IC697MDL654
1
Discrete Input Modules
45
GFK-0380G
August 1997
IC697MDL654
48 Volt DC Positive/Negative Logic, 32-Point Input Module
48 Volt DC Positive/Negative Logic, 32-Point Input Module (IC697MDL654)
datasheet GFK-0380G
Features
a44079
D 32 Points - Four isolated groups of 8 points each
D Positive/NegativeLogicCompatibility
D Proximity switch compatible
D Input filter selectable* - 1 ms or 10 ms
A1
A2
A3
A4
A5
A6
A7
A8
D One input configurable as interrupt*
* These features are available for all IC697 Programmable Logic Controllers (PLC). They may not be
available when this module is used with other types
of PLCs. See the applicable Programmable Controller
Reference Manual for details.
B1 C1
B2 C2
B3 C3
B4 C4
B5 C5
B6 C6
B7 C7
B8 C8
FUSE
INPUT
48 VDC, P/N
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
Functions
B3
B4
B5
The 48 Volt DC Pos/Neg Input Module provides 32
input points in four isolated groups of eight points
each. The input current-voltage characteristics meet
IEC standard (type 1) specifications.
B6
B7
B8
C1
C2
C3
LED indicators which give the ON-OFF status of each
point on the logic (PLC) side of the circuit are included at the top of the module.
C4
C5
C6
G7
C8
The module is mechanically keyed to ensure correct
replacement with a similar type in the field. I/O references are user configurable without the use of jumpers or DIP switches on the module.
Configuration is done using the configuration function of the MS-DOSr or Windowsr programming
software running on Windowsr 95 or Windows NTr
over Ethernet TCP/IP or through the SNP port. The
Programming Software configuration function is
installed on the programming device. The programming device can be an IBM XT, AT, PS/2 or compatible Personal Computer.
D1
D2
D3
D4
D5
D6
D7
D8
SLOT
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
Î
D1
D2
D3
D4
D5
D6
D7
D8
A1
A2
A3
A4
A5
A6
A7
A8
B1 C1
B2 C2
B3 C3
B4 C4
B5 C5
B6 C6
B7 C7
B8 C8
FUSE
D1
D2
D3
D4
D5
D6
D7
D8
INPUT
48 VDC, P/N
1
A1
2
3
A2
A3
4
5
A4
+ –
A5
6
7
DC
A6
– +
A7
8
9
A8
10
11
B1
12
13
14
15
16
17
B2
B3
B4
+ –
B5
DC
B6
– +
B7
18
19
B8
20
21
C1
22
23
24
25
C2
C3
C4
+ –
C5
DC
27
C6
C7
– +
29
C8
26
28
30
31
D1
32
33
D2
D3
34
35
36
37
D4
+ –
D5
DC
D6
– +
D7
38
39
D8
40
MODULE IC697MDL654
LABEL 44A726758–012
r IBM and PS/2 are registered trademarks of International Business Machines Corporation.
r MS-DOS, Windows, Windows 95, and Windows NT are registered trademarks of Microsoft Corporation.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
45-1
Discrete Input Modules
2
GFK-0380G
August 1997
48 Volt DC Positive/Negative Logic, 32-Point Input Module
Operation - 48 Volt DC Pos/Neg Input Module
a44080
LED
OPTO
ISOLATOR
FILTER
SYSTEM
INTERFACE
BACKPLANE
DC
USER COMMON (8 CIRCUITS)
FIELD
CONNECTIONS
MODULE
Figure 1. Block Diagram for IC697MDL654
Input Characteristics
This input module is designed to have both positive
and negative logic characteristics - it sinks or sources
current from the input device to the user common.
The input device is connected between the power bus
and the module input as shown above.
This module is compatible with a wide variety of input devices, such as:
characteristics of the switch in the diagram shown
below. If that point falls to the left of the input load
line, the ON state characteristics are compatible. As
an example, the ON state requirements of a compatible proximity switch of 3mA at 5 volts drop are
shown below.
OFF state compatibility is assured if the proximity
switch leakage is less than 2mA with a module input
voltage of 5 volts or less.
D Pushbuttons, limit switches, selector switches;
D Electronic proximity switches, both 2-wire and
48V SUPPLY
a44081
15
14
3-wire.
12
In addition, inputs on this module may be directly
driven by any IC697 PLC voltage compatible output
module.
The input circuitry provides sufficient current to ensure reliable operation of the switching device. Input
current is typically 4.7mA in the ON state, and can
accept up to 2 mA leakage current in the OFF state
without turning on.
NON–OPERATIONAL
10
8
ON–STATE
VOLTAGE
ACROSS
PROXIMITY
SWITCH
To determine compatibility with a specific proximity
switch, find the ON state
45-2
4
OPERATIONAL
2
0
3-wire proximity switches are easily applied, since
they provide low voltage drop in the ON state and
low leakage current in the OFF State.
2-wire proximity switches derive their power from the
signal connections; thus both the ON state voltage
and the OFF state leakage current are higher than for
3-wire devices. This module is designed to be compatible with many such 2-wire devices; however each
device type must be carefully evaluated for compatibility in both the ON and OFF states.
40V SUPPLY
6
0
1
2
I LOAD (mA)
3
4
5
Figure 2. Proximity Switch Compatibility
Input Filter Selection
With the IC697 PLC and certain other CPU options,
this module may be configured to have either a 1mS
or 10mS input filter. Configuration is on a module,
not per point basis; all points have the same filter
time. See the applicable Programmable Controller Reference Manual for detailed information.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Input Modules
3
GFK-0380G
August 1997
48 Volt DC Positive/Negative Logic, 32-Point Input Module
Interrupt
When used with the IC697 CPU, input point A1 may
be configured to cause a CPU interrupt. Configuration allows the CPU to be interrupted on either the
rising or falling edge of the signal transition. Interrupt response is not affected by input filter time
selection. Refer to the applicable Programmable Controller Reference Manual for detailed information.
The wire bundle can be secured to the terminal board
by passing a cable tie through a cleat located at the
lower corner of the terminal board.
TERMINALS
1
3
5
7
9
10
11
B3
14
15
16
18
19
20
21
23
25
DC
B6
+
B8
C2
C4
+
C5
DC
+
C6
C7
29
30
t
B5
C3
24
28
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
+
C1
22
31
C8
D1
32
33
D2
D3
34
35
D4
D5
36
37
D6
+
DC
+
D7
38
39
40
B4
B7
27
The detachable field wiring terminal board will accept
wire sizes ranging from #22 (0.36 mm2 ) through #14
(2.10 mm2 ). Two wires may be terminated on a given
lug if both wires are the same size. There is room for
a bundle of forty #14 (2.10 mm2 ) wires to be routed
out through the terminal board cavity.
A8
B2
26
The module is wired as shown in the illustration on
the right of this page. Since each group of eight inputs is isolated from the others, a wire from the power source to the power input terminal for each group
(terminal number 10, 20, 30, or 40) is required (power
input terminals for each group are not connected inside the module).
DC
+
B1
13
Field Wiring
A6
+
A7
8
17
If it is necessary to change the module location in the
rack after the key has been latched onto the center rail
of the rack, the key can be removed by pushing it upward to unhook the latch while pulling it off the rail.
It may then be reinserted onto the module and the
module inserted into the rack in the desired location.
Note that only the power supply can be placed in the
leftmost rack position.
A4
A5
12
When the module is first installed, the key latches
onto the backplane center rail. When the module is
extracted, the key remains in the center rail, configuring the slot to accept only identical module types.
A2
A3
4
6
This module includes a mechanical key that prevents
inadvertent substitution of one module type for
another in a given slot. The key fits a uniquely
shaped area on the board below the connector. The
key is included with each module.
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
Î
Î
ÎÎ
ÎÎ
Î
ÎÎ
Î
ÎÎ
ÎÎ
ÎÎ
A1
2
Module Mechanical Keying
a43986
FIELD WIRING
D8
Figure 3. Field Wiring Connections
45-3
Discrete Input Modules
4
GFK-0380G
August 1997
48 Volt DC Positive/Negative Logic, 32-Point Input Module
Recommended Field Wiring Procedures
The following procedures are recommended when connecting field wiring to the detachable terminal board on this input
module. Module features referenced in the following procedures which are common to all I/O modules for the IC697
PLC are illustrated in the following figure.
a43855
JACKSCREW
HINGED
DOOR
JACKSCREW
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
Î ÎÎÎÎ
Î
ÎÎÎÎ
ÎÎ
ÎÎ
Î
Î
TERMINAL
BOARD
CORD
TIE
CORD
TIE
CLEAT
CORD
TIE
CLEAT
CORD
TIE
STRAP
CLEAT
Î
Î
ÎÎ
ÎÎ
STRAP
STRAP
Figure 4. I/O Module Features
1. Turn off power before removing or installing terminals boards. Open the hinged door on the module to access a jackscrew which holds the terminal
board securely in place. The detachable field wiring terminal board can now be removed from the
module by turning the jackscrew counter-clockwise until it is fully disengaged.
2. To remove the terminal board, grasp the top of the
terminal board and swing it outward as shown in
Figure 5.
Caution
Do not use the hinged door to remove the
terminal board. The hinged door could
be damaged if this is done.
45-4
3. The terminal board is designed to accept wire sizes
ranging from AWG #22 (0.36 mm2 ) through AWG
#14 (2.10 mm2 ). It is important that when using
AWG #14 (2.10 mm2 ) wire for wiring all points,
that a maximum insulation diameter of .135 inch
not be exceeded. To ensure proper connection,
two wires may be terminated on any one terminal
only if both wires are the same size.
4. The terminal board is designed to accept a maximum of (40) AWG #14 (2.10 mm2 ) wires. If AWG
#14 (2.10 mm2 ) wires are to be used, then wire
markers should be placed at least 8 inches (203
mm) from termination end to provide sufficient
space for the hinged door to close.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Input Modules
5
GFK-0380G
August 1997
48 Volt DC Positive/Negative Logic, 32-Point Input Module
Î
ÎÎÎ
Î
Î
ÎÎ
ÎÎ
Î
Î
ÎÎ
Î
Î
ÎÎ
Î
ÎÎÎ
Î
Î
ÎÎ
ÎÎ
JACKSCREW
a43747
DO NOT
PULL
ON DOOR
WIRE BUNDLE CABLE TIE CLEAT
Figure 5. Removal of I/O Terminal Board
5. After completing connections to all modules in a
rack, the wire bundle must be secured. To ensure
that the wire bundle is secured properly, it is recommended that a cable tie be wrapped around the
wire bundle and tightly secured through the cable
tie cleat located at the lower right corner of the
terminal board. For extremely large wire bundles,
additional cable ties should be used.
6. A door label insert is included with each module to
indicate circuit wiring information and provide
space to record user circuit wiring identification.
A slot is provided on the hinged door to allow for
insertion of this label. If the label is difficult to insert, crease the scored edge before insertion. The
outside label has a color coded stripe to allow
quick identification of the module voltage type
(blue: low voltage; red: high voltage).
7. After field wiring is completed, the terminal board
should be securely fastened to the rack by inserting the terminal board strap (attached to each
module) into the small rectangular slots in the bottom card guide grill on the rack. This strap not
only secures the terminal board to the rack, it also
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
provides a way of identifying the wired terminal
board with its correct mating rack slot location.
8. For adequate module ventilation, it is recommended that at least a 6 inch (152 mm) clearance
be allowed above and below the rack grill. Wire
bundles should not obstruct the rack grill work.
Removing an I/O Module
The instructions below should be followed when removing an I/O module from its slot in a rack.
D Grasp the board firmly at the top and bottom of
the board cover with your thumbs on the front of
the cover and your fingers on the plastic clips on
the back of the cover.
D Squeeze the rack clips on the back of the cover
with your fingers to disengage the clip from the
rack rail and pull the board firmly to remove it
from the backplane connector.
D Slide the board along the card guide and remove it
from the rack.
45-5
Discrete Input Modules
6
GFK-0380G
August 1997
48 Volt DC Positive/Negative Logic, 32-Point Input Module
Table 1. Specifications for IC697MDL654 [
Rated Voltage:
48 volts DC
Inputs per Module:
32 (four groups of eight inputs each)
Isolation:
1500 volts RMS - any input to backplane
500 volts RMS between input groups
Input Voltage Range (Vs)
–3 to +56 volts DC
Input Current:
4.7mA (typical) at rated voltage
InputImpedance:
10.3K ohm, typical
Input Characteristics On-state Voltage:
33 volts to 56 volts
Off-state Current
3mA to 7mA
Off-state Voltage:
0 volts to 10 volts
Off-state Current:
0 to 2mA (2mA minimum at 5V input)
Filter Delay Time:
1 ms or 10 ms configurable
Current Required from 5VDC backplane bus:
0.30 amps
VME
System designed to support the VME standard C.1
[ Refer to GFK-0867B, or later for product standards and general specifications. For installations requiring compliance to more
stringent requirements (for example, FCC or European Union Directives), refer to Installation Requirements for Conformance to
Standards.
Table 2. Ordering Information
Description
Catalog Number
Input Module: 48 Volt DC Positive/NegativeLogic,32Points
IC697MDL654
Note: For Conformal Coat option, or Low Temperature Testing option please consult the factory for price and availability.
45-6
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F