Programa de aplicacion_5WG11411AB02

Programa de aplicacion_5WG11411AB02
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
List of Contents
1
Using the application program................................................................................................................................... 2
2 Product description..................................................................................................................................................... 2
2.1
Essential information about DALI............................................................................................................................. 2
2.2
KNX / DALI Gateway N 141/02 ................................................................................................................................ 2
3 Functional overview .................................................................................................................................................... 3
3.1
Introduction to functional overview........................................................................................................................... 3
3.2
Functions, objects .................................................................................................................................................... 3
3.3
Direct mode ............................................................................................................................................................. 3
3.4
Power supply status of DALI devices....................................................................................................................... 3
3.5
N141/02 power supply status................................................................................................................................... 3
3.6
DALI short circuit status ........................................................................................................................................... 3
3.7
ECG 1-64 ................................................................................................................................................................. 3
3.8
Group 1-16............................................................................................................................................................... 4
3.9
8-bit Scene control ................................................................................................................................................... 5
3.10 Effect control ............................................................................................................................................................ 5
3.11 Export / import.......................................................................................................................................................... 5
3.12 Documentation......................................................................................................................................................... 5
3.13 Commissioning ........................................................................................................................................................ 5
3.14 Test ECGs ............................................................................................................................................................... 6
3.15 Test Groups ............................................................................................................................................................. 6
3.16 Test Scenes ............................................................................................................................................................. 6
3.17 Test Effects .............................................................................................................................................................. 6
3.18 Power supply / bus voltage failure ........................................................................................................................... 6
3.19 Power supply / bus voltage recovery ....................................................................................................................... 6
3.20 Support of ECGs with integrated constant light level control and directly connected brightness sensor.................. 6
4 Communication objects .............................................................................................................................................. 7
4.1
Introduction to communication objects..................................................................................................................... 7
4.2
General objects........................................................................................................................................................ 9
4.3
Objects per group (1…16) ..................................................................................................................................... 11
4.4
Objects per individually addressable (ungrouped) luminaire (1…64)..................................................................... 12
5 Parameters ................................................................................................................................................................. 14
5.1
Introduction to parameters ..................................................................................................................................... 14
5.2
Functions ............................................................................................................................................................... 14
5.3
Objects................................................................................................................................................................... 16
5.4
Groups ................................................................................................................................................................... 19
5.5
ECGs ..................................................................................................................................................................... 22
5.6
Self-contained emergency ECGs........................................................................................................................... 26
5.7
Scenes ................................................................................................................................................................... 28
5.8
Effects.................................................................................................................................................................... 30
5.9
Export / import........................................................................................................................................................ 32
5.10 Commissioning ...................................................................................................................................................... 33
5.11 Test Groups ........................................................................................................................................................... 34
5.12 Test ECGs ............................................................................................................................................................. 35
5.13 Test Scenes ........................................................................................................................................................... 36
5.14 Test Effects ............................................................................................................................................................ 36
6 Appendix .................................................................................................................................................................... 38
6.1
Behaviour in event of 230V recovery at N 141/02, voltage recovery on DALI, KNX bus........................................ 38
6.2
Behaviour in event of 230V failure on N 141/02, DALI, KNX bus........................................................................... 39
6.3
Behaviour on emergency OFF ............................................................................................................................... 40
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/ 1
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Self-test of the inverters of self-contained emergency
luminaires can be started and the test result reported
via the bus. The type of test (function test, short duration test or long duration test) that has to be started or
has started can be commanded or queried by the new
8-bit object “Start test”. A test result will be reported
automatically at the end of a test or can be queried via
the new 3-byte object “Test result”.
1 Using the application program
Product family:
Product type:
Manufacturer:
Lighting
Interface
Siemens
Name:
Order no.:
KNX / DALI Gateway N 141/02
5WG1 141-1AB02
2 Product description
2.1
Essential information about DALI
DALI (Digital Addressable Lighting Interface) is a bidirectional communications interface in accordance with
IEC 60929, whose specification has been defined by
manufacturers of electronic ballasts. It not only enables
the receipt of e.g. switching and dimming commands
but also the sending of status information such as the
failure of a lamp or the report of a detected error in the
electronic ballast. According to IEC 60929 up to 64
DALI devices can be connected to a DALI line and can
each be assigned an individual device address.
2.2
KNX / DALI Gateway N 141/02
The KNX / DALI gateway N 141/02 is a 4 MU wide,
DIN-rail mounted KNX device with one DALI interface
to which up to 64 DALI actuators (e.g. DALI ballasts)
can be connected to. It is not allowed to connect DALI
sensors to the DALI interface of the N 141/02.
The KNX / DALI Gateway N 141/02 enables communicating with up to 64 DALI devices including detection
and transmission of DALI status and failure information
via KNX. DALI actuators can be switched and dimmed
either individually or in groups. If a DALI actuator is assigned to one of the 16 groups it cannot be controlled
individually anymore. An individual name, a group, parameters and scenes (refer to the application program
description) are assigned to the individual DALI electronic ballasts during commissioning with the ETS (Engineering Tool Software).
Via the object “Emergency operation” all luminaires
controlled by a N 141/02 can be dimmed to the set
“Dimming value on emergency” even when they are not
effected by any mains or DALI power failure. By this all
luminaires may be dimmed to the same brightness level
as all self-contained emergency luminaires.
During “Emergency Operation” all luminaires will not respond to any on/off or dim commands and cannot be
commissioned.
Note: If individual communication with each individual
DALI device is not required and you wish for example to
simply connect a group of dimmable fluorescent lamps
in parallel and control them in the same way as you
would previously have connected and controlled dimmable electronic control gear (ECG) with a 1...10 V interface, this is also possible with the switching/dim-ming
actuator N 525E. Status and error signals are also detected by the N 525E and transmitted, whereby these
signals are as-signed to the respective group and not to
an individual DALI device.
The KNX / DALI Gateway N 141/02 can be used to control DALI actuators in emergency luminaires. Selfcontained emergency luminaires containing two DALI
devices (ballast and an inverter, each with a DALI interface) only up to 32 self-contained emergency luminaires may be connected to a N 141/02. The gateway
automatically detects if a self-contained emergency luminaire contains two or only one DALI actuators. Selfcontained emergency luminaires with two DALI interfaces and “normal” luminaires with only one DALI interface may be connected to the N 141/02, but the total
number of 64 DALI devices may not be exceeded.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/ 2
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
3 Functional overview
3.1
Introduction to functional overview
The application program can only be loaded with the
ETS3.
Type and number of communication objects are defined
by the number of attached DALI devices, the configured
groups as well as by the functions and objects activated
via the “Functions” and “Objects” parameter windows.
3.2
Functions, objects
The basic functionality of the gateway can be expanded
by additional functions and communication objects via
the “Functions” and “Objects” parameter windows. This
includes time-limited switching on of lighting during the
night (time-limited cleaning light in night operation), 8bit scene control integrated into the gateway, an additional control of light effects and the determination
whether and how the various status objects are to be
transmitted.
3.3
Direct mode
The power supply unit integrated in the N 141/02 supplies the gateway electronics and generates the DALI
voltage. Additionally, it enables the operation of the
gateway and a direct switching of all lamps controlled
over its DALI interface even if the N 141/02 has not yet
been commissioned with the ETS or if the communication via the KNX bus has been interrupted. For this purpose, the N 141/02 has a pushbutton located bottom
left on its front plate for switching-on the “Direct mode”
as well as for switching back to the “Bus mode”. When
this pushbutton has been pressed for the first time the
yellow light emitting diode (LED) lights up permanently
to indicate direct mode. Then all lamps controlled via
DALI can be switched On or Off all together via the
relevant two pushbuttons on the front plate of the gateway: pressing briefly the upper pushbutton switches the
channel On while pressing briefly the lower push button
switches the channel Off. A red LED integrated in the
upper push button is used to indicate the On state of
the lamps by a continuous light and to indicate a DALI
cable error by flashing.
Detected faults are displayed using this blink code:
1x blinking
Connecting AC 230V to DALI wire is not
permitted
2x blinking
DALI short circuit
3x blinking
DALI voltage too low!
4x blinking
no load / no DALI devices found
If the direct mode button is pressed for a second time,
the yellow LED to indicate direct mode is extinguished
and the N 141/02 is switched to “Bus mode”.
Time functions that have already been launched are interrupted by switching on the direct mode.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
3.4
Power supply status of DALI devices
If it is detected (by scanning of the connected DALI devices) that their power supply is missing, this is transmitted via the object “Mains failure at DALI devices” (0=
no mains failure; 1 = mains failure at DALI devices).
It can be configured using the parameter “Send mains
failure at DALI devices if number of DALI devices with
mains failure >=” in the “Functions” window when this
object is to be sent in the event of a detected error.
3.5
N141/02 power supply status
The status of the common power supply for the DALI
gateway N141/02 and the DALI cable is reported via
the 1-bit “N141/02 power supply failure” status object. If
the object value = “0”, power is supplied. If the object
value = “1”, the power supply to the N141/02 and to
DALI have failed. The gateway is then no longer able
to function, and all DALI ECGs revert to the dimming
status parameter setting in the event of DALI bus voltage failure.
Short-term buffering of the power supply for the gateway electronics ensures that a power supply failure is
recognized and the telegram on the N141/02 power
supply status can still be transmitted.
3.6
DALI short circuit status
A short circuit in the DALI cable is reported via the 1-bit
status object “DALI short circuit”. If the object value =
“0”, there is no short circuit. If the object value = “1”,
the DALI power supply has short-circuited. The gateway is then no longer able to control the DALI devices,
and all DALI ECGs revert to the dimming status parameter setting in the event of DALI bus voltage failure.
3.7
ECG 1-64
An ECG can either be controlled individually or via a
group. It is not possible to do both at the same time.
Only the objects for ECG are relevant when individually
controlling the individual ECG. (Objects 140 to 631; see
also section 4.)
3.7.1. Switching on / off
Up to 64 DALI ECGs can be switched individually. The
desired switching state can be reached via dimming using a configurable dimming time.
3.7.2. Dimming brighter / darker
Up to 64 DALI ECGs may be individually dimmed. The
parameter “Dimming time” can be configured.
After receiving the dimming start command the gateway
N 141/02 communicates with the ECGs to dim them
with the configured dimming time to the desired value. If
a stop command is received before completion of the
dimming process, the dimming process is aborted and
the dimming value reached is maintained. In timer
mode unless on off command was received the follow-
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/3
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
up time is started. Switching on / off via dimming can be
configured via a parameter.
3.7.3. Sending 8-bit dimming value
Up to 64 DALI ECGs can be individually dimmed to a
transmitted 8-bit value. The desired dimming value can
be reached using a configurable dimming time.
3.7.4. Dimming value limitations
If an ECG is assigned to a group, it “inherits” the
“Switch-on value”, “Minimum dimming value” and
“Maximum dimming value” perimeters from this group.
If the “Switch-on value” parameter is set to “last value”
for one group, the “minimum dimming value” set for this
group is used as the switch-on value upon receipt of an
ON telegram sent to an ECG that has been assigned to
this group.
3.7.5. Switching status
The switching status (On / Off) of an individual DALI
ECG can be both reported and queried via the 8-bit
“Status switching, luminaire xy” status object. In this
process bit 0 to bit 5 contain the number of the DALI
ECG. Via bit 6 = 1 it is reported that the ECG / the lamp
is switched on. Bit 7 is reserved for future applications.
A change in the switching status will be automatically
transmitted via this object only once it has been triggered via a switching command or, respectively, via
turning On/Off by dimming brighter/darker or, respectively, via an 8-bit dimming telegram and if automatic
sending is enabled. No telegrams are dispatched via
this status object in the event of switching status
changes in the group.
If a send request is sent to this object, this request must
contain the number of the DALI ECG in bit 0 to 5 and bit
6 and 7 must be set to “1”. The switching status will always be transmitted upon a send request, irrespective
of where it came from.
3.7.6. Dimming value status
The dimming status (0...100%) of an individual DALI
ECG can be both reported and queried via the 16-bit
“Status dimming value, luminaire xy” status object. In
this process bit 8 to bit 13 contain the number of the
DALI ECG. Via bit 14 = 1 it is displayed that the ECG /
the lamp is switched on. Bit 15 is reserved for future
applications. Bit 0 to bit 7 contain the current dimming
status as an 8-bit value (0...100%).
A change in the dimming status will be automatically
transmitted via this object only once it has been triggered via a switching command or, respectively, via a
dimming value telegram and the automatic sending is
released. No telegrams are dispatched via this status
object in the event of brightness changes in the group.
If a send request is sent to this object, this request must
contain the number of the DALI ECG in bit 8 to 13 and
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
bit 14 and 15 must be set to “1”. The dimming status
will always be transmitted upon a send request, irrespective of where it came from.
3.7.7. Failure status
The failure status of an individual DALI ECG can be
both reported and queried via the 8-bit “Failure status,
luminaire xy” status object. In this process bit 0 to bit 5
contain the number of the DALI ECG. A lamp error is
reported via bit 6 = 1 and an ECG error via bit 7 = 1.
If a send request is sent to this object, this request must
contain the number of the DALI ECG in bit 0 to 5 and bit
6 and 7 must be set to “1”.
3.7.8. CIN device identification
DALI devices from the company OSRAM include a
clear 16-figure identification number, the CIN device
identification (CIN = Chip Identification Number). Light
manufacturers can then select the CIN code and attach
a sticker with the CIN code to their lights with integrated
DALI ECG. One CIN can be assigned to each DALI
ECG attached to the N 141/02, via which the ECG can
be directly addressed during commissioning. In order to
facilitate entry, the 16-digit CIN should be entered as
eight 2-digit numbers.
3.8
Group 1-16
Only the objects for groups are relevant when controlling ECGs via groups. (Objects 12 to 139; see also section 4.)
An ECG can either be controlled individually or via a
group. It is not possible to do both at the same time.
