- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Ge Est
- QS4
- User manual
- 138 Pages
Ge Est QS4 Technical Reference Manual
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
QS4 Fire Alarm Control Panel
Technical Reference Manual
P/N 3100186 • Rev 2.0 • 12JUL01
Technical Manuals Online! - http://www.tech-man.com
Compliance Statement
Limitation of Liability
Fire Alarm System
Limitations
FCC Compliance Statement
The QS4, hereinafter referred to as the FACP or control panel, when properly installed, operates as a Local Protected Premises Fire Alarm
System in accordance with the following standards:
• NFPA Standard 72, 1999 Edition
• Underwriters Laboratories Standard 864, 7th Edition
• Underwriters Laboratories of Canada Standard ULC S527
In addition, Auxiliary Fire Alarm System operation requires a Reverse
Polarity Module (RPM). Central Station Fire Alarm System operation requires a Dialer card (DLD).
Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory.
Edwards Systems Technology (EST) shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of EST products beyond the cost of repair or replacement of any defective products. EST reserves the right to make product improvements and changes to product specifications at any time.
While every precaution was taken during the preparation of this document to ensure its accuracy, EST assumes no responsibility for errors or omissions.
Automatic fire alarm systems can not guarantee against property damage, loss of property, or loss of life. An automatic fire alarm system's ability to provide early warning of a developing fire may be limited for a variety of reasons, but mainly due to improper installation or maintenance.
The best way to minimize system failures is to perform regularly scheduled preventive maintenance in accordance with national and local fire codes. All system components and wiring should be tested and maintained by trained fire alarm system professionals.
This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply within the limits for Class A computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment.
Operation of this equipment is likely to cause interference, in which case the user at his own expense, will be required to take whatever measures may be required to correct the interference.
Copyright © 2001. All rights reserved.
Technical Manuals Online! - http://www.tech-man.com
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Content
About this manual • iii
Related documentation • iv
Document history • vi
Product description • 1.1
System overview • 1.2
Component descriptions • 1.3
Circuit descriptions • 1.5
Controls and indicators • 1.9
Controls and indicators behind the flip-down cover • 1.10
Controls and indicators on the zone annunciator card • 1.11
Interpretation of screen displays • 1.12
Installation • 2.1
Installation do's and don'ts • 2.2
Installation checklist • 2.3
Two ways to install the cabinet: Surface or semi-flush mount • 2.4
How to assemble the panel • 2.6
Wiring mains ac and earth ground • 2.7
System jumper settings • 2.8
System addressing • 2.10
Terminal definitions • 2.14
Connecting a PT–1S printer • 2.22
Installing standby batteries • 2.23
Operating instructions • 3.1
Instructions for the Level 1 operator (public mode access) • 3.2
Instructions for the Level 2 operator (emergency mode access) • 3.5
Instructions for the Level 3 operator (maintenance mode access) • 3.7
Instructions for the Level 4 operator (service mode access) • 3.10
QuickReference list • 3.11
Programming instructions • 4.1
Overview • 4.2
QuickStart setup instructions • 4.4
Customizing the system configuration • 4.13
Setting up an Output Group • 4.21
Setting up a Zone • 4.26
Standard applications • 5.1
Notification appliance circuits • 5.2
Initiating device circuits • 5.5
Coded alarm signaling • 5.8
Remote station protective signaling system • 5.10
Auxiliary protective signaling • 5.12
Maintenance instructions • 6.1
Pseudo point definitions • 6.2
Maintenance tasks • 6.6
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
i
Content
Appendix A
Appendix B
Appendix C
System calculations • A.1
Notification appliance circuit maximum wire length calculation • A.2
Signature loop maximum wire length calculations • A.3
Battery calculation worksheet • A.8
Barcode library • B.1
SIGA-REL programming • C.1
Application block diagram • C.2
Programming instructions • C.3
ii
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Content
About this manual
Organization
Safety information
This manual provides information on how to properly install, wire, and maintain the FACP and related components, and is organized as follows:
Chapter 1 provides a detailed description of the fire alarm control panel and its operation.
Chapter 2 provides instructions for installing the fire alarm control panel.
Chapter 3 provides instructions for operating the control panel.
Chapter 4 provides instructions for programming the fire alarm system from the front panel.
Chapter 5 provides simplified wiring schematics for standard applications.
Chapter 6 provides instructions for maintaining the system.
Appendix A provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries.
Appendix B provides a set of bar codes that you can use to enter text for location messages.
Appendix C provides information on how to program the SIGA–REL using the QS–CU (QuickStart Configuration Utility).
Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment.
WARNING: Warnings are used to indicate the presence of a hazard which will or may cause personal injury or death, or loss of service if safety instructions are not followed or if the hazard is not avoided.
Caution: Cautions are used to indicate the presence of a hazard which will or may cause damage to the equipment if safety instructions are not followed or if the hazard is not avoided.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
iii
Content
Related documentation
National Fire Protection Association
1 Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9101
Underwriters Laboratories, Inc.
333 Pfingsten Road
Northbrook, IL 60062-2096
Underwriters Laboratories of
Canada
7 Crouse Road
Scarborough, ON
Canada M1R 3A9
NFPA 70 National Electric Code
NFPA 72 National Fire Alarm Code
NFPA 11 Low-Expansion Foam Systems
NFPA 11A Medium- and High-Expansion Foam Systems
NFPA 12 Carbon Dioxide Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Fixed Systems for Fire Protection
NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray
Systems
NFPA 17Dry Chemical Extinguishing Systems
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single & Multiple Station
UL 228 Door Closers/Holders for Fire Protective Signaling
Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling
Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling
Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Visual Signaling Appliances
Canadian Electrical Code Part 1
ULC S527 Standard for Control Units for Fire Alarm Systems
ULC S524 Standard for the Installation of Fire Alarm Systems
ULC S536 Standard for the Inspection and Testing of Fire
Alarm Systems
ULC S537 Standard for the Verification of Fire Alarm Systems
ULC ORD–C693–1994 Central Station Fire Protective Signaling
System and Services iv
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Content
Edwards Systems Technology
6411 Parkland Drive
Sarasota, FL 34243
2–CTM City Tie Module Installation Sheet (P/N 270496)
CDR–3 Bell Coder Installation Sheet (P/N 3100023)
DLD Dual Inline Dialer Installation Sheet (P/N 3100187)
PS6 Power Supply Card Installation Sheet (P/N 3100201)
QSA–1(X), QSA–2(X) Remote Annunciator Cabinet Installation
Sheet (P/N 3100295)
QS–CPU(X) CPU/Display Unit Installation Sheet (P/N 3100276)
SL30, SL30–1 LED/Switch Card Installation Sheet (P/N
3100193)
SLIC Signature Intelligent Controller Card Installation Sheet
(P/N 3100192)
RS485 (NT–A) Card and QS–232 UART Module Installation
Sheet (P/N 3100191)
ZA8–2 Class A Zone Card Installation Sheet (P/N 3100189)
ZB16–4 Class B Zone Card Installation Sheet (P/N 3100188)
ZR8 Relay Card Installation Sheet (P/N 3100190)
SIGA–APS Auxiliary Power Supply Installation Sheet (P/N
387342)
Signature Series Intelligent Smoke and Heat Detectors
Applications Bulletin (P/N 270145)
Signature Series Component Installation Manual (P/N 270497)
EST Strobe Applications Guide (P/N 85000-0049)
QuickStart Online Help Utility (P/N 7350047)
QuickStart ULI and ULC Compatibility Lists (P/N 3100335)
Network Hardware Technical Reference (P/N 250100)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
v
Content
Document history
Date
24JUN01
12JUL01
Revision
1.0
2.0
Description of changes
Original release.
Corrections and additions on pp 2.12, 2.24, 3.9, 4.4, 4.8, 4.10, 4.19,
A.3.
vi
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 1
Product description
Summary
This chapter provides a detailed description of the fire alarm control panel and its operation.
Content
System overview • 1.2
Component descriptions • 1.3
Circuit descriptions • 1.5
Controls and indicators • 1.9
Controls and indicators behind the flip-down cover • 1.10
Controls and indicators on the zone annunciator card • 1.11
Interpretation of screen displays • 1.12
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.1
Product description
System overview
System hardware capabilities
Hardware capabilities vary depending on cabinet size and option card configuration, but generally:
• Up to four Class A or Class B Signature signaling line circuits that support up to 250 single-address Signature devices each
• Up to 40 Class A or 48 Class B initiating device circuits (IDC). Combination systems can not exceed 40 IDC circuits total
• Up to 16 Class A or 20 Class B notification appliance
• Up to two 30-zone displays
• Up to 96 dry-contact relay
• 4.5 amps of 24 Vdc power for external notification appliances
• Battery charger capable of charging batteries rated up to 40 Ah. Maximum battery size for
ULC applications is 30 Ah
• Up to eight, fully-supervised, mirrored or customized remote annunciators
Minimum system requirements
A Local Protected Premises Fire Alarm System requires only the FACP (CPU, PS6, and enclosure) with at least one SLIC, ZB16–4, or
ZA8–2 card programmed with at least one audible output circuit and one alarm input circuit.
In addition to the hardware requirements of a
Local system:
• Add a 2–CTM City Tie Module for an Auxiliary
Fire Alarm System
• Add a DLD Dual Line Dialer Card or RPM
Reverse Polarity Module for a Remote
Supervising Station Fire Alarm System
• Add a DLD Dual Line Dialer Card or RPM
Reverse Polarity Module for a Central Station
Fire Alarm System
• Add a SIGA–REL for Releasing Device Service
Normal operating mode description
The panel operates in normal mode in the absence of any alarm, supervisory, trouble, and monitor events. In normal mode, the control panel monitors the system for any events.
Off-normal operating mode description
The panel operates in off-normal mode any time there is an event introduced into the system.
When this happens, the CPU:
• Changes the contact positions on the appropriate common relays
• Activates all common alarm outputs (alarm events only)
• Turns on the panel buzzer
• Executes the appropriate programmed output response for the input that signaled the event
• Sends a record of the event to the appropriate display queue and out the serial port
If there is no operator in attendance, the panel displays the content of the highest priority display queue containing a record.
If there is an operator in attendance, the panel displays the content of the current display queue regardless of any new events introduced into the system.
Failsafe operating mode description
The panel operates in failsafe mode when the
CPU loses the ability to communicate with the PS6 and JP1 on the PS6 is in the ON position. When this happens, the power supply:
• Closes the common trouble relay contacts
• Instructs the dialer to send the default trouble message
• Monitors the system for any alarm events
If an alarm event occurs, the power supply:
• Changes the contact positions on the common alarm relay
• Turns on all conventional common alarm outputs. Signature common alarm outputs are not affected.
• Instructs the dialer to send the default alarm message
1.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Component descriptions
1 2 3 6A 4
J6
J5
J8
J7
JP1 CONFIG URATION
PIN 2 & 3 = RTS
JP1
3 1 J2
5 6B 7 8
Product description
9
10
15
1. Cabinet enclosure: Houses the panel electronics and standby batteries.
2. SL30–1 LED/Switch Card: Provides thirty circuits for point or zone annunciation. Each circuit has two LEDs for annunciating alarm, supervisory, and trouble signals, and a button numbered from 31 to 60.
3. SL30 LED/Switch Card: Same as SL30–1 except the buttons are numbered 1–30.
14 13 12 11
4. CPU/Display: Provides operator access to system messages, status information, and programming menus, and executes system responses based on the panel programming.
5. PS6 Power Supply Card: Provides primary dc power to the panel electronics and external circuits. The PS6 also provides common alarm, supervisory and trouble relays for remote station supervision.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.3
Product description
6. RS485 (NT–A) Class A Card: The NT–A comprises the RS485 card and QS–232 UART module. Together these provide an additional
RS–232 channel to allow Class A communication between the control panel and other remote annunciator panels. Control panels require installation of both cards while remote annunciator panels only require installation of a
QS–232 card and only then if you want to connect a printer or service computer.
7. ZA8–2 Class A Conventional Zone Card:
Provides six dedicated Class A initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The
ZA8–2 also provides two circuits that you can configure as IDCs or as 24 Vdc notification appliance circuits (NACs).
8. ZB16–4 Class B Conventional Zone Card:
Provides twelve dedicated Class B initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The ZB16–4 also provides four circuits that you can configure as IDCs or as Class B 24
Vdc notification appliance circuits (NACs).
9. QS–Cable12 Expansion Cable: Extends the
CPU data and power bus to circuit cards installed on the lower DIN rail in the 12-option cabinet.
10. ZR8 Relay Card: Provides eight dry-contact relays. You can configure each relay for normally-open or normally-closed operation.
11. DLD Dual Line Dialer Card: Provides two telephone line connections for sending system messages to a compatible Digital Alarm
Communicator Receiver.
12. SLIC Signature Loop Intelligent Controller
Card: Provides one Class A or Class B signaling line circuit (loop) for connecting Signature series detectors and modules. The SLIC also provides two Class A or Class B notification appliance circuits (NACs) for connecting polarized 24 Vdc notification appliances (horns, strobes).
13. Standby batteries: Provides dc power to the panel electronics in the absence of ac power.
14. Transformer: Changes the mains ac supply voltage for the power supply card.
15. AC wiring block and fuse holder: Provides connections for mains ac (primary power) and 5A fuse.
1.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Product description
Circuit descriptions
PS6 Power Supply Card
1. Relay 1 (Common Alarm)
Style: Form C
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when connected to a power-limited source
2. Relay 2 (Common Supervisory)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when connected to a power-limited source
3. Relay 3 (Common Trouble)
Style: Normally-open, held closed
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when connected to a power-limited source
4. Relay 4 (Programmable)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when connected to a power-limited source
5. Smoke/Accessory Power
Output: Continuous or interruptible via jumper selection
Voltage: 24 Vdc, regulated
Current: 250 mA
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Supervised and power-limited
6. RS485
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Wire type: Twisted pair, six twists per foot minimum
Circuit capacitance: 0.4 µ F
Circuit resistance: 100 Ω
Supervised and power-limited
7. RS232
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited
Wire length: 20 ft maximimum
1
9
2 3 4 5 6
7
8
8. AUX Power #1, #2, and #3
Voltage: 17.5 – 26.4 Vdc FWR (full wave rectified)
Current: 1.5 A each
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Power-limited and supervised for short circuit conditions only
9. Battery Circuit
Charge current: 2 A
Charge capacity: 40 Ah (UL), 30 Ah (ULC)
Supervised and nonpower-limited
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.5
Product description
SLIC Signature Loop Intelligent Controller Card circuits
1. NAC #1
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 2.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
End of line resistor: 10 k Ω , 1/2W
Supervised and power-limited
2. NAC #2
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 1.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
End of line resistor: 10 k Ω , 1/2W
Supervised and power-limited
3. Signature Loop
Configuration: Class B (Style 4) or Class A (Style 6)
Capacity: 125 Signature detectors, 125 Signature single-address modules
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
Circuit resistance: 65 Ω
Circuit capacitance: 0.3 µ F
Supervised and power-limited
4. NAC Riser In/Out
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )
ZR8 Relay Card circuits
1. Dry-contact relays R1 – R4
Outputs: Normally-open or normally-closed contacts via jumper selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
Nonsupervised, and power-limited only when connected to a power-limited source
2. Dry-contact relays R5 – R8
Outputs: Normally-open or normally-closed contacts via jumper selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
Nonsupervised, and power-limited only when connected to a power-limited source
1
4
1
2
2
3
1.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
ZB16–4 Class B Conventional Zone Card circuits
1. IDC Circuits Z1 – Z12
Wiring configuration: Class B
Detector voltage: 20.33 – 24.76 Vdc, max ripple 2000 mV
Short circuit current: 75.9 mA, max.
Resistance: 50 Ω , max.
Capacitance: 100 µ F, max
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
End of line resistor: 4.7 k Ω , 1/2W
Supervised and power-limited
2. NAC Circuits Z13 – Z16
Wiring configuration: Class B
Output voltage: 24 Vdc, nominal
Output current: 2.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
End of line resistor: 10 k Ω , 1/2W
Supervised and power-limited
IDC specifications apply when programmed as IDC circuit
3. R1
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
4. R2
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
ZA8–2 Class A Conventional Zone Card circuits
1. IDC Circuits Zone 1 – Zone 3, Zone 5 – Zone 7
Wiring configuration: Class A
Detector voltage: 19.90 – 22.46 Vdc, max ripple 2000 mV
Short circuit current: 75.9 mA, max.
Resistance: 50 Ω , max.
Capacitance: 100 µ F, max
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 4.7 k Ω , 1/2W
Supervised and power-limited
2
)
2. NAC Circuits Zone 4, Zone 8
Wiring configuration: Class A
Output voltage: 24 Vdc, nominal
Output current: 2.0 A, 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )
End of line resistor: 10 k Ω , 1/2W
Supervised and power-limited
IDC specifications apply when programmed as IDC circuit
3. NAC PWR IN (Zone 4)
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )
4. NAC PWR IN (Zone 8)
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
1
1
1
1
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
Product description
2
3
4
1.7
2
4
3
2
Product description
DLD Dual Line Dialer Card circuits
1. Line #1
Supervised and nonpower-limited
2. Line #2
Supervised and nonpower-limited
1 2
RS485 (NT–A) Class A Card circuits
1. Secondary RS485 channel
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
Supervised and power-limited
)
2. Primary RS485 channel
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
Supervised and power-limited
)
Note: JP1 installed for ground fault detection on RS485 circuits.
