Thermozone® AD Corinte
1 Ambient, no heat
3
2
R
15 – 22,5 kW Electrical heat
Vertical: 2,2 and 2,5 metres
Horizontal: 1,7 and 2,2 metres
Water heat
Thermozone® AD Corinte
Air curtains for doors with heights of up to 3 metres
Application
AD Corinte belongs to a new generation of intelligent
air curtains with SIRe integrated controls, together they
can provide fully automatic protection for the entrance,
adaptable to each area of use.
AD Corinte is intended for exclusive shop entrances
and other environments with high demands in respect
of design and soundlevel. Mounted with one unit on
either side of the opening, thus creating a classic
symmetry, the curtain effect and comfort is optimized.
Comfort
AD Corinte creates an air barrier, which prevents
cold draughts and ensures comfortable heating inside
the door. Thanks to fan technology with radial fans,
the sound level is kept low while maintaning a high
performance. With the integrated SIRe the air curtain is
automatically controlled as required, which reduces the
sound levels even further.
Operation and economy
Air curtains save energy. The air barrier reduces
energy losses through the door opening and the energy
consumption of the air curtain is also low. AD Corinte
never uses more energy than is necessary. Eco mode is
available for further energy savings. AD Corinte can be
controlled and monitored by the BMS system.
Design
AD Corinte is a stylish and exclusive air curtain
available in polished, mirror-polished or brushed
stainless steel.
Product specifications
• Integrated control system SIRe with preset factory
settings and calendar function which makes it easy to
install and use the air curtain.
• AD Corinte is available for horizontal or vertical
mounting.
• For vertical mounting, electricity and/or water may
be connected from above or below.
• Optimized airflow with Thermozone technology.
• Available in polished, mirror-polished or brushed
stainless steel. Colour intake and outlet grille: black,
RAL 9005.
Air velocity profile
AD Corinte
0m
13,0 m/s
1m
5,5 m/s
2m
4,0 m/s
3m
3,1 m/s
Peak values measured with a hot-wire anemometer.
Thermozone® AD Corinte
Technical specifications | Type
Output
[kW]
ADCS17A*¹
0
Thermozone AD Corinte A without heat  1
Output
motor
[W]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[m3/h]
Sound
level*5
[dB(A)]
[mm]
[kg]
1400/3000
40/60
670
230V~
2,9
1700
73
Airflow
Weight
ADCS22A
0
1800/4000
42/61
890
230V~
4,3
2200
95
ADCS25A*²
0
2050/4500
43/63
1150
230V~
5,0
2450
108
Technical specifications | Type
ADCS17E*¹
Thermozone AD Corinte E with electrical heat  3
Output
steps
[kW]
Airflow
[m3/h]
0/7,5/15
1400/3000
∆t*4
Output
motor
[W]
Voltage
motor
[V]
Amperage Voltage [V]
motor
Amperage [A]
[A]
heat
Length
[°C]
Sound
level*5
[dB(A)]
[mm]
[kg]
32/15
40/60
670
230V~
2,9
1700
85
400V3~/21,7
Weight
ADCS22E
0/10/20
1800/3600
33/15
42/61
890
230V~
3,6
400V3~/28,9
2200
110
ADCS25E*²
0/11,2/22,5
2050/4100
33/15
43/63
1080
230V~
4,3
400V3~/32,5
2450
125
Technical specifications | Thermozone AD Corinte WL with water heat, coil for low tempered water < 80/60 °C  2
∆t*3,4
Type
Output*
[kW]
[m3/h]
ADCS17WL*¹
33
1400/3000
3
Airflow
Sound
level*5
[dB(A)]
Output
motor
[W]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[°C]
Watervolume
[l]
[mm]
[kg]
42/32
2,8
39/59
670
230V~
2,9
1700
85
Weight
ADCS22WL
46
1800/4000
43/33
3,6
42/60
990
230V~
4,3
2200
110
ADCS25WL*²
52
2050/4500
43/34
4,0
42/61
1150
230V~
5,0
2450
125
Technical specifications | Type
ADCS17WH*¹
Thermozone AD Corinte WH with water heat, coil for high tempered water ≥ 80/60 °C  2
∆t*3,4
[kW]
[m3/h]
[°C]
Watervolume
[l]
22
1400/3000
30/22
2,8
Output*3 Airflow
Sound
level*5
[dB(A)]
Output
motor
[W]
Voltage
motor
[V]
Amperage
motor
[A]
Length
[mm]
[kg]
39/59
670
230V~
2,9
1700
85
Weight
ADCS22WH
30
1800/4000
31/22
3,6
42/60
990
230V~
4,3
2200
110
ADCS25WH*²
34
2050/4500
31/22
4,0
42/61
1150
230V~
5,0
2450
125
*¹) ADCS17 is available only for horizontal mounting.
*²) ADCS25 is available only for vertical mounting.
*3) Applicable at water temperature 80/60 °C, air temperature in + 15 °C.
*4) Dt= temperature rise of passing air at maximum heat output and lowest/highest airflow.
*5) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2.
Ordering key
Type - Unit shape - Connections position - Finish / Material
Example: ADCS22WL - VL - A - P
Connections position
Type
See technical specifications
Unit shape
HL (Horizontal, connections to the left),
HR (Horizontal, connections to the right),
VL (Vertical Left) or VR (Vertical Right)
Connections
position
A or B, see figure.
Finish / material
P = Polished bright annealed
B = Brushed stainless steel
MP = Mirror polished stainless steel
Horizontal
HL
Design and specifications are subject to change without notice.
Vertical
HR
A
A
B
B
Thermozone® AD Corinte
Dimensions
Vertical
Opening
Upper part of the unit seen from above.
134
44
Min 180
45
45
Ø20(2x)
140
40
65
Bottom part of the unit seen from above.
65
150
Ø20(2x)
40
140
150
150
134
100
44
100
150
Min 180
Connection hatch
Thermozone® AD Corinte
Extension hood
Connections from above
Connections from below
80
60
Thermozone® AD Corinte
Dimensions
Horizontal
1700/2200
1670/2170
1
35
80
180
35
Ø1
2
40
Thermozone® AD Corinte
Mounting and connection
Mounting
AD Corinte can be mounted either vertically or
horizontally.
For horizontal mounting, the unit may be mounted
on the wall or on the ceiling with the enclosed brackets.
For suspended mounting from the ceiling, suitable
devices (threaded bars, rails etc.) are fixed on the
brackets.
A mounting edging is included with the vertically
mounted units. The edging is put on the floor beneath
the air curtain. The unit is anchored to the floor with
expansion-shell bolts for instance.
When ordering AD Corinte for vertical mounting it
is necessary to specify on which side of the opening it
should be positioned. It is recommended to specify if
electricity and/or water connections should be made
from above or below, but this can be altered on site.
When ordering AD Corinte for horizontal mounting,
it is necessary to specify left or right connection (seen
from inside the building).
The unit can be provided with an75extension hood to
cover the distance between unit and ceiling (max length
1000 mm).
Connection
The electrical connection may be done from above or
below when mounted vertically, and from left or right
when mounted horizontally, according to ordering key.
The control system is pre-installed in the air curtain
with an integrated PC board. SIRe is supplied pre376
programmed with quick-fit plug connections.
ADCS A/E: Min 220 mm
ADCS W: Min 180 mm
50
75
376
ADCS A/E: Min 220 mm
ADCS W: Min 180 mm
50
ADCS A/E: Min 220 mm
ADCS W: Min 180 mm
Fig 1. Minimum distances.
Connection AD Corinte A 1
The electrical connection may be done from above or
below when mounted vertically, and from left or right
when mounted horizontally, according to ordering key.
Control (230V~) should be connected to a terminal
block in the terminal box.
Connection AD Corinte E 3
The electrical connection may be done from above or
below when mounted vertically, and from left or right
when mounted horizontally, according to ordering key.
For units with electrical heating, power and control
should be supplied separately. Control (230V~) and
power supply for heat (400V3~) should be connected to
a terminal block in the terminal box.
SIRe
Connection AD Corinte W 2
The electrical connection may be done from above or
below when mounted vertically, and from left or right
when mounted horizontally, according to ordering key.
Control (230V~) should be connected to a terminal
block in the terminal box.
The water connection may be done from above or
below when mounted vertically, and from the left or
right when mounted horizontally. The smooth Ø22 mm
copperpipes is connected by compression fitting or
through welding the pipe work to the unit.
Fig. 2: PC board SIRe is integrated in the air curtain at delivery.
ADCS
ADCS
Thermozone® AD Corinte
Control AD Corinte - control system SIRe
PE N L
SUPPLY 230V
X5
C2
SIReUB1
SIReUA1
X4
C1
X3
ROOM
ACTUATOR
230V
SIReB1
SIReIT
SIReCC
SIReDC
SIReC1X/A1X
This air curtain is supplied with an intregrated PC
board SIRe. SIRe is an intelligent and well designed
low voltage control system which can be customised
for each unique application and environment. SIRe
is supplied pre-programmed with quick fit plug
connections and is very easy to use and install.
SIRe learns the requirements in the entrance it
is installed in (e.g. opening frequency and outdoor
temperature).
It has calendar function and selectable switch off at
set temperatures for up to nine units. Because the fan
speed is adapted, the sound level is optimised and is
never higher than is necessary for comfort. With SIRe
Advanced it is possible to choose between Eco and
Comfort mode dependent on whether energy savings or
optimal comfort has been prioritised.
Included in SIReB Basic:
There are three different levels with different
functionality to choose from, Basic, Competent or
Advanced.
• SIReC1X, PC board HUB Competent
Functions SIReB Basic
• Manual regulation of the fan and temperature
• Automatic control of fan speed and temperature with
integrated thermostat.
Functions SIReAC Competent
• All functions for Basic
• Calendar function
• Filter alarm
• Simple BMS control - on/off, fan speed and alarm
functions
• Flexible mode - for doors that open and close
frequently
SIReOTX
• SIReB1, integrated PC board Base
• SIReIT, internal temperature sensor
• SIReUB1, control unit. Wall unit cover included.
• SIReCC, modular cable, RJ12(6/6), 5 m
Options:
• SIReRTX, external room temperature sensor
• VOS(P), (pressure independent) valve kit on/off or
VOT, three way valve and actuator on/off
Included in SIReAC Competent:
• SIReB1, integrated PC board Base
• SIReIT, internal temperature sensor
• SIReUA1, control unit. Wall unit cover included.
• SIReDC, door contact
• SIReCC, modular cables, RJ12(6/6), 3 m resp. 5 m
Options:
• SIReRTX, external room temperature sensor
• SIReUR, kit for recessed installation
• VOS(P), (pressure independent) valve kit on/off or
VOT, three way valve and actuator on/off
Included in SIReAA Advanced:
• SIReB1, integrated PC board Base
• SIReIT, internal temperature sensor
• SIReUA1, control unit. Wall unit cover included.
• SIReA1X, PC board HUB Advanced
• SIReOTX, outdoor temperature sensor
• SIReDC, door contact
• Open mode - for doors that stay open
• SIReCC, modular cables, RJ12(6/6), 3 m resp. 5 m
Options:
Functions SIReAA Advanced
• SIReRTX, external room temperature sensor
• All functions for Competent
• SIReUR, kit for recessed installation
• Eco mode - extra energy-efficient mode
• SIReWTA, clamp-on sensor
• Comfort mode - when comfort is important
• VMO(P), (pressure independent) modulating valve kit
or VMT, three way valve and modulating actuator
• Advanced BMS control
• Proactive regulation – measures outdoor temperatures
for proactive reaction.
Thermozone® AD Corinte
Control system SIRe - options
SIReRTX
SIReUR
SIReCJ6
SIReCJ4
SIReRTX, external room temperature sensor
Used to obtain a better measuring point in the premises
when the control unit is located so that the internal
room temperature sensor does not show a relevant
value. 10 m. cable with modular connector.
SIReCC
SIReCJ4/SIReCJ6, joint piece
Used to join two RJ11(4/4) respectively RJ12(6/6).
SIReCC, modular cables
Modular cables RJ11(4/4) respectively RJ12(6/6).
Available in lengths 3, 5, 10 and 15 m.
SIReUR, kit for recessed installation
Kit for installing SIReUA1 in a recess in a wall. Only
protrudes 11 mm from the wall.
Type
Description
SIReB
Control system SIRe Basic
SIReAC
Control system SIRe Competent
SIReAA
Control system SIRe Advanced
SIReRTX
External room temperature sensor, 10 m
SIReUR
Kit for recessed installation
SIReCJ4
Used to join two RJ11(4/4)
SIReCJ6
Used to join two RJ12 (6/6)
SIReCC603
Modular cable RJ12 3 m
SIReCC605
Modular cable RJ12 5 m
SIReCC610
Modular cable RJ12 10 m
SIReCC615
Modular cable RJ12 15 m
SIReCC403
Modular cable RJ11 3 m
SIReCC405
Modular cable RJ11 5 m
SIReCC410
Modular cable RJ11 10 m
SIReCC415
Modular cable RJ11 15 m
Accessories
ADCEH, extension hood
Extension hood used to cover the space between the
ceiling and the air curtain for a neat finish.
ADCM P/S, joining kit for horizontal mounting
Joining kit that is used when several AD Corinte are put
together to give a neater and more unified installation.
ADCMP for suspended installation and ADCMS for wall
installation.
Type
Description
ADCEH
Extension hood
ADCMP
Joining kit for suspended installation
ADCMS
Joining kit for wall installation
ADCEH
ADCM P/S
Thermozone® AD Corinte
Water control - Choose valve kit
Water heated units that are controlled by SIRe are supplemented with valve kits. It’s easy to choose the right valve
kit. Look at the guide for the level of SIRe chosen - Basic, Competent or Advanced and select the valve kit which
suits the system requirements and characteristics.
SIRe Basic, SIRe Competent
VOS, valve kit on/off
•Complete kit with two way control and
adjustment valve, on/off-actuator, shut-off
valve and bypass.
VOS15LF
•Kvs 0,90
•Max flow at 10 kPa: 0,079 l/s
•DN15
VOS15NF
•Kvs 1,8
•Max flow at 10 kPa: 0,158 l/s
•DN15
VOS20NF
•Kvs 3,4
•Max flow at 10 kPa: 0,299 l/s
•DN20
VOS25NF
•Kvs 7,2
•Max flow at 10 kPa: 0,630 l/s
•DN25
VOSP, pressure independent
valve kit on/off
VOT, three way control valve and
actuator on/off
•Complete kit with two way pressure
independent control and adjustment
valve, on/off-actuator, shut-off valve
and bypass.
•Two way pressure independent control
and adjustment valve ensures that the
flow always is constant.
•Three way control valve VOSP15LF
•Flow range 0,004 - 0,035 l/s
•DN15
VOSP15NF
•Flow range 0,021 - 0,088 l/s
•DN15
VOSP20NF
•Flow range 0,035 - 0,175 l/s
•DN20
VOSP25NF
•Flow range 0,071 - 0,353 l/s
•DN25
VOT15
•Kvs 1,7
•DN15
VOT20
•Kvs 2,5
•DN20
VOT25
•Kvs 4,5
•DN25
SIRe Advanced
VMO, modulating valve kit
•Complete kit with two way control and
adjustment valve, modulating (stepless)
actuator and shut-off valve.
VMO15LF
•Kvs 0,40
•Max flow at 10 kPa: 0,035 l/s
•DN15
VMO15NF
•Kvs 1,0
•Max flow at 10 kPa: 0,088 l/s
•DN15
VMO20NF
•Kvs 2,1
•Max flow at 10 kPa: 0,185 l/s
•DN20
VMO25NF
•Kvs 4,0
•Max flow at 10 kPa: 0,352 l/s
•DN25
VMOP, pressure independent and
modulating valve kit
VMT, three way control valve and
modulating actuator
•Complete kit with two way pressure
independent control and adjustment valve,
modulating (stepless) actuator and shut-off
valve.
•Two way pressure independent control
and adjustment valve ensures that the flow
always is constant.
•Three way control valve VMOP15LF
•Flow range 0,004 - 0,035 l/s
•DN15
VMOP15NF
•Flow range 0,021 - 0,088 l/s
•DN15
VMOP20NF
•Flow range 0,035 - 0,175 l/s
•DN20
VMOP25NF
•Flow range 0,071 - 0,353 l/s
•DN25
VMT15
•Kvs 1,7
•DN15
VMT20
•Kvs 2,5
•DN20
VMT25
•Kvs 4,5
•DN25
Thermozone® AD Corinte
VAT
Water control
VOS
VOSP
VMO
VOT
VMOP
VMT
VOS, valve kit on/off
Two way combined control and adjustment valve with
on/off actuator, shut-off valve and bypass. DN15/20/25.
230V. Used with SIRe Basic and Competent.
VMO, modulating valve kit
Two way combined control and adjustment valve with
modulating actuator and shut-off valve. DN15/20/25.
24V. Used with SIRe Advanced.
VOSP, pressure independent valve kit on/off
Two way pressure independent control and adjustment
valve with on/off actuator, shut-off valve and bypass.
DN15/20/25. 230V. Used with SIRe Basic and
Competent.
VMOP, pressure independent and modulating valve
kit
Two way pressure independent control and adjustment
valve with modulating actuator and shut-off valve.
DN15/20/25. 24V. Used with SIRe Advanced.
VOT, three way control valve and actuator on/off
DN15/20/25. 230V. Used with SIRe Basic and
Competent.
VMT, three way control valve and modulating
actuator
DN15/20/25. 24V. Used with SIRe Advanced.
VAT, adjustment tool for valve kit VOS, VOSP, VMO,
VMOP
With the adjustment tool the water flow can be
accurately and easily set.
For further information and options regarding our water
controls, see section on thermostats and controls or
contact Frico.
Type
Description
Flow
Voltage
[V]
Connection
VOS15LF
Valve kit on/off
Low flow
230 V
DN15
VOS15NF
Valve kit on/off
Normal flow
230 V
DN15
VOS20
Valve kit on/off
Normal flow
230 V
DN20
VOS25
Valve kit on/off
Normal flow
230 V
DN25
VOSP15LF
Pressure independent valve kit
Low flow
230 V
DN15
VOSP15NF
Pressure independent valve kit
Normal flow
230 V
DN15
VOSP20
Pressure independent valve kit
Normal flow
230 V
DN20
VOSP25
Pressure independent valve kit
Normal flow
230 V
DN25
VMO15LF
Modulating valve kit
Low flow
24 V
DN15
VMO15NF
Modulating valve kit
Normal flow
24 V
DN15
VMO20
Modulating valve kit
Normal flow
24 V
DN20
VMO25
Modulating valve kit
Normal flow
24 V
DN25
VMOP15LF
Pressure independent and modulating valve kit
Low flow
24 V
DN15
VMOP15NF
Pressure independent and modulating valve kit
Normal flow
24 V
DN15
VMOP20
Pressure independent and modulating valve kit
Normal flow
24 V
DN20
VMOP25
Pressure independent and modulating valve kit
Normal flow
24 V
DN25
VOT15
Three way valve and actuator on/off
Normal flow
230 V
DN15
VOT20
Three way valve and actuator on/off
Normal flow
230 V
DN20
VOT25
Three way valve and actuator on/off
Normal flow
230 V
DN25
VMT15
Three way valve and modulating actuator
Normal flow
24 V
DN15
VMT20
Three way valve and modulating actuator
Normal flow
24 V
DN20
VMT25
Three way valve and modulating actuator
Normal flow
24 V
DN25
VAT
Adjustment tool for valve kitVOS, VOSP, VMO, VMOP
Thermozone® AD Corinte
Output charts water
AD Corinte WL
(standard coil)
Incoming / outgoing water temperature 80/60 °C
Incoming air temp. = +15 °C
Type
Fan
position
ADCS17WL
max
min
ADCS22WL
ADCS25WL
Airflow
Output
[m3/h]
3000
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
33,5
47
0,40
30,3
49
0,36
20,1
57
0,24
18,2
58
0,21
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
45,9
48
0,54
41,5
50
0,49
min
1800
26,7
58
0,31
24,2
59
0,28
max
4500
52,0
49
0,62
47,2
50
0,56
min
2050
30,5
58
0,36
27,8
59
0,33
Incoming / outgoing water temperature 60/50 °C
Incoming air temp. = +15 °C
Type
ADCS17WL
ADCS22WL
ADCS25WL
Fan
position
Airflow
Output
[m3/h]
max
3000
min
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
24,5
39
0,58
21,3
41
0,50
14,6
45
0,34
12,7
46
0,30
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
33,4
39
0,79
29,1
41
0,69
min
1800
19,3
46
0,46
16,9
47
0,40
max
4500
37,9
40
0,90
33,1
41
0,78
min
2050
22,0
46
0,52
19,3
47
0,46
Incoming / outgoing water temperature 60/40 °C
Incoming air temp. = +15 °C
Airflow
Output
[m3/h]
3000
[kW]
20,2
Incoming air temp. = +20 °C
Type
Fan
position
ADCS17WL
max
min
1400
12,3
41
0,14
10,4
42
0,12
ADCS22WL
max
4000
28,1
35
0,33
23,6
37
0,28
min
1800
16,6
41
0,19
14,1
43
0,16
ADCS25WL
max
4500
32,0
36
0,38
27,0
37
0,32
min
2050
19,1
42
0,22
16,2
43
0,19
Outgoing
air temp.
[°C]
34
Water
flow
[l/s]
0,24
Output
[kW]
16,9
Outgoing
air temp.
[°C]
36
Water
flow
[l/s]
0,20
Incoming / outgoing water temperature 60/30 °C
Incoming air temp. = +15 °C
Type
ADCS17WL
ADCS22WL
ADCS25WL
Fan
position
Airflow
Output
Incoming air temp. = +20 °C
[m3/h]
[kW]
Outgoing
air temp.
[°C]
max
3000
15,1
29
0,12
11,5
31
0,09
min
1400
9,6
35
0,07
7,4
35
0,05
Water
flow
[l/s]
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
21,6
31
0,17
16,7
32
0,13
min
1800
13,3
36
0,10
10,4
37
0,08
max
4500
24,9
31
0,19
19,3
32
0,15
min
2050
15,3
37
0,12
12,1
37
0,09
Thermozone® AD Corinte
Output charts water
AD Corinte WH
Incoming / outgoing water temperature 130/70 °C
Incoming air temp. = +15 °C
Type
Fan
position
ADCS17WH
max
min
ADCS22WH
ADCS25WH
Airflow
Output
[m3/h]
3000
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
33,1
47
0,13
30,8
50
0,12
21,5
60
0,08
20,1
62
0,07
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
45,7
48
0,18
42,7
51
0,16
min
1800
29,0
62
0,11
27,1
64
0,10
max
4500
52,1
49
0,20
48,6
51
0,19
min
2050
33,2
62
0,13
31,0
64
0,12
Incoming / outgoing water temperature 110/80 °C
Incoming air temp. = +15 °C
Type
Fan
position
ADCS17WH
max
min
ADCS22WH
ADCS25WH
Airflow
Output
[m3/h]
3000
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
33,0
47
0,26
30,7
50
0,24
21,0
59
0,16
19,7
61
0,15
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
45,0
48
0,35
42,0
51
0,33
min
1800
28,0
61
0,22
26,3
63
0,20
max
4500
51,0
48
0,40
47,7
51
0,38
min
2050
32,0
61
0,25
30,0
63
0,23
Incoming / outgoing water temperature 90/70 °C
Incoming air temp. = +15 °C
Type
Fan
position
ADCS17WH
max
min
ADCS22WH
ADCS25WH
Airflow
Output
[m3/h]
3000
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
26,8
41
0,32
24,7
44
0,29
17,1
51
0,20
15,7
53
0,18
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
36,6
42
0,43
33,7
44
0,40
min
1800
22,8
52
0,27
21,0
54
0,25
max
4500
41,5
42
0,49
38,2
45
0,45
min
2050
26,0
52
0,31
24,0
54
0,28
Incoming / outgoing water temperature 80/60 °C
Incoming air temp. = +15 °C
Type
Fan
position
ADCS17WH
max
min
ADCS22WH
ADCS25WH
Airflow
Output
[m3/h]
3000
1400
Incoming air temp. = +20 °C
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
22,4
37
0,26
20,2
40
0,24
14,3
45
0,17
13,0
47
0,15
Output
[kW]
Outgoing
air temp.
[°C]
Water
flow
[l/s]
max
4000
30,7
37
0,36
27,7
40
0,33
min
1800
19,1
46
0,22
17,3
48
0,20
max
4500
34,8
37
0,41
31,5
40
0,37
min
2050
21,8
46
0,26
19,8
48
0,23
Thermozone® AD Corinte
Wiring diagrams AD Corinte A
Control options for units without heat
SIReB Basic
SIReB1
SIReUB1
SIReB Basic - Parallel connection
SIReB1
SIReB1
SIReUB1
Thermozone® AD Corinte
Wiring diagrams AD Corinte A
Control options for units without heat
SIReAC Competent
SIReC1X
SIReB1
C2
Pot.
X5
Unit ID
C1
X4
COM 1
ROOM
X3
ROOM
COM 2
N L PE PE N L
7 8 9 10
1112
15 161718
SIReDC
19 20
SIReUA1
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
SIReAC Competent - Parallel connection
SIReB1
Pot.
Unit ID
Pot.
Unit ID
SIReB1
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
ACTUATOR SUPPLY
SIReC1X
N L PE PE N L
COM 1
COM 2
ROOM
BUS
7 8 9 10
1112
15 161718
SIReUA1
19 20
SIReB1
SIReDC
N L PE PE N
SIReB1
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
ACTUATOR SUPPLY
N L PE PE N L
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
ACTUATOR SUPPLY
EXTERNAL ON/OFF, 5-30V AC/DC
ROOM
X3
EXTERNAL RPM 0-10V DC IN
C1
X4
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
Pot.
Unit ID
C2
X5
Thermozone® AD Corinte
Wiring diagrams AD Corinte E
Control options for electrically heated units
SIReB Basic
SIReB1
SIReRTX
(optional)
230V~
X5
C2
X4
C1
SIReUB1
PE N L
SUPPLY 230V
ACTUATOR
230V
X3
ROOM
SIReB Basic - Parallel connection
SIReB1
SIReB1
230V~
230V~
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReRTX
(optional)
SIReUB1
Thermozone® AD Corinte
Wiring diagrams AD Corinte E
Control options for electrically heated units
SIReAC Competent
PE N L
SUPPLY 230V
ACTUATOR
230V
X3
ROOM
X4
C1
X5
C2
SIReRTX
(optional)
SIReC1X
SIReB1
C2
Pot.
Unit ID X5
C1
X4
COM 1
ROOM
X3
ROOM
COM 2
230V~
N L PE PE N L
1112
7 8 9 10
15 161718
SIReDC
19 20
SIReUA1
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
SIReAC Competent - Parallel connection
SIReB1
Pot.
Unit ID
X5
C2
X4
C1
X3
ROOM
Pot.
Unit ID
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReRTX
SIReB1
230V~
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
SIReC1X
ACTUATOR SUPPLY
N L PE PE N L
COM 1
COM 2
ROOM
BUS
7 8 9 10
1112
15 161718
SIReUA1
19 20
SIReB1
SIReDC
230V~
N L PE PE N L
SIReB1
230V~
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
ACTUATOR SUPPLY
N L PE PE N L
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
ACTUATOR SUPPLY
EXTERNAL ON/OFF, 5-30V AC/DC
ROOM
X3
EXTERNAL RPM 0-10V DC IN
C1
X4
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
Pot.
Unit ID
C2
X5
Thermozone® AD Corinte
Wiring diagrams AD Corinte E
Control options for electrically heated units
SIReAA Advanced
230V~
N L PE PE N L
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL RPM 0-10V DC IN
EXTERNAL HEAT 0-10V DC IN
230V~
EXTERNAL ALARM IN
(potential free contact)
N L PE PE N L
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
ACTUATOR SUPPLY
HEAT INDICATION
0-10V DC out (max 5 mA)
SIReB1
RPM INDICATION
0-10V DC out (max 5 mA)
N L PE PE N L
21 22
19 20
111213 1415 161718
1 2 3 4 5 6 7 8 9 10
SIReB1
ROOM
BUS
COM 2
COM 1
N L PE PE N L
21 22
19 20
111213 1415 161718
1 2 3 4 5 6 7 8 9 10
ROOM
BUS
COM 2
COM 1
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
ACTUATOR SUPPLY
HEAT INDICATION
0-10V DC out (max 5 mA)
RPM INDICATION
0-10V DC out (max 5 mA)
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
SIReA1X
ACTUATOR SUPPLY
ACTUATOR SUPPLY
SIReOTX
SIReDC
SIReOTX
SIReDC
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
SIReA1X
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
PE N L
SUPPLY 230V
ACTUATOR
230V
X3
ROOM
X4
C1
X5
C2
Pot.
Unit ID
Pot.
Unit ID
SIReRTX
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
ACTUATOR
230V
X3
ROOM
X4
C1
X5
C2
SIReUA1
SIReB1
SIReAA Advanced - Parallel connection
SIReB1
SIReB1
SIReUA1
230V~
SIReRTX
230V~
Thermozone® AD Corinte
Wiring diagrams AD Corinte W
Control options for water heated units
SIReB Basic
SIReB1
SIReSD230
X4
C1
X5
C2
X3
ROOM
SIReRTX
(optional)
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReUB1
C
SIReB Basic - Parallel connection
SIReB1
SIReSD230
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReB1
SIReSD230
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReB1
SIReSD230
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReRTX
(optional)
SIReUB1
Thermozone® AD Corinte
Wiring diagrams AD Corinte W
Control options for water heated units
SIReAC Competent
X5
C2
X4
C1
PE N L
SUPPLY 230V
ACTUATOR
230V
X3
ROOM
SIReRTX
(optional)
SIReC1X
SIReB1
C2
Pot.
X5
Unit ID
SIReSD230
ROOM
X3
C1
X4
PE N
N L L
~
COM 1
ROOM
COM 2
L
7 8 9 10
1112
+ -
SIReDC
19 20
15 161718
SIReUA1
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF
5-30V AC/DC
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
SIReAC Competent - Parallel connection
X5
C2
X4
C1
X3
ROOM
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReB1
C2
Pot.
X5
Unit ID
SIReSD230
C1
X4
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
~
SIReB1
C2
Pot.
X5
Unit ID
SIReSD230
C1
X4
SIReRTX
(optional)
ROOM
X3
ACTUATOR SUPPLY
SIReC1X
N L L PE N L
~
COM 1
ROOM
COM 2
7 8 9 10
SIReB1
15 161718
19 20
SIReSD230
ALARM OUT (BMS)
(potential free contact,max 3A, 230V)
~
DOOR CONTACT
(potential free contact)
N L L PE N L
EXTERNAL ON/OFF, 5-30V AC/DC
ACTUATOR SUPPLY
EXTERNAL RPM 0-10V DC IN
ROOM
X3
EXTERNAL ALARM IN
(potential free contact)
C1
X4
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
C2
Pot.
X5
Unit ID
1112
SIReUA1
Thermozone® AD Corinte
Wiring diagrams AD Corinte W
Control options for water heated units
SIReAA Advanced
X3
ROOM
X4
C1
X5
C2
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReUA1
SIReB1
C2
Pot.
X5
Unit ID
ROOM
X3
C1
X4
SIReRTX
SIReWTA
ACTUATOR SUPPLY
N L L PE N L
SIReA1X
~
COM 1
COM 2
ROOM
BUS
1 2 3 4 5 6 7 8 9 10
19 20
111213 1415 161718
21 22
Blue
White
SIReDC
SIReST23024
SIReOTX
SIReSDM24
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
RPM INDICATION
0-10V DC out (max 5 mA)
Blue
White
Red
Black
SIReAA Advanced - Parallel connection
SIReUA1
X5
C2
X3
ROOM
X4
C1
PE N L
SUPPLY 230V
ACTUATOR
230V
SIReST23024
SIReB1
C1
X4
SIReRTX
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
~
24V
Blue
White
Red
Black
C2
Pot.
X5
Unit ID
SIReSDM24
Red
Black
COM 1
SIReST23024
SIReB1
SIReA1X
SIReSDM24
COM 2
BUS
1 2 3 4 5 6 7 8 9 10
ROOM
111213 1415 161718
19 20
21 22
Blue
White
C1
X4
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
~
24V
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
24V
EXTERNAL HEAT 0-10V DC IN
SIReWTA
~
EXTERNAL RPM 0-10V DC IN
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
C1
X4
Blue
White
Red
Black
C2
Pot.
X5
Unit ID
SIReSDM24
RPM INDICATION
0-10V DC out (max 5 mA)
Red
Black
SIReST23024
SIReB1
SIReDC
Blue
White
Red
Black
C2
Pot.
X5
Unit ID
SIReOTX
Red
Black