Ge Est QS4 Technical Reference Manual

Ge Est QS4 Technical Reference Manual
Add to My manuals

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Ge Est QS4 Technical Reference Manual | Manualzz

QS4 Fire Alarm Control Panel

Technical Reference Manual

P/N 3100186 • Rev 2.0 • 12JUL01

Technical Manuals Online! - http://www.tech-man.com

Compliance Statement

Limitation of Liability

Fire Alarm System

Limitations

FCC Compliance Statement

The QS4, hereinafter referred to as the FACP or control panel, when properly installed, operates as a Local Protected Premises Fire Alarm

System in accordance with the following standards:

• NFPA Standard 72, 1999 Edition

• Underwriters Laboratories Standard 864, 7th Edition

• Underwriters Laboratories of Canada Standard ULC S527

In addition, Auxiliary Fire Alarm System operation requires a Reverse

Polarity Module (RPM). Central Station Fire Alarm System operation requires a Dialer card (DLD).

Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory.

Edwards Systems Technology (EST) shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of EST products beyond the cost of repair or replacement of any defective products. EST reserves the right to make product improvements and changes to product specifications at any time.

While every precaution was taken during the preparation of this document to ensure its accuracy, EST assumes no responsibility for errors or omissions.

Automatic fire alarm systems can not guarantee against property damage, loss of property, or loss of life. An automatic fire alarm system's ability to provide early warning of a developing fire may be limited for a variety of reasons, but mainly due to improper installation or maintenance.

The best way to minimize system failures is to perform regularly scheduled preventive maintenance in accordance with national and local fire codes. All system components and wiring should be tested and maintained by trained fire alarm system professionals.

This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply within the limits for Class A computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment.

Operation of this equipment is likely to cause interference, in which case the user at his own expense, will be required to take whatever measures may be required to correct the interference.

Copyright © 2001. All rights reserved.

Technical Manuals Online! - http://www.tech-man.com

Chapter 1

Chapter 2

Chapter 3

Chapter 4

Chapter 5

Chapter 6

Content

About this manual • iii

Related documentation • iv

Document history • vi

Product description • 1.1

System overview • 1.2

Component descriptions • 1.3

Circuit descriptions • 1.5

Controls and indicators • 1.9

Controls and indicators behind the flip-down cover • 1.10

Controls and indicators on the zone annunciator card • 1.11

Interpretation of screen displays • 1.12

Installation • 2.1

Installation do's and don'ts • 2.2

Installation checklist • 2.3

Two ways to install the cabinet: Surface or semi-flush mount • 2.4

How to assemble the panel • 2.6

Wiring mains ac and earth ground • 2.7

System jumper settings • 2.8

System addressing • 2.10

Terminal definitions • 2.14

Connecting a PT–1S printer • 2.22

Installing standby batteries • 2.23

Operating instructions • 3.1

Instructions for the Level 1 operator (public mode access) • 3.2

Instructions for the Level 2 operator (emergency mode access) • 3.5

Instructions for the Level 3 operator (maintenance mode access) • 3.7

Instructions for the Level 4 operator (service mode access) • 3.10

QuickReference list • 3.11

Programming instructions • 4.1

Overview • 4.2

QuickStart setup instructions • 4.4

Customizing the system configuration • 4.13

Setting up an Output Group • 4.21

Setting up a Zone • 4.26

Standard applications • 5.1

Notification appliance circuits • 5.2

Initiating device circuits • 5.5

Coded alarm signaling • 5.8

Remote station protective signaling system • 5.10

Auxiliary protective signaling • 5.12

Maintenance instructions • 6.1

Pseudo point definitions • 6.2

Maintenance tasks • 6.6

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

i

Content

Appendix A

Appendix B

Appendix C

System calculations • A.1

Notification appliance circuit maximum wire length calculation • A.2

Signature loop maximum wire length calculations • A.3

Battery calculation worksheet • A.8

Barcode library • B.1

SIGA-REL programming • C.1

Application block diagram • C.2

Programming instructions • C.3

ii

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Content

About this manual

Organization

Safety information

This manual provides information on how to properly install, wire, and maintain the FACP and related components, and is organized as follows:

Chapter 1 provides a detailed description of the fire alarm control panel and its operation.

Chapter 2 provides instructions for installing the fire alarm control panel.

Chapter 3 provides instructions for operating the control panel.

Chapter 4 provides instructions for programming the fire alarm system from the front panel.

Chapter 5 provides simplified wiring schematics for standard applications.

Chapter 6 provides instructions for maintaining the system.

Appendix A provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries.

Appendix B provides a set of bar codes that you can use to enter text for location messages.

Appendix C provides information on how to program the SIGA–REL using the QS–CU (QuickStart Configuration Utility).

Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment.

WARNING: Warnings are used to indicate the presence of a hazard which will or may cause personal injury or death, or loss of service if safety instructions are not followed or if the hazard is not avoided.

Caution: Cautions are used to indicate the presence of a hazard which will or may cause damage to the equipment if safety instructions are not followed or if the hazard is not avoided.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

iii

Content

Related documentation

National Fire Protection Association

1 Batterymarch Park

P.O. Box 9101

Quincy, MA 02269-9101

Underwriters Laboratories, Inc.

333 Pfingsten Road

Northbrook, IL 60062-2096

Underwriters Laboratories of

Canada

7 Crouse Road

Scarborough, ON

Canada M1R 3A9

NFPA 70 National Electric Code

NFPA 72 National Fire Alarm Code

NFPA 11 Low-Expansion Foam Systems

NFPA 11A Medium- and High-Expansion Foam Systems

NFPA 12 Carbon Dioxide Extinguishing Systems

NFPA 13 Sprinkler Systems

NFPA 15 Water Spray Fixed Systems for Fire Protection

NFPA 16 Deluge Foam-Water Sprinkler and Foam-Water Spray

Systems

NFPA 17Dry Chemical Extinguishing Systems

UL 38 Manually Actuated Signaling Boxes

UL 217 Smoke Detectors, Single & Multiple Station

UL 228 Door Closers/Holders for Fire Protective Signaling

Systems

UL 268 Smoke Detectors for Fire Protective Signaling Systems

UL 268A Smoke Detectors for Duct Applications

UL 346 Waterflow Indicators for Fire Protective Signaling

Systems

UL 464 Audible Signaling Appliances

UL 521 Heat Detectors for Fire Protective Signaling Systems

UL 864 Standard for Control Units for Fire Protective Signaling

Systems

UL 1481 Power Supplies for Fire Protective Signaling Systems

UL 1638 Visual Signaling Appliances

UL 1971 Visual Signaling Appliances

Canadian Electrical Code Part 1

ULC S527 Standard for Control Units for Fire Alarm Systems

ULC S524 Standard for the Installation of Fire Alarm Systems

ULC S536 Standard for the Inspection and Testing of Fire

Alarm Systems

ULC S537 Standard for the Verification of Fire Alarm Systems

ULC ORD–C693–1994 Central Station Fire Protective Signaling

System and Services iv

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Content

Edwards Systems Technology

6411 Parkland Drive

Sarasota, FL 34243

2–CTM City Tie Module Installation Sheet (P/N 270496)

CDR–3 Bell Coder Installation Sheet (P/N 3100023)

DLD Dual Inline Dialer Installation Sheet (P/N 3100187)

PS6 Power Supply Card Installation Sheet (P/N 3100201)

QSA–1(X), QSA–2(X) Remote Annunciator Cabinet Installation

Sheet (P/N 3100295)

QS–CPU(X) CPU/Display Unit Installation Sheet (P/N 3100276)

SL30, SL30–1 LED/Switch Card Installation Sheet (P/N

3100193)

SLIC Signature Intelligent Controller Card Installation Sheet

(P/N 3100192)

RS485 (NT–A) Card and QS–232 UART Module Installation

Sheet (P/N 3100191)

ZA8–2 Class A Zone Card Installation Sheet (P/N 3100189)

ZB16–4 Class B Zone Card Installation Sheet (P/N 3100188)

ZR8 Relay Card Installation Sheet (P/N 3100190)

SIGA–APS Auxiliary Power Supply Installation Sheet (P/N

387342)

Signature Series Intelligent Smoke and Heat Detectors

Applications Bulletin (P/N 270145)

Signature Series Component Installation Manual (P/N 270497)

EST Strobe Applications Guide (P/N 85000-0049)

QuickStart Online Help Utility (P/N 7350047)

QuickStart ULI and ULC Compatibility Lists (P/N 3100335)

Network Hardware Technical Reference (P/N 250100)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

v

Content

Document history

Date

24JUN01

12JUL01

Revision

1.0

2.0

Description of changes

Original release.

Corrections and additions on pp 2.12, 2.24, 3.9, 4.4, 4.8, 4.10, 4.19,

A.3.

vi

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 1

Product description

Summary

This chapter provides a detailed description of the fire alarm control panel and its operation.

Content

System overview • 1.2

Component descriptions • 1.3

Circuit descriptions • 1.5

Controls and indicators • 1.9

Controls and indicators behind the flip-down cover • 1.10

Controls and indicators on the zone annunciator card • 1.11

Interpretation of screen displays • 1.12

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.1

Product description

System overview

System hardware capabilities

Hardware capabilities vary depending on cabinet size and option card configuration, but generally:

• Up to four Class A or Class B Signature signaling line circuits that support up to 250 single-address Signature devices each

• Up to 40 Class A or 48 Class B initiating device circuits (IDC). Combination systems can not exceed 40 IDC circuits total

• Up to 16 Class A or 20 Class B notification appliance

• Up to two 30-zone displays

• Up to 96 dry-contact relay

• 4.5 amps of 24 Vdc power for external notification appliances

• Battery charger capable of charging batteries rated up to 40 Ah. Maximum battery size for

ULC applications is 30 Ah

• Up to eight, fully-supervised, mirrored or customized remote annunciators

Minimum system requirements

A Local Protected Premises Fire Alarm System requires only the FACP (CPU, PS6, and enclosure) with at least one SLIC, ZB16–4, or

ZA8–2 card programmed with at least one audible output circuit and one alarm input circuit.

In addition to the hardware requirements of a

Local system:

• Add a 2–CTM City Tie Module for an Auxiliary

Fire Alarm System

• Add a DLD Dual Line Dialer Card or RPM

Reverse Polarity Module for a Remote

Supervising Station Fire Alarm System

• Add a DLD Dual Line Dialer Card or RPM

Reverse Polarity Module for a Central Station

Fire Alarm System

• Add a SIGA–REL for Releasing Device Service

Normal operating mode description

The panel operates in normal mode in the absence of any alarm, supervisory, trouble, and monitor events. In normal mode, the control panel monitors the system for any events.

Off-normal operating mode description

The panel operates in off-normal mode any time there is an event introduced into the system.

When this happens, the CPU:

• Changes the contact positions on the appropriate common relays

• Activates all common alarm outputs (alarm events only)

• Turns on the panel buzzer

• Executes the appropriate programmed output response for the input that signaled the event

• Sends a record of the event to the appropriate display queue and out the serial port

If there is no operator in attendance, the panel displays the content of the highest priority display queue containing a record.

If there is an operator in attendance, the panel displays the content of the current display queue regardless of any new events introduced into the system.

Failsafe operating mode description

The panel operates in failsafe mode when the

CPU loses the ability to communicate with the PS6 and JP1 on the PS6 is in the ON position. When this happens, the power supply:

• Closes the common trouble relay contacts

• Instructs the dialer to send the default trouble message

• Monitors the system for any alarm events

If an alarm event occurs, the power supply:

• Changes the contact positions on the common alarm relay

• Turns on all conventional common alarm outputs. Signature common alarm outputs are not affected.

• Instructs the dialer to send the default alarm message

1.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Component descriptions

1 2 3 6A 4

J6

J5

J8

J7

JP1 CONFIG URATION

PIN 2 & 3 = RTS

JP1

3 1 J2

5 6B 7 8

Product description

9

10

15

1. Cabinet enclosure: Houses the panel electronics and standby batteries.

2. SL30–1 LED/Switch Card: Provides thirty circuits for point or zone annunciation. Each circuit has two LEDs for annunciating alarm, supervisory, and trouble signals, and a button numbered from 31 to 60.

3. SL30 LED/Switch Card: Same as SL30–1 except the buttons are numbered 1–30.

14 13 12 11

4. CPU/Display: Provides operator access to system messages, status information, and programming menus, and executes system responses based on the panel programming.

5. PS6 Power Supply Card: Provides primary dc power to the panel electronics and external circuits. The PS6 also provides common alarm, supervisory and trouble relays for remote station supervision.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.3

Product description

6. RS485 (NT–A) Class A Card: The NT–A comprises the RS485 card and QS–232 UART module. Together these provide an additional

RS–232 channel to allow Class A communication between the control panel and other remote annunciator panels. Control panels require installation of both cards while remote annunciator panels only require installation of a

QS–232 card and only then if you want to connect a printer or service computer.

7. ZA8–2 Class A Conventional Zone Card:

Provides six dedicated Class A initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The

ZA8–2 also provides two circuits that you can configure as IDCs or as 24 Vdc notification appliance circuits (NACs).

8. ZB16–4 Class B Conventional Zone Card:

Provides twelve dedicated Class B initiating device circuits (IDCs) for connecting two-wire smoke detectors and dry-contact initiating devices. The ZB16–4 also provides four circuits that you can configure as IDCs or as Class B 24

Vdc notification appliance circuits (NACs).

9. QS–Cable12 Expansion Cable: Extends the

CPU data and power bus to circuit cards installed on the lower DIN rail in the 12-option cabinet.

10. ZR8 Relay Card: Provides eight dry-contact relays. You can configure each relay for normally-open or normally-closed operation.

11. DLD Dual Line Dialer Card: Provides two telephone line connections for sending system messages to a compatible Digital Alarm

Communicator Receiver.

12. SLIC Signature Loop Intelligent Controller

Card: Provides one Class A or Class B signaling line circuit (loop) for connecting Signature series detectors and modules. The SLIC also provides two Class A or Class B notification appliance circuits (NACs) for connecting polarized 24 Vdc notification appliances (horns, strobes).

13. Standby batteries: Provides dc power to the panel electronics in the absence of ac power.

14. Transformer: Changes the mains ac supply voltage for the power supply card.

15. AC wiring block and fuse holder: Provides connections for mains ac (primary power) and 5A fuse.

1.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Product description

Circuit descriptions

PS6 Power Supply Card

1. Relay 1 (Common Alarm)

Style: Form C

Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Nonsupervised and power-limited only when connected to a power-limited source

2. Relay 2 (Common Supervisory)

Style: Normally-open

Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Nonsupervised and power-limited only when connected to a power-limited source

3. Relay 3 (Common Trouble)

Style: Normally-open, held closed

Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Nonsupervised and power-limited only when connected to a power-limited source

4. Relay 4 (Programmable)

Style: Normally-open

Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Nonsupervised and power-limited only when connected to a power-limited source

5. Smoke/Accessory Power

Output: Continuous or interruptible via jumper selection

Voltage: 24 Vdc, regulated

Current: 250 mA

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Supervised and power-limited

6. RS485

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Wire type: Twisted pair, six twists per foot minimum

Circuit capacitance: 0.4 µ F

Circuit resistance: 100 Ω

Supervised and power-limited

7. RS232

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Nonsupervised and power-limited

Wire length: 20 ft maximimum

1

9

2 3 4 5 6

7

8

8. AUX Power #1, #2, and #3

Voltage: 17.5 – 26.4 Vdc FWR (full wave rectified)

Current: 1.5 A each

Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)

Power-limited and supervised for short circuit conditions only

9. Battery Circuit

Charge current: 2 A

Charge capacity: 40 Ah (UL), 30 Ah (ULC)

Supervised and nonpower-limited

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.5

Product description

SLIC Signature Loop Intelligent Controller Card circuits

1. NAC #1

Configuration: Class B or Class A

Output voltage: 24 Vdc, nominal

Output current: 2.0 A @ 24 Vdc

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

End of line resistor: 10 k Ω , 1/2W

Supervised and power-limited

2. NAC #2

Configuration: Class B or Class A

Output voltage: 24 Vdc, nominal

Output current: 1.0 A @ 24 Vdc

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

End of line resistor: 10 k Ω , 1/2W

Supervised and power-limited

3. Signature Loop

Configuration: Class B (Style 4) or Class A (Style 6)

Capacity: 125 Signature detectors, 125 Signature single-address modules

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

Circuit resistance: 65 Ω

Circuit capacitance: 0.3 µ F

Supervised and power-limited

4. NAC Riser In/Out

Voltage: 24 Vdc, nominal

Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )

ZR8 Relay Card circuits

1. Dry-contact relays R1 – R4

Outputs: Normally-open or normally-closed contacts via jumper selection

Contact rating: 24 Vdc @ 1.0 A

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

Nonsupervised, and power-limited only when connected to a power-limited source

2. Dry-contact relays R5 – R8

Outputs: Normally-open or normally-closed contacts via jumper selection

Contact rating: 24 Vdc @ 1.0 A

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

Nonsupervised, and power-limited only when connected to a power-limited source

1

4

1

2

2

3

1.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

ZB16–4 Class B Conventional Zone Card circuits

1. IDC Circuits Z1 – Z12

Wiring configuration: Class B

Detector voltage: 20.33 – 24.76 Vdc, max ripple 2000 mV

Short circuit current: 75.9 mA, max.

Resistance: 50 Ω , max.

Capacitance: 100 µ F, max

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

End of line resistor: 4.7 k Ω , 1/2W

Supervised and power-limited

2. NAC Circuits Z13 – Z16

Wiring configuration: Class B

Output voltage: 24 Vdc, nominal

Output current: 2.0 A @ 24 Vdc

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

End of line resistor: 10 k Ω , 1/2W

Supervised and power-limited

IDC specifications apply when programmed as IDC circuit

3. R1

Voltage: 24 Vdc, nominal

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

4. R2

Voltage: 24 Vdc, nominal

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

ZA8–2 Class A Conventional Zone Card circuits

1. IDC Circuits Zone 1 – Zone 3, Zone 5 – Zone 7

Wiring configuration: Class A

Detector voltage: 19.90 – 22.46 Vdc, max ripple 2000 mV

Short circuit current: 75.9 mA, max.

Resistance: 50 Ω , max.

Capacitance: 100 µ F, max

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

End of line resistor: 4.7 k Ω , 1/2W

Supervised and power-limited

2

)

2. NAC Circuits Zone 4, Zone 8

Wiring configuration: Class A

Output voltage: 24 Vdc, nominal

Output current: 2.0 A, 24 Vdc

Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )

End of line resistor: 10 k Ω , 1/2W

Supervised and power-limited

IDC specifications apply when programmed as IDC circuit

3. NAC PWR IN (Zone 4)

Voltage: 24 Vdc, nominal

Wire size: 18 to 12 AWG (0.75 to 2.5 mm 2 )

4. NAC PWR IN (Zone 8)

Voltage: 24 Vdc, nominal

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

)

1

1

1

1

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

Product description

2

3

4

1.7

2

4

3

2

Product description

DLD Dual Line Dialer Card circuits

1. Line #1

Supervised and nonpower-limited

2. Line #2

Supervised and nonpower-limited

1 2

RS485 (NT–A) Class A Card circuits

1. Secondary RS485 channel

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

Supervised and power-limited

)

2. Primary RS485 channel

Wire size: 18 to 12 AWG (0.75 to 2.5 mm

2

Supervised and power-limited

)

Note: JP1 installed for ground fault detection on RS485 circuits.

1 2

1.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Product description

Controls and indicators

1 2 3 4 5 6 7 8 9

3

4

1

2

6 11 16 21 26

7 12 17 22 27

8 13 18 23 28

9 14 19 24 29

5 10 15 20 25 30

1 6 11 16 21 26

2

3

7

8

12 17

13 18

22 27

23 28

4 9 14 19 24 29

5 10 15 20 25 30

1 2 3 4 5 6 7 8 9 0

12 11 10

1. Text display and controls: Displays system messages, status information, programming menus.

Moves the cursor up one line at a time or to the previous record in the display queue

Moves the cursor down one line at a time or to the next record in the display queue

Moves the cursor right one character at a time or to the next display queue

Moves the cursor left one character at a time or to the previous display queue

Enters operator input and selects menu items

2. Alarm LED: Indicates the panel posted an alarm event record into the corresponding display queue.

3. Supervisory LED: Indicates the panel posted a supervisory event record into the corresponding display queue.

4. Disable/Test LED: Indicates part of the system is disabled or is currently under test.

Disabled components also signal a system trouble.

5. Monitor LED: Indicates the panel posted a monitor event record into the corresponding display queue.

6. Trouble LED: Indicates the panel posted a trouble event record into the corresponding display queue.

7. Ground Fault LED: Indicates a ground fault in the system wiring. Ground faults also signal a system trouble.

8. CPU Fail LED: Indicates an unexpected reboot or failure with the microprocessor. CPU failures also signal a system trouble.

9. Power LED: Indicates the panel has ac power.

10. Panel Silence/Acknowledge button/LED:

Turns off the panel buzzer and acknowledges all events. The Panel Silenced LED indicates that all off normal events have been acknowledged and the internal buzzer is off.

11. Status button: Displays the Status menu from which you can identify active or disabled points in the system.

12. Help button: Provides additional information for the event record selected on the display.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.9

Product description

Controls and indicators behind the flip-down cover

7

4

8

5

9

6

3

1 6 11 16 21 26

2 7 12 17 22 27

3

4

8

9

13 18

14 19

23 28

24 29

5 10 15 20 25 30

1

2

6 11 16 21 26

7 12 17 22 27

3

4

8 13 18 23 28

9 14 19 24 29

5 10 15 20 25 30

1 2 3 4 5 6 7 8 9 0

2 1

1. Enable Controls key switch: Gives priority access to control functions reserved for operators with Level 2 access.

2. Barcode scanner jack: Input point for optional barcode scanner.

3. Numeric keypad: Numbered buttons for entering data and selecting menu options.

4. Reset button: Restores devices or zones in alarm or trouble to their standby condition. The

LED indicates when the panel is resetting.

5. Alarm Silence button: Turns active notification appliances off according to the panel programming. Pressing Alarm Silence a second time turns them back on. The LED indicates when the panel is in alarm and operating with notification appliances turned off.

6. Drill button: Turns notification appliances on according to the panel programming but does not place the panel in alarm. The LED indicates when the panel is in Drill mode.

7. Menu button: Displays the operator menus.

8. Delete button: Returns to the previous menu or back spaces the cursor.

9. Enter button: Press the Enter button to accept information from the operator or continue to the next item.

1.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Controls and indicators on the zone annunciator card

1 2 3

1 6 11 16 21 26

2 7 12 17 22 27

3

4

8 13 18 23 28

9 14 19 24 29

5 10 15 20 25 30

Product description

1. Zone display button: Displays an event record for each device in the corresponding zone that signaled an alarm.

2. Zone active LED: Indicates a device in the corresponding zone signaled an alarm condition.

3. Zone trouble LED: Indicates a device or wiring fault in the corresponding Zone.

Note: ULC requires that every fire panel have the capability to visually display system status by means of specific indicators for each zone. All status changes must clearly indicate that the information is an Alarm (ALM), Supervisory

(SUP), Trouble (TBL), or Monitor (MON).

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.11

Product description

Interpretation of screen displays

HH:MM:SS MM/DD This is what the panel display looks like when there are no event records posted in a display queue.

HH:MM:SS is the current time in hours, minutes, and seconds

MM/DD is the current month and date

nnnn is the number times the panel went into alarm since being placed into service

System

Normal

Project Name

Alarm History: nnnn

HH:MM:SS

Axxx Dxxx nnn event name

Custom message 1

Custom message 2

nnn event name

Custom message 1

Custom message 2

ALM SUP TRBL MON aaa sss ttt mmm

This is what the panel display looks like when there are event records posted in a display queue.

HH:MM:SS is the current time in hours, minutes, and seconds

Axxx is the current number of active points

Dxxx is the current number of disabled points

These items comprise the event record:

nnn is the posting sequence number (001 = first, 002 = second, and so on)

event name is the event produced when the device changed states.

Refer to Table 1-1.

P:pp C:cc D:ddd is the address of the device that signaled the event (P = panel number, C = card number, D = device number)

The event record may also include a custom message that typically indicates the location of the device, depending on the panel programming.

These items indicate the content of the display queues:

aaa is the number of alarm event records (highest priority)

sss is the number of supervisory event records

ttt is the number of trouble event records

mmm is the number of monitor event records (lowest priority)

1.12

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 1-1: Event descriptions

Event name

ALARM ACTIVE

ALARM VERIFY

AND GROUP

BAD PRSONATY

BAD TYPE

COMM FAULT

DEV COMPATIB

DIRTY HEAD

DISAB SOUND

DISABLED

GROUND FAULT

HEAT ALARM

INTERNAL TBL

LCL MONITOR

LCL TROUBLE

MAINT ALERT

MATRIX GROUP

MONITOR

OBJECT RUN

PREALARM

PULL STATION

SERVICE GROUP

SUPERVISORY

SWITCH

TAMPER

TEST

TIME CONTROL

TROUBLE

TROUBLE OPEN

TROUBLE SHORT

UNEXPECT DEV

WATERFLOW

ZONE ALARM

ZONE MONITOR

ZONE SUPER

Event type

Monitor

Trouble

Monitor

Alarm

Monitor

Monitor

Monitor

Alarm

Trouble

Supervisory

Monitor

Supervisory

Trouble

Monitor

Trouble

Alarm

Monitor

Alarm

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Alarm

Trouble

Trouble

Trouble

Trouble

Alarm

Alarm

Monitor

Supervisory

Product description

Description

Smoke detector active

Alarm active. Performing auto reset.

And group active

SIGA personality mismatch

SIGA type mismatch

Communication failure

SIGA compatibility fault

Dirty smoke detector. No compensation remaining

Sounder is disabled (EN–54 only)

Device is disabled

Ground fault

Heat detector active

Internal system trouble

Common monitor

Generic trouble.

Dirty smoke detector. Some compensation remaining

Matrix group active

Active non-latching input circuit.

Service group is enabled and governing all defined objects

Possible fire condition exists.

Manual fire alarm box active

Service group active

A device used to monitor a component of the fire suppression system is active

Operator presses switch on LED/Switch card

Sprinkler tamper active

A member of a Service group under test is activated

Time control active

Common trouble

Open detected on a supervised output device's field wiring

Short detected on a supervised output device's field wiring

Signature device not defined in database

Water flowing through the sprinkler system

Alarm zone active

Monitor zone active

Supervisory zone active

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

1.13

Product description

1.14

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 2

Installation

Summary

This chapter provides instructions for installing the fire alarm control panel.

Content

Installation do's and don'ts • 2.2

Installation checklist • 2.3

Two ways to install the cabinet: Surface or semi-flush mount • 2.4

How to assemble the panel • 2.6

Wiring mains ac and earth ground • 2.7

System jumper settings • 2.8

System addressing • 2.10

Terminal definitions • 2.14

Connecting a PT–1S printer • 2.22

Installing standby batteries • 2.23

Connecting a service computer • 2.24

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.1

Installation

Installation do's and don'ts

When installing cabinets...

DO use fasteners that can support the full weight of the cabinet and standby batteries. Tighten firmly to avoid vibrations.

DO NOT drill inside the cabinet with circuit cards installed.

Remove all metal filings before installing the circuit cards.

DO NOT recess the cabinet into the wall deeper than 2–11/16 inches (68.2 mm) from the finished wall surface to allow room for the trim kit.

When installing circuit boards...

When installing circuit wiring...

When installing Signature loops...

DO ground yourself with an approved static-protective wrist strap when handling circuit boards.

DO keep circuit boards in their protective antistatic packaging.

Remove only for inspection or installation.

DO NOT touch component leads and connector pins when handling circuit boards.

DO disconnect ac power and batteries before installing or removing circuit boards. Installing or removing circuit boards while the control panel is energized may damage the equipment.

DO use appropriately sized wire for the application.

Incorrectly-sized wires degrade circuit performance.

DO make sure there are no wire-to-ground shorts or wire-towire shorts before connecting field wires to the panel.

DO NOT over tighten screw terminals. Over tightening may strip screw terminal threads and cause loose connections.

DO NOT install more than fifteen SIGA–UMs or MABs configured for two-wire smoke detectors on a loop.

DO NOT install more than seven SIGA–UMs or MABs configured for two-wire smoke detectors on loops with isolator devices.

DO NOT install more than ten SIGA–RELs on a loop. You must use the QuickStart configuration utility to program a

SIGA–REL. Refer to the technical manual supplied with the

SIGA–REL and appendix C of this manual for programming information.

When installing standby batteries...

DO NOT install standby batteries until after you completely install and test the system.

2.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

Installation checklist

¨ Prepare the site

¨ Unpack the equipment

Make sure the installation location is free from construction dust and debris, and immune to extreme temperature ranges and humidity.

Allow enough floor and wall space so the panel can be installed and serviced without obstructions.

Pull and tag all field wiring. See Appendix A for wire length calculations.

Open the shipping container and carefully unpack the equipment. Check for any visible signs of damage. If there is any damage, return the equipment to the place of purchase.

Keep the container and packing material until after completely installing and testing the equipment. Use the shipping container to return the equipment to the manufacturer.

Verify the shipping container contains the correct parts. If any parts are missing or damaged, return the equipment to the manufacturer.

See Figure 2-1 for cabinet dimensions.

¨ Install the cabinet

¨ Assemble the panel

¨ Wire mains ac and earth ground Bring the primary power conductors into the left side

(nonpower-limited area) of the cabinet and wire to the ac terminal block.

¨ Connect the field wiring

WARNING: Make sure that the circuit breaker providing ac power is switched off before connecting wires to the terminal block.

Bring the field wiring into the power-limited area of the cabinet.

Verify there are no open or shorts then connect the wires to their respective terminals.

Refer to chapter 4.

¨ Use the AutoLearn and

AutoLoop utilities to configure the system

¨ Customize the system configuration

¨ Install the standby batteries

Refer to chapter 4.

Do not connect standby batteries to the panel until after completely testing the panel.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.3

Installation

Two ways to install the cabinet: Surface or semi-flush mount

Surface mount instructions

1. Position the cabinet on the finished wall surface.

2. Fasten the cabinet to the wall surface where indicated. Tighten firmly.

4-7/8 in

(123.8 mm)

Semi-flush mount instructions

1. Frame the interior wall as required to support the full weight of the cabinet and standby batteries.

2. Fasten the cabinet to the framing studs where indicated. Tighten firmly.

2-11/16 in

(68.2 mm)

2-3/16 in

(55.6 mm)

2.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

D3 D4

D1

D5

D2

5-option cabinet

12-option cabinet

D1

18 in

(45.72 cm)

30 in

(76.2 cm)

D2

18-5/8 in

(47.31 cm)

18-5/8 in

(47.31 cm)

D3

4-7/8 in

(12.38 cm)

4-7/8 in

(12.38 cm)

Note: Add 1-1/2 in (3.81 cm) to D1 and D2 dimensions for trim kit.

Dimensions

D4

16-5/8 in

(42.23 cm)

16-5/8 in

(42.23 cm)

D5

13 in

(33.00 cm)

25 in

(63.50 cm)

Figure 2-1: Dimensions for 5-option and 12-option cabinets (arrows show mounting hole locations)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.5

Installation

How to assemble the panel

Circuit card instructions

1. Lock the PS6 onto the DIN rail and configure jumpers.

2. Attach the ground wire to the cabinet. Tighten the lock nut firmly to ensure a good mechanical and electrical connection.

3. Plug the transformer into the PS6.

4. Install remaining option cards according to their respective installation sheets.

Use a QS–Cable12 to connect option cards on the top and bottom DIN rails in a 12-option cabinet.

Door mounting instructions

1. Bolt the door to the cabinet back box.

2. Attach one end of the ground strap to the door and the other to the back box.

3. Screw the CPU/Display unit to the cabinet door.

4. Plug one end of the ribbon cable into the

CPU/Display and the other end into the PS6.

5. Screw the key switch ground wire and the

CPU cover to the cabinet door.

*Actual cabinet door not shown

2.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

Wiring mains ac and earth ground

H

(L1)

G

(E)

N

(L2)

CAUTION: The middle connection on the ac terminal block makes a mechanical connection to chassis (earth) ground. Do not allow the ac hot and neutral conductors to make contact with the middle connector on the ac terminal block.

Wiring instructions

1. Bring the mains ac conductors into the cabinet through the 3/4–1/2 inch combination knock-outs on the left side or upper left corner of the cabinet.

2. Wire the hot (H, L1), neutral (N, L2), and ground (G, E) conductors to the ac terminal block as shown.

3. Insert tabbed end of terminal block cover

(deadfront) into the slot provided on the side of the cabinet.

Notes

Keep power-limited wires in the shaded area and nonpower-limited wires in the nonshaded area.

Maintain a 1/4-inch separation between the mains ac and battery wires (power-limited) and and all other nonpower-limited wiring at all times.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.7

Installation

System jumper settings

PS6 Power Supply Card jumpers

JP2 configures the Smoke/Accessory power output for constant or resettable 24 Vdc.

• Set JP2 to ACC PWR to provide constant

24 Vdc for external equipment.

• Set JP2 to SMK PWR to provide resettable

24 Vdc for four-wire smoke detectors

JP1 configures the panel for failsafe operation.

Failsafe allows the system to generate output responses even when the CPU loses communication with the power supply card.

• Set JP1 to ON to turn failsafe mode on

• Set JP1 to OFF to turn failsafe mode off

SLIC Signature Loop Intelligent Controller

Card jumpers

JP1 and JP2 selects the signal that the SLIC uses for the notification appliances connected to

NAC1.

Note: NAC 2 always uses the external signal connected to TB2–3 and TB2–4.

• Set JP1 and JP2 to INT to use the 24 Vdc that comes from the PS6 over the bus connection.

• Set JP1 and JP2 to EXT to use the 24 Vdc that comes from an external source connected to TB2–3 and TB2–4.

CAUTION: Do not set JP1 and JP2 to EXT if strobes are connected to NAC 1 and a coded signal is connected to TB2–3 and TB2–4.

JP2

ACC PWR

SMK PWR

JP1

ON OFF

JP1 JP2

EXT

INT

2.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

ZR8 Relay Card jumpers

JP1 – JP8 configure which relay contacts are present on the terminal connections for R1 – R8, respectively.

The normal operating state of the relay (on or off when the panel is normal) determines whether the terminal connections are normally-open or normally-closed.

The figure to the right shows the relay contact positions when the relay is turned off.

Installation

JP4

R4+ R4–

RS485 (NT–A) Class A Card jumpers

JP1 configures ground fault supervision for

Class A remote annunciators.

• Set a shorting plug across JP1–1 and JP1–2 when the PS6 powers the remote annunciator and provides ground fault supervision

• Set a shorting plug across JP1–2 and JP1–3 when an external supply powers the remote annunciator and provides ground fault supervision

1 2 3

JP1

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.9

Installation

System addressing

Card addresses

Each option card installed in the panel is assigned a unique card address. Only the SLIC,

ZB16–8, ZA8–2, and ZR–8 have card addresses that you can set. The CPU, DLD and PS6 card addresses are fixed.

00: Reserved for the CPU

01–07: Used for the SLIC, ZB16–8, ZA8–2, and

ZR–8

08–13: Used for the ZB16–8, ZA8–2, and ZR–8

14: Reserved for the DLD

15: Reserved for the PS6

ON

1 2 3 4

= 01

ON

1 2 3 4

= 02

ON

1 2 3 4

= 03

ON

1 2 3 4

= 04

ON

1 2 3 4

= 05

ON

1 2 3 4

= 06

ON

1 2 3 4

= 07

ON

1 2 3 4

= 08

ON

1 2 3 4

= 09

ON

1 2 3 4

= 10

ON

1 2 3 4

= 11

ON

1 2 3 4

= 12

ON

1 2 3 4

= 13

Tip: When you install the option cards, set the card addresses in consecutive order as you move away from the power supply starting at address 01.

01 02 03 04

07 06 05

2.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

SLIC Signature Loop Intelligent Controller

Card device addresses

The device address format is PPCCDDD, where:

PP is the panel number (01)

CC is the card number (any number between 1 and 7 depending on the setting of SW1)

DDD is the device or circuit number, where:

• 001–125 are Signature automatic detectors and SIGA–IM isolator modules

• 126–250 are Signature modules

• 270 is the NAC 1 output circuit

• 271 is the NAC 2 output circuit

Note: Some Signature modules use two or more device addresses.

ZR8 Relay Card device addresses

The device address format is PPCCDDD, where:

PP is the panel number (01)

CC is the card number (any number between 1 and 13 depending on the setting of SW1)

DDD is the device number, where 001 – 008 are relays 1 – 8, respectively

PPCC002

PPCC001

PPCC006

PPCC005

PPCC270

PPCC271

Installation

PPCC001 to

PPCC125

PPCC126 to

PPCC250

PPCC003

PPCC004

PPCC007

PPCC008

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.11

Installation

ZB16–4 Class B Conventional Zone Card device addresses

The device address format is PPCCDDD, where:

PP is the panel number (01)

CC is the card number (any number between

1 and 13 depending on the setting of SW1)

DDD is the circuit number, where:

• 001 – 012 are IDC circuits Z1 – Z12, respectively

• 013 – 016 are NAC circuits Z13 – Z16, respectively

Note: NAC circuits Z13 – Z16 can also be programmed as IDC circuits.

PPCC005

PPCC004

PPCC003

PPCC002

PPCC001

PPCC012

PPCC011

PPCC010

ZA8–2 Class A Conventional Zone Card device addresses

The device address format is PPCCDDD, where:

PP is the panel number (01)

CC is the card number (any number between

1 and 13 depending on the setting of SW1)

DDD is the circuit number, where:

• 001 – 003 and 005 – 007 are IDC circuits

Zone 1 – Zone 3 and Zone 5 – Zone 7, respectively

• 004 and 008 are NAC circuits Zone 4 and

Zone 8, respectively

Note: NAC circuits Zone 4 and Zone 8 can also be programmed as IDC circuits.

PPCC002

PPCC001

PPCC006

PPCC005

PPCC006

PPCC007

PPCC008

PPCC009

PPCC013

PPCC014

PPCC015

PPCC016

PPCC003

PPCC004

PPCC007

PPCC008

2.12

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

SL30 (–1) LED/Switch Card device addresses

The device address format is GGSS for switches and GGSSL for LEDs, where:

GG is the group number (01 for SL30, 02 for

SL30–1)

SS is the switch number

L is the LED number, where:

• 1 is the red Alarm LED

• 2 is the yellow Active LED

• 3 is the yellow Trouble LED

GG011, GG012

1

GG013

GG01

06-10 11-15 16-20 21-25 26-30

GG02

GG03

GG04

GG05

6 11 16 21 26

2 7 12 17 22 27

3 8 13 18 23 28

4 9 14 19 24 29

5 10 15 20 25 30

SL30

01-05 06-10 11-15 16-20 21-25 26-30

GG01

GG02

GG03

GG04

GG05

31 36 41 46 51 56

32 37 42 47 52 57

33 38 43 48 53 58

34 39 44 49 54 59

35 40 45 50 55 60

SL30–1

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.13

Installation

Terminal definitions

Table 2-1: PS6 Power Supply card terminal definitions

RELAY 1 RELAY 2 RELAY 3 RELAY 4

NO C NC C NO C NO C NO N.C.

SMOKE

ACC PWR

+ –

RS485

+ –

RS232

RTS TX RX COM

TB1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Terminal No.

TB1–1, –2

TB1–2, –3

TB1–4, –5

TB1–6, –7

TB1–8, –9

TB1–10

TB1–11, –12

TB1–13, –14

BATT PWR

+ – NC

TB2

1 2 3

AUX POWER

AUX1 AUX2 COM AUX3 COM

TB3

1 2 3 4 5

Name Description

Relay 1 NO, C

Relay 1 C, NC

Relay 2 C, NO

Relay 3 C, NO

Relay 4 C, NO

Normally-open relay contacts that close automatically when the panel processes an alarm event. The contacts remain closed until all active alarm points restore and the panel resets.

Normally-closed relay contacts that open automatically when the panel processes an alarm event. The contacts remain open until all active alarm points restore and the panel resets.

Normally-open relay contacts that close automatically when the panel processes a supervisory event. The contacts remain closed until the active supervisory point restores.

Normally-open relay contacts that close automatically when the panel energizes. The contacts open when the panel processes a trouble event or when the panel loses power and remain open until the trouble condition restores.

Normally-open relay contacts that close depending on how the user programs the panel.

N.C.

Not used

SMK/ACC PWR +, – Provides regulated 24 Vdc for four-wire smoke detectors or accessory devices depending on jumper setting.

RS485 +, – Connects to the Channel 1 input on a remote annunciator

2.14

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Terminal No.

TB1–15

TB1–16

TB1–17

TB1–18

TB2–1

TB2–2

TB2–3

TB3–1

Name

RS232 RTS

RS232 RX

RS232 TX

RS232 COM

BATT PWR +

BATT PWR –

NC

AUX1

TB3–2

TB3–3

TB3–4

TB3–5

AUX2

COM

AUX3

COM

Installation

Description

Not used

Connects to the data transmit (TX) terminal on a peripheral device.

Connects to the receive data (RX) terminal on a peripheral device.

Connects to the common ground (COM) terminal on a peripheral device.

Connects to the positive terminal on the standby battery.

Connects to the negative terminal on the standby battery.

Not used.

Provides 24 Vdc, FWR power to auxiliary devices.

Note: AUX1, AUX2, and AUX3 can not be used to power remote annunciators

Provides 24 Vdc, FWR power to auxiliary devices.

Negative reference for AUX1 and AUX2 outputs.

Provides 24 Vdc, FWR power to auxiliary devices.

Negative reference for AUX3 output.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.15

Installation

Table 2-2: SLIC Signature Loop Intelligent Controller card

NAC 1 NAC 2

B+ B– A+ A– B+ B– A+ A–

TB1

1 2 3 4 5 6 7 8

Terminal No.

TB–1, –2

Name

NAC 1 B+, B–

TB–3, –4

TB–5, –6

NAC 1 A+, A–

NAC 2 B+, B–

TB–7, –8

TB2–1, –2

TB2–3, –4

TB2–5, –6

TB2–7, –8

NAC 2 A+, A–

OUT+, OUT–

IN+, IN–

LOOP A+, A–

LOOP B+, B–

+

OUT

– +

IN LOOP

– A+ A– B+ B–

TB2

1 2 3 4 5 6 7 8

Description

Connects to the IN +/– terminals of the first device on the

NAC circuit. Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.

Connects to the OUT +/– terminals of the last device on the

NAC circuit. Class A configuration only.

Connects to the IN +/– terminals of the first device on the

NAC circuit. Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.

Connects to the OUT +/– terminals of the last device on the

NAC circuit. Class A configuration only.

Connects to the next device on the same 24VDC riser used to provide 24 Vdc to NAC 1 and NAC 2.

Connects to the signal source used to provide 24 Vdc to

NAC 1 and NAC 2.

Connects to the DATA OUT +/– terminals of last device on the Signature signaling line circuit. Class A configuration only.

Connects to the DATA IN +/– terminals of the first device on the Signature signaling line circuit.

2.16

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

Table 2-3: ZA8–2 terminal definitions

ZONE 1

B+ B– A+ A–

ZONE 2

B+ B– A+ A–

ZONE 3

B+ B– A+ A–

ZONE 4

B+ B– A+ A–

NAC PWR

IN+ IN–

1 2 3 4 5 6

IDC

7 8 9 10 11 12 13 14 15 16 17 18

IDC/NAC

TB1

ZONE 5

B+ B– A+ A–

IDC

ZONE 6

B+ B– A+ A–

ZONE 7

B+ B– A+ A–

IDC/NAC

ZONE 8

B+ B– A+ A–

NAC PWR

IN+ IN–

TB2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

IDC circuit connections

Terminal No.

Name Description

TB1–1, –2 ZONE 1 B+, B– Connects to the IN +/– terminals of the first device on the IDC.

TB1–3, –4 ZONE 1 A+, A– Connects to the OUT +/– terminals of the last device on the

IDC.

Note: ZONE 2, 3, 5, 6, and 7 connect the same as described for ZONE 1.

IDC/NAC circuit connections

Terminal No.

TB1–13, –14

TB1–15, –16

Name

ZONE 4 B+, B–

ZONE 4 A+, A–

Description

Connects to the IN +/– terminals of the first device on the NAC.

Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.

Connects to the OUT +/– terminals of the last device on the

NAC.

TB1–17, –18

TB2–13, –14

NAC PWR IN+, IN–

ZONE 8 B+, B–

Connects to the signal source used to provide 24VDC to ZONE

4.

Connects to the IN +/– terminals of the first device on the NAC.

Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.

TB2–15, –16 ZONE 8 A+, A– Connects to the OUT +/– terminals of the last device on the

NAC.

TB2–17, –18 NAC PWR IN+, IN– Connects to the signal source used to provide 24VDC to ZONE

8.

Note: ZONE 4 and ZONE 8 may be programmed as IDC circuits.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.17

Installation

Table 2-4: ZB16–4 Class B Zone card terminal definitions

+ Z1 – + Z2 – + Z3 – + Z4 – + Z5 – + Z6 – + Z7 – + Z8 – + Z9 –

1 2 3 4 5 6 7 8 9

IDC

10 11 12 13 14 15 16 17 18

TB1

IDC IDC/NAC

+ Z10 – + Z11 – + Z12 – + Z13 – + Z14 – + Z15 – + Z16 – + R1 – + R2 –

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

TB2

IDC circuit connections

Terminal No.

Name Description

TB1–1, –2 Z1+, Z1– Connects to the IN +/– terminals of the first device on the IDC.

Note: Z2–Z16 connect the same as described for Z1.

IDC/NAC circuit connections

Terminal No.

Name Description

TB2–7, –8 Z13+, Z13– Connects to the IN +/– terminals of the first device on the NAC.

Polarity markings (+/–) indicate output signal polarity with the circuit turned off. Polarity reverses with the circuit turned on.

TB2–9, –10

TB2–11, –12

TB2–13, –14

Z14+, Z14–

Z15+, Z15–

Z16+, Z16– same as above same as above same as above

TB1–15, –16

TB1–17, –18

R1+, R1–

R2+, R2–

Connects to the signal source used to provide 24VDC to Z13 and

Z14.

Connects to the signal source used to provide 24VDC to Z15 and

Z16.

Note: Z13, Z14, Z15, and Z16 may be programmed as IDC circuits.

2.18

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 2-5: ZR8 Relay card terminal definitions

+ R1 – + R2 – + R3 – + R4 –

1 2 3 4 5 6 7 8

TB1

Installation

Terminal No.

TB1–1, –2

TB1–3, –4

TB1–5, –6

TB1–7, –8

TB2–1, –2

TB2–3, –4

TB2–5, –6

TB2–7, –8

Name

R1+, R1–

R2+, R2–

R3+, R3–

R4+, R4–

R5+, R5–

R6+, R6–

R7+, R7–

R8+, R8–

+ R5 – + R6 – + R7 – + R8 –

1 2 3 4 5 6 7 8

TB2

Description

Terminal connections for relay 1.

Terminal connections for relay 2.

Terminal connections for relay 3.

Terminal connections for relay 4.

Terminal connections for relay 5.

Terminal connections for relay 6.

Terminal connections for relay 7.

Terminal connections for relay 8.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.19

Installation

Table 2-6: RS485 (NT–A) Class A card terminal definitions

RS485

+ CH2 – + CH1 –

TB1

1 2 3 4

Terminal No.

TB1–1, –2

TB1–3, –4

Name

CH2+, CH2–

CH1+, CH1–

Description

Connects to CH2+/– on the first remote annunciator on the Class

A RS485 riser.

Connects to CH1+/– on the first remote annunciator on the Class

A RS485 riser.

2.20

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 2-7: DLD Dual Line Dialer card terminal definitions

LINE 1 LINE 2

IN OUT IN OUT

TIP RING TIP RING TIP RING TIP RING

TB1

1 2 3 4 5 6 7 8

Installation

Terminal No.

TB1–1

TB1–2

TB1–3

TB1–4

TB1–5

TB1–6

TB1–7

TB1–8

Name Description

LINE 1 TIP IN

LINE 1 RING IN

LINE 1 TIP OUT

Connects to the Tip In connector on the telco side of an RJ31X block via an RJ–12 modular cable.

Connects to the Ring In connector on the telco side of an

RJ31X block via an RJ–12 modular cable.

Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ–12 modular cable.

LINE 1 RING OUT Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ–12 modular cable.

LINE 2 TIP IN Connects to the Tip In connector on the telco side of an RJ31X block via an RJ–12 modular cable.

LINE 2 RING IN Connects to the Ring In connector on the telco side of an

RJ31X block via an RJ–12 modular cable.

LINE 2 TIP OUT Connects to the Tip Out connector on the protected premises side of an RJ31X block via an RJ–12 modular cable.

LINE 2 RING OUT Connects to the Ring Out connector on the protected premises of an RJ31X block via an RJ–12 modular cable.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

2.21

Installation

Connecting a PT–1S printer

For control panels with only a printer

1. Locate the printer in the same room as and within 20 ft of the panel (printer wiring is nonsupervised and power-limited).

2. Wire the printer cable to the RS232 connections on the power supply card then plug the cable into the printer.

3. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details.

For control panels with a printer and a CDR–

3 Bell Coder module

1. Install the IOP3A in the same enclosure as the CDR–3. Refer to appendix B.

2. Wire the IOP3A to the CDR–3.

3. Wire the printer cable to the RS232 connections on the IOP3A then plug the cable into the printer.

4. Configure the IOP3A as follows:

JP1 = 2–3

JP2 = ON

JP3 = ON

JP4 = ON

SW1 = UP

5. Set the printer switches for 9600 bps, 8 bits, no parity. Refer to the documentation included with the printer for more details.

PS6 TB1–18

PS6 TB1–17

PS6 TB1–16

CDR–3 TB2–4

CDR–3 TB2–5

CDR–3 TB2–6

CDR–3 TB2–7

PS6 TB1–17

COM–COM

TX–RX

RX–TX

DB–25P

REAR VIEW

3

2

7

TO

PT–1S

TB1

1

2

3

4

5

6

DB–25P

REAR VIEW

TO

PT–1S

7 3 2

IOP3A

COM–COM

RxD–TxD

TxD–RxD

TB3

1

2

3

4

TB2

2.22

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Installation

Installing standby batteries

For batteries rated at 10 Ah or less

1. Place the batteries in the bottom of the control panel.

2. Wire the batteries to the

PS6.

Notes

Do not run wires through the bottom knock-outs when batteries are installed in the control panel.

Battery wiring is supervised and nonpower-limited.

Maintain a 1/4-inch separation between powerlimited and nonpower-limited wiring at all times.

For batteries rated greater than 10 Ah

1. Place the batteries in a

BC-1 Battery Cabinet. The cabinet must be mounted within 3 ft of the control panel, in the same room, and connected with conduit.

2. Wire the batteries to the

PS6.

Note: Install, maintain, and test standby batteries in accordance with NFPA 72.

BC-1

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

+ –

+ –

+ + – –

2.23

Installation

Connecting a service computer

Connection of a service computer to the control panel requires programming cable P/N 260097, ordered separately.

Connection of a service computer to a remote annunciator requires programming cable P/N 360136 and a

RJ–11 to DB9 adapter P/N 240507, both ordered separately.

DB-9F

REAR VIEW

RTS

RX

PS6

TX

COM

NOT USED

1

P/N 260097

9

2.24

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 3

Operating instructions

Summary

This chapter provides instructions for operating the control panel.

Content

Instructions for the Level 1 operator (public mode access) • 3.2

Instructions for the Level 2 operator (emergency mode access) • 3.5

Instructions for the Level 3 operator (maintenance mode access) • 3.7

Instructions for the Level 4 operator (service mode access) • 3.10

QuickReference list • 3.11

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.1

Operating instructions

Instructions for the Level 1 operator (public mode access)

Tasks that do not require you to log in

What is it you want to do This is how you do it

Silence the panel trouble buzzer Press Panel Silence.

Get a list of all the active points on a panel

1. Press Status.

2. Choose All Active to get a list of all the active points.

Choose Alarm to get a list of only the active alarm points.

Choose Supervisory to get a list of only the active supervisory points.

Choose Monitor to get a list of only the active monitor points.

3. Press DEL to backspace the cursor then enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Identify points that are in trouble 1. Press Status.

2. Choose Trouble

3. Press DEL to backspace the cursor then enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Identify active points in a Service

Group that is being tested

1. Press Status.

2. Choose Test.

3. Press DEL to backspace the cursor then enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

3.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Operating instructions

Tasks that do not require you to log in

What is it you want to do This is how you do it

Identify points that are disabled 1. Press Status.

2. Choose Disabled Pts.

3. Press DEL to backspace the cursor then enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Identify output devices that are turned on

1. Press Status.

2. Choose Outputs

3. Press DEL to backspace the cursor then enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Verify power supply voltage levels 1. Press Status.

2. Choose Internal

3. Press Enter.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%)

1. Press Menu.

2. Choose Reports > Maintenance > Dirty>80%.

3 Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.3

Operating instructions

Tasks that do not require you to log in

What is it you want to do This is how you do it

Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%)

1. Press Menu.

2. Choose Reports > Maintenance > Dirty>20%.

3 Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Get the attributes for a single smoke detector

1. Press Menu.

2. Choose Reports > Maintenance > Single Device.

3. Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Get the attributes for every smoke detector on a single SLIC

Perform a lamp test

1. Press Menu.

2. Choose Reports > Maintenance > Card Devices.

3 Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

1. Press Menu.

2. Choose Test > Lamp Test.

3.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Operating instructions

Instructions for the Level 2 operator (emergency mode access)

Tasks that require you to log on as a Level 2 operator

What is it you want to do This is how you do it

Log onto the panel as a Level 2 operator

Turn the Enable Controls key 1/4 of a turn clockwise.

— or —

1. Press Menu.

2. Choose Login then enter the password required for Level 2 access.

Reset the panel Press System Reset.

Turn off alarm signaling circuits when the panel is in alarm (Alarm

Silence)

Press Alarm Silence.

Turn on alarm signaling circuits when the panel is not in alarm (Drill)

Press Drill then Enter.

Get a list of all events processed on a panel

1. Press Menu.

2. Choose Reports > History.

3. Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Change the password required for

Level 1 access

1. Press Menu.

2. Choose Program > Edit Password > Level 1.

3. Enter the new password.

Switch automatic detectors to their alternate sensitivity settings

1. Press Menu.

2. Choose Activate > Alt Sens.

Switch automatic detectors to their primary sensitivity settings

1. Press Menu.

2. Choose Restore > Prm Sens.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.5

Operating instructions

Tasks that require you to log on as a Level 2 operator

What is it you want to do This is how you do it

Distribute event records according to their alternate message routing

1. Press Menu.

2. Choose Activate > Alt Msg Route.

Distribute event records according to their primary message routing

1. Press Menu.

2. Choose Restore > Prm Msg Route.

Disable a Zone

Enable a Zone

1. Press Menu.

2. Choose Disable > Zone.

3. Select a Zone from the pick list then press Enter.

1. Press Menu.

2. Choose Enable > Zone.

3. Select a Zone from the pick list then press Enter.

Disable a device

Enable a device

1. Press Menu.

2. Choose Disable > Device.

3. Enter the device address, where:

PP is the panel number (01)

CC is the card number

DDD is the circuit or device number

1. Press Menu.

2. Choose Enable > Device.

3. Enter the device address, where:

PP is the panel number (01)

CC is the card number

DDD is the circuit or device number

3.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Operating instructions

Instructions for the Level 3 operator (maintenance mode access)

Tasks that require you to log on as a Level 3 operator

What is it you want to do This is how you do it

Log onto the panel as a Level 3 operator

1. Press Menu.

2. Choose Login then enter the password required for Level 3 access.

Change the password required for

Level 2 access

1. From the Main Menu, select Program.

2. Select Edit Password.

3. Select Level 2 then enter the new password.

Get a list of all the hardware and software components installed on a panel and their revision levels

1. Press Menu.

2. Choose Reports > Revision.

3. Enter the panel number.

4. Choose Display to view the list on the CPU/Display unit.

— or —

Choose Printer to print the list.

Set the system time and date 1. Press Menu.

2. Choose Program > Time/Date.

3. Choose Enter Time, then press DEL until the display shows

HHMMSS.

Enter the time in 24–hour format where HH is the hour, MM is the minutes, and SS is the seconds.

Example: To set the time for 1:00 p.m., enter 130000.

4. Select Enter Date.

Enter the date where MM is the number of the month, DD is the date, and YYYY is the year.

Example: To set the date for January 1, 2001, enter

01012001.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.7

Operating instructions

Tasks that require you to log on as a Level 3 operator

What is it you want to do This is how you do it

Turn on an output circuit

Note: A typical system may assign manual override functions a high priority level, alert responses a low priority, and alarm responses a medium priority.

1. Press Menu.

2. Choose Activate > Output.

3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number.

4. Choose Steady to change the circuit's output to always on

Choose 20 BPM to change the circuit's output to a 20 beat per minute signal rate (On = 2–1/2 s; Off = 2–1/2 s).

Choose 120 BPM to change the circuit's output to a 120 beat per minute signal rate (On = 1/4 s; Off = 1/4 s).

Choose Temporal to change the circuit's output to a 3–3–3 pattern.

5. Choose High Priority.

Turn off an output circuit

Turn an LED on

1. Press Menu.

2. Choose Restore > Output.

3. Enter the output circuit's address, where PP is the panel number, CC is the card number, and DDD is the circuit number.

4. Choose Off.

1. Press Menu.

2. Choose Activate > LED.

3. Choose one of the following:

Steady to turn the LED on

Fast Blink to have the LED flash at a fast rate

Slow Blink to have the LED flash at a slow rate

4. Enter the LED's address where GG is the group number,

SS is the switch number, and L is the LED number.

Turn an LED off 1. Press Menu.

2. Choose Restore > LED.

3. Choose Off

4. Enter the LED's address where GG is the group number,

SS is the switch number, and L is the LED number.

3.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Operating instructions

Tasks that require you to log on as a Level 3 operator

What is it you want to do This is how you do it

Disable or enable an And Group,

Matrix Group, or Time Control

1. Press Menu.

2. Choose Disable or Enable.

3. Choose And if an And group, Matrix if a Matrix group, or

Time Control if a time control.

4. Pick a group from the appropriate list and press Enter.

Disable or enable a switch on a zone display

1. Press Menu.

2. Choose Disable > Switch.

— or —

Enable > Switch.

3. Enter the switch address, where GG is the group number, and SS is the switch number.

Disable or enable the mapping function on an SLIC

1. Press Menu.

2. Choose Disable > Loop Mapping.

— or —

Enable > Loop Mapping.

3. Enter the card address for the SLIC.

Start a Service Group test 1. Press Menu.

2. Choose Test > Start Test.

3. Select a Service group from the pick list and press Enter.

Cancel a Service Group test

Note: The panel automatically resets after you cancel a test.

1. Press Menu.

2. Choose Test > Cancel Test.

2. Select a Service group from the pick list and press Enter.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.9

Operating instructions

Instructions for the Level 4 operator (service mode access)

What is it you want to do

Log onto the panel as a Level 4 operator

This is how you do it

1. Press Menu.

2. Choose Login then enter the password required for Level 4 access.

Change the password required for

Level 3 access

1. Press Menu.

2. Choose Program > Edit Password > Edit Password

3. Choose Level 3 then enter the new password.

Change the password required for

Level 4 access

1. Press Menu.

2. Choose Program > Edit Password > Edit Password

3. Choose Level 4 then enter the new password.

Restart a panel 1. Press Menu.

2. Choose Program > Restart > Panel

3. Enter the panel's address.

Reset the alarm history counter 1. From the Main Menu, select Program.

2. Select Reset.

3. Enter the panel's address.

3.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Operating instructions

QuickReference list

What is it you want to do

Change smoke detector sensitivity settings to their alternate values

Change smoke detector sensitivity settings to their primary values

Change the current state of an LED (manual override)

Change the current state of an output circuit (manual override)

Change the password required for Level 1 access

Change the password required for Level 2 access

Change the password required for Level 3 access

Change the password required for Level 4 access

Disable or enable a device

Disable or enable a switch on a zone display

Disable or enable a zone

Disable or enable all the devices on a single card

Disable or enable an And Group, Matrix Group, or Time Control

Disable or enable the mapping function on an SLIC

Get a list of all the active points on a panel

Get a list of all the hardware and software components installed on a panel and their revision levels

Get a list of smoke detectors that may require servicing (DIRTY attribute greater than 20%)

Get a list of smoke detectors that require servicing (DIRTY attribute greater than 80%)

Get the attributes for a single smoke detector

Get the attributes for all the smoke detectors on a single SLIC

Identify output devices that are turned on

Identify active points in a Service Group that is being tested

Identify points that are disabled

Identify points that are in their active state

Identify points that are in trouble

Log onto the panel as a Level 2 operator

Log onto the panel as a Level 3 operator

Log onto the panel as a Level 4 operator

Perform a lamp test

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

L1

Required access level

ü

ü

ü

L2

ü

ü

ü

ü

ü

ü

L3

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

L4

ü ü ü ü

ü ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

3.11

Operating instructions

What is it you want to do

Reset the alarm history counter

Reset the panel

Restart the panel

Restore an LED to its previous state

Restore an output circuit to its previous state

Route off-normal signals to the alternate set of panels used to post messages

Route off-normal signals to the primary set of panels used to post messages

Set the system time and date

Silence the panel trouble buzzer

Start a Service Group test

Cancel a Service Group test

Turn off alarm signaling circuits when the panel is in alarm (Alarm

Silence)

Turn on alarm signaling circuits when the panel is not in alarm (Drill)

Verify power supply voltage levels

ü

ü

L1

Required access level

L2 L3

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

L4

ü ü ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

ü

3.12

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 4

Programming instructions

Summary

This chapter provides instructions for programming the fire alarm system from the front panel. Worksheets are provided at the end of the chapter to use as programming aids and to document the system programming.

Content

Overview • 4.2

QuickStart setup instructions • 4.4

Customizing the system configuration • 4.13

Setting up an Output Group • 4.21

Setting up a Zone • 4.24

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.1

Programming instructions

Overview

What is a Zone?

A Zone is a function in the system software that initiates an active response based on a single alarm event. Firewall designations, planned evacuation criteria, architectural design, and other factors all contribute to how the system designer divides the protected premises into zones.

ZONE 1

FACP

ZONE 2 ZONE 3

J

What is an Output Group?

An Output Group is a function in the system software that establishes the correlation between input circuits and responses. When an input changes states, the condition of the input determines which response the panel runs. For example, a smoke detector initiates the Active response when it signals an alarm condition but initiates the Trouble response when removed from its base.

ZONE 1

Output 1

Active

Trouble

Output 2

Active

Trouble

4.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 4-1: Programmable features

Feature

And Groups

Output Groups

Matrix Groups

Service Groups

Time Controls

Zones

LED Configure

Switch Configure

SIGA - Prealarm

SIGA - Sensitivity levels

Alarm Verification

Coded Operation

Custom Messages

Message Routing

SIGA - Diagnostics

AC Delay

Two-stage Operation

General Alarm Inhibit

Market Place

Card Configuration

Language

Zone Resound Inhibit

Drill Programming

Alarm Silence Programming

Waterflow Silence

Supervisory Duct

Enable Trouble Reminder

Auto Alarm Signal Silence

Alarm Signal Silence/Reset Inhibit

Panel Silence Resound Time

SIGA–REL

Front Panel Programming

(FPP)

No

Yes

No

Limited

No

Yes

Limited

Limited

Yes

Yes

Yes

Yes

Yes (requires bar code wand)

No

No

No

No

No

No

No

Yes

No

No

No

Yes

No

No

No

No

No

No

Programming instructions

Configuration Utility

(CU)

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.3

Programming instructions

QuickStart setup instructions

Step 1:

Read this before proceeding

Note: If at any time you get an

Exception Event while programming the system, note the error code, and then contact EST Technical Services at 6411 Parkland Drive, Sarasota, FL

34243 or at 1-800-655-4497.

To clear the Exception Event, press

Alarm Silence while the event is displayed. You may have to reset the panel to display the event again.

This procedure uses the AutoLearn and AutoLoop utilities to automatically configure the system. The AutoLearn utility configures the option cards. The AutoLoop utility configures the circuits on the Signature loop.

Caution: Running the AutoLearn utility deletes the existing panel programming. If you have already programmed the system, running AutoLearn requires you to re-enter everything again from the beginning.

If you have a dialer installed, the AutoLearn utility requires you to program the DLD before exiting. Be sure to have the following:

• Subscriber account numbers, telephone numbers, and transmission formats obtained from the CMS (Central

Monitoring Station). Appendic C provides a list of Contact ID event codes.

• A completed copy of the DLD Programming Worksheet

(Figure 4-1).

After you have finished using the AutoLearn and AutoLoop utilities to configure the system, you can either:

• Customize the system programming

• Go to step 11 and Save and Sync.

Step 2:

Apply power to the system

1. Verify that each circuit card installed in the control panel has a unique card address.

2. Apply power to the control panel and to all the remote annunciators.

After applying power, the panel CPU performs a diagnostic check in the background. You can not begin programming until this finishes and the AutoLearn option becomes available.

4.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Step 3:

Assign Panel ID numbers to the remote annunciator panels

On each remote annunciator panel:

1. Press Menu.

2. Choose Login then enter the password required for Level 4 access (default is 4444).

3. Choose Program > Configure > AutoLearn.

4. Press Del twice then enter an unused Panel ID from 02 to

09 (01 is reserved for the control panel).

5. Enter the number of panels that are connected to the

RS485 riser, including the control panel. This is your maximum number of panel addresses.

6. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter.

Note: The wiring configuration must be the same for all panels.

Step 4:

AutoLearn the control panel.

Note: Before running the AutoLearn utility, make sure you have not installed more cards than the system allows.

On the control panel:

1. Press Menu.

2. Choose Login then enter the password required for Level 4 access (default is 4444).

3. Choose Reports > Revision > Enter > Display. Verify all the cards installed in the cabinet appear in the list.

4. Press Menu then choose Program > Configure >

AutoLearn.

5. Enter 01 for the Panel ID.

6. Enter the number of panels that are connected to the

RS485 riser, including the control panel. This is your maximum number of panel addresses.

7. Select the wiring configuration of the RS485 riser (Class A or Class B) then press Enter.

If you do not have a DLD card installed, the system will automatically reboot after the AutoLearn utility configures the system. Go to step 10.

If you do have a DLD card installed, go to step 5.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.5

Programming instructions

Step 5:

Set up the receiver call-in numbers and retry attempts

Step 6:

Set up the subscriber accounts

1. Choose #'s of CMS then choose the number of CMS receivers that the DLD may dial into over the public switched telephone network.

2. Choose CMS Phone # then enter the telephone numbers of the CMS receivers:

§ Choose Rcvr 1 Prim # then enter the first number to try for the first CMS receiver.

§ Choose Rcvr 1 Sec # then enter the second number to try for the first CMS receiver.

§ Choose Rcvr 2 Prim # then enter the first number to try for the second CMS receiver.

§ Choose Rcvr 2 Sec # then enter the second number to try for the second CMS receiver.

§ Choose Exit.

3. Choose Retry Count then enter the number of times you want the dialer to attempt to contact the CMS receiver.

1. Choose Accounts then <New> to set up a new account

— or —

Select an account number then press Enter.

2. Choose Account # then enter the number of the subscriber account.

3. Choose Formats then choose the required transmission format.

4. Choose Test–Normal then enter the character string to send when the control panel is normal.

5. Choose Test–Abnormal then enter the character string to send when the control panel is off-normal.

6. Choose Test Time then enter when you want the dialer to transmit the test string in 24-hour format.

7. Choose CMS then choose which CMS receiver to dial.

This is the receiver that holds the account.

8. Choose Exit.

4.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Step 7:

Edit the default alarm messages

Note: The dialer automatically sends the default alarm message for active alarm inputs that are not programmed to initiate a dialer response.

1. Choose Default Msgs > Alarm.

2. Choose Account then select the subscriber account you want to receive the message.

3. Choose Active Msg then enter the message you want sent for alarm activation events.

For example, for Contact ID enter 111000000

4. Choose Restore Msg then enter the message you want sent for alarm restoration event.

For example, for Contact ID enter 311000000

5. Choose Exit.

Step 8:

Edit the default trouble messages

Note: The dialer automatically sends the default trouble message for inputs that signal a trouble but are not programmed to initiate a dialer response.

1. Choose Default Msgs > Trouble.

2. Choose Account then select the subscriber account you want to receive the message.

3. Choose Active Msg then enter the message you want sent for trouble activation events.

For example, for Contact ID enter 130000000

4. Choose Restore Msg then enter the message you want sent for trouble restoration event.

For example, for Contact ID enter 330000000

5. Choose Exit.

Step 9:

Edit the default supervisory messages

Note: The dialer automatically sends the default supervisory message for active supervisory inputs that are not programmed to initiate a dialer response.

1. Choose Default Msgs > Supervisory.

2. Choose Account then select the subscriber account you want to receive the message.

3. Choose Active Msg then enter the message you want sent for supervisory activation events.

For example, for Contact ID enter 120000000

4. Choose Restore Msg then enter the message you want sent for a supervisory restoration event.

For example, for Contact ID enter 220000000

5. Choose Exit.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.7

Programming instructions

Step 10:

AutoLoop the loop controller cards

Run the AutoLoop utility on each loop controller installed in the control panel.

Caution: When the system reboots, the loop controller reinitializes the loop. If you attempt to run the AutoLoop utility during this time, you could corrupt the project database.

1. On the control panel, press Menu.

2. Choose Login then enter the password required for Level 4 access.

3. Choose Program > Configure.

If the loop is still initializing, do not proceed until loop initialization has finished.

4. Choose Cards > Edit, then enter the card number for the loop controller.

5. On the Edit Cards menu, choose AutoLoop.

6. If the number of detector and module addresses on the display match the number installed on the loop, press

Enter to accept, then wait while the database is updated.

If not, press Del to cancel. You must correct the problem before continuing with this loop.

7. On the SLIC menu, choose Exit.

8. For each additional loop controller, repeat steps 4–7.

9. Choose Exit.

Step 11:

Saving the project database

Tip: Only Save and Sync after you have finished programming the control panel and you want to update the project databases in the remote annunciators.

At this point, you have configured the project database for a general alarm system. Refer to Table 4-2, Table 4-3 and

Table 4-4 for initial system settings.

If you want to accept the general alarm system configuration, choose Save and Sync.

If you want to make changes to the system configuration, choose Save, and then make your changes. See Customizing

the system configuration. After making all of your changes:

1. Press Menu.

2. Choose Login then enter the password required for Level 4 access.

3. Choose Program > Configure > Exit.

4. Choose Save and Sync.

Note: If the local AHJ requires a hard copy of your site programming, use the QuickStart Configuration Utility to retrieve the database from the panel and print the required information.

4.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Table 4-2: AutoLearn initial project settings

Option Value Description

Alarm Silence

Drill

Drill Activation Type

Alarm Signal

Silence/Reset Inhibit

Buzzer Reminder Time

AC Power Trouble

Delay

Two-stage Timer

Zone Resound Inhibit

Primary Routing

Alternate Routing

Language

Relay 1 Type

Relay 2 Type

Relay 3 Type

Relay 4 Type

Audible only

Audible only

Steady

None

Indefinitely

6 h

0 s (UL)

300 s (ULC)

No

All Cabinets

All Cabinets

English (U.S.)

Alarm

Supervisory

Trouble

Monitor

Turns off Audible and Common Alarm Output circuits when someone presses Alarm Silence.

Turns off Audible and Common Alarm Output circuits when someone presses Drill.

The Drill signal is a constant signal.

Alarm Silence or Reset functions are not inhibited. You can turn off (silence) notification circuits or reset the panel any time after notification circuits are activated.

The panel trouble buzzer remains silenced until the control panel processes a new off-normal signal.

The panel will operate on battery power for 6 hours before signaling a trouble condition.

The panel will turn on notification circuits immediately after processing an alarm signal (UL) or after 5 minutes

(ULC).

Turn silenced NAC circuits back on if an active alarm input circuit remains in the active condition after resetting the panel.

Distribute event records to all panels in the system when primary routing is activated.

Distribute event records to all panels in the system when alternate routing is activated.

U.S. English displayed on CPU/Display.

Alarm events cause the contact positions of Relay 1 on the PS6 to change positions.

Supervisory events cause the contact positions of Relay

2 on the PS6 to change positions.

Trouble events cause the contact positions of Relay 3 on the PS6 to change positions.

Monitor events cause the contact positions of Relay 4 on the PS6 to change positions.

Edit?

CU

CU

CU

FPP/CU

No

FPP/CU

CU

No

CU

CU

No

No

No

No

CU

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.9

Programming instructions

Table 4-3: AutoLearn initial card configuration settings

Card Circuit Address Device type Edit?

SLIC NAC 1

NAC 2

270

271

Visible

Common Alarm

Output

FPP/CU

FPP/CU

NAC 1

Diagram

NAC 2

Card Circuit

ZB16–4 Z1

Z2

Z3

Z4

Z5

Z6

Z7

Z8

Z9

Z10

Z11

Z12

Z13

Address

008

009

010

011

012

013

001

002

003

004

005

006

007

Z14 014

Z15

Z16

015

016

Device type

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Alarm

Common Alarm

Output

Common Alarm

Output

Visible

Visible

Edit?

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

Z12

Z11

Z10

Z4

Z3

Z2

Z1

Diagram

Z13

Z14

Z15

Z16

Z5

Z6

Z7

Z8

Z9

4.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Table 4-3: AutoLearn initial card configuration settings (cont.)

Card Circuit Address Setting Edit?

ZA8–2 Zone 1

Zone 2

Zone 3

Zone 4

001

002

003

004

Zone 5

Zone 6

Zone 7

Zone 8

005

006

007

008

Alarm

Alarm

Alarm

Common Alarm

Output

Alarm

Alarm

Alarm

Visible

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

Zone 1

Zone 2

Zone 3

Zone 4

Zone 8

Zone 7

Zone 6

Zone 5

Diagram

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.11

Programming instructions

Table 4-4: AutoLoop initial settings for SIGA devices

SIGA Device Personality Description

SIGA–IPHS, –PHS,

–PS, –IS none none

Smoke detector settings as follows:

Sensitivity: Least

Verification: None

Prealarm: None

Heat detector settings not programmable SIGA–HFS, HRS,

–IM

Single-stage pull stations

Dual-stage pull stations

01

01

Class B Alarm Latching

Class B Alarm Latching

SIGA–APS

SIGA–(M)CC1(S)

01

03

03

05

Class B Alarm Latching

Class B Active Non-Latching

Class B Active Non-Latching

Riser selector

Device Type

Alarm

Alarm

Pull

SIGA–(M)CC2

SIGA–(M)CR(R)

SIGA–(M)CT1

SIGA–(M)CT2

SIGA–DTS

SIGA–IO

SIGA–MAB

SIGA–UM

SIGA–MM1

SIGA–WTM

SIGA–(M)RM1

07

08

01

01

01

01

31

00

00

00

00

03

02

04

23

Dual riser selector

Dry contact

Class B Alarm Latching

Class B Alarm Latching

Class B Alarm Latching

Class B Alarm Latching

Monitor Input/Output N.O.

Class A Signal Output not used

Class A Signal Output not used

Class B Active Non-Latching

Class B Active Latching - Delayed

Class B Active Latching.

Riser monitor - 24 Vdc

Monitor

Pull

Monitor

Monitor

Common Alarm

Output

Common Alarm

Output

Nonsupervised

Output

Alarm

Alarm

Alarm

Alarm

Monitor

Monitor

Monitor

Monitor

Alarm

Supervisory

Monitor

Edit?

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

FPP/CU

Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from the previous system as the initial settings for a general alarm system.

4.12

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Customizing the system configuration

You can customize the system configuration, if your requirements exceed that of the general alarm system created using the AutoLearn and

AutoLoop utilities.

Before you can make any changes to the system programming, you must log onto the system to start an editing session.

The control panel has a watchdog timer that kicks you out of an editing session after a period of inactivity. If this happens, you will have to log in again to continue.

After you finish customizing the system configuration, save your changes, and then test the system. After everything checks out then Save and Sync to copy the database to the remote annunciators.

WARNING: Entering Edit mode (choosing

Configure on the Program menu) disables the control panel and leaves the premises unprotected until you exit Edit mode.

To start an editing session:

1. Press Menu.

2. Choose Login then enter the password required for Level 4 access.

3. Choose Program > Configure.

What is it you want to do

Make information about the installer available on the CPU/Display

AutoLearn default: No text

This is how you do it

1. On the Configure menu, choose System > User

Labels.

2. Choose Facility Name, scan in the name of the project, and then press Enter.

3. Choose Inst Company, scan in the name of the installing company, and then press Enter.

4. Choose Phone Number, scan in the telephone number to call for service-related issues, and then press Enter.

5. Choose Programmer, scan in the name of the person that programmed the system, and then press Enter.

6. Choose Exit.

Set how long notification circuits must stay on before pressing Alarm Silence can turn them off or pressing Reset can reset the panel

AutoLearn default: None (no delay)

1. On the Configure menu, choose System >

ALM/RST Inhib.

2. Select a time delay from the pick list then press

Enter.

Set how long the panel must wait before signaling an ac power failure

AutoLearn default: 0 (no delay)

1. On the Configure menu, choose System > AC

Power Dly.

2. Select a time delay from the pick list then press

Enter.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.13

Programming instructions

What is it you want to do

Enter location message text for a circuit on a

ZB16–4 or ZA8–2 card

This is how you do it

1. On the Configure menu, choose Card, and then enter the card address number.

2. Choose Text Message, scan in the text, and then press Enter.

3. Choose Exit.

Change the device type of a circuit on a ZB16–

4 or ZA8–2 card

WARNING: Changing the device type of an input circuit to a device type for an output circuit removes the circuit from all input logic groups.

Changing the device type of an output circuit to a device type for an input circuit removes the output circuit from all output groups.

1. On the Configure menu, choose Card, and then enter the card address number.

2. Choose Device Type, select the device type from the pick list, and then press Enter.

3. Choose Exit.

Change the device type of the NAC circuits on the SLIC

AutoLearn defaults: NAC1 device type is Visible;

NAC 2 device type is Common Alarm Output

Common Alarm Output circuits turn on automatically when an input signals an alarm event. Visible and Audible output circuits must be placed in an Output Group in order to turn them on. The AutoLearn utility automatically places

Visible circuits in an Output Group

WARNING: Changing an output circuit from a

Common Alarm Output device type to an Audible device type does not automatically place the

Audible circuit in an Output Group. You must add the Audible Circuit to the Output Group manually or the Audible circuit will not turn on.

1. On the Configure menu, choose Cards > Edit then enter the card address number.

2. Choose Config Card.

3. Choose NAC 1 then choose the device type for

NAC 1.

4. Choose NAC 2 then choose the device type for

NAC 2.

5. Choose Exit > Save Edits, then wait while the database is updated.

4.14

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

What is it you want to do

Change the performance class of the Signature loop wiring

AutoLearn default: Wiring is Class B.

This is how you do it

1. On the Configure menu, choose Cards > Edit then enter the card address number.

2. Choose Config Card.

3. Choose Wiring Class then choose how the loop is wired to the SLIC.

4. Choose Exit > Save Edits, then wait while the database is updated.

Enter location message text for an automatic detector

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.

3. Choose Message then scan in the text that you want sent when the detector signals an event.

4. Choose Exit > Save Edits.

Change the Alarm Sensitivity setting of a smoke detector

WARNING: Selection of the appropriate detector technology and sensitivity settings should result from a careful analysis of the hazard, environmental conditions, and expected results.

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.

3. Choose Sensitivity then choose the alarm sensitivity setting you want the detector to use.

Refer to Table 4-5 and Table 4-6.

4. Choose Exit > Save Edits.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.15

Programming instructions

What is it you want to do

Change the Alarm Verification setting of a smoke detector

Change the Prealarm setting of a smoke detector

This is how you do it

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the detector's serial number.

3. Choose Verification then choose the length of the alarm verification period.

4. Choose Exit > Save Edits.

WARNING: Prealarm obscuration levels below

80% should not be used without full knowledge of the possible consequences.

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Detect > Edit > Enter Serial # and then scan or enter the serial number of the detector.

3. Choose Pre-Alarm then choose the warning threshold setting you want the detector to use.

Refer to Table 4-5 and Table 4-6.

4. Choose Exit > Save Edits.

4.16

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Table 4-5: %Obscuration levels for SIGA–IPHS, SIGA–PS, and SIGA–PHS

Alarm Obscuration Levels

Sensitivity Settings

%Obscuration

Prealarm Settings

95%

90%

85%

80%

Most

1.00%

75%

70%

65%

60%

55%

50%

45%

40%

35%

30%

25%

20%

15%

10%

5%

0.20%

0.15%

0.10

0.05

Note: Shaded prealarm settings not available for SIGA–IPHS

0.55%

0.50%

0.45%

0.40%

0.35%

0.30%

0.25%

0.95%

0.90%

0.85%

0.80%

0.75%

0.70%

0.65%

0.60%

0.80%

0.70%

0.60%

0.50%

0.40%

0.30%

0.20%

0.10%

1.50%

1.40%

1.30%

1.20%

1.10%

1.00%

0.90%

More

2.00%

Normal

2.50%

Less

3.00%

Prealarm Obscuration Levels

1.90%

1.80%

1.70%

1.60%

2.38%

2.25%

2.13%

2.00%

2.85%

2.70%

2.55%

2.40%

1.88%

1.75%

1.63%

1.50%

1.38%

1.25%

1.13%

2.25%

2.10%

1.95%

1.80%

1.65%

1.50%

1.35%

1.00%

0.88%

0.75%

0.13%

0.50%

0.38%

0.25%

0.13%

1.20%

1.05%

0.90%

0.31%

0.60%

0.45%

0.30%

0.15%

Table 4-6: %Obscuration levels for SIGA–IS

Sensitivity Settings

%Obscuration

Prealarm Settings

95%

90%

85%

80%

75%

70%

65%

60%

55%

50%

Most

0.7%

0.67%

0.63%

0.60%

0.56%

0.53%

0.49%

0.46%

0.42%

0.39%

0.35%

More

Alarm Obscuration Levels

Normal Less

1.00% 1.20% 1.40%

Prealarm Obscuration Levels

0.95% 1.14% 1.33%

0.90%

0.85%

0.80%

0.75%

1.08%

1.02%

0.96%

0.90%

1.26%

1.19%

1.12%

1.05%

0.70%

0.65%

0.60%

0.55%

0.50%

0.84%

0.78%

0.72%

0.66%

0.60%

0.98%

0.91%

0.84%

0.77%

0.70%

Least

1.6%

1.52%

1.44%

1.36%

1.28%

1.20%

1.12%

1.04%

0.96%

0.88%

0.80%

Least

3.50%

1.93%

1.75%

1.58%

1.40%

1.23%

1.05%

0.88%

3.33%

3.15%

2.98%

2.80%

2.63%

2.45%

2.28%

2.10%

0.70%

0.53%

0.35%

0.18%

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.17

Programming instructions

What is it you want to do

Enter location message text for a circuit on a

SIGA module

This is how you do it

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.

3. For a single-address module or the first address of a dual-address module, choose

Device 1.

— or —

For the second address of a dual-address module, choose Device 2.

4. Choose Message, scan in the text, and then press Enter.

5. Choose Exit.

Change the device type for a circuit on a SIGA module

Note: The device types shown in the pick lists vary depending on the SIGA module. The device types shown in the pick lists for the second address of a dual-address module also vary depending on the device type chosen for the first address.

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.

3. For a single-address module or the first address of a dual-address module, choose

Device 1.

— or —

For the second address of a dual-address module, choose Device 2.

4. Choose Type, select a device type from the pick list, and then press Enter.

5. Choose Exit.

4.18

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

What is it you want to do

Change the personality code for a circuit on a

SIGA module

Note: The personality codes shown in the pick lists vary depending on the SIGA module and the chosen device type.

This is how you do it

1. On the Configure menu, choose Cards > Edit and then enter the card address number of the loop controller.

2. Choose Config Module > Edit > Enter Serial # and then scan or enter the serial number of the module.

3. For a single-address module or the first address of a dual-address module, choose

Device 1.

— or —

For the second address of a dual-address module, choose Device 2.

4. Choose Personality, select a personality code from the pick list, and then press Enter.

5. Choose Exit.

Enable the loop controller mapping function

AutoLearn default: Mapping disabled

1. Press Menu.

2. Log onto the panel as a Level 4 operator.

3. Choose Enable > Loop Mapping.

4. Enter the card number of the SLIC that connects to the device you want to replace.

Wait until mapping finishes before continuing.

5. Choose Cards > Edit.

6. Enter the card number of the SLIC that connects to the device you want to replace.

7. Choose Accept Map.

If actual and expected data for detectors and modules are the same, press Enter.

8. Choose Exit > Exit > Save.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.19

Programming instructions

Table 4-7: Device type descriptions

Alarm

Alarm Output

Audible

Heat

Monitor

Output

Pull

Supervisory

Tamper

Verified Smoke

Visible

Water Flow

Device type assigned to IDC circuits that connect to automatic or a combination of automatic and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events.

Device type assigned to IDC/NAC circuits that connect to notification appliances that you want turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn off when you press Alarm Silence and turn on when you press Drill.

Device type assigned to IDC/NAC circuits that connect to audible notification appliances

(horns). Audible circuits turn off when you press Alarm Silence and turn on when you press

Drill.

Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events.

Device type assigned to IDC circuits that connect to monitor-signal initiating devices that monitor the operation of ancillary system functions. Monitor circuits signal Monitor events.

Device type assigned to IDC/NAC circuits that supervise their output wiring for opens and shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press

Drill.

Device type assigned to IDC circuits that connect to manually operated alarm-signal initiating devices. Pull circuits signal Pull Station events.

Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect abnormal conditions that could make the sprinkler system inoperative or ineffective.

Supervisory circuits signal Supervisory events.

Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that detect when someone tampers with a component of the sprinkler system. Tamper circuits signal

Tamper events.

Device type assigned to IDC circuits that connect to automatic alarm-signal initiating devices that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire condition is first detected then Alarm Active events after verifying the fire condition exists.

Device type assigned to IDC/NAC circuits that connect to visual notification appliances

(strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you press Drill unless programmed to do so.

Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.

4.20

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Setting up an Output Group

Before you begin Before you begin, you should complete an Output Group

Programming Worksheet (Figure 4-8) for each Output group.

Keep a copy for your records.

To set up an Output Group:

1. On the control panel, press Menu.

2. Choose Login then enter the password required for Level 4 access.

3. Choose Program > Configure > Output.

4. To program a new Output group, choose Add.

— or —

To edit an existing Output group, choose Edit, select the group from the pick list, and then press Enter.

5. Add the responses.

6. After you finish entering the responses, you should review them to make sure they are correct.

Adding a response that activates an output circuit

1. Choose Responses.

2. Choose Active or Trouble

3. Choose Add > Relay, then enter the circuit address where

CC is the card number and DDD is the circuit number.

4. Choose the activation setting.

5. Choose Exit > Save Edits.

Adding a response that activates a delay

1. Choose Responses.

2. Choose Active or Trouble.

3. Choose Add > Delay.

4. Choose Delay Type, then choose when to initiate the delay response.

5. Choose Delay Time, press Del four times, and then enter how many seconds you want the delay to last.

6. Choose Exit > Save Edits.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.21

Programming instructions

Adding a response that sends a dialer string

Reviewing your responses

1. Choose Responses.

2. Choose Active or Trouble.

3. Choose Add > Dialer.

4. Select an account number from the pick list, and then press

Enter.

5. Choose Send On, select when to send the dialer string from the pick list, and then press Enter.

6. Choose Priority, select the priority classification from the pick list, and then press Enter.

7. Choose String, then enter the message you want sent.

8. Choose Exit > Save Edits.

1. Choose Review.

2. Choose Active to review the active responses.

— or —

Choose Trouble to review the trouble responses.

4.22

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Table 4-8: Response code definitions

Response Description

PppCccDddd 1234 This is what the panel display looks like when you review a response for an output circuit.

P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number)

1 is the command direction (B = Both activation and restoration, A = Activation only,

R = Restoration only)

2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =

Disable, D = Delay)

3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)

4 is the command attribute (S = Set, R = Reset, W = 20 bpm, F = 120 bpm, T =

Temporal)

PppCccDddd 1234

Delay: ssss 1

This is what the panel display looks like when you review a response for an LED.

P:pp C:cc D:ddd is the address of the of the output circuit (P = panel number, C = card number, D = device number)

1 is the command direction (B = Both activation and restoration, A = Activation only,

R = Restoration only)

2 is the command (N = no operation, A = Activate, E = Enable, R = Restore, I =

Disable, D = Delay)

3 is the priority attribute (S = Set, A = Latch, L = Low, M = Medium, H = High)

4 is the command attribute (S = Steady, R = Restore, W = Slow Blink, F = Fast

Blink)

This is what the panel display looks like when you review a response for delay.

ssss is the amount of delay in seconds

1 is the command direction (B = Both activation and restoration, A = Activation only,

R = Restoration only)

ACCT12QEEEGGPPP

— or —

ACCT12PP

This is what the panel display looks like when you review a response for dialer string.

ACCT is the 4-digit subscriber account number (0000–9999)

1 is the priority attribute (L = Life Safety, P = Property, S = System Integrity)

2 s the command direction (B = Both activation and restoration, A = Activation only,

R = Restoration only)

For Contact ID dialer strings:

Q is the event qualifier (1 = activation event, 3 = restoration event)

EEE is the event code. See Table 4-9.

GGPPP is the point being reported

For 4/2 dialer strings:

PP is the point being reported (00–99)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.23

Programming instructions

Table 4-9: Contact ID Event Codes

100 – Medical alarm

101 – Pendant transmitter

102 – Fail to report in

110– Fire Alarm

111 – Smoke

112 – Combustion

113 – Water Flow

114 – Heat

115 – Pull Station

116 – Duct

117 – Flame

118 – Near alarm

120 – Panic Alarm

121 – Duress

122 – Silent

123 – Audible

130 – Burglar Alarm

131 – Perimeter

132 – Interior

133 – 24 Hour

134 – Entry/Exit

135 – Day/Night

136 – Outdoor

137 – Tamper

138 – Near alarm

140 – General Alarm

141 – Polling loop open

142 – Polling loop short

143 – Expansion module failure

144 – Sensor tamper

145 – Expansion module failure

150 and 160 – 24-hour Non-

Burglary

151 – Gas detection

152 – Refrigeration

153 – Loss of heat

154 – Water leakage

155 – Foil break

156 – Day trouble

157 – Low bottled gas level

158 – High temperature

159 – Low temperature

161 – Loss of air flow

200 and 210 – Fire Supervisory

201 – Low water pressure

202 – Low CO

2

203 – Gate valve sensor

204 – Low water level

205 – Pump activated

206 – Pump failure

300 and 310 – System Troubles

301 – AC loss

302 – Low system battery

303 – RAM checksum bad

304 – ROM checksum bad

305 – System reset

306 – Panel program changed

307 – Self–test failure

308 – System shutdown

309 – Battery test failure

310 – Ground fault

320 – Sounder/Relay Trouble

321 – Bell 1

322 – Bell 2

323 – Alarm relay

324 – Trouble relay

325 – Reversing

330 and 340 – System Peripheral

Trouble

331 – Polling loop open

332 – Polling loop short

333 – Expansion module failure

334 – Repeater failure

335 – Local printer paper out

336 – Local printer failure

350 and 360 – Communication

Trouble

351 – Telco 1 fault

352 – Telco 2 fault

353 – Long range radio

354 – Fail to communicate

355 – Loss of radio supervision

356 – Loss of central polling

370 – Protection LoopTrouble

371 – Protection loop open

372 – Protection loop short

373 – Fire trouble

380 – Sensor Trouble

381 – Loss of supervisory (RF)

382 – Loss of supervisory (RPM)

383 – Sensor tamper

384 – RF transmitter low battery

400 – Open/Close

401 – Open/Close by user

402 – Group open/close

403 – Automatic open/close

404 – Late to open/close

405 – Deferred open/close

406 – Cancel

407 – Remote arm/disarm

408 – Quick arm

409 – Keyswitch open/close

410 – Remote Access

411 – Call request made

412 – Success – Download access

413 – Unsuccessful access

414 – System shutdown

415 – Dialer shutdown

4.24

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 4-9: Contact ID Event Codes (cont.)

420 – Access Control

421 – Access denied

600 – Test/Misc.

601 – Manual trigger test

422 – Access report by user

441 – Stay arming

451 – Early opening/closing

452 – Late opening/closing

453 – Late to open

454 – Late to close

455 – Auto–arm failure

500 and 510 – System Disable

602 – Periodic test report

603 – Periodic RF transmission

604 – Fire test

605 – Status report to follow

606 – Listen–in follow

607 – Walk Test mode

621 – Event Log reset

622 – Event Log 50% full

623 – Event Log 90% full 520 – Sounder/Relay Disable

521 – Bell 1 disable

522 – Bell 2 disable

523 – Alarm relay disable

524 – Trouble relay disable

525 – Reversing relay disable

530 and 540 – System Peripheral

Disable

624 – Event log overflow

625 – Time/Date reset

626 – Time/Date inaccurate

627 – Program mode entry

628 – Program mode exit

631 – Exception schedule change

550 and 560 – Communication

Disable

551 – Dialer disable

552 – Radio transmitter

570 – Disable Bypasses

570 – Zone bypass

571 – Fire zone bypass

572 – 24 Hour zone bypass

573 – Burglary zone bypass

574 – Group bypass

Programming instructions

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.25

Programming instructions

Setting up a Zone

Before you begin

Configure the Zone

Before you begin, you should complete a Zone Programming

Worksheet (Figure 4-9) for each Zone. Keep a copy for your records. You will also need to refer to the Output Group programming worksheets.

To set up a Zone:

1. On the control panel, press Menu.

2. Choose Login then enter the password required for Level 4 access.

3. Choose Program > Configure > Zone.

4. To program a new Zone, choose Add, and then choose a zone type (Alarm, Supervisory, or Monitor).

— or —

Choose Edit, select an existing zone from the pick list, and then press Enter.

1. Choose Message, scan in the message text, and then press Enter.

2. Choose Members, then for each device that comprises the

Zone:

Choose Device Address, then enter the member's device number from the worksheet

— or —

Choose Enter Serial#, scan in or enter the member's serial number.

3. Choose Review to verify which devices you added to the

Zone. If you added any devices in error, delete them.

4. Choose Output Group > Add, then select the Output group from the pick list that contains the responses you want activated, and then press Enter.

Repeat for each Output group you want to add.

5. Choose Review to verify which Output groups you added to the Zone. If you added any Output groups in error, remove them.

6 For coded systems, choose Coding, and then enter the

Zone Code.

4.26

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Job Name:

Panel: Card: 14

Page of

# of CMS receivers: ¨ 1 ¨ 2

CMS phone numbers: Receiver 1: #1) Receiver 1: #2)

Receiver 2: #1) Receiver 2: #2)

Retry Count: ¨ 5 ¨ 6 ¨ 7 ¨ 8 ¨ 9 ¨ 10

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Account Number:

Test strings:

Format: ¨ 4/2 ¨ Contact ID

Panel normal: Panel off-normal:

Time: CMS receiver to dial: ¨ 1 ¨ 2

Figure 4-1: DLD Programming Worksheet (sheet 1 of 2)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.27

Programming instructions

Job Name:

Panel: Card: 14

Default Alarm Message: Account Number:

Active Message:

Restore Message:

Default Trouble Message: Account Number:

Active Message:

Restore Message:

Default Supervisory Message: Account Number:

Active Message:

Restore Message:

Figure 4-1 DLD Programming Worksheet (sheet 1 of 2)

Page of

4.28

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Page of Job Name:

Panel: Card:

001 Device Type:

Text Message: 1)

2)

002 Device Type:

Text Message: 1)

2)

003 Device Type:

Text Message: 1)

2)

004 Device Type:

Text Message: 1)

2)

005 Device Type:

Text Message: 1)

2)

006 Device Type:

Text Message: 1)

2)

007 Device Type:

Text Message: 1)

2)

008 Device Type:

Text Message: 1)

2)

IDC 001

IDC 002

IDC 003

IDC/NAC 004

IDC/NAC 008

IDC 007

IDC 006

IDC 005

Defaults: Alarm for IDC 001 – 003 and IDC 005 – 007,

Common Alarm Output for IDC/NAC 004, Visual for

IDC/NAC 008

Figure 4-2: ZA8–2 Programming Worksheet

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.29

Programming instructions

Job Name:

Panel: Card:

Page of

001 Device Type:

Text Message: 1)

2)

002 Device Type:

Text Message: 1)

2)

003 Device Type:

Text Message: 1)

2)

004 Device Type:

Text Message: 1)

2)

005 Device Type:

Text Message: 1)

2)

006 Device Type:

Text Message: 1)

2)

007 Device Type:

Text Message: 1)

2)

008 Device Type:

Text Message: 1)

2)

009 Device Type:

Text Message: 1)

2)

010 Device Type:

Text Message: 1)

2)

011 Device Type:

Text Message: 1)

2)

IDC 001

IDC 002

IDC 003

IDC 004

IDC 012

IDC 011

IDC 010

Defaults: Alarm for IDC 001–012, Common Alarm

Output for IDC/NAC 013–014, Visual for IDC/NAC 015–

016

IDC 005

IDC 006

IDC 007

IDC 008

IDC 009

IDC/NAC 013

IDC/NAC 014

IDC/NAC 015

IDC/NAC 016

012 Device Type:

Text Message: 1)

2)

013 Device Type:

Text Message: 1)

2)

014 Device Type:

Text Message: 1)

2)

015 Device Type:

Text Message: 1)

2)

016 Device Type:

Text Message: 1)

2)

Figure 4-3: ZB16–4 Programming Worksheet

4.30

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Job Name:

Panel: Card:

001 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

002 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

003 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

004 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

005 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

006 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

007 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

008 ¨ NC (normally-closed)

¨ NO (normally-open)

Device type:

004

003

002

001

005

006

007

008

Figure 4-4: ZA8–2 Programming Worksheet

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

Programming instructions

Page of

JP4

004+ 004–

NC

NO

NC

NO

JP8

008+ 008–

4.31

Programming instructions

Job Name:

Panel:

Page of

Card:

NAC 1 device type: ¨ Audible ¨ Visible

Wiring class: ¨ Class A ¨ Class B

NAC 2 device type:

Number of detector addresses used on loop:

¨ Audible ¨ Visible

Number of module addresses used on loop:

Card:

NAC 1 device type: ¨ Audible ¨ Visible

Wiring class: ¨ Class A ¨ Class B

NAC 2 device type:

Number of detector addresses used on loop:

¨ Audible ¨ Visible

Number of module addresses used on loop:

Card:

NAC 1 device type: ¨ Audible ¨ Visible

Wiring class: ¨ Class A ¨ Class B

NAC 2 device type:

Number of detector addresses used on loop:

¨ Audible ¨ Visible

Number of module addresses used on loop:

Card:

NAC 1 device type: ¨ Audible ¨ Visible

Wiring class: ¨ Class A ¨ Class B

NAC 2 device type:

Number of detector addresses used on loop:

¨ Audible ¨ Visible

Number of module addresses used on loop:

Figure 4-5: SLIC Programming Worksheet

4.32

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Page of Job Name:

Panel: Card:

Model:

Sensitivity:

Verification:

Pre-Alarm:

Base type:

Message:

S/N Device:

¨ Most

¨ None

¨ None

¨ Standard

¨ More

¨ 12 s

¨ 20%

¨ Relay

¨ Normal

¨ 24 s

¨ 40%

¨ Isolator

¨ Less

¨ 36 s

¨ 60%

¨ Least

¨ 60 s

¨ 80%

1) 2)

Model:

Sensitivity:

Verification:

Pre-Alarm:

Base type:

Message:

S/N Device:

¨ Most ¨ More ¨ Normal ¨ Less ¨ Least

¨ None

¨ None

¨ 12 s

¨ 20%

¨ 24 s

¨ 40%

¨ 36 s

¨ 60%

¨ 60 s

¨ 80%

¨ Standard ¨ Relay ¨ Isolator

1) 2)

Model:

Sensitivity:

Verification:

Pre-Alarm:

Base type:

Message:

S/N Device:

¨ Most

¨ None

¨ None

¨ Standard

¨ More

¨ 12 s

¨ 20%

¨ Relay

¨ Normal

¨ 24 s

¨ 40%

¨ Isolator

¨ Less

¨ 36 s

¨ 60%

¨ Least

¨ 60 s

¨ 80%

1) 2)

Model:

Sensitivity:

Verification:

Pre-Alarm:

Base type:

Message:

S/N Device:

¨ Most

¨ None

¨ None

¨ Standard

¨ More

¨ 12 s

¨ 20%

¨ Relay

¨ Normal

¨ 24 s

¨ 40%

¨ Isolator

¨ Less

¨ 36 s

¨ 60%

¨ Least

¨ 60 s

¨ 80%

1) 2)

Figure 4-6: Signature Detector Programming Worksheet

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.33

Programming instructions

Job Name:

Panel: Card:

Page of

Model: S/N Device: 1st) 2nd)

Device #1

Device Type:

Personality:

Message: 1)

2)

Device #2

Device Type:

Personality:

Message: 1)

2)

Model: S/N Device: 1st) 2nd)

Device #1

Device Type:

Personality:

Message: 1)

2)

Device #2

Device Type:

Personality:

Message: 1)

2)

Model: S/N Device: 1st) 2nd)

Device #1

Device Type:

Personality:

Message: 1)

2)

Device #2

Device Type:

Personality:

Message: 1)

2)

Model: S/N Device: 1st) 2nd)

Device #1

Device Type:

Personality:

Message: 1)

2)

Device #2

Device Type:

Personality:

Message: 1)

2)

Figure 4-7: Signature Module Programming Worksheet

4.34

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Programming instructions

Page of Job Name:

Panel: Output Group:

Response: __ __ __ Type: ¨ Active ¨ Trouble

¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal

¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s

¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration

Priority: ¨ Life Safety ¨ Property ¨ System Integrity

String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Type: ¨ Active ¨ Trouble

¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal

¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s

¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration

Priority: ¨ Life Safety ¨ Property ¨ System Integrity

String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Type: ¨ Active ¨ Trouble

¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal

¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s

¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration

Priority: ¨ Life Safety ¨ Property ¨ System Integrity

String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Response: __ __ __ Type: ¨ Active ¨ Trouble

¨ Relay Device: __ __ __ __ __ ¨ On ¨ 20 bpm ¨ 120 bpm ¨ Temporal

¨ Delay Delay Type: ¨ Act and Restoration ¨ Activation ¨ Restoration Time: __ __ __ __s

¨ Dialer Account No.: __ __ __ __ Send On: ¨ Activation ¨ Restoration

Priority: ¨ Life Safety ¨ Property ¨ System Integrity

String: (CID) __ __ __ __ __ __ __ __ __ (4/2) __ __

Figure 4-8: Output Group Programming Worksheet

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

4.35

Programming instructions

Job Name:

Panel: Zone:

Zone Type: ¨ Alarm ¨ Supervisory ¨ Monitor

Zone Code:

Message: 1)

2)

Page of

Zone Members (32 max):

Output groups (6 max):

Figure 4-9: Zone Programming Worksheet

4.36

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 5

Standard applications

Summary

This chapter provides simplified wiring schematics for standard applications.

Content

Notification appliance circuits • 5.2

Initiating device circuits • 5.5

Coded alarm signaling • 5.8

Remote station protective signaling system • 5.10

Auxiliary protective signaling • 5.12

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.1

Standard applications

Notification appliance circuits

SLIC

NAC1 B+

NAC1 B–

NAC1 A+

NAC1 A–

UL/ULC LISTED

10 K EOLR

NAC2 B+

NAC2 B–

NAC2 A+

NAC2 A–

UL/ULC LISTED

Typical Class A NAC circuits

SLIC

NAC1 B+

NAC1 B–

NAC1 A+

NAC1 A–

NOT USED

NAC2 B+

NAC2 B–

NAC2 A+

NAC2 A–

NOT USED

Typical Class B NAC circuits

UL/ULC LISTED

10 K EOLR

Note: The plus and minus symbols indicate signal polarity when the

NAC circuit is turned on.

UL/ULC LISTED

10 K EOLR

Note: The plus and minus symbols indicate signal polarity when the

NAC circuit is turned on.

5.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Standard applications

UL/ULC LISTED

47 K EOLR

8 7 6 5

10 9

SIGA–CC1

4 3 2 1 8 7 6 5

SIGA–RM1

4 3 2 1

PS6

AUX(n)

COM

SLIC

LOOP B+

LOOP B–

LOOP A+

LOOP A–

TO DATA OUT TERMINALS

ON LAST DEVICE (CLASS A ONLY)

TO DATA IN TERMINALS

ON NEXT DEVICE

Note: The plus and minus symbols indicate signal polarity when the NAC circuit is turned on.

Typical NAC riser wiring

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.3

Standard applications

ZB16–4

Z13+

Z13–

Z14+

Z14–

Z15+

Z15–

Z16+

Z16–

Typical Class B NAC circuits

ZA8–2

ZONE 4 B+

ZONE 4 B–

ZONE 4 A+

ZONE 4 A–

UL/ULC LISTED

10 K EOLR

NAC1 B+

NAC1 B–

NAC1 A+

NAC1 A–

UL/ULC LISTED

10 K EOLR

Typical Class A NAC circuit

UL/ULC LISTED

UL/ULC LISTED

10 K EOLR

UL/ULC LISTED

10 K EOLR

UL/ULC LISTED

10 K EOLR

5.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Initiating device circuits

PS6

24VDC+

24VDC–

JP2

ACC PWR

SMK PWR

8 7

SIGA–CT1

4 3 2 1

SLIC

LOOP B+

LOOP B–

LOOP A+

LOOP A–

TO DATA IN TERMINALS

ON NEXT DEVICE

TO DATA OUT TERMINALS

ON LAST DEVICE (CLASS A ONLY)

Typical four-wire smoke detector circuit

Standard applications

UL/ULC LISTED

EOL RELAY

UL/ULC LISTED

PS6

24VDC+

24VDC–

JP2

ACC PWR

SMK PWR

UL/ULC LISTED

22 K EOLR

2–SMK

SLIC

LOOP B+

LOOP B–

LOOP A+

LOOP A–

TO DATA OUT TERMINALS

ON LAST DEVICE (CLASS A ONLY)

Typical Class B two-wire smoke detector circuit

14 13 3-2-1 12 11 10 9

SIGA–UM

8 7 6 5 4 3 2 1

UL/ULC LISTED

TO

DATA IN TERMINALS

ON NEXT DEVICE

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.5

Standard applications

PS6

24VDC+

24VDC–

JP2

ACC PWR

SMK PWR

UL/ULC LISTED

22 K EOLR

2–SMK

SLIC

LOOP B+

LOOP B–

LOOP A+

LOOP A–

TO DATA OUT TERMINALS

ON LAST DEVICE (CLASS A ONLY)

Typical Class A two-wire smoke detector circuit

14 13 3-2-1 12 11 10 9

SIGA–UM

8 7 6 5 4 3 2 1

ZB16–4

Z(n)+

Z(n)–

Typical Conventional Class B IDC circuit

ZA8–2

ZONE (n) B+

ZONE (n) B–

ZONE (n) B+

ZONE (n) B–

UL/ULC LISTED

4.7 K EOLR

Typical Conventional Class A IDC circuit

UL/ULC LISTED

4.7 K EOLR

TO

DATA IN TERMINALS

ON NEXT DEVICE

5.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

PS6

24VDC+

24VDC–

JP2

ACC PWR

SMK PWR

ZB16–4

Z(n)+

Z(n)–

Typical Conventional Class B four-wire smoke detector circuit

PS6

24VDC+

24VDC–

JP2

ACC PWR

SMK PWR

ZA8–2

ZONE (n) B+

ZONE (n) B–

ZONE (n) A+

ZONE (n) A–

UL/ULC LISTED

Typical Conventional Class A four-wire smoke detector circuit

Standard applications

UL/ULC LISTED

EOL RELAY

UL/ULC LISTED

UL/ULC LISTED

EOL RELAY

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.7

Standard applications

Coded alarm signaling

1 2 3

1. FACP: Fire alarm control panel with a CPU,

PS6, ZB16–4, and standby batteries.

2. MFC–A Accessory Enclosure: Used for mounting the remote fire alarm equipment.

3. CDR–3 Bell Coder: Provides coded alarm signals for 24 Vdc notification appliance circuits and one of three evacuation signals (temporal, 60 bpm, and 90 bpm).

Note: CDR–3 must have firmware version greater than 2.0.

Notes

• Place the MFC–A and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit.

• Set SW–6 on CDR–3 to ON. Refer to the CDR–

3 installation sheet for programming information.

• Install a 10 k Ω EOLR across TB2–1 and TB2–

2, and TB2–11 and TB2–12 on the CDR–3.

• Set JP2 on the PS6 for ACC PWR

• If the system uses a NAC circuit on an SLIC to output the coded signal, program the NAC circuit signal rate as Steady.

• If the system uses the NAC 1 circuit on an SLIC to output the coded signal to audible notification appliances, set JP1 and JP2 on the SLIC to

EXT.

Figure 5-1: Typical equipment layout, coded alarm signaling application

5.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Standard applications

PS6TB1–16

PS6TB1–18

PS6TB1–12

PS6TB1–11

PS6TB3–3

PS6TB3–1

NAC RISER –

NAC RISER +

10K Ω

SW1

TB1

JP1 JP2

CDR–3

Figure 5-2: Coded alarm signaling wiring (coded alarm signal only)

10K Ω

TB2

PS6TB1–16

PS6TB1–18

PS6TB1–12

PS6TB1–11

PS6TB3–3

PS6TB3–1

NAC RISER –

NAC RISER +

SW1

10K Ω 10K Ω

TB1

TB2

JP1 JP2

CDR–3

Figure 5-3: Coded alarm signaling wiring (coded signal followed by evacuation signal)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.9

Standard applications

Remote station protective signaling system

1 2 3

1. FACP: Fire alarm control panel with a CPU,

PS6, ZB16–4, and standby batteries.

2. MFC–A Accessory Enclosure: Used for mounting the remote fire alarm equipment.

3. RPM Reverse Polarity Module: Provides three independent reverse polarity signals (alarm, supervisory, trouble) for transmitting system status to a remote location.

Notes

• Place the MFC–A and the FACP in the same room and connect using a section of conduit no greater than 20 ft in length. Run all wiring between cabinets through the conduit.

• Set JP2 on the PS6 for ACC PWR.

• Install a 3.9 K Ω EOLR across TB1–1 and TB1–

2 on the RPM.

Figure 5-4: Typical equipment layout, Remote station protective signaling application

5.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Standard applications

PS6

RELAY 1 NO

RELAY 1 C

RELAY 2 C

RELAY 2 NO

RELAY 3 C

RELAY 3 NO

24VDC+

24VDC–

ALRM

RPM

JP1

CITY BOX+

CITY BOX–

SUPV

TRBL

+24V

COM

ALARM+

ALARM–

TROUBLE+

TROUBLE–

SUPV+

SUPV–

3.9 K Ω

Note: Plus and minus symbols indicate signal polarity when the circuit is active.

Figure 5-5: Remote station protective signaling wiring

OFF-SITE

MONITORING

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

5.11

Standard applications

Auxiliary protective signaling

Wire as shown in Figure 5-6. Program the SIGA–CC1 as a common alarm output device. Plus and minus symbols indicate signal polarity with the circuit turned on.

8 7 6 5

10 9

SIGA–CC1

4 3 2 1

LISTED 24VDC

SUPPLY

24VDC+

24VDC–

TO NEXT DEVICE

SLIC

LOOP B+

LOOP B–

LOOP A+

LOOP A–

TO DATA OUT TERMINALS

ON LAST DEVICE (CLASS A ONLY)

Figure 5-6: Auxiliary protective signaling cabling diagram

TO DATA IN TERMINALS

ON NEXT DEVICE

1 2

2–CTM

2 1

Master box

Municipal circuit

5.12

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Chapter 6

Maintenance instructions

Summary

This chapter provides instructions for maintaining the system.

Content

Pseudo point definitions • 6.2

Table 6-1: Main Panel pseudo points • 6.2

Table 6-2: Remote Annunciator pseudo points • 6.2

Table 6-3: Power Supply pseudo points • 6.3

Table 6-4: SLIC card pseudo points • 6.3

Table 6-5: Dialer pseudo points • 6.4

Table 6-6: General CPU pseudo points • 6.5

Maintenance tasks • 6.6

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

6.1

Maintenance instructions

Pseudo point definitions

Table 6-1: Main Panel pseudo points

LCD Indication Event Type

Panel xx Card Communications Trouble

Panel 01 Reset Extension

Panel 01 Service Active Trouble

Monitor/Trouble

Trouble

Trouble Pnl 0x Database Incompatible

Panel 01 Reboot Fault

Panel 0x, CH1 Communications

Panel 01 Task Failure

Card xx Setup Mismatch

Trouble

Trouble

Trouble

Dailer Setup Mismatch

Power Supply Setup Mismatch

Panel 01 LED/Switch display

Panel 0x, CH2 Communications

Pnl 01 Database Supervision

Panel 01 Code Supervision

Panel 01, Call For Service

Panel 01, ROM Supervision

Panel 01 RS232 Port Fault

Panel 01 Unexpected Card

Panel 01 Switch Latched

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Panel 01 Loop Database Fault Trouble

Table 6-2: Remote Annunciator pseudo points

LCD Indication Event Type

Ann 0x Service Active Trouble Trouble

Ann 0x Database Incompatible

Annunciator 0x Reboot Fault

Trouble

Trouble

Definition

CPU has failed to communicate with the option card at address xx.

Signature loop is still resetting.

Service group was restored with a device still in the active condition.

Changes made to the system programming on the control panel were not updated in this unit.

Control panel CPU restarted unexpectedly.

Annunciator is not communicating on RS485 channel 1.

Internal processing fault.

CPU encountered problem configuring the option card at address xx.

A problem has occurred with the CPU configuring the dialer card.

A problem has occurred with the CPU configuring the POWER supply card.

LED/Switch card is not connected.

Annunciator is not communicating on RS485 channel 2.

Internal CPU memory failure

Internal CPU memory failure

Internal CPU processing error

Internal CPU memory failure

CPU detected an option card not defined in the database.

Button either on the main display or on an

LED/Switch card has been pressed too long.

Internal CPU memory failure with Signature data.

Definition

Indicates that a device was left in an active condition after service group has restored.

Indicates that the data

Indicates CPU has restarted due to internal processing failure.

6.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

LCD Indication

Ann 0x, CH1 Communications

Annunciator 0x Task Failure

Ann 0x, LED/ Switch Display

Ann 0x, CH2 Communications

Ann 0x Database Supervision

Ann 0x Code Supervision

Ann 0x, Call For Service

Ann 0x ROM Supervision

Ann 0x RS232 Port Fault

Ann 0x Program Mode

Ann 0x Switch Latched

Annunciator 0x Power Fault

Table 6-3: Power Supply pseudo points

LCD Indication Event Type

Battery Charger Fault Trouble

Battery Wiring or Battery Fault

Aux Power 1/2 Shorted

Trouble

Trouble

Aux Power 3 Shorted

Smoke Power Shorted

Primary AC Power Failure

Excessive Battery Current

Check System Wiring

Power Supply Card RAM Fault

Power Supply Card ROM Fault

Power Supply EEPROM Fault

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Table 6-4: SLIC card pseudo points

LCD Indication

Card 0x, Loop Wiring Problem

Card 0x Map Fault

Event Type

Trouble

Trouble

Event Type

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

Maintenance instructions

Definition

Indicates failure to communicate with the main panel on RS485 channel 1.

Internal software failure

Indicates that a SL30-x has been disconnected or is connected but not defined.

Indicates failure to communicate with the main panel on RS485 channel 2.

Internal memory failure

Internal memory failure

Internal software failure

Internal memory failure

Panel has entered program mode.

Indicates that a button either on the main display or on an SL30-x has been pressed to long.

Indicates a loss of power on either of the 24vdc inputs to the RAI card.

Definition

This fault will occur when the battery charger charging voltage falls below 20.4vdc.

Caused by an open in the battery wiring or if the batteries are below 20.4vdc.

This point occurs when Aux 1 or Aux 2 power is shorted on the PS6

This point occurs when Aux 3

This point occurs when smoke power is shorted

Caused by loss of AC or very low AC.

Will go active when PS6 detects over current condition

Indicates a ground fault exists on field wiring.

Internal memory fault

Internal memory fault

Internal memory fault

Definition

Indicates a break on a Class A signature loop

Signature map is different than the one written in memory

6.3

Maintenance instructions

LCD Indication

Card 0x, Mapping In Progress

Card 0x Unconfig. Device

Card 0x, Line Initialization

Card 0x, Loop Ground Fault

Card 0x, LIM Driver Fault

Card 0x, RAM Supervision

Card 0x, ROM Supervision

Card 0x, EEPROM Supervision

Table 6-5: Dialer pseudo points

LCD Indication

Primary Phone Line:check Telco

Secondary Phone Line:check Telco

Pri. Receiver Failed to answer

Sec. Receiver Failed to answer

Dialer Account 1 Fault

Dialer Account 2 Fault

Dialer Account 3 Fault

Dialer Account 4 Fault

Dialer Account 5 Fault

Dialer Account 6 Fault

Dialer Account 7 Fault

Dialer Account 8 Fault

Dialer ROM Fault

Dialer Queue Overflow

Dialer Card, RAM Supervision

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Event Type

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Trouble

Event Type

Monitor

Trouble

Monitor

Trouble

Trouble

Trouble

Trouble

Trouble

Definition

Indicates Signature devices are in the process of being mapped.

Indicates that a new signature device has been detected on a loop.

Occurs after power up or a restart. Indicates signature devices are being initialized.

Indicates a ground fault on a signature module.

Internal hardware failure.

Internal memory fault

Internal memory fault

Internal memory fault

Definition

Telephone line has low or no voltage

Telephone line has low or no voltage

Dialer attempted to dial event to CMS but did not get an answer.

Dialer attempted to dial event to CMS but did not get an answer.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 1.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 2.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 3.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 4.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 5.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 6.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 7.

Indicates dialer did not get proper handshake for event sent to the CMS for Account 8.

Internal memory fault

Indicates that too many dialer messages are trying to be sent.

Internal memory fault

6.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Table 6-6: General CPU pseudo points

LCD Indication Event Type

Startup Response Monitor

First Alarm

First Supervisory

Alarm

Supervisory

Trouble

Monitor

First Trouble

First Monitor

Evacuation

Drill

Alarm Silence

Two Stage Expiration

Reset

Reset Phase 1

Reset Phase 2

Reset Phase 3

First Disable

First Test

Two Stage Timer Started

User Trouble

Monitor

Monitor

Monitor

Monitor

Monitor

Monitor

Trouble

Trouble

Trouble

Maintenance instructions

Definition

Monitor point that goes active on system startup or after restart.

Occurs anytime that the system goes into alarm for the first time.

Occurs anytime that the system goes into supervisory for the first time.

Occurs anytime that the system goes into a trouble for the first time.

Occurs anytime that the system goes into a monitor condition for the first time.

This point will go active anytime drill is pressed.

This point will go active anytime alarm silence is pressed.

This point goes active anytime reset is pressed.

Active during the power down phase of reset.

Active during the retard phase of reset.

Active during the restoration phase of reset.

Activated the first time an item is disabled from the front menu.

Activated the first time a service group is started from the front menus.

Triggered by custom programming.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

6.5

Maintenance instructions

Maintenance tasks

What is it you want to do

Change the fuse

Replacing a SIGA device when mapping is disabled)

This is how you do it

1. Switch the circuit breaker that supplies ac power to the control panel to the OFF position.

2. Expose the ac terminal block and pull out the fuse holder.

3. Replace the blown fuse with a new one of the same type and size.

4. Plug the fuse holder back into the ac terminal block.

5. Switch the circuit breaker that supplies ac power to the control panel to the ON position.

WARNING: Replacing a device when mapping is disabled leaves the area unprotected. The control panel does not automatically reassign responses to replaced devices when mapping is disabled.

To replace devices on a loop that operates with mapping disabled, you must first enable mapping then accept the map.

After you replace your devices, you can disable mapping on the loop.

Note: Replacement devices must be the same model as the devices being replaced.

1. Press Menu.

2. Log onto the panel as a Level 4 operator.

3. Choose Enable > Loop Mapping.

4. Enter the card number of the SLIC that connects to the device you want to replace.

Wait until mapping finishes before continuing.

5. Choose Cards > Edit.

6. Enter the card number of the SLIC that connects to the device you want to replace.

7. Choose Accept Map.

If actual and expected data for detectors and modules are the same, press Enter.

8. Choose Exit > Exit > Save and Sync.

9. Replace the device.

6.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Appendix A

System calculations

Summary

This appendix provides worksheets for calculating maximum wire lengths for notification and Signature circuits, and for sizing standby batteries.

Content

Notification appliance circuit maximum wire length calculation • A.2

Signature loop maximum wire length calculations • A.3

Battery calculation • A.8

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

A.1

System calculations

Notification appliance circuit maximum wire length calculation

Use this worksheet to determine the maximum wire length of a notification appliance circuit. Fill in one worksheet for each NAC connected to the panel.

Maximum signal loss allowed

1

Wire resistance per 1000 ft/pair 2

×

÷

1.5 V

1000

1500

Ω

Total operating current required

Maximum wire length

3 ÷ A ft

Notes

1. For worst case estimates, assume a 1.5 V line loss and all appliances are clustered at the end of the circuit.

2. Use 3.5 for 12 AWG and 2.5 mm and 1.0 mm

2

2

wire, 5.2 for 14 AWG and 1.5 mm

wire, and 13.0 for 18 AWG and 0.75 mm

2

wire.

2

wire, 8.0 for 16 AWG

3. Use the filtered 20 Vdc Average Operating Current ratings found on the installation or catalog sheet of each device.

A.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

System calculations

Signature loop maximum wire length calculations

Use this worksheet to determine the maximum amount of wire you can use to construct a Signature loop.

Step 1: Calculate the total amount of wire you can used based on the cable manufacturer's capacitance per foot rating. Total amount of wire shall not exceed the values listed in Table A-1.

500000

Cable capacitance ÷ pF/ft

Total wire ft

Table A-1: Maximum amount of wire you can use to construct a Signature loop

Wire type 14 AWG / 1.5 mm² 16 AWG / 1.0 mm² 18 AWG / 0.75 mm

2

Twisted pair, nonshielded

25 pF/36 pF/38 pF

13157 ft

(4010 m)

13888 ft

(4233 m)

20000 ft

(6096 m)

Twisted pair, shielded

58 pF/82 pF/84 pF

Nontwisted pair, nonshielded

20 pF/20 pF/20 pF

5952 ft

(1814 m)

20000 ft

(6096 m)

6098 ft

(1859 m)

20000 ft

(6096 m)

8621 ft

(2628 m)

20000 ft

(6096 m)

Step 2: Use Table A-2, Table A-3, Table A-4, and Table A-5 to determine the longest allowable circuit path based on wire size and type, and the number of detector, module, SIGA–UMs or –MABs installed on the loop.

In the illustration below, the longest circuit path (shown in bold lines) is 1240 ft (377.95 m). The total amount of wire comprising the loop is 1740 ft (530.35 m)

10 ft

(3.05 m)

200 ft

(60.96 m)

FACP J

30 ft

(9.14 m)

200 ft

(60.96 m)

200 ft

(60.96 m)

J J

100 ft

(30.48 m)

1000 ft

(304.8 m)

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

A.3

System calculations

Table A-2: Longest allowable circuit path with 0 SIGA-UMs or SIGA-MABs configured for 2-wire smokes

Signature detector addresses

Maximum allowable wire distance using nontwisted, nonshielded wire pairs

Signature module

18 AWG addresses ft m

16 AWG ft m

14 AWG ft m

51–75

51–75

51–75

51–75

51–75

51–75

26–50

26–50

26–50

26–50

26–50

26–50

76–100

76–100

76–100

76–100

76–100

76–100

101–125

101–125

101–125

101–125

101–125

101–125

0

0

0

0

0

1–25

1–25

1–25

1–25

1–25

1–25

9383

8340

7360

6435

5558

4723

6245

5407

4605

3833

3089

2371

10639

10004

9369

8734

8099

7464

4180

3439

2721

2023

1345

685

11815

11180

10545

9910

9275

11544

10909

10275

9640

9005

8370

5906

5250

4633

4051

3498

2973

3931

3404

2899

2413

1945

1493

6697

6297

5897

5498

5098

4698

2631

2165

1713

1274

847

431

7437

7038

6638

6238

5839

7267

6867

6467

6068

5668

5268

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

1800

1600

1412

1235

1066

906

1198

1037

883

735

593

455

2041

1919

1798

1676

1554

1432

802

660

522

388

258

131

2267

2145

2023

1901

1780

2215

2093

1971

1849

1728

1606

2860

2542

2243

1961

1694

1440

1903

1648

1404

1168

942

723

3243

3049

2856

2662

2469

2275

1274

1048

829

617

410

209

3601

3408

3214

3021

2827

3519

3325

3132

2938

2745

2551

14923

13265

11707

10235

8839

7512

9932

8601

7324

6096

4913

3771

16921

15911

14901

13891

12881

11871

6649

5470

4328

3218

2140

1089

18792

17782

16772

15762

14752

18361

17351

16342

15332

14322

13312

4549

4043

3568

3120

2694

2290

3027

2621

2232

1858

1498

1149

5157

4850

4542

4234

3926

3618

2027

1667

1319

981

652

332

5728

5420

5112

4804

4497

5597

5289

4981

4673

4365

4057

A.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

System calculations

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

51–75

51–75

51–75

51–75

51–75

51–75

26–50

26–50

26–50

26–50

26–50

26–50

76–100

76–100

76–100

76–100

76–100

76–100

101–125

101–125

101–125

101–125

101–125

101–125

0

0

0

0

0

1–25

1–25

1–25

1–25

1–25

1–25

Table A-3: Longest allowable circuit path with 1–5 SIGA-UMs or SIGA-MABs configured for 2-wire smokes

Signature detector addresses

Signature module addresses

Maximum wire distance using nontwisted, nonshielded wire pairs

18 AWG 16 AWG 14 AWG ft m ft m ft m

17126

15492

13899

12342

10819

13525

11926

10359

8821

7311

5826

9542

7966

6416

4890

3387

1905

6293

4720

3168

1638

126

3282

2969

2664

2365

2073

2592

2286

1985

1691

1401

1116

1829

1527

1230

937

649

365

1206

904

607

314

24

8504

7498

6513

5546

4597

3663

10768

9741

8739

7760

6802

5999

5009

4034

3075

2130

1197

3957

2967

1992

1030

80

2066

1869

1677

1489

1305

1632

1439

1250

1064

882

703

1151

961

774

590

409

230

759

569

382

198

15

6778

6131

5501

4885

4282

5353

4720

4100

3491

2893

2306

3776

3153

2539

1935

1340

754

2491

1868

1254

648

50

1386

760

143

422

232

44

2201

1208

227

671

368

69

3501

1921

361

5220

4722

4236

3762

3298

4122

3635

3157

2689

2228

1776

2908

2428

1956

1491

1032

581

1918

1439

966

499

39

1067

586

110

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

A.5

System calculations

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

51–75

51–75

51–75

51–75

51–75

51–75

26–50

26–50

26–50

26–50

26–50

26–50

76–100

76–100

76–100

76–100

76–100

76–100

101–125

101–125

101–125

101–125

101–125

101–125

0

0

0

0

0

1–25

1–25

1–25

1–25

1–25

1–25

Table A-4: Longest allowable circuit path with 6–10 SIGA-UMs or SIGA-MABs configured for 2-wire smokes

Signature detector addresses

Signature module addresses

Maximum wire distance using nontwisted, nonshielded wire pairs

18 AWG 16 AWG 14 AWG ft m ft m ft m

12748

11355

9981

8625

7286

10375

8950

7542

6152

4778

3419

7248

5802

4372

2957

1558

172

4537

3067

1613

173

2443

2176

1913

1653

1396

1988

1715

1445

1179

916

655

869

588

309

33

1389

1112

838

567

299

33

8015

7139

6275

5423

4581

6523

5627

4742

3868

3004

2150

4557

3648

2749

1859

979

108

2853

1929

1014

109

1538

1370

1204

1040

879

1252

1080

910

742

576

412

874

700

527

357

188

21

547

370

195

21

5045

4494

3950

3414

2884

4106

3542

2985

2435

1891

1353

2869

2296

1730

1170

617

68

1796

1214

638

69

833

242

254

74

1323

385

403

117

2105

613

3886

3461

3042

2629

2221

3162

2728

2299

1875

1456

1042

2209

1768

1332

901

475

53

1383

935

492

53

642

187

A.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

System calculations

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

1–25

26–50

51–75

76–100

101–125

0

1–25

26–50

51–75

76–100

101–125

51–75

51–75

51–75

51–75

51–75

51–75

26–50

26–50

26–50

26–50

26–50

26–50

76–100

76–100

76–100

76–100

76–100

76–100

101–125

101–125

101–125

101–125

101–125

101–125

0

0

0

0

0

1–25

1–25

1–25

1–25

1–25

1–25

Table A-5: Longest allowable circuit path with 11–15 SIGA-UMs or SIGA-MABs configured for 2wire smokes

Signature detector addresses

Signature module addresses

Maximum wire distance using nontwisted, nonshielded wire pairs

18 AWG 16 AWG 14 AWG ft m ft m ft m

3931

3427

2928

2432

1941

3247

2722

2202

1686

1174

666

2204

1664

1129

598

71

1198

1045

892

741

592

990

830

671

514

358

203

672

507

344

182

22

6245

5444

4651

3864

3083

5158

4324

3498

2678

1865

1058

3502

2644

1793

950

113

1903

1659

1418

1178

940

1572

1318

1066

816

568

323

1067

806

547

289

34

9932

8659

7397

6145

4903

8204

6878

5563

4259

2966

1683

5570

4205

2852

1511

179

1263

710

161

385

216

49

2007

1128

256

612

344

78

3192

1794

407

3027

2639

2255

1873

1495

2501

2096

1696

1298

904

513

1698

1282

869

460

55

973

547

124

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

A.7

System calculations

Battery calculation worksheet

Use this worksheet to determine the amperage capacity of the panel's standby battery. You can obtain operating current requirements for field devices from their respective installation sheets.

Example: There are 10 strobes rated at 80 mA and 40 mini–horns rated at 10 mA connected to NAC circuits powered by AUX 1. Enter 1200 mA in the Alarm box for AUX 1.

Standby

Current (mA)

Alarm

Current (mA)

Base Panel (Form A)

SMK/ACC power (FormB)

AUX 1 load

[1]

AUX 2 load

AUX 3 load

Loop 1 load

Loop 2 load

Loop 3 load

Loop 4 load

Total Current

[2]

× hr × min

÷ 60

+ = mAh

× 1.2

mAh

÷ 1000

Battery size

[3]

====

Notes

[1] Maximum 1.5 A per AUX circuit.

[2] If the Total Current Required value exceeds 6 A, switch part of the load to an auxiliary power source. The auxiliary power source must be UL/ULC listed for Fire Protective Signaling Systems.

[3] If the calculated battery size exceeds 40 Ah, switch part of the load to an auxiliary power source.

Ah

A.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

System calculations

(A) Base panel current load calculation

Card Qty

Standby

Current (mA)

1 PS6

CPU/Display

SL30 (–1)

[1]

SLIC

DLD

ZB16–4

ZA8–2

X485

ZR8

[2]

73

60

11

33

13

117

82

117

1

Totals

[3]

Qty ×××× Standby

Current (mA)

82

Notes

[1] Add 0.75 mA for each energized LED.

[2] Add 18 mA for each energized relay.

[3] Base panel current must be less than 1.32 mA.

(B) Smoke/Accessory (SMK/ACC) Power current load calculation (max 250 mA)

Card Qty

Standby

Current (mA)

Qty ×××× Standby

Current (mA)

Alarm

Current (mA)

CPU/Display

[3]

SL30 (–1)

[1]

117

1

123

1

CDR–3

IOP3A

RPM

[2]

SIGA-UM, -MAB

[4]

60

60

20

2

100

60

20

17

Alarm

Current (mA)

100

135

1

116

60

18

57

20

152

Totals

Notes

[1] Add 0.75 mA for each energized LED.

[2] Add 0.7 mA for each output used.

[3] This value includes RAI currents

Qty ×××× Alarm

Current (mA)

100

Qty ×××× Alarm

Current (mA)

[4] This represents the smoke power requirements. Only the

SIGA–UM or SIGA–MAB that signaled the alarm draws alarm current. The remaining SIGA–UMs or SIGA–MABs do not.

17

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

A.9

System calculations

A.10

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Appendix B

Barcode library

Summary

This appendix contains a set of barcodes that you can use to add location messages.

Content

Uppercase letters • B.2

Numbers and ordinals • B.2

Common words • B.3

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

B.1

Barcode library

Uppercase letters

A

M

Q

E

I

U V

Y

Numbers and ordinals

Z

1 2

5

9

6

0

B

F

J

N

R

1ST

5TH

9TH

2ND

6TH

0TH

3

7

O

S

W

C

G

K

Space

P

T

X

D

H

L

4

8

3RD

7TH

4TH

8TH

Backspace

Delete

Enter

Backspace

Delete

Enter

B.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

BASEMENT

BELOW

CAFETERIA

CEILING

CLASSROOM

CLOSET

COMPUTER

CONFERENCE

CORRIDOR

DAMPER

DETECTOR

Common words

ABORT

ABOVE

ALARM

APARTMENT

APT

AREA

ATRIUM

AUDITORIUM

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

Barcode library

B.3

Barcode library

DOOR

DUCT

EAST

ELECTRICAL

ENTRANCE

EXIT

FAN

FAULT

FIRE

FIRE PUMP

FLAME

FLOOR

FOYER

GARAGE

GENERATOR

GYM

HALL

HEAT

HORN

JANITOR

B.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

KITCHEN

LAB

LEFT

LEVEL

LIBRARY

LOBBY

LOWER

MACHINE

MECHANICAL

MENS

MEZZANINE

MONITOR

NORTH

OFFICE

PARKING

PENTHOUSE

PULL

RELAY

RESTROOM

RIGHT

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

Barcode library

B.5

Barcode library

ROOM

SECURITY

SHAFT

SMOKE

SOUTH

STAGE

STAIRWELL

STOCKROOM

STORAGE

STROBE

SUITE

SUPERVISORY

TROUBLE

UNDER

UPPER

UTILITY

WAREHOUSE

WATERFLOW

WEST

WOMENS

B.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

ZONE

Barcode library

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

B.7

Barcode library

B.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

Appendix C

SIGA-REL programming

Summary

This appendix provides information on how to program the SIGA–REL using the QuickStart Configuration Utility

Content

Application block diagram • C.2

Programming instructions • C.3

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

C.1

SIGA-REL programming

Application block diagram

FACP

SLIC

LOOP DATA

RACCR

SIGA–APS

24VDC

LOOP DATA

MFC–A

SIGA–REL

Minimum system requirements

• A QS1 with SLIC card and appropriately sized standby batteries

• A SIGA–APS mounted in an RACCR enclosure with appropriately sized standby batteries to supply 24 Vdc to the SIGA–REL

• A SIGA–REL mounted in an MFC–A enclosure

Caution: You can not have more than 10 SIGA–

RELs on one loop.

Related documentation

Refer to the SIGA–REL Technical Reference

Manual (P/N 387348) and the latest technical bulletins for installation and connection information.

Refer to the SIGA–APS installation sheet for installation and connection information.

Refer to the RACCR installation sheet for installation information.

C.2

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

SIGA-REL programming

Programming instructions

WARNING: Attempting to program this application without a complete understanding of the operation of the SIGA–REL, the latest technical information, and the consequences of exposing someone to fire suppression agents may cause personal injury, event death.

WARNING: Improper application of fire suppression agents can lead to property damage, serious injury, or loss of life. Consult the applicable NFPA documents and the local authority having jurisdiction (AHJ) for more information.

WARNING: Disabled and Service Group points will not prevent activation of the release circuits.

This application requires the operation of at least two automatic detectors to activate the fire suppression system. In order to meet NFPA 72 requirements, you must program an And group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their Primary and

Alternate Verification properties set to None.

The SIGA–REL has six addressable circuits. To add the SIGA–

REL to the loop controller database you must add three SIGA–

RELs. The first SIGA–REL is for the Abort switch and Manual

Release switch circuits, the second for the two release circuits, and the third for the two prerelease circuits.

Perform these instructions in order from beginning to end.

Check the check box provided as you complete each step.

As a safety precaution, disconnect releasing devices from

SIGA–REL TB4 before downloading setup data to the loop controller.

¨ Add the Abort and Manual

Release Switch circuits

Note: Enter the information exactly as shown to ensure that you program the application according to manufacturer's specifications.

1. Click Configure, then click Cabinets.

2. Select the SLIC connected to the SIGA–REL then click

Configure.

3. Click the Modules tab, then set the Quantity box to 1.

4. Enter the following information:

Device Type: Monitor

Model: REL

Personality: (3) Active B

Message Specification: SIGA–REL1 A001 and ABORT SW

2nd Device Type: Pull

2nd Personality: (1) Alarm B

2nd Message Specification: SIGA–REL1 A002 and MAN

RELEASE SW

5. Click Add.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

C.3

SIGA-REL programming

¨ Add the the two releasing circuits

1. Set the Quantity box to 1.

2. Enter the following information:

Device Type: Output

Model: REL

Personality: (16) Output B

Message Specification: SIGA–REL1 A003 and RELEASE

1&2

2nd Device Type: Monitor

2nd Personality: (0) None

2nd Message Specification: SIGA–REL1 A004 and NOT

USED

3. Click Add.

1. Set the Quantity box to 1.

2. Enter the following information:

Device Type: Output

Model: REL

Personality: (16) Output B

Message Specification: SIGA–REL1 A005 and

PRERELEASE 1&2

2nd Device Type: Monitor

2nd Personality: (0) None

2nd Message Specification: SIGA–REL1 A006 and NOT

USED

3. Click Add.

This is how your entries in the Modules table should look. Your addresses may be different.

Address

126

127

128

129

130

132

Serial Number Device Type Model

Monitor

Pull

Output

Monitor

Output

Monitor REL

REL

REL

REL

REL

REL

Text 1

SIGA–REL1 A001

SIGA–REL1 A002

SIGA–REL1 A003

SIGA–REL1 A004

SIGA–REL1 A005

SIGA–REL1 A006

Text 2

ABORT SW

MAN RELEASE SW

RELEASE 1&2

NOT USED

PRERELEASE 1&2

NOT USED

Personality

(3) Active B

(1) Alarm B

(16) Output B

(0) None

(16) Output B

(0) None

C.4

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

SIGA-REL programming

¨ Create a response that activates the prerelease circuits when any one detector in the protected area signals an alarm

1. Click Configure > Correlations

2. Click the Zones tab, then click Add Zones.

3. Click the Members tab, then click Add Device.

4. Select only the devices required to activate the SIGA–REL prerelease circuits then click OK.

5. Click the Responses tab, click the Response Type arrow, and then select Active.

6. Click Outputs, select the device labeled SIGA REL1 A005

PRERELEASE 1&2, and then click OK.

¨ Create a response that activates the release circuits when two or more detectors in the protected area signal an alarm

Note: To comply with NFPA 72, you must program an And Group with at least two smoke detectors and a minimum activation count of 2. The smoke detectors must have their

Primary and Alternate Verification properties set to None (verified smoke detectors not allowed).

1. Click the And Groups tab, then click Add AND Group.

2. Set the Activation Count box for 2.

3. Click the Members tab, then click Add Device.

4. Select only the detectors required to activate the SIGA–

REL release circuits then click OK.

5. Click the Responses tab, click the Response Type arrow, and then select Active.

6. Click Delays

7. In the Delay On list, click Activation and Restoration.

8. Set the Seconds box to 10.

9. Click Outputs, select the device labeled SIGA REL1 A003

RELEASE 1&2, and then click OK.

¨ the release circuits when someone presses the manual release switch

1. Click the Devices tab, then select the circuit labeled

SIGA–REL A002 MAN RELEASE SW.

2. Click the Responses tab, click the Response Type arrow, and then select Active.

3. Click Outputs, then:

Hold the Ctrl key down

Select the device labeled SIGA REL1 A005 Prerelease

1&2

Select the device labeled SIGA REL1 A003 Release 1&2

Release the Ctrl key then click OK.

Note: The prerelease circuit must appear before the releasing circuit in the response list.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

C.5

SIGA-REL programming

¨ the prerelease circuits when someone presses the Drill switch

Note: Create this response only if required. Pressing Drill will activate the prerelease circuits but pressing Drill a second time will not restore the prerelease circuits. You must press

Reset to silence the prerelease circuits.

1. Click the Devices tab then select the Show Pseudo Points check box.

2. Select the circuit labeled Drill (address 007).

3. Click the Responses tab, click the Response Type arrow, and then select Active.

4. Click Outputs, select the device labeled SIGA REL1 A005

PRERELEASE 1&2, and then click OK.

¨ Retrieve the loop data from the

SLIC

1. Click Configure, then click Cabinets.

2. Select the SLIC connected to the SIGA–REL then click

Configure.

3. Set the Communications Port setting for the COM port used to connect the service computer to the control panel.

4. Click Retrieve Signature Data

5. After the upload has finished, click OK.

¨ Reconcile the actual and expected data

Caution: Clicking Accept Actual will enter the selected device into the database with its current programmed parameters. This will corrupt the database if you have already entered the device.

1. Click the Mapping tab, then click Model.

2. Look for a string of at least six RELs marked with red backgrounds and double-click the first REL in the string.

3. If the serial number displayed in the Module Properties dialog is not the same as the serial number shown on the bar code attached to the SIGA–REL, click Close, and then double-click the next REL in the string.

4. If the serial numbers are the same:

Click Select Expected.

In the Module Selection dialog, select the row that has the

REL with the Monitor device type and marked SIGA–REL1

A001 Abort SW, then click OK.

Click Close.

5. Select the next REL then click Select Expected.

In the Module Selection dialog, select the row that has the

REL with the Output device type and marked SIGA–REL1

A003 Release 1&2, then click OK.

Click Close.

6. Select the next REL then click Select Expected.

In the Module Selection dialog, select the row that has the

REL with the Output device type and marked SIGA–REL1

A005 Prerelease 1&2, then click OK.

Click Close.

C.6

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

SIGA-REL programming

¨ Send the reconciled data to the loop controller

Click the Controller tab, then click Send Signature Data.

QS4 Technical Reference Manual

Technical Manuals Online! - http://www.tech-man.com

C.7

SIGA-REL programming

C.8

Technical Manuals Online! - http://www.tech-man.com

QS4 Technical Reference Manual

advertisement

Related manuals

Download PDF

advertisement

Table of contents