CE RoHS compliance
LT 23A series is a 48×48mm digital indicating controller with
indicating accuracy of ±0.5% and the control cycle of approximately 0.5 seconds.
There are two type of mounting methods, terminal block type
and socket type.
3 types of auto tuning functions and overshoot suppression
functions are provided and highly safe control is achieved.
Combination of internal computing function and enriched input and output option support various usage scenarios.
Special loader software provides ease of setting operations
and data acquisition.
■FEATURES
■MODELS
●Compact design
Short depth of instrument (case 60mm) saves the space of instrument
and control board.
●Enriched input types
Thermocouple group, resistance thermometer group, DC voltage / DC
group can be selected. Input types can be changed within each group.
●Outstanding controllability
Control system can be selected from two-position control, PID control
and self-tuning.
It has overshoot suppression function and high functionality PID.
●3 type of auto tuning
Can be selected from normal, rapid-response, safe tuning on the control
target.
●Various input / output signal (optional) are available
Current transformer input 2 points, event output 3 points (Max), remote
signal input 2 points, communication interface (RS485).
●Terminal block type and socket type are available
●Conformance to international safety standards
Conformance to CE marking, RoHS
●Loader software is available
Various parameter settings and data acquisition can be done easily using
loader software (sold separately) .
LT23A□□□□□□□□□
Measur- Control
ing input output
I/O Terminal Power Extra
option type
48mmX48mm front size
LT23A
1
Thermocouple input
2
RTD input
8
DC voltage/current input
Control output 1 Control output 2
*2 1 0
5 0
*1 5 3
*1 5 5
②
⑦
⑤
③Status display lamp
④[FUNC] key :
⑤[MODE] key :
⑥<,∨,∧ Key :
⑦Recorder connector :
SSR drive pulse output
—
SSR drive pulse output SSR drive pulse output
3 0
SSR drive pulse output
*1 3 3
Current output
Current output
Event output 3 points
*1,*3 02
Event output 3 points,
CT input 2 points,External signal input 2 points
*1,*3 03
Event output 3 points,CT input 2 points,
Communication interface RS485
*5 04
Event output 2 points (independent contact)
*1,*3,*5 05
Event output 2 points (independent contact),
CT input 2 points,External signal input 2 points
Event output 2 points (independent contact),
CT input 2points,Communication interface RS485
Terminal block type
0
Displays PV values (preset temperature,etc) or
settings items.
Displays SP values (set temperature,etc) and
other parameter values.
RDY : Lights when READY (Control stop)
MAN : Lights when MANUAL (manual mode)
EV1 to EV3 : Lights when event outputs are ON.
O1 to O2 : Lights when the control output is ON.
The operations which has been set beforehand can
be done by pushing the key for 1s or more.
The function is disabled at factory default.
Switches the display.
Used for incrementing numeric values and
performing arithmetic shift operation.
Connects to a personal computer by using USB
loader cable.
—
—
*1,*3,*5 06
⑥
②Lower display :
—
SSR drive pulse output Current output
01
①
①Upper display :
ON-OFF pulse
00
■PARTS NAMES OF FUNCTIONS
④
③
Specifications
Socket type
*4 S
A
100-240 V AC
D
24V AC/DC
00 No additional treatment
Y0 Complying with the traceability certification
*1: Cannot be selected for the socket type *2: Only 1a contact applicable for the socket type
*3: Current transformer is sold separately *4: Socket is sold separately
*5: Cannot be selected for 24V AC/DC power supply
Note) For ON-OFF pulse 2 control outputs, even output
(option) will be used as control outputs.
There is 3 points (common) and 2 points (independent contact) so please select
depending on the usage.
PSE-809
LT23A Series
48x48mm compact body
IP66 protection structure of dust
and water proof
48mm
60mm
48mm
Compact body of 48x48mm and 60mm in depth.
There is not only panel mounting type but also socket type,
so it can correspond to multiple types of installations such as
panel mounting type and DIN rail mounting type.
