ASWL2 DC ALARM BEFORE USE .... MODEL

ASWL2 DC ALARM BEFORE USE .... MODEL
ASWL2
INSTRUCTION MANUAL
DC ALARM
MODEL
(rotary switch adjustment)
56
7 89
34
56
X1
Input Resistor
789
34
x10
HI SET.
(%)
56
34
56
X1
7 89
34
x10
LO SET.
(%)
7 89
0
12
n ENVIRONMENT
•Indoor use.
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +60°C (23
to 140°F) with relative humidity within 30 – 90% RH in order
to ensure adequate life span and operation.
Specification
Label
0
n GENERAL
• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
Base Socket
0
■ POWER INPUT RATINGS
• Operational range & power consumption: Check the power
rating for the unit on the specification label.
AC rating: Rating ±10%, 50/60 ±2 Hz, approx. 2VA
DC rating: Rating ±10%, approx. 2W
Body
0
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for Pollution Degree 2 and Installation Category II.
The relay output circuit is suitable for use in Pollution Degree
2 environment in Over Voltage Category II with the maximum
operating voltage 150V, in Over Voltage Category I with 240V.
Reinforced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V) are
maintained. Prior to installation, check that the insulation
class of this unit satisfies the system requirements.
• The equipment must be mounted inside a suitable fire enclosure.
•Altitude up to 2000 meters
•The equipment must be installed such that appropriate clearance and creepage distances are maintained to conform to CE
requirements. Failure to observe these requirements may
invalidate the CE conformance.
COMPONENT IDENTIFICATION
12
POINTS OF CAUTION
n AND ....
• The unit is designed to function as soon as power is supplied,
however, a warm up for 10 minutes is required for satisfying
complete performance described in the data sheet.
12
Thank you for choosing M-System. Before use, check the package
you received as below.
If you have any problems or questions with the product, please
contact M-System's Sales Office or representatives.
n PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor).....(1)
Input resistor is provided only with current input type.
n MODEL NO.
Check that model No. described on specification label is exactly
what you ordered.
n INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic maintenance
procedures.
n WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
12
BEFORE USE ....
ASWL2
INSTALLATION
Detach the yellow clamps located at the top and bottom of the
unit for separating the body from the base socket.
n DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at
the rear side of
base socket on the DIN rail and
push in the lower. When removing the socket, push down the
DIN rail
adaptor utilizing a screwdriver
(–) and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
n WALL MOUNTING
Shape and size of the base socket
Refer to “EXTERNAL DIMEN- are slightly different with various
SIONS.”
socket types.
EM-1619 Rev.2
P. 1 / 3
ASWL2
FRONT PANEL CONFIGURATION
• Explanations
Hi and Lo setpoint rotary switches are used to set the alarm setpoints.
The Hi and Lo LED lights turn on when the coil for each relay is energized.
1 Hi LED
2 Hi Setpoint Rotary Switch (x10%)
x10
HI SET
[%]
x1
• Examples
For setting the relay to trip above 80% of the full-scale input signal, set the Hi
rotary switch (x10) to "8", while the switch (x1) to "0".
3 Hi Setpoint Rotary Switch (x1%)
4 Lo Setpoint Rotary Switch (x10%)
x10
LO SET
[%]
x1
5 Lo Setpoint Rotary Switch (x1%)
6 Lo LED
TERMINAL CONNECTIONS
CHECKING
Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.
When an input resistor is provided with the module, attach it
together with input wiring to the input screw terminals.
1) Terminal wiring: Check that all cables are correctly connected
according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
– 14 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of the
full scale.
4) Alarm operations: Check the alarm operations referring to
the figure below.
5) Output load: Check that the output load is 380V AC/120VA or
125V DC/30W at the maximum (≤0.5A). For maximum relay
life with inductive load, external protection is recommended.
2 N.C.
+
INPUT
–
R
*
4
12
11 N.O.
HI OUTPUT
1 COM
10 N.C.
15 N.O.
LO OUTPUT
Alarm Trip Operation Terminal No. in parentheses
9 COM
14 V(–)
(1–11)ON
Hi Output
7 U(+)
(1–2)ON
POWER
(9–15)ON
Lo Output
Input shunt resistor attached for current input.
*
Input
(%)
(9–10)ON
0
50
Lo Setpoint
100
Hi Setpoint
Trip Operation in Power Failure
: Terminals 1 – 2, 9 – 10 turn ON.
MAINTENANCE
Regular calibration procedure is explained below:
n CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the setpoint and
check that the trip point remains within the accuracy described
in the data sheet.
• Lo Setpoint
Decrease the input signal from a value higher than the setpoint and
check that the trip point remains within the accuracy described
in the data sheet.
When the trip points are out of tolerance, contact M-System's Sales
Office or local representatives.
EM-1619 Rev.2
P. 2 / 3
ASWL2
EXTERNAL DIMENSIONS unit: mm (inch)
INPUT RESISTOR
(model: REM)
12 (.47)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
DIN RAIL
35mm wide
7 14 6
5 12 4
50 (1.97)
72 (2.83)
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
14–M3.5
SCREW
103 (4.06)
132 (5.20)
[3.3 (.13)]
80 (3.15)
80 (3.15)
35.4 (1.39)
3
8
9 15 10
1 11 2
60 (2.36)
72 (2.83)
•When mounting, no extra space is needed between units.
•Input shunt resistor attached for current input.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
EM-1619 Rev.2
P. 3 / 3
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement