ENTES MPR-53CS-DIN Network Analyzer User Manual
Below you will find brief information for Network Analyzer MPR-53CS. This device measures electrical parameters and provides protection for your electrical system. You can set multiple parameters for alarms, configure energy counter, and setpoint for protection. It also has a user-friendly interface for monitoring and setting parameters. There are two energy counters, two pulse counters, two energy and two relay outputs and two digital inputs. The device is panel mounted and has an RS485 interface for communication with other devices.
Advertisement
Advertisement
NETWORK ANALYSER
MPR-53CS
Technical Data
Operating Voltage (Un)
Measuring Range
: Please look behind the device.
Operating Frequency (f)
Auxiliary supply Power Consumption
: 45-65 Hz
: < 4 VA
Measuring Input Power Consumption : < 1 VA
VIn : 10-300 V AC 45-65 Hz. (L-N)
: 10-500 V AC 45-65 Hz. (L-L)
IIn : 0.05 - 5.5 A~
1-120 A~ (for CT-25)
: 10V...200 kV AC
: 0...215 M (W,VAr,VA)
: 99999999999.9 kWh, kVArh
Class
Voltage Transformer ratio (Vtr)
Current Transformer Ratio (Ctr)
Max. Ctr x Vtr
Hour SP
Demand Time
Serial Interface
Baud Rate
Address
Parity
Relay Output
Pulse Output
Switch Period
Operatimg Current
Operating Voltage
Input
Ambient Temperature
Display
Dimensions
Equipment Protection Class
Box Protection Class
Box Material
Installation
Wire Crossection For Terminal Block
Weight
Installation Class
Panel Size
: 1% ± 1 digit [(10%-110%) xFull Scale]
: 0,1 ... 4000,0
: 1 ... 2000
: 40.000
: 1-9999 hour (programmable)
: 1-60 min. (programmable)
: MODBUS RTU (RS 485)
Optically Isolated, programmable
: 2400-38400 bps
: 1-247
: No, Odd, Even, 8 Data Bits, 2 Stop Bits
: 2 NO, 5 A, 1250 VA
: NPN Transistör
: Min. 100 msec. pulse period
80 msec. pulse width
: Max. 50 mA
: 5.....24 V DC, max. 30 VDC
: 12...48 V AC / DC
: -5°C; +50°C
: Red LED Display
: PR-19, PK-26
: Double Installation-Class II ( )
: IP 40 (front panel)
: Non-flammable
: Panel Mounted (PR-19)
Rail Mounted (PK-26)
: 2.5 mm
2
: 0.45 kg (PR-19, PK-26)
: Class III
: 91x91 mm (PR-19)
46x107 mm (PK-26)
Factory Settings
Transformer : Eng Cnt :
Dimensions
10.8
96mm
Type PR 19 (96x96)
PULSE Cnt :
30.1
26.5
21.5
53.0
58.0
Panel Cut-out
7.6
91mm
9.5
10.0
Type PR 19 (96x96)
Wall
79.3mm
70mm
60.6
106.0
Type PK 26
50mm
79.3mm
70mm
Tip 19
Ctr (Current Transformer Ratio) : 0001 trn (Turn number for CT-25): 01
Utr (Voltage Transformer Ratio) : 0001.0
CAL (Calculation Method) : 1
E-1 (Energy Counter 1) : on
E-2 (Energy Counter 2) : on
PULSE :
C-1 ACt (Pals Counter 1) : on
C-2 ACt (Pals Counter 2) : on
C-1 rAt ýo (Ratio) : 0001
C-2 rAt ýo (Ratio) : 0001
Pin : 0000 (Not activated) rAt ýo (Ratio) : 1k o-1 (output 1) : A-I o-2 (output 2) : r-L
RS-485 :
Adr (Address) : 1
Bau (Baud Rate) : 9600
PAr (Parity) : no
dEtý (Delay Time) : 15 hoU r : hoU r SP (Setpoint) : 0000
ACt : on out : 1
PRECAUTIONS FOR INSTALLATION AND SAFE USE
In CT-25 (120A) compliant models, only CT-25 current transformer must be used.
Other type of CTs have a high risk to damage to device.
LAT Ch : bUt ton : on
ýn PUT : oFF
AUT o : oFF
Set point :
SP -01....-16 ACt : oFF
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment..
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like. Only clean with dry cloth.
- Control the connections.
- Electrical equipment should be serviced only by your component seller.
- Device is only for rack panel mounting.
- The type of the circuit breaker must be F and current limit value must be 1 A.
- No responsibility is taken on by manufacturer or any of its subsidiaries for any conditions about the wrong using of this device.
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
8
A4396/Rev.2
NETWORK ANALYSER
MPR-53CS
General
MPR-53CS measures all the electrical parameters that belong to network.
MPR-53CS is designed for protection of electrical system. Measured parameters are shown in 5 separate displays. This allows to monitor more than 50 parameters at the same time. MPR-53CS has also MODBUS serial interface feature.
The table below shows the parameters that are measured by MPR-53CS:
V
V
LN
LL
(Phase Voltage )
(Phase to Phase Voltage)
Cosj
AI ( kWh) (Import Active Energy I)
Hz. (Frequency)
SW (Total Active Power)
A (Phase Current, Neutral Current) AE (kWh) (Export Active Energy)
W (Active Power)
SVAr (Total Reactive Power) rI (kVArh) (Import Reactive Energy) SVA (Total Apparent Power)
VAr (Reactive Power) rE(kVArh) (Export Reactive Energy) C (Digital Input Pulse Counter)
VA (Apparent Power) THD (Total Harmonic Distortion) h (Run Hours)
Digital Input LEDs
Pulse Output LEDs
Digital Output LEDs
Relay Outputs LEDs
UP button
DOWN button
Max. LED
SET button
Min. LED
Demand LED
Phase
Displays
SW, SVA and
Hz Display
SVAr and
Cosj Display
Back button
ESC button
Phase Displays
UP button
DOWN button
Max. LED
SET button
Min. LED
SW, SVA and
Hz Display
SVAr and
Cosj Display
Back button
ESC button
Demand LED
Functions of Buttons
Used for switching between (V
LN
, V
LL
, A, W, VAr, VA, Cosj, kWh, kVarh, THD, C-1, C-2, tot-h, run-h) parameters in the monitoring mode.
Used for switching between previous ( ) or next ( ) menu in main menu or submenus and also use for changing chosen values.
(SET) Used for switching between min., max demand and instant values in the monitoring mode. In display when run hour (run -h) is displayed, if SET button is pressed, it shows setpoint hours
(SP -h) counted time. In latch function when button feature is used, with SET button latch position operation is done. Switching to the programming mode if it pressed for 3 sec. It is used for switching to the menu and saving changes for the parameters in programming mode.
(Back) Used for switching between SW, SVA and Hz parameters in the monitoring mode. Used for switching previous digit in submenu.
(ESC) Used for switching between SVAr and Cosj values in the monitoring mode. Used for entering to upper menu or it is used to quit from the programming mode without saving values in the programming mode.
When Pin is activated, after pressed SET button for 3 seconds,
PIN is required; after entering correct PIN code, you can enter to menu.