1 2
1.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Product description
Controls and indicators
1 2 3 4 5 6 7 8 9
3
4
1
2
6 11 16 21 26
7 12 17 22 27
8 13 18 23 28
9 14 19 24 29
5 10 15 20 25 30
1 6 11 16 21 26
2
3
7
8
12 17
13 18
22 27
23 28
4 9 14 19 24 29
5 10 15 20 25 30
1 2 3 4 5 6 7 8 9 0
12 11 10
1. Text display and controls: Displays system messages, status information, programming menus.
Moves the cursor up one line at a time or to the previous record in the display queue
Moves the cursor down one line at a time or to the next record in the display queue
Moves the cursor right one character at a time or to the next display queue
Moves the cursor left one character at a time or to the previous display queue
Enters operator input and selects menu items
2. Alarm LED: Indicates the panel posted an alarm event record into the corresponding display queue.
3. Supervisory LED: Indicates the panel posted a supervisory event record into the corresponding display queue.
4. Disable/Test LED: Indicates part of the system is disabled or is currently under test.
Disabled components also signal a system trouble.
5. Monitor LED: Indicates the panel posted a monitor event record into the corresponding display queue.
6. Trouble LED: Indicates the panel posted a trouble event record into the corresponding display queue.
7. Ground Fault LED: Indicates a ground fault in the system wiring. Ground faults also signal a system trouble.
8. CPU Fail LED: Indicates an unexpected reboot or failure with the microprocessor. CPU failures also signal a system trouble.
9. Power LED: Indicates the panel has ac power.
10. Panel Silence/Acknowledge button/LED:
Turns off the panel buzzer and acknowledges all events. The Panel Silenced LED indicates that all off normal events have been acknowledged and the internal buzzer is off.
11. Status button: Displays the Status menu from which you can identify active or disabled points in the system.
12. Help button: Provides additional information for the event record selected on the display.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.9
Product description
Controls and indicators behind the flip-down cover
7
4
8
5
9
6
3
1 6 11 16 21 26
2 7 12 17 22 27
3
4
8
9
13 18
14 19
23 28
24 29
5 10 15 20 25 30
1
2
6 11 16 21 26
7 12 17 22 27
3
4
8 13 18 23 28
9 14 19 24 29
5 10 15 20 25 30
1 2 3 4 5 6 7 8 9 0
2 1
1. Enable Controls key switch: Gives priority access to control functions reserved for operators with Level 2 access.
2. Barcode scanner jack: Input point for optional barcode scanner.
3. Numeric keypad: Numbered buttons for entering data and selecting menu options.
4. Reset button: Restores devices or zones in alarm or trouble to their standby condition. The
LED indicates when the panel is resetting.
5. Alarm Silence button: Turns active notification appliances off according to the panel programming. Pressing Alarm Silence a second time turns them back on. The LED indicates when the panel is in alarm and operating with notification appliances turned off.
6. Drill button: Turns notification appliances on according to the panel programming but does not place the panel in alarm. The LED indicates when the panel is in Drill mode.
7. Menu button: Displays the operator menus.
8. Delete button: Returns to the previous menu or back spaces the cursor.
9. Enter button: Press the Enter button to accept information from the operator or continue to the next item.
1.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Controls and indicators on the zone annunciator card
1 2 3
1 6 11 16 21 26
2 7 12 17 22 27
3
4
8 13 18 23 28
9 14 19 24 29
5 10 15 20 25 30
Product description
1. Zone display button: Displays an event record for each device in the corresponding zone that signaled an alarm.
2. Zone active LED: Indicates a device in the corresponding zone signaled an alarm condition.
3. Zone trouble LED: Indicates a device or wiring fault in the corresponding Zone.
Note: ULC requires that every fire panel have the capability to visually display system status by means of specific indicators for each zone. All status changes must clearly indicate that the information is an Alarm (ALM), Supervisory
(SUP), Trouble (TBL), or Monitor (MON).
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.11
Product description
Interpretation of screen displays
HH:MM:SS MM/DD This is what the panel display looks like when there are no event records posted in a display queue.
HH:MM:SS is the current time in hours, minutes, and seconds
MM/DD is the current month and date
nnnn is the number times the panel went into alarm since being placed into service
System
Normal
Project Name
Alarm History: nnnn
HH:MM:SS
Axxx Dxxx nnn event name
Custom message 1
Custom message 2
nnn event name
Custom message 1
Custom message 2
ALM SUP TRBL MON aaa sss ttt mmm
This is what the panel display looks like when there are event records posted in a display queue.
HH:MM:SS is the current time in hours, minutes, and seconds
Axxx is the current number of active points
Dxxx is the current number of disabled points
These items comprise the event record:
nnn is the posting sequence number (001 = first, 002 = second, and so on)
event name is the event produced when the device changed states.
Refer to Table 1-1.
P:pp C:cc D:ddd is the address of the device that signaled the event (P = panel number, C = card number, D = device number)
The event record may also include a custom message that typically indicates the location of the device, depending on the panel programming.
These items indicate the content of the display queues:
aaa is the number of alarm event records (highest priority)
sss is the number of supervisory event records
ttt is the number of trouble event records
mmm is the number of monitor event records (lowest priority)
1.12
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 1-1: Event descriptions
Event name
ALARM ACTIVE
ALARM VERIFY
AND GROUP
BAD PRSONATY
BAD TYPE
COMM FAULT
DEV COMPATIB
DIRTY HEAD
DISAB SOUND
DISABLED
GROUND FAULT
HEAT ALARM
INTERNAL TBL
LCL MONITOR
LCL TROUBLE
MAINT ALERT
MATRIX GROUP
MONITOR
OBJECT RUN
PREALARM
PULL STATION
SERVICE GROUP
SUPERVISORY
SWITCH
TAMPER
TEST
TIME CONTROL
TROUBLE
TROUBLE OPEN
TROUBLE SHORT
UNEXPECT DEV
WATERFLOW
ZONE ALARM
ZONE MONITOR
ZONE SUPER
Event type
Monitor
Trouble
Monitor
Alarm
Monitor
Monitor
Monitor
Alarm
Trouble
Supervisory
Monitor
Supervisory
Trouble
Monitor
Trouble
Alarm
Monitor
Alarm
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Alarm
Trouble
Trouble
Trouble
Trouble
Alarm
Alarm
Monitor
Supervisory
Product description
Description
Smoke detector active
Alarm active. Performing auto reset.
And group active
SIGA personality mismatch
SIGA type mismatch
Communication failure
SIGA compatibility fault
Dirty smoke detector. No compensation remaining
Sounder is disabled (EN–54 only)
Device is disabled
Ground fault
Heat detector active
Internal system trouble
Common monitor
Generic trouble.
Dirty smoke detector. Some compensation remaining
Matrix group active
Active non-latching input circuit.
Service group is enabled and governing all defined objects
Possible fire condition exists.
Manual fire alarm box active
Service group active
A device used to monitor a component of the fire suppression system is active
Operator presses switch on LED/Switch card
Sprinkler tamper active
A member of a Service group under test is activated
Time control active
Common trouble
Open detected on a supervised output device's field wiring
Short detected on a supervised output device's field wiring
Signature device not defined in database
Water flowing through the sprinkler system
Alarm zone active
Monitor zone active
Supervisory zone active
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
1.13
Product description
1.14
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 2
Installation
Summary
This chapter provides instructions for installing the fire alarm control panel.
Content
Installation do's and don'ts • 2.2
Installation checklist • 2.3
Two ways to install the cabinet: Surface or semi-flush mount • 2.4
How to assemble the panel • 2.6
Wiring mains ac and earth ground • 2.7
System jumper settings • 2.8
System addressing • 2.10
Terminal definitions • 2.14
Connecting a PT–1S printer • 2.22
Installing standby batteries • 2.23
Connecting a service computer • 2.24
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.1
Installation
Installation do's and don'ts
When installing cabinets...
DO use fasteners that can support the full weight of the cabinet and standby batteries. Tighten firmly to avoid vibrations.
DO NOT drill inside the cabinet with circuit cards installed.
Remove all metal filings before installing the circuit cards.
DO NOT recess the cabinet into the wall deeper than 2–11/16 inches (68.2 mm) from the finished wall surface to allow room for the trim kit.
When installing circuit boards...
When installing circuit wiring...
When installing Signature loops...
DO ground yourself with an approved static-protective wrist strap when handling circuit boards.
DO keep circuit boards in their protective antistatic packaging.
Remove only for inspection or installation.
DO NOT touch component leads and connector pins when handling circuit boards.
DO disconnect ac power and batteries before installing or removing circuit boards. Installing or removing circuit boards while the control panel is energized may damage the equipment.
DO use appropriately sized wire for the application.
Incorrectly-sized wires degrade circuit performance.
DO make sure there are no wire-to-ground shorts or wire-towire shorts before connecting field wires to the panel.
DO NOT over tighten screw terminals. Over tightening may strip screw terminal threads and cause loose connections.
DO NOT install more than fifteen SIGA–UMs or MABs configured for two-wire smoke detectors on a loop.
DO NOT install more than seven SIGA–UMs or MABs configured for two-wire smoke detectors on loops with isolator devices.
DO NOT install more than ten SIGA–RELs on a loop. You must use the QuickStart configuration utility to program a
SIGA–REL. Refer to the technical manual supplied with the
SIGA–REL and appendix C of this manual for programming information.
When installing standby batteries...
DO NOT install standby batteries until after you completely install and test the system.
2.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
Installation checklist
¨ Prepare the site
¨ Unpack the equipment
Make sure the installation location is free from construction dust and debris, and immune to extreme temperature ranges and humidity.
Allow enough floor and wall space so the panel can be installed and serviced without obstructions.
Pull and tag all field wiring. See Appendix A for wire length calculations.
Open the shipping container and carefully unpack the equipment. Check for any visible signs of damage. If there is any damage, return the equipment to the place of purchase.
Keep the container and packing material until after completely installing and testing the equipment. Use the shipping container to return the equipment to the manufacturer.
Verify the shipping container contains the correct parts. If any parts are missing or damaged, return the equipment to the manufacturer.
See Figure 2-1 for cabinet dimensions.
¨ Install the cabinet
¨ Assemble the panel
¨ Wire mains ac and earth ground Bring the primary power conductors into the left side
(nonpower-limited area) of the cabinet and wire to the ac terminal block.
¨ Connect the field wiring
WARNING: Make sure that the circuit breaker providing ac power is switched off before connecting wires to the terminal block.
Bring the field wiring into the power-limited area of the cabinet.
Verify there are no open or shorts then connect the wires to their respective terminals.
Refer to chapter 4.
¨ Use the AutoLearn and
AutoLoop utilities to configure the system
¨ Customize the system configuration
¨ Install the standby batteries
Refer to chapter 4.
Do not connect standby batteries to the panel until after completely testing the panel.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.3
Installation
Two ways to install the cabinet: Surface or semi-flush mount
Surface mount instructions
1. Position the cabinet on the finished wall surface.
2. Fasten the cabinet to the wall surface where indicated. Tighten firmly.
4-7/8 in
(123.8 mm)
Semi-flush mount instructions
1. Frame the interior wall as required to support the full weight of the cabinet and standby batteries.
2. Fasten the cabinet to the framing studs where indicated. Tighten firmly.
2-11/16 in
(68.2 mm)
2-3/16 in
(55.6 mm)
2.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
D3 D4
D1
D5
D2
5-option cabinet
12-option cabinet
D1
18 in
(45.72 cm)
30 in
(76.2 cm)
D2
18-5/8 in
(47.31 cm)
18-5/8 in
(47.31 cm)
D3
4-7/8 in
(12.38 cm)
4-7/8 in
(12.38 cm)
Note: Add 1-1/2 in (3.81 cm) to D1 and D2 dimensions for trim kit.
Dimensions
D4
16-5/8 in
(42.23 cm)
16-5/8 in
(42.23 cm)
D5
13 in
(33.00 cm)
25 in
(63.50 cm)
Figure 2-1: Dimensions for 5-option and 12-option cabinets (arrows show mounting hole locations)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.5
Installation
How to assemble the panel
Circuit card instructions
1. Lock the PS6 onto the DIN rail and configure jumpers.
2. Attach the ground wire to the cabinet. Tighten the lock nut firmly to ensure a good mechanical and electrical connection.
3. Plug the transformer into the PS6.
4. Install remaining option cards according to their respective installation sheets.
Use a QS–Cable12 to connect option cards on the top and bottom DIN rails in a 12-option cabinet.
Door mounting instructions
1. Bolt the door to the cabinet back box.
2. Attach one end of the ground strap to the door and the other to the back box.
3. Screw the CPU/Display unit to the cabinet door.
4. Plug one end of the ribbon cable into the
CPU/Display and the other end into the PS6.
5. Screw the key switch ground wire and the
CPU cover to the cabinet door.
*Actual cabinet door not shown
2.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
Wiring mains ac and earth ground
H
(L1)
G
(E)
N
(L2)
CAUTION: The middle connection on the ac terminal block makes a mechanical connection to chassis (earth) ground. Do not allow the ac hot and neutral conductors to make contact with the middle connector on the ac terminal block.
Wiring instructions
1. Bring the mains ac conductors into the cabinet through the 3/4–1/2 inch combination knock-outs on the left side or upper left corner of the cabinet.
2. Wire the hot (H, L1), neutral (N, L2), and ground (G, E) conductors to the ac terminal block as shown.
3. Insert tabbed end of terminal block cover
(deadfront) into the slot provided on the side of the cabinet.
Notes
Keep power-limited wires in the shaded area and nonpower-limited wires in the nonshaded area.
Maintain a 1/4-inch separation between the mains ac and battery wires (power-limited) and and all other nonpower-limited wiring at all times.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.7
Installation
System jumper settings
PS6 Power Supply Card jumpers
JP2 configures the Smoke/Accessory power output for constant or resettable 24 Vdc.
• Set JP2 to ACC PWR to provide constant
24 Vdc for external equipment.
• Set JP2 to SMK PWR to provide resettable
24 Vdc for four-wire smoke detectors
JP1 configures the panel for failsafe operation.
Failsafe allows the system to generate output responses even when the CPU loses communication with the power supply card.
• Set JP1 to ON to turn failsafe mode on
• Set JP1 to OFF to turn failsafe mode off
SLIC Signature Loop Intelligent Controller
Card jumpers
JP1 and JP2 selects the signal that the SLIC uses for the notification appliances connected to
NAC1.
Note: NAC 2 always uses the external signal connected to TB2–3 and TB2–4.
• Set JP1 and JP2 to INT to use the 24 Vdc that comes from the PS6 over the bus connection.
• Set JP1 and JP2 to EXT to use the 24 Vdc that comes from an external source connected to TB2–3 and TB2–4.
CAUTION: Do not set JP1 and JP2 to EXT if strobes are connected to NAC 1 and a coded signal is connected to TB2–3 and TB2–4.
JP2
ACC PWR
SMK PWR
JP1
ON OFF
JP1 JP2
EXT
INT
2.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
ZR8 Relay Card jumpers
JP1 – JP8 configure which relay contacts are present on the terminal connections for R1 – R8, respectively.
The normal operating state of the relay (on or off when the panel is normal) determines whether the terminal connections are normally-open or normally-closed.
The figure to the right shows the relay contact positions when the relay is turned off.
Installation
JP4
R4+ R4–
RS485 (NT–A) Class A Card jumpers
JP1 configures ground fault supervision for
Class A remote annunciators.
• Set a shorting plug across JP1–1 and JP1–2 when the PS6 powers the remote annunciator and provides ground fault supervision
• Set a shorting plug across JP1–2 and JP1–3 when an external supply powers the remote annunciator and provides ground fault supervision
1 2 3
JP1
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.9
Installation
System addressing
Card addresses
Each option card installed in the panel is assigned a unique card address. Only the SLIC,
ZB16–8, ZA8–2, and ZR–8 have card addresses that you can set. The CPU, DLD and PS6 card addresses are fixed.
00: Reserved for the CPU
01–07: Used for the SLIC, ZB16–8, ZA8–2, and
ZR–8
08–13: Used for the ZB16–8, ZA8–2, and ZR–8
14: Reserved for the DLD
15: Reserved for the PS6
ON
1 2 3 4
= 01
ON
1 2 3 4
= 02
ON
1 2 3 4
= 03
ON
1 2 3 4
= 04
ON
1 2 3 4
= 05
ON
1 2 3 4
= 06
ON
1 2 3 4
= 07
ON
1 2 3 4
= 08
ON
1 2 3 4
= 09
ON
1 2 3 4
= 10
ON
1 2 3 4
= 11
ON
1 2 3 4
= 12
ON
1 2 3 4
= 13
Tip: When you install the option cards, set the card addresses in consecutive order as you move away from the power supply starting at address 01.
01 02 03 04
07 06 05
2.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
SLIC Signature Loop Intelligent Controller
Card device addresses
The device address format is PPCCDDD, where:
PP is the panel number (01)
CC is the card number (any number between 1 and 7 depending on the setting of SW1)
DDD is the device or circuit number, where:
• 001–125 are Signature automatic detectors and SIGA–IM isolator modules
• 126–250 are Signature modules
• 270 is the NAC 1 output circuit
• 271 is the NAC 2 output circuit
Note: Some Signature modules use two or more device addresses.
ZR8 Relay Card device addresses
The device address format is PPCCDDD, where:
PP is the panel number (01)
CC is the card number (any number between 1 and 13 depending on the setting of SW1)
DDD is the device number, where 001 – 008 are relays 1 – 8, respectively
PPCC002
PPCC001
PPCC006
PPCC005
PPCC270
PPCC271
Installation
PPCC001 to
PPCC125
PPCC126 to
PPCC250
PPCC003
PPCC004
PPCC007
PPCC008
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.11
Installation
ZB16–4 Class B Conventional Zone Card device addresses
The device address format is PPCCDDD, where:
PP is the panel number (01)
CC is the card number (any number between
1 and 13 depending on the setting of SW1)
DDD is the circuit number, where:
• 001 – 012 are IDC circuits Z1 – Z12, respectively
• 013 – 016 are NAC circuits Z13 – Z16, respectively
Note: NAC circuits Z13 – Z16 can also be programmed as IDC circuits.
PPCC005
PPCC004
PPCC003
PPCC002
PPCC001
PPCC012
PPCC011
PPCC010
ZA8–2 Class A Conventional Zone Card device addresses
The device address format is PPCCDDD, where:
PP is the panel number (01)
CC is the card number (any number between
1 and 13 depending on the setting of SW1)
DDD is the circuit number, where:
• 001 – 003 and 005 – 007 are IDC circuits
Zone 1 – Zone 3 and Zone 5 – Zone 7, respectively
• 004 and 008 are NAC circuits Zone 4 and
Zone 8, respectively
Note: NAC circuits Zone 4 and Zone 8 can also be programmed as IDC circuits.
PPCC002
PPCC001
PPCC006
PPCC005
PPCC006
PPCC007
PPCC008
PPCC009
PPCC013
PPCC014
PPCC015
PPCC016
PPCC003
PPCC004
PPCC007
PPCC008
2.12
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
SL30 (–1) LED/Switch Card device addresses
The device address format is GGSS for switches and GGSSL for LEDs, where:
GG is the group number (01 for SL30, 02 for
SL30–1)
SS is the switch number
L is the LED number, where:
• 1 is the red Alarm LED
• 2 is the yellow Active LED
• 3 is the yellow Trouble LED
GG011, GG012
1
GG013
GG01
06-10 11-15 16-20 21-25 26-30
GG02
GG03
GG04
GG05
6 11 16 21 26
2 7 12 17 22 27
3 8 13 18 23 28
4 9 14 19 24 29
5 10 15 20 25 30
SL30
01-05 06-10 11-15 16-20 21-25 26-30
GG01
GG02
GG03
GG04
GG05
31 36 41 46 51 56
32 37 42 47 52 57
33 38 43 48 53 58
34 39 44 49 54 59
35 40 45 50 55 60
SL30–1
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.13
Installation
Terminal definitions
Table 2-1: PS6 Power Supply card terminal definitions
RELAY 1 RELAY 2 RELAY 3 RELAY 4
NO C NC C NO C NO C NO N.C.
SMOKE
ACC PWR
+ –
RS485
+ –
RS232
RTS TX RX COM
TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Terminal No.
TB1–1, –2
TB1–2, –3
TB1–4, –5
TB1–6, –7
TB1–8, –9
TB1–10
TB1–11, –12
TB1–13, –14
BATT PWR
+ – NC
TB2
1 2 3
AUX POWER
AUX1 AUX2 COM AUX3 COM
TB3
1 2 3 4 5
Name Description
Relay 1 NO, C
Relay 1 C, NC
Relay 2 C, NO
Relay 3 C, NO
Relay 4 C, NO
Normally-open relay contacts that close automatically when the panel processes an alarm event. The contacts remain closed until all active alarm points restore and the panel resets.
Normally-closed relay contacts that open automatically when the panel processes an alarm event. The contacts remain open until all active alarm points restore and the panel resets.
Normally-open relay contacts that close automatically when the panel processes a supervisory event. The contacts remain closed until the active supervisory point restores.
Normally-open relay contacts that close automatically when the panel energizes. The contacts open when the panel processes a trouble event or when the panel loses power and remain open until the trouble condition restores.
Normally-open relay contacts that close depending on how the user programs the panel.
N.C.
Not used
SMK/ACC PWR +, – Provides regulated 24 Vdc for four-wire smoke detectors or accessory devices depending on jumper setting.
RS485 +, – Connects to the Channel 1 input on a remote annunciator
2.14
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Terminal No.
TB1–15
TB1–16
TB1–17
TB1–18
TB2–1
TB2–2
TB2–3
TB3–1
Name
RS232 RTS
RS232 RX
RS232 TX
RS232 COM
BATT PWR +
BATT PWR –
NC
AUX1
TB3–2
TB3–3
TB3–4
TB3–5
AUX2
COM
AUX3
COM
Installation
Description
Not used
Connects to the data transmit (TX) terminal on a peripheral device.
Connects to the receive data (RX) terminal on a peripheral device.
Connects to the common ground (COM) terminal on a peripheral device.
Connects to the positive terminal on the standby battery.
Connects to the negative terminal on the standby battery.
Not used.
Provides 24 Vdc, FWR power to auxiliary devices.
Note: AUX1, AUX2, and AUX3 can not be used to power remote annunciators
Provides 24 Vdc, FWR power to auxiliary devices.
Negative reference for AUX1 and AUX2 outputs.
Provides 24 Vdc, FWR power to auxiliary devices.
Negative reference for AUX3 output.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.15
Installation
Table 2-2: SLIC Signature Loop Intelligent Controller card
NAC 1 NAC 2
B+ B– A+ A– B+ B– A+ A–
TB1
1 2 3 4 5 6 7 8
Terminal No.
TB–1, –2
Name
NAC 1 B+, B–
TB–3, –4
TB–5, –6
NAC 1 A+, A–
NAC 2 B+, B–
TB–7, –8
TB2–1, –2
TB2–3, –4
TB2–5, –6
TB2–7, –8
NAC 2 A+, A–
OUT+, OUT–
IN+, IN–
LOOP A+, A–
LOOP B+, B–
+
OUT
– +
IN LOOP
– A+ A– B+ B–
TB2
1 2 3 4 5 6 7 8
Description
Connects to the IN +/– terminals of the first device on the
NAC circuit. Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.
Connects to the OUT +/– terminals of the last device on the
NAC circuit. Class A configuration only.
Connects to the IN +/– terminals of the first device on the
NAC circuit. Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.
Connects to the OUT +/– terminals of the last device on the
NAC circuit. Class A configuration only.
Connects to the next device on the same 24VDC riser used to provide 24 Vdc to NAC 1 and NAC 2.
Connects to the signal source used to provide 24 Vdc to
NAC 1 and NAC 2.
Connects to the DATA OUT +/– terminals of last device on the Signature signaling line circuit. Class A configuration only.
Connects to the DATA IN +/– terminals of the first device on the Signature signaling line circuit.
2.16
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
Table 2-3: ZA8–2 terminal definitions
ZONE 1
B+ B– A+ A–
ZONE 2
B+ B– A+ A–
ZONE 3
B+ B– A+ A–
ZONE 4
B+ B– A+ A–
NAC PWR
IN+ IN–
1 2 3 4 5 6
IDC
7 8 9 10 11 12 13 14 15 16 17 18
IDC/NAC
TB1
ZONE 5
B+ B– A+ A–
IDC
ZONE 6
B+ B– A+ A–
ZONE 7
B+ B– A+ A–
IDC/NAC
ZONE 8
B+ B– A+ A–
NAC PWR
IN+ IN–
TB2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
IDC circuit connections
Terminal No.
Name Description
TB1–1, –2 ZONE 1 B+, B– Connects to the IN +/– terminals of the first device on the IDC.
TB1–3, –4 ZONE 1 A+, A– Connects to the OUT +/– terminals of the last device on the
IDC.
Note: ZONE 2, 3, 5, 6, and 7 connect the same as described for ZONE 1.
IDC/NAC circuit connections
Terminal No.
TB1–13, –14
TB1–15, –16
Name
ZONE 4 B+, B–
ZONE 4 A+, A–
Description
Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.
Connects to the OUT +/– terminals of the last device on the
NAC.
TB1–17, –18
TB2–13, –14
NAC PWR IN+, IN–
ZONE 8 B+, B–
Connects to the signal source used to provide 24VDC to ZONE
4.
Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.
TB2–15, –16 ZONE 8 A+, A– Connects to the OUT +/– terminals of the last device on the
NAC.
TB2–17, –18 NAC PWR IN+, IN– Connects to the signal source used to provide 24VDC to ZONE
8.
Note: ZONE 4 and ZONE 8 may be programmed as IDC circuits.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.17
Installation
Table 2-4: ZB16–4 Class B Zone card terminal definitions
+ Z1 – + Z2 – + Z3 – + Z4 – + Z5 – + Z6 – + Z7 – + Z8 – + Z9 –
1 2 3 4 5 6 7 8 9
IDC
10 11 12 13 14 15 16 17 18
TB1
IDC IDC/NAC
+ Z10 – + Z11 – + Z12 – + Z13 – + Z14 – + Z15 – + Z16 – + R1 – + R2 –
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
TB2
IDC circuit connections
Terminal No.
Name Description
TB1–1, –2 Z1+, Z1– Connects to the IN +/– terminals of the first device on the IDC.
Note: Z2–Z16 connect the same as described for Z1.
IDC/NAC circuit connections
Terminal No.
Name Description
TB2–7, –8 Z13+, Z13– Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.
TB2–9, –10
TB2–11, –12
TB2–13, –14
Z14+, Z14–
Z15+, Z15–
Z16+, Z16– same as above same as above same as above
TB1–15, –16
TB1–17, –18
R1+, R1–
R2+, R2–
Connects to the signal source used to provide 24VDC to Z13 and
Z14.
Connects to the signal source used to provide 24VDC to Z15 and
Z16.
Note: Z13, Z14, Z15, and Z16 may be programmed as IDC circuits.
2.18
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 2-5: ZR8 Relay card terminal definitions
+ R1 – + R2 – + R3 – + R4 –
1 2 3 4 5 6 7 8
TB1
Installation
Terminal No.
TB1–1, –2
TB1–3, –4
TB1–5, –6
TB1–7, –8
TB2–1, –2
TB2–3, –4
TB2–5, –6
TB2–7, –8
Name
R1+, R1–
R2+, R2–
R3+, R3–
R4+, R4–
R5+, R5–
R6+, R6–
R7+, R7–
R8+, R8–
+ R5 – + R6 – + R7 – + R8 –
1 2 3 4 5 6 7 8
TB2
Description
Terminal connections for relay 1.
Terminal connections for relay 2.
Terminal connections for relay 3.
Terminal connections for relay 4.
Terminal connections for relay 5.
Terminal connections for relay 6.
Terminal connections for relay 7.
Terminal connections for relay 8.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.19
Installation
Table 2-6: RS485 (NT–A) Class A card terminal definitions
RS485
+ CH2 – + CH1 –
TB1
1 2 3 4
Terminal No.
TB1–1, –2
TB1–3, –4
Name
CH2+, CH2–
CH1+, CH1–
Description
Connects to CH2+/– on the first remote annunciator on the Class
A RS485 riser.
Connects to CH1+/– on the first remote annunciator on the Class
A RS485 riser.
2.20
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 2-7: DLD Dual Line Dialer card terminal definitions
LINE 1 LINE 2
IN OUT IN OUT
TIP RING TIP RING TIP RING TIP RING
TB1
1 2 3 4 5 6 7 8
Installation
Terminal No.
TB1–1
TB1–2
TB1–3
TB1–4
TB1–5
TB1–6
TB1–7
TB1–8
Name Description
LINE 1 TIP IN
LINE 1 RING IN
LINE 1 TIP OUT
Connects to the Tip In connector on the telco side of an RJ31X block via an RJ–12 modular cable.
Connects to the Ring In connector on the telco side of an
RJ31X block via an RJ–12 modular cable.
Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ–12 modular cable.
LINE 1 RING OUT Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ–12 modular cable.
LINE 2 TIP IN Connects to the Tip In connector on the telco side of an RJ31X block via an RJ–12 modular cable.
LINE 2 RING IN Connects to the Ring In connector on the telco side of an
RJ31X block via an RJ–12 modular cable.
LINE 2 TIP OUT Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ–12 modular cable.
LINE 2 RING OUT Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ–12 modular cable.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
2.21
Installation
Connecting a PT–1S printer
For control panels with only a printer
1. Locate the printer in the same room as and within 20 ft of the panel (printer wiring is nonsupervised and power-limited).
2. Wire the printer cable to the RS232 connections on the power supply card then plug the cable into the printer.
3. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details.
For control panels with a printer and a CDR–
3 Bell Coder module
1. Install the IOP3A in the same enclosure as the CDR–3. Refer to appendix B.
2. Wire the IOP3A to the CDR–3.
3. Wire the printer cable to the RS232 connections on the IOP3A then plug the cable into the printer.
4. Configure the IOP3A as follows:
JP1 = 2–3
JP2 = ON
JP3 = ON
JP4 = ON
SW1 = UP
5. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details.
PS6 TB1–18
PS6 TB1–17
PS6 TB1–16
CDR–3 TB2–4
CDR–3 TB2–5
CDR–3 TB2–6
CDR–3 TB2–7
PS6 TB1–17
COM–COM
TX–RX
RX–TX
DB–25P
REAR VIEW
3
2
7
TO
PT–1S
TB1
1
2
3
4
5
6
DB–25P
REAR VIEW
TO
PT–1S
7 3 2
IOP3A
COM–COM
RxD–TxD
TxD–RxD
TB3
1
2
3
4
TB2
2.22
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Installation
Installing standby batteries
For batteries rated at 10 Ah or less
1. Place the batteries in the bottom of the control panel.
2. Wire the batteries to the
PS6.
Notes
Do not run wires through the bottom knock-outs when batteries are installed in the control panel.
Battery wiring is supervised and nonpower-limited.
Maintain a 1/4-inch separation between powerlimited and nonpower-limited wiring at all times.
For batteries rated greater than 10 Ah
1. Place the batteries in a
BC-1 Battery Cabinet. The cabinet must be mounted within 3 ft of the control panel, in the same room, and connected with conduit.
2. Wire the batteries to the
PS6.
Note: Install, maintain, and test standby batteries in accordance with NFPA 72.
BC-1
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
+ –
+ –
+ + – –
2.23
Installation
Connecting a service computer
Connection of a service computer to the control panel requires programming cable P/N 260097, ordered separately.
Connection of a service computer to a remote annunciator requires programming cable P/N 360136 and a
RJ–11 to DB9 adapter P/N 240507, both ordered separately.
DB-9F
REAR VIEW
RTS
RX
PS6
TX
COM
NOT USED
1
P/N 260097
9
2.24
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 3
Operating instructions
Summary
This chapter provides instructions for operating the control panel.
Content
Instructions for the Level 1 operator (public mode access) • 3.2
Instructions for the Level 2 operator (emergency mode access) • 3.5
Instructions for the Level 3 operator (maintenance mode access) • 3.7
Instructions for the Level 4 operator (service mode access) • 3.10
QuickReference list • 3.11
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.1
Operating instructions
Instructions for the Level 1 operator (public mode access)
Tasks that do not require you to log in
What is it you want to do This is how you do it
Silence the panel trouble buzzer Press Panel Silence.
Get a list of all the active points on a panel
1. Press Status.
2. Choose All Active to get a list of all the active points.
Choose Alarm to get a list of only the active alarm points.
Choose Supervisory to get a list of only the active supervisory points.
Choose Monitor to get a list of only the active monitor points.
3. Press DEL to backspace the cursor then enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Identify points that are in trouble 1. Press Status.
2. Choose Trouble
3. Press DEL to backspace the cursor then enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Identify active points in a Service
Group that is being tested
1. Press Status.
2. Choose Test.
3. Press DEL to backspace the cursor then enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
3.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Operating instructions
Tasks that do not require you to log in
What is it you want to do This is how you do it
Identify points that are disabled 1. Press Status.
2. Choose Disabled Pts.
3. Press DEL to backspace the cursor then enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Identify output devices that are turned on
1. Press Status.
2. Choose Outputs
3. Press DEL to backspace the cursor then enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Verify power supply voltage levels 1. Press Status.
2. Choose Internal
3. Press Enter.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%)
1. Press Menu.
2. Choose Reports > Maintenance > Dirty>80%.
3 Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.3
Operating instructions
Tasks that do not require you to log in
What is it you want to do This is how you do it
Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%)
1. Press Menu.
2. Choose Reports > Maintenance > Dirty>20%.
3 Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Get the attributes for a single smoke detector
1. Press Menu.
2. Choose Reports > Maintenance > Single Device.
3. Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Get the attributes for every smoke detector on a single SLIC
Perform a lamp test
1. Press Menu.
2. Choose Reports > Maintenance > Card Devices.
3 Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
1. Press Menu.
2. Choose Test > Lamp Test.
3.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Operating instructions
Instructions for the Level 2 operator (emergency mode access)
Tasks that require you to log on as a Level 2 operator
What is it you want to do This is how you do it
Log onto the panel as a Level 2 operator
Turn the Enable Controls key 1/4 of a turn clockwise.
— or —
1. Press Menu.
2. Choose Login then enter the password required for Level 2 access.
Reset the panel Press System Reset.
Turn off alarm signaling circuits when the panel is in alarm (Alarm
Silence)
Press Alarm Silence.
Turn on alarm signaling circuits when the panel is not in alarm (Drill)
Press Drill then Enter.
Get a list of all events processed on a panel
1. Press Menu.
2. Choose Reports > History.
3. Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Change the password required for
Level 1 access
1. Press Menu.
2. Choose Program > Edit Password > Level 1.
3. Enter the new password.
Switch automatic detectors to their alternate sensitivity settings
1. Press Menu.
2. Choose Activate > Alt Sens.
Switch automatic detectors to their primary sensitivity settings
1. Press Menu.
2. Choose Restore > Prm Sens.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.5
Operating instructions
Tasks that require you to log on as a Level 2 operator
What is it you want to do This is how you do it
Distribute event records according to their alternate message routing
1. Press Menu.
2. Choose Activate > Alt Msg Route.
Distribute event records according to their primary message routing
1. Press Menu.
2. Choose Restore > Prm Msg Route.
Disable a Zone
Enable a Zone
1. Press Menu.
2. Choose Disable > Zone.
3. Select a Zone from the pick list then press Enter.
1. Press Menu.
2. Choose Enable > Zone.
3. Select a Zone from the pick list then press Enter.
Disable a device
Enable a device
1. Press Menu.
2. Choose Disable > Device.
3. Enter the device address, where:
PP is the panel number (01)
CC is the card number
DDD is the circuit or device number
1. Press Menu.
2. Choose Enable > Device.
3. Enter the device address, where:
PP is the panel number (01)
CC is the card number
DDD is the circuit or device number
3.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Operating instructions
Instructions for the Level 3 operator (maintenance mode access)
Tasks that require you to log on as a Level 3 operator
What is it you want to do This is how you do it
Log onto the panel as a Level 3 operator
1. Press Menu.
2. Choose Login then enter the password required for Level 3 access.
Change the password required for
Level 2 access
1. From the Main Menu, select Program.
2. Select Edit Password.
3. Select Level 2 then enter the new password.
Get a list of all the hardware and software components installed on a panel and their revision levels
1. Press Menu.
2. Choose Reports > Revision.
3. Enter the panel number.
4. Choose Display to view the list on the CPU/Display unit.
— or —
Choose Printer to print the list.
Set the system time and date 1. Press Menu.
2. Choose Program > Time/Date.
3. Choose Enter Time, then press DEL until the display shows
HHMMSS.
Enter the time in 24–hour format where HH is the hour, MM is the minutes, and SS is the seconds.
Example: To set the time for 1:00 p.m., enter 130000.
4. Select Enter Date.
Enter the date where MM is the number of the month, DD is the date, and YYYY is the year.
Example: To set the date for January 1, 2001, enter
01012001.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.7
Operating instructions
Tasks that require you to log on as a Level 3 operator
What is it you want to do This is how you do it
Turn on an output circuit
Note: A typical system may assign manual override functions a high priority level, alert responses a low priority, and alarm responses a medium priority.
1. Press Menu.
2. Choose Activate > Output.
3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number.
4. Choose Steady to change the circuit's output to always on
Choose 20 BPM to change the circuit's output to a 20 beat per minute signal rate (On = 2–1/2 s; Off = 2–1/2 s).
Choose 120 BPM to change the circuit's output to a 120 beat per minute signal rate (On = 1/4 s; Off = 1/4 s).
Choose Temporal to change the circuit's output to a 3–3–3 pattern.
5. Choose High Priority.
Turn off an output circuit
Turn an LED on
1. Press Menu.
2. Choose Restore > Output.
3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number.
4. Choose Off.
1. Press Menu.
2. Choose Activate > LED.
3. Choose one of the following:
Steady to turn the LED on
Fast Blink to have the LED flash at a fast rate
Slow Blink to have the LED flash at a slow rate
4. Enter the LED's address where GG is the group number,
SS is the switch number, and L is the LED number.
Turn an LED off 1. Press Menu.
2. Choose Restore > LED.
3. Choose Off
4. Enter the LED's address where GG is the group number,
SS is the switch number, and L is the LED number.
3.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Operating instructions
Tasks that require you to log on as a Level 3 operator
What is it you want to do This is how you do it
Disable or enable an And Group,
Matrix Group, or Time Control
1. Press Menu.
2. Choose Disable or Enable.
3. Choose And if an And group, Matrix if a Matrix group, or
Time Control if a time control.
4. Pick a group from the appropriate list and press Enter.
Disable or enable a switch on a zone display
1. Press Menu.
2. Choose Disable > Switch.
— or —
Enable > Switch.
3. Enter the switch address, where GG is the group number, and SS is the switch number.
Disable or enable the mapping function on an SLIC
1. Press Menu.
2. Choose Disable > Loop Mapping.
— or —
Enable > Loop Mapping.
3. Enter the card address for the SLIC.
Start a Service Group test 1. Press Menu.
2. Choose Test > Start Test.
3. Select a Service group from the pick list and press Enter.
Cancel a Service Group test
Note: The panel automatically resets after you cancel a test.
1. Press Menu.
2. Choose Test > Cancel Test.
2. Select a Service group from the pick list and press Enter.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.9
Operating instructions
Instructions for the Level 4 operator (service mode access)
What is it you want to do
Log onto the panel as a Level 4 operator
This is how you do it
1. Press Menu.
2. Choose Login then enter the password required for Level 4 access.
Change the password required for
Level 3 access
1. Press Menu.
2. Choose Program > Edit Password > Edit Password
3. Choose Level 3 then enter the new password.
Change the password required for
Level 4 access
1. Press Menu.
2. Choose Program > Edit Password > Edit Password
3. Choose Level 4 then enter the new password.
Restart a panel 1. Press Menu.
2. Choose Program > Restart > Panel
3. Enter the panel's address.
Reset the alarm history counter 1. From the Main Menu, select Program.
2. Select Reset.
3. Enter the panel's address.
3.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Operating instructions
QuickReference list
What is it you want to do
Change smoke detector sensitivity settings to their alternate values
Change smoke detector sensitivity settings to their primary values
Change the current state of an LED (manual override)
Change the current state of an output circuit (manual override)
Change the password required for Level 1 access
Change the password required for Level 2 access
Change the password required for Level 3 access
Change the password required for Level 4 access
Disable or enable a device
Disable or enable a switch on a zone display
Disable or enable a zone
Disable or enable all the devices on a single card
Disable or enable an And Group, Matrix Group, or Time Control
Disable or enable the mapping function on an SLIC
Get a list of all the active points on a panel
Get a list of all the hardware and software components installed on a panel and their revision levels
Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%)
Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%)
Get the attributes for a single smoke detector
Get the attributes for all the smoke detectors on a single SLIC
Identify output devices that are turned on
Identify active points in a Service Group that is being tested
Identify points that are disabled
Identify points that are in their active state
Identify points that are in trouble
Log onto the panel as a Level 2 operator
Log onto the panel as a Level 3 operator
Log onto the panel as a Level 4 operator
Perform a lamp test
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
L1
Required access level
ü
ü
ü
L2
ü
ü
ü
ü
ü
ü
L3
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
L4
ü ü ü ü
ü ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
3.11
Operating instructions
What is it you want to do
Reset the alarm history counter
Reset the panel
Restart the panel
Restore an LED to its previous state
Restore an output circuit to its previous state
Route off-normal signals to the alternate set of panels used to post messages
Route off-normal signals to the primary set of panels used to post messages
Set the system time and date
Silence the panel trouble buzzer
Start a Service Group test
Cancel a Service Group test
Turn off alarm signaling circuits when the panel is in alarm (Alarm
Silence)
Turn on alarm signaling circuits when the panel is not in alarm (Drill)
Verify power supply voltage levels
ü
ü
L1
Required access level
L2 L3
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
L4
ü ü ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
3.12
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 4
Programming instructions
Summary
This chapter provides instructions for programming the fire alarm system from the front panel. Worksheets are provided at the end of the chapter to use as programming aids and to document the system programming.
Content
Overview • 4.2
QuickStart setup instructions • 4.4
Customizing the system configuration • 4.13
Setting up an Output Group • 4.21
Setting up a Zone • 4.24
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.1
Programming instructions
Overview
What is a Zone?
A Zone is a function in the system software that initiates an active response based on a single alarm event. Firewall designations, planned evacuation criteria, architectural design, and other factors all contribute to how the system designer divides the protected premises into zones.
ZONE 1
FACP
ZONE 2 ZONE 3
J
What is an Output Group?
An Output Group is a function in the system software that establishes the correlation between input circuits and responses. When an input changes states, the condition of the input determines which response the panel runs. For example, a smoke detector initiates the Active response when it signals an alarm condition but initiates the Trouble response when removed from its base.
ZONE 1
Output 1
Active
Trouble
Output 2
Active
Trouble
4.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 4-1: Programmable features
Feature
And Groups
Output Groups
Matrix Groups
Service Groups
Time Controls
Zones
LED Configure
Switch Configure
SIGA - Prealarm
SIGA - Sensitivity levels
Alarm Verification
Coded Operation
Custom Messages
Message Routing
SIGA - Diagnostics
AC Delay
Two-stage Operation
General Alarm Inhibit
Market Place
Card Configuration
Language
Zone Resound Inhibit
Drill Programming
Alarm Silence Programming
Waterflow Silence
Supervisory Duct
Enable Trouble Reminder
Auto Alarm Signal Silence
Alarm Signal Silence/Reset Inhibit
Panel Silence Resound Time
SIGA–REL
Front Panel Programming
(FPP)
No
Yes
No
Limited
No
Yes
Limited
Limited
Yes
Yes
Yes
Yes
Yes (requires bar code wand)
No
No
No
No
No
No
No
Yes
No
No
No
Yes
No
No
No
No
No
No
Programming instructions
Configuration Utility
(CU)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.3
Programming instructions
QuickStart setup instructions
Step 1:
Read this before proceeding
Note: If at any time you get an
Exception Event while programming the system, note the error code, and then contact EST Technical Services at 6411 Parkland Drive, Sarasota, FL
34243 or at 1-800-655-4497.
To clear the Exception Event, press
Alarm Silence while the event is displayed. You may have to reset the panel to display the event again.
This procedure uses the AutoLearn and AutoLoop utilities to automatically configure the system. The AutoLearn utility configures the option cards. The AutoLoop utility configures the circuits on the Signature loop.
Caution: Running the AutoLearn utility deletes the existing panel programming. If you have already programmed the system, running AutoLearn requires you to re-enter everything again from the beginning.
If you have a dialer installed, the AutoLearn utility requires you to program the DLD before exiting. Be sure to have the following:
• Subscriber account numbers, telephone numbers, and transmission formats obtained from the CMS (Central
Monitoring Station). Appendic C provides a list of Contact ID event codes.
• A completed copy of the DLD Programming Worksheet
(Figure 4-1).
After you have finished using the AutoLearn and AutoLoop utilities to configure the system, you can either:
• Customize the system programming
• Go to step 11 and Save and Sync.
Step 2:
Apply power to the system
1. Verify that each circuit card installed in the control panel has a unique card address.
2. Apply power to the control panel and to all the remote annunciators.
After applying power, the panel CPU performs a diagnostic check in the background. You can not begin programming until this finishes and the AutoLearn option becomes available.
4.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Step 3:
Assign Panel ID numbers to the remote annunciator panels
On each remote annunciator panel:
1. Press Menu.
2. Choose Login then enter the password required for Level 4 access (default is 4444).
3. Choose Program > Configure > AutoLearn.
4. Press Del twice then enter an unused Panel ID from 02 to
09 (01 is reserved for the control panel).
5. Enter the number of panels that are connected to the
RS485 riser, including the control panel. This is your maximum number of panel addresses.
6. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter.
Note: The wiring configuration must be the same for all panels.
Step 4:
AutoLearn the control panel.
Note: Before running the AutoLearn utility, make sure you have not installed more cards than the system allows.
On the control panel:
1. Press Menu.
2. Choose Login then enter the password required for Level 4 access (default is 4444).
3. Choose Reports > Revision > Enter > Display. Verify all the cards installed in the cabinet appear in the list.
4. Press Menu then choose Program > Configure >
AutoLearn.
5. Enter 01 for the Panel ID.
6. Enter the number of panels that are connected to the
RS485 riser, including the control panel. This is your maximum number of panel addresses.
7. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter.
If you do not have a DLD card installed, the system will automatically reboot after the AutoLearn utility configures the system. Go to step 10.
If you do have a DLD card installed, go to step 5.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.5
Programming instructions
Step 5:
Set up the receiver call-in numbers and retry attempts
Step 6:
Set up the subscriber accounts
1. Choose #'s of CMS then choose the number of CMS receivers that the DLD may dial into over the public switched telephone network.
2. Choose CMS Phone # then enter the telephone numbers of the CMS receivers:
§ Choose Rcvr 1 Prim # then enter the first number to try for the first CMS receiver.
§ Choose Rcvr 1 Sec # then enter the second number to try for the first CMS receiver.
§ Choose Rcvr 2 Prim # then enter the first number to try for the second CMS receiver.
§ Choose Rcvr 2 Sec # then enter the second number to try for the second CMS receiver.
§ Choose Exit.
3. Choose Retry Count then enter the number of times you want the dialer to attempt to contact the CMS receiver.
1. Choose Accounts then <New> to set up a new account
— or —
Select an account number then press Enter.
2. Choose Account # then enter the number of the subscriber account.
3. Choose Formats then choose the required transmission format.
4. Choose Test–Normal then enter the character string to send when the control panel is normal.
5. Choose Test–Abnormal then enter the character string to send when the control panel is off-normal.
6. Choose Test Time then enter when you want the dialer to transmit the test string in 24-hour format.
7. Choose CMS then choose which CMS receiver to dial.
This is the receiver that holds the account.
8. Choose Exit.
4.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Step 7:
Edit the default alarm messages
Note: The dialer automatically sends the default alarm message for active alarm inputs that are not programmed to initiate a dialer response.
1. Choose Default Msgs > Alarm.
2. Choose Account then select the subscriber account you want to receive the message.
3. Choose Active Msg then enter the message you want sent for alarm activation events.
For example, for Contact ID enter 111000000
4. Choose Restore Msg then enter the message you want sent for alarm restoration event.
For example, for Contact ID enter 311000000
5. Choose Exit.
Step 8:
Edit the default trouble messages
Note: The dialer automatically sends the default trouble message for inputs that signal a trouble but are not programmed to initiate a dialer response.
1. Choose Default Msgs > Trouble.
2. Choose Account then select the subscriber account you want to receive the message.
3. Choose Active Msg then enter the message you want sent for trouble activation events.
For example, for Contact ID enter 130000000
4. Choose Restore Msg then enter the message you want sent for trouble restoration event.
For example, for Contact ID enter 330000000
5. Choose Exit.
Step 9:
Edit the default supervisory messages
Note: The dialer automatically sends the default supervisory message for active supervisory inputs that are not programmed to initiate a dialer response.
1. Choose Default Msgs > Supervisory.
2. Choose Account then select the subscriber account you want to receive the message.
3. Choose Active Msg then enter the message you want sent for supervisory activation events.
For example, for Contact ID enter 120000000
4. Choose Restore Msg then enter the message you want sent for a supervisory restoration event.
For example, for Contact ID enter 220000000
5. Choose Exit.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.7
Programming instructions
Step 10:
AutoLoop the loop controller cards
Run the AutoLoop utility on each loop controller installed in the control panel.
Caution: When the system reboots, the loop controller reinitializes the loop. If you attempt to run the AutoLoop utility during this time, you could corrupt the project database.
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4 access.
3. Choose Program > Configure.
If the loop is still initializing, do not proceed until loop initialization has finished.
4. Choose Cards > Edit, then enter the card number for the loop controller.
5. On the Edit Cards menu, choose AutoLoop.
6. If the number of detector and module addresses on the display match the number installed on the loop, press
Enter to accept, then wait while the database is updated.
If not, press Del to cancel. You must correct the problem before continuing with this loop.
7. On the SLIC menu, choose Exit.
8. For each additional loop controller, repeat steps 4–7.
9. Choose Exit.
Step 11:
Saving the project database
Tip: Only Save and Sync after you have finished programming the control panel and you want to update the project databases in the remote annunciators.
At this point, you have configured the project database for a general alarm system. Refer to Table 4-2, Table 4-3 and
Table 4-4 for initial system settings.
If you want to accept the general alarm system configuration, choose Save and Sync.
If you want to make changes to the system configuration, choose Save, and then make your changes. See Customizing
the system configuration. After making all of your changes:
1. Press Menu.
2. Choose Login then enter the password required for Level 4 access.
3. Choose Program > Configure > Exit.
4. Choose Save and Sync.
Note: If the local AHJ requires a hard copy of your site programming, use the QuickStart Configuration Utility to retrieve the database from the panel and print the required information.
4.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Table 4-2: AutoLearn initial project settings
Option Value Description
Alarm Silence
Drill
Drill Activation Type
Alarm Signal
Silence/Reset Inhibit
Buzzer Reminder Time
AC Power Trouble
Delay
Two-stage Timer
Zone Resound Inhibit
Primary Routing
Alternate Routing
Language
Relay 1 Type
Relay 2 Type
Relay 3 Type
Relay 4 Type
Audible only
Audible only
Steady
None
Indefinitely
6 h
0 s (UL)
300 s (ULC)
No
All Cabinets
All Cabinets
English (U.S.)
Alarm
Supervisory
Trouble
Monitor
Turns off Audible and Common Alarm Output circuits when someone presses Alarm Silence.
Turns off Audible and Common Alarm Output circuits when someone presses Drill.
The Drill signal is a constant signal.
Alarm Silence or Reset functions are not inhibited. You can turn off (silence) notification circuits or reset the panel any time after notification circuits are activated.
The panel trouble buzzer remains silenced until the control panel processes a new off-normal signal.
The panel will operate on battery power for 6 hours before signaling a trouble condition.
The panel will turn on notification circuits immediately after processing an alarm signal (UL) or after 5 minutes
(ULC).
Turn silenced NAC circuits back on if an active alarm input circuit remains in the active condition after resetting the panel.
Distribute event records to all panels in the system when primary routing is activated.
Distribute event records to all panels in the system when alternate routing is activated.
U.S. English displayed on CPU/Display.
Alarm events cause the contact positions of Relay 1 on the PS6 to change positions.
Supervisory events cause the contact positions of Relay
2 on the PS6 to change positions.