3.8.1. Switching on / off
The DALI devices attached to the gateway can be assigned to up to 16 groups.
When a switch-on telegram is sent to a group the parameter setting determines whether the configured
dimming value or the value prior to switching off will be
set. If the switch-on value is below the configured minimum value, the minimum value is set; if the value is
above the maximum value, the maximum value is set.
Parameters can be used to set whether the desired
value is jumped or gradually dimmed to. Switch-off
telegrams always switch off. Depending on parameter
setting, switch-on telegrams activate follow-up times.
3.8.2. Dimming brighter/darker
The “dimming time” feature is adjustable. After the start
command is received gateway N 141/02 commences
communication with the ECGs in order to change the
dimming value in the indicated direction using the configured dimming time. If a stop command is received
before the dimming process is completed, the dimming
process is cancelled and the dimming value obtained is
maintained. In time-switch operation, the follow-up time
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/4
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
is (re) commenced if the device has not been switched
off. Parameters can be used to set whether dimming
can be used to switch on and off.
3.8.3. Sending 8-bit dimming value
The communication object with the description “Dimming value, group X” sets all ECGs of this group to the
transmitted dimming value. Parameters can be set to
determine whether this value comes on immediately or
is brightened gradually. If this object contains the value
0, the corresponding group is switched off. Values
smaller than the minimum value (with the exception of
the value 0) and values bigger than the maximum value
are limited to the minimum / maximum dimming value.
A parameter can be used to determine whether a
switched-off ECG takes over the received value immediately and switches on or only takes over the received
value when there is an ON command. The configured
switch-on value is then invalid. Depending on parameter setting, the dimming value telegrams also activate
the follow-up times.
3.8.4. Dimming value limitations
A maximum and minimum dimming value can be configured via the limitation. For all switching and dimming
procedures the dimming value can only be changed
within the configured limits.
Note:
Status annunciations may be delayed by up to six (6)
seconds after a switching or dimming command has
been completed.
3.8.5. Switching status
The on/off status of each group can be sent via a
“Status switching, group x” object upon a read request
or automatically when the object value is changed.
3.8.6. Dimming value status
The “Status dimming value, group x” object is an 8-bit
status object. It contains the current dimming value of
the respective group. It can be sent and / or read independently.
ECGs, Group x” object or, respectively, the status can
be queried at any time.
3.8.9 Failure status
The failure status of a group can be reported or read via
the 8-bit status object „Failure status, Group x“.
The error code contains information about the number
of defective ECGs / converters and lamps. Additionally
it shows if lamps and/or ECGs for emergency lighting
have failed.
3.9
8-bit Scene control
The application program makes it possible to parameterize up to 16 scenes, each of which can contain up
to 16 groups and/or up to 64 ECG’s. The saving and retrieving of scenes is effected via the 8-bit communication object “8-bit scene, retrieve / save”.
Time functions cannot be executed within a scene.
3.10
Effect control
The application program contains a special effects control that can be used to produce running light effects or
cyclically repeating coloured light effects. Recalling and
stopping of a special effect is effected via the 8-bit
communication object “Effect, recall / stop”.
3.11
Export / import
The export mechanism makes it possible to save the
parameter setting of a KNX / DALI Gateway N 141/02 in
a file. The numbers and names of the DALI ECGs assigned upon commissioning are also exported to this
file. These exported numbers, names and group allocations are only valid, however, for as long as no new initialization of ECGs is carried out on the associated
KNX / DALI Gateway N 141/02 or, respectively, no
other application has been loaded into the device. The
export file can be used, for example, to import the parameter settings into another project data base or into a
newer version of the application program.
The import function only imports data from the application program 07 B0 KNX / DALI Gateway 981Cxx. Conversion of the data of other application programs in order then to be able to load them into the N 141/02 are
not part of the functional scope of the import function.
3.8.7. Lamp error status
One recognized lamp failure in a participant in this
group can be reported per group via the 1-bit "Status
lamps, group x” object or, respectively, the status can
be queried at any time.
3.12
Documentation
The application program makes it possible to print out
the entire parameter setting of the N 141/02.
3.8.8. ECG error status
One recognized ECG failure in a participant in this
group can be reported per group via the 1-bit "Status
Note:
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
3.13
Commissioning
The application program can only be imported by ETS 3
starting with version 3.0 f.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/5
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Following download by means of ETS 3, all DALI ECGs
that are attached to the Gateway N 141/02 can be established and displayed. An individual name of up to 50
characters long can then be assigned to every ECG
and the EBS can be allocated to the individual groups
and tested.
The individual name assigned in each case to an ECG
and a group is automatically adopted as the object
name in the ECG and group objects. By printing out the
documentation it can be followed which ECG has which
number and name / which group has which name and
which ECGs are allocated to it.
Note:
If during a download an ECG cannot be contacted either because it is missing or the installation is faulty this
ECG is not downloaded to. ECGs that could not be
downloaded to are annuniciated with an ECG error.
This also applies to dummy ECGs.
The commissioning function also makes it possible to
assign the new ECG with the predecessor’s name and
data following replacement of a defective ECG.
3.14
Test ECGs
The individual ECGs can be directly switched / dimmed
to an adjustable value by way of a test immediately after commissioning, without KNX telegrams needing to
be sent via group addresses.
3.15
Test Groups
The individual groups can be directly tested immediately after allocation of the ECGs and of a parameter
download, without KNX telegrams needing to be sent
via group addresses.
3.16
Test Scenes
The individual scenes can be directly tested immediately after allocation of the ECGs and of a parameter
download, without KNX telegrams needing to be sent
via group addresses.
3.17
Test Effects
The individual effects can be directly launched and cancelled immediately after allocation of the ECGs and of a
parameter download, without KNX telegrams needing
to be sent via group addresses.
3.18
Power supply / bus voltage failure
In the event of power supply failure the program always
saves the current dimming values of all groups, so that
these are available once the power supply has been recovered. The individual groups may assume different
dimming values in the event of power supply failure.
See also appendix item 6.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Note:
The default configuration for power supply failure is “no
action”. For power supply recovery it is “as before
power failure”.
If there is a power supply failure at the N141/02 with the
default settings for power supply failure and recovery
shortly after a switching (e.g. all ballasts on or off) or
dimming action then it is possible that after power recovery not all ballasts are reset to the state “as before
power failure”.
The period “shortly” is determined by the number of
connected ballasts and the split of the connected ballasts between single ballasts and groups and may be
up to approximately one minute long.
3.19
Power supply / bus voltage recovery
The dimming value that is set on power supply recovery
can be adjusted via parameters.
A time delay can be set in order to avoid high bus loads
on the KNX (if a setting has been made to have the current ECG and group status reports transmitted on bus
voltage recovery). The status reports are only transmitted after this time has elapsed. See also appendix
item 6.
3.20
Support of ECGs with integrated constant
light level control and directly connected brightness sensor
ECGs with integrated constant light level control and directly connected brightness sensor are supported as
follows:
• Switching on/off
The lamp switches on to maximum brightness and
then dims to the calibrated value.
• Dimming brighter/darker
Dimming brighter/darker (dimming with stop telegram)
shifts the set point of the constant light level control.
The following limitations apply to these ECGs:
• „Normal Mode“ is the only permissible selection as
„Operation Mode“.
• The parameters „Starting value“, „Dimming value on
emergency“, „ Dimming time for switching on/off from
0% to 100% [hh:mm:ss] “, „ Dimming time for dimming
brighter/darker from 0% to 100% [in seconds] “, „
Dimming time for set value from 0% to 100%
[hh:mm:ss] “, „Switch On/Off via dimming
brighter/darker“, „Switch on/off via set value“ and „Accept dimming value“ are deactivated and have no effect.
• These ECGs cannot be assigned to groups as the
status of the individual ECGs can be different.
• These ECGs cannot be assigned to scenes.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/6
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
4 Communication objects
Currently, these ECGs with integrated constant light
level control and directly connected brightness sensor
are supported:
Tridonic
PCA 1/49 T5
Excel one4all IP - Smart-LS
4.1
Introduction to communication objects
Maximum number of group addresses:
Maximum number of assignments:
1023
1023
The communication objects can be grouped into
(a) general communication objects
Obj Object name
Function
direct On / Off
Type
Flag
1 Bit
CRT
1
Status
mode
2
Night mode
On / Off
1 Bit
CWTU
3
8-bit Scene
recall / store
1 Byte
CW
4
Effect
recall / stop
5
Mains failure at 1=mains failure
DALI devices
6
N 141/02 power 1=power
supply failure
failure
7
DALI short circuit 1=short circuit
1 Bit
CRT
8
Emergency
eration
1 Bit
CWT
9
Status switching, Return
luminaire no. xy
code
status 1 Byte
CWT
10
Status switching / Return
dimming value, code
luminaire no. xy
status 2 Byte
CWT
11
Failure
status, Return error code 1 Byte
luminaire no. xy
CWT
1 Byte
CW
1 Bit
CRT
supply 1 Bit
CRT
op- On / Off
(b) communication objects for DALI groups 1 to 16
Obj Object name
Type
Flag
12
Switching, Group On / Off
01
Function
1 Bit
CW
13
Dimming,
Group 01
4 Bit
CW
14
Dimming
Group 01
1 Byte
CW
15
Status switching, On / Off
Group 01
1 Bit
CRT
16
Status dimming 8-bit value
value,
Group 01
1 Byte
CRT
17
Status
lamps, 1 = lamp failure
Group 01
1 Bit
CRT
18
Status
ECGs, 1 = ECG failure
Group 01
1 Bit
CRT
19
Failure
status, Report error code 4 Byte
Group 01
Brighter / Darker
value, 8-bit value
CRT
...
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/7
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
The description of the communication objects 12 to 19
also applies to the communication objects 20 to 139 of
groups 2 to 16 (max. 16 DALI groups supported).
…
Obj Object name
Function
Type
Flag
644 Switching,
“Luminaire 64”
On / Off
1 Bit
CW
Brighter / Darker
4 Bit
CW
Type
Flag
132 Switching, Group On / Off
16
1 Bit
CW
133 Dimming,
Group 16
4 Bit
CW
645 Dimming,
“Luminaire 64”
Setpoint
adjustment,
“Luminaire 64”
CW
CW
646 Dimming value, 8-bit value
“Luminaire 64”
1 Byte
1 Byte
CRT
1 Bit
CRT
647 Status switching, On / Off
“Luminaire 64”
1 Bit
135 Status switching, On / Off
Group 16
CRT
1 Byte
CRT
648 Status dimming 8-bit value
value,
“Luminaire 64”
1 Byte
136 Status dimming 8-bit value
value,
Group 16
1 Bit
CRT
649 Failure
status, Report error code 1 Byte
“Luminaire 64”
CRT
137 Status
lamps, 1 = lamp failure
Group 16
1 Bit
CRT
650 Start test,
verter 64”
CWRT
138 Status
ECGs, 1 = ECG failure
Group 16
CRT
651 Test result, “In- Report test type / 3 Byte
result
verter 64”
Obj Object name
134 Dimming
Group 16
Function
Brighter / Darker
value, 8-bit value
139 Failure
status, Report error code 4 Byte
Group 16
“In- Start test / report 1 Byte
status
CRT
(c) communication objects for individual luminaires (1 to
64)
Obj Object name
Function
Type
Flag
140 Switching,
“Luminaire 01”
On / Off
1 Bit
CW
141 Dimming,
“Luminaire 01”
Setpoint
adjustment,
“Luminaire 01”
Brighter / Darker
4 Bit
CW
142 Dimming value, 8-bit value
“Luminaire 01”
1 Byte
CW
143 Status switching, On / Off
“Luminaire 01”
1 Bit
CRT
144 Status dimming 8-bit value
value,
“Luminaire 01”
1 Byte
CRT
145 Failure
status, Report error code 1 Byte
“Luminaire 01”
CRT
146 Start test,
verter 01”
CWRT
“In- Start test / report 1 Byte
status
147 Test result, “In- Report test type / 3 Byte
result
verter 01”
CRT
…
The description of the communication objects 140 to
147 also applies to the communication objects 148 to
651.
…
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/8
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
4.2
General objects
Obj
Object name
1
Status
mode
Function
direct On / Off
Type
Flag
1 Bit
CRT
This object is used to report that the gateway was switched
from bus mode to direct mode via the “direct mode” button on
its upper side (direct mode = On) or, respectively, that it has
been switched back from direct mode to bus mode (direct
mode = Off).
When direct mode is switched on (the associated yellow LED
on the upper side of the gateway illuminates) the direct
switching of all attached DALI devices is released via the two
buttons on the gateway upper side. In this process the switching status of the DALI devices is displayed via the LED integrated in the upper button. This LED also serves to display an
error independently of bus or direct mode. If a short-circuit in
the DALI bus cable or a failure of the power supply of an DALI
device is detected or if there is no DALI device attached to the
gateway, the LED flashes to display a failure.
In direct mode the gateway does not execute switching, dimming value or scene recall commands received via the bus,
but stores them as the desired intended status. After switching back to bus mode (the yellow LED for displaying the direct
mode on the upper side of the gateway is switched off) the
gateway compares the actual statuses of the luminaires /
groups with the saved planned statuses and automatically
eliminates deviations.
2
Night mode
On / Off
1 Bit
CWTU
This object is used to activate / deactivate the “Night mode”
operating mode via the bus for all groups. This object can be
sent, for example, by a button, a timer or a building automation system. If a log. 1 is received, the groups switch over to
night mode.
In “Night mode” a group (for which night mode has been released by the set parameter) can no longer be switched-on
permanently, but only on a time-limited basis (e.g. cleaning
light for 30 minutes). If the “Warn before switching-off during
night mode” parameter (see “Group, parameters” parameter
window) is set to “Yes”, after the configured ON-period has
elapsed the group’s dimming value will first be set to 50% of
the previous value, dimmed darker during approx. 30 seconds, and then the group is switched off. This means that the
end of the ON period can be recognized and that the lighting
can be switched on for another 30 minutes, for example, by
pressing the light switch again.
3
8-bit Scene
recall / store
1 Byte CW
Via this object the 8-bit scene is recalled (i.e. recovered) or,
respectively, stored, with the number x. In this process bit
0...5 contain the scene number x. If bit 7 = log. 1, the scene is
stored, if bit 7 = log. 0, then it is recalled. Bit 6 is currently of
no significance and must be set to log. 0.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Obj
Object name
Function
Type
Flag
4
Effect
recall / stop
1 Byte
CW
Via this object the effect with the number x is recalled (i.e.
launched) or, respectively, stopped. In this process bit 0...5
contain the effect number x. If bit 7 = log. 0, the effect is recalled, if bit 7 = log. 1, then it is stopped. Bit 6 is currently of
no significance and must be set to log. 0.
5
Mains failure at 1=mains
DALI devices
ure
fail- 1 Bit
CRT
If it is detected (by scanning of the connected DALI devices)
that their power supply is missing, this is transmitted via the
group address linked to this object (0= no mains failure; 1 =
mains failure at DALI devices).
It can be configured using the “DALI, status objects failure”
parameter in the “Objects” window whether and when this object is to be sent in the event of a detected error.
If in case of a mains failure at the DALI devices connected to
this gateway all emergency luminaries connected to other
gateways shall also dim to the value defined by the parameter
“Dimming value on emergency” the group address assigned
to this object 5 must also be assigned to the object 8 “Emergency operation” of this gateway and to the objects 5, 6 and 8
of all other KNX/DALI gateways (see appendix section 6).
Note: If a phase power monitor is used to detect a mains failure at the DALI devices the object used for the transmission
of this information has to be linked to the same group address
as assigned to objects 5 and 8 of this and of all other gateways.
6
N141/02 power 1=power sup- 1 Bit
supply failure
ply failure
CRT
The status of the mains power supply for the Gateway
N 141/02 and its integrated power supply for the DALI bus is
sent via the group address linked to this object (0= no power
supply failure; 1 = power supply failure).
It can be adjusted using the “DALI, status objects failure” parameter in the “Objects” window whether and when this object
is to be sent in the event of a detected failure.
If in case of a DALI power failure at one gateway all emergency luminaries connected to this gateway and also those
connected to other gateways shall dim to the value defined by
the parameter “Dimming value on emergency” the group address assigned to this object 6 must also be assigned to the
object 8 “Emergency operation” of this gateway and to the objects 6 and 8 of all other KNX / DALI gateways (see appendix
section 6).
7
DALI short circuit 1=short circuit 1 Bit
CRT
A short circuit of the DALI bus is reported via the group address linked to this object (0=no short circuit; 1=short circuit).
It can be adjusted using the “DALI, status objects failure” parameter in the “Objects” window whether and when this object
is to be sent in the event of a detected failure.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/9
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Obj
Object name
8
Emergency
eration
Function
op- On / Off
Type
Flag
Obj
Object name
1 Bit
CWT
10
Status switching / Return status 2 Byte
dimming value, code
luminaire no. xy
The group address which is assigned to the object no. 5
“N 141/02 power supply failure” and the object no. 6 “Mains
failure at DALI devices” must be also assigned to this object
and to the objects no. 5, 6 and 8 of all other KNX / DALI gateways. If one KNX / DALI gateway detects a power or mains
failure, this is reported via the group address of either the object no. 6 “N 141/02 power supply failure” or the object no. 5
“Mains failure at DALI devices” with the logical value “1”. This
gateway and all other KNX / DALI gateways receiving via this
group address at the object “Emergency operation” the logical
value “1” (1= Emergency operation ON) will dim all their luminaires to the dimming value defined by the parameter “Dimming value on emergency”.
When the KNX / DALI gateway which detected the mains failure at the DALI devices returns to normal operation after
mains recovery this is reported via the group address at its
object no. 5 with the logical value “0”. If there is no other KNX
/ DALI gateway still having detected a mains failure at the
DALI devices and when the time defined by the parameter
“Gateway prolong. time on emergency op. OFF” is over then
this gateway and all other KNX / DALI gateways having received via the group address assigned to the object “Emergency operation” the logical value “0” (0= Emergency operation OFF) will dim all their luminaires to the dimming value set
by the parameter “Behaviour on emergency operation OFF”.
9
Status switching, Return status 1 Byte
luminaire no. xy
code
CWT
The switching status of each attached luminaire can be queried or automatically sent via this object.
It can be adjusted using the “Luminaire no. xy, switching
status object” parameter in the “Objects” window whether and
when (upon request, automatically after a change, or upon
bus voltage recovery) the current switching status is to be
sent via this object. This takes place even with luminaires that
have been allocated to a group. In the process the following
bit allocation is used:
Bit 7
6
5
4
3
2
1
0
reserved
Lamp
[Luminaire number-1]
Off/On
Bit 0 to bit 5 contain the number of the luminaire as a binary
number in the 0...63 range, where the binary number 0 corresponds to luminaire number 1, etc. The recognition of a failure
can, depending on the number of the luminaires, last up to 90
seconds.
Note:
To read the switching status a value containing the luminaire
number and bits 6 and 7 both set to 1 has to be sent to the
corresponding group address.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Function
Type
Flag
CWT
The switching and dimming status of each attached luminaire
can be queried or automatically sent via this object.
It can be adjusted using the “Luminaire no. xy, switching /
dimming value status object” parameter in the “Objects” window whether and when (upon request, automatically after a
change, or upon bus voltage recovery) the current status information is to be sent via this object. This takes place even
with luminaires that have been allocated to a group. In the
process the following bit allocation is used:
Bit 15
14
13
12
11
10
9
8
1 = status
Lamp
[Luminaire number-1]
request
On/Off
Bit 7
6
5
4
3
8-bit value
2
1
0
Note:
To read the switching status a value containing the luminaire
number and bits 14 and 15 both set to 1 has to be sent to the
corresponding group address.
11
Failure
status, Return
luminaire no. xy
code
error 1 Byte
CWT
The failure status of each attached luminaire can be queried
or automatically sent via this object.
It can be adjusted via the “Luminaire no. xy, failure status object” parameter in the “Objects” window whether and when
this object is to be sent in the event of a detected error. In the
process the following bit allocation is used:
Bit 7
6
5
4
3
2
1
0
ECG
Lamp
[Luminaire number-1]
failure
failure
Note:
To read the switching status a value containing the luminaire
number and bits 6 and 7 both set to 1 has to be sent to the
corresponding group address.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/10
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
4.3
Objects per group (1…16)
Obj Object name
The description of the communication objects 12 to 19
also applies to the communication objects 20 to 139 of
groups 2 to 16 (max. 16 DALI groups supported).
Note:
The name „Group 01“ in the object names is replaced
by the name for the group entered in the parameter
window.
Obj Object name
Function
Type
Flags
12
Switching,
On / Off
1 Bit
CW
“Group 01”
All luminaires assigned to group 1 are switched via this object.
13
Dimming,
Brighter / Darker 4 Bit
CW
“Group 01”
The dimming telegrams for all luminaires assigned to group 1
are received via this object.
14
Dimming value, 8-bit value
1 Byte CW
“Group 01”
A dimming value for all luminaires assigned to group 1 is received via this object.
15
Status switch- On / Off
1 Bit
CRT
ing,
“Group 01”
The current switching status of group 1 is sent via this object.
It can be adjusted via the “Group 1-16, status objects switching” parameter in the “Objects” window whether and when
(upon request, automatically after a change, or upon bus voltage recovery) the current switching status is to be sent via
this object.
16
Status dimming 8-bit value
1 Byte CRT
value,
“Group 01”
This object is used as a send object for the current status
(dimming value) of group 1. It can be adjusted via the “Group
1-16, status objects dimming value” parameter in the “Functions, objects” window whether and when (upon request,
automatically after a change, or upon bus voltage recovery)
the current dimming value status is to be sent via this object.
The “Send block time after status change value”, which can
be adjusted from 1-60 seconds (see “Objects” parameter window) ensures that no high bus load is produced due to rapidly
consecutive dimming value status telegrams during dimming.
Once one dimming value telegram has been sent, the next
one will only be sent after the send block time has elapsed.
17
Status lamps, 1 = lamp failure 1 Bit
CRT
“Group 01”
The status of the lamps from group 1 is sent via this object (0
= all lamps intact, 1 = one or several lamps defective). It can
be adjusted via the “Group 1-16, status objects lamp failure”
parameter in the “Objects” window whether and when (upon
request, automatically after a change, or upon bus volt-age
recovery) the current lamp status is to be sent via this object.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Function
Type
Flags
18
Status ECGs, 1 = ECG failure 1 Bit
CRT
“Group 01”
The status of the ECGs from group 1 is sent via this object (0
= all ECGs intact, 1 = one or several ECGs defective). It can
be adjusted via the “Group 1-16, status objects ECG failure”
parameter in the “Objects” window whether and when (upon
request, automatically after a change, or upon bus voltage recovery) the current ECG status is to be sent via this object.
19
Failure status, Report error
4 Byte CRT
code
“Group 01”
This object transmits the quantity of ballasts and inverters assigned to this group and the quantity and type of failures that
have been detected in this group.
This object will be transmitted as set by the parameter “Group
1-16, status objects failure code”.
The different bytes of this object have the following meaning:
Bit 31
Bit 30
Bit 29…Bit 24
Norm
ECG
Emer.
ECG
Number of defective ballasts (ECG) / inverters
Bit 23
Bit 22
Bit 21…Bit 16
Norm.
lamp
Emer.
lamp
Number of defective lamps
Bit 15
Bit 14
Bit 13…Bit 8
Def.
invert.
n.u.
Number of inverters
Bit 7
Bit 6
Bit 5 …Bit 0
n.u.
n.u.
Number of ballasts (ECG)
“Number of ballasts” (bit 0…5) contains the total number of
ballasts belonging to this group.
“n.u.” means “not used” and is reserved for future use.
“Number of inverters” (bit 8…12) contains the number of inverters of self-contained emergency luminaires belonging to
this group.
“Defective inverter” (bit 13) signals (if set to the logical value
“1”) that there is at least one defective inverter in this group.
“Number of defect lamps” (bit 16…21) contains the number of
lamps that have been detected as defective in this group.
“Emergency lamp” (bit 22) signals (if set to the logical value
“1”) that there is at least one defective emergency lamp.
“Normal lamp” (bit 23) signals (if set to the logical value “1”)
that there is at least one defective “normal” lamp.
“Number of defective ballasts (ECG) / inverters” (bit 24…29)
contains the number of ballasts and inverters that have been
detected as defective in this group.
“ Emergency ECG” (bit 30) signals (if set to the logical value
“1”) that there is at least one emergency luminaire with a defective ballast.
“Normal ECG” (bit 31) signals (if set to the logical value “1”)
that there is at least one normal luminaire with a defective ballast.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/11
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
4.4
Objects per individually addressable (ungrouped) luminaire (1…64)
The description of the communication objects 140 to
147 also applies to the communication objects 148 to
651.
Up to 64 individually addressable luminaires with a
DALI ballast or 64 emergency luminaires with one DALI
device or 32 emergency luminaires with two DALI devices are supported.
Note:
The names „Luminaire 01“ and „Inverter 01“ in the object names are replaced by the corresponding names
for the ECG respectively the inverter entered in the parameter window.
Obj Object name
Function
Type
Flags
140 Switching,
On / Off
1 Bit
CW
“Luminaire 01”
“Luminaire 01” can be switched individually via this object.
The name “Luminaire 01” changes dependent on the name
set via the configuration of this ECG.
When an On command is received the ECG immediately
jumps to the configured On value or dims to that value using
the configured dimming time. If the ECG is assigned to a
group then only objects 12 to 139 are relevant.
141 Dimming,
Brighter / Darker 4 Bit
CW
“Luminaire 01”
Setpoint
adjustment,
“Luminaire 01”
The dimming telegrams for the individual dimming of luminaire x are received via this object. The name “Luminaire 01”
changes dependent on the name set via the configuration of
this ECG.
If the ECG is assigned to a group then only objects 12 to 139
are relevant.
If the configuration „Fluorescent lamp with brightness control“
is selected, then the object name changes from Dimming to
Setpoint adjustment.
142 Dimming value, 8-bit value
1 Byte CW
“Luminaire 01”
A dimming value for the individual dimming of luminaire x is
received via this object.
The name “Luminaire 01” changes dependent on the name
set via the configuration of this ECG.
When a dimming value is received the ECG dims to that value
using the configured dimming time. If the ECG is assigned to
a group then only objects 12 to 139 are relevant.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Obj Object name
Function
143 Status switch- On / Off
ing,
“Luminaire 01”
Type
Flags
1 Bit
CRT
The current switching status of luminaire x is sent via this object. It can be adjusted via the “Ungrouped Luminaire 1-64,
status objects switching” parameter in the “Objects” window
whether and when (upon request, automatically after a
change, or upon bus voltage recovery) the current switching
status is to be sent via this object.
144 Status dimming 8-bit value
value,
“Luminaire 01”
1 Byte
CRT
This object is used as a send object for the current status
(dimming value) of luminaire x. It can be adjusted via the “Ungrouped luminaire 1-64, status objects dimming value” parameter in the “Objects” window whether and when (upon request, automatically after a change, or upon bus voltage recovery) the current dimming value status is to be sent via this
object.
The “Disable time after dimming status change”, which can be
adjusted between 2 and 60 seconds (see “Functions” parameter window), ensures that no high bus load is produced
due to rapidly consecutive dimming value status telegrams
during dimming. Once one dimming value telegram has been
sent, the next one will only be sent after the send block time
has elapsed.
145 Failure status,
Report error
1 Byte CRT
“Luminaire 01” code
The information if the lamp is defect, the ballast or the inverter
(in case of an individually addressable self-contained emergency luminaire) is transmitted via this object. This object
will be transmitted as set by the parameter “Ungrouped luminaire 1-64, status objects failure code” in the “Objects” window.