Use of MPR-53CS:
By using Up/Down buttons parameters are shown in L1, L2, L3 displays (V
LN
;
V
LL
; A; I
N
; W; VAr; VA; Cosj; kWh, kVarh, THD, C-1, C-2, tot-h, run-h). Total
Active (SW), Total Apparent Power (SVA) and Frequency (Hz) are selected by Back button.
Total Reactive Power (SVAr) and Cosj are selected by Esc button.
Digital Inputs
MPR-53CS has 2 digital inputs. Digital inputs have 2 functions :
- If remote control is activated (battery, thermostat, circuit breaker, engines status) the status of devices connected to digital input will be seen according to datas in time regiters.
- When digital inputs of energy count, run hour and latch menus are selected, digital inputs controls these menus functions ( Example: It is used for measuring of energy separately at the using of network and generator).
I1 (digital input 1) and I2 (digital input 2) lights on the front panel are off when there arent any signal in digital inputs. Otherwise on.
Energy Pulse Outputs
MPR-53CS has 2 energy pulse outputs. Pulse outputs give the pulses only for
E-1 (energy counter). Pulse outputs can be programmed one by one. When pulse outputs give pulse P1 (Pulse 1) and P2 (Pulse 2) lights (Not included in the PK-26 box) are onand until the next pulse output, it stays off.
Pul1 ve Pul2 : There are sub menus o-1 (pulse 1) and o-2 (pulse 2) in pulse out menu. Device gives pulse according to chosen energy parameters [Active energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. For energy count values, look at the pulse menu.
Pulse Counter
MPR-53CS has 2 pulse counters (C-1, C-2). C-1 counts the pulses from digital input 1 and C-2 counts the pulses from digital input 2.
Pulse counter detect the pulses which are in condition of signal 1. When the number of pulses reach pulse C1/2 ratio value, releated pulse counter is increase by 1. When C-1/C-2 counters are not activated in pulse counter menu, instant values of C-1/C-2 are not displayed.
Note: DC signals must be use supplied in order to use this menu.
1
Digital Outputs
MPR-53CS has 6 digital outputs. Only 2 of them have LED on the front panel.
These are O-3 and O-4 LEDs (O-4 light is not available in the PK-26 box).
When digital outputs are activated, related addresses can be displayed with
xxx values, only O-3 and O-4 LEDs are lighted for digital outputs 1 and
2 on front panel. Digital output on devices menus output parameters;
1/2/3/4/5/6 correspond to 3/4/5/6/7/8 parameters.
User can check the digital output register for fault about set parameters by communicating with the device.
Relay Outputs
MPR-53CS has 2 NO contact outputs. On front panel, MPR-53CS has o-1 and o-2 LEDs. When alarm parameters are selected 1 (out 1) and 2
(out 2) for output, device gives alarm. Related contact outputs will close and
LEDs will be on.
Total Hours
Shows running time of MPR-53CS from the beginning. User can not reset this counter.
Run Hours
Shows MPR-53CSs running hour. This can be resetted and can be controlled by digital inputs different from Total Hour. When selected the control with digital inputs, it runs if there is a signal in digital inputs. It does not run if there is no signal in digital inputs.
Setpoint Hours
By pressing SET button during monitoring of Run Hour, set point hour can be monitored. Setpoint hour runs according to run hour. When run hour runs actively, setpoint hour runs. When set time value reaches to hoU r SP which set by user, selected output will be active (1) and give an alarm and setpoint hour continues to count. This alarm can be erased by resetting setpoint hour or getting out from locked position. When setpoint output is required to remove by using latch function, latch auto function cant be used. If MPR-53CS returned to normal operation from failure by using latch function, it automatically starts the time from zero. To make setpoint hour passive, the value of SP hour is set 0000. This setting only closes the setpoint output, doesnt effect the counting of the setpoint hour.
Note: Total hour and run hour do not count during electric interruptions. Total hour and run hour is saved to memory and is not affected by electric interruptions. During measurement mode, by scrolling UP and DOWN buttons, user can see running time. Run hour display is shown is HH HHH H.HH
(H=Hour) form. All the values shown on the display are in terms of hour. For example, if displayed value is 00 000 1.75, means that device worked for 1.75
hours. If the user wants to convert last digit to minutes, last digitx0.6 (75x0.6=45 minutes) formula is used conversion. Device worked 1 hour 45 minutes.
Ýmportant: In hoU r SP menu when chosen output is activated and devices is set for giving an alarm at the end of one hour. After counting to 99 on display, devices gives an alarm (1 hour = 60 min. for MPR-53CS on display
99 corresponds to 59).
Monitoring of Min.- Max. and Max. Demand Values:
Min. and Max. values are defined for; V
LN
, V
LL
, A, W, VAr, VA, SW, SVAr, SVA; demand values are defined for; A, W, VAr, VA, SW, SVA, SVAr.
If measured instant value is smaller than min. value, they are saved as new min. and if measured instant value is bigger than instant max. value, new max. value is saved. During demand time (example 15 min.) demand value is got max. demand.
If press SET button when the device is in any parameter (example A) min., max. or max. demand values are displayed. If SET button is pressed when an undefined parameter (example Cosj) is displayed, the device continues to display instant values because min., max. and max. demand values are undefined for that parameters.
Monitoring THD Values
If V LN and THD LEDs light on together, voltage THD is monitored. And if A and THD LEDs light on, current THD is monitored.
Monitoring Neutral Current
When instant current values of 3 phases are shown on the display, by pressing the DOWN button, I-n (neutral current) is displayed. A LED continues light on. When connection form is chosen as delta, this display will be closed.
Monitoring Setpoint Parameters Fault Warning
Device activates the selected output if there is a failure because of any causes.
User can set more then one parameters to output, so outputs can be monitored depending which parameter and this parameters protection type (low, high, both of them) even in failure situation when rUn -h menu is displayed, pushing DOWN button or when V LN is displayed pushing UP button, failure parameter will be seen as SP -xx h/L/hL x-x x-x. If there is a no failure, you will not see such a display. After pressing SET button you can see other failure parameter.
Calculation Methods for Active / Reactive Values
If the dot on the right down corner blinks it shows that active power and reactive powers directions are negative. There are 2 methods for calculating total active and total reactive powers.
1) Active and reactive powers are calculated by summing import and export values and shown as a single value.
2) Active and reactive powers are calculated one by one according to import/export condition.
Note :
1) During SW LED is displayed, if the dot at the most right down digit of the forth display lights on, it represents that displayed value is export active power value. If not, it represents that displayed value is import active power value.
2) During SVAr LED is displayed, if the dot at the most right down of the fifth display lights on, it represents that displayed value is capacitive reactive power value. If not, it represents that displayed value is inductive reactive power value.
3) The displayed parameter will not change if power is off after 30 seconds of stand by.
NETWORK ANALYSER
MPR-53CS
Current Transformer Ratio Setup:
In this menu current transformer ratio is set (There is no in CT-25 models).
Current transformer ratio can be set between 1 ..... 2000.
Note: If the current transformer is not used between the system and the device, current transformer ratio is entered as 1.
Example: If between the device and the system there is a 30A/5A current transformer is used;
Current transformer ratio = 30/5 = 6 must be setup.
Press SET button for 3 sec. (trA Fo menu is displayed)
Press SET button, trA Fo Ctr menu is displayed (For CT-25 models trA Fo trn menu is displayed).
(Note: trA Fo Utr / Con nEC týo n menu can be displayed by scrolling
UP/DOWN buttons.)
1 2 3 4 5 6 7 8 9 10
Mechanical Energymeter
(Vectoral summation of 3-phase)
Digital Energymeter
(Each phase seperately)
Reactive Energy
(Q)
0 1
11 12 13 14 15
Description
90° rotation of voltage vector and multiply with current
It is the most preferred reactive power calculation methode.
Press SET button for 3 sec. (trA Fo menu is displayed.)
Press SET button (TrA Fo Ctr menu is displayed.)
16 17 18 19 20
1.00
0.50
0.33
0.25
0.20
0.16
0.14
0.12
0.11
0.10
0.09
0.08
0.07
0.07
0.06
0.06
0.06
0.05
0.05
0.05
120 60.0
40.0
30.0
24.0
20.0
17.1
15.0
13.3
12.0
10.9
10.0
9.23
8.57
8.00
7.50
7.05
6.66
6.31
6.00
Voltage Transformer Ratio Setup:
In this menu, voltage transformer ratio setup is set.
Voltage Transformer ratio is set between 0000,1 - 4000,0.
Note: If the voltage transformer is not used between the system and the device. The voltage transformwer ratio is entered as 1.
Example: Between the voltage transformer and the device, if there is a 34,5KV/100V voltage transformer is used;
Voltage transformer ratio = 34500/100 = 345 can be entered.
Chosing connection option:
In this menu connection option is selected. There are 2 option as
delta and star.
When Star connection is chosen, the device makes a protection between phase-neutral for voltage.
When Delta connection is chosen, the device makes a protection between phase-phase for voltage.
NOTE: When Delta is chosen Neutral Current (I N ) and
Phase-Neutral Voltage (V LN ) values can not be shown in instant values. Functions that belong to this parameters are inactive.
Reactive Energy Calculation Method Settings:
Informations about Reactive energy calculation method is explained in below table.
The method of active and reactive energy calculation of mechanic and electrical counters must be chosen from the table.
By using UP/DOWN buttons find
CAL CUL Atý on menu.
Press SET button (Most right digit of 5th display blinks)
By using UP/DOWN buttons select energy calculation method.
Press SET button, CAL CUL Atý on is displayed. (Data is entered but is not activated yet, for activating new data please follow below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button (When
SAU E SEt yES is displayed. If you press ESC button or choose
no option instead of yES option, new data will be cancelled and previous value will be activated).
Max. Demand Time Setup:
In this menu, Max. demand time is set between 01 - 60 minutes.
Press SET button. Blinking the first digit of displayed value appears.
(trA Fo Utr or Con nEC týo n menus can be programmed similarly.)
Using the UP/DOWN buttons and program the blinking digit. Switch to other digits by using SET button, use BACK button to go topevious digit. After programming last digit press SET button, trA Fo Ctr is displayed. (Data is entered but is not activated yet. For activating new data please follow the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed on display.
When SAU E SEt yES is displayed, press SET button. If you press
ESC button or choose no option instead of yES option by using
UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Entering Turn Number:
This menu is available for CT-25 adapted devices. Turn number is chosen from CT-25 current transformer (How many tour the current cable has rounded). The values between 1 and 20 can be written. Greater the number of turn means greater the sensivity.
2
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons find de tý menu.
Press SET button (Most right digit of 5th display blinks)
By using UP/DOWN buttons, blinking digit value can be programmed. By using SET button, switch respectively to the digits.
Use BACK button go to go previous digit. After you entered last digit, press SET button, de tý is displayed in the display. (Data is entered but is not activated yet. For activating new data please follow the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button (When
SAU E SEt yES is displayed. If you press ESC button or choose
no option instead of yES option, new data will be cancelled and previous value will be activated).
Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):
In this menu value of min., max., max. demand, energy values, pulse counters, run hour and alarm clock are erased. It saves the instant measured min., max., max. demand energy values, the devices running time, time after the device is setted into its memory.
In this menu when you enter rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoUr/SP hoU r menu then press yES parameter, then quit from all menus if you confirm the changes all the values are erased at the same time.
Note: Measured values which are saved in memory are not affected from power cut.
Reset Menu (hL, dE, E-1, E-2, C-1, C-2, rUn hoUr, SP hoU r):
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons find rES Et menu.
Press SET button (rES Et hL menu is displayed.)
By using UP/DOWN buttons rES Et hL/dE/E-1/E-2/C-1/C-2/ rUn hoU r/SP hoU r menu.
Press SET button (rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/
SP hoU r is displayed).
By using UP/DOWN buttons, if you want to delete, the min., max., max. demand, energy values, the running time of the device and the running time after the device is set; select yES otherwise select no option.
Press SET button, rES Et hL/dE/E-1/E-2/C-1/C-2/rUn hoU r/SP hoU r is displayed. (Data is entered but is not activated yet. For activating new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button (When
SAU E SEt yES is displayed. If you press ESC button or choose
no option instead of yES option, new data will be cancelled and previous value will be activated).
NETWORK ANALYSER
MPR-53CS
PR 19 Box Connection Diagram
L1
L2
L3
N k
K L l k
K L l k
K L l
1
I
L1
2 3 4
I I L2
Current Measuring Input
5
I I L3
6
13 14 15 16
Out 2 Out 1
Relay Outputs
Pul C
( 12-48V DC )
InC In1 In2
RS485
17 18 19 20 21 22 23 24 25 26
GND B A TR
Pul 2
Pul 1
Voltage Measuring Input
L1 L2 L3 N
Auxiliary
Supply
7 8 9 10 11 12
Max: 30 VDC
_
+
L1
L2
L3
N
3 Phase neutral
L1
L2
L3 k
K L l k
K L l k
K L l
1
I
L1
2 3 4
I I
L2
Current Measuring Input
5
I I L3
6
13 14 15 16
Out 2 Out 1
Relay Outputs
Pul C
( 12-48V DC )
InC In1 In2 RS485
17 18 19 20 21 22 23 24 25 26
GND B A TR
Pul 2
Pul 1
Voltage Measuring Input
L1 L2 L3 N
Auxiliary
Supply
7 8 9 10 11 12
Max: 30 VDC
_
+
L1
L2
L3
N
3 Phase without neutral
Note: For CT-25 models: k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.
7
L1
L2
L3 k
K L l k
K L l
1
I
L1
2 3 4
I
L2
Current Measuring Input
5
I L3
6
13 14 15 16
Out 2 Out 1
Relay Outputs
Pul C
( 12-48V DC )
InC In1 In2
RS485
17 18 19 20 21 22 23 24 25 26
GND B A TR
Pul 2
Pul 1
Voltage Measuring Input
L1 L2 L3 N
Auxiliary
Supply
7 8 9 10 11 12
Max: 30 VDC
_
+
L1
L2
L3
N
3 Phase without neutral current input wþth
Aron wiring configuration
L1
L2
L3 k
K L l k
K L l
1
I
L1
2 3 4
I
L2
Current Measuring Input
5
I
L3
6
13 14 15 16
Out 2 Out 1
Relay Outputs
Pul C
( 12-48V DC )
InC In1 In2 RS485
17 18 19 20 21 22 23 24 25 26
GND B A TR
Pul 2
Pul 1
Voltage Measuring Input
L1
7
L2
8
L3
9
N
10
Auxiliary
Supply
11 12
Max: 30 VDC
_
+
L1
L2
L3
N
3 Phase without neutral current input with
Aron wiring configuration
NETWORK ANALYSER
MPR-53CS
31 DEVICES CAN BE CONNECTED AT THE SAME LINE
MAX. 1200 mt.
RS485/RS232
CONVERTER
B
A
GND
TR B A GND TR B A GND TR B A GND
MPR-53CS-31 MPR-53CS-2 MPR-53CS-1
MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
MAX. 1200 mt.
MAX. 1200 mt.
PC
RS485/RS232
CONVERTER
B
A
GND
PC
TR B A GND
MPR-53CS -247
PK 26 Box Connection Diagram
Max: 30 VDC
REPEATER
(12-48V DC)
- + - +
Gnd A B
RS-485
TR Out1 Out2
Relay Outputs
Auxiliary
Supply
Voltage Measuring Input
L1 L2 L3 N
Current Measuring Input
I
L1
I
L2
I
L3
1A
L1
L2
L3
N
3 Phase neutral
k
K l
L k
K l
L k
K l
L
Max: 30 VDC
MPR-53CS -31 MPR-53CS -2 MPR-53CS -1
Max: 30 VDC
1A
Auxiliary
Supply
Voltage Measuring Input
L1 L2 L3 N
L1
L2
L3 k
K l
L
3 Phase without neutral current input with
Aron wiring configuration
Max: 30 VDC k
K
+
_
N
(12-48V DC)
- + - +
Gnd A B
RS-485
TR Out1 Out2
Relay Outputs
Current Measuring Input
I
L1
I
L2
I
L3 l
L
(12-48V DC)
- + - +
Auxiliary
Supply
Voltage Measuring Input
L1 L2 L3 N
Gnd A B
RS-485
TR Out1 Out2
Relay Outputs
Current Measuring Input
I
L1
I
L2
I
L3
1A
N
L1
L2
L3
3 Phase without neutral
k
K l
L k
K L l k
K l
L
Note: For CT-25 models: k: When CT-25 is used, Red cable is connected to k terminal.
l: When CT-25 is used, Black cable is connected to l terminal.
6
Gnd A B
RS-485
TR Out1 Out2
Relay Outputs
Auxiliary
Supply
Voltage Measuring Input
L1 L2 L3 N
Current Measuring Input
I
L1
I
L2
I
L3
N
1A
L1
L2
L3 k
K l
L
3 Phase without neutral current input with
Aron wiring configuration
k
K l
L
NETWORK ANALYSER
MPR-53CS
Pulse Menu
In this menu, 3 parameter can be selected. PUL oUt rAt ýo,
PUL oUt o-1, PUL oUt o-2.
PUL oUt rAt ýo : In this menu, the pulse ratio of pulse outputs is defined. The values below can be defined.
1, 10, 100 (Wh/VArh); 1, 10, 100 (kWh/kVArh); 1 MWh/MVArh.
PUL oUt o-1 / PUL oUt o-2 : Pulse is taken for respected consumption which assigned in PUL oUt rAt ýo.
o-1/o-2 parameters can be set the below settings;
ACt (Export/Import), A-I (Active Import), A-E (Active Export), rEA (Inductive / Capacitive), r-L (Reactive Inductive), r-C (Reactive Capacitive).
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons, find
PUL SE oUt menu.
Press SET button PUL oUt rAt ýo menu is displayed.
By using UP/DOWN buttons, find PUL oUt rAt ýo/PUL oUt o-1
/PUL oUt o-2 menu.
Press SET button (1k / A-I / r-L blink)
By using UP/DOWN buttons, select required parameter of value.
Press SET button (Data is entered but is not activated yet. For activating the new data please follow the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press ESC button or choose no option instead of yES option by using UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Energy Counter (Eng Cnt) Menu:
MPR-53CS has 2 energy counters:
Energy Counter 1 (E-1), Energy Counter 2 (E-2).
E-1 / E-2 have 4 parameters: on : E-1 / E-2 counters count without depending on any parameters.
ý-1 : It counts when E-1 / E-2 counter is on in digital input 1 (Activate
E-1/E-2 counters, when digital input 1 is on).
ý-2 : It counts when E-1 / E-2 counter is on in digital input 2.
E-2: When E-2 counter is active, E-1 counter do not count. (It is only E-1 counters parameter)
E-1: When E-1 counter is active, E-2 counter do not count. (It is only E-2 counters parameter)
Note: When E-2 is chosen in E-1 counter and when E-1 is chosen in E-2 counter the counting status is undefined. When counters are set with this parameters, if digital inputs hasnt got the information 1 both of the counters count but if one or both of the counters has got the information, both of the counters dont count.
Press SET button for 3 sec. (trA Fo menu is displayed)
By using UP/DOWN buttons, find
Eng Cnt menu.
Press SET button (Eng Cnt E-1 menu is displayed).
By using UP/DOWN buttons, find Eng Cnt E-1 / Eng Cnt E-2 menu.
Press SET button (on blinks)
By using UP/DOWN buttons, select required parameters.
Press SET button. (Data is entered, but is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press ESC button or choose no option instead of yES option by using UP/DOWN buttons, new data will be cancelled and previous value will be activated.
3
User Password Setup :
In this menu user password is defined and activated. You must define and activate a 4 digit user password for preventing device setting from the illegal usage.
There are 2 sub menus under Pýn menu.
Changing of User Password :
This menu is to change the user password.
Note: Factory default value for user password is 0000.
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons, find Pýn menu.
Press SET button (Pýn ACt IUA tE menu is displayed.)
By using UP/DOWN buttons, find
Pýn CHA n9E menu is displayed.
By using UP/DOWN/SET buttons, enter the old password.
By using UP/DOWN/SET buttons, enter the new password.
By using UP/DOWN/SET buttons, re-enter the new password.
Press SET button, Pýn CHA ngE is displayed (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press ESC button or choose no option instead of yES option by using UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Activating User Password :
This menu is used for activating the user password.
After the user password is activated for entering to the instant values are observed, user password is required.
If the user password is entered wrong device does not latch.
Note: Factory default value of user password is 0000
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons, find Pýn menu.
Press SET button
(Pýn ACt IUA tE menu is displayed.)
Press SET button. First digit blinks.
By using UP/DOWN buttons enter the values for blinking digit. By using SET button, switch the other digits. Use BACK button to switch the previous digit. After setting the last digit, press the SET button, Pýn ACt oF is displayed. on can be selected by using
UP/DOWN buttons. (Data is entered but is not activated yet. For activating the new data please follow the below steps.)
Displaylerde (SAU E SEt yES) görününceye kadar ESC tuþuna tek tek basýn.
Displaylerde (SAU E SEt yES) göründüðünde SET tuþuna basýn
(SAU E SEt yES göründüðünde ESC tuþuna basarsanýz veya yES yerine no seçeneðini seçerseniz yeni ayarlar kaydedilmeden ayar menüsünden çýkýlýr. Cihaz önceki ayarlarýyla çalýþmaya devam eder.)
NETWORK ANALYSER
MPR-53CS
Latch menu:
When latch function of set parameters is active, user can choose the way how to fault recovery in this menu. User can make this by
3 ways.
LAt Ch bUt ton: Removal of latch is chosen by pressing the SET button. By chosing oFF, SET button becomes passive.
LAt Ch ýn PUt: Fault recovery can be done with using digital inputs.
When LAt Ch ýn I-1 is chosen only first digital input becomes active.
When LAt Ch ýn I-2 is chosen only second digital input becomes active.
When LAt Ch ýn ALL is chosen both of the digital inputs become active.
User can remove the latch when the signal comes to digital inputs.
When LAt Ch ýn oFF is chosen this feature becomes pasive.
LAt Ch AUto: When this feature is chosen fault recovery occurs at the end of the set time. User can set the turning time below.
User can choose the time between 15 min. - 180 min.. Time can be set by multiples 15 (15, 30, 45, 60, 75, 90, 105, 120,135, 150, 165 or 180 min.).
NOTE: LAt Ch bUt ton, LAt Ch ýn PUt ve LAt Ch AUt o can be activated at the same time.
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons, find LAt CH menu.
Press SET button (LAt Ch bUt ton menu is displayed.)
By using UP/DOWN buttons, from the menus of LAt Ch bUt ton/
ýn PUt/AUt o choose the menu where the setting will be done.
Press SET button (on/oFF/oFF is displayed).
By using UP/DOWN buttons, select related parameter values
(on, oFF/ oFF, I-1, I-2, ALL / oFF, 15 ... 180).
Press SET button, LAt Ch bUt ton/ýn PUt/AUt o is displayed.
(Option is entered but is not activated yet. For activating the new data please follow the below steps.)
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press
ESC button or choose no option instead of yES option by using
UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Pulse Counter (PUL SE CoU ntE r)
PUL C-1 ACt: In this menu, the activation of C-1 counter is done.
If on is chosen C-1 counter will be active, and if oFF is chosen
C-1 counter will become passive.
PUL C-1 rAt ýo: In this menu first pulse counter is increased by 1.
C-2 counters is set same way.
Example : If the ratio of the C-1 counters is 10, every 10 pulses come from In-1 input the counter counts 1.
Note: DC signal has to be given to the digital inputs when this menu is used. When AC signal is given, pulse counter counts according to the given sources frequency.
Note: If ACt oFF is chosen for C-1 and C-2 counters, the pulse counting feature will become passive. In instant values, passive counter is not displayed.
Press SET button for 3 sec. (trA Fo menu is displayed)
By using UP/DOWN buttons, find
PUL SE CoU ntE rmenu
Press SET button (PUL C-1 ACt menu is displayed).
By using UP/DOWN buttons, from the menus of PUL C-1 ACt/
C-1 rAt ýo/C-2 ACt/C-2 rat ýo select the menu.
Press SET button (on/9999/on/9999 is displayed).
By using UP/DOWN buttons and select interested parameter values (on-oFF/0001...9999/on-oFF/0001...9999).
Press SET button, PUL C-1 ACt/C-1 rAt ýo/C-2 ACt/C-2 rat ýo is displayed. (Option is entered but is not activated yet. For activating the new data please follow the below steps.)
Press ESC button one by one, until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press
ESC button or choose no option instead of yES option by using
UP/DOWN buttons, new data will be cancelled and previous value will be activated.
4
Hour menu:
In this menu run hour and setpoint hour is set.
hoU r ACT: In this menu the run hours activation conditions are set.
When hoU r ACT on is chosen, the run hour keeps working unconditionally.
When hoU r ACT ý-1 is chosen, the run hour runs if first digital input is active.
When hoU r ACT ý-2 is chosen, the run hour runs if second digital input is active.
When hoU r ACT ALL is chosen, the run hour runs if one of the digital inputs is active.
hoU r SP : In this menu, alarm time is set. When the set time reaches
SP -h chosen output will be active.
Between 0001 - 9999 the hours can be set.
hoU r oUt : In this menu the alarm output is chosen. It can be chosen between 1 ... 8. First and second outputs are relay outputs 3. ... 8 outputs are digital outputs.
Press SET button for 3 sec. (trA Fo menu is displayed)
By using UP/DOWN buttons find hoU r menu
Press SET button (hoU r SP menu is displayed.)
Press SET button (hoU r SP 000 0 is displayed)
By using UP/DOWN buttons, enter the values for blinking digits.
By using SET button, other digits in turn, by using BACK button for previous menu. When last digit is programmed press SET button,
hoU r SP is displayed.
By using UP/DOWN buttons from the menus of hoU r ACT/oUt select the menu.
Press SET button (on/1 displayed).
By using UP/DOWN buttons set the related parameters values
(on, ý-1, ý-2, ALL / 1 ... 8).
Press SET button, hoU r ACT/oUt is diplayed (Option is entered but is not activated yet. or activating please follow the below steps).
Press ESC button one by one until SAU E SEt yES is displayed.
When SAU E SEt yES is displayed, press SET button. If you press
ESC button or choose no option instead of yES option by using
UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Setpoint menu:
In this menu setpoint setting can be programmed. In this menu there are 16 setpoint setting (SP -01 ... SP -16). SP -xx ACt menu must be activated from the chosen setpoint menu. If not, user can not enter the
SP -xx parameters.
SP -01 ... SP -16 : 16 setpoint settings which are set by the user.
SP-01 protection setting activation and settings of the sub menu parameters are given below. All other setpoint protection settings can be done by same way.
SP -01 ACt : In this menu SP -01 protection settings is done. When protection setting is chosen oFF, SP -01s other menus can not be reached.
SP -01 ACt on: Protection setting is active.
SP -01 ACt oFF: Protection setting is passive.
SP -01 PAr : In this menu 76 different parameters settings is done.
Only one of these parameters can be setted.
Note : Protection settings parameters and the information are in the attachement.
SP -01 oPE : In this menu, extreme, low or both protection settings are determined. Sub menus are explained below.
SP -01 oPE rAn gE: Low, extreme protection is done.
SP -01 oPE hýg hEr: Extreme protection is done.
SP -01 oPE LoU Er: Low protection is done.
SP -01 hý : In this menu extreme protection value is set.
SP -01 Lo: In this menu low protection value is set.
Note: When extreme protection value is chosen low protection value is closed, and when low protection value is chosen extreme protection value is closed in SP -01 oPE menu.
SP -01 hYS : In this menu fault recovery hysteresis value is set.
SP -01 ond : In this menu entering the fault delay is set
(000.0-999.9 sec.).
SP -01 oFd : In this menu fault recovery is set (000.0-999.9 sec.).
SP -01 oUt : In this menu alarm output is chosen. 1. ... 8. outputs can be chosen. First and the second outputs are relay outputs, the others (3. ... 8) are digital outputs.
SP -01 LAt Ch: In this menu lock function is activated.
SP -01 LAt oFF: Closes the latch function.
SP -01 LAt on: Activates the latch function.
Note: Latch functions are set in latch menu.
Note: When protection parameters give error the user can see the erroneous parameter by using UP/DOWN buttons in instant values
(more than one error use SET button).
NETWORK ANALYSER
MPR-53CS
Press SETbutton for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons find
SEt Poý nt menu.
Press SET button (SP -01 menu is displayed)
By using UP/DOWN buttons select one of the setpoint settings
SP -01 .. SP -16 (In example SP -01 is chosen)
Press SET button (SP -01 ACt is displayed)
Press SET button (SP -01 ACt oFF is displayed). By using
UP/DOWN buttons, select SP -01 ACt on and press SET button
(SP -01 ACt is displayed).
Note: If you select SP -01 ACt oFF, parameter settings can not be done for SP -01.
By using UP/DOWN buttons select protection parameter from
SP -01 Par menu. (for example SP -01 PAr 3-P L-n setting is selected).
Press SET button (SP 0-1 PAr is displayed).
By using UP/DOWN buttons find SP -01 oPE menu. Press SET button (SP -01 oPE rAn gE in displayed). By using UP/DOWN buttons select SP -01 oPE rAn gE/hýg hEr/LoU Er protection form (for example SP -01 oPE rAn gE is selected).
Press SET button, SP -01 oPE is displayed.
By using UP/DOWN buttons from the menus of SP -01 Hý/Lo/hYS
/ond/oFd/oUt/Lat Ch select the menu.
Press SET button, SP -01 hý 0 00.0 / Lo 0 00.0 / hYS 0 00.0 / ond 0 00.0 / oFd 0 00.0 / oUt 1 / LAt oFF is displayed.
By using UP/DOWN buttons select related parameter values
(000.0-300.0/000.0-300.0/000.0-150.0/000.0-999.9/000.0-999.9/
1-8/on-oFF).
Press SET button SP -01 Hý/Lo/hYS/ond/oFd/oUt/Lat Ch is displayed. (Option is entered but is not activated yet. For activating please follow the below steps)
Press ESC button one by one, until SAU E SEt yES is displayed.
Press SET button when SAU E SEt yES is displayed. If you press
ESC button or choose no option instead of yES option by using
UP/DOWN buttons, new data will be cancelled and previous value will be activated.
Serial Communication
The device has optical isolated MODBUS RTU communication protocal. All the measured parameters can be transferred to the computer. Transformer ratio and communication parameters can be set. Saved demand and energy values can be resetted.
Parameter Settings
Address Parameter : Between 001-247.
Baud Rate parameter : Can be chosen 2400, 4800, 9600, 19200 and
38400 bps.
Parity parameter : Can be chosen no, odd and EUEn.
Press SET button for 3 sec. (trA Fo menu is displayed.)
By using UP/DOWN buttons find RS-485 menu
Press SET button (rS- 485 Adr ES menu is displayed)
By using UP/DOWN buttons from the menus of rS- 485 Adr ES/ bAU d/PAr ýty select the menu.
Press SET button (001 / 9600 /no is displayed)
By using UP/DOWN buttons select related parameter values
(001...247 / 2400...38400 /no, EUEn, odd).
Press SET button, rS- 485 Adr ES/bAU d/PAr ýty is displayed.
(Option is entered but is not activated yet. For activating please follow the below steps)
Press ESC button one by one, until SAU E SEt yES is displayed.
Press SET button when SAU E SEt yES is displayed. If you press
ESC button or choose no option instead of yES option by using UP/DOWN buttons, new option will be cancelled, previous option will be activated.
5
MODBUS RTU PROTOCOL
Standart MODBUS RTU message is shown below.
T
ADDRESS
8 BIT
FUNCTION
8 BIT
DATA
NX8BIT
CRCH CRCL T
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave.
CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.
Available Modbus Function:
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
Read Hold (03) function is used for reading the measured parameter and setting values. Device will sent error message if the device tries to read addresses which are not in the register table.
For example to read phase 1 voltage below message can be sent;
01 03 00 00 00 02 XX XX
01 Device address
03 Function
00 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
XX CRC MSB
XX CRC LSB
Preset Single Register (06) function is used for writting energy values, erasing energy counter or reseting the min., max. demand values. Current transformer ratio can be set between 1-2000, voltage transformer ratio can be set between
1-400000.
For example setting CT ratio as 100;
01 06 80 02 00 64 XX XX
01 Device address
06 Function
80 MSB address
02 LSB address
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Preset Multiple register (10H) function is used for changing more than one register value.
For example setting ratio as 100 and voltage transformer ratio as 20.0.;
01 10 80 00 00 02 04 00 C8 00 64 XX XX girilebilir.
01 Device Address
10 Function
80 MSB address
00 LSB address
00 Register number MSB
02 Register number LSB
04 Byte count
00 Data MSB
C8 Data LSB
00 Data MSB
64 Data LSB
XX CRC MSB
XX CRC LSB
Digital Input
Din (Din=Dijital giriþ)16 bit olarak aþaðýda gösterildiði gibi gönderilir.
55H 15
U U U U
MSB
U U
(Most Significant Byte)
U U U U U U U U
LSB
(Least Significant Byte)
1
DIN2 input 2
0
DIN1 input 1
U: undefined
In1 (input 1) if 12-48 V AC / DC is applied to in 1, 0 bit of DIN register is set as 1. In otherwise 0 bit of DIN register is set as 0.
In2 (input 2) if 12-48 V AC / DC is applied to in 2, 1 bit of DIN register is set as 1. In otherwise 0 bit of DIN register is set as 0.
Parameters are sent in 32 bit Hexadecimal form. For example 230,0 V voltage is sent as 000008FCH. Cosj is divided by 1000. 0.980 Cosj value is sent as 000003D4H. Energy values are sent as 64bit.
12345678901234567890 Wh = AB 54 A9 8C EB 1F 0A D2 Wh
Data Cable :
- 24 AWG or thicker
- Less than 100 ohm-km impedance
- Nominal characteristic impedance in 100 kHz is 100 ohm.
- Between 2 wires mutual capacitance is less than 60 pF/m
- Between one wire and all the wires which are grounded mutual capacitance is less than 120 pF/m.
- Double wire.
ERROR CODES
Slave device (MPR-53CS) sends error message when receive any missing query. Error codes are given below:
01 Invalid Function: If any message except given above is used, then 01 error messages will be sent.
02 Invalid Register: Error 02 will be send when a reading of a register is requested, except the registers which mentioned in table.
03 Invalid data: If any different value is been set for dedicated Transformer values and nonzero for demand value, then error message 03 will be sent.
ADDRESS
(HEX)
0058
005A
005C
005E
0060
0062
0064
0066
0068
006A
006C
006E
0070
0072
0074
0076
003E
0040
0042
0044
0046
0048
004A
004C
004E
0050
0052
0054
0055
0056
0022
0024
0026
0028
002A
002C
002E
0030
0032
0034
0036
0038
003A
003C
0000
0002
0004
0006
0008
000A
000C
000E
0010
0012
0014
0016
0018
001A
001C
001E
0020
0078
007A
007C
007E
0080
0082
0084
0086
0088
008A
008C
008E
0090
0092
0094
0096
0098
009A
009C
009E
00A0
00A2
00A4
00A6
00A8
00AA
00AC
ADDRESS
134
136
138
140
142
144
146
120
122
124
126
128
130
132
148
150
152
154
156
158
160
162
164
166
168
170
172
102
104
106
108
110
112
114
116
118
88
90
92
94
96
98
100
30
32
34
36
38
40
42
44
46
12
14
16
18
20
0
2
4
6
8
10
22
24
26
28
62
64
66
68
70
72
74
48
50
52
54
56
58
60
76
78
80
82
84
85
86
MODBUS REGISTER MAP
MODBUS REGISTER MAP
REGISTER
L1 PHASE VOLTAGE
L2 PHASE VOLTAGE
L3 PHASE VOLTAGE
L1 PHASE CURRENT
L2 PHASE CURRENT
L3 PHASE CURRENT
NEUTRAL CURRENT
L1-L2 PHASE-PHASE VOLTAGE
L2-L3 PHASE-PHASE VOLTAGE
L3-L1 PHASE-PHASE VOLTAGE
L1 PHASE ACTIVE POWER
L2 PHASE ACTIVE POWER
L3 PHASE ACTIVE POWER
L1 PHASE REACTIVE POWER
L2 PHASE REACTIVE POWER
L3 PHASE REACTIVE POWER
L1 PHASE APPARENT POWER
L2 PHASE APPARENT POWER
L3 PHASE APPARENT POWER
L1 PHASE COSj
L2 PHASE COSj
L3 PHASE COSj
TOTAL IMPORT ACTIVE POWER
TOTAL EXPORT ACTIVE POWER
TOTAL INDUCTIVE REACTIVE POWER
TOTAL CAPACITIVE REACTIVE POWER
TOTAL APPARENT POWER
AVERAGE INDUCTIVE COSj
AVERAGE CAPACITIVE COSj
FREQUENCY
L1 PHASE VOLTAGE ANGLE
L2 PHASE VOLTAGE ANGLE
L3 PHASE VOLTAGE ANGLE
L1 PHASE CURRENT ANGLE
L2 PHASE CURRENT ANGLE
L3 PHASE CURRENT ANGLE
L1 PHASE VOLTAGE THD
L2 PHASE VOLTAGE THD
L3 PHASE VOLTAGE THD
L1 PHASE CURRENT THD
L2 PHASE CURRENT THD
L3 PHASE CURRENT THD
DIGITAL OUTPUT STATUS
DIGITAL INPUT STATUS
IMPORT ACTIVE ENERGY-1
EXPORT ACTIVE ENERGY-1
INDUCTIVE REACTIVE ENERGY-1
CAPACITIVE REACTIVE ENERGY-1
IMPORT ACTIVE ENERGY-2
EXPORT ACTIVE ENERGY-2
INDUCTIVE REACTIVE ENERGY-2
CAPACITIVE REACTIVE ENERGY-2
L1 PHASE MIN. VOLTAGE
L2 PHASE MIN. VOLTAGE
L3 PHASE MIN. VOLTAGE
L1-L2 PHASE-PHASE MIN. VOLTAGE
L2-L3 PHASE-PHASE MIN. VOLTAGE
L3-L1 PHASE-PHASE MIN. VOLTAGE
L1 PHASE MIN. CURRENT
L2 PHASE MIN. CURRENT
L3 PHASE MIN. CURRENT
L1 PHASE MIN. ACTIVE POWER
L2 PHASE MIN. ACTIVE POWER
L3 PHASE MIN. ACTIVE POWER
L1 PHASE MIN. REACTIVE POWER
L2 PHASE MIN. REACTIVE POWER
L3 PHASE MIN. REACTIVE POWER
L1 PHASE MIN. APPARENT POWER
L2 PHASE MIN. APPARENT POWER
L3 PHASE MIN. APPARENT POWER
TOTAL MIN. IMPORT ACTIVE POWER
TOTAL MIN. EXPORT ACTIVE POWER
TOTAL MIN. IMPORT REACTIVE POWER
TOTAL MIN. EXPORT REACTIVE POWER
TOTAL MIN. APPARENT POWER
L1 PHASE MAX. VOLTAGE
L2 PHASE MAX. VOLTAGE
L3 PHASE MAX. VOLTAGE
L1-L2 PHASE-PHASE MAX. VOLTAGE
L2-L3 PHASE-PHASE MAX. VOLTAGE
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RANGE
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(0-5000)xUT
(0-5000)xUT
(0-5000)xUT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 -18000)xCTxVT
(0 -18000)xCTxVT
(0 -18000)xCTxVT
(-1000 -1000)
(-1000 -1000)
(-1000 -1000)
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(0 -54000)xCTxVT
(-1000 -1000)
(-1000 -1000)
(4000 -7000)
0-360
0-360
0-360
0-360
0-360
0-360
0-999
0-999
0-999
0-999
0-999
0-999
-
-
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
0-FFFFFFFFFFFFFFFF
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0-3000)xUT
(0-3000)xUT
(0-3000)xUT
(0-5000)xUT
(0-5000)xUT
MULTIPLIER
0.1
0.1
0.1
0.1
0.1
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
1
1
1
1
1
1
1
1
0.1
1
1
1
1
1
1
1
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
1
1
1
1
1
0.1
0.1
0.1
0.1
0.1
0.001
0.001
0.01
1
0.1
0.1
0.1
0.1
-
-
1
FORMAT unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int
-
long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int long int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int int int int unsigned int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int unsigned int unsigned int unsigned int unsigned int unsigned int
UNIT
Wh
Wh
Wh
VArh
VArh
VArh
VArh
Wh
Wh
Wh
Wh
VArh
VArh
VArh
Var
Var
VA
-
-
Hz
Degre
Degre
Degre
Degre
Degre
Degre
%
%
%
%
%
%
-
-
Wh
Var
VA
VA
VA
-
-
-
Watt
Watt
Volt
Volt
Volt
Amper
Amper
Amper
Amper
Volt
Volt
Volt
Watt
Watt
Watt
Var
Var
VArh
Volt
Volt
Volt
Volt
Volt
Volt
Amper
Amper
Amper
Watt
Watt
Watt
Var
Var
Var
VA
VA
VA
Watt
Watt
Var
Var
VA
Volt
Volt
Volt
Volt
Volt
MPR-53CS
ADDRESS
208
210
212
214
216
218
220
222
224
226
228
230
232
234
174
176
178
180
182
184
186
188
190
192
194
196
198
200
202
204
206
250
252
254
256
258
260
262
264
236
238
240
242
244
246
248
ADDRESS
(HEX)
00D0
00D2
00D4
00D6
00D8
00DA
00DC
00DE
00E0
00E2
00E4
00E6
00E8
00EA
00AE
00B0
00B2
00B4
00B6
00B8
00BA
00BC
00BE
00C0
00C2
00C4
00C6
00C8
00CA
00CC
00CE
00EC
00EE
00F0
00F2
00F4
00F6
00F8
00FA
00FC
00FE
0100
0102
0104
0106
0108
REGISTER
MODBUS REGISTER MAP
L3-L1 PHASE-PHASE MAX. VOLTAGE
L1 PHASE MAX. CURRENT
L2 PHASE MAX. CURRENT
L3 PHASE MAX. CURRENT
L1 PHASE MAX. ACTIVE POWER
L2 PHASE MAX. ACTIVE POWER
L3 PHASE MAX. ACTIVE POWER
L1 PHASE MAX. REACTIVE POWER
L2 PHASE MAX. REACTIVE POWER
L3 PHASE MAX. REACTIVE POWER
L1 PHASE MAX. APPARENT POWER
L2 PHASE MAX. APPARENT POWER
L3 PHASE MAX. APPARENT POWER
TOTAL MAX. IMPORT ACTIVE POWER
TOTAL MAX. EXPORT ACTIVE POWER
TOTAL MAX. IMPORT REACTIVE POWER
TOTAL MAX. EXPORT REACTIVE POWER
TOTAL MAX. APPARENT POWER
L1 PHASE MAX. CURRENT DEMAND
L2 PHASE MAX. CURRENT DEMAND
L3 PHASE MAX. CURRENT DEMAND