Trouble events cause the contact positions of Relay 3 on the PS6 to change positions.
Monitor events cause the contact positions of Relay 4 on the PS6 to change positions.
Edit?
CU
CU
CU
FPP/CU
No
FPP/CU
CU
No
CU
CU
No
No
No
No
CU
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.9
Programming instructions
Table 4-3: AutoLearn initial card configuration settings
Card Circuit Address Device type Edit?
SLIC NAC 1
NAC 2
270
271
Visible
Common Alarm
Output
FPP/CU
FPP/CU
NAC 1
Diagram
NAC 2
Card Circuit
ZB16–4 Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
Z9
Z10
Z11
Z12
Z13
Address
008
009
010
011
012
013
001
002
003
004
005
006
007
Z14 014
Z15
Z16
015
016
Device type
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Common Alarm
Output
Common Alarm
Output
Visible
Visible
Edit?
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
Z12
Z11
Z10
Z4
Z3
Z2
Z1
Diagram
Z13
Z14
Z15
Z16
Z5
Z6
Z7
Z8
Z9
4.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Table 4-3: AutoLearn initial card configuration settings (cont.)
Card Circuit Address Setting Edit?
ZA8–2 Zone 1
Zone 2
Zone 3
Zone 4
001
002
003
004
Zone 5
Zone 6
Zone 7
Zone 8
005
006
007
008
Alarm
Alarm
Alarm
Common Alarm
Output
Alarm
Alarm
Alarm
Visible
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
Zone 1
Zone 2
Zone 3
Zone 4
Zone 8
Zone 7
Zone 6
Zone 5
Diagram
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.11
Programming instructions
Table 4-4: AutoLoop initial settings for SIGA devices
SIGA Device Personality Description
SIGA–IPHS, –PHS,
–PS, –IS none none
Smoke detector settings as follows:
Sensitivity: Least
Verification: None
Prealarm: None
Heat detector settings not programmable SIGA–HFS, HRS,
–IM
Single-stage pull stations
Dual-stage pull stations
01
01
Class B Alarm Latching
Class B Alarm Latching
SIGA–APS
SIGA–(M)CC1(S)
01
03
03
05
Class B Alarm Latching
Class B Active Non-Latching
Class B Active Non-Latching
Riser selector
Device Type
Alarm
Alarm
Pull
SIGA–(M)CC2
SIGA–(M)CR(R)
SIGA–(M)CT1
SIGA–(M)CT2
SIGA–DTS
SIGA–IO
SIGA–MAB
SIGA–UM
SIGA–MM1
SIGA–WTM
SIGA–(M)RM1
07
08
01
01
01
01
31
00
00
00
00
03
02
04
23
Dual riser selector
Dry contact
Class B Alarm Latching
Class B Alarm Latching
Class B Alarm Latching
Class B Alarm Latching
Monitor Input/Output N.O.
Class A Signal Output not used
Class A Signal Output not used
Class B Active Non-Latching
Class B Active Latching - Delayed
Class B Active Latching.
Riser monitor - 24 Vdc
Monitor
Pull
Monitor
Monitor
Common Alarm
Output
Common Alarm
Output
Nonsupervised
Output
Alarm
Alarm
Alarm
Alarm
Monitor
Monitor
Monitor
Monitor
Alarm
Supervisory
Monitor
Edit?
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
FPP/CU
Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from the previous system as the initial settings for a general alarm system.
4.12
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Customizing the system configuration
You can customize the system configuration, if your requirements exceed that of the general alarm system created using the AutoLearn and
AutoLoop utilities.
Before you can make any changes to the system programming, you must log onto the system to start an editing session.
The control panel has a watchdog timer that kicks you out of an editing session after a period of inactivity. If this happens, you will have to log in again to continue.
After you finish customizing the system configuration, save your changes, and then test the system. After everything checks out then Save and Sync to copy the database to the remote annunciators.
WARNING: Entering Edit mode (choosing
Configure on the Program menu) disables the control panel and leaves the premises unprotected until you exit Edit mode.
To start an editing session:
1. Press Menu.
2. Choose Login then enter the password required for Level 4 access.
3. Choose Program > Configure.
What is it you want to do
Make information about the installer available on the CPU/Display
AutoLearn default: No text
This is how you do it
1. On the Configure menu, choose System > User
Labels.
2. Choose Facility Name, scan in the name of the project, and then press Enter.
3. Choose Inst Company, scan in the name of the installing company, and then press Enter.
4. Choose Phone Number, scan in the telephone number to call for service-related issues, and then press Enter.
5. Choose Programmer, scan in the name of the person that programmed the system, and then press Enter.
6. Choose Exit.
Set how long notification circuits must stay on before pressing Alarm Silence can turn them off or pressing Reset can reset the panel
AutoLearn default: None (no delay)
1. On the Configure menu, choose System >
ALM/RST Inhib.
2. Select a time delay from the pick list then press
Enter.
Set how long the panel must wait before signaling an ac power failure
AutoLearn default: 0 (no delay)
1. On the Configure menu, choose System > AC
Power Dly.
2. Select a time delay from the pick list then press
Enter.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.13
Programming instructions
What is it you want to do
Enter location message text for a circuit on a
ZB16–4 or ZA8–2 card
This is how you do it
1. On the Configure menu, choose Card, and then enter the card address number.
2. Choose Text Message, scan in the text, and then press Enter.
3. Choose Exit.
Change the device type of a circuit on a ZB16–
4 or ZA8–2 card
WARNING: Changing the device type of an input circuit to a device type for an output circuit removes the circuit from all input logic groups.
Changing the device type of an output circuit to a device type for an input circuit removes the output circuit from all output groups.
1. On the Configure menu, choose Card, and then enter the card address number.
2. Choose Device Type, select the device type from the pick list, and then press Enter.
3. Choose Exit.
Change the device type of the NAC circuits on the SLIC
AutoLearn defaults: NAC1 device type is Visible;
NAC 2 device type is Common Alarm Output
Common Alarm Output circuits turn on automatically when an input signals an alarm event. Visible and Audible output circuits must be placed in an Output Group in order to turn them on. The AutoLearn utility automatically places
Visible circuits in an Output Group
WARNING: Changing an output circuit from a
Common Alarm Output device type to an Audible device type does not automatically place the
Audible circuit in an Output Group. You must add the Audible Circuit to the Output Group manually or the Audible circuit will not turn on.
1. On the Configure menu, choose Cards > Edit then enter the card address number.
2. Choose Config Card.
3. Choose NAC 1 then choose the device type for
NAC 1.
4. Choose NAC 2 then choose the device type for
NAC 2.
5. Choose Exit > Save Edits, then wait while the database is updated.
4.14
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
What is it you want to do
Change the performance class of the Signature loop wiring
AutoLearn default: Wiring is Class B.
This is how you do it
1. On the Configure menu, choose Cards > Edit then enter the card address number.
2. Choose Config Card.
3. Choose Wiring Class then choose how the loop is wired to the SLIC.
4. Choose Exit > Save Edits, then wait while the database is updated.
Enter location message text for an automatic detector
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.
3. Choose Message then scan in the text that you want sent when the detector signals an event.
4. Choose Exit > Save Edits.
Change the Alarm Sensitivity setting of a smoke detector
WARNING: Selection of the appropriate detector technology and sensitivity settings should result from a careful analysis of the hazard, environmental conditions, and expected results.
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.
3. Choose Sensitivity then choose the alarm sensitivity setting you want the detector to use.
Refer to Table 4-5 and Table 4-6.
4. Choose Exit > Save Edits.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.15
Programming instructions
What is it you want to do
Change the Alarm Verification setting of a smoke detector
Change the Prealarm setting of a smoke detector
This is how you do it
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.
3. Choose Verification then choose the length of the alarm verification period.
4. Choose Exit > Save Edits.
WARNING: Prealarm obscuration levels below
80% should not be used without full knowledge of the possible consequences.
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the serial number of the detector.
3. Choose Pre-Alarm then choose the warning threshold setting you want the detector to use.
Refer to Table 4-5 and Table 4-6.
4. Choose Exit > Save Edits.
4.16
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Table 4-5: %Obscuration levels for SIGA–IPHS, SIGA–PS, and SIGA–PHS
Alarm Obscuration Levels
Sensitivity Settings
%Obscuration
Prealarm Settings
95%
90%
85%
80%
Most
1.00%
75%
70%
65%
60%
55%
50%
45%
40%
35%
30%
25%
20%
15%
10%
5%
0.20%
0.15%
0.10
0.05
Note: Shaded prealarm settings not available for SIGA–IPHS
0.55%
0.50%
0.45%
0.40%
0.35%
0.30%
0.25%
0.95%
0.90%
0.85%
0.80%
0.75%
0.70%
0.65%
0.60%
0.80%
0.70%
0.60%
0.50%
0.40%
0.30%
0.20%
0.10%
1.50%
1.40%
1.30%
1.20%
1.10%
1.00%
0.90%
More
2.00%
Normal
2.50%
Less
3.00%
Prealarm Obscuration Levels
1.90%
1.80%
1.70%
1.60%
2.38%
2.25%
2.13%
2.00%
2.85%
2.70%
2.55%
2.40%
1.88%
1.75%
1.63%
1.50%
1.38%
1.25%
1.13%
2.25%
2.10%
1.95%
1.80%
1.65%
1.50%
1.35%
1.00%
0.88%
0.75%
0.13%
0.50%
0.38%
0.25%
0.13%
1.20%
1.05%
0.90%
0.31%
0.60%
0.45%
0.30%
0.15%
Table 4-6: %Obscuration levels for SIGA–IS
Sensitivity Settings
%Obscuration
Prealarm Settings
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
Most
0.7%
0.67%
0.63%
0.60%
0.56%
0.53%
0.49%
0.46%
0.42%
0.39%
0.35%
More
Alarm Obscuration Levels
Normal Less
1.00% 1.20% 1.40%
Prealarm Obscuration Levels
0.95% 1.14% 1.33%
0.90%
0.85%
0.80%
0.75%
1.08%
1.02%
0.96%
0.90%
1.26%
1.19%
1.12%
1.05%
0.70%
0.65%
0.60%
0.55%
0.50%
0.84%
0.78%
0.72%
0.66%
0.60%
0.98%
0.91%
0.84%
0.77%
0.70%
Least
1.6%
1.52%
1.44%
1.36%
1.28%
1.20%
1.12%
1.04%
0.96%
0.88%
0.80%
Least
3.50%
1.93%
1.75%
1.58%
1.40%
1.23%
1.05%
0.88%
3.33%
3.15%
2.98%
2.80%
2.63%
2.45%
2.28%
2.10%
0.70%
0.53%
0.35%
0.18%
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.17
Programming instructions
What is it you want to do
Enter location message text for a circuit on a
SIGA module
This is how you do it
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.
3. For a single-address module or the first address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address module, choose Device 2.
4. Choose Message, scan in the text, and then press Enter.
5. Choose Exit.
Change the device type for a circuit on a SIGA module
Note: The device types shown in the pick lists vary depending on the SIGA module. The device types shown in the pick lists for the second address of a dual-address module also vary depending on the device type chosen for the first address.
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.
3. For a single-address module or the first address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address module, choose Device 2.
4. Choose Type, select a device type from the pick list, and then press Enter.
5. Choose Exit.
4.18
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
What is it you want to do
Change the personality code for a circuit on a
SIGA module
Note: The personality codes shown in the pick lists vary depending on the SIGA module and the chosen device type.
This is how you do it
1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.
2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.
3. For a single-address module or the first address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address module, choose Device 2.
4. Choose Personality, select a personality code from the pick list, and then press Enter.
5. Choose Exit.
Enable the loop controller mapping function
AutoLearn default: Mapping disabled
1. Press Menu.
2. Log onto the panel as a Level 4 operator.
3. Choose Enable > Loop Mapping.
4. Enter the card number of the SLIC that connects to the device you want to replace.
Wait until mapping finishes before continuing.
5. Choose Cards > Edit.
6. Enter the card number of the SLIC that connects to the device you want to replace.
7. Choose Accept Map.
If actual and expected data for detectors and modules are the same, press Enter.
8. Choose Exit > Exit > Save.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.19
Programming instructions
Table 4-7: Device type descriptions
Alarm
Alarm Output
Audible
Heat
Monitor
Output
Pull
Supervisory
Tamper
Verified Smoke
Visible
Water Flow
Device type assigned to IDC circuits that connect to automatic or a combination of automatic and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events.
Device type assigned to IDC/NAC circuits that connect to notification appliances that you want turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn off when you press Alarm Silence and turn on when you press Drill.
Device type assigned to IDC/NAC circuits that connect to audible notification appliances
(horns). Audible circuits turn off when you press Alarm Silence and turn on when you press
Drill.
Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events.
Device type assigned to IDC circuits that connect to monitor-signal initiating devices that monitor the operation of ancillary system functions. Monitor circuits signal Monitor events.
Device type assigned to IDC/NAC circuits that supervise their output wiring for opens and shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press
Drill.
Device type assigned to IDC circuits that connect to manually operated alarm-signal initiating devices. Pull circuits signal Pull Station events.
Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect abnormal conditions that could make the sprinkler system inoperative or ineffective.
Supervisory circuits signal Supervisory events.
Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect when someone tampers with a component of the sprinkler system. Tamper circuits signal
Tamper events.
Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire condition is first detected then Alarm Active events after verifying the fire condition exists.
Device type assigned to IDC/NAC circuits that connect to visual notification appliances
(strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you press Drill unless programmed to do so.
Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.
4.20
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Setting up an Output Group
Before you begin Before you begin, you should complete an Output Group
Programming Worksheet (Figure 4-8) for each Output group.
Keep a copy for your records.
To set up an Output Group:
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4 access.
3. Choose Program > Configure > Output.
4. To program a new Output group, choose Add.
— or —
To edit an existing Output group, choose Edit, select the group from the pick list, and then press Enter.
5. Add the responses.
6. After you finish entering the responses, you should review them to make sure they are correct.
Adding a response that activates an output circuit
1. Choose Responses.
2. Choose Active or Trouble
3. Choose Add > Relay, then enter the circuit address where
CC is the card number and DDD is the circuit number.
4. Choose the activation setting.
5. Choose Exit > Save Edits.
Adding a response that activates a delay
1. Choose Responses.
2. Choose Active or Trouble.
3. Choose Add > Delay.
4. Choose Delay Type, then choose when to initiate the delay response.
5. Choose Delay Time, press Del four times, and then enter how many seconds you want the delay to last.
6. Choose Exit > Save Edits.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.21
Programming instructions
Adding a response that sends a dialer string
Reviewing your responses
1. Choose Responses.
2. Choose Active or Trouble.
3. Choose Add > Dialer.
4. Select an account number from the pick list, and then press
Enter.
5. Choose Send On, select when to send the dialer string from the pick list, and then press Enter.
6. Choose Priority, select the priority classification from the pick list, and then press Enter.
7. Choose String, then enter the message you want sent.
8. Choose Exit > Save Edits.
1. Choose Review.
2. Choose Active to review the active responses.
— or —
Choose Trouble to review the trouble responses.
4.22
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Table 4-8: Response code definitions
Response Description
PppCccDddd 1234 This is what the panel display looks like when you review a response for an output circuit.
P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number)
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =
Disable, D = Delay)
3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)
4 is the command attribute (S = Set, R = Reset, W = 20 bpm, F = 120 bpm, T =
Temporal)
PppCccDddd 1234
Delay: ssss 1
This is what the panel display looks like when you review a response for an LED.
P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number)
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =
Disable, D = Delay)
3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)
4 is the command attribute (S = Steady, R = Restore, W = Slow Blink, F = Fast
Blink)
This is what the panel display looks like when you review a response for delay.
ssss is the amount of delay in seconds
1 is the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
ACCT12QEEEGGPPP
— or —
ACCT12PP
This is what the panel display looks like when you review a response for dialer string.
ACCT is the 4-digit subscriber account number (0000–9999)
1 is the priority attribute (L = Life Safety, P = Property, S = System Integrity)
2 s the command direction (B = Both activation and restoration, A = Activation only,
R = Restoration only)
For Contact ID dialer strings:
Q is the event qualifier (1 = activation event, 3 = restoration event)
EEE is the event code. See Table 4-9.
