) cable when a switch or hub is
used.
Use a Crossover cable when a switch or hub is not used.
8
1
For a list of protocols supported by each
port, please refer to the Communications
topic of the Do-more T1H Series PLC
Overview in this section.
Battery Specifications
DIP Switch Specifications
A battery is included with the Do-more
CPU and is used to retain the Time and
Date along with any Tagname values that
are set up as retentive. It is recommended
that the battery be replaced once every
five years or when one year of cumulative
OFF time has been exceeded.
The T1H Series Do-more CPU also comes
equipped with a set of eight DIP switches
(0-7) that can be used to affect the boot
sequence of the controller.
The default position for all of the
DIP switches is OFF.
At least two hours is allowed to change
out a battery without loss of data.
T1H-DM1 and T1H-DM1E
Battery Replacement
Part # D0-MC-BAT
7 6 5 4 3 2 1 0
ON
Battery
Coin type, 3.0V
D0-MC-BAT Lithium battery,
number CR2032
$3.00
Book 1 (14.3)
eDT-20
Do-more T1H PLCs
1-800-633-0405
Prices as of April 15, 2015. Check Web site for most current prices.
CPU Modules
Company
Information
Control Systems
Overview
CLICK PLC
Ethernet I/O
The T1H-DM1E CPU’s built-in Ethernet
port can be configured as an Ethernet I/O
master. The Ethernet I/O feature allows
expansion beyond the local base to
slave I/O using the onboard high-speed
Ethernet link. The onboard Ethernet port
can support up to 16 slave devices. The
slave I/O modules supported are:
• H2-EBC100
• T1H-EBC100 (Terminator I/O)
• GS-EDRV100 (GS Drives)
Do-More
PLCs
The Ethernet I/O network uses Category
5 UTP cables for cable runs up to 100
meters (328 ft.) with extended distances
achieved through Ethernet switches.
Do-More H2
PLC
Do-More T1H
PLC
It is highly recommended that a dedicated network be used with the Ethernet
I/O feature. Ethernet I/O networks and
ECOM/office networks should be isolated
from one another to prevent network
delays.
DirectLOGIC
PLCs Overview
DirectLOGIC
DL05/06
DirectLOGIC
DL105
Stride
Ethernet
Switch
DirectLOGIC
DL205
DirectLOGIC
DL305
Do-more T1H-DM1E CPU
DirectLOGIC
DL405
T1H-DM1E
TERM
RUN
I/O
ERR
RUN
STOP
USB
TX
RX
USB
PGM
PORT
Productivity
Controller
Productivity
3000
DirectLOGIC
DL205 I/O with
H2-EBC100
Module
C-more Operator
Interface
Universal
Field I/O
Software
C-More
HMI
GS-EDRV100
C-More Micro
HMI
Terminator I/O
with T1H-EBC100
Module
ViewMarq
Industrial
Marquees
Other HMI
Communications
GS
Drive
Appendix
Book 1
Terms and
Conditions
Book 1 (14.3)
www.automationdirect.com/do-more-plcs
Do-more T1H PLCs
eDT-21
Prices as of April 15, 2015. Check Web site for most current prices.
Do-more T1H Series PLC Overview
Company
Information
Control Systems
Overview
Do-more T1H Series PLC Hardware User Manual (T1H-DM-M)
CLICK PLC
Do-more T1H Series PLC Hardware User Manual is available as a free download from Automationdirect.
com. A hard copy is also available for purchase.
Do-More
PLCs
Do-More H2
PLC
Do-more Designer (Part No. DM-PGMSW)
Do-More T1H
PLC
Do-more Designer is the full-featured programming software for the
Do-more PLC series. Do-more Designer is a free download from
Automationdirect.com. A CD-ROM version is also available for
purchase for $10.00.
DirectLOGIC
PLCs Overview
1.2
DirectLOGIC
DL05/06
DirectLOGIC
DL105
DirectLOGIC
DL205
Start Page
DirectLOGIC
DL305
When the software is started, the Start Page is
displayed. This page contains a Launchpad with
Projects, Applications and Links windows. It also
contains shortcuts to important help file topics, and
you can start the Do-more Simulator from this page.
DirectLOGIC
DL405
Productivity
Controller
Productivity
3000
Universal
Field I/O
Launchpad
Software
C-More
HMI
C-More Micro
HMI
ViewMarq
Industrial
Marquees
Do-more
Simulator
Help File
Shortcuts
Other HMI
Communications
Main Programming Window
Project
Toolbar
Project
Browser
The Main Programming Window is displayed
when a new project is started or an existing
project is opened. It is divided into Menus,
Toolbars, and Windows that work together to
make project development simple.
Ladder
View
Ladder
Palette
Bar
Book 1 (14.3)
www.automationdirect.com/do-more-plcs
Do-more T1H PLCs
eDT-9
Appendix
Book 1
Terms and
Conditions