advertisement
INSTALLATION INSTRUCTIONS
COMMERCIAL ROOM VENTILATORS
WITH EXHAUST
MODEL
CHCRV-3
For Use with
Bard C**H Series 2 & 2½ Ton
2-Stage Wall Mount Heat Pumps
NOTE: CHCRV-3 Models must be installed with TCURB –
No Exceptions!
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead just as planned.
Manual : 2100-598
Supersedes: NEW
File: Volume III Tab 19
Date: 08-08-13
Manual 2100-598
Page 1 of 12
CONTENTS
General
General Information .................................................. 3
Unpacking ................................................................. 3
Description ................................................................ 3
Models ................................................................. 3
Commercial Room Ventilator –
C**H Series (Features) ............................................. 3
Installation
Basic Installation ..................................................4 - 5
CO
2
Control ............................................................... 6
Blade Adjustment for Desired Ventilation Air ............. 9
Sequence of Operation ...................................... 11-12
Figures
Figure 1 Removal of Exterior Panels & Air Filter .... 4
Figure 2 Condenser Exhaust Plate w/Screen ........ 5
Figure 3 Install Ventilator ........................................ 6
Figure 3A Vent Control Location ............................... 7
Figure 4 CO
2
Sensor Default Settings (8403-067) .. 8
Figure 5 (C**H) Call for Vent. with or without
Compressor Operation ........................... 11
Figure 6 (C**H) Call for Compressor or Fan Only ... with Ventilation Off ................................. 12
Graphs
Graph 1 C24H Vent Airflow .................................. 10
Graph 2 C30H Vent Airflow .................................. 10
Manual 2100-598
Page 2 of 12
BARD MANUFACTURING COMPANY, INC.
BRYAN, OHIO USA 43506
GENERAL
GENERAL INFORMATION
The ventilator should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the ventilator package. They are not intended as a step by step procedure with which the mechanically inclined owner can install the package.
The ventilator housing is shipped in one carton which contains the electrical harness, miscellaneous hardware and installation instructions.
UNPACKING
Upon receipt of the equipment be sure to compare the model number found on the shipping label with the accessory identification information on the ordering and shipping document to verify that the correct accessory has been shipped.
Inspect the carton housing of each ventilator as it is received, and before signing the freight bill, verify that all items have been received and that there is no visible damage. Note any shortages or damage on all copies of the freight bill. The receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt.
DESCRIPTION
The CHCRV-3 ventilator is designed to be used with
Bard C24H1-* and C30H1-* Series Wall Mount heat pumps.
C24H1-* & C30H1-* MODELS:
When installed in the above-listed models, the CRV provides built in exhaust provisions. When the damper blade opens to bring fresh air in, the damper also opens an exhaust relief. The exhaust air will flow into the condenser section of the unit. The condenser fan will help draw exhaust air out when it is operating with compressor in cooling or heat pump mode.
COMMERCIAL ROOM VENTILATOR –
C**H SERIES
FEATURES
• One piece construction – easy to install with no
mechanical linkage adjustment required.
• Exhaust air damper – built in with positive closed
position. Provides exhaust air capability to prevent
pressurization of tight buildings.
• Actuator motor – 24 volt, power open, spring return
with built in torque limiting switch.
Manual 2100-598
Page 3 of 12
INSTALLATION
BASIC INSTALLATION
1. Unpack the ventilator assembly which includes the integral ventilator with attached electrical harness and miscellaneous hardware.
2. Remove and save the existing exterior blower access, filter access and service access panels on the Bard wall mount unit. (See Figure 1.)
3. Remove and save existing unit air filter and screws from front center grille. (See Figure 1.)
WARNING
Open and lock unit disconnect switch before installing this accessory to prevent injury or death due to electrical shock or contact with moving parts. Turn thermostat to off.
MODEL
CHCRV-3
FOR USE WITH
FOLLOWING UNITS
C24H1
C30H1
4. Remove the filter brackets and save. Install return fill on CRV with two (2) screws provided (See
Figure 2.)
5. Install ventilator by inserting the ventilator into the unit to the far left side clearing the right filter bracket. Once the ventilator is fully inserted, slide the ventilator to the right or until right hole in CRV lines up with hole in condenser partition. (See
Figure 3.)
IMPORTANT: Position front lip of ventilator on top of front grille & condenser partition.
(See Figure 3 inset.) This is important to ensure proper drainage of any water entering damper assembly.
FIGURE 1
REMOVAL OF EXTERIOR PANELS AND AIR FILTER
BLOWER ACCESS PANEL
FILTER ACCESS PANEL
VENT OPTION PANEL
FILTER
SCREW
Manual 2100-598
Page 4 of 12
REMOVE AND
DISCARD RETURN
AIR FLANGE
MIS-3304
Once secure, remove the tape holding the rear extension and flip down. Push the locking plates down until screw locks into channel. Secure the rear blade bracket to the front blade with the screws provided
(See Figure 2).
6. Open control panel to gain access to unit low voltage terminal block.
7. Route four (4) wires (pink, purple/white, black/ white and orange) from CRV assembly down to and through 7/8" bushing on bottom left side of control panel and into low voltage terminal block section (See Figure 3).
8. Install the vent control board assembly in the upper left corner in unit control panel (See Figure
3A for reference on vent control location). Insert
7/8" bushing into hole on lower right side of low voltage terminal block enclosure. Route the red, yellow, purple and blue/white wires {pre-attached} to the vent control board into the low voltage terminal block section through this opening.
Reference Wiring Diagram 4056-221B (enclosed).
Connect wires as follows to 24V terminal block:
Yellow to Y
Purple to Y1
Blue/White to DH
Red to R
Purple/White to P1
Pink to P
Black/White to C with short jumper to the minus (-) terminal
Orange: If optional CO
2 connect to OCC. If no CO
sensor is used,
2
sensor is used, make no connection and tape off.
10. Close control panel cover
11. Replace the filter brackets, filter and four (4) screws in condenser grille.
12. Reinstall the blower access panel at top of unit and secure with sheet metal screws.
13. Ventilator Checkout
A. Resupply power to unit.
B. Energize the evaporator blower by switching
thermostat to the manual fan position with heat/ cool in OFF position.
C. Ventilator should open to the position set by
R#1 Potentiometer on vent control. Observe damper blade operation throughout travel to assure free, unobstructed movement.
D. De-energize evaporator blower. Damper blade should close.
E. This completes ventilator checkout.
9. On the 24V terminal block, connect the forked terminal of the orange wire to O1, and the forked terminal of black/white wire to C. Route the remaining portion of orange and black/white wires with ¼" quick connects along with the pink and purple/white wires out of the low voltage terminal section and up to the vent control board. Connect these wires as follows to the vent control board:
14. Replace mist eliminator. Be sure it is installed with the drain holes to the bottom.
15. Remove blank off plate or barometric fresh air damper installed on service access door. Plug four
(4) mounting holes with the plastic plugs provided with the ventilator.
16. Replace service access panel.
17. Ventilator is now ready for operation.
FIGURE 2
CONDENSER EXHAUST PLATE WITH SCREEN
SECURE RETURN FILL
WITH PROVIDED SCREWS
PUSH LOCKING PLATE
DOWN UNTIL SCREW
LOCKS INTO CHANNEL
REMOVE TAPE AND FLIP EXTENSION
DOWN FLUSH TO BOTTOM
SECURE BRACKET
TO MAIN BLADE WITH
PROVIDED SCREWS
MIS-3294
Manual 2100-598
Page 5 of 12
FIGURE 3
INSTALL VENTILATOR
Front of unit with doors removed
Blower motor leads shown as reference only
Ref. Step 7
Route the pink, purple/white, orange and black/white wires through the lower grommet and into low voltage terminal block area.
Ref. Step 5
When installing CRV position so hole in front lip is centered over hole in condenser grille to insert a self drilling screw.
Right side of
CRV in unit
Service Door
FIGURE 3 INSET
SIDE SECTION
Lip of CRV is to be between the condenser grille and service door
Front Grille
Note: Plug the (4) Ø.125 holes in the service door with canoe clips.
MIS-3302
CO
2
CONTROL
For CO
2
-based control, add a CO
2
sensor/controller
(Bard Part #8403-067) to the wall and run additional optional wires.
The CO
2 controller also must be re-configured from the standard default settings as it comes out of the box. See next two pages for complete details.
Manual 2100-598
Page 6 of 12
FIGURE 3A
VENT CONTROL LOCATION
MIS-3324
Manual 2100-598
Page 7 of 12
CO
2
FIGURE 4
SENSOR DEFAULT & FINAL SETTINGS
8403-067 CO2 CONTROLLER
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
JUMPERS MUST BE
POSITIONED AS SHOWN
FOR PROPER OPERATION
2-10V
4
4.5
5
5.5
6
2
2.5
3
3.5
8.5
9
9.5
10
6.5
7
7.5
8
AN (ppm) Damper (1)
700 FULLY CLOSED
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500 FULLY OPEN
8
9
10
11
12
6
7
14
15
16
17
Approc. Blade
Position (2)
0
1
4
5
2
3
Settings Recommended
RON
ROF
DSP
UNI
COL
COH
TOL
TOH
CAL
C
US
700
1500
Not Used
Not Used
Not Used
Not Used
Default
CT
US
0
2000
For High Altitude Installations
Used for Field Calibration
(1) Damper should be fully closed at 700 ppm, if not Potentiometer R7 can be adjusted clockwise (CW) to close it. If it is fully closed at 700 ppm or lower no adjustments required.
(2) Blade as referenced to the Blade Position Label.
MIS-3305
Manual 2100-598
Page 8 of 12
BLADE ADJUSTMENT FOR DESIRED
VENTILATOR AIR
The amount of ventilation air supplied by the commercial room ventilator is dependant on four (4) factors.
1. Return air duct static pressure drop.
2. Supply air duct static pressure drop.
3. Indoor blower motor speed.
4. Damper blade open position setting.
Refer to the graph below to determine the blade setting necessary to achieve the ventilation air required for each operating mode.
FACTORY DEFAULT SETTINGS ARE:
Potentiometer R1.
C**H
17
Potentiometer R2. 14
Potentiometer R3. 12
For more accurate adjustment, use a flowhood over the intake opening to measure and adjust the airflow operation.
Potentiometer R1. Adjusts the airflow during blower operation only.
Potentiometer R2. Adjusts the airflow during 1st stage cooling or heating operation.
Potentiometer R3. Adjusts the airflow during 2nd stage cooling or heating operation.
Energize blower only mode and adjust #1
Potentiometer to desired airflow.
Energize 1st stage cooling mode and adjust #2
Potentiometer to desired airflow.
Energize 2nd stage cooling mode and adjust #3
Potentiometer to desired airflow.
Minimum damper position when using CO
2
control damper should be fully closed at 700 ppm or lower, if not Potentiometer R7 can be adjusted clockwise (CW) to close it. If it is fully closed at 700 ppm or lower, no adjustments required.
Manual 2100-598
Page 9 of 12
Manual 2100-598
Page 10 of 12
GRAPH 1
C24H VENT AIRFLOW
Data Pending
GRAPH 2
C30H VENT AIRFLOW
Data Pending
COMMERCIAL ROOM VENTILATOR
SEQUENCE OF OPERATION
On a call for blower operation, CRV opens to a position as set by #1 Potentiometer. See Figure 5.
NOTE: These sequence descriptions do not apply if
CO
2
controller is used. The CRV will control according to observed CO
2
levels in the conditioned space. Refer to information on Page 6.
MIST
FIGURE 5
CALL FOR VENTILATION
WITH OR WITHOUT COMPRESSOR OPERATION
COOLING COIL SUPPLY AIR
ELIMINATOR
100% OUTDOOR AIR
CONDENSER AIR
CONDENSER COIL
AIR FILTER
RETURN AIR
EXHAUST AIR
MIS-3289
Manual 2100-598
Page 11 of 12
A call for 1st stage cooling or heating cycles the compressor, and the dampers reposition to the
Potentiometer #2 setpoint. A call for 2nd stage cooling or heating energizes compressor solenoid and repositions the damper blade to the Potentiometer
#3 position. On loss of blower operation, CRV closes fully. See Figure 6.
FIGURE 6
CALL FOR COMPRESSOR OR FAN ONLY
WITH VENTILATION OFF
COOLING COIL SUPPLY AIR
MIST
ELIMINATOR
DAMPER BLADE
CONDENSER AIR
CONDENSER COIL
AIR FILTER
100% RETURN
AIR
MIS-3290
Manual 2100-598
Page 12 of 12
advertisement