GGPPP is the point being reported
For 4/2 dialer strings:
PP is the point being reported (00–99)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.23
Programming instructions
Table 4-9: Contact ID Event Codes
100 – Medical alarm
101 – Pendant transmitter
102 – Fail to report in
110– Fire Alarm
111 – Smoke
112 – Combustion
113 – Water Flow
114 – Heat
115 – Pull Station
116 – Duct
117 – Flame
118 – Near alarm
120 – Panic Alarm
121 – Duress
122 – Silent
123 – Audible
130 – Burglar Alarm
131 – Perimeter
132 – Interior
133 – 24 Hour
134 – Entry/Exit
135 – Day/Night
136 – Outdoor
137 – Tamper
138 – Near alarm
140 – General Alarm
141 – Polling loop open
142 – Polling loop short
143 – Expansion module failure
144 – Sensor tamper
145 – Expansion module failure
150 and 160 – 24-hour Non-
Burglary
151 – Gas detection
152 – Refrigeration
153 – Loss of heat
154 – Water leakage
155 – Foil break
156 – Day trouble
157 – Low bottled gas level
158 – High temperature
159 – Low temperature
161 – Loss of air flow
200 and 210 – Fire Supervisory
201 – Low water pressure
202 – Low CO
2
203 – Gate valve sensor
204 – Low water level
205 – Pump activated
206 – Pump failure
300 and 310 – System Troubles
301 – AC loss
302 – Low system battery
303 – RAM checksum bad
304 – ROM checksum bad
305 – System reset
306 – Panel program changed
307 – Self–test failure
308 – System shutdown
309 – Battery test failure
310 – Ground fault
320 – Sounder/Relay Trouble
321 – Bell 1
322 – Bell 2
323 – Alarm relay
324 – Trouble relay
325 – Reversing
330 and 340 – System Peripheral
Trouble
331 – Polling loop open
332 – Polling loop short
333 – Expansion module failure
334 – Repeater failure
335 – Local printer paper out
336 – Local printer failure
350 and 360 – Communication
Trouble
351 – Telco 1 fault
352 – Telco 2 fault
353 – Long range radio
354 – Fail to communicate
355 – Loss of radio supervision
356 – Loss of central polling
370 – Protection LoopTrouble
371 – Protection loop open
372 – Protection loop short
373 – Fire trouble
380 – Sensor Trouble
381 – Loss of supervisory (RF)
382 – Loss of supervisory (RPM)
383 – Sensor tamper
384 – RF transmitter low battery
400 – Open/Close
401 – Open/Close by user
402 – Group open/close
403 – Automatic open/close
404 – Late to open/close
405 – Deferred open/close
406 – Cancel
407 – Remote arm/disarm
408 – Quick arm
409 – Keyswitch open/close
410 – Remote Access
411 – Call request made
412 – Success – Download access
413 – Unsuccessful access
414 – System shutdown
415 – Dialer shutdown
4.24
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 4-9: Contact ID Event Codes (cont.)
420 – Access Control
421 – Access denied
600 – Test/Misc.
601 – Manual trigger test
422 – Access report by user
441 – Stay arming
451 – Early opening/closing
452 – Late opening/closing
453 – Late to open
454 – Late to close
455 – Auto–arm failure
500 and 510 – System Disable
602 – Periodic test report
603 – Periodic RF transmission
604 – Fire test
605 – Status report to follow
606 – Listen–in follow
607 – Walk Test mode
621 – Event Log reset
622 – Event Log 50% full
623 – Event Log 90% full 520 – Sounder/Relay Disable
521 – Bell 1 disable
522 – Bell 2 disable
523 – Alarm relay disable
524 – Trouble relay disable
525 – Reversing relay disable
530 and 540 – System Peripheral
Disable
624 – Event log overflow
625 – Time/Date reset
626 – Time/Date inaccurate
627 – Program mode entry
628 – Program mode exit
631 – Exception schedule change
550 and 560 – Communication
Disable
551 – Dialer disable
552 – Radio transmitter
570 – Disable Bypasses
570 – Zone bypass
571 – Fire zone bypass
572 – 24 Hour zone bypass
573 – Burglary zone bypass
574 – Group bypass
Programming instructions
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.25
Programming instructions
Setting up a Zone
Before you begin
Configure the Zone
Before you begin, you should complete a Zone Programming
Worksheet (Figure 4-9) for each Zone. Keep a copy for your records. You will also need to refer to the Output Group programming worksheets.
To set up a Zone:
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4 access.
3. Choose Program > Configure > Zone.
4. To program a new Zone, choose Add, and then choose a zone type (Alarm, Supervisory, or Monitor).
— or —
Choose Edit, select an existing zone from the pick list, and then press Enter.
1. Choose Message, scan in the message text, and then press Enter.
2. Choose Members, then for each device that comprises the
Zone:
Choose Device Address, then enter the member's device number from the worksheet
— or —
Choose Enter Serial#, scan in or enter the member's serial number.
3. Choose Review to verify which devices you added to the
Zone. If you added any devices in error, delete them.
4. Choose Output Group > Add, then select the Output group from the pick list that contains the responses you want activated, and then press Enter.
Repeat for each Output group you want to add.
5. Choose Review to verify which Output groups you added to the Zone. If you added any Output groups in error, remove them.
6 For coded systems, choose Coding, and then enter the
Zone Code.
4.26
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Job Name:
Panel: Card: 14
Page of
# of CMS receivers: ¨ 1 ¨ 2
CMS phone numbers: Receiver 1: #1) Receiver 1: #2)
Receiver 2: #1) Receiver 2: #2)
Retry Count: ¨ 5 ¨ 6 ¨ 7 ¨ 8 ¨ 9 ¨ 10
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Account Number:
Test strings:
Format: ¨ 4/2 ¨ Contact ID
Panel normal: Panel off-normal:
Time: CMS receiver to dial: ¨ 1 ¨ 2
Figure 4-1: DLD Programming Worksheet (sheet 1 of 2)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.27
Programming instructions
Job Name:
Panel: Card: 14
Default Alarm Message: Account Number:
Active Message:
Restore Message:
Default Trouble Message: Account Number:
Active Message:
Restore Message:
Default Supervisory Message: Account Number:
Active Message:
Restore Message:
Figure 4-1 DLD Programming Worksheet (sheet 1 of 2)
Page of
4.28
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Page of Job Name:
Panel: Card:
001 Device Type:
Text Message: 1)
2)
002 Device Type:
Text Message: 1)
2)
003 Device Type:
Text Message: 1)
2)
004 Device Type:
Text Message: 1)
2)
005 Device Type:
Text Message: 1)
2)
006 Device Type:
Text Message: 1)
2)
007 Device Type:
Text Message: 1)
2)
008 Device Type:
Text Message: 1)
2)
IDC 001
IDC 002
IDC 003
IDC/NAC 004
IDC/NAC 008
IDC 007
IDC 006
IDC 005
Defaults: Alarm for IDC 001 – 003 and IDC 005 – 007,
Common Alarm Output for IDC/NAC 004, Visual for
IDC/NAC 008
Figure 4-2: ZA8–2 Programming Worksheet
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.29
Programming instructions
Job Name:
Panel: Card:
Page of
001 Device Type:
Text Message: 1)
2)
002 Device Type:
Text Message: 1)
2)
003 Device Type:
Text Message: 1)
2)
004 Device Type:
Text Message: 1)
2)
005 Device Type:
Text Message: 1)
2)
006 Device Type:
Text Message: 1)
2)
007 Device Type:
Text Message: 1)
2)
008 Device Type:
Text Message: 1)
2)
009 Device Type:
Text Message: 1)
2)
010 Device Type:
Text Message: 1)
2)
011 Device Type:
Text Message: 1)
2)
IDC 001
IDC 002
IDC 003
IDC 004
IDC 012
IDC 011
IDC 010
Defaults: Alarm for IDC 001–012, Common Alarm
Output for IDC/NAC 013–014, Visual for IDC/NAC 015–
016
IDC 005
IDC 006
IDC 007
IDC 008
IDC 009
IDC/NAC 013
IDC/NAC 014
IDC/NAC 015
IDC/NAC 016
012 Device Type:
Text Message: 1)
2)
013 Device Type:
Text Message: 1)
2)
014 Device Type:
Text Message: 1)
2)
015 Device Type:
Text Message: 1)
2)
016 Device Type:
Text Message: 1)
2)
Figure 4-3: ZB16–4 Programming Worksheet
4.30
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Job Name:
Panel: Card:
001 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
002 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
003 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
004 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
005 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
006 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
007 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
008 ¨ NC (normally-closed)
¨ NO (normally-open)
Device type:
004
003
002
001
005
006
007
008
Figure 4-4: ZA8–2 Programming Worksheet
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
Programming instructions
Page of
JP4
004+ 004–
NC
NO
NC
NO
JP8
008+ 008–
4.31
Programming instructions
Job Name:
Panel:
Page of
Card:
NAC 1 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
NAC 2 device type:
Number of detector addresses used on loop:
¨ Audible ¨ Visible
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
NAC 2 device type:
Number of detector addresses used on loop:
¨ Audible ¨ Visible
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
NAC 2 device type:
Number of detector addresses used on loop:
¨ Audible ¨ Visible
Number of module addresses used on loop:
Card:
NAC 1 device type: ¨ Audible ¨ Visible
Wiring class: ¨ Class A ¨ Class B
NAC 2 device type:
Number of detector addresses used on loop:
¨ Audible ¨ Visible
Number of module addresses used on loop:
Figure 4-5: SLIC Programming Worksheet
4.32
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Page of Job Name:
Panel: Card:
Model:
Sensitivity:
Verification:
Pre-Alarm:
Base type:
Message:
S/N Device:
¨ Most
¨ None
¨ None
¨ Standard
¨ More
¨ 12 s
¨ 20%
¨ Relay
¨ Normal
¨ 24 s
¨ 40%
¨ Isolator
¨ Less
¨ 36 s
¨ 60%
¨ Least
¨ 60 s
¨ 80%
1) 2)
Model:
Sensitivity:
Verification:
Pre-Alarm:
Base type:
Message:
S/N Device:
¨ Most ¨ More ¨ Normal ¨ Less ¨ Least
¨ None
¨ None
¨ 12 s
¨ 20%
¨ 24 s
¨ 40%
¨ 36 s
¨ 60%
¨ 60 s
¨ 80%
¨ Standard ¨ Relay ¨ Isolator
1) 2)
Model:
Sensitivity:
Verification:
Pre-Alarm:
Base type:
Message:
S/N Device:
¨ Most
¨ None
¨ None
¨ Standard
¨ More
¨ 12 s
¨ 20%
¨ Relay
¨ Normal
¨ 24 s
¨ 40%
¨ Isolator
¨ Less
¨ 36 s
¨ 60%
¨ Least
¨ 60 s
¨ 80%
1) 2)
Model:
Sensitivity:
Verification:
Pre-Alarm:
Base type:
Message:
S/N Device:
¨ Most
¨ None
¨ None
¨ Standard
¨ More
¨ 12 s
¨ 20%
¨ Relay
¨ Normal
¨ 24 s
¨ 40%
¨ Isolator
¨ Less
¨ 36 s
¨ 60%
¨ Least
¨ 60 s
¨ 80%
1) 2)
Figure 4-6: Signature Detector Programming Worksheet
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.33
Programming instructions
Job Name:
Panel: Card:
Page of
Model: S/N Device: 1st) 2nd)
Device #1
Device Type:
Personality:
Message: 1)
2)
Device #2
Device Type:
Personality:
Message: 1)
2)
Model: S/N Device: 1st) 2nd)
Device #1
Device Type:
Personality:
Message: 1)
2)
Device #2
Device Type:
Personality:
Message: 1)
2)
Model: S/N Device: 1st) 2nd)
Device #1
Device Type:
Personality:
Message: 1)
2)
Device #2
Device Type:
Personality:
Message: 1)
2)
Model: S/N Device: 1st) 2nd)
Device #1
Device Type:
Personality:
Message: 1)
2)
Device #2
Device Type:
Personality:
Message: 1)
2)
Figure 4-7: Signature Module Programming Worksheet
4.34
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Programming instructions
Page of Job Name:
Panel: Output Group:
Response: __ __ __ Type: ¨ Active ¨ Trouble
¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal
¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s
¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration
Priority: ¨ Life Safety ¨ Property ¨ System Integrity
String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __
Response: __ __ __ Type: ¨ Active ¨ Trouble
¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal
¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s
¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration
Priority: ¨ Life Safety ¨ Property ¨ System Integrity
String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __
Response: __ __ __ Type: ¨ Active ¨ Trouble
¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal
¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s
¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration
Priority: ¨ Life Safety ¨ Property ¨ System Integrity
String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __
Response: __ __ __ Type: ¨ Active ¨ Trouble
¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal
¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s
¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration
Priority: ¨ Life Safety ¨ Property ¨ System Integrity
String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __
Figure 4-8: Output Group Programming Worksheet
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
4.35
Programming instructions
Job Name:
Panel: Zone:
Zone Type: ¨ Alarm ¨ Supervisory ¨ Monitor
Zone Code:
Message: 1)
2)
Page of
Zone Members (32 max):
Output groups (6 max):
Figure 4-9: Zone Programming Worksheet
4.36
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 5
Standard applications
Summary
This chapter provides simplified wiring schematics for standard applications.
Content
Notification appliance circuits • 5.2
Initiating device circuits • 5.5
Coded alarm signaling • 5.8
Remote station protective signaling system • 5.10
Auxiliary protective signaling • 5.12
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.1
Standard applications
Notification appliance circuits
SLIC
NAC1 B+
NAC1 B–
NAC1 A+
NAC1 A–
UL/ULC LISTED
10 K EOLR
NAC2 B+
NAC2 B–
NAC2 A+
NAC2 A–
UL/ULC LISTED
Typical Class A NAC circuits
SLIC
NAC1 B+
NAC1 B–
NAC1 A+
NAC1 A–
NOT USED
NAC2 B+
NAC2 B–
NAC2 A+
NAC2 A–
NOT USED
Typical Class B NAC circuits
UL/ULC LISTED
10 K EOLR
Note: The plus and minus symbols indicate signal polarity when the
NAC circuit is turned on.
UL/ULC LISTED
10 K EOLR
Note: The plus and minus symbols indicate signal polarity when the
NAC circuit is turned on.
5.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Standard applications
UL/ULC LISTED
47 K EOLR
8 7 6 5
10 9
SIGA–CC1
4 3 2 1 8 7 6 5
SIGA–RM1
4 3 2 1
PS6
AUX(n)
COM
SLIC
LOOP B+
LOOP B–
LOOP A+
LOOP A–
TO DATA OUT TERMINALS
ON LAST DEVICE (CLASS A ONLY)
TO DATA IN TERMINALS
ON NEXT DEVICE
Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on.
Typical NAC riser wiring
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.3
Standard applications
ZB16–4
Z13+
Z13–
Z14+
Z14–
Z15+
Z15–
Z16+
Z16–
Typical Class B NAC circuits
ZA8–2
ZONE 4 B+
ZONE 4 B–
ZONE 4 A+
ZONE 4 A–
UL/ULC LISTED
10 K EOLR
NAC1 B+
NAC1 B–
NAC1 A+
NAC1 A–
UL/ULC LISTED
10 K EOLR
Typical Class A NAC circuit
UL/ULC LISTED
UL/ULC LISTED
10 K EOLR
UL/ULC LISTED
10 K EOLR
UL/ULC LISTED
10 K EOLR
5.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Initiating device circuits
PS6
24VDC+
24VDC–
JP2
ACC PWR
SMK PWR
8 7
SIGA–CT1
4 3 2 1
SLIC
LOOP B+
LOOP B–
LOOP A+
LOOP A–
TO DATA IN TERMINALS
ON NEXT DEVICE
TO DATA OUT TERMINALS
ON LAST DEVICE (CLASS A ONLY)
Typical four-wire smoke detector circuit
Standard applications
UL/ULC LISTED
EOL RELAY
UL/ULC LISTED
PS6
24VDC+
24VDC–
JP2
ACC PWR
SMK PWR
UL/ULC LISTED
22 K EOLR
2–SMK
SLIC
LOOP B+
LOOP B–
LOOP A+
LOOP A–
TO DATA OUT TERMINALS
ON LAST DEVICE (CLASS A ONLY)
Typical Class B two-wire smoke detector circuit
14 13 3-2-1 12 11 10 9
SIGA–UM
8 7 6 5 4 3 2 1
UL/ULC LISTED
TO
DATA IN TERMINALS
ON NEXT DEVICE
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.5
Standard applications
PS6
24VDC+
24VDC–
JP2
ACC PWR
SMK PWR
UL/ULC LISTED
22 K EOLR
2–SMK
SLIC
LOOP B+
LOOP B–
LOOP A+
LOOP A–
TO DATA OUT TERMINALS
ON LAST DEVICE (CLASS A ONLY)
Typical Class A two-wire smoke detector circuit
14 13 3-2-1 12 11 10 9
SIGA–UM
8 7 6 5 4 3 2 1
ZB16–4
Z(n)+
Z(n)–
Typical Conventional Class B IDC circuit
ZA8–2
ZONE (n) B+
ZONE (n) B–
ZONE (n) B+
ZONE (n) B–
UL/ULC LISTED
4.7 K EOLR
Typical Conventional Class A IDC circuit
UL/ULC LISTED
4.7 K EOLR
TO
DATA IN TERMINALS
ON NEXT DEVICE
5.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
PS6
24VDC+
24VDC–
JP2
ACC PWR
SMK PWR
ZB16–4
Z(n)+
Z(n)–
Typical Conventional Class B four-wire smoke detector circuit
PS6
24VDC+
24VDC–
JP2
ACC PWR
SMK PWR
ZA8–2
ZONE (n) B+
ZONE (n) B–
ZONE (n) A+
ZONE (n) A–
UL/ULC LISTED
Typical Conventional Class A four-wire smoke detector circuit
Standard applications
UL/ULC LISTED
EOL RELAY
UL/ULC LISTED
UL/ULC LISTED
EOL RELAY
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.7
Standard applications
Coded alarm signaling
1 2 3
1. FACP: Fire alarm control panel with a CPU,
PS6, ZB16–4, and standby batteries.
2. MFC–A Accessory Enclosure: Used for mounting the remote fire alarm equipment.
3. CDR–3 Bell Coder: Provides coded alarm signals for 24 Vdc notification appliance circuits and one of three evacuation signals (temporal, 60 bpm, and 90 bpm).
Note: CDR–3 must have firmware version greater than 2.0.
Notes
• Place the MFC–A and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit.
• Set SW–6 on CDR–3 to ON. Refer to the CDR–
3 installation sheet for programming information.
• Install a 10 k Ω EOLR across TB2–1 and TB2–
2, and TB2–11 and TB2–12 on the CDR–3.
• Set JP2 on the PS6 for ACC PWR
• If the system uses a NAC circuit on an SLIC to output the coded signal, program the NAC circuit signal rate as Steady.
• If the system uses the NAC 1 circuit on an SLIC to output the coded signal to audible notification appliances, set JP1 and JP2 on the SLIC to
EXT.
Figure 5-1: Typical equipment layout, coded alarm signaling application
5.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Standard applications
PS6TB1–16
PS6TB1–18
PS6TB1–12
PS6TB1–11
PS6TB3–3
PS6TB3–1
NAC RISER –
NAC RISER +
10K Ω
SW1
TB1
JP1 JP2
CDR–3
Figure 5-2: Coded alarm signaling wiring (coded alarm signal only)
10K Ω
TB2
PS6TB1–16
PS6TB1–18
PS6TB1–12
PS6TB1–11
PS6TB3–3
PS6TB3–1
NAC RISER –
NAC RISER +
SW1
10K Ω 10K Ω
TB1
TB2
JP1 JP2
CDR–3
Figure 5-3: Coded alarm signaling wiring (coded signal followed by evacuation signal)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.9
Standard applications
Remote station protective signaling system
1 2 3
1. FACP: Fire alarm control panel with a CPU,
PS6, ZB16–4, and standby batteries.
2. MFC–A Accessory Enclosure: Used for mounting the remote fire alarm equipment.
3. RPM Reverse Polarity Module: Provides three independent reverse polarity signals (alarm, supervisory, trouble) for transmitting system status to a remote location.
Notes
• Place the MFC–A and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit.
• Set JP2 on the PS6 for ACC PWR.
• Install a 3.9 K Ω EOLR across TB1–1 and TB1–
2 on the RPM.
Figure 5-4: Typical equipment layout, Remote station protective signaling application
5.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Standard applications
PS6
RELAY 1 NO
RELAY 1 C
RELAY 2 C
RELAY 2 NO
RELAY 3 C
RELAY 3 NO
24VDC+
24VDC–
ALRM
RPM
JP1
CITY BOX+
CITY BOX–
SUPV
TRBL
+24V
COM
ALARM+
ALARM–
TROUBLE+
TROUBLE–
SUPV+
SUPV–
3.9 K Ω
Note: Plus and minus symbols indicate signal polarity when the circuit is active.
Figure 5-5: Remote station protective signaling wiring
OFF-SITE
MONITORING
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
5.11
Standard applications
Auxiliary protective signaling
Wire as shown in Figure 5-6. Program the SIGA–CC1 as a common alarm output device. Plus and minus symbols indicate signal polarity with the circuit turned on.
8 7 6 5
10 9
SIGA–CC1
4 3 2 1
LISTED 24VDC
SUPPLY
24VDC+
24VDC–
TO NEXT DEVICE
SLIC
LOOP B+
LOOP B–
LOOP A+
LOOP A–
TO DATA OUT TERMINALS
ON LAST DEVICE (CLASS A ONLY)
Figure 5-6: Auxiliary protective signaling cabling diagram
TO DATA IN TERMINALS
ON NEXT DEVICE
1 2
2–CTM
2 1
Master box
Municipal circuit
5.12
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Chapter 6
Maintenance instructions
Summary
This chapter provides instructions for maintaining the system.
Content
Pseudo point definitions • 6.2
Table 6-1: Main Panel pseudo points • 6.2
Table 6-2: Remote Annunciator pseudo points • 6.2
Table 6-3: Power Supply pseudo points • 6.3
Table 6-4: SLIC card pseudo points • 6.3
Table 6-5: Dialer pseudo points • 6.4
Table 6-6: General CPU pseudo points • 6.5
Maintenance tasks • 6.6
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
6.1
Maintenance instructions
Pseudo point definitions
Table 6-1: Main Panel pseudo points
LCD Indication Event Type
Panel xx Card Communications Trouble
Panel 01 Reset Extension
Panel 01 Service Active Trouble
Monitor/Trouble
Trouble
Trouble Pnl 0x Database Incompatible
Panel 01 Reboot Fault
Panel 0x, CH1 Communications
Panel 01 Task Failure
Card xx Setup Mismatch
Trouble
Trouble
Trouble
Dailer Setup Mismatch
Power Supply Setup Mismatch
Panel 01 LED/Switch display
Panel 0x, CH2 Communications
Pnl 01 Database Supervision
Panel 01 Code Supervision
Panel 01, Call For Service
Panel 01, ROM Supervision
Panel 01 RS232 Port Fault
Panel 01 Unexpected Card
Panel 01 Switch Latched
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Panel 01 Loop Database Fault Trouble
Table 6-2: Remote Annunciator pseudo points
LCD Indication Event Type
Ann 0x Service Active Trouble Trouble
Ann 0x Database Incompatible
Annunciator 0x Reboot Fault
Trouble
Trouble
Definition
CPU has failed to communicate with the option card at address xx.
Signature loop is still resetting.
Service group was restored with a device still in the active condition.
Changes made to the system programming on the control panel were not updated in this unit.
Control panel CPU restarted unexpectedly.
Annunciator is not communicating on RS485 channel 1.
Internal processing fault.
CPU encountered problem configuring the option card at address xx.
A problem has occurred with the CPU configuring the dialer card.
A problem has occurred with the CPU configuring the POWER supply card.
LED/Switch card is not connected.
Annunciator is not communicating on RS485 channel 2.
Internal CPU memory failure
Internal CPU memory failure
Internal CPU processing error
Internal CPU memory failure
CPU detected an option card not defined in the database.
Button either on the main display or on an
LED/Switch card has been pressed too long.
Internal CPU memory failure with Signature data.
Definition
Indicates that a device was left in an active condition after service group has restored.
Indicates that the data
Indicates CPU has restarted due to internal processing failure.
6.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
LCD Indication
Ann 0x, CH1 Communications
Annunciator 0x Task Failure
Ann 0x, LED/ Switch Display
Ann 0x, CH2 Communications
Ann 0x Database Supervision
Ann 0x Code Supervision
Ann 0x, Call For Service
Ann 0x ROM Supervision
Ann 0x RS232 Port Fault
Ann 0x Program Mode
Ann 0x Switch Latched
Annunciator 0x Power Fault
Table 6-3: Power Supply pseudo points
LCD Indication Event Type
Battery Charger Fault Trouble
Battery Wiring or Battery Fault
Aux Power 1/2 Shorted
Trouble
Trouble
Aux Power 3 Shorted
Smoke Power Shorted
Primary AC Power Failure
Excessive Battery Current
Check System Wiring
Power Supply Card RAM Fault
Power Supply Card ROM Fault
Power Supply EEPROM Fault
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Table 6-4: SLIC card pseudo points
LCD Indication
Card 0x, Loop Wiring Problem
Card 0x Map Fault
Event Type
Trouble
Trouble
Event Type
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
Maintenance instructions
Definition
Indicates failure to communicate with the main panel on RS485 channel 1.
Internal software failure
Indicates that a SL30-x has been disconnected or is connected but not defined.
Indicates failure to communicate with the main panel on RS485 channel 2.
Internal memory failure
Internal memory failure
Internal software failure
Internal memory failure
Panel has entered program mode.
Indicates that a button either on the main display or on an SL30-x has been pressed to long.
Indicates a loss of power on either of the 24vdc inputs to the RAI card.
Definition
This fault will occur when the battery charger charging voltage falls below 20.4vdc.
Caused by an open in the battery wiring or if the batteries are below 20.4vdc.
This point occurs when Aux 1 or Aux 2 power is shorted on the PS6
This point occurs when Aux 3
This point occurs when smoke power is shorted
Caused by loss of AC or very low AC.
Will go active when PS6 detects over current condition
Indicates a ground fault exists on field wiring.
Internal memory fault
Internal memory fault
Internal memory fault
Definition
Indicates a break on a Class A signature loop
Signature map is different than the one written in memory
6.3
Maintenance instructions
LCD Indication
Card 0x, Mapping In Progress
Card 0x Unconfig. Device
Card 0x, Line Initialization
Card 0x, Loop Ground Fault
Card 0x, LIM Driver Fault
Card 0x, RAM Supervision
Card 0x, ROM Supervision
Card 0x, EEPROM Supervision
Table 6-5: Dialer pseudo points
LCD Indication
Primary Phone Line:check Telco
Secondary Phone Line:check Telco
Pri. Receiver Failed to answer
Sec. Receiver Failed to answer
Dialer Account 1 Fault
Dialer Account 2 Fault
Dialer Account 3 Fault
Dialer Account 4 Fault
Dialer Account 5 Fault
Dialer Account 6 Fault
Dialer Account 7 Fault
Dialer Account 8 Fault
Dialer ROM Fault
Dialer Queue Overflow
Dialer Card, RAM Supervision
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Event Type
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Trouble
Event Type
Monitor
Trouble
Monitor
Trouble
Trouble
Trouble
Trouble
Trouble
Definition
Indicates Signature devices are in the process of being mapped.
Indicates that a new signature device has been detected on a loop.
Occurs after power up or a restart. Indicates signature devices are being initialized.
Indicates a ground fault on a signature module.
Internal hardware failure.
Internal memory fault
Internal memory fault
Internal memory fault
Definition
Telephone line has low or no voltage
Telephone line has low or no voltage
Dialer attempted to dial event to CMS but did not get an answer.
Dialer attempted to dial event to CMS but did not get an answer.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 1.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 2.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 3.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 4.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 5.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 6.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 7.
Indicates dialer did not get proper handshake for event sent to the CMS for Account 8.
Internal memory fault
Indicates that too many dialer messages are trying to be sent.
Internal memory fault
6.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Table 6-6: General CPU pseudo points
LCD Indication Event Type
Startup Response Monitor
First Alarm
First Supervisory
Alarm
Supervisory
Trouble
Monitor
First Trouble
First Monitor
Evacuation
Drill
Alarm Silence
Two Stage Expiration
Reset
Reset Phase 1
Reset Phase 2
Reset Phase 3
First Disable
First Test
Two Stage Timer Started
User Trouble
Monitor
Monitor
Monitor
Monitor
Monitor
Monitor
Trouble
Trouble
Trouble
Maintenance instructions
Definition
Monitor point that goes active on system startup or after restart.
Occurs anytime that the system goes into alarm for the first time.
Occurs anytime that the system goes into supervisory for the first time.
Occurs anytime that the system goes into a trouble for the first time.
Occurs anytime that the system goes into a monitor condition for the first time.
This point will go active anytime drill is pressed.
This point will go active anytime alarm silence is pressed.
This point goes active anytime reset is pressed.
Active during the power down phase of reset.
Active during the retard phase of reset.
Active during the restoration phase of reset.
Activated the first time an item is disabled from the front menu.
Activated the first time a service group is started from the front menus.
Triggered by custom programming.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
6.5
Maintenance instructions
Maintenance tasks
What is it you want to do
Change the fuse
Replacing a SIGA device when mapping is disabled)
This is how you do it
1. Switch the circuit breaker that supplies ac power to the control panel to the OFF position.
2. Expose the ac terminal block and pull out the fuse holder.
3. Replace the blown fuse with a new one of the same type and size.
4. Plug the fuse holder back into the ac terminal block.
5. Switch the circuit breaker that supplies ac power to the control panel to the ON position.
WARNING: Replacing a device when mapping is disabled leaves the area unprotected. The control panel does not automatically reassign responses to replaced devices when mapping is disabled.
To replace devices on a loop that operates with mapping disabled, you must first enable mapping then accept the map.
After you replace your devices, you can disable mapping on the loop.
Note: Replacement devices must be the same model as the devices being replaced.
1. Press Menu.
2. Log onto the panel as a Level 4 operator.
3. Choose Enable > Loop Mapping.
4. Enter the card number of the SLIC that connects to the device you want to replace.
Wait until mapping finishes before continuing.
5. Choose Cards > Edit.
6. Enter the card number of the SLIC that connects to the device you want to replace.
7. Choose Accept Map.
If actual and expected data for detectors and modules are the same, press Enter.
8. Choose Exit > Exit > Save and Sync.
9. Replace the device.
6.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Appendix A
System calculations
Summary
This appendix provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries.
Content
Notification appliance circuit maximum wire length calculation • A.2
Signature loop maximum wire length calculations • A.3
Battery calculation • A.8
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
A.1
System calculations
Notification appliance circuit maximum wire length calculation
Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one worksheet for each NAC connected to the panel.
Maximum signal loss allowed
1
Wire resistance per 1000 ft/pair 2
×
÷
1.5 V
1000
1500
Ω
Total operating current required
Maximum wire length
3 ÷ A ft
Notes
1. For worst case estimates, assume a 1.5 V line loss and all appliances are clustered at the end of the circuit.
2. Use 3.5 for 12 AWG and 2.5 mm and 1.0 mm
2
2
wire, 5.2 for 14 AWG and 1.5 mm
wire, and 13.0 for 18 AWG and 0.75 mm
2
wire.
2
wire, 8.0 for 16 AWG
3. Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.
A.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
System calculations
Signature loop maximum wire length calculations
Use this worksheet to determine the maximum amount of wire you can use to construct a Signature loop.
Step 1: Calculate the total amount of wire you can used based on the cable manufacturer's capacitance per foot rating. Total amount of wire shall not exceed the values listed in Table A-1.
500000
Cable capacitance ÷ pF/ft
Total wire ft
Table A-1: Maximum amount of wire you can use to construct a Signature loop
Wire type 14 AWG / 1.5 mm² 16 AWG / 1.0 mm² 18 AWG / 0.75 mm
2
Twisted pair, nonshielded
25 pF/36 pF/38 pF
13157 ft
(4010 m)
13888 ft
(4233 m)
20000 ft
(6096 m)
Twisted pair, shielded
58 pF/82 pF/84 pF
Nontwisted pair, nonshielded
20 pF/20 pF/20 pF
5952 ft
(1814 m)
20000 ft
(6096 m)
6098 ft
(1859 m)
20000 ft
(6096 m)
8621 ft
(2628 m)
20000 ft
(6096 m)
Step 2: Use Table A-2, Table A-3, Table A-4, and Table A-5 to determine the longest allowable circuit path based on wire size and type, and the number of detector, module, SIGA–UMs or –MABs installed on the loop.
In the illustration below, the longest circuit path (shown in bold lines) is 1240 ft (377.95 m). The total amount of wire comprising the loop is 1740 ft (530.35 m)
10 ft
(3.05 m)
200 ft
(60.96 m)
FACP J
30 ft
(9.14 m)
200 ft
(60.96 m)
200 ft
(60.96 m)
J J
100 ft
(30.48 m)
1000 ft
(304.8 m)
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
A.3
System calculations
Table A-2: Longest allowable circuit path with 0 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Signature detector addresses
Maximum allowable wire distance using nontwisted, nonshielded wire pairs
Signature module
18 AWG addresses ft m
16 AWG ft m
14 AWG ft m
51–75
51–75
51–75
51–75
51–75
51–75
26–50
26–50
26–50
26–50
26–50
26–50
76–100
76–100
76–100
76–100
76–100
76–100
101–125
101–125
101–125
101–125
101–125
101–125
0
0
0
0
0
1–25
1–25
1–25
1–25
1–25
1–25
9383
8340
7360
6435
5558
4723
6245
5407
4605
3833
3089
2371
10639
10004
9369
8734
8099
7464
4180
3439
2721
2023
1345
685
11815
11180
10545
9910
9275
11544
10909
10275
9640
9005
8370
5906
5250
4633
4051
3498
2973
3931
3404
2899
2413
1945
1493
6697
6297
5897
5498
5098
4698
2631
2165
1713
1274
847
431
7437
7038
6638
6238
5839
7267
6867
6467
6068
5668
5268
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
1800
1600
1412
1235
1066
906
1198
1037
883
735
593
455
2041
1919
1798
1676
1554
1432
802
660
522
388
258
131
2267
2145
2023
1901
1780
2215
2093
1971
1849
1728
1606
2860
2542
2243
1961
1694
1440
1903
1648
1404
1168
942
723
3243
3049
2856
2662
2469
2275
1274
1048
829
617
410
209
3601
3408
3214
3021
2827
3519
3325
3132
2938
2745
2551
14923
13265
11707
10235
8839
7512
9932
8601
7324
6096
4913
3771
16921
15911
14901
13891
12881
11871
6649
5470
4328
3218
2140
1089
18792
17782
16772
15762
14752
18361
17351
16342
15332
14322
13312
4549
4043
3568
3120
2694
2290
3027
2621
2232
1858
1498
1149
5157
4850
4542
4234
3926
3618
2027
1667
1319
981
652
332
5728
5420
5112
4804
4497
5597
5289
4981
4673
4365
4057
A.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
System calculations
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
51–75
51–75
51–75
51–75
51–75
51–75
26–50
26–50
26–50
26–50
26–50
26–50
76–100
76–100
76–100
76–100
76–100
76–100
101–125
101–125
101–125
101–125
101–125
101–125
0
0
0
0
0
1–25
1–25
1–25
1–25
1–25
1–25
Table A-3: Longest allowable circuit path with 1–5 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Signature detector addresses
Signature module addresses
Maximum wire distance using nontwisted, nonshielded wire pairs
18 AWG 16 AWG 14 AWG ft m ft m ft m
17126
15492
13899
12342
10819
13525
11926
10359
8821
7311
5826
9542
7966
6416
4890
3387
1905
6293
4720
3168
1638
126
3282
2969
2664
2365
2073
2592
2286
1985
1691
1401
1116
1829
1527
1230
937
649
365
1206
904
607
314
24
8504
7498
6513
5546
4597
3663
10768
9741
8739
7760
6802
5999
5009
4034
3075
2130
1197
3957
2967
1992
1030
80
2066
1869
1677
1489
1305
1632
1439
1250
1064
882
703
1151
961
774
590
409
230
759
569
382
198
15
6778
6131
5501
4885
4282
5353
4720
4100
3491
2893
2306
3776
3153
2539
1935
1340
754
2491
1868
1254
648
50
1386
760
143
422
232
44
2201
1208
227
671
368
69
3501
1921
361
5220
4722
4236
3762
3298
4122
3635
3157
2689
2228
1776
2908
2428
1956
1491
1032
581
1918
1439
966
499
39
1067
586
110
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
A.5
System calculations
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
51–75
51–75
51–75
51–75
51–75
51–75
26–50
26–50
26–50
26–50
26–50
26–50
76–100
76–100
76–100
76–100
76–100
76–100
101–125
101–125
101–125
101–125
101–125
101–125
0
0
0
0
0
1–25
1–25
1–25
1–25
1–25
1–25
Table A-4: Longest allowable circuit path with 6–10 SIGA-UMs or SIGA-MABs configured for 2-wire smokes
Signature detector addresses
Signature module addresses
Maximum wire distance using nontwisted, nonshielded wire pairs
18 AWG 16 AWG 14 AWG ft m ft m ft m
12748
11355
9981
8625
7286
10375
8950
7542
6152
4778
3419
7248
5802
4372
2957
1558
172
4537
3067
1613
173
2443
2176
1913
1653
1396
1988
1715
1445
1179
916
655
869
588
309
33
1389
1112
838
567
299
33
8015
7139
6275
5423
4581
6523
5627
4742
3868
3004
2150
4557
3648
2749
1859
979
108
2853
1929
1014
109
1538
1370
1204
1040
879
1252
1080
910
742
576
412
874
700
527
357
188
21
547
370
195
21
5045
4494
3950
3414
2884
4106
3542
2985
2435
1891
1353
2869
2296
1730
1170
617
68
1796
1214
638
69
833
242
254
74
1323
385
403
117
2105
613
3886
3461
3042
2629
2221
3162
2728
2299
1875
1456
1042
2209
1768
1332
901
475
53
1383
935
492
53
642
187
A.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
System calculations
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
1–25
26–50
51–75
76–100
101–125
0
1–25
26–50
51–75
76–100
101–125
51–75
51–75
51–75
51–75
51–75
51–75
26–50
26–50
26–50
26–50
26–50
26–50
76–100
76–100
76–100
76–100
76–100
76–100
101–125
101–125
101–125
101–125
101–125
101–125
0
0
0
0
0
1–25
1–25
1–25
1–25
1–25
1–25
Table A-5: Longest allowable circuit path with 11–15 SIGA-UMs or SIGA-MABs configured for 2wire smokes
Signature detector addresses
Signature module addresses
Maximum wire distance using nontwisted, nonshielded wire pairs
18 AWG 16 AWG 14 AWG ft m ft m ft m
3931
3427
2928
2432
1941
3247
2722
2202
1686
1174
666
2204
1664
1129
598
71
1198
1045
892
741
592
990
830
671
514
358
203
672
507
344
182
22
6245
5444
4651
3864
3083
5158
4324
3498
2678
1865
1058
3502
2644
1793
950
113
1903
1659
1418
1178
940
1572
1318
1066
816
568
323
1067
806
547
289
34
9932
8659
7397
6145
4903
8204
6878
5563
4259
2966
1683
5570
4205
2852
1511
179
1263
710
161
385
216
49
2007
1128
256
612
344
78
3192
1794
407
3027
2639
2255
1873
1495
2501
2096
1696
1298
904
513
1698
1282
869
460
55
973
547
124
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
A.7
System calculations
Battery calculation worksheet
Use this worksheet to determine the amperage capacity of the panel's standby battery. You can obtain operating current requirements for field devices from their respective installation sheets.
Example: There are 10 strobes rated at 80 mA and 40 mini–horns rated at 10 mA connected to NAC circuits powered by AUX 1. Enter 1200 mA in the Alarm box for AUX 1.
Standby
Current (mA)
Alarm
Current (mA)
Base Panel (Form A)
SMK/ACC power (FormB)
AUX 1 load
[1]
AUX 2 load
AUX 3 load
Loop 1 load
Loop 2 load
Loop 3 load
Loop 4 load
Total Current
[2]
× hr × min
÷ 60
+ = mAh
× 1.2
mAh
÷ 1000
Battery size
[3]
====
Notes
[1] Maximum 1.5 A per AUX circuit.
[2] If the Total Current Required value exceeds 6 A, switch part of the load to an auxiliary power source. The auxiliary power source must be UL/ULC listed for Fire Protective Signaling Systems.
[3] If the calculated battery size exceeds 40 Ah, switch part of the load to an auxiliary power source.
Ah
A.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
System calculations
(A) Base panel current load calculation
Card Qty
Standby
Current (mA)
1 PS6
CPU/Display
SL30 (–1)
[1]
SLIC
DLD
ZB16–4
ZA8–2
X485
ZR8
[2]
73
60
11
33
13
117
82
117
1
Totals
[3]
Qty ×××× Standby
Current (mA)
82
Notes
[1] Add 0.75 mA for each energized LED.
[2] Add 18 mA for each energized relay.
[3] Base panel current must be less than 1.32 mA.
(B) Smoke/Accessory (SMK/ACC) Power current load calculation (max 250 mA)
Card Qty
Standby
Current (mA)
Qty ×××× Standby
Current (mA)
Alarm
Current (mA)
CPU/Display
[3]
SL30 (–1)
[1]
117
1
123
1
CDR–3
IOP3A
RPM
[2]
SIGA-UM, -MAB
[4]
60
60
20
2
100
60
20
17
Alarm
Current (mA)
100
135
1
116
60
18
57
20
152
Totals
Notes
[1] Add 0.75 mA for each energized LED.
[2] Add 0.7 mA for each output used.
[3] This value includes RAI currents
Qty ×××× Alarm
Current (mA)
100
Qty ×××× Alarm
Current (mA)
[4] This represents the smoke power requirements. Only the
SIGA–UM or SIGA–MAB that signaled the alarm draws alarm current. The remaining SIGA–UMs or SIGA–MABs do not.
17
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
A.9
System calculations
A.10
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Appendix B
Barcode library
Summary
This appendix contains a set of barcodes that you can use to add location messages.
Content
Uppercase letters • B.2
Numbers and ordinals • B.2
Common words • B.3
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
B.1
Barcode library
Uppercase letters
A
M
Q
E
I
U V
Y
Numbers and ordinals
Z
1 2
5
9
6
0
B
F
J
N
R
1ST
5TH
9TH
2ND
6TH
0TH
3
7
O
S
W
C
G
K
Space
P
T
X
D
H
L
4
8
3RD
7TH
4TH
8TH
Backspace
Delete
Enter
Backspace
Delete
Enter
B.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
BASEMENT
BELOW
CAFETERIA
CEILING
CLASSROOM
CLOSET
COMPUTER
CONFERENCE
CORRIDOR
DAMPER
DETECTOR
Common words
ABORT
ABOVE
ALARM
APARTMENT
APT
AREA
ATRIUM
AUDITORIUM
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
Barcode library
B.3
Barcode library
DOOR
DUCT
EAST
ELECTRICAL
ENTRANCE
EXIT
FAN
FAULT
FIRE
FIRE PUMP
FLAME
FLOOR
FOYER
GARAGE
GENERATOR
GYM
HALL
HEAT
HORN
JANITOR
B.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
KITCHEN
LAB
LEFT
LEVEL
LIBRARY
LOBBY
LOWER
MACHINE
MECHANICAL
MENS
MEZZANINE
MONITOR
NORTH
OFFICE
PARKING
PENTHOUSE
PULL
RELAY
RESTROOM
RIGHT
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
Barcode library
B.5
Barcode library
ROOM
SECURITY
SHAFT
SMOKE
SOUTH
STAGE
STAIRWELL
STOCKROOM
STORAGE
STROBE
SUITE
SUPERVISORY
TROUBLE
UNDER
UPPER
UTILITY
WAREHOUSE
WATERFLOW
WEST
WOMENS
B.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
ZONE
Barcode library
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
B.7
Barcode library
B.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
Appendix C
SIGA-REL programming
Summary
This appendix provides information on how to program the SIGA–REL using the QuickStart Configuration Utility
Content
Application block diagram • C.2
Programming instructions • C.3
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
C.1
SIGA-REL programming
Application block diagram
FACP
SLIC
LOOP DATA
RACCR
SIGA–APS
24VDC
LOOP DATA
MFC–A
SIGA–REL
Minimum system requirements
• A QS1 with SLIC card and appropriately sized standby batteries
• A SIGA–APS mounted in an RACCR enclosure with appropriately sized standby batteries to supply 24 Vdc to the SIGA–REL
• A SIGA–REL mounted in an MFC–A enclosure
Caution: You can not have more than 10 SIGA–
RELs on one loop.
Related documentation
Refer to the SIGA–REL Technical Reference
Manual (P/N 387348) and the latest technical bulletins for installation and connection information.
Refer to the SIGA–APS installation sheet for installation and connection information.
Refer to the RACCR installation sheet for installation information.
C.2
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
SIGA-REL programming
Programming instructions
WARNING: Attempting to program this application without a complete understanding of the operation of the SIGA–REL, the latest technical information, and the consequences of exposing someone to fire suppression agents may cause personal injury, event death.
WARNING: Improper application of fire suppression agents can lead to property damage, serious injury, or loss of life. Consult the applicable NFPA documents and the local authority having jurisdiction (AHJ) for more information.
WARNING: Disabled and Service Group points will not prevent activation of the release circuits.
This application requires the operation of at least two automatic detectors to activate the fire suppression system. In order to meet NFPA 72 requirements, you must program an And group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their Primary and
Alternate Verification properties set to None.
The SIGA–REL has six addressable circuits. To add the SIGA–
REL to the loop controller database you must add three SIGA–
RELs. The first SIGA–REL is for the Abort switch and Manual
Release switch circuits, the second for the two release circuits, and the third for the two prerelease circuits.
Perform these instructions in order from beginning to end.
Check the check box provided as you complete each step.
As a safety precaution, disconnect releasing devices from
SIGA–REL TB4 before downloading setup data to the loop controller.
¨ Add the Abort and Manual
Release Switch circuits
Note: Enter the information exactly as shown to ensure that you program the application according to manufacturer's specifications.
1. Click Configure, then click Cabinets.
2. Select the SLIC connected to the SIGA–REL then click
Configure.
3. Click the Modules tab, then set the Quantity box to 1.
4. Enter the following information:
Device Type: Monitor
Model: REL
Personality: (3) Active B
Message Specification: SIGA–REL1 A001 and ABORT SW
2nd Device Type: Pull
2nd Personality: (1) Alarm B
2nd Message Specification: SIGA–REL1 A002 and MAN
RELEASE SW
5. Click Add.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
C.3
SIGA-REL programming
¨ Add the the two releasing circuits
1. Set the Quantity box to 1.
2. Enter the following information:
Device Type: Output
Model: REL
Personality: (16) Output B
Message Specification: SIGA–REL1 A003 and RELEASE
1&2
2nd Device Type: Monitor
2nd Personality: (0) None
2nd Message Specification: SIGA–REL1 A004 and NOT
USED
3. Click Add.
1. Set the Quantity box to 1.
2. Enter the following information:
Device Type: Output
Model: REL
Personality: (16) Output B
Message Specification: SIGA–REL1 A005 and
PRERELEASE 1&2
2nd Device Type: Monitor
2nd Personality: (0) None
2nd Message Specification: SIGA–REL1 A006 and NOT
USED
3. Click Add.
This is how your entries in the Modules table should look. Your addresses may be different.
Address
126
127
128
129
130
132
Serial Number Device Type Model
Monitor
Pull
Output
Monitor
Output
Monitor REL
REL
REL
REL
REL
REL
Text 1
SIGA–REL1 A001
SIGA–REL1 A002
SIGA–REL1 A003
SIGA–REL1 A004
SIGA–REL1 A005
SIGA–REL1 A006
Text 2
ABORT SW
MAN RELEASE SW
RELEASE 1&2
NOT USED
PRERELEASE 1&2
NOT USED
Personality
(3) Active B
(1) Alarm B
(16) Output B
(0) None
(16) Output B
(0) None
C.4
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
SIGA-REL programming
¨ Create a response that activates the prerelease circuits when any one detector in the protected area signals an alarm
1. Click Configure > Correlations
2. Click the Zones tab, then click Add Zones.
3. Click the Members tab, then click Add Device.
4. Select only the devices required to activate the SIGA–REL prerelease circuits then click OK.
5. Click the Responses tab, click the Response Type arrow, and then select Active.
6. Click Outputs, select the device labeled SIGA REL1 A005
PRERELEASE 1&2, and then click OK.
¨ Create a response that activates the release circuits when two or more detectors in the protected area signal an alarm
Note: To comply with NFPA 72, you must program an And Group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their
Primary and Alternate Verification properties set to None (verified smoke detectors not allowed).
1. Click the And Groups tab, then click Add AND Group.
2. Set the Activation Count box for 2.
3. Click the Members tab, then click Add Device.
4. Select only the detectors required to activate the SIGA–
REL release circuits then click OK.
5. Click the Responses tab, click the Response Type arrow, and then select Active.
6. Click Delays
7. In the Delay On list, click Activation and Restoration.
8. Set the Seconds box to 10.
9. Click Outputs, select the device labeled SIGA REL1 A003
RELEASE 1&2, and then click OK.
¨ the release circuits when someone presses the manual release switch
1. Click the Devices tab, then select the circuit labeled
SIGA–REL A002 MAN RELEASE SW.
2. Click the Responses tab, click the Response Type arrow, and then select Active.
3. Click Outputs, then:
Hold the Ctrl key down
Select the device labeled SIGA REL1 A005 Prerelease
1&2
Select the device labeled SIGA REL1 A003 Release 1&2
Release the Ctrl key then click OK.
Note: The prerelease circuit must appear before the releasing circuit in the response list.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
C.5
SIGA-REL programming
¨ the prerelease circuits when someone presses the Drill switch
Note: Create this response only if required. Pressing Drill will activate the prerelease circuits but pressing Drill a second time will not restore the prerelease circuits. You must press
Reset to silence the prerelease circuits.
1. Click the Devices tab then select the Show Pseudo Points check box.
2. Select the circuit labeled Drill (address 007).
3. Click the Responses tab, click the Response Type arrow, and then select Active.
4. Click Outputs, select the device labeled SIGA REL1 A005
PRERELEASE 1&2, and then click OK.
¨ Retrieve the loop data from the
SLIC
1. Click Configure, then click Cabinets.
2. Select the SLIC connected to the SIGA–REL then click
Configure.
3. Set the Communications Port setting for the COM port used to connect the service computer to the control panel.
4. Click Retrieve Signature Data
5. After the upload has finished, click OK.
¨ Reconcile the actual and expected data
Caution: Clicking Accept Actual will enter the selected device into the database with its current programmed parameters. This will corrupt the database if you have already entered the device.
1. Click the Mapping tab, then click Model.
2. Look for a string of at least six RELs marked with red backgrounds and double-click the first REL in the string.
3. If the serial number displayed in the Module Properties dialog is not the same as the serial number shown on the bar code attached to the SIGA–REL, click Close, and then double-click the next REL in the string.
4. If the serial numbers are the same:
Click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Monitor device type and marked SIGA–REL1
A001 Abort SW, then click OK.
Click Close.
5. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A003 Release 1&2, then click OK.
Click Close.
6. Select the next REL then click Select Expected.
In the Module Selection dialog, select the row that has the
REL with the Output device type and marked SIGA–REL1
A005 Prerelease 1&2, then click OK.
Click Close.
C.6
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
SIGA-REL programming
¨ Send the reconciled data to the loop controller
Click the Controller tab, then click Send Signature Data.
QS4 Technical Reference Manual
Technical Manuals Online! - http://www.tech-man.com
C.7
SIGA-REL programming
C.8
Technical Manuals Online! - http://www.tech-man.com
QS4 Technical Reference Manual
advertisement
Related manuals
advertisement
Table of contents
- 10 System overview
- 11 Component descriptions
- 13 Circuit descriptions
- 17 Controls and indicators
- 18 Controls and indicators behind the flip-down cover
- 19 Controls and indicators on the zone annunciator card
- 20 Interpretation of screen displays
- 24 Installation do's and don'ts
- 25 Installation checklist
- 26 Two ways to install the cabinet: Surface or semi-flush mount
- 28 How to assemble the panel
- 29 Wiring mains ac and earth ground
- 30 System jumper settings
- 32 System addressing
- 36 Terminal definitions
- 44 Connecting a PT–1S printer
- 45 Installing standby batteries
- 46 Connecting a service computer
- 48 Instructions for the Level 1 operator (public mode access)
- 51 Instructions for the Level 2 operator (emergency mode access)
- 53 Instructions for the Level 3 operator (maintenance mode access)
- 56 Instructions for the Level 4 operator (service mode access)
- 57 QuickReference list
- 60 Overview
- 62 QuickStart setup instructions
- 71 Customizing the system configuration
- 79 Setting up an Output Group
- 82 Setting up a Zone
- 96 Notification appliance circuits
- 99 Initiating device circuits
- 102 Coded alarm signaling
- 104 Remote station protective signaling system
- 106 Auxiliary protective signaling
- 108 Pseudo point definitions
- 108 Table 6-1: Main Panel pseudo points
- 108 Table 6-2: Remote Annunciator pseudo points
- 109 Table 6-3: Power Supply pseudo points
- 109 Table 6-4: SLIC card pseudo points
- 110 Table 6-5: Dialer pseudo points
- 111 Table 6-6: General CPU pseudo points
- 112 Maintenance tasks