System Sensor B501 Plug-in Detector Base Installation and Maintenance Instructions

System Sensor B501 Plug-in Detector Base Installation and Maintenance Instructions

Below you will find brief information for Plug-in Detector Base B501. The B501 is a plug-in detector base intended for use in an intelligent system with screw terminals provided for power (+) and (–), and remote annunciator connections. The communication takes place over the power (+) and (–) lines. This base also includes an optional tamperproof feature that when activated prevents removal of the detector without the use of a tool. This device is UL listed and compatible with control panels and remote annunciators.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

System Sensor B501 Plug-in Detector Base Installation Guide | Manualzz
I56-0357-008R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
B501 Plug-in Detector Base
Specifications
Diameter:
Mounting:
4.0 inches (10.2cm)
50mm, 60mm, and 70mm centers
Electrical Ratings – includes base and detector
Voltage Range:
15 to 32 VDC
Standby Current (Nominal):
150µA at 24 VDC
Power-Up Surge at Max. Rated Voltage: 1.5mA–Sec.
LED Current (Nominal):
6mA at 24 VDC
Operating Temperature Range:
Refer to applicable sensor Operating Temperature Range
using the Base/Sensor Cross Reference Chart at http:\\www.systemsensor.com
For signal wiring (the wiring between interconnected detectors and modules),
it is recommended that the wiring be no smaller than 18 gauge (1.0 square
mm). Wire sizes up to 12 gauge wire (2.5 square mm) may be used with the
base. For best system performance, the power (+) and (–) loop wires should
be twisted pair or shielded cable installed in separate grounded conduit to
protect the loop from extraneous electrical interference. If a cable shield is provided, the shield connection to and from the base must be continuous by using wire nuts, crimping, or soldering as appropriate for a reliable connection.
Before Installing
Please thoroughly read the System Sensor manual, System Smoke Detectors
Application Guide, which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies of this manual are
available at no charge from System Sensor.
General Description
The B501 is a plug in detector base intended for use in an intelligent system with
screw terminals provided for power (+) and (–), and remote annunciator connections. The communication takes place over the power (+) and (–) lines.
Wire Connections are made by simply stripping about 3⁄8 of an inch of insulation from the end of the wire (use strip gauge molded in base), sliding the
bare end of the wire under the clamping plate and tightening the clamping
plate screw. Do not loop the wire under the clamping plate.
Base Terminals
No. Function
1 Power (–), Remote Annunciator (–)
2 Power (+)
3 Remote Annunciator (+)
Figure 1. Terminal layout:
The zone wiring of the detector base should be checked before the detector
heads are installed in them. The wiring should be checked for continuity, polarity in the base, and dielectric tests.
The base contains a label to write the zone, address, and type of detector to
be installed at that location. This information is used to set the address of the
detector head that will later be plugged into the base and to verify the type
required for that location.
TAMPER PROOF
TAB
BASE
TERMINALS
Figure 2. Typical wiring diagram for 2-wire loop:
UL LISTED COMPATIBLE
CONTROL PANEL
REMOTE
ANNUNCIATOR
+
-
2(+)
1(–)
3
(+)
3
2
3
2
1
3
1
2
1
(–)
(–)
(+)
CLASS A OPTIONAL WIRING
SHE
C0133-00
ILD
Tamperproof Feature
NOTE: Do Not use the tamper-resistant capability if the XR2 or XR2B Removal
Tool will be used. This detector base also includes an optional tamperproof
feature that when activated prevents removal of the detector without the use
of a tool.
To activate this feature, simply break off the tab on the detector base shown in
Figure 3A, and install the detector. To remove the detector from the base once
the tamperproof feature has been activated, place a small-bladed screwdriver
into the small hole on the side of the base and push the plastic lever away
from the detector head (see Figure 3B). This will allow the detector to be rotated counterclockwise for removal.
C0131-00
Wiring Installation Guidelines (See Figure 2)
All wiring must be installed in compliance with the National Electrical Code
and the local authority having jurisdiction. Proper wire gauges should be
used. The conductors used to connect the smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes.
Improper connections can prevent a system form responding properly in the
event of a fire.
D550-02-00
CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
The tamperproof feature may be defeated by breaking and removing the plastic lever from the base, however this prevents ever using the feature again.
1
I56-0357-008R
E.
Remote Annunciator (RA400)
The remote annunciator is connected between terminals 1 and 3 using the
spade lug terminal packed with the remote annunciator. The spade lug terminal is connected to the base terminal as shown in Figure 4.
It is not acceptable to have three stripped wires under the same wiring terminal unless they are separated by a washer or equivalent means. The spade lug
supplied with the model RA400 is considered an equivalent means. See Figure
2 for proper installation.
Figure 3A. Activating tamperproof feature:
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE.
SCREWDRIVER TO PRESS PLASTIC LEVER
IN DIRECTION OF ARROW
C0132-00
Figure 3B. Removing detector head from base:
SCREWDRIVER TO PRESS PLASTIC LEVER
IN DIRECTION OF ARROW
C0132-00
Figure 4. Connection to remote annunciator terminal:
STRIPPED WIRE
WIRE WITH SPADE LUG
C0116-00
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
System Sensor warrants its enclosed smoke detector base to be free from defects in mainclude a note describing the malfunction and suspected cause of failure. The Company
terials and workmanship under normal use and service for a period of three years from
shall not be obligated to repair or replace units which are found to be defective because
date of manufacture. System Sensor makes no other express warranty for this smoke
of damage, unreasonable use, modifications, or alterations occurring after the date of
detector base. No agent, representative, dealer, or employee of the Company has the aumanufacture. In no case shall the Company be liable for any consequential or incidental
thority to increase or alter the obligations or limitations of this Warranty. The Company’s
damages for breach of this or any other Warranty, expressed or implied whatsoever, even
obligation of this Warranty shall be limited to the repair or replacement of any part of the
if the loss or damage is caused by the Company’s negligence or fault. Some states do not
smoke detector base which is found to be defective in materials or workmanship under
allow the exclusion or limitation of incidental or consequential damages, so the above
normal use and service during the three year period commencing with the date of manulimitation or exclusion may not apply to you. This Warranty gives you specific legal
facture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a
rights, and you may also have other rights which vary from state to state.
Return Authorization number, send defective units postage prepaid to: System Sensor,
D550-02-00
2
I56-0357-008R
©2008 System Sensor

advertisement

Key Features

  • Plug-in detector base
  • Intelligent system compatible
  • Screw terminals for power and remote annunciator connections
  • Communication over power lines
  • Optional tamperproof feature
  • UL listed and compatible

Frequently Answers and Questions

What is the purpose of the tamperproof feature?
The tamperproof feature prevents removal of the detector without the use of a tool. To activate this feature, simply break off the tab on the detector base and install the detector. To remove the detector from the base once the tamperproof feature has been activated, place a small-bladed screwdriver into the small hole on the side of the base and push the plastic lever away from the detector head.
How do I connect the remote annunciator?
The remote annunciator is connected between terminals 1 and 3 using the spade lug terminal packed with the remote annunciator. The spade lug terminal is connected to the base terminal as shown in Figure 4.
What size wiring should I use for the detector base?
For signal wiring (the wiring between interconnected detectors and modules), it is recommended that the wiring be no smaller than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge wire (2.5 square mm) may be used with the base. For best system performance, the power (+) and (–) loop wires should be twisted pair or shielded cable installed in separate grounded conduit to protect the loop from extraneous electrical interference.