IC693MDL740

IC693MDL740
This Datasheet is for the
IC693MDL740
12/24 Volt DC Positive Logic Output - 0.5 Amp, 16 Point
http://www.cimtecautomation.com/parts/p-14668-ic693mdl740.aspx
Provides the wiring diagrams and installation guidelines for this GE Series 90-30
module.
For further information, please contact Qualitrol Technical Support at
1-800-784-9385
[email protected]
7
12/24 Volt DC Positive Logic Output - 0.5 Amp, 16 Point
IC693MDL740
The 12/24 volt DC Positive Logic 0.5 Amp Output module for the Series 90-30 Programmable
Logic Controller provides 16 output points in two groups of eight with a common power output
terminal for each group. This output module is designed to have positive logic characteristics
in that it sources current to the loads from the user common or positive power bus. The output
device is connected between the negative power bus and the module output. The output
characteristics are compatible with a wide range of user-supplied load devices, such as: motor
starters, solenoids, and indicators. Power to operate the field devices must be supplied by the
user.
LED indicators which provide the ON/OFF status of each point are located at the top of the
module. This LED block has two horizontal rows with eight green LEDs in each row with the
top row labeled A1 through 8 (points 1 through 8) and the bottom row labeled B1 through 8
(points 9 through 16). An insert goes between the inside and outside surface of the hinged door.
The surface towards the inside of the module (when the hinged door is closed) has circuit
wiring information, and circuit identification information can be recorded on the outside
surface. The outside left edge of the insert is color-coded blue to indicate a low-voltage
module. There are no fuses on this module.
This module can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC
system.
Table 7-12. Specifications for IC693MDL740
Rated Voltage
Output Voltage Range
12/24 volts DC
12 to 24 volts DC (+20%, –15%)
Outputs per Module
Isolation
16 (two groups of eight outputs each)
1500 volts between field side and logic side
500 volts between groups
Output Current
0.5 amps maximum per point
2 amps maximum per common
Output Characteristics
Inrush Current
Output Voltage Drop
Off-state Leakage
On Response Time
Off Response Time
4.78 amps for 10 ms
1 volt maximum
1 mA maximum
2 ms maximum
2 ms maximum
Power Consumption
110 mA (all outputs on) from 5 volt bus on backplane
Refer to Appendix B for product standards and general specifications.
7-24
Series 90-30 PLC I/O Module Specifications – July 2000
GFK-0898F
Discrete Output Modules
7
IC693MDL740 Output Module Field Wiring Information
The following figure provides wiring information for connecting user supplied load devices
and power source to the 12/24 volt DC positive logic - 0.5 amp output module.
a43098
MODULE CIRCUITRY
TERMINALS
FIELD WIRING
+
1
2
A1
3
A2
4
A3
6
A5
8
A7
5
A4
7
1µ f
A6
9
A8
10
OTHER
CIRCUITS
+
11
12
B1
14
B3
16
B5
18
B7
13
B2
15
B4
17
B6
19
B8
20
Figure 7-22. IC693MDL740 Output Module Field Wiring
a45049
4
TOTAL
MODULE
LOAD
CURRENT
(AMPS)
3
2
1
10°C
20°C 30°C 40°C 50°C 60°C
AMBIENT TEMPERATURE (°C)
Figure 7-23. Load Current vs. Temperature for IC693MDL740