L1 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L1 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L2 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L2 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L3 PHASE IMPORT MAX. DEMAND ACTIVE POWER
L3 PHASE EXPORT MAX. DEMAND ACTIVE POWER
L1 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L1 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L2 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L2 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L3 PHASE IMPORT MAX. DEMAND REACTIVE POWER
L3 PHASE EXPORT MAX. DEMAND REACTIVE POWER
L1 PHASE MAX. DEMAND APPARENT POWER
L2 PHASE MAX. DEMAND APPARENT POWER
L3 PHASE MAX. DEMAND APPARENT POWER
TOTAL IMPORT MAX. DEMAND ACTIVE POWER
TOTAL EXPORT MAX. DEMAND ACTIVE POWER
TOTAL IMPORT MAX. DEMAND REACTIVE POWER
TOTAL EXPORT MAX. DEMAND REACTIVE POWER
TOTAL MAX. DEMAND APPARENT POWER
C1 (PULSE METER 1) COUNTER
C2 (PULSE METER 2) COUNTER
RUN HOUR COUNTER
SETPOINT HOUR COUNTER
TOTAL HOUR COUNTER
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RANGE
(0-5000)xUT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0-6000)xCT
(0-6000)xCT
(0-6000)xCT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(0 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(-18000 - 18000)xCTxVT
(0 - 18000)xCTxVT
-
-
-
-
-
UNIT
Var
Var
VA
VA
VA
Watt
Watt
Watt
Watt
Watt
Var
Var
Var
Var
Var
Var
VA
-
-
Hour
Hour
Hour
Volt
Amper
Amper
Amper
Watt
Watt
Watt
Var
Var
Var
VA
VA
VA
Watt
Watt
Var
Var
VA
Amper
Amper
Amper
Watt
Watt
Watt
MULTIPLIER FORMAT
ADDRESS
32768
32769
32770
32771
32772
32773
32774
32775
32776
32777
32778
32779
32780
32781
32782
32783
32784
32785
32786
32787
32788
32789
32790
32791
ADDRESS
(HEX)
8000
8001
8002
8003
8004
8005
8006
8007
8008
8009
800A
800B
800C
800D
800E
800F
8010
8011
8012
8013
8014
8015
8016
8017
REGISTER
VOLTAGE TRANSFORMER RATIO
CURRENT TRANSFORMER RATIO
CALCULATION METHOD
DEMAND TIME
PULSE RATIO
PULSE OUTPUT 1 PARAMETER SETTING
PULSE OUTPUT 2 PARAMETER SETTING
ENERGY COUNTER 1 SELECTION
ENERGY COUNTER 2 SELECTION
COMMUNICATION ADDRESS
BAUD RATE
PARITY
PASSWORD ENABLE
PASSWORD
CONNECTION TYPE
CANCEL THE LATCH FUNCTION BY BUTTON
CANCEL THE LATCH FUNCTION BY DIGITAL INPUT
CANCEL THE LATCH FUNCTION ACCORDING TO PROGRAMMED TIME
SETPOINT TIME SET VALUE
SETPOINT TIME ACTIVE / PASSIVE AND WARNING OUTPUT SELECTION
PULSE COUNTER 1 ACTIVE / PASSIVE SELECTION
PULSE COUNTER 1 PULSE COUNT RATIO
PULSE COUNTER 2 ACTIVE / PASSIVE SELECTION
PULSE COUNTER 2 PULSE COUNT RATIO
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
PULSE OUTPUT 1-2
PARAMETER SETTING 0-5 :
0: Active
1: Active Import
2: Active Export
3: Reactive
4: Reactive Import
5: Reactive Export
BAUD RATE 1-5 :
1: 38400 bps
2: 19200 bps
PULSE RATIO 0-6 :
0: 1 Watt / Pulse
1: 10 Watt / Pulse
2: 100 Watt / Pulse
3: 1 kW / Pulse
4: 10 kW / Pulse
5: 100 kW / Pulse
ENER GY COUNTER 1 SELECTION 0-3 :
0 : On (EC -Energy counter- will count on all conditions)
1: EC will count when Digital Input 1 is 1 (1=active)
2: EC will count when Digital Input 2 is 1 (1=active)
3: Inverse Energy Counter 2 (It will count when EC2 is not counted)
CONNECTION SELECTION 0-1 :
6: 1 MW / Pulse
PARITY 0-2 :
0: Star 1: Delta
PASSWORD ENABLE 0-1 :
CANCEL THE LATCH FUNCTION BY BUTTON
0: No
1: Odd
0: Disable
1: Enable
0: Disable
1: Enable
3: 9600 bps
4: 4800 bps
2: Even
CANCEL THE LATCH FUNCTION ACCORDING TO PROGRAMMED TIME 0-180 :
5: 2400 bps
Values are entered like 15 or multiples between 0 and 180
SETPOINT TIME ACTIVE / PASSIVE AND WARNING OUTPUT SELECTION AA-BB :
AA : Alarm condition Active / Passive is chosen. 00: Disable 01: Enable
BB : Alarm output is chosen. 00: Output Relay 1 01: Output Relay 2 02: Digital Output 1 .... 07: Digital Output 6
RANGE
0-40000
0-2000
0-1
1-60
0-6
0-5
0-5
0-3
0-3
0 - 247
1 - 5
0 - 2
0-1
0-9999
0 - 1
0 - 1
0 - 3
0 - 180
0 - 9999
AABB*
0 - 1
0 - 9999
0 - 1
0 - 9999
UNIT
-
-
minute
-
-
-
-
-
-
-
-
-
-
-
-
minute hour
-
-
-
-
-
MULTIPLIER
-
-
-
-
-
-
-
0.1
1
-
1
-
-
-
-
-
-
-
-
-
-
-
-
-
FORMAT short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int short-int
HEX short-int short-int short-int short-int
ENERGY COUNTER 2 SELECTION 0-3 :
0 : On (EC -Energy counter- will count on all conditions)
1: EC will count when Digital Input 1 is 1 (1=active)
2: EC will count when Digital Input 2 is 1 (1=active)
3: Inverse Energy Counter 2 (It will count when EC2 is not counted)
CALCULATION 0-1 :
Refer to Reactive Energy Calculation Method Setting on page 2.
PULSE COUNTERS ACTIVE / PASSIVE SELECTION 0-1 :
0: Disable
1: Enable
CANCEL THE LATCH FUNCTION BY DIGITAL INPUT 0-3 :
0: Disable
1: When digital input 1 is active
2: When digital input 2 is active
3: When digital input 1 or 2 is active
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
-
-
0.01
0.01
0.01
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.001
0.001
0.001
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
unsigned int unsigned int unsigned int unsigned int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int unsigned int unsigned int unsigned int int int int int int int int int int int int int unsigned int unsigned int unsigned int int int int int unsigned int
HEX
HEX
HEX
HEX
HEX

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Measures electrical parameters
- Protection for electrical systems
- Multiple alarm parameter settings
- Energy counter configuration
- Setpoint protection settings
- RS485 interface for communication
- Panel mounted
- User-friendly interface