The different bits of this object have the following meaning:
Bit 7
6
5
4
3
2
1
0
n.u.
n.u.
n.u.
n.u.
n.u.
Inv.
defect
ECG
defect
Lamp
defect
“Lamp defect” signals that the lamp is defect.
“ECG defect” signals that the ballast is defect.
“Inv. defect” signals that the inverter is defect.
“n.u.” means “not used” and is reserved for future use.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/12
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Obj Object name
Function
Type
Flags
146 Start test,
Start test / re- 1 Byte CWRT
port status
“Inverter 01”
Via this object the test of a self-contained emergency luminaire can be started and it can be queried or sent automatically if a test has been started (test active).
The setting of the parameter “Sending test status” in the
“Functions” window defines, if and when the test status has to
be sent.
The following bit assignment is used for this object:
Bit 7
6
5
4
3
2
1
0
n.u.
n.u.
Long
durat.
test
active
Start
long
durat.
test
Short
durat.
test
active
Start
short
durat.
test
Funct.
test
active
Start
funct.
test
If bit 0 is set to log. “1” a function test will be started.
If bit 1 is set to log. “1” the luminaire is in the function test
mode.
If bit 2 is set to log. “1” a short duration test will be started.
If bit 3 is set to log. “1” the luminaire is in the short duration
test mode.
If bit 4 is set to log. “1” a long duration test will be started.
If bit 5 is set to log. “1” the luminaire is in the long duration
test mode.
The KNX/DALI gateway will ignore any values written to bits
1, 3, 5, 6 & 7 and it will ignore the telegram/command if more
than one of bits 0, 2 & 4 is set to log. “1” or if all bits are set to
log. “0”.
147 Test result,
Report test type 3 Byte CRT
/ result
“Inverter 01”
The test result of a self-contained luminaire can be queried or
sent automatically via this object.
The setting of the parameter “Sending test result” in the parameter window “Functions” defines, if and when the test result has to be sent.
The following bit assignment is used for this object:
Bit
23
22
21
20
19
18
17
16
Test result
Bit
15
14
13
12
11
10
9
8
Dur.
test
faile
d
Func.
test
failed
Dur.
test
max.
delay
exc.
failure
Func.
test
max.
delay
exc.
failure
Emer.
lamp
failure
Batt.
failure
Batt.
durat.
failure
Circ.
failure
Bit 7
6
5
4
3
2
1
0
n.u.
n.u.
n.u.
n.u.
Test
failed
End
of
long
durat.
test
End
of
short
durat.
test
End
of
Funct.
test
Obj Object name
Function
Type
Flags
failed. When the test passed bit 8 to 15 are set to “0”.
Bit 4 to 7: “n.u.” means “not used” and is reserved for future
use.
Bit 8 “Circuit failure”: a hardware failure of the inverter has
been detected.
Bit 9 “Battery duration failure”: indicates that the battery failed
to maintain its output for the rated duration.
Bit 10 “Battery failure”: indicates an open circuit or low voltage
failure of the battery
Bit 11 “Emergency lamp failure”: indicates that the lamp attached to the inverter has failed
Bit 12 “Function test max. delay exceeded failure”: indicates
that the inverter was unable to perform the function test within
the maximum timeout period.
Bit 13 “Duration test max. delay exceeded failure”: indicates
that the inverter was unable to perform the duration test within
the maximum timeout period.
Bit 14 “Function test failed”: indicates a Function Test Failure.
Bit 15 “Duration test failed”: indicates a Duration Test Failure.
Bit 16…23 “Test result”: This byte contains the battery charge
status as a value between 0 and 255 (= 0…100%) at the end
of a function test. It contains at the end of a duration test either the time (as a multiple of 2 minutes) of the duration test
without battery failure (bit 3 = 0) or the time until the battery
failed (bit 3 = 1).
If the error status of the inverter could not be retrieved then
test failure (bit 3 = 1) is indicated and all bits 8...15 are set to
log. “1“. In this case the value of the test result (bits 16…23)
has no meaning.
If a test failure (bit 3 = 1) is indicated and all bits 8...15 are set
to log. “0“ then the value of the test result (bits 16…23) is dependent on these error states:
0xfe: error on reading the battery load state after function test
or battery test.
0xfd: error while receiving results of the short duration test
0xfc: Unforeseen end of the short duration test (no valid test
result available)
0xfb: Unforeseen end of the short duration test (no valid test
result available)
0xfa: error while receiving result of long duration test
0xf9: Unforeseen end of the function test (no valid test result
available)
If bit 0 is set to log. “1” the end of a function test is signalled.
If bit 1 is set to log. “1” the end of a short duration test is signalled.
If bit 2 is set to log. “1” the end of a long duration test is signalled.
If bit 3 is set to log. “1” the test failed. Bit 8 to 15 signal why it
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/13
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5 Parameters
5.2
5.1
5.2.1 Essential information
Introduction to parameters
Functions
5.1.1. Parameter window overview
The overview of parameter windows lists the maximum
available parameter windows. Depending on configuration parameter windows (e.g. scenes, effects) may
automatically be removed from this list.
5.1.2. Standard buttons
The buttons explained below are always visible on the
upper edge of a selected parameter window.
The basic functionality of the gateway can be expanded
by additional functions via the “Functions” parameter
window. This includes time-limited switching on of lighting during the night (cleaning light), 8-bit scene control
integrated into the gateway, an additional control of light
effects and the determination whether and how the
various status objects are to be transmitted.
5.2.2. Parameter description
Button
Parameter
Settings
File
Save: Saves the current configuration. Different from the OK
button the window is not closed. If the Cancel button is
pressed then only those changes since the last Save via this
menu selection are discarded.
Export: Initiates the export function (see 5.8)
Import: Initiates the import function (see 5.8)
Close: Closes the Plug-in like the OK button
Print
Print: The configuration is printed.
Preview: A preview of the configuration printout is presented.
Standard
Load default values of current page
Load default values of all pages
Help
Dependent on the current window explanations on the parameters are presented.
8-bit scene control
yes
no
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
If this parameter is set to “Yes”, then communication object 7
“8-bit scene”, which is used to control the scene control integrated in the gateway, is supplemented. Additionally, a
“Scenes” parameter window is supplemented in the selection
list on the left-hand edge of the parameter window. Using the
“Scenes” parameter window, it can be established for every
scene which of the 16 light groups are to be integrated in the
scene.
Effects
yes
no
If this parameter is set to “Yes”, then communication object 8
“Effect”, which is used to active the light effect control integrated in the gateway, is supplemented. Additionally, an “Effects” parameter window is supplemented in the selection list
on the left-hand edge of the parameter window. The time
lapse of up to 16 light effects (with up to 500 steps in total)
can be established via the "Effects" parameter window.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/14
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Night mode
yes
no
Parameter
This parameter is used to set whether the lighting is to be
switched on in a time-limited manner at night or not.
If the parameter is set to “no”, the lighting can be switched on
permanently at night. If, on the other hand, the parameter is
set to “yes”, then communication object 2 “Night mode” is automatically added to the comm. objects. If this object is set to
log. 1, the lighting can only be switched on in a time-limited
manner and is automatically switched off after the set ONperiod has elapsed. If a new On command is received before
the On period has elapsed, this time function (night mode) is
re-triggered.
ON period during night
mode
5 minutes
10 minutes
15 minutes
20 minutes
30 minutes
45 minutes
60 minutes
This parameter is only visible if the parameter “Night mode” is
set to “Yes”. It is used to set how long the lighting is to be
switched on in a time-limited manner if the object “Night
mode” is set to “ON”.
ON period during direct
mode
unlimited
5 minutes
10 minutes
15 minutes
20 minutes
30 minutes
45 minutes
60 minutes
This parameter is used to set whether the direct mode has a
permanent or time-limited On period and after what time, in
the case of time-limited direct mode, the device will automatically switch back to bus mode.
Settings
no delay
Delay time after restart
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
20 seconds
30 seconds
35 seconds
... [5 second increments]
4 minutes 15 seconds
If one of the group / ECG status parameters is set to automatic “send after bus voltage recovery”, the current status reports are automatically sent to the bus after bus voltage recovery. This can lead to high bus loads when several Gateways N 141/02 are used.
With this parameter it is possible to delay the automatic sending and thus reduce the bus load on bus voltage recovery. If
several Gateways N 141/02 are installed, these should be set
to different delay values.
Note:
The selected delay time after restart increases the duration of
a download and on power recovery the duration of the “Behaviour on bus voltage recovery of KNX or DALI”.
Disable time after dimming 2 seconds
status change
3 seconds
4 seconds
5 seconds
7 seconds
10 seconds
15 seconds
20 seconds
30 seconds
45 seconds
60 seconds
The disable time for the dynamic sending of the dimming
value status can be set with this parameter.
When using brightness controllers or several channels, a disable time ≥ 15 seconds should be selected as excessive bus
loads may otherwise arise. Once the final value has been
reached, the status is sent once this interval has elapsed.
Send mains failure at DALI
devices if number of DALI
devices with mains failure
>=
1-64
1
If the number of DALI devices experiencing a power failure is
larger than the value set with this parameter then the communication object 5 “Mains failure at DALI devices“ is set to 1 =
“mains failure”, otherwise it is set to 0 = “no mains failure”.
Optimise DALI behaviour
after mains power recovery
yes
no
After operating power has resumed some DALI ballasts need
a short pause in the DALI communication, which is activated
when this parameter is set to “Yes”.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/15
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
5.3
Settings
Emergency luminaires
yes
no
If emergency luminaires will be connected to the gateway this
parameter has to be set to “Yes”. Then the following 4 parameters will become visible.
Gateway prolong time on
emergency op. OFF
Objects
5.3.1 Essential information
0 seconds
10 seconds
30 seconds
1 minute
2 minutes
5 minutes
10 minutes
15 minutes
20 minutes
This parameter defines the time after which a luminaire which
was set to emergency operation ON will be switched or dimmed to the value defined by the parameter “Behaviour on
emergency operation OFF” when the object “Emergency operation” has been reset to the logical value “0”.
Behaviour on emergency
operation OFF
as before emergency operation
starting value
maximum dimming value
minimum dimming value
switch OFF
last received dimming value
This parameter defines which dimming values the groups and
luminaires adopt when the emergency operation is finished.
If this parameter is set to “starting value” and the starting value of a group is selected as “last value”, the corresponding
group or luminaire is set on “emergency operation OFF” to the
last received dimming value. If the group or luminaire was
switched OFF on “emergency operation ON”, the minimum
dimming value is set in this case.
Sending test status
only upon read request
on change of status
In the parameter setting “Sending test status: only upon read
request”, the current value of the object “Start test” is sent
upon a read request only.
In the setting “Sending test status: on change of status”, the
current value of the object “Start test” is sent automatically after a change. There is no automatic sending of the test status
after bus voltage recovery, even if it changed in accordance
with the parameterisation.
Sending test result
only upon read request
at end of test
The basic functionality of the gateway can be expanded
by additional communication objects via the “Objects”
parameter window.
5.3.2. Parameter description
Parameter
Settings
Group 1-16, status objects
switching
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status switching”
communication object is to be supplemented per group and
when these objects are to be sent.
The switching status is automatically sent with every status
change when the parameter is set to “send on change of
status”.
With “send on change of status / after bus voltage recovery”
the switching status is sent after bus voltage recovery if this
changed before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
In the parameter setting “Sending test result: at end of test”,
the current value of the object “Test result” is sent automatically when a test is finished.
In the parameter setting “Sending test result: only upon read
request”, the current value of the object “Test result” is only
sent upon a read request.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/16
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Parameter
Settings
Group 1-16, status objects
dimming value
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
Group 1-16, staus objects
failure code
not available
send only upon read request
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status dimming
value” communication object is to be supplemented per group
and when these objects are to be sent.
The dimming value status is automatically sent with every
status change when the parameter is set to “send on change
of status”.
With “send on change of status / after bus voltage recovery”
the dimming status is sent after bus voltage recovery if this
changed before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
Group 1-16, status objects
lamp failure
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status lamps”
communication object (see object no. 17) is to be supplemented per group, via which a lamp failure in the group is to
be reported and when these objects are to be sent.
If “send on change of status” is selected, the “Status lamps”
object is automatically sent with every status change.
With “send on change of status / after bus voltage recovery”
the object is sent after bus voltage recovery if this changed
before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
Group 1-16, status objects
ECG failure
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status ECGs”
communication object (see object no. 18) is to be supplemented per group, via which an ECG failure in the group is to
be reported and when these objects are to be sent.
If “send on change of status” is selected, the “Status ECGs”
object is automatically sent with every status change.
With “send on change of status / after bus voltage recovery”
the object is sent after bus voltage recovery if this changed
before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
This parameter is used to set whether one 4 byte “Failure
status” communication object (see object no. 19) is to be supplemented per group, via which a detailed failure information
of the group is to be reported and when these objects are to
be sent.
In the parameter setting “send only upon send request”, the
current status of the object “Failure status, Group xy” is only
sent upon a send request.
In the parameter setting “send on change of status / after bus
voltage recovery” the current status of the object “Failure,
Group xy” is sent automatically after a change and after bus
voltage recovery.
Ungrouped luminaire 1-64,
status objects switching
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status switching”
communication object (see object no. 143) is to be supplemented per luminaire and when these objects are to be sent.
The switching status is automatically sent with every status
change when the parameter is set to “send on change of
status”.
With “send on change of status / after bus voltage recovery”
the switching status is sent after bus voltage recovery if this
changed before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
Luminaire no. xy, status ob- not available
ject switching
send only upon read request
send on change of status / after bus voltage recovery
This parameter is used to set whether one single 1 byte
“status switching, Luminaire no. xy,” communication object
(see object no. 9) is to be supplemented, via which the
switching of each luminaire is to be reported and when this
object is to be sent.
In the parameter setting “send only upon read request”, the
current status of the object no. 9 is only sent upon a read request.
In the setting “send on change of status / after bus voltage recovery”, the current status of the object no. 9 is sent automatically after a change and after bus voltage recovery.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/17
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Parameter
Ungrouped luminaire 1-64,
status objects dimming
value
not available
send only upon read request
send on change of status
send on change of status / after bus voltage recovery
Luminaire no. xy, status ob- not available
ject failure code
send only upon read request
send on change of status / after bus voltage recovery
This parameter is used to set whether one “Status dimming
value” communication object (see object no. 144) is to be
supplemented per luminaire and when these objects are to be
sent.
The dimming value status is automatically sent with every
status change when the parameter is set to “send on change
of status”.
With “send on change of status / after bus voltage recovery”
the dimming status is sent after bus voltage recovery if this
changed before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
Sending the status via a read request is possible with every
parameter setting, with the exception of the “not available” parameter.
Luminaire no. xy, status ob- not available
ject switching / dimming
send only upon read request
value
send on change of status / after bus voltage recovery
This parameter is used to set whether one single 2 byte
“status switching / dimming value, Luminaire no. xy” communication object (see object no. 10) is to be supplemented, via
which the switching and the dimming value status of each luminaire is to be reported and when this object is to be sent.
In the parameter setting “send only upon read request”, the
current status of the object no. 10 is only sent upon a read request.
In the setting “send on change of status / after bus voltage recovery”, the current status of the object no. 10 is sent automatically after a change and after bus voltage recovery.
Ungrouped luminaire 1-64,
status objects failure code
Settings
This parameter is used to set whether one single 1 byte “Failure status, Luminaire no. xy” communication object (see object no. 11) is to be supplemented, via which the failure status
of each luminaire is to be reported and when this object is to
be sent.
In the parameter setting “send only upon read request”, the
current status of the object no.11 is only sent upon a read request.
In the setting “send on change of status / after bus voltage recovery”, the current status of the object no. 10 is sent automatically after a change and after bus voltage recovery.
DALI, status objects failure
send on change of status
send only upon read request
send on change of status /
after bus voltage recovery
This parameter is used to set when comm. Object 5 “Mains
failure at DALI devices”, comm. object 6 “N 141/02 power
supply failure” and comm. object 7 “DALI short circuit” are to
be sent via which a N 141/02 power supply failure and the
status of the DALI bus voltage (failed or not) as well as the
status of the DALI bus (short-circuited or not) can be queried
or, respectively, every change of status can be automatically
reported.
The objects are automatically sent with every status change
when the parameter is set to “send on change of status”.
With “send on change of status / after bus voltage recovery”
the object is sent after bus voltage recovery if this changed
before the bus voltage recovery.
No automatic sending takes place with “send only upon read
request”.
not available
send only upon read request
send on change of status / after bus voltage recovery
This parameter is used to set whether a 1 byte “Failure status,
luminaire xy” communication object (see object no. 143) is to
be supplemented per luminaire, via which a detailed failure information of the luminaire is to be reported and when these
objects are to be sent.
In the parameter setting “send only upon read request”, the
current value of the object no. 143 is only sent upon a send
request.
In the parameter setting “send on change of status / after bus
voltage recovery”, the current value of the object no. 143 is
sent automatically after a change and after bus voltage recovery.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/18
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.4
Groups
5.4.1. Essential information
5.4.2 Parameter description
Parameter
The “Groups” parameter window enables an overview
of how many switching / dimming groups were assigned
to the Gateway N 141/02. When the cursor is placed in
the first row under the column header “Name”, a line
appears explaining the abbreviations used in the
header.
A new group with pre-set parameters can be entered
using the “New” button.
Double-clicking on a list entry or on the "Edit" button the
parameter window “Group, parameters” (see below)
opens, via which the pre-set parameters can be
changed.
A group and its parameter settings can be copied via
the “Copy” button and then inserted as a new group via
the “Insert” button.
A group can be completely deleted via the “Delete” button.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Settings
Group name (30 char.)
A name of a maximum 30 characters long can be assigned to
a group via this parameter. This name is also used with the
communication objects belonging to this group.
Operation mode
normal mode
normal / night mode
permanent mode
1-level time switch mode
2-level time switch mode
This parameter enables switching between normal mode,
normal / night mode, permanent mode and time switch mode.
If the parameter is set to “Normal / night mode”, the group is
integrated with the night mode.
No control parameters are created for the group on “permanent mode”. The ECG is permanently switched on to the set
On value. All other parameters, with the exception of behaviour in the event of bus voltage failure and recovery, cannot
be set. However, the status objects are available.
A time switch mode can be launched via an ON telegram, a
dimming telegram (brighter/darker) or a dimming value telegram.
When “1-level time switch mode” respectively “2-level time
switch mode” is set and On period 1 respectively On period 2
has expired the output is dimmed down with a dimming time
set by the parameter “dimming time from 0%--100% on
switching on/off [hh:mm:ss]" for switching on/off.
When “2-level time switch mode” is set the interim value (i.e.
the dimming value following the elapse of On period 1) is
gradually brightened using the dimming time established via
the “dimming time from 0%-100% when setting dimming value
[hh:mm:ss]” parameter.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/19
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
dimming
time
8-bit-value
On
period
2
dimming
time
On/Off
On
period
1
brightness
dimming
time
On/Off
Parameter
Settings
Graph
Via the “Diagram” button it is possible, when “1-level time
switch mode” and “2-level time switch mode” are set, to call
up a window that shows the elapsed time of the configured
time switch mode following receipt of an On telegram.
time
ON Telegramm
ON period 1
00:02:00
[hh:mm:ss]
Here the time is entered after which (in the case of 1-level
time switch mode) the lighting is switched off or after which
the interim dimming value is to be gradually achieved (in the
case of 2-level time switch mode).
The On period is a maximum of 15 hours (15:00:00).
The set On period 1 commences only after the On dimming
value has been achieved following the launch of the time
switch mode via On / dimming / value telegrams.
hh= for hours; mm= for minutes; ss= for seconds.
On period 2
[hh:mm:ss]
00:00:30
hh= for hours; mm= for minutes; ss= for seconds.
Here, in 2-level time switch mode, the time is entered that
commences after the interim dimming value has been
achieved (i.e. according to the dimming value after On period
1 has elapsed). When this time elapses the group is switched
off.
On period 2 is a maximum of 15 hours (15:00:00).
When On period 2 is set to 00:00:00 then the time for the
interim dimming value does not automatically elapse, i.e. the
group is not automatically switched off. The diagram does not
reflect this setting.
Dimming value after period 5%
10%, 15%, 20%, 25%, 30%,
1
35%, 40%, 45%, 50%, 55%,
60%, 65%, 70%, 75%, 80%
This parameter determines the interim value that is set after
period 1. The configured value is limited to the range between
minimum/maximum dimming value. For technical reasons, the
percentages are rounded values, and have a precision of +/1%.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Parameter
Settings
no action
Behaviour on bus voltage
starting value
failure of KNX or DALI
maximum dimming value
minimum dimming value
dimming value on emergency
switch OFF
With this parameter it is established which dimming value the
group is to assume if communication with the ECGs is no
longer possible due to failure of the KNX bus voltage, failure
of the power supply for the Gateway N 141/02 or due to short
circuit/interruption of the DALI bus cable. The presupposition
is that the power supply of the ECGs is still present.
If this parameter is on “starting value” and if the “starting
value” of the group is configured with “last value”, the group
will be set to maximum brightness in the event of bus voltage
failure.
See appendix item 6.
as before bus voltage failBehaviour on bus voltage
ure
recovery of KNX or DALI
starting value
maximum dimming value
minimum dimming value
switch OFF
last received dimming value
This parameter establishes which dimming value the group is
to assume after both the KNX bus voltage and the power
supply voltage are again present on Gateway N 141/02. This
presupposes that the power supply for the ECGs of the group
is already present. If this parameter is on “starting value” and
if the “starting value” of the group is configured with “last
value”, the group will be set to the dimming value before bus
voltage failure in the event of bus voltage recovery. If the
group was switched off when the bus voltage failed, in this
case the minimum dimming value will be set.
Should the power supply voltage of one ECG in the group be
recovered at a later time, this will be set to the current dimming value of the group, where applicable, after a maximum
of 30 seconds.
See appendix item 6.
Warn before switch off in
night mode and 1-level time
switch mode
yes
no
This parameter is used to set whether the group is to indicate
approximately 30 seconds before switch off that the group will
soon be switched off by dimming to 50% of the previous dimming value in night mode or 1-level time switch mode.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/20
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Parameter
Settings
Switch on/off via dimming
brighter/darker
not possible
switch ON possible
switch OFF possible
switch ON and OFF possible
Accept dimming value
immediately
only when ON
If a switched off group is to be switched on via the receipt of a
relative “brighter” dimming value, this parameter must be set
to “switch ON possible”. In this case the group is always
switched on first, the minimum dimming value reached and
then, from here, the group is brightened with the configured
dimming time for dimming by the received relative dimming
value. Switching off by darkening is not possible with this setting.
If a group is to be switched off by dimming its brightness to a
value below the minimum dimming value, this parameter must
be set to “switch OFF possible”. Switching on by brightening
is not possible with this setting. If both switching on and
switching off the group under the basic conditions described
above is to be possible, this parameter must be set to “switch
ON and switch OFF possible”.
Switch on/off via set value
not possible
ON, if dimming value >= min.
dimming value
OFF, if dimming value < min.
dimming value
switch ON and OFF possible
ON, if dimming value > 0%
and OFF, if dimming value =
0%
If, while switched off, switching on the group through the receipt of a dimming value that is as high or higher than the
minimum dimming value, is to be possible, this parameter
must be set to “ON, if dimming value >= min. dimming value”.
The group is then switched on and the dimming value, depending on the configured dimming time for dimming value
setting, is either switched on immediately or gradually brightened. If the received dimming value is under the minimum
dimming value, the group remains switched off. Switching off
the group by setting the dimming value is not possible with
this setting. If the group is switched on and this parameter is
set to “OFF, if dimming value < min. dimming value”, the receipt of a telegram with a dimming value lower than the minimum dimming value for darkening (with the configured dimming time for setting the dimming value) leads to the minimum dimming value and then to the switching off of the
group. Switching on the group by setting the dimming value is
not possible with this setting. If this parameter is set to “switch
ON and OFF possible”, the group is switched on if the received dimming value is higher than or equal to the minimum
dimming value and it is switched off if the received dimming
value is under the minimum dimming value.
If this parameter is set to “ON, if dimming value > 0% and
OFF, if dimming value = 0%”, every dimming value > 0%
leads to the switching on of the group. If the dimming value is
below the minimum dimming value, the group is dimmed to
the minimum dimming value. Only following receipt of a dimming value = 0% is the group switched off.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
This parameter specifies whether the luminaire carries out a
dimming value telegram received via the bus when it is in the
OFF state (accept immediately) or whether it stores the dimming value and selects the value after the next ON telegram.
The dimming value is then also accepted immediately if the
luminaire / group is already switched on.
Starting value
(limited by minimum/maximum dimming value)
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 40%, 30%, 20%, 10%,
last received dimming value,
dimming value at switching
off
This parameter indicates the On value on receipt of an ON
switching telegram. The configured value is limited to the
range between minimum and maximum dimming value. When
switched on twice, not the switching on value but the maximum dimming value is switched on. For technical reasons,
the percentages are rounded values, and have a precision of
+/- 1%.
Note on setting “last received dimming value”:
The minimum dimming value will always be switched onto
when switching on, even if the last received dimming value <
minimum dimming value (also applies for the value 0). This
also applies even if there is no “last received dimming value”.
0,5%, 1% , 3%,5%, 10%,
Minimum dimming value
15%, 20%, 25%, 30%, 35%,
40%, 45%, 50%, 60%, 70%,
100%
The minimum dimming value is established via this parameter. Only as far as this value can be reached when darkening.
For technical reasons, the percentages are rounded values,
and have a precision of +/- 1%.
Maximum dimming value
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 40%, 30%
The maximum dimming value is established via this parameter. Only as far as this value can be reached when brightening. For technical reasons, the percentages are rounded values, and have a precision of +/- 1%.
Dimming value on emer100%, 95%, 90%, 85%, 80%,
gency
75%, 70%, 65%, 60%, 55%,
50%, 45%, 40%, 35%, 30%,
25%, 20%, 15%, 10%, 5%,
no change
This parameter defines the dimming value of the luminaire /
group on receipt of an “Emergency operation ON” telegram.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/21
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Dimming time for switching
on/off from 0%-100%
[hh:mm:ss]
00:00:00
5.5
ECGs
5.5.1 Essential information
This parameter establishes the dimming time in which the
group gradually brightens to the On value following an ON
telegram or, respectively, darkens to the Off value following
an OFF telegram, in which process the set dimming time applies for dimming from 0% to 100%. The On or, respectively,
Off value is switched on at setting 00:00:00 .
The dimming time can be adjusted to a maximum 15 hours
(15:00:00).
hh= for hours; mm= for minutes; ss= for seconds.
Dimming time for dimming
brighter/darker from
0%-100% [in seconds]
1-255
10
This parameter determines the time in which dimming from
0% to 100% is achieved during dimming.
Dimming time for set value 00:00:00
from 0%-100% [hh:mm:ss]
This parameter determines the time in which the new value is
achieved following receipt of an 8-bit dimming value. The set
time applies for a dimming process from 0% to 100%. The
new dimming value is switched on during setting.
hh= for hours; mm= for minutes; ss= for seconds.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
The “ECGs” parameter window enables an overview of
how many DALI ECGs are attached to the Gateway
and whether or, respectively, to which group an ECG
has been assigned. When the cursor is placed in the
first row under the column header “Nr.”, a line appears
explaining the abbreviations used in the header.
A new ECG with pre-set parameters can be entered using the “New” button.
Double-clicking on a list entry or on the "Edit" button the
parameter window "ECG, parameters" (see below)
opens, via which the pre-set parameters can be
changed.
An ECG and its parameter settings can be copied via
the “Copy” button and then inserted as a new ECG via
the “Insert” button.
An ECG can be completely deleted via the “Delete” button.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/22
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Settings
Name (50 char.)
A name of a maximum 50 characters long can be assigned to
an ECG via this parameter. This name is also used with the
communication objects belonging to this ECG.
Group number
none
1, 2, ... 16
Group numbers only appear for those groups that have been
created.
The ECG can be assigned to a group via this parameter. In
this case entry of all ensuing parameters (except the CIN,
DALI device type, fluorescent lamp, and emergency luminaire) is deactivated, since the parameter setting of the group
is then automatically assigned to the ECG. The diagram is activated if time switch mode is selected.
When “None” is selected the ECG is marked with n.a. (= not
assigned) in the ECG list.
Group name
On
period
1
dimming
time
8-bit-value
On
period
2
dimming
time
On/Off
Parameter
brightness
5.5.2. Parameter description
normal mode
normal / night mode
permanent mode
1-level time switch mode
2-level time switch mode
This parameter enables switching between normal mode,
normal / night mode, permanent mode and time switch mode.
If the parameter is set to “Normal / night mode”, the group is
integrated with the night mode.
No control parameters are created for the group on “permanent mode”. The ECG is permanently switched on to the set
On value. All other parameters, with the exception of behaviour in the event of bus voltage failure and recovery, cannot
be set. However, the status objects are available.
A time switch mode can be launched via an ON telegram, a
dimming telegram (brighter/darker) or a dimming value telegram. The set On value is gradually brightened using the
dimming time established via the “dimming time from 0%-100% on switching on/off [hh:mm:ss]" parameter. Darkening
is effected following the elapse of On period 1 using the same
dimming time as on switch-on.
When “2-level time switch mode” is set the interim value (i.e.
the dimming value following the elapse of On period 1) is
gradually brightened using the dimming time established via
the “dimming time from 0%-100% when setting dimming value
[hh:mm:ss]” parameter.
Graph
Via the “Diagram” button it is possible, when “1-level time
switch mode” and “2-level time switch mode” are set, to call
up a window that shows the elapsed time of the configured
time switch mode following receipt of an On telegram.
dimming
time
On/Off
Operation mode
none
Only those group names appear that have been created.
The ECG can be assigned to a group via this parameter. The
name of the assigned group is displayed. This name may be
up to 30 characters long. The name displayed (e.g. the default name) of the assigned group can only be changed via
the “Group” parameter window.
If the ECG is not assigned to a group “none” will be displayed.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
time
ON Telegramm
ON period 1
[hh:mm:ss]
00:02:00
Here the time is entered after which (in the case of 1-level
time switch mode) the lighting is switched off or after which
the interim dimming value is to be gradually achieved (in the
case of 2-level time switch mode).
The On period is a maximum of 15 hours (15:00:00).
The set On period 1 commences only after the On dimming
value has been achieved following the launch of the time
switch mode via On / dimming / value telegrams.
hh= for hours; mm= for minutes; ss= for seconds.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/23
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Parameter
Settings
On period 2
[hh:mm:ss]
00:00:30
Warn before switch off in
night mode and 1-level time
switch mode
yes
no
hh= for hours; mm= for minutes; ss= for seconds.
Here, in 2-level time switch mode, the time is entered that
commences after the interim dimming value has been
achieved (i.e. according to the dimming value after On period
1 has elapsed). When this time elapses the ballast is switched
off.
On period 2 is a maximum of 15 hours (15:00:00).
When On period 2 is set to 00:00:00 then the time for the
interim dimming value does not automatically elapse, i.e. the
ballast is not automatically switched off. The diagram does
not reflect this setting.
Dimming value after period 5%
10%, 15%, 20%, 25%, 30%,
1
35%, 40%, 45%, 50%, 55%,
60%, 65%, 70%, 75%, 80%
This parameter determines the interim value that is set after
period 1. The configured value is limited to the range between
minimum/maximum dimming value. For technical reasons, the
percentages are rounded values, and have a precision of +/1%.
no action
Behaviour on bus voltage
starting value
failure of KNX or DALI
maximum dimming value
minimum dimming value
dimming value on emergency
switch OFF
With this parameter it is established which dimming value the
ECG is to assume if communication with the ECGs is no
longer possible due to failure of the KNX bus voltage, failure
of the power supply for the Gateway N 141/02 or due to short
circuit/interruption of the DALI bus cable. The presupposition
is that the power supply of the ECGs is still present. If this parameter is on “starting value”, the ECG is set to minimum
brightness in the event of bus voltage failure.
See also appendix item 6.
no action
Behaviour on bus voltage
as before bus voltage failrecovery of KNX or DALI
ure
starting value
maximum dimming value
minimum dimming value
switch OFF
last received dimming value
This parameter establishes which dimming value the ECG is
to assume after both the KNX bus voltage and the power
supply voltage are again present on Gateway N 141/02. This
presupposes that the power supply for the ECGs is already
present. If this parameter is on “starting value”, the ECG is set
to the dimming value before bus voltage failure in the event of
bus voltage recovery. If the ECG was switched off when the
bus voltage failed, in this case the maximum dimming value
will be set.
See also appendix item 6.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
This parameter is used to set whether the group is to indicate
approximately 30 seconds before switch off that the group will
soon be switched off by dimming to 50% of the previous dimming value in night mode or 1-level time switch mode.
Switch on/off via dimming
brighter/darker
not possible
switch ON possible
switch OFF possible
switch ON and OFF possible
If a switched off group is to be switched on via the receipt of a
relative “brighter” dimming value, this parameter must be set
to “switch ON possible”. In this case the group is always
switched on first, the minimum dimming value reached and
then, from here, the group is brightened with the configured
dimming time for dimming by the received relative dimming
value. Switching off by darkening is not possible with this setting.
If a group is to be switched off by dimming its brightness to a
value below the minimum dimming value, this parameter must
be set to “switch OFF possible”. Switching on by brightening
is not possible with this setting. If both switching on and
switching off the group under the basic conditions described
above is to be possible, this parameter must be set to “switch
ON and switch OFF possible”.
Switch on/off via set value
not possible
ON, if dimming value >= min.
dimming value
OFF, if dimming value < min.
dimming value
switch ON and OFF possible
ON, if dimming value >% and
OFF, if dimming value = 0%
If, while switched off, switching on the group through the receipt of a dimming value that is as high or higher than the
minimum dimming value, is to be possible, this parameter
must be set to “ON, if dimming value >= min. dimming value”.
The group is then switched on and the dimming value, depending on the configured dimming time for dimming value
setting, is either switched on immediately or gradually brightened. If the received dimming value is under the minimum
dimming value, the group remains switched off. Switching off
the group by setting the dimming value is not possible with
this setting. If the group is switched on and this parameter is
set to “OFF, if dimming value < min. dimming value”, the receipt of a telegram with a dimming value lower than the minimum dimming value for darkening (with the configured dimming time for setting the dimming value) leads to the minimum dimming value and then to the switching off of the
group. Switching on the group by setting the dimming value is
not possible with this setting. If this parameter is set to “switch
ON and OFF possible”, the group is switched on if the received dimming value is higher than or equal to the minimum
dimming value and it is switched off if the received dimming
value is under the minimum dimming value.
If this parameter is set to “ON, if dimming value > 0% and
OFF, if dimming value = 0%”, every dimming value > 0%
leads to the switching on of the group. If the dimming value is
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/24
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
below the minimum dimming value, the group is dimmed to
the minimum dimming value. Only following receipt of a dimming value = 0% is the group switched off.
Accept dimming value
Parameter
Settings
Dimming value on emergency
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 45%, 40%, 35%, 30%,
25%, 20%, 15%, 10%, 5%,
no change
immediately
only when ON
This parameter specifies whether the luminaire carries out a
dimming value telegram received via the bus when it is in the
OFF state (accept immediately) or whether it stores the dimming value and selects the value after the next ON telegram.
The dimming value is then also accepted immediately if the
luminaire / group is already switched on.
This parameter defines the dimming value of the luminaire /
group on receipt of an “Emergency operation ON” telegram
on object 8 (“Emergency operation”).
Device ID (CIN)
16-figure ID
The company OSRAM assigns every DALI device factoryside a clear 16-figure identification number (CIN = Chip Identification Number), which can be entered here and via which
the device can be directly addressed during commissioning.
This identification number should be entered as 8 two-figure
numbers in order to make entry easier.
Remove device assignment (ECG # = x)
Remove the device ID
By clicking on the entry field the 16-figure CIN is set to the default value “FFFFFFFFFFFFFFFF” (i.e. “no device ID assigned”).
After removing the device ID the parameter text changes to
“Remove the device ID”. Also this is the parameter text when
no ECG has been assigned.
Starting value
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 40%, 30%, 20%, 10%,
last received dimming value,
dimming value at switching
OFF
This parameter indicates the On value on receipt of an ON
switching telegram. The configured value is limited to the
range between minimum and maximum dimming value. For
technical reasons, the percentages are rounded values, and
have a precision of +/- 1%.
Note on setting “last received dimming value”:
The minimum dimming value will always be switched onto
when switching on, even if the last received dimming value <
minimum dimming value (also applies for the value 0). This
also applies even if there is no “last received dimming value”.
0.5%, 1% , 3%,5%, 10%,
Minimum dimming value
15%, 20%, 25%, 30%, 35%,
40%, 45%, 50%, 60%, 70%,
100%
The minimum dimming value is established via this parameter. Only as far as this value can be reached when darkening.
For technical reasons, the percentages are rounded values,
and have a precision of +/- 1%.
Maximum dimming value
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 40%, 30%
The maximum dimming value is established via this parameter. Only as far as this value can be reached when brightening. For technical reasons, the percentages are rounded values, and have a precision of +/- 1%.
This parameter establishes the dimming time in which the
group gradually brightens to the On value following an ON
telegram or, respectively, darkens to the Off value following
an OFF telegram, in which process the set dimming time applies for dimming from 0% to 100%. The On or, respectively,
Off value is switched on at setting 00:00:00 .
The dimming time can be adjusted to a maximum 15 hours
(15:00:00).
hh= for hours; mm= for minutes; ss= for seconds.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Dimming time for switching
on/off from 0%-100%
[hh:mm:ss]
Dimming time for dimming
brighter/darker from
0%-100% [in seconds]
00:00:00
1-255
10
This parameter determines the time in which dimming from
0% to 100% is achieved during dimming.
Dimming time for set value 00:00:00
from 0%-100% [hh:mm:ss]
This parameter determines the time in which the new value is
achieved following receipt of an 8-bit dimming value. The set
time applies for a dimming process from 0% to 100%. The
new dimming value is switched on during setting.
hh= for hours; mm= for minutes; ss= for seconds.
DALI device type
0=Flourescent lamp
1=Self-contained emergency
lighting
2=Discharge lamp
3=Low voltage halogen lamp
4= Incandescent lamp (dimmer)
5=10V Converter
6=LED module
7 = switching function
This parameter sets the corresponding lamp type of a DALI
device.
Note:
Any DALI device with an unknown DALI type can be discovered and assigned to one of the supported DALI types.
Fluorescent lamp
without additional function
with brightness control
This parameter becomes visible if the parameter “DALI device
type” has been set to “0”.
If a brightness sensor is directly connected to the DALI ballast
for local brightness control by the DALI ballast, dimming
brighter / darker will lead to a corresponding set-point shifting
if this parameter is set to “with brightness control”. This shift-
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/25
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
ing is only temporarily valid until the lamp is switched off. If
the lamp is switched on again the calibrated set-point will be
used for brightness control.
5.6
Self-contained emergency ECGs
5.6.1 Essential information
Emergency luminaire
self-contained with 1 DALI
device
self-contained with 2 DALI
devices
This parameter becomes visible if the parameter “DALI device
type” has been set to “1”.
By this parameter an emergency luminaire can be marked as
a self-contained emergency luminaire with either one or two
DALI devices.
Emergency luminaire
no
central-battery supplied
This parameter becomes visible if the parameter “DALI device
type” has not been set to “1”.
With this parameter a luminaire can be marked as an emergency luminaire with one DALI device powered by a central
battery or other source of emergency power in case of emergency.
When the ballast of a luminaire marked as an emergency luminaire is assigned to a group, then the failure of the lamp or
of the ballast of this luminaire is marked in the failure status of
the group it is assigned to. Bit 22 (lamp for emergency luminaire failed) respectively Bit 30 (ballast for emergency luminaire failed) are set. See information on object 19.
The parameter window “Self-contained emergency
ECGs” enables an overview of how many DALI ECGs
in emergency luminaires are attached to the Gateway
and whether or, respectively, to which group an ECG
has been assigned. When the cursor is placed in the
first row under the column header “Nr.”, a line appears
explaining the abbreviations used in the header.
A new ECG with pre-set parameters can be entered using the “New” button.
Double-clicking on a list entry or on the "Edit" button the
parameter window "ECG, emergency luminaire parameters" (see below) opens, via which the pre-set parameters can be changed.
An ECG and its parameter settings can be copied via
the “Copy” button and then inserted as a new ECG via
the “Insert” button.
An ECG can be completely deleted via the “Delete” button.
Note:
To avoid concurrent testing of all self-contained emergency ECGs and to avoid overlapping of different tests
the ECGs are automatically configured such that the
tests start staggered over time. The time offset depends
on the DALI short address assigned to the specific
ECG.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/26
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
Emergency value of inverter
5%
10%
15%
20%
25%
….
85%
90%
95%
100%
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. It defines the dimming value of the luminaire / group in case of an
AC 230V power failure. This value is downloaded by the gateway into the inverter of the luminaire.
Inverter prolong time on
emergency op. OFF
5.6.2. Parameter description
Parameter
Settings
Name (50 char.)
A name of a maximum 50 characters long can be assigned to
an emergency luminaire (ECG) via this parameter. This name
is also used with the communication objects belonging to this
emergency luminaire (ECG).
Group number
none
1, 2, ... 16
Group numbers only appear for those groups that have been
created.
Via this parameter the emergency luminaire (ECG) can be
assigned to a group or marked as a stand-alone emergency
luminaire.. An emergency luminaire can only be assignd to
one group. Up to 64 luminaires may be assigned to a group.
When an emergency luminaire is assigned to a group all parameters for this group automatically apply to this emergency
luminaire.
When “None” is selected the ECG is marked with n.a. (= not
assigned) in the ECG list.
Group name
none
Only those group names appear that have been created.
The emergency luminaire (ECG) can be assigned to a group
via this parameter. The name of the assigned group is displayed. This name may be up to 30 characters long. The
name displayed (e.g. the default name) of the assigned group
can only be changed via the “Group” parameter window.
If the ECG is not assigned to a group “none” will be displayed.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
0 seconds
30 seconds
1 minute
2 minutes
5 minutes
10 minutes
15 minutes
20 minutes
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. At
mains recovery the supply of the lamp from battery will be
continued for the time defined by this parameter.
Interval of short duration
tests (weeks)
0,
1, 2, 3, ... 27
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. The
selected value defines the time interval between two short duration tests. This value is stored in the gateway which controls
the timer for this interval. The short duration test is started the
first time automatically after the download into the gateway
according to the set interval.
If this parameter is set to 0 (= “never”) no short duration test
will be executed.
Interval of long duration
tests (weeks)
0,
1, 2, 3, ... 52
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. The
selected value defines the time interval between two long duration tests. This value is downloaded by the gateway into the
inverter of the self-contained luminaire. The test is started the
first time automatically after the download according to the set
interval.
If this parameter is set to 0 (= “never”) no duration test will be
executed.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/27
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Parameter
Settings
5.7
Scenes
Interval of function tests
(days)
0, 1, 2, 3, 4, 5, 6, 7,
8,
5.7.1 Scenes parameter window description
9, ... 28
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. The
selected value defines the time interval between two function
tests. This value is downloaded by the gateway into the inverter of the self-contained luminaire. The test is started the
first time automatically after the download according to the set
interval.
If this parameter is set to 0 (= “never”) no function test will be
executed.
Duration of short duration
tests
5 minutes
10 minutes
15 minutes
20 minutes
30 minutes
45 minutes
60 minutes
This parameter is faded-in only when the parameter “Emergency luminaire” has been set to “Yes, self-contained”. The
selected value defines the duration of a short duration test.
Note:
Self-contained emergency ballasts automatically switch
over to their battery when mains power fails.
In exceptional situations, e.g. during the building phase,
it may be required to turn off the power to the emergency luminaires but without the self-contained emergency luminaires switching into emergency mode.
The KNX-DALI Gateway N141/02 supports this.
A1
A2
A3
A5
The “Scenes” parameter window enables an overview
of how many scenes have already been configured and
which groups are integrated in a scene in each case.
When the cursor is placed in the first row under the column header “Name”, a line appears explaining the abbreviations used in the header.
A new scene can be added using the “New” button.
Double-clicking on a list entry or on the "Edit" button the
parameter window "Scene, parameters" (see below)
opens, via which the groups belonging to a scene can
be changed.
A scene and its parameter settings can be copied via
the “Copy” button and then inserted as a new scene via
the “Insert” button.
A scene can be completely deleted via the “Delete” button.
A4
A10
A9
A8
A6
A7
When the „Off“-button of the button pair A4 is pressed
for more than 10 seconds, then the KNX-DALI Gateway
N141/02 sets an inhibit flag in the emergency ballasts.
This action is acknowledged by briefly flashing LED A5.
If power is turned off within 15 minutes after setting the
inhibit flag, e.g. by switching off the circuit breakers,
then the emergency ballasts do not enter the emergency mode and are turned off until power resumes. After power resumed the emergency ballasts run in normal operation mode and the inhibit flag is reset.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
A new group or ECG can be added in the “Scene, parameters” window using the “New” button. Doubleclicking on a list entry or on the "Edit" button the “Scene
value” parameter window further down now opens.
A marked group or ECG can be deleted in the “Scene,
parameters” window with the “Delete” button.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/28
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
channel 2 are to be dimmed from 100% to 20%, the dimming
process should be completed simultaneously for both lights.
Channel 1 will therefore have a flatter dimming curve than
channel 2.
The dimming time of a scene is independent of the dimming
times set for the groups.
Note:
Via the “Scene value” window the group/ECG belonging
to the scene can be changed, as well as assigned a
dimming value (scene value) to which the group/ECG in
this scene is to be set. If another group/ECG than the
group/ECG displayed on opening of the window is selected via the “ECG/Group” parameter, this leads to the
deleting (replacement) of the previous group/ECG in
the respective scene.
5.7.2 Parameter description
Note:
Time functions cannot be executed within a scene.
Parameter
Settings
Name (50 char.)
A name of a maximum 50 characters long can be assigned to
a scene via this parameter.
Scene number
1-64
A number in the range of 1 to 64 (scene number) can be assigned to the scene via this parameter. If a certain scene is to
be saved or recalled, comm. object 3 must contain the number [scene number 1].
Dimming time
jump
0.7 seconds
1.0 seconds
1.4 seconds
2.0 seconds
2.8 seconds
4.0 seconds
5.7 seconds
8.0 seconds
11.3 seconds
16.0 seconds
22.6 seconds
32.0 seconds
45.3 seconds
64.0 seconds
90.5 seconds
This parameter “Dimming time” corresponds, when recalling a
scene, to the time in which the dimming process for all lights
together is completed.
If for example the lights of channel 1 are at 50% and if 90%
dimming is to take place in this scene and if the lights of
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
Different dimming times (both when brightening to a new
value and during joint brightening to new values in scenes)
lead to re-programming of the internal dimming time of all
DALI ECGs attached to the Gateway N 141/02 when sending
the dimming value / calling up a scene. If dimming times are
constantly changed at very brief intervals (this can occur for
example in the case of coloured light control via rapidly
changing scenes), this can lead to damage to the ECGs of
some manufacturers in the long term. This problem does not
occur if the same dimming times are used for all scene recalls
and where possible the standard dimming time of 0.7 seconds
is used in the process.
ECG / Group
All groups / ECGs assigned to a scene are listed. In total up
to 16 groups and up to 64 ECGs can be assigned. The already projected groups are identifiable by the changed group
name (and the not yet projected groups by their name “New
group xy”). Only the projected groups/ECGs are set to the
configured brightness when the scene is recalled. All nonprojected groups/ECGs are ignored when the scene is recalled.
Scene value
0-100 %
(0% - 100%)
100 %
This value indicates the dimming value as a percentage which
the group (if projected) assumes when this scene is recalled.
The value can be projected for each group for the first time
here. The data are overwritten on subsequent saving of the
scene using a scene button. The application program automatically limits the entered value to the value range between
minimum and maximum dimming value.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/29
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.8
Effects
5.8.1. Essential information
The “Effects” parameter window enables an overview of
how many effects have already been configured and
how many steps and run-throughs they consist of in
each case.
When the cursor is placed in the first row under the column header “Name”, a line appears explaining the abbreviations used in the header.
A new effect can be added using the “New” button.
Double-clicking on a list entry or on the "Edit" button
opens the parameter window "Effect, parameters" (see
below).
An effect and its settings can be completely copied in
the “Effects” window via the “Copy” button and then inserted as a new effect via the “Insert” button.
An effect can be completely deleted via the “Delete”
button.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
The “Effect, parameters” parameter window provides an
overview of how many steps the effect consists of and
what happens step by step: whether an individual ECG
or a group are switched or dimmed or whether a scene
is recalled and which interval should be observed following every step. If the cursor is placed in the header,
a line appears explaining the abbreviations used in the
header.
A new step can be added using the “New” button.
Double-clicking on a list entry or on the "Edit" button
opens the parameter window further down with the
name of the effect being revised and the step number
to be revised. The ECGs, groups, scenes and parameters belonging to a step can be selected and changed
via this window. 16 effects with a total of 500 steps are
possible.
A step and its settings can be completely copied in the
“Effects, parameter” window via the “Copy” button and
then inserted as a new step via the “Insert” button.
A step can be completely deleted via the “Delete” button.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/30
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.8.2 Parameter description
Parameter
Parameter
Dimming value (in %)
Settings
Name (50 char.)
A name of a maximum 50 characters long can be assigned to
an effect via this parameter.
Effect number:
1-64
A number in the range of 1 to 64 (effect number) can be assigned to the effect via this parameter. If a certain effect is to
be saved or recalled, comm. object 4 must contain the number [effect number 1].
Number of cycles
0-500
(0=unlimited):
1
With this parameter it is established how often the effect
should run upon recall. If the parameter is set to “0”, the effect
runs until it is either stopped when its number is called up and
bit 7 set to log. 0 or this takes place when another effect is
called up.
Filament heating ON
Filament heating in ECGs can be switched on in advance via
this parameter, so that rapid effects can be carried out even
with fluorescent lamps. This presupposes that the ECG
manufacturer support pre-heating, as is the case for example
with OSRAM with ECGs of type QTi. The heating automatically switches itself off again after 15 minutes if the ECG has
not been controlled within that time.
Parameter
Settings
Settings
100%, 95%, 90%, 85%, 80%,
75%, 70%, 65%, 60%, 55%,
50%, 45%, 40%, 35%, 30%,
25%, 20%, 15%, 10%, 5%
This parameter is only available if an ECG or a group is controlled. It sets the dimming value to which the ECG or group in
this step is to be dimmed. For technical reasons, the percentages are rounded values, and have a precision of +/- 1%.
Dimming time
jump
0.7 seconds
1.0 seconds
1.4 seconds
2.0 seconds
2.8 seconds
4.0 seconds
5.7 seconds
8.0 seconds
11.3 seconds
16.0 seconds
22.6 seconds
32.0 seconds
45.3 seconds
64.0 seconds
90.5 seconds
The ECG or, respectively, group is dimmed to the dimming
value set in the effect step using the dimming time set here.
This dimming time can be different one to the dimming time
assigned to the group, ECG or, respectively, scene.
Note:
Different dimming times (both when brightening to a new
value and during joint brightening to new values in scenes)
lead to re-programming of the internal dimming time of all
DALI ECGs attached to the Gateway N 141/02 when sending
the dimming value / calling up a scene. If dimming times are
constantly changed at very brief intervals (this can occur for
example in the case of coloured light or effect control via rapidly changing scenes), this can lead to damage to the ECGs
of some manufacturers in the long term. This problem does
not occur if the same dimming times are used for all scene
recalls and where possible the standard dimming time of 0.7
seconds is used in the process.
Delay before next step
00:01.0
[mm:ss,s]
This time indicates how long the interval following completion
of this step is before the next step is launched.
Step Nr.
1-500
This number is used for consecutive numbering of the individual effect steps. A total of up to 500 steps is possible.
Control
List of names with all projected ECGs, groups and
scenes.
This parameter is used to set which ECG or which group in
this step is to be switched on or dimmed or which scene is to
be launched.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/31
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.9
Export / import
Conversions of configurations of the GE 141 (802311)
and N 141 (802701) to the configuration of the N
141/02 have to be done using an external conversion
program. This program support the following conversions as far as the individual parameters can be transferred:
GE141 802311 Æ N141/02
981C03
N141
802701 Æ N141/02
981C03
The export mechanism makes it possible to save the
parameter settings of a KNX/DALI Gateway N 141/02 to
a file. The numbers and names of the DALI ECGs assigned upon commissioning are also exported to this
file. These exported numbers, names and group allocations are only valid, however, for as long as no new initialization of ECGs is carried out on the associated KNX
/ DALI Gateway N 141/02 or, respectively, no other application has been loaded into the device.
The export file can be used, for example, to import the
parameter settings into another project data base or
into a newer version of the application program.
A checksum protects the file containing the exported
configuration against tampering. The import mechanism
will not accept a file with an invalid checksum.
After the configuration has been successfully exported
the following window appears.
If the question is answered with „Yes“ the current configuration settings are saved automatically into the
same export file just created or used when the parameter window is closed.
Note:
The import function only imports data from the application program 07 B0 KNX/DALI Gateway 981Cxx
(x=1…7, i.e. its own application). Conversion of the
data of other application programs in order then to be
able to load them into the N 141/02 are not part of the
functional scope of the import function.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/32
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.10
Commissioning
5.10.1 instabus commissioning
Commissioning of the KNX / DALI Gateway N 141/02
takes these steps described here:
a) The power supply must be present on the DALI
devices. This also applies for power supply of the
KNX / DALI Gateway N 141/02. All DALI participants must be connected with the KNX /DALI
Gateway N 141/02.
b) The physical address is loaded into the KNX / DALI
Gateway N 141/02.
c) The configuration is loaded into the KNX / DALI
Gateway N141/02.
d) The parameter window is opened while the bus
connection is active. It may take up to one minute
before a message appears if the KNX / DALI Gateway is not connected to the bus.
5.10.2. Commissioning of the DALI devices
When searching for ballasts (ECGs) not all expected
ballasts may appear in the list in the right window. In
such a case use the button „Add dummy ballast“ to add
a ballast (ECG) and assign it as a place holder to a
luminaire before commissioning. After a download the
KNX-DALI gateway annuciates an ECG error for a
dummy ECG. After missing ballasts have been installed
or the installation of ballasts has been corrected the
ballasts have to be assigned to their associated
luminaires instead of the respective dummy ECGs. The
new configuration has to be downloaded to the KNXDALI gateway.
Use the button “Delete dummy ballast” to delete a place
holder.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
The column “Dummy” in the list on the right displays if a
ballast was added as a place holder.
The firmware version of the KNX/DALI Gateway (in the
screen shot: V03) is displayed in the Commissioning
window when a connection exists to the KNX/DALI
Gateway.
Button
Commissioning mode
automatic
flash
switch OFF
switch ON
function test
This parameter is used to set how an individual DALI device
can be identified: “automatically” (by flashing or switching off,
depending on the recognized luminant type that it attached to
the DALI device), via “flashing”, via “switching OFF”, or via
“switching ON” the luminant attached to the DALI device.
Search ballasts
All DALI devices attached to the KNX/DALI Gateway
N 141/02 and operational are searched for by pressing this
button. A search process that could last for a number of minutes begins. The DALI devices found first appear in the narrow window on the right-hand side underneath the “Search
DALI devices” button with the titles “ECG” and “Type” (type of
the DALI device). Only figures from 1 to 64 are indicated as
the ECG number of a DALI device (therefore always the short
address +1). For a DALI device displayed in the left-hand
window, to which no found device has yet been allocated, the
ECG number is displayed as “na” (not allocated).
This search must also be carried out when DALI devices are
replaced or supplemented.
Further searches may follow after the first one, if for example
further DALI devices have been installed or replaced. It can
also be the case that DALI devices already found during
commissioning are no longer present on the power supply in
the event of a further search. This is displayed via an “X” in
the error column. The table can be sorted according to every
column, so that the defective DALI devices can be controlled
in a very easy-to-view manner. With renewed searching the
defective DALI devices, if they are now operational again, are
also displayed again with an error flag.
Note: Before searching for DALI devices all installed DALI devices must be connected with the KNX / DALI Gateway
N 141/02 and ready for operation. If DALI devices with clear
CIN identification are found and if these are already contained
with their CIN in the left-hand window, the found device is allocated immediately and does not even appear on the righthand side.
Note: DALI devices that support several DALI device types
appear in the right-hand side window with the type identifier
“MASK”. When such a device is assigned to a configured
DALI device then the DALI device type selected for this configured DALI device is used if this DALI device type is supported by the found DALI device. Otherwise, DALI device type
0 (= fluorescent lamp) is used.
To avoid a false assignment this security question appears:
“The DALI device supports more than one DALI device type. It will be
controlled as the DALI device type configured in the ETS parameters.
Continue assignment?”
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/33
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Button
<Selection of the configured and the actual ECG takes place
by selecting the desired ECG on the left-hand / right-hand
side and clicking on the <- button with the mouse. It is also
possible to carry out the allocation via a double click on one of
the two selected ECGs. This button is only enabled if suitable
entries are selected on both sides.
->
With this function it is possible to transfer an already allocated
ECG back into the right-hand field as a non-allocated ECG.
No actual ECG is then allocated to this configured ECG any
longer when the parameters are downloaded into the
KNX/DALI Gateway N 141/02. This process is also carried out
in order to remove an ECG that has been marked as defective. A new ECG can then be allocated (ECG exchange). This
button is only enabled when an allocated ECG is selected on
the left-hand side.
Edit
With this button it is possible to edit the ECG marked on the
left-hand side in another dialogue window. The manufacturer’s ID, name, etc. can be changed. See also chapter
5.5.2.
Note: Please enquire whether the ECG manufacturer supports the device ID function. The company OSRAM already
markets ECGs of the type QTi that include this function.
All ballasts ON
All ECGs attached to the KNX/DALI Gateway N 141/02 are
switched on to maximum brightness.
All ballasts OFF
All ECGs attached to the KNX/DALI Gateway N 141/02 are
switched off.
Initialize device
If two ECGs with the same incidental time are found (recognizable by: two lamps flash when selecting the ECG), this
match can be cancelled by pressing the “Initialize device” button.
Add dummy ballast
Delete dummy ballast
When searching for ballasts (ECGs) not all expected ballasts
may appear in the list in the right window. In such a case use
the button „Add dummy ballast“ to add a ballast (ECG) and
assign it as a place holder to a luminaire before commissioning. After a download the KNX-DALI gateway annuciates an
ECG error for a dummy ECG. After missing ballasts have
been installed or the installation of ballasts has been corrected the ballasts have to be assigned to their associated
luminaires instead of the respective dummy ECGs. The new
configuration has to be downloaded to the KNX-DALI gateway.
The column “Dummy” in the list on the right displays if a ballast was added as a place holder.
The N141/02 announces an ECG failure while a dummy ECG
is missing.
A dummy ECG can be removed by clicking on the “Delete
dummy ballast” button.
Note: Luminaires with dummy ECGs will not be controlled via
the bus in the test dialogs for ECGs, groups, scenes or effects.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
5.11
Test Groups
The individual groups and their parameters are listed.
The following functions in the selected group can be
tested using the buttons:
- Switch on / off
- Brighten / dim
- Read value.
The group’s behaviour for the above named functions
corresponds with a receipt upon the corresponding
communication objects: Switch On/Off, dim brighter /
darker, set dimming value. The dimming times that
have already been configured are ignored in this process. The time function is likewise deactivated. However,
no group addresses need to be assigned for the test
yet. To this end only the power supplies for the DALI
devices, DALI and the KNX need to be present, a
physical address needs to be assigned to the N 141/02,
and the DALI devices must be allocated to groups.
Select an entry in the group list to execute these functions via the buttons:
Button
I / O (ON / OFF)
The selected group can be switched on or off as relevant via
these buttons.
Set value
After the value has been entered, this button should be activated in order to adopt the dimming value for the group.
-/+
The selected group can be gradually brightened/darkened by
about 1/20 (5%) as relevant via these buttons.
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/34
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.12
Button
Test ECGs
? (Display Field)
The current dimming value [%] is displayed in this filed after
the “Read value” button has been pressed. A dimming value
[%] can also be entered here, and sent using the button “Set
value”.
Read value
Reading of the current dimming value of the selected group is
initiated via this button.
All groups ON
All groups are switched on using this button
All groups OFF
All groups are switched off using this button.
Note:
Double-clicking on an entry in the list opens the parameter window for configuration of the ECG parameters.
Select an entry in the group list to execute these functions via the buttons:
Button
I / O (ON / OFF)
The selected ECG can be switched on or off as relevant via
these two buttons.
-/+
The selected group can be gradually brightened/darkened by
about 1/20 (5%) as relevant via these buttons.
Set value
After the value has been entered, this button should be activated in order to adopt the dimming value for the ECG.
? (Entry / display field)
The current dimming value (as a percentage) is displayed in
this field after the “Read value” button has been pressed.
Moreover, a dimming value (as a percentage) can be entered
in this field, which is then adopted by pressing the “Set value”
button and sent to the selected device.
Read value
Reading of the current dimming value of the ECG is triggered
via this button and is displayed here.
All ballasts ON
All ECGs can be switched on here.
All ballasts OFF
All ECGs can be switched off here.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/35
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
5.13
Test Scenes
5.14
Test Effects
Double-clicking on an entry in the list or on the „Test“
button opens the configuration window for testing of effects.
Double-clicking on a list entry or on the "Edit" button
opens the parameter window for scene parameters.
Button
Recall
The selected scene is recalled using this button. The integrated groups and ECGs set the dimming values saved in the
KNX/DALI Gateway N 141/02.
Edit
The “Scene”, parameters window to insert parameters for the
selected scene is opened using this button.
Read value
The current dimming values of all groups and ECGs are read
and displayed using this button.
This allows for setting the scene with wall switches or by other
means and then reading this setting back into the configuration. The values read can be adopted or changed for the
scene before saving or downloading into the N141/02.
All ballasts ON
All ballasts can be switched on using this button (“Central On”
for all groups).
All ballasts OFF
All ballasts can be switched off using this button (“Central Off”
for all groups).
After selection of an entry in the list these functions can
be executed by clicking on the respective buttons.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/36
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Button
Settings
Fast motion
1:1
1:2
1:3
1:4
1:5
1:6
1:7
1:8
1:9
1:10
The effects test can be accelerated. In doing so all delay
times surrounding the factor selected in this window are accelerated. In doing so, in the case of very rapid processes
there may be an incorrect time lapse if the minimum times
were calculated from 0.1 seconds. In this case a time limit of
0.1 seconds applies. If the manufacturer supports separate
starting of the filament heating, this is automatically switched
on for these tests.
Cycle (display field)
1/1
The number of the current run-through (left-hand figure) and
the configured number of run-throughs (right-hand figure) are
displayed in this field.
Filament heating ON (display field)
This field displays whether the filament heating is switched on
permanently (even when a fluorescent light is switched off).
Note: This function is not supported by all ECGs.
Start
Using this button the selected effect is launched for testing
with the factor of the set time motion.
Stop
Using this button the launched effect is stopped with the factor of the set time motion.
Single Step
The individual effect steps can be controlled using this button.
The process is commenced with the currently selected step. If
no step is selected, the first step is automatically selected and
executed.
Edit
A step can be edited here. The new settings are not, however, transferred into the Gateway N 141/02. A transfer only
takes place via the downloading of parameters.
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/37
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
6 Appendix
6.1
Behaviour in event of 230V recovery at N 141/02, voltage recovery on DALI, KNX bus
Operation Behavior on bus
voltage failure of Starting Value
Mode
KNX or DALI
no action
230 V recovery *
KNX Recovery
no action
dimming value
at switching off
set to min (not time limited)
set value to w, if no switch off value available (it
is cleared on voltage failure) set to min (not
time limited)
last received
dimming value
set to min (not time limited)
set to last received value, if no value or 0 has
been the last received value since last voltage
failure set to min (not time limited)
x%
set to x % (not time limited)
starting value
normal mode
maximum dimming
value
minimum dimming
value
set to max (not time limited)
set to min (not time limited)
as before bus voltage
failure
no action
switch OFF
switch off
no action
no action
time switch mode / night mode
dimming value
at switching off
set to min (time limited)
set value to w, if no switch off value available (it
is cleared on voltage failure) set to min (time
limited)
last received
dimming value
set to min (time limited)
set to last received value, if no value or 0 has
been the last received value since last voltage
failure set to min (time limited)
x%
set to x % (time limited)
starting value
maximum dimming
value
minimum dimming
value
set to max (time limited)
set to min (time limited)
as before bus voltage
failure
no action
switch OFF
switch off
* On 230V recovery, night mode luminaires are switched on not time limited
Definitions:
w = value at last switch off
y = value when arriving Emergency ON
max = maximum dimming value
min = minimum dimming value
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/38
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
6.2
Behaviour in event of 230V failure on N 141/02, DALI, KNX bus
Operation
Mode
Behavior on bus
voltage failure of Starting Value
KNX or DALI
Dimming value
230 V Failure
on emergency
no action
KNX Failure
no action
set to min (not time limited)
set value to w, if no switch off
value available (it is cleared on
voltage failure) set to min (not
time limited)
last received
dimming value
set to min (not time limited)
set to last received value, if no
value or 0 has been the last
received value since last voltage failure set to min (not time
limited)
x%
set to x % (not time limited)
dimming value
at switching off
starting value
normal mode
maximum dimming
value
minimum dimming
value
set to max (not time limited)
set to min (not time limited)
no change
dimming value on
emergency
x%
no action
set to x % (not time limited)
switch OFF
switch off
no action
no action
set to min (not time limited)
set value to w, if no switch off
value available (it is cleared on
voltage failure) set to min (not
time limited)
last received
dimming value
set to min (not time limited)
set to last received value, if no
value or 0 has been the last
received value since last voltage failure set to min (not time
limited)
x%
set to x % (not time limited)
dimming value
at switching off
time switch mode / night mode
starting value
maximum dimming
value
minimum dimming
value
dimming value on
emergency
switch OFF
set to max (not time limited)
set to min (not time limited)
no change
no action
x%
set to x % (not time limited)
switch off
Definitions:
w = value at last switch off
y = value when arriving Emergency ON
max = maximum dimming value
min = minimum dimming value
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/39
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
6.3
Behaviour on emergency OFF
Operation
Behaviour on emergency OFF
Mode
as before emergency operation
ON
normal mode
last received dimming value
starting value
Starting Value Emergency OFF
set value to dimming value when “Emergency ON” commenced;
(starting with firmware version 5) If dimming value was zero when
“Emergency ON” commenced, then set value to min for emergency
lamps or for groups containing one or more emergency lamps.
(up to firmware version 4) If dimming value was zero when “Emergency ON” commenced, then set value to min.
set to last received value;
if no value was received since last voltage failure or the value was
zero then set the value to min
set value to dimming value when the last switching off command
was received,
dimming value if no switch off value is available (it is cleared on voltage failure) set
at switching off the value to min.
If the lamp was turned on when „Emergency ON“ commenced, restore that state.
last received
dimming value
time switch mode / night mode
x%
set to last received value;
if no value or zero has been the last received value since last voltage failure set to min
set to x %
maximum dimming value
set to max
minimum dimming value
set to min
switch OFF
switch off
as before emergency operation
ON
set value to dimming value when “Emergency ON” commenced;
if this value was zero then set value to min (time limited)
last received dimming value
set to last received value, if no value or zero has been the last received value since last voltage failure set to min (time limited)
set value to dimming value when the last switching off command
dimming value was received;
at switching off if no switch off value available (it is cleared on voltage failure) set to
min (time limited)
starting value
last received
dimming value
set to last received value;
if no value or zero has been the last received value since last voltage failure set to min (time limited)
x%
set to x % (time limited)
maximum dimming value
set to max (time limited)
minimum dimming value
set to min (time limited)
switch OFF
switch off
Definitions:
max = maximum dimming value
min = minimum dimming value
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/40
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Space for notes
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/ 41
GAMMA instabus
Application Descriptions
March 2011
07 B0 KNX / DALI Gateway 981C0C
Siemens AG
Industry Sector, Building Technologies
Room Automation & Control
PO Box 10 09 53, D-93009 Regensburg
981C0C, 42 Seiten
© Siemens AG 2011
Subject to change without further notice
Technical Manual
Update: http://www.siemens.com/gamma
3.4.2.3.8/42