SMART2600RM2U
Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: SMART2600RM2U
SmartPro 2U Rack/Tower Extended Run UPS - Line interactive, sine wave UPS with integrated switched PDU
and current monitoring
Highlights
2600VA / 2.6kVA high efficiency line interactive, extended-run 2U rack / tower
UPS
Maintains sine-wave 120V nominal output over an input range of 83 to 145V
Network communications supported via HID enabled USB port, DB9 serial
port, SNMP/Web card slot and EPO interface
Current monitoring and switched PDU control via 3 individually controllable
load banks
Input: NEMA 5-20P (120V 20A) / Output: 1 L5-20R, 4 NEMA 5-15/20R, 4
NEMA 5-15R (120V)
2 year product warranty / $250,000 Ultimate Lifetime Insurance (USA, Puerto
Rico & Canada only)
Description
2600VA line interactive UPS system for server, network and telecommunications equipment. 2U rackmount or tower form factor with an installed
depth of only 19 inches. High 96% line-power efficiency rating reduces energy consumption and BTU heat output. Expandable battery runtime with
optional BP48V24-2U and BP48V60RT-3U external battery packs. Uninterruptible Power Supply (UPS) switches to battery-derived AC output during
power failures and extreme voltage variations. Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during
brownouts and one level of voltage cut during overvoltages to maintain regulated 120v output over an input range of 83-145V. Includes 5-20P input
plug and 5-15R, 5-15/20R and L5-20R output receptacles. Network-grade AC surge and noise suppression. Network management interfaces
support communications via USB, DB9 serial and SNMPWEBCARD slot. HID-compliant USB interface enables full integration with built-in power
management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test
data and utility power conditions via all 3 network interfaces at once. Includes PowerAlert monitoring software and complete cabling. Emergency
Power Off (EPO) interface. Integrated 3-bank PDU switching supports load shedding and remote-reboot of connected equipment. 3-stage metered
current monitoring and battery charge status LEDs. Utility power and voltage regulation LEDs. Audible alarm. Self-test. 4-post rackmount
accessories included; 2-9USTAND tower kit and 2POSTRMKITWM two post rack & wallmount accessories available. Field-replaceable,
hot-swappable internal batteries and external battery packs. Attractive all-black color scheme. 2-year warranty and $250,000 connected equipment
insurance; extended warranty and service contracts available.
Package Includes
SMART2600RM2U UPS System, PowerAlert Software and cabling, 4-post rackmount installation hardware, Warranty information,
Instruction manual
Features
SmartPro line interactive UPS system is ideal for voice, data, medical and industrial networking applications
High 96% line-power efficiency rating reduces energy consumption and BTU heat output
Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut during
overvoltages
Maintains continuous operation through blackouts, voltage fluctuations and surges
Corrects line voltage conditions as low as 83V and as high as 145 back to 120V nominal values
Standard internal battery set offers 12 minutes at full load and 4 minutes at full load
Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operation
Compact form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, with
the built-in ability to shutdown any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot
Built-in Emergency Power Off (EPO) interface with cable
Factory installed NEMA 5-20P input plug; user configurable L5-20P or L5-30P input plug-in connections supported
NEMA 5-15R, NEMA 5-15/20R and L5-20R output receptacles
Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (1 outlet
per load bank)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
2 year manufacturer's product warranty, $250,000 ULtimate Lifetime Insurance
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
2600
Output kVA capacity
(kVA)
2.6
Output Watt Capacity
(watts)
2100
Output kW capacity
2.1
Output power factor
0.8
Nominal Output
Voltage(s) Supported
120V
Frequency compatibility
60 Hz
Output voltage
regulation (line mode)
-18%, +8%
Output voltage
regulation (Battery mode)
+/- 5%
Built-in UPS output
receptacles
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-20R outlet(s)
Built-in controllable
switched load banks
Three switchable single-outlet 5-15R load banks
Output circuit breaker
15A breaker protects 5-15R, 20A breaker protects 5-15/20R, L5-20R is unbreakered
Basic PDU options
PDUNV (1U / 2 C19, 12 C13 outlets); PDU1420T (0U / 14 5-15/20R outlets); PDU40TDUAL (0U / 40 5-15/20R
outlets)
Metered PDU options
PDUMH20 (1U / 13 5-15/20R outlets); PDUMH20AT (1U / 16 5-15/20R outlets)*; PDUMV20 (0U / 16 5-15/20R
outlets); PDUMV40 (0U / 32 5-15/20R outlets)
Switched PDU options
PDUMH20ATNET (1U / 16 5-15/20R outlets)*; PDUMV20NET (0U / 24 5-15/20R outlets)
External PDU
redundancy options
*Auto Transfer Switch features utilizing the secondary PDU input cord are compatible with Smart Online UPS
models only
Output AC waveform (AC
mode)
Sine wave
Output AC waveform
(battery mode)
Sine wave
INPUT
Rated input current (at
maximum load)
24A (with user-supplied L5-30P plug), 16A (with factory 5-20P plug)
Nominal Input Voltage(s)
Supported
120V AC
UPS input connection
type
5-20P
Input circuit breaker
30A
UPS Input cord length
(ft.)
10
UPS Input cord length
(m)
3
Recommended Electrical
Service
20-30A 120V
BATTERY
Full load runtime
(minutes)
4 min. (2100w)
Half load runtime
(minutes)
11 min. (1050w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP48V24-2U (limit 1); BP48V60RT3U (multi-pack compatible)
DC system voltage (VDC)
48
Battery recharge rate
(included batteries)
Less than 4.5 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC94-2U
Battery Access
Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
Overvoltage correction
Input voltages between 127 and 147 are reduced by 12%
Undervoltage correction
Input voltages between 95 and 104 are boosted by 12%
Severe undervoltage
correction
Input voltages between 83 and 94 are boosted by 24%
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms
Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
480
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form factors
supported with included
accessories
4 post 19 inch rackmount (mounting rail kit included)
Installation form factors
supported with optional
accessories
2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor
Rackmount
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)
3.5 x 17.5 x 19
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)
8.9 x 44.4 x 48.3
Installed whole system
total rack space height
(rack spaces)
2U
Secondary form factor
Tower (requires 2-9USTAND)
Installed whole system
dimensions in secondary
form factor (height x
width x depth / inches)
17.5 x 3.5 x 19
UPS dimensions in
secondary form factor
(height x width x depth /
cm)
44.4 x 8.9 x 48.3
UPS / Power Module
weight (lbs)
64
UPS / Power Module
weight (kg)
29.1
UPS Shipping
dimensions (height x
width x depth / inches)
9 x 23.5 x 20
UPS Shipping
dimensions (height x
width x depth / cm)
22.9 x 59.7 x 50.8
Shipping weight (lbs)
72
Shipping weight (kg)
32.7
UPS housing material
Steel
Cooling method
Fan
ENVIRONMENTAL
Operating Temperature
Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature
Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr. (full
load)
297.5
Battery mode BTU / hr.
(full load)
1360
COMMUNICATIONS
Communications
interface
USB (HID enabled); DB9 Serial; Contact closure
Network monitoring port
description
Supports detailed monitoring of UPS and site power conditions; 1 USB port and 1 DB9 serial contact closure port
PowerAlert software
Included
Communications cable
USB and DB9 cabling included
WatchDog compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
5 milliseconds
Low voltage transfer to
battery power (setpoint)
83
High voltage transfer to
battery power (setpoint)
145
SPECIAL FEATURES
Grounding lug
Back panel grounding lug
Cold Start (startup in
battery mode during a
power failure)
Cold-start operation supported
High availability UPS
features
Hot swappable batteries
Green & high efficiency
features
Greater than 95% efficiency - GREEN UPS; Individually controllable load banks
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A
(EMI); ROHS (Reduction of Hazardous Substances)
WARRANTY
Product Warranty Period
(U.S., Canada & Puerto
Rico)
2 years
Connected Equipment
Insurance (U.S., Canada
& Puerto Rico)
$250,000 connected equipment insurance
Related Items
Optional Products
Product Type
Related Model
Description
Qty.
Power Distribution
PDU1220
Basic PDU / Power Distribution Unit - Safe, reliable power distribution
for critical networking equipment
-
Power Distribution
PS7224-20
Tripp Lite Power Strip - Multiple outlets wherever you need them
-
SNMP Accessories
SNMPWEBCARD
For remote monitoring and control via SNMP, Web, or Telnet.
-
SNMP Accessories
ENVIROSENSE
Monitors temperature, humidity and contact-closure inputs. (Requires
SNMPWEBCARD or switched PDU.)
-
USB Hubs/Accessories
U022-010
10-ft. USB2.0 A/B Gold Device Cable
(A Male to B Male)
-
Rackmount/Wallmount Kits
2POSTRMKITWM
Enables 2-Post Rackmount or Wallmount Installation of Select
Rackmount UPS Systems
-
Surge Protectors
DNET1
Network Surge Suppressor - Essential protection for data and
communication lines
-
Surge Protectors
DTEL2
Network Surge Suppressor - Essential protection for data and
communication lines
-
Extended Warranties
WEXT3-2200-3000
3-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 2200-3000VA
-
Extended Warranties
WEXT5-2200-3000
5-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 2200-3000VA or less
-
External Battery Packs
BP48V60RT-3U
External Battery Pack and Cable. 3U, Expandable, Blue 2-Point
Connector
-
External Battery Packs
BP48V24-2U
BP48V242U - External Battery Pack for UPS System
-
Tower Stands
2-9USTAND
Enables Tower Placement of Rackmount UPS Systems
-
UPS Accessories
MODBUSCARD
For remote monitoring and control via MODBUS protocol
-
More information, including related products, owner's manuals, and additional technical specifications, can be found online at
www.tripplite.com/en/products/model.cfm?txtModelID=3024.
Copyright © 2010 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous
improvement. Specifications are subject to change without notice. Photos may differ slightly from final products.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising