2600.283111.0011 Mulrooney fire alarm
Submittal Transmittal
Detailed, Grouped by Each Number
1654 - Marywood Learning Commons
2300 Adams Avenue
Scranton, PA 18509
Date:
Project # 1654
Tel: 570-348-6201
12/29/2014
Transmitted To:
Qty
Reference Number: 0352
James Egan
Mulrooney & Sporer, Inc.
103 Birch Dr.
Roaring Brook Twsp., PA 18444
Tel: (570) 342-9254
Fax: (570) 344-6959
Submittal Package No
12/29/20 2600-283111-0011 - - 0
14
Transmitted By:
Description
Mulrooney fire alarm
Delivered Via
E-Mail
Qty
Description
fire alarm
Spec Section
283111
01
Company Name
Contact Name
Package Action
Approved as Noted
Construction
Items
Todd Plociniak
Sordoni Construction Services, Inc.
45 Owen Street
Forty Fort, PA 18704
Tel: (570) 287-3161
Fax: (570) 287-0298
Due Date
Transmitted For
Cc:
Sordoni Construction Services, Inc.
Fax: 570-961-4749
Tracking Number
Type
Product Data
Notes
Item Action
Approved as Noted
Copies Notes
Remarks
Signature
Prolog Manager
Printed on: 12/29/2014
SCS PA
Signed Date
Page 1
Submittal Transmittal
Detailed, Grouped by Each Number
1654 - Marywood Learning Commons
2300 Adams Avenue
Scranton, PA 18509
Date:
Project # 1654
Tel: 570-348-6201
Sordoni Construction Services, Inc.
Fax: 570-961-4749
11/18/2014
Transmitted To:
Reference Number: 0328
Transmitted By:
Phil Scheuermann
Hemmler + Camayd
409 Lackawanna Ave.
Suite 400
Scranton, PA 18503-2062
Tel: (570) 961-1302
Fax: (570) 961-3919
Todd Plociniak
Sordoni Construction Services, Inc.
45 Owen Street
Forty Fort, PA 18704
Tel: (570) 287-3161
Fax: (570) 287-0298
Qty
Submittal Package No
Description
Due Date
01
2600-283111-0011 - - 0
Mulrooney fire alarm
12/2/2014
Transmitted For
Delivered Via
Approval
E-Mail
Items
Qty
283111
01
Cc:
Description
fire alarm
Spec Section
Company Name
Contact Name
Package Action
Tracking Number
Type
Product Data
Notes
Item Action
Copies Notes
Remarks
APPROVED
APPROVED AS NOTED
REVISE & RESUBMIT
FABRICATION/
INSTALLATION MAY BE
UNDERTAKEN. APPROVAL
DOES NOT AUTHORIZE
CHANGES IN THE
CONTRACT SUM OR
CONTRACT TIME.
SEE FORTHCOMING WCPR
FOR NEW LOCATIONS OF
DEVICES FORMERLY
LOCATED ON BLACK BRICK
WALLS.
FABRICATION/
INSTALLATION MAY NOT
BE UNDERTAKEN. IN
RESUBMITTING, LIMIT
CORRECTIONS TO THE
ITEMS MARKED.
ALL DEVICES TO BE WHITE,
EXCEPT FOR MANUAL PULL
STATIONS TO BE RED.
REVIEW / APPROVAL NEITHER EXTENDS NOR ALTERS ANY CONTRACTUAL
OBLIGATIONS OF THE ARCHITECT OR CONTRACTOR
12/23/2014
CL
BY:_________________________________________
DATE:__________
hemmler + camayd architects
Signature
Prolog Manager
Printed on: 11/18/2014
SCS PA
Signed Date
Page 1
Shop Drawing Review
SMA Job #: 12-012
Project Name: Marywood University Learning Commons
Equipment Reviewed: Fire Alarm
Specification Section: 283111-0011
Date of Review: 12/3/2014
Reviewed By: Ben Ardary
Comments



Submittal Review was for product data
only.
CONSTRUCTION SUBMITTAL REVIEW
SMITH MILLER ASSOCIATES
NO EXCEPTIONS TAKEN
REVISE & RESUBMIT
Provide the information stated in
specification section 283111.1.4 for
review and approval.
X NOTE MARKINGS
NOT APPROVED
Shop drawing layouts shall represent all
WCPR changes.
THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
CORRECTNESS OF DIMENSIONS AND QUANTITIES AND
FITTING TO OTHER WORK: VERIFICATION OF PHYSICAL
INTERRELATION OF ELEMENTS OF THE WORK FROM
PLANS AND SPECIFICATIONS AND IN THE FIELD
FABRICATING PROCEDURES, CONSTRUCTION METHODS,
TECHNIQUES, AND SEQUENCES. THIS REVIEW DOES NOT
RELIEVE
THE
CONTRACTOR
FROM
THEIR
RESPONSIBILITIES.
REVIEW IS ONLY FOR GENERAL CONFIRMATION WITH THE
CURRENT DESIGN OF THE PROJECT NON-CONFORMITIES
AND ANY ERRORS FOUND ARE NOTED.
THIS REVIEW DOES NOT CONSTITUTE APPROVAL OR
ACCEPTANCE
OF
DEVIATIONS
FROM
CONTRACT
DOCUMENTS, SUCH DEVIATIONS MUST BE REQUESTED BY
WRITING OR CLEARLY IDENTIFIED AS DEVIATIONS IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
38 N. Main Street, Pittston, PA 18640
Phone: 570-299-5865
Fax: 570-299-7865
Page 1 of 1
H:\SM Projects Active\12-012 Marywood University Learning Commons\4-Construction Phase\Shop Drawings\Out\2014-12-03 Fire Alarm\SMA Shop
Dwg Review.Doc
PROJECT SUBMITTAL COVER SHEET
HC Arch BCJ
Marywood Learning Center
Scranton PA
Wilkes Barre PA
Contractor:
Address:
City:
Telephone:
Learning Commons
Dunmore PA
Mulrooney & Sporer, INC.
522 Prospect Ave.
Scranton
State / Zip:
570-342-9254
Fax:
PA 18505
570-344-6959
Date:
Submittal #:
# of Copies:
11/15/2014
10
Ele
Email: [email protected]
Submittal Title: Fire Alarm - Video Intercom - Panic Buttons
CSI Number: 283111 - Sheet E504 - Shhet E212
X Material / Product Data
MSDS Sheet
Sample
Shop Drawing
Test Report
Qualification
Warranty
Other _____________
Name of Installer or Manufacture: Vector Security
Location of Manufacturer or Product Origin:
Additional Information:
Approx. Value of Installed material, product,
equipment only listed above (Labor not Inc.)
% Total Recycled Content:
% Post-Consumer Recycled Content:
% Post-Industrial Recycled Content:
VOC Content (if applicable):
$ NA
Smith Miller Assoc
Preliminary Approval
Final Approval as Noted
M&S Stamp
Approved
Mulrooney & Sporer
Electrical
Final Approval
Date:
Disapproved - Resubmit
By: James Egan
For design and general arrangement only. All
dimensions to be verified at site by contractor.
Not checked for quantities or for detailed
dimensions.
By:
Date:
HC A / BCJ Arch Stamp
11/15/2014
Sordoni Stamp
0%
0%
0%
0%
SUBMITTAL
November 14, 2014
MARYWOOD UNIVERSITY
LEARNING COMMONS
FIRE ALARM SYSTEM
VECTOR SECURITY
23 CASEY AVENUE
WILKES BARRE, PA 18702
(570) 824-4605
TABLE OF CONTENTS
1.
2.
3.
4.
5.
COVER SHEET
TABLE OF CONTENTS
BILL OF MATERIALS
EQUIPMENT DATA SHEETS
FIRE ALARM SYSTEM BATTERY CALCULATIONS
FIRE ALARM BILL OF MATERIALS
The Learning Commons
Quantity
Part Number
Description
1
1
4
1
13
127
22
3
12
28
13
13
13
2
2
149
13
75
13
36
1
1
8
2
CPU2-640
UDACT-2
FCPS-24S8
FDU80
FSP-851R
FSP-851
FST-851R
FCM-1
FDM-1
FRM-1
DNR
DST-5
RA100Z
FSB-200S
RTS151
B210LP
NBG-12LX
P2W
SW
PC2W
SCW
NFS-LBB
PS1270
PS12550
Fire Alarm Control Panel
Digital Communicator
8 Amp Power Supply
Remote Annunciator 80 Character
Photo Detector Head for Duct Smoke
Photo Detector Head
Thermal Detector Head
Addressable Control Module
Addressable Dual Monitor Module
Addressable Relay Module
InnovairFlex Duct Detector Housing
5' Duct Detector Sample Tube
Duct Detector Remote Indicator
Addressable Beam Detector
Photo Beam Remote Test Station
Intelligent Detector Base
Addressable Pull Station with Key Lock
Wall Horn/Strobe
Wall Strobe
Ceiling Horn/Strobe
Ceiling Strobe
Battery Box
PowerSonic 12V 7AH Battery
PowerSonic 12V 18AH Battery
Rough In Box Type
NA
NA
NA
Single Gang
NA
4" Octagon
4" Octagon
4"x4"x2 1/8" Box
4"x4"x2 1/8" Box
4"x4"x2 1/8" Box
NA
NA
Single Gang
NA
Single Gang
4" Octagon
Single Gang
Single Gang
Single Gang
4" Octagon
4" Octagon
NA
NA
NA
Mounting Height/Details
NA
NA
NA
48" on Center
NA
NA
NA
NA
NA
NA
NA
NA
NA
Within 3' of Ceiling
NA
NA
48" on Center
80" to Bottom of Box
80" to Bottom of Box
NA
NA
NA
NA
NA
DN-7111:J • A-13
NFS2-640(E)
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS2-640 intelligent Fire Alarm Control Panel is part of
the ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products meet virtually every application requirement.
The NFS2-640’s modular design makes system planning easier. The panel can be configured with just a few devices for
small building applications, or networked with many devices to
protect a large campus or a high-rise office block. Simply add
additional peripheral equipment to suit the application.
A host of other options are available, including single- or multichannel voice; firefighter’s telephone; LED, LCD, or PC-based
graphic annunciators; networking; advanced detection products for challenging environments; wireless fire protection; and
many additional options.
NFS2-640-DVC_right.jpg
NOTE: Unless called out with a version-specific “E” at the end of
the part number, “NFS2-640” refers to models NFS2-640 and
NFS2-640E; similarly, “CPU2-640” refers to models CPU2-640
and CPU2-640E.
Features
• Certified for seismic applications when used with the appropriate seismic mounting kit.
• Approved for Marine applications when used with listed
compatible equipment. See DN-60688.
• One, expandable to two, isolated intelligent Signaling Line
Circuit (SLC) Style 4, 6 or 7.
• Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-60820.
• Up to 159 detectors and 159 modules per SLC; 318 devices
per loop/636 per FACP or network node.
– Detectors can be any mix of ion, photo, thermal, or multisensor; wireless detectors are available for use with the
FWSG.
– Modules include addressable pull stations, normally open
contact devices, two-wire smoke detectors, notification, or
relay; wireless modules are available for use with the
FWSG.
• Standard 80-character display, 640-character large display
(NCA-2), or display-less (a node on a network).
• Network options:
– High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
when DVC-EM is used in network paging.
• 6.0 A switch mode power supply with four Class A/B built-in
Notification Appliance Circuits (NAC). Selectable System
Sensor, Wheelock, or Gentex strobe synchronization.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• VeriFire® Tools online or offline programming utility. Upload/
Download, save, store, check, compare, and simulate panel
databases. Upgrade panel firmware.
• Autoprogramming and Walk Test reports.
NFS2-640
• Multiple central station communication options:
– Standard UDACT
– Internet
– Internet/GSM
• 80-character remote annunciators (up to 32).
• EIA-485 annunciators, including custom graphics.
• Printer interface (80-column and 40-column printers).
• History file with 800-event capacity in nonvolatile memory,
plus separate 200-event alarm-only file.
• Alarm Verification selection per point, with automatic
counter.
• Presignal/Positive Alarm Sequence (PAS).
• Silence inhibit and Auto Silence timer options.
• March time/temporal/California two-stage coding/strobe
synchronization.
• Field-programmable on panel or on PC, with VeriFire Tools
program check, compare, simulate.
• Full QWERTY keypad.
• Battery charger supports 18 – 200 AH batteries.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
• Automatic time control functions, with holiday exceptions.
• Surface Mount Technology (SMT) electronics.
• Extensive, built-in transient protection.
• Powerful Boolean logic equations.
DN-7111:J • 09/09/2014 — Page 1 of 8
• Support for SCS Series smoke control system in HVAC
mode.
NCA-2 AS PRIMARY DISPLAY
• Backlit, 640-character display.
• Supports SCS Series smoke control system in FSCS mode
when SCS is connected to the NCA-2 used as primary
display.
• Supports DVC digital audio loop.
• Printer and CRT EIA-232 ports.
• EIA-485 annunciator and terminal mode ports.
• Alarm, Trouble, Supervisory, and Security relays.
FLASHSCAN® INTELLIGENT FEATURES
•
•
•
•
•
•
•
•
•
Polls up to 318 devices in less than two seconds.
Activates up to 159 outputs in less than five seconds.
Multicolor LEDs blink device address during Walk Test.
Fully digital, high-precision protocol (U.S. Patent
5,539,389).
Manual sensitivity adjustment — up to nine levels.
Pre-alarm ONYX intelligent sensing — up to nine levels.
Day/Night automatic sensitivity adjustment.
Sensitivity windows:
– Ion – 0.5 to 2.5%/foot obscuration.
– Photo – 0.5 to 2.35%/foot obscuration.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
– Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
– IntelliQuad™ – 1.0 to 4.0%/foot obscuration.
– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
Drift compensation (U.S. Patent 5,764,142).
• Degraded mode — in the unlikely event that the CPU2-640
microprocessor fails, FlashScan detectors revert to
degraded operation and can activate the CPU2-640 NAC
circuits and alarm relay. Each of the four built-in panel
circuits includes a Disable/Enable switch for this feature.
• Multi-detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
FSL-751 (VERY INTELLIGENT EARLY WARNING)
SMOKE DETECTION TECHNOLOGY
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
• Addressable operation pinpoints the fire location.
• Early warning performance comparable to the best aspiration systems at a fraction of the lifetime cost.
FAPT-851 ACCLIMATE PLUS
LOW-PROFILE INTELLIGENT MULTI-SENSOR
• Detector automatically adjusts sensitivity levels without
operator intervention or programming. Sensitivity increases
with heat.
• Microprocessor-based technology; combination photo and
thermal technology.
• Low-temperature warning signal at 40°F ± 5°F (4.44°C ±
2.77°C).
SLC Intelligent Loop 1
Up to 32 remote displays
DEVICES
FWSG
LCD2-80
FDU-80
FSC-851 IntelliQuad
FAPT-851 Acclimate PLUS
FSL-751 FlashScan VIEW
FSP-851 Photo
FSI-851 Ion
FST-851 Thermal
FSA-8000
...etc.
NBG-12LX
XP6/10 I/O Modules
FMM-1
IDC
FCM-1
NAC
FRM-1
Relay Contact
SLC Intelligent Loop 2
EIA-485
EIA-485
KDM-R2 display
OR
NCA-2
OR
with no display
ACM-8R
Relay Control
EIA-232
Sample
System
Options
2048 annunciator/control points
Optional 636-point UDACT
NFS2-640
“C” cabinet size shown
Page 2 of 8 — DN-7111:J • 09/09/2014
ACM/AEM-24AT
LED Annunciator
PRN Series Printer
LDM-32
Custom Graphics
Dual phone
lines to
Central
Station
7111blok-2014.wmf
FSC-851 INTELLIQUAD
ADVANCED MULTI-CRITERIA DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO,
and flame).
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
FSA-8000 INTELLIGENT FAAST DETECTOR
• Connects directly to the SLC loop of compatible ONYX
series panels
• Provides five event thresholds that can be individually programmed with descriptive labels for control-by-event programming; uses five detector addresses.
• Uses patented particle separator and field-replaceable filter
to remove contaminants.
• Advanced algorithms reject common nuisance conditions
FCO-851 INTELLIQUAD™ PLUS
ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire.
• Separate signal for life-safety CO detection.
• Optional addressable sounder base for Temp-3 (fire) or
Temp-4 (CO) tone.
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
SWIFT WIRELESS
• Self-healing mesh wireless protocol.
• Each SWIFT Gateway supports up to 50 devices: 1 wireless
gateway and up to 49 SWIFT devices.
• Up to 4 wireless gateways can be installed with overlapping
network coverage.
RELEASING FEATURES
•
•
•
•
•
Ten independent hazards.
Sophisticated cross-zone (three options).
Delay timer and Discharge timers (adjustable).
Abort (four options).
Low-pressure CO2 listed.
DIGITAL VOICE AND TELEPHONE FEATURES
• Up to eight channels of digital audio.
• 35, 50, 75, and 100/125 watt digital amplifiers (DAA2/DAX
series and DS series; NCA-2 required as primary display).
• Solid-state digital message generation.
• Firefighter telephone option.
• 30- to 120-watt high-efficiency amplifiers (AA Series).
• Backup tone generator and amplifier option.
• NFS2-640 can also integrate with the FirstCommand Emergency Communications System. See DN-60772.
HIGH-EFFICIENCY OFFLINE SWITCHING
3.0 A POWER SUPPLY (6.0 A IN ALARM)
• 120 VAC (NFS2-640); 240 VAC (NFS2-640E).
• Displays battery current/voltage on panel (with display).
FlashScan, Exclusive
World-Leading Detector Protocol
At the heart of the NFS2-640 is a set of detection devices and
device protocol — FlashScan (U.S. Patent 5,539,389). FlashScan is an all-digital protocol that gives superior precision and
high noise immunity.
In addition to providing quick identification of an active input
device, this protocol can also activate many output devices in a
fraction of the time required by competitive protocols. This high
speed also allows the NFS2-640 to have the largest device per
loop capacity in the industry — 318 points — yet every input
and output device is sampled in less than two seconds. The
microprocessor-based FlashScan detectors have bicolor LEDs
that can be coded to provide diagnostic information, such as
device address during Walk Test.
ONYX Intelligent Sensing
Intelligent sensing is a set of software algorithms that provides
the NFS2-640 with industry-leading smoke detection capability. These complex algorithms require many calculations on
each reading of each detector, and are made possible by the
high-speed microcomputer used by the NFS2-640.
Drift Compensation and Smoothing: Drift compensation
allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to
automatically perform the periodic sensitivity measurements
required by NFPA 72. Smoothing filters are also provided by
software to remove transient noise signals, such as those
caused by electrical interference.
Maintenance Warnings: When the drift compensation performed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
are given. There are three warning levels: (1) Low Chamber
value; (2) Maintenance Alert, indicative of dust accumulation
that is near but below the allowed limit; (3) Maintenance
Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust: Nine sensitivity levels are provided for
alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or
self-restoring, and can be used to activate special control functions.
Self-Optimizing Pre-Alarm: Each detector may be set for
“Self-Optimizing” pre-alarm. In this special mode, the detector
“learns” its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre-alarm
level just above these normal peaks.
Cooperating Multi-Detector Sensing: A patented feature of
ONYX intelligent sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
pre-alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.
Field Programming Options
Autoprogram is a timesaving feature. The FACP “learns” what
devices are physically connected and automatically loads
them in the program with default values for all parameters.
Requiring less than one minute to run, this routine allows the
user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.
Keypad Program Edit (with KDM-R2) The NFS2-640, like all
NOTIFIER intelligent panels, has the exclusive feature of program creation and editing capability from the front panel keypad, while continuing to provide fire protection. The
architecture of the NFS2-640 software is such that each point
entry carries its own program, including control-by-event links
to other points. This allows the program to be entered with
independent per-point segments, while the NFS2-640 simultaneously monitors other (already installed) points for alarm conditions.
DN-7111:J • 09/09/2014 — Page 3 of 8
VeriFire® Tools is an offline programming and test utility that
can greatly reduce installation programming time, and
increase confidence in the site-specific software. It is Windows®-based and provides technologically advanced capabilities to aid the installer. The installer may create the entire
program for the NFS2-640 in the comfort of the office, test it,
store a backup file, then bring it to the site and download from
a laptop into the panel.
Placement of Equipment
in Chassis and Cabinet
The following guidelines outline the NFS2-640’s flexible system design.
Rows: The first row of equipment in the cabinet mounts in the
chassis shipped with the FACP. Mount the second, third, or
fourth rows of equipment in a CHS-4 series chassis or, for Digital Voice Command products, in CA-1 or CA-2. (For DVC-EM
and DAA2/DAX components see DVC Manual; for DS series
components see DS-AMP Manual; for DVC-AO applications,
see AA Series Installation Manual). Other options are available; see your panel’s installation manual.
Wiring: When designing the cabinet layout, consider separation of power-limited and non-power-limited wiring as discussed in the NFS2-640 Installation Manual.
Positions: A chassis offers four basic side-by-side positions
for components; the number of modules that can be mounted
in each position depends on the chassis model and the size of
the individual module. There are a variety of standoffs and
hardware items available for different combinations and configurations of components.
It is critical that all mounting holes of the NFS2-640 are
secured with a screw or standoff to ensure continuity of Earth
Ground.
Layers: The control panel’s chassis accepts four layers of
equipment, including the control panel. The CPU2-640 fills
three positions (left to right) in the first-installed layer (the back
of the chassis); its integral power supply occupies the center
two positions in the next two layers; the optional display occupies (the left) two positions at the front, flush with the door.
Some equipment, such as the NCA-2, may be mounted in the
dress panel directly in front of the control panel. The NCA-2
can be used as a primary display for the NFS2-640 (use NCA/
640-2-KIT) by directly connecting their network ports (required
in Canadian stand-alone applications); see NCA-2 data sheet
for mounting options (DN-7047).
Expansion: Installing an LEM-320 Loop Expander Module
adds a second SLC loop to the control panel. The LEM-320 is
mounted onto the CPU2-640, occupying the middle-right, second (back) slot on the chassis.
Networking: If networking two or more control panels, each
unit requires a Network Communication Module or HighSpeed Network Communication Module. (HS-NCM can support two nodes; see “Networking Options” on page 5). These
modules can be installed in any option board position (see
manual), and additional option boards can be mounted in front
of the network communication modules.
KDM-R2 Controls and Indicators
Program Keypad: QWERTY type (keyboard layout, see
figure).
12 LED indicators: Power; Fire Alarm; Pre-Alarm; Security;
Supervisory; System Trouble; Signals Silenced; Points Disabled; Control Active; Abort; Pre-Discharge; Discharge.
Keypad Switch Controls: Acknowledge/Scroll Display; Signal
Silence; Drill; System Reset; Lamp Test.
Page 4 of 8 — DN-7111:J • 09/09/2014
LCD Display: 80 characters (2 x 40) with long-life LED
backlight.
Product Line Information
•
•
•
•
•
•
•
•
•
“Configuration Guidelines” on page 4
“Networking Options” on page 5
“Auxiliary Power Supplies and Batteries” on page 5
“Audio Options” on page 5
“Compatible Devices, EIA-232 Ports” on page 5
“Compatible Devices, EIA-485 Ports” on page 5
“Compatible Intelligent Devices” on page 6
“Enclosures, Chassis, and Dress Plates” on page 7
“Other Options” on page 7
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. On
systems with one FACP (one CPU2-640/-640E), display
options are the KDM-R2 or the NCA-2. On network systems
(two or more networked fire panel nodes), at least one NCA-2,
NCS, or ONYXWorks annunciation device is required. Other
options listed as follows;
KDM-R2: 80-character backlit LCD display with QWERTY programming and control keypad. Order two BMP-1 blank modules and DP-DISP2 mounting plate separately. Requires top
row of a cabinet. Required for each stand-alone 80-character
display system. The KDM-R2 may mount in network nodes to
display “local” node information as long as at least one NCA-2
or NCS/ONYXWorks network display is on the system to display network information. (Non-English versions also available:
KDM-R2-FR, KDM-R2-PO, KDM-R2-SP.)
NCA-2: Network Control Annunciator, 640 characters. On single CPU2-640/-640E systems, the optional NCA-2 can be
used as the Primary Display for the panel and connects
directly to the CPU2-640/-640E. On network systems (two or
more networked fire panel nodes), one network display (either
NCA-2 or NCS/ONYXWorks) is required for every system. On
network systems, the NCA-2 connects to (and requires) a
standard Network Communication Module or High-Speed Network Communication Module. Mounts in a row of FACP node
or in two annunciator positions. Mounting options include the
DP-DISP2, ADP-4B, or in an annunciator box, such as the
ABS-2D. In CAB-4 top-row applications, a DP-DISP2 and two
BMP-1 blank modules are required for mounting. Required for
NFS2-640 applications employing the DVC-EM with DAL
devices. Non-English versions are available. For marine applications, order NCA-2-M; for non-English Marine applications,
order NCA-2-M and the appropriate KP-KIT-XX. See DN-7047.
CPU2-640: Central processing unit (CPU) with integral 3.0 A
(6.0 A in alarm) power supply for an NFS2-640 system.
Includes control panel factory-mounted on a chassis; one Signaling Line Circuit expandable to two; documentation kit.
Order one per system or as necessary (up to 103 network
nodes) on a network system. (Non-English versions also available: CPU2-640-FR, CPU2-640-PO, CPU2-640-SP.)
CPU2-640E: Same as CPU2-640 but requires 240 VAC, 1.5 A,
(3.0 A in alarm). (Non-English versions also available: CPU2640E-PO, CPU2-640E-SP.)
NCA/640-2-KIT: Bracket installation kit required to mount
NCA-2 to the CPU2-640/-640E’s standard chassis.
DP-DISP2: Dress panel for top row in cabinet with CPU2-640/
640E installed.
ADP2-640: Dress panel for middle rows with CPU2-640/640E.
BMP-1: Blank module for unused module positions.
BP2-4: Battery plate, required.
LEM-320: Loop Expander Module. Expands each NFS2-640
to two Signaling Line Circuits. See DN-6881.
NETWORKING OPTIONS
NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN6861.
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network
Communications Modules that can connect to two nodes.
Wire, single-mode fiber, multi-mode fiber, and media conversion models are available. See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board
with wire connection (RPT-W), multi-mode fiber connection
(RPT-F), or allowing a change in media type between wire and
fiber (RPT-WF). Not used with high-speed networks. See DN6971.
ONYXWorks: UL-listed graphics PC workstation, software,
and computer hardware. See DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFNGW-EM.) See DN-60499.
DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS
requires DS-XF70V step-up transformer. Digital Series Amplifier, part of the DS-DB system. See DN-60663.
DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for
DVC-EM, DS-DB distribution board, and DAX and DAA2
Series amplifiers. See DN-60633.
DVC-AO: DVC Analog Output board provides four analog output circuits for use with AA Series amplifiers. Four-channel
operation supported. See DN-7045.
DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier
assembly with power supply; includes chassis. See DN-60556.
DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly
with power supply; includes chassis. See DN-60556.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly
with power supply, includes chassis. See DN-60561.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.
DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly
with power supply, includes chassis. See DN-60561.
CAP-GW: Common Alerting Protocol Gateway. See DN60576.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
VESDA-HLI-GW: VESDAnet high-level interface gateway. See
DN-60753.
TELH-1: Firefighter’s Telephone Handset for use with the
DVC-EM when mounted in the CA-2 chassis. See DN-7045.
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic
and high-speed NOTI•FIRE•NET networks through the NFN
Gateway. See DN-60679.
CMIC-1: Optional microphone and microphone well assembly
used with the CA-1 chassis.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See
DN-60679.
AUXILIARY POWER SUPPLIES AND BATTERIES
ACPS-610: 6.0 A or 10.0 A addressable charging power supply. See DN-60244.
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes
of power for peripheral devices. Includes battery input and
transfer relay, and overcurrent protection. Mounts on two of
four positions on a CHS-4L or CHS-4 chassis. See DN-5952.
FCPS-24S6/S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927.
BAT Series: Batteries. NFS2-640 uses two 12 volt, 18 to 200
AH batteries. See DN-6933.
AUDIO OPTIONS
NOTE: For mounting hardware, see “Enclosures, Chassis, and
Dress Plates” on page 7 and peripheral data sheets.
DVC-EM: Digital Voice Command, digital audio processor with
message storage for up to 32 minutes of standard quality (4
minutes at high quality) digital audio. Capable of playing up to
eight simultaneous messages when used with Digital Audio
Loop (DAL) devices. See DN-7045.
RM-1/RM-1SA: Remote microphone assemblies, mount on
ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA)
stand-alone cabinets. See DN-6728.
AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier
and audio input supervision, backup input, and automatic switchover, power supply, cables. See DN-3224.
AA-120/AA-100: Audio Amplifier provides up to 120 watts of
25 VRMS audio power for the NFS-640. The amplifier contains
an integral chassis for mounting to a CAB-B4, -C4, or -D4
backbox (consumes one row). Switch-mode power. Includes
audio input and amplified output supervision, backup input,
and automatic switchover to backup tone. Order the AA-100
for 70.7 VRMS systems and 100 watts of power. See DN-3224.
DAA Series Digital Audio Amplifiers: Legacy DAA Series
amplifiers are compatible with DVC-EM systems running
SR4.0. For specific information on DAA-50 series amplifiers,
refer to DN-7046. For information on DAA-7525 Series, refer to
DN-60257.
NFC-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation
Control Panel (VECP) with integral commercial microphone,
digital message generator, and single-/dual-channel Class A
or Class B speaker circuits. See DN-60772.
COMPATIBLE DEVICES, EIA-232 PORTS
DVC-RPU: Digital Voice Command Remote Paging Unit for
use with DVC-EM. Includes the keypad/display. See DN60726.
PRN-6: 80-column printer. See DN-6956.
DS-DB: Digital Series Distribution Board, provides bulk amplification capabilities to the DVC-EM while retaining digital audio
distribuition capabilities. Can be configured with up to four DSAMPs, supplying high-level risers spread throughout an installation. See DN-60565.
DPI-232: Direct Panel Interface, specialized modem for
extending serial data links to remotely located FACPs and/or
peripherals. See DN-6870.
DVC-KD: DVC-EM keypad for local annunciation and controls;
status LEDs and 24 user-programmable buttons. See DN7045.
ACM-24AT: ONYX Series ACS annunciator – up to 96 points
of annunciation with Alarm or Active LED, Trouble LED, and
switch per circuit. Active/Alarm LEDs can be programmed (by
VS4095/5: Printer, 40-column, 24V. Mounted in external backbox. See DN-3260.
COMPATIBLE DEVICES, EIA-485 PORTS
DN-7111:J • 09/09/2014 — Page 5 of 8
powered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow. See DN-6862.
FST-851: FlashScan thermal detector 135°F (57°C). See DN6936.
AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
FST-851R: FlashScan thermal detector 135°F (57°C) with
rate-of-rise. See DN-6936.
ACM-48A: ONYX Series ACS annunciator – up to 96 points of
annunciation with Alarm or Active LED per circuit. Active/
Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to
96 points with one AEM-48A. See DN-6862.
FST-851H: FlashScan 190°F (88°C) high-temperature thermal
detector. See DN-6936.
AEM-48A: Same LED capabilities as ACM-48A, expands the
ACM-48A to 96 points. See DN-6862.
ACM-8R: Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four
wires. See DN-3558.
FDU-80: Terminal mode. 80-character, backlit LCD display.
Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP. See DN-6820.
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD
display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32
per FACP. See DN-60548.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDMR32; remote custom graphic driver modules. See DN-0551.
FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor
detector. See DN-6937.
FSL-751: FlashScan VIEW laser photo detector. See DN6886.
DNR: InnovairFlex low-flow non-relay duct-detector housing
(order FSP-851R separately). Replaces FSD-751PL/FSD751RPL. See DN-60429.
DNRW: Same as above with NEMA-4 rating, watertight. See
DN-60429.
B224RB: Low-profile relay base. See DN-60054.
B224BI: Isolator base for low-profile detectors. See DN60054.
B210LP: Low-profile base. Standard U.S. style. Replaces
B710LP. See DN-60054.
B501: European-style, 4" (10.16 cm) base. See DN-60054.
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers
SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC
only). See DN-4818.
B200S: Intelligent programmable sounder base, capable of
producing a variety of tone patterns including ANSI Temporal
3. Compatible with sychronization protocol. See DN-60054.
TM-4: Transmitter Module. Includes three reverse-polarity circuits and one municipal box circuit. Mounts in panel module
position (single-address-style) or in CHS2-M2 position. See
DN-6860.
B200SCOA: Based on B200SA, with added CO detector
markings in English/French. For Canadian applications only.
UDACT-2: Universal Digital Alarm Communicator Transmitter,
636 channel. See DN-60686.
UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microprocessorcontrolled, field-programmable from IBM®-compatible PCs
(requires optional programming kit). Up to 256 programmable
codes. Mounts in BB-UZC or other compatible chassis (purchased separately). See DN-3404.
COMPATIBLE INTELLIGENT DEVICES
FWSG Wireless SWIFT Gateway: Addressable gateway supports wireless SLC devices. Not appropriate for ULC applications. See DN-60820.
FSA-8000: Intelligent FAAST Fire Alarm Aspiration Sensing
Technology®. Intelligent aspirating smoke detector. For Canadian applications, order FSA-8000A. See DN-60792.
FSB-200: Intelligent beam smoke detector. See DN-6985.
FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985.
B200SR: Sounder base, Temporal 3 or Continuous tone. See
DN-60054.
FMM-1: FlashScan monitor module. See DN-6720.
FDM-1: FlashScan dual monitor module. See DN-6720.
FZM-1: FlashScan two-wire detector monitor module. See DN6720.
FMM-101: FlashScan miniature monitor module. See DN6720.
FTM-1: Firephone Telephone Module connects a remote firefighter telephone to a centralized telephone console. Reports
status to panel. Wiring to jacks and handsets is supervised.
See DN-6989.
FCM-1: FlashScan control module. See DN-6720.
FCM-1-REL: FlashScan releasing control module. See DN60390.
FRM-1: FlashScan relay module. See DN-6720.
FDRM-1: FlashScan dual monitor/dual relay module. See DN60709.
NBG-12LX: Manual pull station, addressable. See DN-6726.
FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria
Detector. See DN-60412.
ISO-X: Isolator module. See DN-2243. See DN-2243.
FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Criteria Fire/CO Detector. See DN-60689.
XP6-C: FlashScan six-circuit supervised control module. See
DN-6924.
FSI-851: Low-profile FlashScan ionization detector. See DN6934.
XP6-MA: FlashScan six-zone interface module; connects
intelligent alarm system to two-wire conventional detection
zone. See DN-6925.
FSP-851: Low-profile FlashScan photoelectric detector. See
DN-6935.
FSP-851T: FSP-851 plus dual electronic thermistors that add
135°F (57°C) fixed-temperature thermal sensing. See DN6935.
FSP-851R: FSP-851, remote-test capable. For use with
DNR(W). See DN-6935.
Page 6 of 8 — DN-7111:J • 09/09/2014
XP6-R: FlashScan six-relay (Form-C) control module. See
DN-6926.
XP10-M: FlashScan ten-input monitor module. See DN-6923.
SLC-IM: SLC integration module, for VESDAnet detectors.
See DN-60755.
ENCLOSURES, CHASSIS, AND DRESS PLATES
DPA-2B: Dress panel used with CA-2 chassis assembly.
CAB-4 Series Enclosure: NFS2-640 mounts in a standard
CAB-4 Series enclosure (available in four sizes, “A” through
“D”). Backbox and door ordered seperately; requires BP2-4
battery plate. A trim ring option is available for semi-flush
mounting. See DN-6857.
VP-2B: Dress panel, required when CA-2 chassis is installed
in the top two cabinet rows.
EQ Series Cabinets: EQ series cabinets will house amplifiers,
power supplies, battery chargers and control modules. EQ
cabinets are available in three sizes, “B” through “D”. See DN60229. .
CAB-BM Marine System: Protects equipment in shipboard
and waterfront applications. Also order BB-MB for systems
using 100 AH batteries. For a full list of required and optional
equipment, see DN-60688.
CHS-4: Chassis for mounting up to four APS-6Rs.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
amplifiers or one AMG-E and one AA-30.
DP-1B: Blank dress panel. Provides dead-front panel for
unused tiers; covers DAA2/DAX series or AA-series amplifier.
DPA-1A4: Dress panel, used with the CA-1 chassis when the
CMIC-1 is not used. Provides mounting options on right two
bays for two ACS annunciators, or for blank plates. See DN7045.
BP-CA2: Blank plate for CA-2 chassis.
BB-UZC: Backbox for housing the UZC-256 in applications
where the UZC-256 will not fit in panel enclosure. Black; for
red, order BB-UZC-R.
SEISKIT-CAB: Seismic mounting kit. Required for seismiccertified applications with NFS2-640 and other equipment
mounted in CAB-4 Series Enclosures. Includes battery bracket
for two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery
bracket for two 55 AH batteries.
OTHER OPTIONS
NFS-LBB: Battery Box (required for batteries larger than 26
AH).
411: Slave digital alarm communicator. See DN-6619.
NFS-LBBR: Same as above but red.
IPDACT-2/2UD, IPDACT Internet Monitoring Module: Connects to primary and secondary DACT telephone output ports
for internet communications over customer-provided Ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static IP. See DN-60408.
CHS-BH1: Battery chassis; holds two 12.0 AH batteries.
Mounts one the left side of DAA2 chassis. See DN-7046.
CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure.
The left side accommodates one DVC-EM and a DVC-KD
(optional); and the right side houses a CMIC-1 microphone
and its well (optional). See DN-7045.
CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series
enclosure. The left side accommodates one DVC-EM mounted
on a half-chassis and one NCA-2 mounted on a half-chassis.
The right side houses a microphone/handset well. The CA-2
assembly includes CMIC-1 microphone. ADDR Series doors
with two-tier visibility are available for use with the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4 (below).
CFFT-1: Chassis to mount firefighter’s telephone and one ACS
annunciator in a CAB-4 row. Includes TELH-1 firefighter’s
handset for the DVC-EM, chassis, phone well and mounting
hardware. Order DP-CFFT dress panel separately.
DP-CFFT: CFFT-1 dress panel. Requires BMP-1 if no ACS
annunciator is installed.
ADDR-B4*: Two-tier-sized door designed for use with the CA2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-B4
backbox with the ADDR-B4. See DN-7045, DN-6857.
ADDR-C4*: Three-tier-sized door, designed for use with the
CA-2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-C4
backbox with the ADDR-C4. See DN-7045, DN-6857.
ADDR-D4*: Four-tier-sized door designed for use with the CA2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-D4
backbox with the ADDR-D4. See DN-7045, DN-6857.
*Use ADDR-B4/C4/D4 when CA-2 chassis is installed in top
two rows with NCA-2 or BP-CA2. Use standard door when CA2 is not installed in top two rows. For additional configuration
information, see the DVC application guide on http://esd.notifier.com.
DPA-1: Dress panel, used with the CA-1 chassis when configured with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
411UDAC: Digital alarm communicator. See DN-6746.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket; Red. For Black order IPENC-B.
IPGSM-4G: Internet and Digital Cellular Fire Alarm Communicator. Provides selectable configurable paths: cellular only, IP only,
or IP primary with cellular backup. Connects to the primary and
secondary ports of a DACT. For Canadian applications order
IPGSM-4GC. See DH-60769.
NOTE: For other options including compatibility with retrofit equipment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
System Specifications
SYSTEM CAPACITY
•
•
•
•
•
•
Intelligent Signaling Line Circuits ............1 expandable to 2
Intelligent detectors ......................................... 159 per loop
Addressable monitor/control modules .............. 159 per loop
Programmable software zones......................................... 99
Special programming zones ............................................. 14
LCD annunciators per CPU2-640/-640E
and NCA-2 (observe power)............................................. 32
• ACS annunciators per
CPU2-640/-640E .......................... 32 addresses x 64 points
• ACS annunciators per
NCA-2.................................. 32 addresses x 64 or 96 points
NOTE: The NCA-2 supports up to 96 annunciator address points
per ACM-24AT/-48A.
ELECTRICAL SPECIFICATIONS
• Primary input power:
– CPU2-640 board: 120 VAC, 50/60 Hz, 5.0 A.
– CPU2-640E board: 220/240 VAC, 50/60 Hz, 2.5 A.
DN-7111:J • 09/09/2014 — Page 7 of 8
• Current draw (standby/alarm):
– CPU2-640(E) board: 0.250 A. Add 0.035 A for each NAC
in use.
– KDM-R2: 0.100 A.
– LEM-320: 0.100 A.
• Total output 24 V power: 6.0 A in alarm.
NOTE: The power supply has a total of 6.0 A. of available power.
This is shared by all internal circuits. See Installation Manual for a
complete current draw calculation sheet.
• Standard notification circuits (4): 1.5 A each.
• Resettable regulated 24V power: 1.25 A.
• Two non-resettable regulated 24V power outputs:
– 1.25 A.
– 0.50 A.
• Non-resettable 5V power: 0.15 A.
• Battery charger range: 18 AH – 200 AH. Use separate cabinet for batteries over 26 AH.
• Float rate: 27.6 V.
CABINET SPECIFICATIONS
• Systems can be installed in CAB-4 Series cabinets (four
sizes with various door options, see DN-6857). Requires
BP2-4 Battery Plate.
SHIPPING WEIGHT
• CPU2-640/-640: 14.3 lb (6.49 kg).
• CPU2-640/-640E: 14.55 lb (6.60 kg).
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
requirements are followed, systems are approved by the following agencies:
• US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46
CFR and 161.002).
• Lloyd's Register 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS) Type Approval.
NOTE: For information on marine applications, see DN-60688.
STANDARDS
The NFS2-640 complies with the following UL Standards and
NFPA 72, International Building Code (IBC), and California
Building Code (CBC) Fire Alarm Systems requirements:
• UL 864, 9th Edition (Fire).
• UL 1076 (Burglary).
• UL 2572 (Mass Notification Systems). (NFS2-640 version
20 or higher.)
• LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
• AUXILIARY (Automatic, Manual and Waterflow) (requires
TM-4).
• REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
• PROPRIETARY (Automatic, Manual and Waterflow).
Not applicable for FM.
• EMERGENCY VOICE/ALARM.
• OT, PSDN (Other Technologies, Packet-switched Data Network).
• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
• CBC 2007 (Seismic).
AGENCY LISTINGS AND APPROVALS
The listings and approvals below apply to the basic NFS2-640
control panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: S635.
• ULC Listed: S635.
• FM Approved.
• MEA: 128-07-E.
• Fire Dept. of New York: #6121.
• CSFM: 7165-0028:0243.
• City of Chicago.
• City and County of Denver.
• CCCF listed.
Marine Applications: Marine approved systems must be configured using components itemized in this document. (See
Main System Components, in “Product Line Information.) Specific connections and requirements for those components are
described in the installation document, PN 54756. When these
IntelliQuad™, NOTI•FIRE•NET™, ONYXWorks™, and SWIFT™ are
trademarks; and Acclimate® Plus™, FirstCommand®, FlashScan®,
NOTIFIER®, ONYX®, VeriFire®, and VIEW® are registered
trademarks of Honeywell International Inc. Microsoft® and Windows®
are registered trademarks of Microsoft Corporation. IBM® is a registered
trademark of IBM Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 8 of 8 — DN-7111:J • 09/09/2014
DN-60686:A1
UDACT-2
Universal Digital Alarm
Communicator Transmitter
Annunciator Control System
General
The Universal Digital Alarm Communicator Transmitter (UDACT2) is designed for use on Notifier Fire Alarm Control Panels and
on the NCA-2 Network Control Annunciator. When used in conjunction with the NCA-2 network control annunciator, the
UDACT-2 can report the status of all control panels on
NOTI•FIRE•NET™. The UDACT-2 transmits system status to UL
listed Central Station Receivers via the public switched telephone network. The UDACT-2 can be installed in the panel cabinet or remotely in a separate enclosure.
NOTE: The UDACT-2 can also be used with legacy panels.
Please refer to the UDACT-2 manual for more information.
The UDACT-2 upload/download programming and firmware
updates are accomplished with VeriFire Tools. Refer to the Programming Section for further details.
The UDACT-2 is capable of transmitting the status of software
zones (Alarm and Trouble), System Trouble, Panel Off-Normal,
Supervisory, Bell Trouble, Low Battery, and AC Fail. The
UDACT-2 is capable of transmitting all of the zone and point status associated with each panel.
When the UDACT-2 is used with the NFS-3030, NFS2-3030,
and NCA-2 it is capable of reporting up to 2,040 points. Reporting may be in the form of points or zones (refer to the UDACT-2
manual for specific reporting parameters). Points transmitted
may be programmed for a variety of types, including fire, waterflow, supervisory, etc.
NOTE: Descriptions regarding point capacity, listed above, are for
receivers which receive in Ademco Contact ID format. See chart
on page 2 for compatible receivers.
Features
• Programmable with VeriFire Tools version 6.60 or higher,
allowing the UDACT-2 programming to be uploaded/downloaded and saved.
• Maximum of 14 point trouble messages transmitted per hour.
• Dual phone lines with line voltage detect.
• Compact in size: 6.75" x 4.25" (17.145 x 10.795 cm).
• USB port for upload/download programming.
• Manual Test Report function.
• Manual Transmission Clear function.
• Mounts in a separate enclosure (ABS-8RB or UBS-1B/R).
• Communicates vital system status including:
– Independent zone fire alarm.
– Independent zone non-fire alarm.
– Independent zone trouble.
– Independent zone supervisory.
– AC (mains) Power Loss (programmable).
– Low Battery and Earth Fault.
– System Off-Normal.
– 12 or 24 hour test signal.
– Abnormal Test Signal per new UL requirements.
– EIA-485 Communication Bus Failure.
• Annunciation of UDACT-2 Troubles including: loss of phone
lines, communication failure with either Central Station, total
communications failure.
• Individual LEDs for: Power, EIA-485 Loss, Manual Test, Kissoff, Comm Fail, Primary Line Seize, Secondary Line Seize
and Modem Communications.
UDACT-2
• Open Collector relay driver for Total Communications Failure
or UDACT-2 trouble.
• Real-time clock.
• Extensive transient protection.
• EIA-485 interface to host panel.
Programming
The UDACT-2 programming is created and downloaded using
VeriFire Tools. This enables the unit to be programmed prior to
installation, be easily modified, and saved either online or
offline. A printed report with point or zone information can be
generated from VeriFire Tools for an ONYX Series panel or network annunciator. The point report consists of the central station
point address, ACS point, ACS point function, panel label, panel
point, type code, custom and extended label, alarm verification,
walktest participation, presignal, and PAS information. The zone
report consists of a grid with the central station point address,
ACS point address, source, ACS point function, custom label
and panel label. This report may be sent to the Central Station
for their records. VeriFire Tools also supports upgrading the
UDACT-2 operating firmware.
DN-60686:A1 • 4/2/12 — Page 1 of 2
Communication Formats
UL Listed Receivers
• Ademco Contact ID
• 4+2 Standard
• SIA
NOTE: Ademco Contact ID must be used for independent zone
reporting.
The chart below shows UL listed receivers compatible with the
UDACT-2. A check in the protocol column indicates the receiver
supports that protocol.
4+2
Standard
1800/2300
Ademco
Contact
ID
Ademco 685 (1)


Ademco MX8000 (2)



Silent Knight 9500 (3)



Silent Knight 9800 (4)



FBI CP220FB (5)



Osborne Hoffman 2000E (6)


Electrical Specifications
Radionics 6600 (7)


Standby current: 40 mA.
SurGard MLR2 (8)
Type Mode Feature
Ademco Contact ID format - only Use Type Mode to identify
reports to Central Station as:
•
•
•
•
•
•
•
•
Fire Alarm
Supervisory
Pull Station
Heat Detector
Waterflow
Duct Detector
Flame Sensor
Smoke Zone
• Burglary
• 24 hour Non-Burglary
• High Temperature
• Low Temperature
• Low Water Pressure
• Low Water Level
• Pump Failure
Receiver
Current while communicating: 75 mA.
Maximum current while communicating and with open collector
output activated: 100 mA.
Voltage: Regulated 24 volts. Range: 21.2 to 28.2 volts.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory
for latest listing status.
• UL/ULC Listed: S635
• FM Approved
• CSFM: 7165-0028:0243 (NFS2-640/320), 7165-0028:0224
(NFS2-3030)
• FDNY: COA#6085, COA#6098

SIA

SurGard System III (9)

SurGard MLR-2000 (10)


(1) With 685-8 Line Card with Rev 4.4d software
(2) With 124060V206B and 124063 Line Card Rev B
(3) With version V2.4 Receiver & 126047 Line Card Rev G
(4) With 124077V2.00 Receiver &126047 Line Card Rev M
(5) With software V3.9
(6) With V.7301 Receiver S/W
(7) With 01.01.03 Receiver S/W & Line Card 01.01.03
(8) With software V1.86
(9) With sotware V1.72
(10) With DSP4016 and V1.6 Line Card
Ordering Information
UDACT-2: Universal Digital Alarm Communicator Transmitter.
Includes operating and programming instructions, and mounting
hardware.
MCBL-7: DACT phone cord, 7 ft (2.13 m) long (two required).
ABS-8RB: Metal enclosure for externally mounting UDACT-2 up
to 6,000 ft./1828.8 m from host FACP. 9.94" H x 4.63" W x 2.50"
D (cm: 25.248 H x 11.760 W x 6.350 D).
UBS-1B: Metal enclosure with solid door, Black.
UBS-1BR: Metal enclosure with solid door, Red.
R-10E: SPDT Form-C relay. Contacts rated for 10 A @ 115 VAC.
Connects to open collector relay driver.
R-20E: DPDT Two Form-C relays. Contacts rated for 10A @ 115
VAC. Connects to open collector relay driver.
FBD-1: Ferrite bead kit. Use for remote mounting only.
NOTI•FIRE•NET™ is a trademark and Notifier® is a registered trademark of
Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-60686:A1 • 4/2/12
dn-6927:a
FCPS-24S6(C/E) & FCPS24S8(C/E)
6- & 8-Amp 24-Volt
Remote Power Supplies
Power Supplies
General
The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are
remote power supplies with battery charger. The FCPS-24S6/24S8 may be connected to any 12 or 24 volt fire alarm control
panel (FACP) or may be used as stand-alone supplies. Primary applications include notification appliance (bell) circuit
(NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to support 24 volt system
accessories. The FCPS-24S6/-24S8 provides regulated and
filtered 24 VDC power to four notification appliance circuits
configured as either four Class B (Style Y) or Class A (Style Z,
with ZNAC-4 option module). Alternately, the four outputs may
be configured as all non-resettable, all resettable or two nonresettable and two resettable. The FCPS-24S6/-24S8 also
contains a battery charger capable of charging up to 18 AH
batteries. FCPS-24S6C & FCPS-24S8C are ULC-listed.
NOTE: Unless otherwise specified, the terms FCPS-24S6 and
FCPS-24S8 used in this document refers to the standard FCPS24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the
FCPS-24S6E and FCPS-24S8E
Features
• UL-Listed NAC synchronization using System Sensor,
Wheelock, or Gentex “Commander2” appliances.
• Operates as a “sync-follower” or as a “sync-generator”
(default). See note on page 2.
• Contains two fully-isolated input/control circuits - triggered
from FACP NAC (NAC expander mode) or jumped permanently “ON” (stand-alone mode).
• Four Class B (Style Y) or four Class A (Style Z, with
ZNAC-4 module) NACs.
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output, with 3 amps maximum/circuit, in NAC expander mode
(UL 864).
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous
output in stand-alone mode (UL 1481).
• Compatible with coded inputs; signals passed through.
• Optional power-supervision relay (EOLR-1).
• In stand-alone mode, output power circuits may be configured as: resettable, (reset line from FACP required),
non-resettable, or a mix of two and two.
• Fully regulated and filtered power output - optimal for powering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
• Power-limiting technology meets UL power-limiting requirements.
• Form-C normally-closed trouble relay.
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
• AC trouble report selectable for immediate 2-hour delay.
• Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power).
• Requires input trigger voltage of 9 - 32 VDC.
• Self-contained in compact, locking cabinet - 15”H x 14.5”W
x 2.75”D (cm: 38.1H x 36.83W x 6.985D).
6927pho1.jpg
• Includes integral battery charger capable of charging up to
18 AH batteries. Cabinet capable of housing 7.0 AH batteries.
• Battery charger may be disabled via DIP switch for applications requiring larger batteries.
• Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1mm2) wire.
Specifications
Primary (AC) Power:
• FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum.
• FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum.
• Wire Size: minimum #14 AWG (2.0mm2) with 600 V insulation.
Control Input Circuit:
• Trigger Input Voltage: 9 to 32 VDC.
• Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9
- 16 V).
Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA
maximum.
Output Circuits:
• +24 VDC filtered, regulated.
• 3.0 A maximum for any one circuit.
• Total continuous current for all outputs (stand-alone mode):
– FCPS-24S6: 4.0 A maximum.
– FCPS-24S8: 6.0 A maximum.
• Total short-term current for all outputs (NAC expander mode):
– FCPS-24S6: 6.0 A maximum.
– FCPS-24S8: 8.0 A maximum.
Secondary Power (Battery) Charging Circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 VDC.
dn-6927:a • 04/30/09 — Page 1 of 2
• Maximum current charge: 1.5 A.
• Maximum battery capacity: 18 AH.
Applications
Example 1: Expand notification appliance power an additional
6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four
Class B (Style Y) outputs or four Class A (Style Z) outputs
(using ZNAC-4). For example, the FACP notification appliance
circuits will activate the FCPS when reverse-polarity activation
occurs. Trouble conditions on the FCPS are sensed by the
FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A
(FCPS-24S8). Both resettable and non-resettable power
options are available. Resettable outputs are created by connecting the resettable output from the FACP to one or both of
the FCPS inputs.
Example 3: Use addressable control modules to activate the
FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
Standards and Codes
The FCPS-24S6 and FCPS-24S8 comply with the following
standards:
• NFPA 72 National Fire Alarm Code.
• UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
• UL 1481 Power Supplies for Fire Alarm Systems.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
•
•
•
•
•
UL Listed: S635, S674
ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C)
CSFM Approved: 7315-0028:225
MEA: 299-02-E
FM Approved
Ordering Information
For example, an addressable control module is used to activate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output
from the FCPS provides power to the addressable control
module.
FCPS-24S6: 6.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
*NOTE: Addressable FACPs are capable of locating control and
monitor modules at distances of up to 12,500 feet (3,810 meters).
FCPS-24S6R: Same as FCPS-24S6 with red enclosure.
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash
timing of all strobes in the system for ADA compliance.
Strobes accomplish this by monitoring very short timing pulses
on the NAC power which are created by the FACP. When
installed at the end of a NAC wire run, the FCPS-24S6/-24S8
can track (i.e. “follow”) the strobe synchronization timing
pulses on the existing NAC wire run. This maintains the overall
system flash timing of the additional strobes attaches to the
FCPS.
FCPS-24S6C: Same as above, ULC-listed.
FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S8: 8.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S8C Same as above, ULC-listed.
FCPS-24S8R: Same as FCPS-24S8 with red enclosure.
When the FCPS-24S6/-24S8 is configured (via DIP switch settings) as a “sync follower,” the FCPS’s NAC outputs track the
strobe synchronization pulses present at the FCPS’s sync
input terminal. The pulses originate from an upstream FACP or
other power supply.
FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
When the FCPS-24S6/-24S8 are configured (via DIP switch
settings) as a “sync generator,” the FCPS’s sync input terminals are not used. Rather, the FCPS is the originator of the
strobe synchronization pulses on the FCPS’s NAC outputs. In
“sync generator” mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings.
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire
smoke detector power.
ZNAC-4: Class A (Style Y) NAC option module.
BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT
Series data sheet DN-6933).
PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS
Series data sheet DN-1109)
System Sensor® and NOTIFIER® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — dn-6927:a • 04/30/09
DN-6820:B • D-123
FDU-80
80 Character Liquid Crystal Display
Annunciators
General
The FDU-80 is a compact, cost-effective, 80-character, backlit
LCD remote Fire Annunciator for use with the NOTIFIER FireWarden-100-2, NFS2-640, and NFS-320 Fire Alarm Control
Panels (FACPs). The FDU-80 mimics the display of the control
panel and displays complete system point status information.
Up to 32 FDU-80s may be connected onto the EIA-485 terminal port of each FACP. The FDU-80 requires no programming,
which saves time during system commissioning.
Features
• 80-character Liquid Crystal Display.
• Mimics all display information from the host panel.
• Control switches for System Acknowledge, Signal Silence,
Drill and Reset with enable key.
• System status LEDs for Power, Alarm, Trouble, Supervisory
and Alarm Silenced.
• No programming necessary — FDU-80 connects to the terminal porton the FACP.
• Displays device type identifiers, individual point alarm, trouble or supervisory, zone and custom alpha labels.
• Time-and-date display field.
• Aesthetically pleasing design.
• May be powered from the host FACP or by remote power
supply (requires 24 VDC).
• Up to 32 FDU-80 annunciators per FACP.
• Plug-in terminal blocks for ease of installation and service.
• Can be remotely located up to 6,000 feet (1828.8 m) from
the FACP.
• Local piezo sounder with alarm and trouble resound.
• Semi-flush mounts to 2.188" (5.556 cm) minimum deep,
three-gang electrical box (NOTIFIER PN 10103) or threegangable electrical switchbox.
• Surface-mounts to NOTIFIER PN SBB-3 surface backbox.
Operation
The FDU-80 annunciator provides the FACP with point annunciation with full display text on an 80-character LCD display.
The FDU-80 also provides an array of LEDs to indicate system
status, and includes control switches for remote control of critical system functions.
6820fdu8.jpg
Ordering Information
FDU-80: 80 character, backlit, LCD Fire Annunciator with control switches for remote control of system functions, and keyswitch lock.
FDU-80C: ULC-listed version; see DN-60573 for details.
10103: Three-gang electrical box, minimum 2.188" (5.556 cm)
deep, for semi-flush mount applications.
SBB-3: Three-gang surface backbox for surface-mount applications.
Agency Listings And Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
• UL Listed: S635
• MEA Listed: 245-00-E
• FDNY: COA#6038
• CSFM: 7120-0028:209
• FM Approved
NOTE: For ULC-listed version, see DN-60573.
The FDU-80 provides the FACP with up to 32 remote serially
connected annunciators. All field-wiring terminations on the
FDU-80 use removable, compression-type terminal blocks for
ease of wiring and circuit testing.
Communication between the FACP and the annunciators is
accomplished over an EIA-485 serial interface, which greatly
reduces wire and installation cost over traditional systems.
Installation
The FDU-80 can be semi-flush mounted to a 2.188" (5.556
cm) minimum deep, three-gang electrical box or three-gangable electrical switchboxes. Alternately, an SBB-3 surface
backbox is available for surface-mount applications.
DN-6820:B • 05/17/2010 — Page 1 of 2
NOTIFIER® is a registered trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6820:B • 05/17/2010
DN-6935:D • H-202
FSP-851(A) Series
Intelligent Plug-In Photoelectric
Smoke Detectors with FlashScan®
Intelligent/Addressable Devices
Notifier FSP-851(A) Series intelligent plug-in smoke detectors
with integral communication provide features that surpass conventional detectors. Detector sensitivity can be programmed in
the control panel software. Sensitivity is continuously monitored
and reported to the panel. Point ID capability allows each detector’s address to be set with rotary, decimal address switches,
providing exact detector location for selective maintenance
when chamber contamination reaches an unacceptable level.
The FSP-851(A) photoelectric detector’s unique optical sensing
chamber is engineered to sense smoke produced by a wide
range of combustion sources. Dual electronic thermistors add
135°F (57°C) fixed-temperature thermal sensing on the FSP851T(A). The FSP-851R(A) is a remote test capable detector for
use with DNR(A)/DNRW duct detector housings. FSP-851(A)
series detectors are compatible with Notifier Onyx and CLIP
series Fire Alarm Control Panels (FACPs).
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by Notifier that greatly increases the speed of
communication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the devices
in the group has new information, the panel’s CPU stops the
group poll and concentrates on single points. The net effect is
response speed greater than five times that of earlier designs.
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Sleek, low-profile design.
Addressable-analog communication.
Stable communication technique with noise immunity.
Low standby current.
Two-wire SLC connection.
Compatible with FlashScan® and CLIP protocol systems.
Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on
FlashScan systems).
Optional remote, single-gang LED accessory.
Dual LED design provides 360° viewing angle.
Visible bi-color LEDs blink green every time the detector is
addressed, and illuminate steady red on alarm (FlashScan
systems only).
Remote test feature from the panel.
Walk test with address display (an address on 121 will blink
the detector LED: 12-[pause]-1(FlashScan systems only).
Built-in functional test switch activated by external magnet.
Built-in tamper-resistant feature.
Sealed against back pressure.
Constructed of off-white fire-resistant plastic, designed to
commercial standards, and offers an attractive appearance.
94-5V plastic flammability rating.
SEMS screws for wiring of the separate base.
Optional relay, isolator, and sounder bases.
Specifications
Sensitivity: 0.5% to 2.35% per foot obscuration
Size: 2.1" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200S(A): 6.875" (17.46 cm) diameter.
FSP-851(A) in B210LP(A) Base
B210-2951.jpg
General
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
– B224BI(A): 6.2" (15.748 cm) diameter.
Shipping Weight: 5.2oz. (147g).
Operating Temperature range: FSP-851(A), 0°C to 49°C
(32°F to 120°F). FSP-851T(A), 0°C to 38°C (32°F to 100°F).
Low temperature signal for FSP-851T(A) at 45°F +/- 10°F
(7.22°C +/- 5.54°C). FSP-851R(A) installed in a DNR(A)/DNRW,
-20°C to 70°C (-4°F to 158°F).
UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/
min.), suitable for installation in ducts.
Relative Humidity: 10%-93% noncondensing.
Thermal Ratings: Fixed-temperature setpoint 135°F (57°C).
DETECTOR SPACING AND APPLICATIONS
Notifier recommends spacing detectors in compliance with
NFPA 72. In low airflow applications with smooth ceiling, space
detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m)
and higher. For specific information regarding detector spacing,
placement, and special applications refer to NFPA 72. System
Smoke Detector Application Guide, document A05-1003, is
available at systemsensor.com
ELECTRICAL SPECIFICATIONS
Voltage Range: 15-32 volts DC peak.
Standby Current (max. avg.): 300μA @ 24VDC (one communication every five seconds with LED enabled).
LED Current (max.): 6.5mA @ 24 VDC (“ON”).
Installation
FSP-851(A) plug-in detectors use a separate base to simplify
installation, service, and maintenance. A special tool allows
maintenance personnel to plug in and remove detectors without
using a ladder.
Mount base (all base types) on an electrical backbox which is at
least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: 1) Because of inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult the ISO-X(A) installation
DN-6935:D • 12/08/2011 — Page 1 of 2
sheet I56-1380 for device limitations between isolator modules
and isolator bases.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may be
in process. Consult factory for latest listing status.
UL Listed: S1115.
ULC Listed: S1115 (FSP-851A, FSP-851RA, FSP-851TA).
MEA Listed: 225-02-E .
FM Approved.
CSFM: 7272-0028:0206 .
Maryland State Fire Marshal: Permit # 2122 .
BSMI: CI313066760036.
CCCF: Certif. # 2004081801000017 (FSP-851T)
Certif. # 2004081801000016 (FSP-851).
• U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0
(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS320C, excluding B210LP(A)).
•
•
•
•
•
•
•
•
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the
B710LP(A) profile, or to convert older high-profile bases to lowprofile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Mounts to a
U.S. single-gang electrical box. For use with B501(A) and
B210LP(A) bases only.
SMB600: Surface mounting kit
M02-04-00:Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or removal
of detector heads from bases in high ceiling applications.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m)
sections.
T55-127-010: Detector removal tool without pole.
BCK-200B: Black detector covers for use with FSP-851(A) only;
box of 10.
WCK-200B: White detector covers for use with FSP-851(A)
only; box of 10.
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FSP-851: Low-profile intelligent photoelectric sensor. Must be
mounted to one of the bases listed below.
FSP-851A: Same as FSP-851 but with ULC listing.
FSP-851T: Same as FSP-851 but includes a built-in 135°F
(57°C) fixed-temperature thermal device.
FSP-851TA: Same as FSP-851T but with ULC listing.
FSP-851R: Low-profile intelligent photoelectric sensor, remote
test capable. For use with DNRA/DNRW.
FSP-851RA: Same as FSP-851R but with ULC listing. For use
with DNRA.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details on intelligent bases, see DN-60054.
B210LP(A): Standard U.S. flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200S(A): Intelligent, programmable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and
custom tone.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB(A): Plug-in System Sensor relay base. Screw terminals: up to 14 AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0
A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30
VDC inductive.
B224BI(A): Plug-in System Sensor isolator detector base.
Maximum 25 devices between isolator bases .
-Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6935:D • 12/08/2011
DN-6936:B • H-211
FST-851(A) Series
Intelligent Thermal (Heat) Detectors
with FlashScan®
Intelligent / Addressable Devices
Notifier FST-851(A) Series intelligent plug-in thermal detectors
with integral communication has features that surpass conventional detectors. Point ID capability allows each detector’s
address to be set with rotary, decimal address switches, providing exact detector locations. FST-851(A) Series thermal
detectors use an innovative thermistor sensing circuit to produce 135°F/57°C fixed-temperature (FST-851/A) and rate-ofrise thermal detection (FST-851R/A) in a low-profile package.
FST-851H(A) provides fixed high-temperature detection at
190°F/88°C. These thermal detectors provide effective, intelligent property protection in a variety of applications. FST851(A) Series detectors are compatible with Notifier Onyx and
CLIP series Fire Alarm Control Panels (FACPs).
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by Notifier Engineering that greatly enhances
the speed of communication between analog intelligent
devices and certain NOTIFIER systems. Intelligent devices
communicate in a grouped fashion. If one of the devices within
the group has new information, the panel’s CPU stops the
group poll and concentrates on single points. The net effect is
response speed greater than five times that of earlier designs.
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Sleek, low-profile, stylish design.
State-of-the-art thermistor technology for fast response.
Rate-of-rise model (FST-851R/A), 15°F (8.3°C) per minute.
Factory preset fixed temperature at 135°F (57°C); high-temperature model fixed at 190°F (88°C).
Addressable by device.
Compatible with FlashScan® and CLIP protocol systems.
Rotary, decimal addressing (1-99 on CLIP systems, 1-159
on FlashScan systems).
Two-wire SLC connection.
Visible LEDs “blink” every time the unit is addressed.
360°-field viewing angle of the visual alarm indicators (two
bi-color LEDs). LEDs blink green in Normal condition and
turn on steady red in Alarm.
Integral communications and built-in device-type identification.
Remote test feature from the panel.
Built-in functional test switch activated by external magnet.
Walk test with address display (an address of 121 will blink
the detector LED 12-(pause)-1).
Low standby current.
Backward-compatible.
Built-in tamper-resistant feature.
Designed for direct-surface or electrical-box mounting.
Sealed against back pressure.
Plugs into separate base for ease of installation and maintenance. Separate base allows interchange of photoelectric, ionization and thermal sensors.
SEMS screws for wiring of the separate base.
Constructed of off-white fire-resistant plastic, designed to
commercial standards, and offers an attractive appearance.
FST-851(A) in B210LP(A) Base
B210-2251.jpg
General
• 94-5V plastic flammability rating.
• Remote LED output connection to optional RA100Z(A)
remote LED annunciator.
• Optional sounder, relay, and isolator bases.
• Optional flanced surface mounting kit.
Specifications
Size: 2.1" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200S(A): 6.875" (17.46 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
– B224BI(A): 6.2" (15.748 cm) diameter.
Shipping weight: 4.8 oz. (137 g).
Operating temperature range: FST-851(A) Series, FST851R(A): –20°C to 38°C (–4°F to 100°F); FST-851H(A): –20°C
to 66°C (–4°F to 150°F).
Detector spacing: UL approved for 50 ft. (15.24 m) center to
center. FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing.
Relative humidity: 10% – 93% noncondensing.
Thermal ratings: fixed-temperature setpoint 135°F (57°C),
rate-of-rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C).
ELECTRICAL SPECIFICATIONS
Voltage range: 15 - 32 volts DC peak.
Standby current (max. avg.): 300 μA @ 24 VDC (one communication every 5 seconds with LED enabled).
LED current (max.): 6.5 mA @ 24 VDC (“ON”).
Applications
Use thermal detectors for protection of property. For further
information, go to systemsensor.com for manual I56-407-00,
Applications Manual for System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, wiring, and special applications.
DN-6936:B • 12/07/2011 — Page 1 of 2
Installation
The FST Series plug-in intelligent thermal detectors use a separate base to simplify installation, service, and maintenance.
Installation instructions are shipped with each detector. A special tool allows maintenance personnel to plug in and remove
detectors without using a ladder
Mount base (all base types) on an electrical backbox which is
at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: 1) Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult the ISO-X(A) installation
sheet I56-1380 for device limitations between isolator modules
and isolator bases.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document.In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
UL Listed: S747.
ULC Listed: S6978.
MEA Listed: 383-02-E.
FM Approved.
CSFM: 7270-0028:0196.
BSMI: CI313066760025.
CCCF: Certif. # 2004081801000018.
U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0
(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS320C, excluding B210LP(A)).
•
•
•
•
•
•
•
•
with ANSI Temporal 3, ANSI Temporal 4, continuous tone,
marching tone, and custom tone.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB(A): Intelligent relay base. Screw terminals: up to 14
AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
B224BI(A): Intelligent isolator base. Isolates SLC from loop
shorts. Maximum: 25 devices between isolator bases; see
Note 2 under Installation.
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the
B710LP(A) profile, or to convert older high-profile bases to
low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Fits U.S.
single-gang electrical box. Supported by B210LP(A) and
B501(A) bases only.
SMB600: Surface mounting kit, flanged.
M02-04-00: Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of FlashScan® Series detector heads from base in
high ceiling installations. Includes T55-127-010.
T55-127-010: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FST-851: Intelligent thermal detector. Must be mounted to one
of the bases listed below.
FST-851A: Same as FST-851 but with ULC Listing.
FST-851R: Intelligent thermal detector with rate-of-rise feature.
FST-851RA: Same as FST-851R but with ULC Listing.
FST-851H: Intelligent high-temperature thermal detector.
FST-851HA: Same as FST-851H but with ULC Listing.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Standard U.S. flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200S(A): Addressable Intelligent, programmable sounder
base capable of producing sound output in high or low volume
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6936:B • 12/07/2011
DN-6724:B3
FCM-1(A) & FRM-1(A)
Series
Control and Relay Modules
Intelligent / Addressable Devices
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
7000cov.JPG
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power,
audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops,
01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for
Class B or A (Style Y or Z).
Applications
The FCM-1(A) is used to switch 24 VDC audible/visual power,
high-level audio (speakers). The FRM-1(A) may be programmed to operate dry contacts for applications such as door
holders or Air Handling Unit shutdown, and to reset four-wire
smoke detector power.
• The FCM-1(A) is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• The FRM-1(A) provides two Form-C dry contacts that
switch together.
Operation
Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
addresses on a SLC loop (99 on CLIP loops). It responds to
regular polls from the control panel and reports its type and
status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll
received. On command, it activates its internal relay. The
FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
notification or control circuits.
Upon code command from the panel, the FCM-1(A) will disconnect the supervision and connect the external power supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication
to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the communication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a module and a sensor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-1-REL
datasheet (DN-60390) for new FlashScan® releasing applications.
Specifications for FCM-1(A)
Construction
Maximum current draw: 6.5 mA (LED on).
• The face plate is made of off-white heat-resistant plastic.
• Controls include two rotary switches for direct-dial entry of
address (01-159).
Average operating current: 350 μA direct poll, 375 μA group
poll with LED flashing, 485 μA Max. (LED flashing, NAC
shorted.)
Normal operating voltage: 15 to 32 VDC.
DN-6724:B3 • 2/17/2011 — Page 1 of 2
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC
supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the
current rating is 3A; For class A wiring system, the current rating is 2A.
Temperature range: 32°F to 120°F (0°C to 49°C).
Contact Ratings for FRM-1(A)
Current
Rating
Load
Description
Application
30 VDC
Resistive
Non-Coded
2A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-Coded
.9 A
125 VDC
Resistive
Non-Coded
.5 A
30 VDC
Inductive
(L/R=5ms)
Coded
1A
30 VDC
Inductive
(L/R=2ms)
Coded
.3 A
125 VAC
Inductive
(PF=0.35)
Non-Coded
1.5 A
25 VAC
Inductive
(PF=0.35)
Non-Coded
.7 A
70.7 VAC
Inductive
(PF=0.35)
Non-Coded
2A
25 VAC
Inductive
(PF=0.35)
Non-Coded
3A
Maximum
Voltage
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Specifications for FRM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 μA direct poll; 255 μA group
poll.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S3705 (A version only)
FM Approved
CSFM: 7300-0028:0219
MEA: 14-00-E
FDNY: COA #6067, #6065
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FCM-1(A): Intelligent Addressable Control Module.
FRM-1(A): Intelligent Addressable Relay Module.
A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the same
junction box as FCM-1(A).
NOTE: For installation instructions, see the following documents:
• FCM-1(A) Installation document I56-1169.
• FRM-1(A) Installation document I56-3502.
• Notifier SLC Wiring Manual, document 51253.
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6724:B3 • 2/17/2011
DN-6720:C • H-220
FMM-1(A), FMM-101(A),
FZM-1(A) & FDM-1(A)
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
General
Four different monitor modules are available for Notifier’s intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Style D (Class
A) or Style B (Class B) circuit of dry-contact input devices.
FMM-101(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices.
Its compact design allows the FMM-101(A) to be mounted in a
single-gang box behind the device it monitors.
FDM-1(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class
B) dry-contact initiating device circuits (IDCs) at two separate,
consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed
of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
FMM-1(A) Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
• LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate
alarm.
The FMM-1(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.
6999cov.jpg
FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style
D (Class A) or Style B (Class B) circuit.
FMM-1(A) (Type H)
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1 communication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FMM-1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normallyopen dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
DN-6720:C • 10/06/2010 — Page 1 of 4
FMM-101(A) Mini Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
FZM-1(A) Interface Module
6720m101.wmf
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power
source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops,
01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a programmable option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1(A) Interface Module is intended for use in intelligent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor twowire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The FZM-1(A)
can be used to replace MMX-2(A) modules in existing systems.
FZM-1(A) APPLICATIONS
The FMM-101(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The FMM-101(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and
security devices. The FMM-101(A) can be used to replace
MMX-101(A) modules in existing systems.
FMM-101(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the circuit.
Use the FZM-1(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K
ohm End-of-Line Resistor (provided) terminates the end of the
Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for
Style D application.
FZM-1(A) OPERATION
Each FZM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FZM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
FMM-101(A) OPERATION
Maximum current draw: 5.1 mA (LED on).
Each FMM-101(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC).
Maximum IDC wiring resistance: 25 ohms.
FMM-101(A) SPECIFICATIONS
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every
5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Page 2 of 4 — DN-6720:C • 10/06/2010
Average operating current: 300 μA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FDM1(A) Dual Monitor Module
The FDM-1(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices; or either normally open or normally closed security devices. The module has a single panelcontrolled LED.
NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits
ONLY. Style D (Class A) IDC circuits are NOT supported in any
application.
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
• Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)
• FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058
(NFS2-3030)
Product Line Information
FDM-1(A) SPECIFICATIONS
NOTE: “A” suffix indicates ULC-listed model.
Normal operating voltage range: 15 to 32 VDC.
FMM-1(A): Monitor module.
Maximum current draw: 6.4 mA (LED on).
FMM-101(A): Monitor module, miniature.
Average operating current: 750 μA (LED flashing).
FZM-1(A): Monitor module, two-wire detectors.
Maximum IDC wiring resistance: 1,500 ohms.
FDM-1(A): Monitor module, dual, two independent Class B circuits.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
SMB500: Optional surface-mount backbox.
EOL resistance: 47K ohms.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1(A) AUTOMATIC ADDRESSING
The FDM-1(A) automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1(A) is set to address “26”, then it will automatically
assign itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
!
CAUTION:
Avoid duplicating addresses on the system.
Installation
FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directly
to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The FMM-101(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S635
FM Approved
CSFM: 7300-0028:0219
MEA: 457-99-E
U.S. Coast Guard:
DN-6720:C • 10/06/2010 — Page 3 of 4
FlashScan® and NOTIFIER® are registered trademarks and FireWatch™ is
a trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 — DN-6720:C • 10/06/2010
DN-60429:C1
DNR(A)/DNRW InnovairFlex
Intelligent Non-Relay Photoelectric
Duct Smoke Detector
Intelligent Devices
General
The Notifier InnovairFlex® DNR(A) intelligent non-relay photoelectric duct smoke detector and DNRW watertight non-relay
photoelectric duct smoke detector feature a pivoting housing
that fits both square and rectangular footprints capable of
mounting to a round or rectangular duct.
DNRW duct smoke detector, with its NEMA-4 rating, is listed
as a watertight, UV resistant enclosure providing protection
against falling dirt, rain, and windblown dust, splashing and
hose directed water, allowing operators to use the detector in
the most extreme environments.
These units sense smoke in the most challenging conditions,
operating in airflow speeds of 100 to 4,000 feet per minute (0.5
to 20.32 m/s), temperatures of -4°F to 158°F (-20°C to 70°C),
and a humidity range of 0 to 95 percent (non-condensing.)
intelligent
An improved cover design isolates the sensor head, which
allows for ease of maintenance. A cover tamper feature indicates a trouble signal for a removed or improperly installed
sensor cover. The Notifier InnovairFlex housing provides a 3/
4-inch conduit knockout and ample space to facilitate easy wiring and mounting of a relay module.
Specifications
The Notifier InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional
wiring. The new InnovairFlex product line is compatible with all
previous Innovair models, including remote test accessories.
Weight: 1.6 lb (0.73 kg).
Features
• Photoelectric, integrated low-flow technology.
• Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to
20.32 m/s).
• Versatile mounting options: square or rectangular configuration.
• Broad ranges for operating temperature (-4°F to 158°F, 20°C to 70°C) and humidity (0% to 95% non-condensing).
• Patented sampling tube installs from front or back of the
detector with no tools required.
• Cover tamper signal.
• Increased wiring space with a newly added 3/4” conduit
knockout.
• Available space within housing to accommodate mounting
of a relay module.
• Easily accessible code wheels on sensor head (sold separately).
• Clear cover for convenient visual inspection.
• Remote testing capability.
• Requires com line power only.
• Accommodates the installation of an addressable relay
module, sold separately, (FRM-1 or NC-100R) for applications requiring a Form-C relay.
innovair-
Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm)
Width, 2.5 in (6.6 cm) Depth.
Size: (Square) 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width;
2.5 in (6.35 cm) Depth.
Operating Temperature Range: -4°F to 158°F (-20°C to
70°C).
Storage Temperature Range: -22°F to 158°F (-30°C to
70°C).
Operating Humidity Range: 0% to 95% relative humidity
(non-condensing).
Air Duct Velocity: 100 to 4,000 ft/min (0.5 to 20.32 m/s).
Accessories
Notifier provides system flexibility with a variety of accessories,
including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke
detectors, all duct smoke detectors accessories are UL listed.
DNR(W)s with a date code of 0013 or higher do not require
external 24VDC for remote test applications when used with a
remote-test-capable detector.
ACCESSORY CURRENT LOADS AT 24 VDC
Device
Standby
Alarm
RA100Z
0mA
12 mA Max
RTS151/
RTS151KEY
0mA
12mA Max
Agency Listings and Approvals
Consult product manual for lists of compatible UL-Listed
devices. In some cases, certain modules may not be listed by
certain approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL: S911, S3705.
• ULC: S635.
DN-60429:C1 • 4/19/2012 — Page 1 of 2
• CSFM: 3242-1653:0209.
• FM approved.
Product Line Information
NOTE: “A suffix indicates ULC listed model.
DNR(A): Intelligent non-relay photoelectric low flow smoke
detector housing. Requires photoelectric smoke detector (sold
separately).
DNRW: Watertight intelligent non-relay photoelectric low flow
duct smoke detector housing. Requires photoelectric smoke
detector (sold separately).
FSP-851R(A): Remote test capable addressable low-profile
photoelectric smoke detector.
FSP-851(A): Addressable low-profile photoelectric smoke
detector.
NP-100: Addressable low-profile photoelectric smoke detector
for FireWarden series panels.
NP-100R(A): Remote test capable addressable low-profile
photoelectric smoke detector for FireWarden series panels.
DCOIL: Remote test coil. Required for older DNR(W) duct
detector housing.
DST1(A): Metal sampling tube duct width up to 1 ft (0.3m).
DST1.5(A): Metal sampling tube duct widths up to 1 ft to 2 ft
(0.3 to 0.6 m).
DST3(A): Metal sampling tube duct widths up to 2 ft to 4 ft (0.6
to 1.2 m).
DST5(A): Metal sampling tube duct widths up to 4 ft to 8 ft (1.2
to 2.4 m).
DST10(A): Metal sampling tube duct widths up to 8 ft to 12 ft
(2.4 to 3.7 m).
DH400OE-1: Weatherproof enclosure.
ETX: Metal exhaust tube duct, width 1 ft (0.3 m).
M02-04-00: Test magnet.
P48-21-00: End cap for metal sampling tubes.
RA100Z(A): Remote annunciator alarm LED.
RTS151(A): Remote test station.
RTS151KEY(A): Remote test station with key lock.
Important Note
• DNRW duct detector housings with a date code of 0013 or
higher do not require a DCOIL or auxiliary 24 VDC for
remote test applications when used with a remote test
capable detector.
• DNRW duct detector housings with a date code of 0012 or
earlier require a DCOIL and auxiliary 24 VDC power for
remote test applications.
Notifier® and FlashScan® are a registered trademark of Honeywell
International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-60429:C1 • 4/19/2012
dn-60535:b1
Duct Smoke Detector
Accessories
for Notifier/System Sensor Products
Miscellaneous
General
Duct smoke detector accessories add functionality to the duct
smoke system by allowing quick, convenient inspections at eye
level and effective audible and visual notification options. All
System Sensor duct smoke detectors and accessories are UL
listed.
Specifications
APA151 PIEZO ANNUNCIATOR
APA151.wmf
60535cov.wmf
The APA151 piezo annunciator, which replaces the APA451
with a new, improved look, provides an audible alarm signal, a
red LED to indicate alarm status, and a green LED to indicate
power status. It is intended for use with System Sensor 4-wire
conventional duct smoke detector applications without a system
control panel, to comply with NFPA 90A.
APA151 Piezo Annunciator
Voltage
Regulated 24 VDC
Operating Voltage
16 to 33 VDC
Maximum Alarm Current
30 mA
Temperature Range
32°F to 120°F (0°C to 49°C)
Relative Humidity
10 to 93%, non-condensing
Wire Gauge
12 to 18 AWG
Dimensions
4.6” H x 2.9” W x .45” D
MHR/MHW SpectrAlert Advance Mini-Horns
Voltage
Regulated 12 DC or FWR (Full
Wave Rectified) or Regulated
24 VDC or FWR
Operating Voltage
8 to 33 VDC (9 to 33 VDC with
Sync-Circuit™ Module)
Sounder Current Draw
22 mA RMS max. at 8 to 17.5
Volts DC
17 mA RMS max. at 8 to 17.5
Volts FWR
29 mA RMS max. at 16 to 33
Volts DC
25 mA RMS max. at 16 to 33
Volts FWR
Temperature Range
32°F to 120°F (0°C to 49°C)
Humidity Range
10 to 93% non-condensing
Nominal Sounder Frequency
3 kHz
The MHR and MHW SpectrAlert® Advance mini-horns feature
temporal or continuous tones at high and low volume settings.
Their small footprint allows mounting to single-gang back
boxes for applications where a small device is desired.
Wire Gauge
12 to 18 AWG
Dimensions
4.6”H x 2.9”W x 0.45”D
MHR.wmf, MHW.wmf
MHR/MHW MINI-HORNS
dn-60535:b1 • 1/27/12 — Page 1 of 4
RA100Z/RA100ZA REMOTE ANNUNCIATORS
RA100Z.wmf
The RA100Z and RA100ZA remote annunciators are designed
for both conventional and intelligent applications. Their red LED
provides visual indication of an alarm condition.
RA100Z/RA100ZA Remote Annunciator
Voltage Range
Conventional System: 3.1 to 32
VDC
Intelligent System: 18 to 32
VDC
Maximum Alarm Current
10 mA
Dimensions
4.6”H x 2.8”W x 1.3”D
RTS151KEY Remote Test Station with Key
Power Requirements
Power LED (Green): 14 to 35
VDC, 12 mA max.
Alarm LED (RED): 2.8 to 32
VDC, 12 mA max.
Alarm Response Time
40 seconds max.
Temperature Range
14°F to 140°F (-10°C to 60°C)
Relative Humidity
95% non-condensing
Wire Gauge
14 to 18 AWG
Dimensions
4.6”H x 2.75W x 1.8”D
RTS2/RTS-AOS MULTI-SIGNALLING ACCESSORIES
The RTS2 and RTS2-AOS multi-signaling accessories are
designed to work with InnovairFlex 4-wire conventional duct
smoke detectors. These accessories include a key switch that
can be used to select one of two connected sensors to be
tested, reset, or both by a push button switch. They also enable
sensitivity measurements using the SENS-RDR sensitivity
reader (sold separately). The AOS (Add-On Strobe) is an
optional accessory included with the RTS2-AOS model.
RTS-AOS.wmf, AOS.wmf
RTS151/RTS151KEY REMOTE TEST STATIONS
The RTS151 and RTS151KEY remote test stations are automatic fire detector accessories designed to test duct smoke
detectors from a convenient location. For 4-wire detectors, the
RTS151KEY test station features a multi-colored LED that alternates between steady green and red. For 2-wire detectors, the
LED illuminates red for alarm.
RTS151.wmf, RTS151KEY.wmf
RTS2 and RTS-AOS Multi-signaling Accessory
RTS151 Remote Test Station
Power Requirements
Alarm LED 2.8 to 32 VDC, 10
mA max.
Total Current: 95 mA max.
Test Switch
10 VA @ 32 VDC
Reset Switch
10 VA @ 32 VDC
Alarm Response Time
40 seconds max.
Temperature Range
14°F to 140°F (-10°C to 60°C)
Relative Humidity
95% non-condensing
Wire Gauge
14 to 18 AWG
Dimensions
4.8”H x 2.9W x 1.4”D
Page 2 of 4 — dn-60535:b1 • 1/27/12
Voltage
20 to 29 VDC
Power Requirements
Standby: 3.0 mA max.
Trouble: 16.0 mA max.
Alarm without Strobe: 30 mA
max.
Alarm with Strobe: 55 mA max.
Sounder
85 dBA at 10 ft.
Temperature Range
14°F to 140°F (-10°C to 60°C)
Relative Humidity
95% non-condensing
Wire Gauge
14 to 22 AWG
Dimensions
4.8”W x 5.3”H x 1.6”D
Product Line Information
Agency Listings and Approvals
APA151: Piezo Annunciator
The listings and approvals below apply to the basic products. In
some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory
for latest listing status.
MHR: Mini-Horn, Red
MHW: Mini-Horn, White
RA100Z/RA100ZA: Remote Annunciator
RTS151: Remote Test Station
RTS151KEY: Remote Test Station with Key
RTS2: Multi-signaling Accessory
• UL: S4011 (APA 151, MHR, MHW), S2522 (RTS2,
RA100Z, RTS151, RTS151KEY, RTS2-AOS)
• FM Approved
• CSFM: 7135-1653:0212
AOS: Add-On Strobe
RTS2-AOS: Multi-Signaling Accessory
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49ºC/32 – 120ºF and at a relative humidity 93% ± 2% RH
(noncondensing) at 32ºC ± 2ºC (90ºF ± 3ºF). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27ºC/60 – 80ºF.
dn-60535:b1 • 1/27/12 — Page 3 of 4
FlashScan®, NOTIFIER® and System Sensor® are registered trademarks
of Honeywell International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 — dn-60535:b1 • 1/27/12
DN-6985:C • H-212
FSB-200(A) and FSB-200S(A)
Single-Ended, Reflector-Type
Addressable Beam Smoke Detector
Intelligent/Addressable Devices
GENERAL
The Notifier FSB-200 and FSB-200S are intelligent,
addressable reflected beam smoke detectors for protecting
open areas with high and sloping ceilings, and wide-open
areas, where spot-type smoke detectors are difficult to install
and maintain. Ideal applications are atriums, cathedral
ceilings, aircraft hangars, warehouses, sporting arenas,
concert halls, and enclosed parking facilities. They are
compatible with the NFS-3030, NFS2-3030, NFS-640, NFS2640, and NFS-320 in FlashScan® or CLIP mode, as well as
legacy addressable panels. Installation of the single-ended
reflective design is much quicker than a dual-ended projected
beam detector. Alignment is easily accomplished with an
optical sight and a two-digit signal strength meter incorporated
into the beam detector. Listed for operation from –22°F to
131°F, the FSB-200 and FSB-200S are usable in open area
applications where temperature extremes exceed the design
limits of other types of smoke detection.
The FSB-200 and FSB-200S are a transmitter/receiver unit
and a reflector. When smoke enters the area between the unit
and the reflector it causes a reduction in the signal strength.
When the smoke level (signal strength) reaches the
predetermined threshold, an alarm is activated. The detectors
have four standard sensitivity selections as well as two
Acclimate® settings. When either Acclimate® setting is
selected, the detector’s advanced software algorithms
automatically adjust to the optimum sensitivity for the specific
environment.
The FSB-200S has an integral sensitivity test feature of a filter
attached to a servomotor inside the detector optics. Activation
of the RTS151 or RTS151KEY remote test stations moves the
filter into the pathway of the light beam, testing the detector’s
sensitivity. This sensitivity test feature allows the user to
quickly and easily meet the annual maintenance and test
requirements of NFPA 72, without physical access to the
detector. The servomotor must be powered by +24 VDC, not
SLC power.
FEATURES
•
•
•
•
•
•
•
•
•
•
•
•
Listed to UL 268, ULC CAN/ULC S529.
Transmitter/receiver built into same unit.
Six user-selectable sensitivity levels.
16' to 328' (use BEAMLRK beyond 230') protection range.
Removable plug-in terminal blocks.
Digital display — no special tools required.
Built-in automatic gain control compensates for signal deterioration from dust buildup.
Optional remote test station.
Optional long-range kit (BEAMLRK) for applications in
excess of 230' (70 m).
Optional multi-mount kit (BEAMMMK) providing ceiling or
wall mount capability with increased angular adjustment.
Optional heater kits (BEAMHK and BEAMHKR) for
prevention of condensation (not intended to increase or
reduce the specified operating temperature).
Paintable cover.
FSB-200 with
Reflective Plate
6975reflect.jpg
FSB-200 with
BEAMMMK
6975beammk.jpg
SPECIFICATIONS
OPERATIONAL SPECIFICATIONS
Protection Range: 16 to 230 feet (5 to 70 m), 230 to 328 feet
(70 to 100 m) using optional BEAMLRK kit.
Adjustment Angle: ±10° horizontal and vertical. Note that
the optics move independently of the unit.
Sensitivity (6 levels):
NOTE: Sensitivity settings are a feature of specific control panels.
• Level 1 — 25%.
• Level 2 — 30%.
• Level 3 — 40%.
• Level 4 — 50%.
• Acclimate® Level 5 — 30% to 50%.
• Acclimate® Level 6 — 40% to 50%.
Fault Condition (trouble):
• 96% or more obscuration blockage.
• In alignment mode.
• Improper initial alignment.
• Self-compensation limit reached.
Alignment Aid:
• Optical gunsight.
• Integral signal strength indication.
• Two-digit display.
Indicators:
• Alarm — local red LED and remote alarm.
• Trouble — local yellow LED and remote trouble.
• Normal — local flashing green LED.
DN-6985:C • 11/16/09 — Page 1 of 4
Test/reset features:
MECHANICAL SPECIFICATIONS
• Integral sensitivity test filter (FSB-200S only, requires
external power supply).
• Sensitivity filter (incremental scale on reflector).
• Local alarm test switch.
• Local alarm reset switch.
• Remote test and reset switch (compatible with RTS151 and
RTS151KEY test stations).
Smoke Detector Spacing: On smooth ceilings, 30 – 60 feet
(9.1 to 18.3 m) between projected beams and not more than
one-half that spacing between a projected beam and a
sidewall. Other spacing may be used depending on ceiling
height, airflow characteristics, and response requirements.
See NFPA 72.
Shipping Weight: 3.7 lbs (1.68 kg)
ENVIRONMENTAL SPECIFICATIONS
Temperature: –22°F to 131°F (–30°C to 55°C).
Humidity: 10 – 93% RH noncondensing.
ELECTRICAL SPECIFICATIONS
• Voltage: 15 to 32 VDC.
• Average Standby Current (24 VDC): 2 mA maximum
(LED flashing, SLC @ 24 V).
• Alarm Current (LED on): 8.5 mA maximum.
• Trouble Current (LED on): 4.5 mA maximum.
• Alignment Current: 20 mA maximum.
• External Supply (FSB-200S only):
Voltage — 15 to 32 VDC
Current — 0.5 A maximum.
• Remote Output (Alarm):
Voltage - 15 to 32 VDC (Output voltage same as device
input voltage)
Current - 15 mA maximum, 6 mA minimum (Output current
is limited by 2.2K ohm resistor)
• Heater Kit BEAMHK: Voltage - 15 to 32 V; Current - 92 mA
maximum @ 32 V (heater only); Power Consumption nominal 1.6 W @ 24 V, maximum 3.0 W @ 32 V.
• Reflector Heater Kit BEAMHKR: Voltage - 15 to 32 V;
Current - 450 mA maximum @ 32 V (per reflector); Power
Consumption (per reflector) - nominal 7.7 W @ 24 V,
maximum 15.0 W @ 32 V.
Detector Dimensions: 10.0" H x 7.5" W x 3.3" D (254 mm H x
191 mm W x 84 mm D).
Reflector Dimensions for 16' to 230' (5 to 70m)
Applications: 7.9" x 9.1" (200 x 230 mm).
Reflector Dimensions for Applications Beyond 230'/70m:
15.7" x 18.1" (400 x 460 mm).
SENSITIVITY SELECTION
The detector has six sensitivity selections (sensitivity settings
are a feature of specific control panels). Each of these
selections is only acceptable over a specific distance
separation between the detector and the reflector per UL 268.
The chart below determines which selections are acceptable
for your installed distance. The sensitivity of the detector can
be set only when the housing is removed and the detector is
not in the fine adjustment step of the alignment mode,
indicated by the illumination of the dual digital display. To set
the sensitivity, depress the sensitivity button one time. See
Switch Locations diagram. Once the switch is pressed, the
digital display will illuminate and read the current sensitivity
setting in percent obscuration. To change the sensitivity,
continue to depress the sensitivity switch until the desired
setting is achieved. The digital display will turn off
automatically if no further switch presses occur.
Sensitivity
Percent
Setting Obscuration
Display
Reading
Acceptable Acceptable
DISTANCE DISTANCE
between
between
Detector
Detector
and
and
Reflector
Reflector
(ft)
(m)
Level 1
25%
Level 2
30%
Level 3
40%
Level 4
50%
Acclimate ®
30% to 50%
Level 1
Acclimate ®
40% to 50%
Level 2
25
30
40
50
16.4 to 120 5.0 to 36.6
25 to 150 7.6 to 45.7
60 to 220
18.3 to 67
80 to 328 24.4 to 100
A1
80 to 150
24.4 to 45.7
A2
80 to 200
24.4 to 67
In addition to the four standard sensitivity selections, the
detector has two Acclimate® settings. When either Acclimate®
setting is chosen the detector will automatically adjust its
sensitivity using advanced software algorithms to select the
optimum sensitivity for the environment. The sensitivity will be
continuously adjusted within the ranges specified in the chart
above.
Total obscuration can be converted to percent per foot,
assuming uniform smoke density for the entire length of the
beam. The chart below converts total obscuration percent per
foot for all acceptable sensitivity settings.
Page 2 of 4 — DN-6985:C • 11/16/09
6985graph.tif
6985swlo.wmf
Table 1: Total Obscuration
6985wir1-2.wmf
Switch Locations
Listed
Remote
Power
Source*
*Used only for
FSB-200S.
See electrical
ratings.
From Panel
or Previous
device.
Communication Line
32 VDC Maximum
Twisted pair is
recommended
To Next
Device
6985adjloc.tif
Wiring Diagram
FSB-200/FSB-200S
Pin 2
Pin 4
Pin 3
Pin 5
RTS151/KEY
Remote Alarm Out
AUX (-)
Reset Input
Test Input
Alignment and Adjustment Locations
6985wirerts151.tif
Pin 1
See RTS151/KEY Installation Instructions
for electrical ratings of the RTS151/KEY
Wiring Diagram with RTS151/KEY
PARTS LIST
Item Quantity
Transmitter/Receiver Unit 1
Paintable Trim Ring 1
Reflector 1
Plug-In Terminal Blocks 3
Isolator Shunts 2
Instruction Manual 1
Housing Screw Locations
6985part.wmf
6985screwlocs.tif
Orange Sticky Paper 1
DN-6985:C • 11/16/09 — Page 3 of 4
AGENCY LISTINGS AND APPROVALS
PRODUCT LINE INFORMATION
These listings and approvals apply to the devices specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
FSB-200: Intelligent beam smoke detector
•
•
•
•
•
•
UL Listed: S2522 (FSB-200, FSB-200S)
ULC Listed: S2522 (FSB-200A, FSB-200SA)
CSFM: 7260-0028:228
MEA: 95-04-E
Maryland State Fire Marshal: Permit # 2167
FM Approved
FSB-200A: Same as FSB-200 with ULC Listing.
FSB-200S: Intelligent beam smoke detector with integral sensitivity test.
FSB-200SA: Same as FSB-200S with ULC Listing.
BEAMLRK: Long range accessory kit (required for applications in excess of 230 ft/70 m).
BEAMMMK: Multi-mount kit (provides ceiling or wall mount
capability with increased angular adjustment).
BEAMSMK: Surface-mount kit.
RTS151: Remote test station.
RTS151A: Same RTS151 with ULC listing.
RTS151KEY: Remote test station with key lock.
RTS151KEYA: Same as the RTS151KEY with ULC listing.
BEAMHK: Heating kit for use with the transmitter/receiver unit
of FSB-200S. For prevention of condensation.
BEAMHKR: Heating kit for use with the reflector on
FSB-200S. For prevention of condensation
6500-MMK: Heavy-duty multi-mount kit for installations prone
to vibration or where there is difficulty mounting the set angle.
When installed with the transmitter/receiver unit, the 6500SMK must be used as well.
6500-SMK: Surface-mount kit (required when using 6500MMK to mount transmitter/receiver).
6975beammk.jpg
rts151key.wmf
rts151.wmf
6985hk.tif
BEAMMMK
(ceiling or wall mount kit sold separately)
RTS151
RTS151KEY
BEAMHK
Acclimate® Plus™ is a trademark of Honeywell International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 — DN-6985:C • 11/16/09
DN-60054:F • H-320
Intelligent Bases
B501(A), B200S(A), B200SR(A),
B210LP(A), B2241BI(A), B224RB(A), 
Mounting Kits, and Accessories
Intelligent/Addressable Devices
60054b5.jpg
Flangeless Mounting Base
B501(A)
Specifications
Diameter:
– B501: 4.1" (104 mm).
– B224BI, B224RB, B210LP: 6.1" (155 mm).
– B200S/SR/SCOA: 6.875" (17.46 cm).
Wire gauge:
– B224BI, B224RB: 14 to 24 AWG.
– B210LP, B501, B200S/SR/SCOA: 12 to 24 AWG.
Temperature range:
– B224BI, B224RB, B200S/SR/SCOA: 32°F to 120°F (0°C
to 49°C).
– B210LP, B501: -4°F to 150°F (-20°C to 66°C).
Humidity range: 10% to 93% RH, non-condensing.
System temperature and humidity ranges: This system
meets NFPA requirements for operation at 0°C to 49°C (32°F
to 120°F); and at a relative humidity (noncondensing) of 85%
at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C
(89.6°F ± 1.1°F) per ULC. However, the useful life of the system’s standby batteries and the electronic components may be
adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all
peripherals be installed in an environment with a nominal room
temperature of 15°C to 27°C (60°F to 80°F).
60054sr.jpg
Relay, isolator, and sounder bases can be used to meet
local code requirements. Relay bases provide one Form-C
contact relay for control of auxiliary functions such as door closure and elevator recall. Isolator bases allow loops to continue
to operate under fault conditions and automatically restore
when the fault is removed. Sounder bases are available in
temporal and non-temporal pattern versions depending on
whether the signal is to be used for evacuation purposes.
Flanged Mounting Base
B210LP(A)
Sounder Base
B200S(A), B200SR(A),
B200SCOA
60054rb.jpg
Intelligent FlashScan® and CLIP mounting bases and kits provide a variety of ways to install NOTIFIER detectors in any
application. Intelligent detectors can be mounted in either
flanged or flangeless bases depending on junction box selection (see Junction Box Selection Guide). Across this product
line, detectors plug in easily to the base with SEMS screws;
and models employ various 12 to 24 AWG wire ranges.
60054LP.jpg
General
Relay Base
B224RB(A)
– B200S, high-volume*: Greater than 85 dBA minimum.
– B200S, low-volume*: Greater than 75 dBA minimum.
– B200SR*: Greater than 85 dBA minimum.
– B200SCOA, high-volume**: Greater than 87 dBA minimum.
– B200SCOA, low-volume**: Greater than 85 dBA minimum
*Measured in a UL reverberant room at 10 feet, 24 Volts (continuous tone)
**Measured in a ULC anechoic room at 10 feet, 24 Volts continuous tone)
FOR B224RB, B224BI:
Operating voltage: 15 to 32 VDC (powered by SLC).
Standby ratings: <500 µA maximum @ 24 VDC.
Set time (B224RB only): short delay 55 to 90 msec; long
delay 6 to 9 seconds.
Reset time (B224RB only): 20 msec maximum.
Relay characteristics (B224RB only): two-coil latching relay;
one Form-C contact; ratings (UL/CSA): 0.9 A @ 125 VAC, 0.9
A @ 110 VDC, and 3.0 A @ 30 VDC.
Product Line Information
INTELLIGENT BASES
Electrical Ratings
B501: Flangeless mounting base.
FOR B200S/SR/SCOA:
B501A: Flangeless mounting base, ULC Listed.
External supply voltage: 16 to 33 VDC (VFWR)
B501BP: Bulk pack of B501 (10).
Standby current: 500 µA maximum.
B210LP: Flanged mounting base.
Alarm current:
B210LPA: Flanged mounting base, ULC listed
– B200S: 35 mA maximum at high-volume setting; 
15 mA maximum at low-volume setting.
– B200SR: 35 mA maximum.
– B200SCOA: 40mA Max. (DC), 70mA Max. (FWR)
SLC operating voltage: 15 to 32 VDC.
B210LPBP: Bulk pack of B210LP (10).
SLC standby current: 300 µA.
B200S: Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal
3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. Only compatible with the
NFS-320, NFS2-640 and NFS2-3030 operating version with
version 15.0 or higher panel firmware.
Sound output:
B200SA: Same as B200S with ULC-listing.
DN-60054:F • 09/03/2013 — Page 1 of 2
B200SCOA: Same as B200S with ULC-listing and CO detector markings in English/French (required in Canada for ULC
applications with FCO-851A).
M02-09-00: Test magnet with telescoping handle.
B200SR: Intelligent sounder base capable of producing sound
output with ANSI Temporal 3 or continuous tone.
XR2: Detector Remove Tool for use with low profile detector
heads, and FSL-751.
B200SRA: Same as B200SR with ULC-listing.
XP-4: Extension pole for XR2/B (5 to 15 ft/1.524 to 4.572 m).
B224RB: Relay base.
T55-127-010: Detector removal head.
B224RBA: Relay base, ULC Listed.
BCK-200B: Black detector kit, package of 10 (for use with
photo and ion detectors).
XR2B: Detector removal tool for current heads (T55-127-010
included).
B224BI: Isolator base.
B224BIA: Isolator base, ULC Listed.
WCK-200B: White detector kit, package of 10 (for use with
photo and ion detectors).
MOUNTING KITS AND ACCESSORIES
SMB600: Surface mounting kit, flanged.
Agency Listings and Approvals
F110: Retrofit flange for converting high-profile bases to lowprofile.
The listings and approvals below apply to intelligent bases as
noted. In some cases, certain modules or applications may not
be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
F110BP: Bulk pack of F110 (10).
F210: Accessory flange ring for B210LP(A) base (new
design). 6-inch diameter.
•
•
•
•
•
F210BP: Bulk pack of F210 (10).
RA100Z: Remote LED annunciator.
RA100ZA: Remote LED annunciator, ULC Listed.
M02-04-00: Detector test magnet.
UL Listed: S911
ULC Listed: S911
FM Approved
MEA: 22-95-E, 205-94-E Vol. 2; 257-06-E
CSFM:
7300-1653:0126,
7135-1653:0213,
1653:0109
7300-
Junction Box Selection Guide
Base Models
Single
Gang
3.5" Oct.
4.0" Oct.
4.0" Sq.
4.0" Sq.
with 3.0"
mud ring
50 mm
60 mm
70 mm
75 mm
B200S, B200SR,
B200SCOA
Yes
Yes
Yes
Yes
Yes
No
No
No
No
B501
No
Yes
No
No
Yes
Yes
Yes
Yes
No
B210LP
Yes
Yes
Yes
Yes
Yes
No
No
No
No
B224RB
No
Yes
Yes
Yes
No
No
Yes
Yes
Yes
B224BI
No
Yes
Yes
Yes
No
No
No
Yes
Yes
NOTE: Box depth contingent on base and wire size.
Refer to National Electric Code or applicable local codes for appropriate recommendations.
FlashScan®, NOTIFIER® and System Sensor® are registered trademarks
of Honeywell International Inc.
©2013 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-60054:F • 09/03/2013
DN-6726:D • H-240
NBG-12LX
Addressable Manual Pull Station
Intelligent/Addressable Devices
‘General
The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e.,
requires two motions to activate the station) pull station that
includes an addressable interface for any Notifier intelligent
control panel except FireWarden series panels, and the NSP25 panel. Because the NBG-12LX is addressable, the control
panel can display the exact location of the activated manual
station. This leads fire personnel quickly to the location of the
alarm.
Construction
Shell, door, and handle are molded of durable polycarbonate
material with a textured finish.
Specifications
•
•
•
•
•
•
•
•
Shipping Weight: 9.6 oz. (272.15 g)
Normal operating voltage: 24 VDC.
Maximum SLC loop voltage: 28.0 VDC.
Maximum SLC standby current: 375 μA.
Maximum SLC alarm current: 5 mA.
Temperature Range: 32°F to 120°F (0°C to 49°C)
Relative Humidity: 10% to 93% (noncondensing)
For use indoors in a dry location
6643cov1.jp
• Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word “ACTIVATED”
appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to
SLC loop (accepts up to 12 AWG/3.25 mm² wire).
• Can be surface mounted (with SB-10 or SB-I/O) or semiflush mounted. Semi-flush mount to a standard singlegang, double-gang, or 4" (10.16 cm) square electrical box.
• Smooth dual-action design.
• Meets ADAAG controls and operating mechanisms guidelines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
maximum activation force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
• Includes Braille text on station handle.
• Optional trim ring (BG12TR).
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Up to 99 NBG-12LX stations per loop on CLIP protocol
loops.
• Up to 159 NBG-12LX stations per loop on FlashScan® protocol loops.
• Dual-color LED blinks green to indicate normal on
FlashScan® systems.
g
Features
The NBG-12LX
Addressable Manual Pull Station
Installation
The NBG-12LX will mount semi-flush into a single-gang, double-gang, or standard 4" (10.16 cm) square electrical outlet
box, or will surface mount to the model SB-10 or SB-I/O surface backbox. If the NBG-12LX is being semi-flush mounted,
then the optional trim ring (BG12TR) may be used. The
BG12TR is usually needed for semi-flush mounting with 4"
(10.16 cm) or double-gang boxes (not with single-gang boxes).
Operation
Pushing in, then pulling down on the handle causes it to latch
in the down/activated position. Once latched, the word “ACTIVATED” (in bright yellow) appears at the top of the handle,
while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
key and pull the door open. This action resets the handle; closing the door automatically resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address settings
(1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems).
Architectural/Engineering
Specifications
Manual Fire Alarm Stations shall be non-coded, with a keyoperated reset lock in order that they may be tested, and so
designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key. An operated station shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
red-colored polycarbonate material with clearly visible operating instructions provided on the cover. The word FIRE shall
appear on the front of the stations in white letters, 1.00 inches
(2.54 cm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-10 or SB-I/O; or semi-flush
mounting on a standard single-gang, double-gang, or
DN-6726:D • 4/13/2012 — Page 1 of 2
4" (10.16 cm) square electrical box, and shall be installed
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the control panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.
The loop poll LED shall be clearly visible through the front of
the station. The LED shall flash while in the normal condition,
and stay steadily illuminated when in alarm.
Product Line Information
NBG-12LX: Dual-action addressable pull station. Includes key
locking feature. (Listed for Canadian and non-Canadian applications.)
NBG-12LXSP: Spanish/English labelled version.
NBG-12LXP: Portuguese labelled version.
SB-10: Surface backbox; metal.
SB-I/O: Surface backbox; plastic.
BG12TR: Optional trim ring.
17021: Keys, set of two.
NY-Plate: New York City trim plate.
Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL/ULC Listed: S692 (listed for Canadian and non-Canadian applications).
• MEA: 67-02-E.
• CSFM: 7150-0028:0199.
• FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030).
• BSMI: CI313066760047.
• U.S. Coast Guard.
• Lloyd’s Register.
• FM Approved.
Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772;
6,632,108.
NOTIFIER® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6726:D • 4/13/2012
A/E verify
Indoor SelectableOutput Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert® Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• A
utomatic selection of 12- or 24-volt operation at
15 and 15/75 candela
• F
ield-selectable candela settings on wall units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for wall units
• M
ounting plate shorting spring checks wiring continuity before
device installation
• Electrically Compatible with legacy SpectrAlert devices
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting
3023572
Like the entire SpectrAlert Advance product line, wall-mount horns,
strobes, and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.
Agency Listings
S4011 (chimes, horn strobes, horns)
S5512 (strobes)
The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance
can meet virtually any application requirement.
MEA452-05-E
7125-1653:186 (indoor strobes)
7125-1653:188 (horn strobes,
chime strobes)
7135-1653:189 (horns, chimes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or
double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or fullwave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature
Humidity Range
Strobe Flash Rate
Nominal Voltage
Operating Voltage Range2
Operating Voltage Range MDL3 Sync Module
Input Terminal Wire Gauge
Wall-Mount Dimensions (including lens)
Horn Dimensions
Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS)
32°F to 120°F (0°C to 49°C)
10 to 93% non-condensing
1 flash per second
Regulated 12 DC/FWR or regulated 24 DC/FWR1
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
12 to 18 AWG
5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)
5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)
5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS)
8–17.5 Volts
Candela DC
FWR
Standard
15
123
128
Candela
15/75
142
148
Range
30
NA
NA
75
NA
NA
95
NA
NA
110
NA
NA
115
NA
NA
High
135
NA
NA
Candela
150
NA
NA
Range
177
NA
NA
185
NA
NA
16–33 Volts
DC
FWR
66
71
77
81
94
96
158
153
181
176
202
195
210
205
228
207
246
220
281
251
286
258
UL Max. Horn Current Draw (mA RMS)
8–17.5 Volts
Sound Pattern
dB
DC
FWR
Temporal
High
57
55
Temporal
Medium
44
49
Temporal
Low
38
44
Non-temporal
High
57
56
Non-temporal
Medium
42
50
Non-temporal
Low
41
44
Coded
High
57
55
Coded
Medium
44
51
Coded
Low
40
46
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts
16–33 Volts
DC Input
15
15/75
15
15/75
30
75
Temporal High
137
147
79
90
107
176
Temporal Medium
132
144
69
80
97
157
Temporal Low
132
143
66
77
93
154
Non-Temporal High
141
152
91
100
116
176
Non-Temporal Medium
133
145
75
85
102
163
Non-Temporal Low
131
144
68
79
96
156
FWR Input
Temporal High
136
155
88
97
112
168
Temporal Medium
129
152
78
88
103
160
Temporal Low
129
151
76
86
101
160
Non-Temporal High
142
161
103
112
126
181
Non-Temporal Medium
134
155
85
95
110
166
Non-Temporal Low
132
154
80
90
105
161
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
16–33 Volts
DC Input
135
150
177
185
FWR Input
Temporal High
245
259
290
297
Temporal High
Temporal Medium
235
253
288
297
Temporal Medium
Temporal Low
232
251
282
292
Temporal Low
Non-Temporal High
255
270
303
309
Non-Temporal High
Non-Temporal Medium
242
259
293
299
Non-Temporal Medium
Non-Temporal Low
238
254
291
295
Non-Temporal Low
Horn and Horn Strobe Output (dBA)
Switch
Position
1
2
3
4
5
6
7†
8†
9†
Sound Pattern
Temporal
Temporal
Temporal
Non-Temporal
Non-Temporal
Non-Temporal
Coded
Coded
Coded
dB
High
Medium
Low
High
Medium
Low
High
Medium
Low
8–17.5
Volts
DC FWR
78 78
75 75
71 71
82 82
78 78
73 74
82 82
78 78
74 75
16–33
Volts
DC FWR
84 84
80 80
76 76
88 88
85 85
81 81
88 88
85 85
81 81
Settings 7, 8, and 9 are not available on 2-wire horn strobes.
†
95
194
182
179
201
187
182
110
212
201
198
221
207
201
115
218
210
207
229
216
210
190
184
184
203
189
184
210
202
194
221
208
202
218
206
201
229
216
211
16–33 Volts
135
150
215
231
209
224
207
221
233
248
219
232
214
229
Horn Tones and Sound Output Data
24-Volt Nominal
Reverberant Anechoic
DC
FWR
DC FWR
88
88
99 98
86
86
96 96
83
80
94 89
93
92
100 100
90
90
98 98
88
84
96 92
93
92
101 101
90
90
97 98
88
85
96 92
16–33 Volts
DC
FWR
69
75
58
69
44
48
69
75
60
69
50
50
69
75
56
69
52
50
177
258
250
248
275
262
256
185
265
258
256
281
267
262
SpectrAlert Advance Dimensions
4.7˝
6.8˝
Dia.
2.5˝
2.5˝
5.6˝
Wall-mount horn strobes
SpectrAlert Advance Ordering Information
Model
Description
Wall Horn Strobes
P2R
2-Wire Horn Strobe, Standard cd, Red
P2R-P
2-Wire Horn Strobe, Standard cd, Red, Plain
P2R-SP
2-Wire Horn Strobe, Standard cd, Red, “FUEGO”
P2RH
2-Wire Horn Strobe, High cd, Red
P2RH-P
2-Wire Horn Strobe, High cd, Red, Plain
P2W
2-Wire Horn Strobe, Standard cd, White
P2W-P
2-Wire Horn Strobe, Standard cd, White, Plain
P2WH
2-Wire Horn Strobe, High cd, White
P2WH-P
2-Wire Horn Strobe, High cd, White, Plain
P4R
4-Wire Horn Strobe, Standard cd, Red
P4R-P
4-Wire Horn Strobe, Standard cd, Red, Plain
P4RH
4-Wire Horn Strobe, High cd, Red
P4W
4-Wire Horn Strobe, Standard cd, White
Wall Strobes
SR
Strobe, Standard cd, Red
SR-P
Strobe, Standard cd, Red, Plain
SR-SP
Strobe, Standard cd, Red, “FUEGO”
Model
Description
Wall Strobes (cont.)
SRH
Strobe, High cd, Red
SRH-P
Strobe, High cd, Red, Plain
SRH-SP
Strobe, High cd, Red, “FUEGO”
SW
Strobe, Standard cd, White
SW-P
Strobe, Standard cd, White, Plain
SWH
Strobe, High cd, White
SWH-P
Strobe, High cd, White, Plain
Horns
HR
Horn, Red
HW
Horn, White
Accessories
TR-HS
Trim Ring, Wall, Red
SBBR
Indoor Surface Mount Back Box, Red
SBBW
Indoor Surface Mount Back Box, White
Notes:
All -P models have a plain housing (no “FIRE” marking on cover)
All -SP models have “FUEGO” marking on cover
“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.
“High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS10201 • 1/14
PS-12550 12 Volt 55.0 AH
Features
•Absorbent Glass Mat (AGM) technology for superior
performance
•Valve regulated, spill proof construction allows safe
operation in any position
•Power/volume ratio yielding unrivaled energy density
• Rugged impact resistant ABS case and cover (UL94-HB)
• Integrated ABS carrying handles for ease of movement
•Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and
C.A.B. certified
• U.L. recognized under file number MH 20845
Terminals
(mm)
U: Positive Terminal
10
8.5
8.5
9
T6
Nominal Capacity
22
13
Nominal Voltage......................................................................... 12 volts (6 cells)
18
9
• T 6: Threaded insert
w. 6 mm stud
fastener
15.9
22
10
17.4
18
•U
: Universal
terminals: Heavyduty posts with ‘nut
& bolt’ fasteners
Performance Specifications
U: Negative Terminal
13
16
M6
6
20-hr. (2.75A to 10.50 volts) . ......................................................... 55.0 AH
10-hr. (5.1A to 10.50 volts) .............................................................. 51.0 AH
5-hr.
(8.8A to 10.20 volts) ............................................................. 44.0 AH
1-hr.
(30.6A to 9.00 volts) . ........................................................... 30.6 AH
15-min.(96A to 9.00 volts)...................................................................24.0 AH
Approximate Weight .......................................................... 36.0 lbs. (16.33 kg)
Physical Dimensions: in (mm)
Energy Density (20-hr. rate) ............................... 1.64 W-h/in3 (100.30 W-h/l)
Specific Energy (20-hr. rate) . ............................. 17.65 W-h/lb (38.91 W-h/kg)
Internal Resistance (approx.) . ....................................................... 7 milliohms
W
Max Discharge Current (7 Min.) .............................................. 165.0 amperes
Max Short-Duration Discharge Current (10 Sec.)................. 410.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
Sealed Rechargeable
Battery
HT
MODEL PS-12550 U
H
12 Volt 55.0 Amp. Hr.
1 Month ...................................................................................................... 97%
3 Months...................................................................................................... 91%
6 Months . ................................................................................................... 83%
ST B E R
MU
Pb
YC L ED
EC
T TE RY
BA
®
MH20845
www.power-sonic.com
NONSPILLABLE
L
Operating Temperature Range
Charge... ........................................................... -4°F (-20°C) to 122°F (50°C)
Discharge........................................................ -40°F (-40°C) to 140°F (60°C)
L: 9.04 (230) W: 5.45 (138) H: 8.15 (207) HT: 8.98 (228)
Case....................................................................................................... ABS Plastic
Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for
height dimensions. All data subject to change without notice.
Power-Sonic Chargers.............................................................PSC-1210000A-C
To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.
All data subject to change without notice.
www.power-sonic.com
PS-12550 12 Volt 55.0 AH
®
Constant Power Discharge Ratings
MODEL
WATTS PER CELL @ 25° C
FINAL
VOLTAGE
5 MIN
10 MIN
15 MIN
20 MIN
30 MIN
45 MIN
60 MIN
1.75
320
210
184
153
115
87
72
1.70
342
225
190
158
118
89
73
1.67
354
230
194
160
120
90
74
PS-12550
Discharge Characteristics
Discharge Time vs. Discharge Current
14.0
5
Discharge Time
o
Final
Voltage
10.5V
2
10.2V
1
9.6V
min
30
5
o
8.1V
2.75
5.5
11
12.0
11.0
10.0
9.0
27.5 55
1.2
o
40 C (104 F)
o
o
20 C (68 F)
o
o
0 C (32 F)
2.4
6
Note: Due to the self-discharge characteristics of this type of battery, it is
imperative that they be charged within 6 months of storage, otherwise permanent
loss of capacity might occur as a result of sulfation.
Chargers
24 36 48 1
2
4 6 8 10
20 4 0
h
Discharge Time
Shelf Life & Storage
Capacity Retention Ratio (%)
“Float” or “Stand-By” Service: Hold battery across constant voltage source of
13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its
own current level and maintain itself in a fully charged condition.
12
min
110
Cycle Applications: Limit initial current to 16.5A. Charge until battery voltage
(under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7
volts until current drops to under 550mA. Battery is fully charged under these
conditions, and charger should be disconnected or switched to “float” voltage.
55
110
Discharge Current (A)
Charging
2.75
5.5
11
27.5
Final
Voltage
8.0
9.0V
10
o
Ambient Temperature 20 C (68 F)
13.0
Terminal Voltage (V)
h
20
15
10
100
Charging is not
necessary unless
100% of capacity
is required.
80
Charging before
use is necessary
to help recover
full capacity.
5oC
(41oF)
60
40
0
o
30 C
o
(86 F)
40oC
(104oF)
0
2
4
6
8
10
Charge may fail
to restore full
capacity. Do not
let batteries reach
this state.
20oC
(68oF)
12
14
16
18
20
Standing Period (Months)
Further Information
Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH.
Please refer to the Charger Selection Guide in our specification sheets for “C-Series
Switch Mode Chargers” and “Transformer Type A and F Series”. Please contact our
Technical department for advice if you have difficulty in locating suitable models.
Please refer to our website www.power-sonic.com for a complete range of useful
downloads, such as product catalogs, material safety data sheets (MSDS), ISO
certification, etc..
Contact Information
DOMESTIC SALES
Tel: +1-619-661-2020
Fax: +1-619-661-3650
[email protected]
www.power-sonic.com
CUSTOMER SERVICE
Tel: +1-619-661-2030
Fax: +1-619-661-3648
[email protected]
TECHNICAL SUPPORT
Tel: +1-619-661-2020
Fax: +1-619-661-3648
[email protected]
INTERNATIONAL SALES
Tel: +1-650-364-5001
Fax: +1-650-366-3662
[email protected]
CORPORATE OFFICE • 7550 Panasonic Way • San Diego, CA 92154 • USA • Tel: +1-619-661-2020 • Fax: +1-619-661-3650
© 2012. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.
0812 1M
SUBMITTAL
November 14, 2014
MARYWOOD UNIVERSITY
LEARNING COMMONS
VIDEO INTERCOM SYSTEM
PANIC BUTTON SYSTEM
VECTOR SECURITY
23 CASEY AVENUE
WILKES BARRE, PA 18702
(570) 824-4605
TABLE OF CONTENTS
1.
2.
3.
4.
COVER SHEET
TABLE OF CONTENTS
BILL OF MATERIALS
EQUIPMENT DATA SHEETS
BILL OF MATERIALS
The Learning Commons
Quantity
Part Number
Description
1
2
1
Concord 4
HUB2SA
HFX-700M
Security Panel
Momentary Panic Buttons
Video Intercom Kit
Rough In Box Type
NA
NA
Single Gang
Mounting Height/Details
NA
NA
NA
Intrusion
Concord 4
Powerful, expandable security
with Learn Mode technology
Overview
Concord™ 4 is a full-featured security system for residential and
commercial intrusion as well as residential fire detection that
complies with false alarm standards. Easy to install and simple to
use, Concord’s modular design and advanced software provide
outstanding system flexibility to meet the needs of virtually any
residential or commercial security application.
High standards
The panel comes standard with eight hardwire zone inputs, including
a two-wire smoke detector loop that can handle up to 20 detectors.
A built-in RF receiver with 96-zone capacity (600-1021-95R only)
provides instant compatibility with the complete line of Interlogix Learn
Mode sensors. Two programmable outputs can be set up to activate
external devices during an alarm or other system event.
Easy expansion
Expand Concord’s capabilities by adding SuperBus® 2000 8Z Input
Modules for eight additional zones per module, or SuperBus 2000
4-Relay Output Modules to add four more output points. SnapCards™
also add to system zone inputs and outputs. Each card (one per
panel) connects easily to the panel circuit board inside the cabinet for
a clutter-free, professional installation. Increase RF coverage area by
adding up to four SuperBus 2000 RF receivers or SuperBus 2000 RF
transceivers. Each receiver supports all 96 zones.
Expand the system even further with a Phone Interface/Voice
Module for on- and off-site system control using touch-tone phones.
The module includes a speaker output that provides on-site voice
status and alarm messages.
Adding a SuperBus 2000 Energy Saver Module lets users control
heating and air conditioning. With the addition of a Z-Wave® enabled
Cellular Module, with service from Alarm.com,® control of automated
lights, door locks, thermostats and more is available using almost
any Web enabled device.
Increase power capability for system peripherals with a
SuperBus 2000 two-amp Power Supply Module with battery
backup. The module provides two amps at 12VDC.
Effortless programming
Conduct quick and easy on-site programming with alphanumeric
touchpads and a menu-driven text interface with shortcut menu
numbers. A quick programming menu makes it even easier to install
smaller, basic systems. For off-site programming, use Enterprise®
downloader software (version 3.1 and later).
Standard Features
•6
partitions and 8 built-in hardwire zones—96 zones maximum
as either hardwire, wireless, or combination
•9
6 wireless zones standard onboard (600-1021-95R only)
• 2 onboard programmable outputs
•C
ompatible with all Interlogix crystal and SAW Learn Mode sensors
•S
IA CP-01 False Alarm Reduction Standard compliant
• 2- and 4-wire smoke detector compatibility
• Panel auxiliary power provides 1 amp
• Built-in 12-watt siren driver
ADDITIONAL Features
•2
30 user-programmable access codes with programmable
authority levels
•L
atchkey numeric paging with optional keychain touchpad activation
• Audio verification in partition 1 with VOX mode (requires
Interrogator® 200)
•2
50-event history buffer viewable from any alphanumeric keypad,
downloader or automation device
•K
eyswitch arming using a hardwire or wireless zone
•P
rogrammable on-site using alphanumeric touchpads or off-site
using Enterprise
•P
rogrammable macro keys simplify user interaction with singlebutton system commands
• Time and status displayed on all touchpads
•1
6 schedules available for scheduled lighting and outputs
interlogix.com
Concord 4
North America
T 855-286-8889
Asia
T 852-2907-8108
Australia
T 61-3-9239-1200
Europe
T 32-2-725-11-20
Latin America
T 561-998-6114
Powerful, expandable security
with Learn Mode technology
Specifications
Power supply
Required transformer
Backup battery
Battery backup time
Battery test
Transformer fuse
Panel auxiliary
voltage output
Ordering Information
Class II, 16.5 VAC, 40 VA, 60 Hz
12VDC, 4.5 Ah or 7 Ah rechargeable, sealed,
lead-acid
24 hours (when fully charged, with appropriate
external load)
15 minutes under load every 24 hours
(every 4 hours for UL installations)
Non-replaceable fuse
Current-limited, 1.0 A max. @ 12VDC
Communication formats
Dialing
DTMF or pulse with integrated line seizure relay
Formats supported
SIA Digital II (300 bps) or Contact ID
3 central station phone numbers and 5 pager
Capabilities
phone numbers
Inputs
Input zones
Databus format
Databus capacity
96 max. hardwire or wireless; 8 hardwire zones
built in, 96 zone wireless capacity built in
(600-1021-95R only)
SuperBus 2000 with auto-enrolling capability
Up to 16 devices
Outputs
OUT1/+12V (output 1)
OUT2/OC (output 2)
Auxiliary power output
Storage temperature
Relative humidity
Physical
Dimensions (HxWxD)
Weight
Chassis material
Color
600-1040
Expansion options
60-620-01
60-756
60-757
60-758
60-770
60-774
60-783-02
60-777-01
60-821-95
600-1053-3
600-1053-4
600-1019
600-1025-01-95R
Touchpad options
60-597-95
600-1064-95R
12VDC, 1.0 A
(max. combined with auxiliary power output)
Open-collector, 300 mA max
Regulated, current limited, self-resetting 12VDC:
1.0 A (max. combined with output 1)
60-746-01/60-803-04
32 to 120°F (0 to 49°C); up to 140°F (60°C)
under temporary conditions
-30 to 140°F (-34 to 60°C)
90% max., noncondensing
60-985/60-984
Environmental
Operating temperature
Concord 4 panels
600-1021-95R
60-804-04
60-820
60-983
600-1020
SuperBus® 2000 energy-saver module (ESM)
Combo input/output SnapCard™
8Z hardwire input SnapCard
4-output SnapCard
SuperBus 2000 4-output module
SuperBus 2000 8Z input module
SuperBus 2000 automation module
SuperBus 2000 phone interface and voice
module
SuperBus 2000 commercial transceiver module
(compatible with crystal sensors and touchpads)
SuperBus 2000 GSM module (2.5G)
SuperBus 2000 GSM (3G) or CDMA module
SuperBus 2000 2.0 A power supply module
SuperBus 2000 transceiver module
HiTech handheld touchpad
Micro key fob, 4-button SAW
SuperBus 2000 2x16 and 2x20 LCD
alphanumeric touchpads
SuperBus 2000 2x20 vacuum fluorescent
display alphanumeric touchpad
SuperBus 2000 fixed display LCD touchpad
ATP1000 alphanumeric touchpad
ATP2100 and ATP2600 alphanumeric
touchpads
FTP1000 fixed English touchpad
Transformer options
600-1023
14.0 x 12.0 x 3.0 in. (356 x 305 x 76 mm)
5 lb., 10 oz. (2.5 kg)
0.048-in. (1.2 mm) 16-gauge steel, punched
and formed
Beige
Concord 4 RF panel
Concord 4 Commercial (does not include
96-zone wireless receiver)
600-1023-CN
600-1024
16.5 V, 40 VA standard transformer, UL listed for
U.S. applications
16.5 V, 40 VA standard transformer, cUL/CSA
listed for Canadian applications
16.5 V, 40 VA power line carrier transformer, UL
listed for U.S. applications
Regulatory
FCC Parts 15 and 68
UL 985, UL 1023, UL 1635
UL 1610 (600-1040 panel only), cUL
SIA CP-01 2000 False Alarm Prevention
interlogix.com
Specifications subject to change without notice.
© 2013 Interlogix.
All rights reserved.
Interlogix is part of UTC Climate, Controls & Security,
a unit of United Technologies Corporation.
301-3619
2013/08
(73444)
USPs’ HUB ™ Brand Hold Up
Hold-Up Buttons
HUB Series
Buttons, have set the standard
for quality throughout the
Features
Nickel Plated Brass Terminals
industry. The switch is
Impact Resistant Housing
manufactured with gold, silver
and copper for maximum
Copper Alloy Blades
conductivity and corrosion
Gold or Silver Crosspoint Contacts
resistance, with a current rating
of 10 Amps, and a voltage rating
Silent Actuating Button
of 125/250 volts. Button Locating
Ridges are a HUB ™ exclusive.
Give your customers the industry standard in high quality Hold-Up
UL and ULC Listed
Buttons. The switch inside the case is manufactured with gold,
U.S. and World patents pending.
silver and copper. We require the highest standard of components
and take the extra time to hand-assemble the units in the USA to
assure reliability.
Voltage Rating: 125/250
Current Rating: 10 Amps
United Security Products, Inc.
has supplied quality products to
the security alarm industry for
over 40 years, with proven
Model
Operation
Terminal Configuration
performance in more than 100
HUB2
HUB2A
DPDT
DPDT
LATCHING
LATCHING
6 SOLDER TERMINALS
3 SOLDER/3 SCREW TERMINALS
the most innovative products in
HUB2B
HUB2S
HUB2SA
DPDT
SPDT
SPDT
LATCHING
MOMENTARY
MOMENTARY
6 SCREW TERMINALS
3 SOLDER TERMINALS
3 SCREW TERMINALS
the security industry. For your
HUB3
HUB3A
DPDT
DPDT
MOMENTARY
MOMENTARY
6 SOLDER TERMINALS
3 SOLDER/3 SCREW TERMINALS
MOMENTARY
6 SCREW TERMINALS
million installations. Security
systems dealers rely on USP for
next installation, be sure to
specify USP products.
HUB3B
HUB-RT
Switch Type
DPDT
RESET TOOL FOR
HOLD UP BUTTONS
40 Years of Superior American Manufacturing
Made in U.S.A
U.S. and FOREIGN PATENTS PENDING
United Security Products • 13250 Gregg St. Suite B • Poway, CA 92064
Toll Free: 800-227-1592 • Tel: 858-413-0149 • Fax: 858-413-0124
www.unitedsecurity.com
DATA SHEET
COD.
HFX-700M
COLOR HANDS FREE KIT WITH 3.5'' LCD MONITOR
Color hands free kit with 3.5'' LCD monitor. Includes master monitor, door bell and power
supply. Expandable to 2 door cameras and 4 inside monitors.
Mounting/Installation
Flush-mounted:
Optional (EX-700V)
Wall-mounted:
Yes
Desk base-mounted:
Optional (CDSK)
Surface-mounted:
Surface mounted Door station and Monitor
DIN rail mounted:
No
DIN modules (no.):
No
Audio/video specifications
Display size (inches):
3.5''
B/W or colour display:
Digital Color Display
Type of display:
LCD
Hardware specifications
Dry contact for fault signalling:
Magnetic contact terminals
SD memory card:
Micro SD Card
Sensitive Touch technology:
N/A
Connectivity
Type of connections/ports:
2 Conductor screw termination
Functions - Settings
Intercom function:
All-Page Intercom
Key button function:
Door release
Electrical specifications
Direct voltage output A (V):
The technical specifications are subject to variations without warning
12VDC 300mA
DATA SHEET
Maximum current absorption (mA):
23VDC/1A
General info
Self-ignition:
Yes
EAN product code:
8023903215496
Type of finish:
Plastic
Product height (mm):
7.0''
Product width (mm):
4.65''
Product depth (mm):
1.42''
Product weight:
1 LBS
Product colour:
White
Unit of measurement:
Inches
Packaging
Single pack quantity (no.):
The technical specifications are subject to variations without warning