Front of LT23A employs IP66 protection structure of dust-proof
and water-proof.
Advanced controllability
Overshoot suppression
factor Small
(SP)
(SP)
PV
PV
Overshoot suppression
factor Large
High-performance PID
PID
Time
Time
Easy-to-read display
On the display, measuring value (PV) is indicated in green
and setting value (SP) is indicated in orange LEDs
Frequently used operation can be assigned to the FUNC key
By assigning frequently used operation such as RUN/READY
to the FUNC key, only one press of a button enables switching
the functions.
Easy-to-read display
Measuring input
Control output (select at model)
*Group selection by the model
ON-OFF pulse outputs
Thermocouple 12 types
RTD 2 types
DC Voltage / Current 6 types
Event output (option)
Current transformer input (option)
2 points
3 points
2 points (independent contact)
External signal input (option)
2 points
Loader connector
Support loader software 1 port
Communication (option)
RS485 1 port
*Various parameter settings are available from PC by using dedicated loader software. However, it requires exclusive loader cable (sold separately).
Internal event can be output as external
contact output by logical operation
Loader software (sold separately)
On LT23A…
Event 1
Event 2
Event 3
Program
Operation
3 points of event can be output
Result of the logical operation which performed on selected five points
of various internal events is able to be assigned to the three points of
external digital outputs. It can simplify process of event outputs which
logical operation was conventionally performed on receiver side.
Various parameter settings and data acquisition are available by connecting
this controller to the PC which the loader software is installed.
2
■ SPECIFICATIONS
●Input specifications
●General specifications
Input signal:
Operation temperature:
0 to 50℃
Power supply voltage range:
AC power supply model 100 to 240 V AC, 50/60Hz
DC power supply model 24 V AC, 50/60Hz/24V to 48V DC
Power consumption:
AC power supply model 12 VA or/and lower
DC power supply model 7 VA or/and lower (24V AC) 5W
or/and lower (24V DC)
Safety standards: CE marking compliant product
Structure:
IP66 (front part)
Weight:
Terminal block type: 150g
Socket type: 200g (including socket)
Group selection by the models (Thermocouple, Resistance
Thermometer, DC voltage/current)
Range type:
Refer to a measuring range table
Input sampling cycle:
500ms
Accuracy rating: ±0.5%FS±1digit
●Control specifications
Output type:
ON-OFF pulse output type:1c 250V AC, 30V DC 3A
(resistance load)
Current output type:
0 to 20 A DC, 4 to 20 mA DC (It
can be changed by the setting)
SSR drive pulse output type:
19V DC±15%, Internal resistance
82Ω, Allowable current Max.
24mA DC
■ ACCESSORY (Sold separetely)
■ ACCESSORY
Item
Model
Item
Model
Attachment (for terminal block type)
LTA-P205
Hard cover
LTA-P202
Manual
L2A-11-□
Soft cover
LTA-P203
Gasket (for terminal block type)
LTA-P206
Terminal cover
LTA-P204
Current transformer
LTA-P207 (5.8mm hole dia.), LTA-P208 (12mm hole dia.)
■ OPTIONAL SOFTWARE
Attachment (for terminal block type)
LTA-P205
LTA-P206
Item
Model
Gasket (for terminal block type)
20 pieces
Loader software (cable included)
LTA-S001
Socket
LTA-P201
Loader software
LTA-S002
Plug coversion cable for LT23A
LTA-P209
Loader cable
LTA-S003
Shunt resister 250Ω
RZ-EX250
■ MEASURING RANGE
C01
Set value
Input type
K
J
Thermocouple
E
T
R
S
B
N
Platinel
WRe5-26
RTD
DC voltage/current
DIN U
DIN L
Pt100
JPt100
Pt100
JPt100
Pt100
JPt100
Pt100
JPt100
Pt100
JPt100
Pt100
JPt100
Pt100
JPt100
0 to 1V
1 to 5V
0 to 5V
0 to 10V
0 to 20mA
4 to 20mA
1
2
3
4
5
6
9
10
11
13
14
15
16
17
18
19
20
21
24
25
41
42
43
44
45
46
51
52
53
54
63
64
67
68
84
86
87
88
89
90
Measuring range
-200
to
1200℃
0
to
1200℃
0.0
to 800.0℃
0.0
to 600.0℃
0.0
to 400.0℃
-200.0
to 400.0℃
0.0
to 800.0℃
0.0
to 600.0℃
-200.0
to 400.0℃
0.0
to 600.0℃
-200.0
to 400.0℃
0
to
1600℃
0
to
1600℃
0
to
1800℃
0
to
1300℃
0
to
1300℃
0
to
1400℃
0
to
2300℃
-200.0
to 400.0℃
-100.0
to 800.0℃
-200
to
500℃
-200
to
500℃
-200
to
200℃
-200
to
200℃
-100
to
300℃
-100
to
300℃
-50.0
to 200.0℃
-50.0
to 200.0℃
-50.0
to 100.0℃
-50.0
to 100.0℃
0.0
to 200.0℃
0.0
to 200.0℃
0
to
500℃
0
to
500℃
Measuring accuracy
±0.5%FS±1digit
Minus area is
±1.0%FS±1digit
Range with decimal
point is
±0.5%FS±2digit
Under 260℃:±5%FS,260-800℃:±1%FS
Minus area is
±1.0%FS±2digit
±0.5%FS±1digit
The scaling and decimal point
position can be changed variably
in a range of -1999 to +9999
±0.5%FS±1digit
Lower limit of indication value of B thermocouple is 20℃
*●Applicable
standards
・Thermocouple
K,J,E,T,R,S,B,N :
Platinel :
WRe5-26 :
DIN U,DIN L :
JIS C 1602-1995
Engelhard Industries(ITS90)
ASTEM E988-96(Reapproved 2002)
DIN43710-1985
・Resistance thermometer
Pt100 :
JIS C 1604-1997
JPt100 :
JIS C 1604-1989
3
■TERMINAL BOARD
●Terminal block type
●Socket type
CT input
Control output
Control output
Event output
NO
NO
COM
ON-OFF pulse
ON-OFF pulse
Relay
NC
NC
Event output
SSR driver pulse
SSR driver pulse
Relay
Individual contact
COM
Relay
SSR driver pulse
Current
Current
Measurement input
Relay
Individual contact
SSR driver pulse
SSR driver pulse
Power supply
100-240V AC
Thermocouple
Power supply
Current
Current
Current
Current
24V AC
24-48V DC
(Non polar)
Measurement input
24V AC
24-48V DC
(Non polar)
RTD
100-240V AC
−
Voltage
Socket terminal number
Thermocouple
●RS485 communication connection
DI/communication
16
RTD
17
18
RS-485
Remote signal input
Cautions for handling
Current
Do not connect the external resistor because this unit has
a built in termination resistor.
Communication interface
RS485
Voltage
Example: Method to connect with 5 line type instrument.
■DIMENSIONS
●Terminal block type
●Panel cutout
Compliant panel board thickness 9 max
●Separate installation
60
Mounting
(Accessories)
13
7
2
14
8
3
15
9
4
16
10
5
17
11
6
18
12
+0.5
0
45
45 +0.5
0
1
More than 30
More than 50
48
59
Terminal screws M3
□44.8
48
● Closed installation
45 +0.5
0
2
(48xN-3)+0.5
0
N indicates No of
devices to be mounted.
●Socket type
●Wiring terminal block
48
2
□44.8
74.2
61.2
31
26.5
51
Terminal screws M3.5
8
7
6
5
4
48
71
Mounting hole for 2-M4
40
9
3
11
1
2
3.4
10
Unit : mm
Specifications subject to change without notice. Printed in Japan (I) 2014. 8
32-8 KUMANO-CHO,ITABASHI-KU,TOKYO 173-8632
Telephone : +81-3-3956-2171
Facsimile : +81-3-3956-0915
E-mail : [email protected]
Website : www.chino.co.jp/
"
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement