wilkins catalog1
LLATION
350OSYG
MODEL 375SAG (3/4”- 1”)
MODEL 375AG (1 1/4”- 2”)
3/4" 375 RP
B64.4
2
375 RP
ZURN /
1013
ZURN
WILKINS
175 PSIG 180ß F
WILKINS
175 PSIG 180° F
(1-1/4” - 2”) 8 1/8
(3/4” - 1”) 5 1/2
OPTIONAL
WATER METER
(1-1/4” - 2”) 3” PIPE
(3/4” - 1”) 2” PIPE
(DRAIN LINE CAN
BE ANY STANDARD
PIPING MATERIAL)
PROTECTIVE
ENCLOSURE
AIR GAP
12" MIN.
30" MAX.
12" MIN.
30" MAX.
Product
Catalog
DIRECTION OF FLOW
INLET SHUT OFF
FLOOR DRAIN
INDOOR INSTALLATION
FLOOR
DRAIN
DIRECTION OF FLOW
OUTDOOR INSTALLATION
PROTECTIVE
ENCLOSURE
12" MIN.
30" MAX.
1” 720A PVB
(25mm)
DIRECTION OF FLOW
TO IR
SYST
INDOORS
MODEL ZW3
OUTDOOR INSTALLATION
MODEL 350AFSC
OUTDOORS
KEY
1/2” NPT DRAIN PLUG
OR BLOW DOWN
LENGTH
Product Index
Automatic Control Valves.........................................................................17-21, 65
Float Controlled Valves............................................................................................21
Backflow Preventers........................................................................................... 23-61
Accessories...................................................................................................... 63-73
Air Gaps...................................................................................................................72
Atmospheric Vacuum Breakers....................................................................59
Double Check Assemblies.................................................................23-28, 39
Double Check Detector Assemblies.................................................... 29-31
Dual Check Assemblies.......................................................................48-52, 60
Hose Connection Vacuum Breakers..........................................................61
Integral Relief Valve Monitor Switch Accessories.......................... 63-64
Pressure Vacuum Breakers...................................................................... 56-58
Quick Test Fitting Set..........................................................................................71
Reduced Pressure Principle Assemblies.......................................32-45, 58
Reduced Pressure Principle Detector Assemblies.......................... 46-47
Reduced Pressure Principle Assemblies
with Integral Relief Valve Monitor Switch...........................35-36, 41
Security Products................................................................................. 62, 68, 97
Single Check Valve Assemblies.............................................................. 54-55
Test Kits.....................................................................................................................71
Gate Valves............................................................................................................ 69-71
Hose Bibbs............................................................................................................. 16, 96
Miscellaneous Plumbing Products............................................................90-100
Pressure Relief Valves......................................................................................... 84-89
Slip Joint Couplings and Tees...............................................................................99
Strainers (Bronze and Cast Iron)................................................................... 74-76
Temperature and Pressure Relief Valves.................................................. 83-89
Thermostatic Mixing Valves............................................................................ 77-81
Accessories............................................................................................................ 15, 82
Vacuum Relief Valves...............................................................................................98
Water Hammer Arresters.......................................................................................96
Water Heater Shut-Off Valve with Thermal
Expansion Relief Valve.......................................................................................95
Water Pressure Reducing Valves....................................................................4-14
Accessories.......................................................................................15-16, 82, 96
Ball Valves............................................................................................................... 68-69
Cast Iron Flanged................................................................................................69
Full Port....................................................................................................................68
Check Valves, In-Line......................................................................................... 48-55
For full list of products by category,
see Product Locator on page 107.
Dielectric Unions................................................................................................99-100
Expansion Tanks................................................................................................... 90-94
Hydronic..................................................................................................................94
Potable............................................................................................................... 90-93
*All product cross references are not absolute and are
provided for guidance only.
Fire Sprinkler and Fire Hose Valves........................................................101-106
Index by Model Number
Model Number
Page
35..............................................................59
40XL.........................................................54
48..............................................................69
48OSY.....................................................70
48PI..........................................................70
49GVIC...................................................71
70................................................................ 7
80CI..........................................................12
80BR.........................................................12
90..............................................................14
92-25.......................................................16
92-25A....................................................16
310...........................................................55
350 3/4"-2"............................................23
350A/350..............................................27
350ADA/350DA................................30
375 3/4"-2"............................................33
375A/375..............................................40
375ADA/375DA................................46
375MS/375AMS.................................41
400...........................................................72
420...........................................................56
450...........................................................28
450DA....................................................31
460...........................................................58
475/475V..............................................45
475DA/475DAV................................47
500............................................................. 8
500FC........................................................ 9
500YSBR.................................................10
600...........................................................11
700...........................................................48
705...........................................................49
720A........................................................57
Model Number
Page
Model Number
®
company
Model Number
Page
YB Series.................................................74
Z2100...................................................102
Z2105...................................................102
Z3000...................................................105
Z3004...................................................103
Z3005...................................................105
ZW104...................................................21
ZW105...................................................19
ZW105FP..............................................20
ZW106...........................................21, 65
ZW109...................................................17
ZW109FP..............................................18
ZW1017.................................................77
ZW1017HT...........................................79
ZW1017MM........................................78
ZW1070.................................................80
ZW3 Winterizer..................................66
ZW3870T..............................................81
ZW3870T-4P........................................81
ZW4000..............................................104
ZW4004..............................................104
ZW4100..............................................106
ZW4104..............................................106
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
Page
FLS/MJS/MJFS.....................................72
FS Series..................................................76
HBL/HBHL............................................97
HGI-25............................................16, 96
HXT...........................................................94
MSK/BMSK............................................63
NR3............................................................ 4
NR3XL....................................................... 5
OS&Y Supervisory Switch...............67
P1000A...........................................84, 85
P1500..............................................87, 88
P1520......................................................88
P1550..............................................87, 88
P220.................................................84, 85
P3000..............................................84, 85
P3000BR........................................85, 86
P3000CI..........................................85, 86
P4000......................................................89
QT-SET....................................................71
RPHBM....................................................42
S Series....................................................75
SCI Series................................................75
SPK Series...............................................16
Spools......................................................73
TCL24......................................................62
TG-3/TG-5.............................................71
TP1100A........................................83, 85
TP1100AE-3C......................................83
TP220 Series.................................83, 85
TP3000 Series..............................84, 85
TPK Series.......................................15, 82
VR10........................................................98
WTTA......................................................93
XT..............................................................91
730/735.................................................60
740...........................................................52
760...........................................................51
850....................................................68,69
860/860FT............................................62
876...........................................................13
950LF......................................................50
950XL......................................................24
950XLT....................................................26
950XLTDABF.......................................29
950XLV...................................................25
975/950 Pre-Set Series....................39
975XL, 1/4"–1/2"...............................32
975XL, 3/4"–2"....................................34
975XLBMS.............................................36
975XLHBM...........................................43
975XLMS................................................35
975XLSE.................................................38
975XLST.................................................53
975XLV...................................................37
1250/1250AA-3C..............................96
AG Series...............................................72
BFP-8F.....................................................61
BFP-9........................................................61
BR4............................................................. 6
BVEC........................................................95
BVHL.......................................................68
BVLK........................................................68
BVMS.......................................................67
DU.........................................................100
DUBI.....................................................100
DUC.........................................................99
DUM.....................................................100
EST............................................................64
2
PRESSURE REGULATORS
Wilkins is synonymous with quality in the water pressure reducing valve industry. When you purchase, specify, or install a
Wilkins PRV you are selecting the most reliable regulator in the industry!
WILKINS CONTROL VALVES
Wilkins automatic control valves provide innovative solutions to specific water system requirements!
BACKFLOW PREVENTERS
Wilkins backflow preventers offer the best value backflow prevention on the market. From single checks to vacuum breakers
to backflow assemblies, Wilkins has what you need. And with our multiple configurations Wilkins makes your installation easy
which in turn saves you money and time.
In addition to ease of installation and maintenance Wilkins offers many options for large backflow.
Follow this simple guide and you can build a Wilkins backflow part number to fit your needs:
Example:
4-375AOSYPIFG
4
375
A
OSY
PI
F
G
4 inch
375 RP
Grooved body
OSY gate on inlet
Post Indicating gate on outlet
Flanged inlet
Grooved outlet
(size)-(model number) (“A” =grooved body or no letter = standard flanged body) (DA =Detector Assembly)
(inlet shutoff =”OSY”, “PI”, “NRS”, or “BGVIC”) (outlet shutoff = “OSY”, “PI”, “NRS”, “BGVIC” or nothing if same
as inlet) (inlet connection “G”=grooved or “F”=flanged) (outlet connection “G”=grooved or “F”=flanged)
BACKFLOW ACCESSORIES & SECURITY PRODUCTS
STRAINERS
Help keep your valve clean with a Wilkins Strainer!
THERMOSTATIC MIXING VALVES
The Wilkins Thermostatic Mixing Valve helps in keeping people safe from scalding injuries while allowing the
temperatures to remain high enough to inhibit the growth of bacteria. In addition to safety, it also helps save money and
energy by allowing you to turn up your water heater thermostat without risk of injury.
TEMPERATURE AND PRESSURE RELIEF VALVES
MISCELLANEOUS PLUMBING PRODUCTS
FIRE VALVES
Wilkins Pressure-Tru fire system valves. A reliable choice in the Fire Industry!
PRODUCT LOCATOR
Tech Support: 1-877-BACKFLO
www.zurn.com
®
3
a
®
company
Water Pressure Reducing Valves
Typical Installation
Accessories
Options
Features
Applications
NR3 Series
As the newest member of the Wilkins pressure reducing valve family, the NR3 is the most versatile
yet. Its cartridge loaded design with integral strainer allow for rapid cleaning and repair, making the
valve most suitable for residential and commercial applications that require minimal downtime for
maintenance. Both ends of the regulator are threaded for unions and female NPT, allowing for a
tremendous number of end connection options. As with all Wilkins pressure reducing valves, the
NR3 reduces pressure in both flowing and non-flowing applications.
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Pressure rated 400 psi (1/2” – 11/4”), 300 psi (11/2”, 2”)
Spring range 15 to 75 psi (1/2” – 11/4”), 25 to 75 psi (11/2”, 2”);
Factory set at 50 psi
Maximum temperature 180°F
All bronze body and composite bell housing
Replaceable acetal cartridge with integral stainless steel strainer
Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion
• Nylon reinforced Buna-N diaphragm
•
•
•
•
•
•
•
•
•
Model NR3
Single union with FNPT tailpiece, inlet and outlet
both male threaded for union on either or both
sides
Model NR3SC
Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor
applications
Model NR3C
Union end connection in female copper sweat
Model NR3PEX
Model NR3DU
Double union with two FNPT tailpieces and union
nuts
Union end supplied with male barb connection
tailpiece for cross-linked polyethylene (PEX)
tubing
Model NR3DUC
Double union with two female copper sweat
tailpieces and two union nuts
Model NR3DULU
Less tailpieces and union nuts, female iron pipe
thread
•
•
•
•
•
•
•
•
Balanced piston design
May be installed in any position
All internal parts corrosion-resistant and included in a drop-in cartridge
Short lay length makes for easy retrofit
No special tools required
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
ASSE® Listed 1003, IAPMO® Listed
Model NR3DUPEX Supplied with two male barb connection
tailpieces for cross-linked polyethylene (PEX)
tubing

Special plastic spacer nipple for use with 1/2”, 3/4” and 11/4” NR3
double union regulators (Model BR4DUSPC)


Special spacer nipple for use with 1” NR3 double union regulators
(Model 70DUSPC)

Special plastic spacer nipple for use with 11/2” and 2” NR3 double
union regulators (Model NR3DUSPC)
For other tailpiece options, see page 15.
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Pressure gauge (Model 92-25)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall
be mounted in accordance with the latest edition of the Uniform Plumbing Code. The Model NR3
may be installed in any position. If installed in a pit, vault or indoors, specify the “SC” sealed cage
option. The assembly shall be installed with sufficient side clearance for testing and maintenance.
Multiple installations are recommended for wide demand variations
or where the desired pressure reduction is more than 4 to 1 (ie: 200
psi inlet reduced to 50 psi outlet). CAUTION: Anytime a reducing
valve is adjusted, a pressure gauge (Model HGI-25) must
be used downstream to verify correct pressure setting.
Do not bottom out adjustment bolt on bell housing.
MODEL 375
BACKFLOW PREVENTER
MODEL 850
SHUT OFF
MODEL S
STRAINER
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
MODEL NR3
REGULATOR
4
Water Pressure Reducing Valves
Options
Features
Applications
NR3XL Series
Designed with low lead construction, the NR3XL is compliant with California Assembly Bill 1953 which
states that the weighted average surface area shall contain less that 0.25% lead. Additionally, the valve
is NSF 61 approved. Embodying all of the features and benefits of the NR3, the NR3XL, with its low
lead construction, is the ideal valve for residential and commercial drinking water systems. Removal of
lead from drinking water systems is in the best health interest of all who come in contact with water,
and the NR3XL is the perfect valve to accomplish this goal.
•
•
•
•
•
•
•
•
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Pressure rated 400 psi (1/2” – 11/4”), 300 psi (11/2”, 2”)
Spring range 15 to 75 psi (1/2” – 11/4”), 25 to 75 psi (11/2”, 2”)
Factory set at 50 psi
Maximum temperature 180°F
Low lead alloy body and composite bell housing
Replaceable acetal cartridge with integral stainless steel strainer
Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion
• Nylon reinforced Buna-N diaphragm
• Balanced piston design
•
•
•
•
•
•
•
•
•
•
Model NR3XL
Single union with FNPT tailpiece, inlet and outlet
both male threaded for union on either or both
sides
Model NR3XLSC
Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor
applications
Model NR3XLC
Union end connection in female copper sweat
Model NR3XLPEX
Model NR3XLDU
Double union with two FNPT tailpieces and
union nuts
Union end
supplied
with male barb connection
HOSE
BIBB
tailpiece for cross-linked polyethylene (PEX)
tubing (1/2”, 3/4” and 1)
Model NR3XLDUC
Double union with two female copper sweat
tailpieces and two union nuts
Typical Installation
Accessories
Model NR3XLDULU Less tailpieces and union nuts, female iron pipe
thread



Model NR3XLDUPEX Supplied with two male barb connection
MODEL
tailpieces for cross-linked
polyethylene (PEX)
BR4XL
tubing (1/2”, 3/4” and 1)

Special plastic spacer nipple for use with 1/2”, 3/4” and 11/4” NR3
double union regulators (Model NR3DUSPC)
May be installed in any position
All internal parts corrosion-resistant and included in a drop-in cartridge
Short lay length makes for easy retrofit
No special tools required
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
ASSE® Listed 1003, IAPMO® Listed
NSF® Standard 61 Certified
California AB 1953 compliant
SHUT-OFF
VALVE
Pressure gauges (Model 92-25)
WATER
METER
Special spacer nipple for use with 1” NR3XL double union regulators
(Model 70DUSPC)
For other tailpiece options, see page 15.
For Additional Information, including flow curves, reference
visit our
web site.
DIRECTION
OF FLOW
Special plastic spacer nipple for use with 11/2” and 2” NR3 double union WK-RC catalog or
regulators (Model NR3DUSPC)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the latest edition of
the Uniform Plumbing Code. The Model NR3XL may be installed in any position. If installed in a pit, vault, or indoors, specify the “SC” sealed cage option.
The assembly shall be installed with sufficient side clearance for testing and maintenance. Multiple installations are recommended for wide demand variations or where the desired pressure reduction is more than 4 to 1 (ie: 200 psi inlet MODEL TP1100A
T & P VALVE
reduced to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge (Model HGI-25) must be
used downstream to verify correct pressure setting. Do not bottom out adjustment bolt on bell housing.
TAILPIECE
HOSE BIBB
MODEL BFP-8
HOSE BIBB VACUUM
BREAKER
UNION NUT
SUPPORT
TYP. STUD BAY OR
EXPOSED WALL
WATER
HEATER
MODEL YB
STRAINER
MODEL BR4XL
REGULATOR
UNION
GASKET
CRIMP RING
WATER
METER
MODEL 975XL
MODELBACKFLOW
375XL
BACKFLOWPREVENTER
PREVENTER
REGULATOR
DIRECTION OF FLOW
DIRECTION OF FLOW
NR3XL PEX INSTALLATION
MODEL WXTP
EXPANSION
TANK
MODEL NR3XL
SHUT-OFF
MODEL SXL
STRAINER
MODEL 850XL
SHUT OFF
Tech Support: 1-877-BACKFLO
www.zurn.com
®
5
a
®
company
Water Pressure Reducing Valves
X Ref
Typical Installation
Accessories
Options
Features
Applications
BR4 Series
The BR4 was Wilkins first pressure reducing valve to utilize a replaceable thermoplastic cartridge. The plastic
cartridge reduces internal corrosion, thus increasing the time between cartridge replacements. Its 15 to
150 psi adjustment range is the broadest of any regulator that Wilkins offers. Accepting up to 400 psi on
the inlet and having end connections that are threaded for both unions and female NPT make the BR4
extremely versatile in residential, commercial and irrigation applications. As with all Wilkins regulators, the
integral by-pass helps prevent pressure buildup in a closed system due to thermal expansion.
3/8" – 1"
11/4" – 2"
• 3/8”, 1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
• Pressure rated 400 psi
• Spring range 15 to 150 psi (sizes 3/8” – 1”); spring range 15 to 75 psi
(sizes 11/4” – 2”); factory set at 50 psi
• Maximum temperature 180°F
• Sizes 1/2” – 1”, all bronze body and composite bell housing
• Sizes 11/4” – 2”, all bronze body and bell housing
• Replaceable acetal cartridge with integral stainless steel strainer
• Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion
• Removable spacer limits adjustment range to 80 psi (sizes 3/8” – 1”)
•
•
•
•
•
•
•
•
•
•
•
Model BR4
Model BR4DM
Double meter end connections (3/4”, 1”)
Model BR4EC
(1/2” – 1”) Supplied with thermal expansion
control valve. See REG-BR4EC for additional
information
Single union with FNPT tailpiece, inlet and outlet
both male threaded for union on either or both
sides
Nylon reinforced Buna-N diaphragm
Balanced piston design
May be installed in any position
All internal parts corrosion-resistant and included in a drop-in cartridge
Short lay length makes for easy retrofit
No special tools required
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Available with BSP threads (optional)
ASSE® Listed 1003, IAPMO® Listed, CSA® Certified, City of Los Angeles.
Model BR4C
Union end connection standard in female copper
sweat
Model BR4SC
Model BR4DU
Double union with two FNPT tailpieces and union
nuts
Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor applications
Model BR4PEX
Model BR4DUC
Double union with two female copper sweat
tailpieces and two union nuts
Union end supplied with male barb connection
tailpiece for cross-linked polyethylene (PEX) tubing
Model BR4DULU
Less tailpieces and union nuts, female iron pipe
thread
Model BR4DUPEX Supplied with two male barb connection tailpieces
for cross-linked polyethylene (PEX) tubing
Model BR5

Special plastic spacer nipple for use with 1/2”, 3/4”, 11/4”, 11/2” and 2”
BR4 double union regulators (Model BR4DUSPC)

Special spacer nipple for use with 1” BR4 double union regulators
(Model 70DUSPC)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance
with the latest edition of the Uniform Plumbing Code. The Model
BR4 may be installed in any position. If installed in a pit, vault, or
indoors, specify the “SC” sealed cage option. The assembly shall
be installed with sufficient side clearance for testing and maintenance. Multiple installations are recommended for wide demand
variations or where the desired pressure reduction is more than 4
to 1 (ie: 200 psi inlet reduced to 50 psi outlet). CAUTION: Anytime
a reducing valve is adjusted, a pressure gauge (Model HGI-25)
must be used downstream to verify correct pressure setting. Do
not bottom out adjustment bolt on bell housing.
WILKINS BR4 WATTS CONBRACO N35BU, N45BU, N55BU
36C-U BR4DU N35BDU, N45BDU, N55BDU 36C-U2T BR4DUC N35BDU-S,N45BDU-S, N55BDU-S 36C-U2S BR4DULU N35B, N45B, N55B 36C EB-86
BR4C N35BU-S, N45BU-S, N55BU-S 36C-US ®
company
Pressure gauges (Model 92-25)
For other tailpiece options, see page 15.
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
MODEL 375
BACKFLOW PREVENTER
MODEL S
STRAINER
MODEL BR4
REGULATOR
MODEL 850
SHUT OFF
CASH-ACME HONEYWELL-BRAUKMANN
EB-86U, EB-87U D05A, DO6G
D05D, DO6G
EB-86C
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a

Stainless steel main valve body (3/4”, 1”)
6
Water Pressure Reducing Valves
Options
Features
Applications
70 Series
When the model 70 was introduced in 1972, its cartridge loaded design was revolutionary when compared to the 50 plus year-old regulator designs that dominated the market at that time. Still with us today,
the model 70 has a multitude of followers that appreciate its ruggedness along with its compact size and
simplicity in repair. Available in less union, single union, and double union end configurations, the model
70 is perfect for those residential and light commercial applications requiring a regulator that accepts 300
psi on the inlet and an adjustment range of 25 to 75 psi on the outlet.
•
•
•
•
•
•
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Pressure rated 300 psi
Spring range 25 to 75 psi; factory set at 50 psi
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Built-in by-pass prevents buildup of excessive system pressure caused
by thermal expansion
• Integral stainless steel strainer
• Nylon reinforced Buna-N diaphragm
• Balanced piston design
• May be installed in any position
• All internal parts corrosion-resistant and included in a replaceable
cartridge
• Serviceable in-line
• Available tapped and plugged for gauge (optional)
• Available tapped with gauge (optional)
• Available with BSP threads (optional)
• ASSE® Listed 1003, IAPMO® Listed, CSA® Certified, City of Los Angeles
Model 70
Union end connection standard, available 1/2”
through 1” in FNPT
Model 70SC
Sealed cage bell and stainless steel adjusting screw.
For below-ground and indoor applications
Model 70C
Union end connection standard, available 1/2”
through 1” female copper sweat
Model 70SS
Same as 70SC except with stainless steel spring. For
meter box and below-ground applications
Model 70DU
Double union FNPT.*
Model 70PEX
Model 70DUC
Double union female copper sweat*
Union end supplied with male barb connection
tailpiece for cross-linked polyethylene (PEX) tubing
Model 70DUCM Double union male copper sweat*
Model 70DULU Double union, less tailpieces and union nuts (see
Accessories on page 14 –15)*
X Ref
Typical Installation
Accessories
Model 70DM


Double male meter thread, no union included
(1” National Hose Thread, fits 5/8” x 3/4” and 3/4”
water meter)
Special plastic spacer nipple for use with 70 series double union
regulators (Model 70DUSPC)
Pressure gauges (Model 92-25A 1/2" Only) (Model 92-25 3/4" – 2")
Model 70DUPEX Supplied with two male barb connection tailpieces
for cross-linked polyethylene (PEX) tubing
Model 70CH
Chrome plated internals for aggressive water
conditions
*Note: 70DU Series 11/4” through 2” uses same internals as Model 500
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Local codes shall govern installation requirements. Unless otherwise specified,
the assembly shall be mounted in accordance with the manufacturer’s instructions and the latest edition of the Uniform Plumbing Code. The assembly shall
be installed with sufficient side clearance for testing and maintenance. The
Model 70 may be installed in any position. If installed in a pit, vault or indoors,
specify the “SC” sealed cage option. Multiple installations are recommended for
wide demand variations or where the desired pressure reduction
is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet).
CAUTION: Anytime a reducing valve is adjusted, a pressure gauge
(Model HGI-25)must be used downstream to
verify correct pressure setting. Do not bottom
out adjustment bolt on bell housing.
WILKINS 70
70LU
70DU
70DUC
70C
CONBRACO 36-100
36-200
36-400
36-500
36-300
Tech Support: 1-877-BACKFLO
www.zurn.com
®
7
a
®
company
Water Pressure Reducing Valves
X Ref
Typical Installation
Accessories
Options
Features
Applications
500 Series
The model 500 is the workhorse of the Wilkins pressure reducing valve line up. The model 500
exhibits the highest flow rates of the entire Wilkins regulator line, making it most suitable for commercial,
industrial, and irrigation applications that demand high flow rates with minimal fall-off. The model 500
is available in 10 – 35 psi, 25 – 75 psi, 75 – 125 psi, and 10 – 125 psi adjustment ranges. All 1/2” to 2”
500’s are equipped with a union inlet and female NPT outlet, while the 21/2” and 3” are provided with
female NPT on the inlet and outlet.
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”, 21/2”, 3”
Pressure rated 300 psi
Spring range 25 to 75 psi; factory set at 50 psi
Field set 21/2” – 3”
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion (1/2” – 2”)
• Nylon reinforced Buna-N diaphragm
•
•
•
•
•
•
•
•
Model 500
Union end connection standard and available
1/2” through 2” in FNPT
Model 500LPC
Spring range is 10-35 psi, factory set at 20 psi.
Model 500SW
Chrome plated internals for salt water
Model 500C
Union end connection, 1/2” through 2” female
copper sweat
Model 510
Model 500HR
Spring range is 75-125 psi, factory set at 85 psi;
field set 21/2” – 3”
Rated for 400 psi and spring range is
75 - 125 psi, factory set at 85 psi; field set
21/2” – 3”
Model 500SC
Model 500HLR
Spring range is 10-125 psi, factory set at 50 psi;
field set 21/2” – 3”
Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor
applications
Model 500HT
For high temperature application, up to 210°F.
Model 500XL
California AB 1953 compliant
Model 500L
Less built-in by-pass. (1/2” – 2”)
Model 500LPV
Same as 500HT except spring range is
10-35 psi, factory set at 20 psi
•
•
•
•
•
•
•

Balanced piston design
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Available with BSP threads 1/2” through 2” (optional)
ASSE® Listed 1003, IAPMO® Listed, CSA® Certified, City of Los Angeles
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Pressure gauges (Model 92-25A 1/2", 3/4") (Model 92-25 1" – 3")
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturer’s
instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient clearance for testing & maintenance.
The Model 500 may be installed in any position. If installed in a pit, vault, or indoors, specify the “SC” sealed cage option. Multiple installations are
recommended for wide demand variations or where the desired pressure reduction is more than 4 to 1 (ie: 200 psi inlet reduced to 50 psi outlet).
CAUTION: Anytime a reducing vale is adjusted, a pressure gauge (Model HGI-25) must be used downstream to verify correct pressure setting. Do
not bottom out adjustment bolt on bell housing.
WILKINS 500
500HR
WATTS 223, N223B
223HP, N223BHP
CONBRACO 36H
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
8
Water Pressure Reducing Valves
Applications
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2”, 21/2”, 3”
Pressure rated 300 psi
Spring range 25 to 75 psi; field set
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Nylon reinforced Buna-N diaphragm
Balanced piston design
With ANSI B16.1, Class 125 commercial drilled flanged connections
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Built-in bypass (size 2” only)
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Model 510FC
Rated for 400 psi and spring range is 75-125, field
set
Model 500FCHT
Model 500FCL
Less built-in bypass (2")
Model 500FCBP
Supplied with plugs for low-flow by-pass
(34-BR4DUBPK - sold separately)
Model 500FCLPV
Same as 500FCHT except spring range is
10 – 35 psi, factory set at 20 psi
Model 500FN
Navy drilled flange connections per MIL-P-3 class
1, made for salt water service
Model 500FCLPC
Spring range is 10 – 35 psi, factory set at
20 psi
Model 500FCFSC
Supplied with an FDA approved epoxy coated
wye strainer (21/2” – 3”)
Model 500FCSW
Chrome internals for salt water service
Model 500FCHR
Spring range is 75 – 125 psi, field set
Model 500FCHLR
Spring range is 10 – 125 psi, field set
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.

(34-BR4DUBPK) 3/4” BR4 reducing valve by-pass kit for Model 500FCBP
(Model BR4DUBPK)

Pressure gauges (Model 92-25)
Local codes shall govern installation requirements.
Unless otherwise specified, the assembly shall be
mounted in accordance with the manufacturer’s
instructions and the latest edition of the Uniform
Plumbing Code. The assembly shall be installed with
sufficient side clearance for testing and maintenance.
The Model 500FC may be installed in any position.
If installed in a pit, vault, or indoors, specify the “SC”
sealed cage option. Multiple installations are recommended for wide demand variations or where the
desired pressure reduction is more than 4 to 1 (i.e.:
200 psi inlet reduced to 50 psi outlet). CAUTION:
Anytime a reducing valve is adjusted, a pressure
gauge (Model HGI-25) must be used downstream
to verify correct pressure setting. Do not bottom out
adjustment bolt on bell housing.
High temperature application, up to 210°F
OPTIONAL
PRESSURE
GAUGE
MODEL 92
DIRECTION OF FLOW
Typical Installation
Accessories
Options
For pressure reduction applications where flanges are used to connect the piping, the Wilkins 500FC fits
the bill. The 500FC is available in 2”, 21/2”, and 3” sizes , and is equipped with 150 # flanges. Just like its
threaded brethren, the 500FC is capable of reducing 300 psi down to any pressure between 10 – 125 psi
with four distinct adjustment ranges. The 500FC is the perfect solution for reducing pressure in industrial,
commercial, and large irrigation applications that demand a flanged regulator that exhibits high flow and
low fall-off.
Features
500FC Flanged Series
34-BR4DUBPK
(SOLD SEPARATELY)
(FOR LOW FLOWS)
MODEL 500FC
VERTICAL INSTALLATION
212-500FCBP
500
2 1/2
IN
W
I
L
K
I
N
S
MODEL FSC
"Y" STRAINER
MODEL 500FC
DIRECTION OF FLOW
X Ref
PARALLEL INSTALLATION
WILKINS 500FC
500FCFS
HORIZONTAL INSTALLATION
WATTS N223F 3” ONLY
N223FS 3” ONLY
Tech Support: 1-877-BACKFLO
www.zurn.com
®
9
a
®
company
Water Pressure Reducing Valves
The 500YSBR series pressure reducing valve with wye strainer rounds out the model 500 series offering.
Combining the features and benefits of the model 500 with the protection offered by a wye strainer,
the 500YSBR is ideal for reducing pressure on the incoming line to any commercial or industrial building. The model 500YSBR’s high flow rate and low fall-off also make its use desirable in irrigation systems
that are susceptible to damage from high pressure. The provided “S” strainer protects downstream
equipment from suffering the deleterious effects of sand or debris found in many municipal water lines.
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”, 21/2”, 3”
Pressure rated 300 psi
Spring range 25 to 75 psi; factory set at 50 psi
Field set 21/2” – 3”
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion (1/2” – 2”)
• Includes in-line bronze wye type strainer with 20 mesh stainless steel
screen
•
•
•
•
•
•
•
•
•
Model 500YSBR
Union end connection standard and available
1/2” through 2” in FNPT
Model 500YSBRHT
For high temperature application, up to 210°F
Model 500YSBRL
Less built-in bypass
Model 500HRYSBR
Spring range is 75-125 psi, factory set at
85 psi; field set 21/2” – 3”
Model 500YSBRLPV Same as 500YSBRHT except spring range is
10 – 35 psi, factory set at 20 psi
Model 510YSBR
Rated for 400 psi inlet and spring range is 75125 psi, factory set at 85 psi; field set
21/2” – 3”
Model 500YSBRLPC Spring range is 10 – 35 psi, factory set at
20 psi
Model 510YSBRSC
Sealed cage bell and stainless steel adjusting
screw. For meter box, below-ground, and
indoor applications
•
•
•
•
•
•
•
Model 500YSBRSW
Chrome internals for salt water service
Model 500XLYSBR
California AB 1953 compliant
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Model 500YSBRHLR Spring range is 10 – 125 psi, factory set at
50 psi; field set 21/2” – 3”
Pressure gauges (Model 92-25A 1/2", 3/4") (Model 92-25 1" – 3")
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturers’ instructions and the latest
edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient
OPTIONAL PRESSURE GAUGE
MODEL 92
side clearance for testing and maintenance. The Model 500YSBR may be installed in any
position. If installed in a pit, vault, or indoors, specify the “SC” sealed cage option. Multiple
MODEL 500YSBR
installations are recommend for wide demand variations or where the desired presMODEL 500YSBR
sure reduction is more than 4 to 1 (ie: 200 psi inlet reduced to 50 psi outlet). CAUTION:
Anytime a reducing valve is adjusted, a pressure gauge (Model HGI-25) must be used
OPTIONAL
PRESSURE
GAUGE
downstream to verify correct pressure setting. Do not bottomOPTIONAL
out adjustment
bolt on bell
PRESSURE
MODEL
92 GAUGE
housing.
MODEL 92
DIRECTION OF FLOW

Nylon reinforced Buna-N diaphragm
Balanced piston design
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Available with BSP threads 1/2” through 2” (optional)
ASSE® Listed 1003, IAPMO® Listed, CSA® Certified, City of Los Angeles
MODEL 850
SHUT-OFF VALVE
MODEL
MODELDU
500YSBR
DIELECTRIC UNION
MODEL 500YSBR
OPTIONAL
PRESSURE GAUGE
MODEL 92
DIRECTION OF FLOW
Typical Installation
Accessories
Options
Features
Applications
500YSBR Series
MODEL 850
SHUT-OFF VALVE
MODEL DU
DIELECTRIC UNION
DIRECTION OF FLOW
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
DIRECTION OF FLOW
HORIZONTAL INSTALLATION
VERTICAL INSTALLATION
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
10
Water Pressure Reducing Valves
Many water pressure reduction applications involve water that has a high concentration of sand. Sandy
water results in frequent integral strainer cleaning. The model 600 is just the regulator for these applications. The model 600 has its strainer accessible through a separate cap. Unlike other regulator designs
that require disassembly of the valve, the model 600’s screen is accessed by the removal of a single cap.
This will drastically reduce the time needed to clean the strainer screen. Just like the 500 series, the 600
is also equipped with a union inlet connection and a female NPT outlet connection.
•
•
•
•
•
•
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Pressure rated 300 psi
Spring range 25 to 75 psi; factory set at 50 psi
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Built-in by-pass prevents buildup of excessive system pressure caused
by thermal expansion
• Integral stainless steel strainer with separate access cover
• Nylon reinforced Buna-N diaphragm
•
•
•
•
•
•
•
•
Model 600
Union end connection standard and available 1/2”
through 2” in FNPT
Model 600LPC
Spring range is 10 to 35 psi, factory set at
20 psi (2” must be field set only)
Model 600C
Union end connection standard, available 1/2”
through 2” female copper sweat
Model 610
Same as 600HR except rated for 400 psi and
spring range is 75 – 125 psi, factory set at 85 psi
Model 600L
Less built-in by-pass
Model 600SC
Model 600HR
Spring range is 75 – 125 psi, factory set at 85 psi
Model 600HLR
Spring range is 10 – 125 psi, factory set at 50 psi
Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor
applications
Model 600LU
Less union; female by female NPT
Model 600DM
Model 600HT
For high temperature application not to exceed
210°F
Double male meter thread, no union included
(1” National Hose Thread, fits 5/8” x 3/4” and
3/4” water meter)
Model 600CH
Chrome internals for harsh water conditions
Model 600XL
California AB 1953 compliant
Model 600LPV
Same as 600HT except spring range is
10 – 35 psi, factory set at 20 psi

Balanced piston design
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Available with BSP threads 1/2” through 2” (optional)
ASSE® Listed 1003, IAPMO® Listed, CSA® Certified, City of Los Angeles
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Pressure gauges (Model 92-25A 1/2", 3/4") (Model 92-25 1" – 2")
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the latest edition of
the Uniform Plumbing Code. The Model 600 may be installed in any position. If installed in a pit, vault or indoors, specify the “SC” sealed cage option.
Multiple installations are recommend for wide demand variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced
to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge (Model HGI-25) must be used downstream to verify correct pressure
setting. Do not bottom out adjustment bolt on bell housing.
SHUT-OFF
OPTIONAL PRESSURE
GAUGE
MODEL 92
MODEL
600
MODEL
600
12" MIN.
30" MAX.
DIRECTION OF FLOW
PROTECTIVE
ENCLOSURE
MODEL 975XL
BACKFLOW PREVENTER
Typical Installation
Accessories
Options
Features
Applications
600 Series
OPTIONAL PRESSURE GAUGE
MODEL 92
DIRECTION OF FLOW
X Ref
OUTDOOR INSTALLATION
WILKINS 600
600L
WATTS U5B, 25AUB
U5 VERTICAL INSTALLATION
CASH-ACME EB-24U
E-3
Tech Support: 1-877-BACKFLO
www.zurn.com
®
11
a
®
company
Water Pressure Reducing Valves
Applications
The Wilkins Model 80CI and 80BR are designed to reduce pressure on boiler feed lines in
hydronic heating systems. Equipped with a quick fill / purge lever, the Model 80CI and
80BR allow high capacity feeding to the boiler when commissioning the boiler for the
heating season. The quick fill / purge lever also allows the purging of air from the boiler
relief valve prior to start up. A built-in check valve prevents reverse flow of the boiler water
into the feed line.
Features
•
•
•
•
Accessories Options
80CI and 80BR Series
Model 80CI Cast iron body and bell, FNPT end connections
Model 80CIC
Cast iron body and female copper sweat
Model 80BR Bronze body and bell, FNPT end connections
Model 80BRC
Bronze body and female copper sweat

•
•
•
•
1/2”
Maximum working water pressure 100 psi
Maximum working water temperature 210°F
Reduced pressure range 10 psi to 25 psi
Model 80CI
Model 80BR
Factory preset 15 psi
Threaded connections ANSI B1.20.1
Copper connections (FC) ANSI B16.22
Standard with 20 mesh strainer screen
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
HXT - hydronic expansion tank
WILKINS MODEL P220 OR P3000
PRESSURE RELIEF VALVE
WILKINS MODEL 80CI
WILKINS MODEL 760
DUAL CHECK WITH VENT
OUTLET
Typical Installation
WATER SUPPLY
HOT WATER
BOILER
MODEL 850
SUPPLY SHUT-OFF
MODEL SCI
WYE STRAINER
RETURN
X Ref
DRAIN
WILKINS 80
80C
80LU
80CI
80CIC
WATTS CONBRACO TB1156F
35-503-01
SB1156F
35-703-01
B1156F
35-603-01
T1156F
S1156F
DRAIN
CASH-ACME A-43CRF
A-43RF
A-89C
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
12
Water Pressure Reducing Valves
Applications
The Wilkins 876 series is a combination of the Model 80CI boiler feed pressure reducing valve
and a 760 dual check with intermediate atmospheric vent. Designed to reduce pressure on
boiler feed lines, the 876 also prevents polluted water from entering the boiler feed line due to
backpressure or backsiphonage. Although the 876 handles two problems at once, its preassembled construction eases installation, thereby saving the installer time and money.
Features
• 1/2”
• Model 80BR fast fill regulator combined with Model 760 dual check
backflow preventer with atmospheric vent
• All bronze body construction
• Maximum temperature 210°F
•
•
•
•
Accessories Options
876 Series
Model 876
Model 876CI Model 80BR fast fill regulator combined with
Model 760 dual check backflow preventer with
atmospheric vent
Maximum emergency backflow temperature 250°F
Model 80 outlet pressure 10 to 25 psi, factory set at 15 psi
Available in copper or FNPT inlet connection
ASSE Listed 1012, CSA Certified (Model 760)
Model 80CI (cast iron) fast fill regulator combined
with Model 760 dual check backflow preventer
with atmospheric vent
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.



HXT - Hydronic expansion tank
TP1100A - Temperature & pressure relief valve
P1000A - Pressure relief valve
Under certain conditions, The Model 760 will spill water from the vent port. WARNING: Provisions must be made to collect this spillage through an air
gap or other means. The vent port should never be directly piped into a drainage ditch, sewer or pump. Under no circumstances should the vent port
or drain line be plugged. Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ installation instructions and the latest edition of the Uniform Plumbing Code. The installation shall be made so that no part of the unit can be submerged.
MODEL P1000A
PRESSURE RELIEF VALVE
PRESSURE GUAGE
MODEL 92
Typical Installation
MODEL 876
or 876CI
OUTLET
WILKINS
INLET SHUT-OFF
MODEL 850
BOILER
RETURN
DRAIN
DIRECTION OF FLOW
Tech Support: 1-877-BACKFLO
www.zurn.com
®
13
a
®
company
Water Pressure Reducing Valves
Options
Features
Applications
90 Series
The 90 series pressure reducing valves are the perfect choice for reducing pressure in drip irrigation
applications. Its balanced piston design makes this regulator smooth and highly responsive. Further,
the 0 - 50 psi adjustment range, with very precise control, lends itself very well to those drip systems that
demand precise pressure control in order to maintain system longevity. Available in 3/4” and 1” sizes,
the Model 90 is also ideal for use in the poultry industry for controlling pressure to watering stations.
•
•
•
•
•
•
•
•
•
•
•
•
3/4”, 1”
Pressure rated 300 psi
Spring range 0 to 50 psi; factory set at 30 psi
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Integral stainless steel strainer
Nylon reinforced Buna-N diaphragm
Balanced piston design
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Available with BSP threads (optional)
Model 90
Union end connection standard and available
copper sweat or FNPT end connections
Model 90G
Supplied with pressure gauge (Model 92-25)
Model 90P
Supplied tapped with plug for pressure gauge
Model 90LU
Less union
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient side clearance for testing and maintenance.
The Model 90 may be installed in any position. Multiple installations are recommend for wide demand variations or where the desired pressure reduction
is more than 4 to 1 (ie: 200 psi inlet reduced to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge (Model HGI-25) must be
used downstream to verify correct pressure setting. Do not bottom out adjustment bolt on bell housing.
MODEL 90G
Typical Installation
MODEL YB
STRAINER
100
20
80
psi
40
60
MODEL DU
DIELECTRIC UNION
MODEL 850
SHUT OFF VALVE
X Ref
DIRECTION OF FLOW
WILKINS 90LU
WATTS 123LP
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
14
Water Pressure Reducing
Valves Accessories
Applications
Tailpiece Kits TPK Series
Tailpiece Kits (TPK) are accessories for water pressure reducing valves. These kits are comprised of a cast
brass union nut (ASTM B584), a EPDM gasket and a specific type of tailpiece for direct connection to
specific types of piping. Tailpiece kits are available for connection to FNPT, MNPT, female copper SWT,
male copper SWT, PEX (male barb), CPVC and compression (male) piping systems. A valve may utilize
two different tailpiece kits for connection to two dissimilar piping systems. An example of this
scenario is having copper sweat piping on the valve inlet and PEX piping on the outlet. By using a TPKC
on the inlet and a TPKPEX on the outlet, the valve will bridge the dissimilar piping systems.
TPK
•
•
•
•
•
TPKPEX
• 3/4”, 1”
• Male barb connection tailpiece for
cross-linked polyethylene (PEX) tubing
• EPDM gasket
• Brass tailpiece - ASTM B-16
• Cast brass union nut - ASTM B584
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Female NPT Tailpiece
EPDM gasket
Brass tailpiece - ASTM B-16
Cast brass union nut - ASTM B584
Features
TPKM
•
•
•
•
•
TPKCPVC
3/4”, 1”
Male NPT Tailpiece
EPDM gasket
Brass tailpiece - ASTM B-16
Cast brass union nut - ASTM B584
•
•
•
•
•
TPKC
•
•
•
•
•
TPKCOMP
1/2”, 3/4”, 1”, 11/4”, 11/2”, 2”
Female Copper Sweat Tailpiece
EPDM gasket
Brass tailpiece - ASTM B-16
Cast brass union nut - ASTM B584
•
•
•
•
•
TPKCM
Options
•
•
•
•
•
3/4”, 1”
Female CPVC Tailpiece
EPDM gasket
CPVC tailpiece - ASTM D2846
Cast brass union nut - ASTM B584
3/8”
Male compression fitting with ferrule ring and compression nut
EPDM gasket
Brass tailpiece and accessories - ASTM B-16
Cast brass union nut - ASTM B584
3/4”, 1”
Male Copper Sweat Tailpiece
EPDM gasket
Brass tailpiece - ASTM B-16
Cast brass union nut - ASTM B584
Model BSPT
British Standard Pipe “tapered” threads available.
Model BSPS
British Standard Pipe “straight” threads available.
Tech Support: 1-877-BACKFLO
www.zurn.com
®
15
a
®
company
Features Applications
Water Pressure Reducing
Valves Accessories
Spacer Nipple Kits for Double Union 70, BR4, NR3 and NR3XL
Models SPK Series
Designed for installation on potable water systems as a temporary spacer prior to installation of the
Model BR4, Model NR3, NR3XL, or Model 70DU water pressure reducing valves. Allows system to be
inspected for leaks. Further, the spacer nipple will prevent water regulator theft during construction,
eliminate tampering with the pressure regulator, and allow testing of the plumbing system at full line
pressure. Stainless steel screen provides protection against sediment and debris.
• 3/4”, 1, 11/4”, 11/2”, 2”
• Spacer nipple kit consists of spacer nipple, two union nuts, two
tailpieces, one union gasket, and one in-line strainer screen
For Additional Information, Ask For REG-DUSPC or visit our web
site.
PART NO.
DUSPC SPACER NIPPLE
FOR MODEL BR4, NR3,
NR3XL, OR 70DU
HOSE BIBB
DUSPC SPACER NIPPLE
FOR MODEL BR4, NR3,
NR3XL, OR 70DU
MODEL 850
BALL VALVE
WATER
METER
DIRECTION OF FLOW
DIRECTION OF FLOW
OUTDOOR INSTALLATION
PIT INSTALLATION
FITS MODEL
34-70DUSPC
3/4" 70DU
34-BR4DUSPC
1/2" & 3/4" BR4
1-70DUSPC
1" 70DU, BR4 &NR3
114-70DUSPC
1-1/4" 70DU
114-BR4DUSPC
1-1/4" BR4 & NR3
112-BR4DUSPC
1-1/2" BR4
112-NR3DUSPC
1-1/2" NR3
112-70DUSPC
1-1/2" 70DU
2-BR4DUSPC
2" BR4
2-NR3DUSPC
2" NR3
2-70DUSPC
2" 70DU
Applications
The Model HGI-25 is designed for measuring water system pressure from any hose bibb or water heater drain valve. The indicator needle identifies the highest pressure reached within the system which
is ideal for registering maximum system pressure caused by thermal expansion or pressure spikes. The
maximum pressure indicator needle can be reset by turning the external knob counter clockwise.
The Model 92-25 & 92-25A are designed for accurately measuring system pressure downstream of a
pressure reducing valve. The pressure gauge can be threaded directly to all Wilkins pressure reducing
valves supplied with tapped or plugged option. For water service only.
Features
Pressure Gauges Model HGI-25 Hose Bibb and
Model 92-25 and 92-25A Pressure Gauge
•
•
•
•
•
•
•
•
•
•
•
•
•
3/4” hose (Model HGI-25)
Dial size 2”
Indicator needle identifies the highest pressure
Range: 0 – 200 psi; minimum 2 psi graduation
3/4” hose adaptor
Knurled for easy tightening on hose bibb
Sold in convenient pegboard packaging
HGI-25
1/8” NPT (Model 92-25A), 1/4” NPT (Model 92-25)
Dial size 2”
Range 0 – 100 psi; minimum 2 psi graduation
Steel black case
Copper alloy bourdon tube
Specify part no. 92-25 (1/4” NPT); 92-25A (1/8” NPT)
HOSE BIBB
Typical Installation
92-25
HOSE BIBB
MODEL HGI-25
HOSE BIBB
PRESSURE GAUGE
200
180
0
160
20
psi
40
60
MODEL NR3
REGULATOR
140
120
80 100
MODEL NR3
REGULATOR
WATER
METER
MODEL 92-25
PRESSURE
GAUGE
MODEL 850
BALL VALVE
WATER
METER
DIRECTION OF FLOW
DIRECTION OF FLOW
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
MODEL 850
BALL VALVE
16
Automatic Control Valves
Applications
• 11/4”, 11/2”, 2”, 21/2”, 3”, 4”, 6”, 8”, 10”, 12”
•­Standard spring range 15 to 150 psi, contact factory for other spring
range options
• Normally-open, direct-acting, diaphragm actuated, spring-loaded
pilots adjustable within a 10:1 ratio
• Ductile iron body and bonnet ASTM-A536 epoxy coated. Bronze
(ASTM B62) trim and pilots (standard)
• Single seated, diaphragm actuated, hydraulically operated, pilot controlled
• Maximum temperature 180°F
• Pressure rated Class 150 250 psi max
Class 300 400 psi max
Threaded 400 psi max
• Globe configuration standard
• Angle configuration available (specify when ordering)
Model ZW109
150 lb flange
Model ZW109E
Model ZW109BP
Supplied with a low flow by-pass
Pressure reducing valve with solenoid shut off
valve
Model ZW109Y
300 lb flange (2” – 12”)
Model ZW109Q
Pressure reducing and surge control valve
Model ZW109G
Grooved (21/2” – 8”)
Options
In pressure reduction applications where high flow rates and/or constant downstream pressure are required, the ZW109 is up to the task. The ZW109 is a pilot operated pressure reducing valve designed
to reduce downstream pressure to a constant value, regardless of flow rate or inlet pressure fluctuations. The ZW109 is ideal for commercial, industrial, and irrigation applications that cannot tolerate the
changes in pressure associated with direct acting pressure reducing valves.
Features
Pressure Reducing Valve – ZW109
For Additional Information, reference WK-ACV catalog or visit
our web site.
Model ZW109TH Threaded (11/4” – 3” only)
Typical pressure reducing valve station using two Model ZW109 in parallel to handle a wide range of flow rates. Larger Model ZW109 valves takes
care of peak loads and smaller Model ZW109 handles low flows.
PEAK LOAD VALVE
Typical Installation
INLET PRESSURE
GAUGE
OUTLET PRESSURE
GAUGE
INLET SHUT-OFF
OUTLET SHUT-OFF
DIRECTION OF FLOW
INLET SHUT-OFF
Tech Support: 1-877-BACKFLO
www.zurn.com
LOW FLOW VALVE
OUTLET SHUT-OFF
Refer to Order Form on Web site
®
17
a
®
company
Automatic Control Valves
Options
Features
Applications
Fire Protection Pressure Reducing Valve – ZW109FP
Fire protection systems are required to have the pressure reduced to a value below 165 psi, Therefore, the pressure within a fire protection system must be tightly controlled. The ZW109FP is designed
to handle this very application. The ZW109FP is a pilot operated pressure reducing valve made specifically for the demands of a fire protection system. Designed to hold downstream pressure constant,
regardless of flow rate or inlet pressure fluctuations, the ZW109FP will accept 300 psi on the inlet and
adjust from 30 to 165 psi on the outlet. The ZW109FP is furnished standard with 300# flanges, but
also available in grooved and 150# flange connections.
• 11/2”, 2”, 21/2”, 3”, 4”, 6”, 8”, 10"
• Pilot control system consists of a two-way, normally open, direct-acting,
adjustable spring-loaded diaphragm actuated pressure reducing pilot
• Inlet pressure 300 psi maximum (class 300 flange)(UL rating)
• Pilot control is field adjustable from 30 psi to 165 psi
• Corrosion-resistant seat and resilient, rectangular seat disk
• Globe or angle configurations available, (globe 11/2” – 3” threaded
ends, 11/2” – 6” flanged ends). (angle 11/2” - 3” threaded ends, 2” – 6”
flanged ends)
• Epoxy coated ductile iron body with flow clean strainer (11/2” – 3”) or
wye type strainer (4” – 6”)
Model ZW109
Model ZW109FPTH 300 lb class flange (11/2” – 6”)
Model ZW109FPX 150 lb flange (1 /2” – 8”)
1
Model ZW109FPG Grooved connections (11/2”, 2”, 21/2”, 3”, 4", 6”, 8")
Underwriters Laboratories requires the installation of pressure
gauges upstream and downstream of the pressure reducing valve. Also, a relief valve of not less than 1/2” in size must
be installed on the downstream side of the pressure control
valve. Adequate drainage for the relief valve discharge must
be provided.
Typical Installation
UL INSTALLATION SPECIFICATIONS REQUIREMENTS
The valve is to be installed in accordance with the standard
for installation of sprinkler systems, NFPA 13. The valve is to
be inspected, tested and maintained in accordance with
the standard for the inspection, testing and maintenance of
water-based fire protection systems, NFPA 25.
MAIN FIRE
HEADER
SIZE
Threaded (11/2” – 3” only)
For Additional Information, reference WK-ACV catalog or visit
our web site.
DUCTILE IRON
DUCTILE IRON
DUCTILE IRON
DUCTILE IRON
DUCTILE IRON
ANGLE GROOVE
150# FLANGE
300# FLANGE
300# THREADED
GLOBE GROOVE
1-1/2"
UL / ULC
UL
UL / ULC
UL
2"
UL / ULC
UL / ULC
UL / ULC
UL
2-1/2"
UL / ULC
UL / ULC
ULC
UL
UL / ULC
UL
3"
UL / ULC
UL / ULC
UL
UL
4"
UL / ULC
UL / ULC
UL
UL
6"
UL / ULC
UL / ULC
UL
8"
UL / ULC
UL / ULC
UL
10"
ULC
ULC
MODEL ZW109FP
PRESSURE
REDUCING VALVE
MODEL P4000
PRESSURE
RELIEF VALVE
DISTRIBUTION TO EACH FLOOR
MODEL ZW109FP
PRESSURE
REDUCING VALVE
MODEL P4000
PRESSURE
RELIEF VALVE
Refer to Order Form on Web site
®
a
®
company
18
Tech Support: 1-877-BACKFLO
www.zurn.com
Automatic Control Valves
Applications
• 11/4”, 11/2”, 2”, 21/2”, 3”, 4”, 6”, 8”, 10”, 12”
• When used in a by-pass line, the Model ZW105 functions as a relief
valve protecting against potentially damaging surges
• Normally-closed, direct-acting, spring-loaded pilots available preset to
the particular pressure requirements of the system
• Ductile iron body and bonnet ASTM-A536 epoxy coated. Bronze
(ASTM B62) trim and pilots (standard)
• Single seated, diaphragm actuated, hydraulically operated, pilot
controlled
• Maximum temperature 180°F
• Pressure rated Class 150 250 psi max
Class 300 400 psi max
Threaded 400 psi max
• Globe or angle configurations available (specify when ordering)
Model ZW105
150 lb flange (11/2” – 12”)
Model ZW105TH Threaded (11/4” – 3” only)
Model ZW105Y
300 lb flange (2” – 12”)
Model ZW105G
Grooved (11/2” – 8”)
Options
When high capacity pressure relief is called for, the ZW105 will answer the calling. The ZW105 is
a hydraulically operated, pilot controlled relief valve that maintains a constant upstream pressure.
When used on a branch line, the ZW105 provides relieving service in applications such as a pump
by-pass. When installed in-line, the ZW105 serves as a pressure sustaining valve, thereby maintaining
upstream pressure. Standard with 150# flanges, the ZW105 will accept 250 psi on the inlet while
providing an adjustment range of 20 to 200 psi.
Features
Pressure Relief, Pressure Sustaining Valve – ZW105
For Additional Information, reference WK-ACV catalog or visit
our web site.
Pressure Relief Service - To provide protection for the system against high pressure surges when pumps are shut down, this fast opening - slow
closing relief valve dissipates the excess pressure.
Pressure Sustaining Service - When installed in a line between an upper zone and a lower area of heavy demand, the valve acts to maintain
desired upstream pressure to prevent “robbing” of the upper zone by the heavy demand in the lower zone. This valve senses the upstream pressure.
Water in excess of pressure setting flows to area of heavy demand; control is smooth, and pressure regulation is positive.
PUMP
Typical Installation
UPPER ZONE
CHECK VALVE
MODEL ZW105
MODEL ZW105
LOWER ZONE
PRESSURE RELIEF SERVICE
Tech Support: 1-877-BACKFLO
www.zurn.com
PRESSURE SUSTAINING SERVICE
Refer to Order Form on Web site
®
19
a
®
company
Automatic Control Valves
Options
Features
Applications
Fire Protection Pressure Relief Valve – ZW105FP
Fire protection systems are susceptible to severe damage if an over-pressure situation were to occur.
To prevent over-pressure due to dead-heading of the pump, a high capacity pressure relief valve
is necessary. This is where the ZW105FP steps up to the plate. Like its domestic counterpart, the
ZW105, the ZW105FP is built to handle the rigors of fire protection duty. Furnished standard with
150# flanges, the ZW105FP can accept up to 250 psi on the inlet and is provided with a standard 20
– 200 psi adjustment range. The ZW105FP is a fast-reacting valve that opens to relieve excess pump
pressure when the demand on the fire protection system slows or ceases, allowing the pump to be
stopped without resulting line pressure surges.
• 2”, 21/2”, 3”, 4”, 6”, 8”, 10”
• Ductile iron body and bonnet ASTM-A536 epoxy coated, stainless
steel (type 303) stem, spring and bronze trim (ASTM B62).
• Pressure Rated 150 class 250 psi max.,
300 class 300 psi, threaded 400 psi
• Isolation valves (sizes 4” – 8”)
• Strainer and needle valve
•
•
•
•
•
Model ZW105FP
150 lb class flanges (inlet rating 175 psi)
Model ZW105FPY
300 lb flange
For Additional Information, reference WK-ACV catalog or visit
our web site.
Epoxy coated
Globe flanged ends 3” through 8”
Angle flanged ends 3” through 8”
Temperature rating water 33°F to 180°F
Pilot spring ranges 20 to 200 psi (150 class standard)
100 to 300 psi (300 class)
• UL® Listed, ULC® Listed and FM® Approved
Model ZW105FPTH Threaded (2” – 3” only)
At pump start, the relief valve modulates to relieve excess pump capacity, maintaining positive system pressure at the pump discharge.
When fire demand slows or ceases, the Model ZW105FP opens, diverting entire pump output to discharge, allowing the fire pump to be stopped
without causing surging in the lines.
(Please note that if the Model ZW105FP is to be used on a continuous duty basis to maintain fire-system pressure, suitable back pressure must be provided
on the valve to prevent cavitation damage. (consult the Wilkins for details.)
Typical Installation
FIRE
PUMP
CHECK VALVE
MODEL ZW105FP
PRESSURE RELIEF
APPLICATION
Refer to Order Form on Web site
®
a
®
company
20
Tech Support: 1-877-BACKFLO
www.zurn.com
Automatic Control Valves
Typical Installation Options Features Applications
Float Valve – ZW104
Level control in tanks can be accomplished in many ways. One of the best ways is through the use of a
pilot controlled, non-modulating float valve such as the ZW104. The ZW104 will fully open when the tank’s
liquid level falls to a predetermined point. When the tank reaches the high set point, the ZW104 will close
drip tight and remain closed until the minimum set point is again reached.
• 11/4”, 11/2”, 2”, 21/2”, 3”, 4”, 6”, 8”, 10”, 12”
• On/off type valve that opens fully at a low set point and closes tightly
at a high set point
• Ductile iron body and bonnet ASTM-A536 epoxy coated. Bronze
(ASTM B62) trim
• Diaphragm actuated, hydraulically operated, float controlled
• Stainless steel float and rod available. Single seated, diaphragm
actuated, hydraulically operated, pilot controlled
• Maximum temperature 180°F
• Pressure rated 150 class, 250 psi max
300 class 300 psi, threaded, 400 psi
• Globe or angle configurations available (specify when ordering)
Model ZW104
150 lb. flange (11/2” – 12”)
Model ZW104G
Model ZW104Y
300 lb. flange (2” – 12”)
Grooved (11/2” – 8”)
For Additional Information, reference WK-ACV catalog or visit
our web site.
Model ZW104TH Threaded (11/4” – 3”)
The Model ZW104 float valve is commonly mounted above the high water level in a tank. Globe pattern
valves are supplied standard with the float control mounted on the right side of the cover as illustrated,
with a horizontal discharge. Angle valves are configured to discharge downward.
MODEL ZW104
Supply
Tank
Stilling Well
Applications
The ZW106 is a pilot operated solenoid valve that either opens or closes upon receiving an electrical
signal. The ZW106 is a perfect valve to use with the Wilkins 375MS and EST. In this application, the
ZW106 is used to stop water flow should the relief valve of the backflow prevention assembly begin to
discharge. Not limited to this application, the ZW106 can be used anytime it is advantageous to open
or close a line electrically rather than mechanically. The ZW106 can be equipped in either a normally
open (energize to close) or a normally closed (energize to open) configuration.
Features
Solenoid Control Valve – ZW106
• 11/4”, 11/2”, 2”, 21/2”, 3”, 4”, 6”, 8”, 10”
• On/off type valve that either opens or closes upon receiving an
electrical signal to the solenoid pilot control
• Valve is furnished either normally open (energized solenoid to close)
or normally closed (energize solenoid to open)
• Ductile iron body and bonnet ASTM-A536 epoxy coated. Bronze
(ASTM B62) trim and pilots
150 lb. flange (1/2” – 10”)
Options
Model ZW106TH Threaded (11/4” – 3)
Model ZW106G
Grooved (11/2” – 8”)
Model ZW106Y
300 lb flange (2” – 10”)
For Additional Information, reference WK-ACV catalog or
visit our web site.
Tech Support: 1-877-BACKFLO
www.zurn.com
Typical Installation
Model ZW106
• Single seated, diaphragm actuated, hydraulically operated, electricallyactuated pilot controlled
• Maximum temperature 180°F
• Pressure rated 150 class 250 psi max
300 class 300 psi, threaded 400 psi
• Globe or angle configurations available (specify when ordering)
Refer to Order Form on Web site
Electric
S olenoid
Timer
12" MIN.
30" MAX.
Model EST Application
®
21
a
®
company
Have you seen the news lately?
nze
o
r
B
Less ans
Me eft
h
Less T
S top C opper
T heft!
2” Model 375
Reduced Pressure
Principle Assembly
*Shown with Optional Air Gap Drain
2” Model 350
Double Check Assembly
All across the country, backflow preventers
are being stolen for their scrap value. The
street value is minimal compared to an all
bronze body backflow preventer. The Wilkins
model 350 & 375 entire housing is composite
material using upwards of 30% less bronze
than comparable backflow preventers. Additionally, their simple design enables easy winterizing by removing wetted components
between shutoff valves and check access
for cleaning or repair. The composite housing and check modules resist corrosion and
extend the life of your backflow preventer.
Insist on the Wilkins Model 350/375 on
your next replacement or installation.
.
Sizes available: 3/4”, 1”, 1 1/4”, 1 1/2” & 2”
Customer Service Representatives available Monday through Friday
5:30 am to 5:00 pm PST • Call: 877-222-5356 or 805-226-6297
[email protected] or visit us online at www.zurn.com
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
22
Backflow Preventers
Applications
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Short lay length – fits in smaller valve box
• Top access to test cocks and shutoff valves and check assembly – easy to
test
• Entire pressure vessel is removable to facilitate check access for cleaning
or repair
• Test cocks are provided with threaded caps
• Easy to winterize by removing pressure vessel between shutoff valves
• Plastic pressure vessel is a theft deterrent
• Removable pressure vessel eliminates the need of union connections
• Blow out flush fitting allows system flush and irrigation system blowouts
• Simple design – composite housing and check modules resist corrosion
• ASSE® Listed 1015 (horizontal/vertical), IAPMO® Listed, CSA® Certified
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
(horizontal and vertical, 3/4" & 1")
• Contact Wilkins for approval updates on 11/4” – 2” sizes
Model 350
With full port QT ball valves (standard)
Model 350SHFT
Stainless steel handles, Fast-test test cocks
Model 350FT
Supplied with fast-test test cocks
Model 350XL
California AB 1953 compliant
Model 350L
Less ball valves – male pipe thread
Model 350S
With bronze wye strainer
Model 350SH
Supplied with stainless steel handles
Model 350BOF
Blow out flush housing for easy winterizing and
startup bundled with the Model 350 (3/4" & 1")
Accessories
Options
The Wilkins model 350 double check valve assembly, with its revolutionary removable pressure vessel, is
designed to protect against backpressure and backsiphonage of polluted water into the potable water
supply. In addition to the removable pressure vessel, the 350 series offers low head loss, short lay length,
and top mounted test cocks resulting in superior valve box installation flexibility. The removable pressure
vessel allows for the most rapid repair of any valve in the Backflow Preventer marketplace. The blow-out,
flush fitting greatly simplifies start-up flushing and winterization blow-outs (where needed). The 350 is
designed for applications where a health hazard does not exist, and is suitable for use in residential, commercial, industrial, and irrigation applications where a double check valve assembly is called for.
Features
Double Check Valve Assembly Model 350



Model 350
RK34-350BOF
For Additional Information, reference WK-BPC catalog or visit
our web site.



Wye strainer (Model S)
Thermal expansion tank (Model XT)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Winterizing blow out / flush fitting (RK34-350BOF or RK1-350BOF)
Ball valve monitor switch (Model BVMS, 3/4" & 1")
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
Typical Installation
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
/ WILKINS
350 DC
ZURN
2
MODEL 350
175 PSIG 180° F
MODEL 350S
12" MIN.
30" MAX.
DIRECTION OF FLOW
X Ref
INDOOR INSTALLATION
WILKINS
350
WATTS
007QT, 775, 719
CONBRACO
40-100-T2
OUTDOOR INSTALLATION
FEBCO
805Y, 850
AMES
200B, 2000B
HERSEY
HDC, FDC
Tech Support: 1-877-BACKFLO
www.zurn.com
®
23
a
®
company
Backflow Preventers
Applications
Double Check Valve Assembly 950XL Series
Model 950XL
With its time tested design, the Wilkins 950XL is capable of handling the toughest backflow conditions
that any double check valve assembly may incur. The 950XL, with its “wye” pattern configuration,
offers individual access covers to each check valve, replaceable check seats, and silicone seal rings,
all wrapped in a bronze body for use in non-health hazard applications. Since the 950XL carries the
Wilkins name, you can rest assured that the 950XL will provide “Performance Under Pressure”.
Temperature range 33°F – 180°F
Maximum pressure 175 psi
With BSP threaded connections
Available with stainless steel handles (optional)
ASSE® Listed 1015, IAPMO® Listed, C-UL® Classified (Model 950LXL),
UL® Classified (Model 950LXL), CSA® Certified, AWWA
• Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California
Model 950XL
FNPT x FNPT end connections
Model 950LXL
Less shut-off valves – male pipe thread
Model 950XLS
Supplied with wye strainer
Model 950XLFDC Same as 2” size 950XL except supplied with
21/2” female swivel inlet hose connection and
21/2” male outlet hose connection, for temporary
water service from fire hydrant
Model 950XLTCU With test cocks up
Model 950XLU
Supplied with union connections between ball
valves and the device
Model 950XLUS
Same as 950XLU except supplied with wye strainer
Model 950XLFT
Supplied with fast-test test cocks
Model 950XLSH
Supplied with stainless steel handles
Model 950XLOSY With OS&Y gate valves. UL® Classified only
For Additional Information, reference WK-BPC catalog or visit
our web site.




Thermal expansion tank (Model XT)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturer’s instructions and the latest edition of the
Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm)
above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be
submerged.
MODEL 950XLS
PROTECTIVE
ENCLOSURE
MODEL S
STRAINER
OUTDOOR INSTALLATION
MODEL 950XL
12" MIN.
30" MAX.
DIRECTION OF FLOW
X Ref
•
•
•
•
•
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Double check valve assembly consisting of two independently operated
spring-loaded center guided check valves, wye pattern body
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• Bronze body construction
• Noryl® replaceable seats and silicone rubber check discs
• Entire unit serviceable in line
Typical Installation
Accessories
Options
Features
Model 950XLOSY
12" MIN
30" MAX
DIRECTION OF FLOW
INDOOR INSTALLATION
WILKINS
WATTS
CONBRACO
FEBCO
AMES
HERSEY
950XL, 007QT, 775, 719
40-100-T2
805Y, 850
200B, 2000B, HDC, FDC
950LXL
007LF
40-100-T1
950XLS
007QTS
950LXTCU
950XLU
U007QT
40-100-T4
950XLUS
U007QTS
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
24
Backflow Preventers
Applications
• 3/4”, 1”
• Double check valve assembly consisting of two independently operated
spring-loaded wye type center guided check valves
• 90° elbow on inlet and outlet allows for easy conversion to different
configurations
• Compact design reduces space requirements for protective enclosures
• Eliminates the need for pipe elbows, nipples and unions
• Bronze body construction
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• Noryl replaceable seats and silicone rubber check discs
• Entire unit serviceable in line
• Temperature range 33°F – 180°F
• Maximum pressure 175 psi
• Available with stainless steel handles (optional)
• ASSE® Listed 1015, IAPMO® Listed (3/4” size), AWWA (3/4” size)
Model 950XLV
FNPT x FNPT with 90° swivel elbows
Model 950XLVS
Supplied with wye strainer
For Additional Information, reference WK-BPC catalog or visit
our web site.
Accessories Options
Building on the proud tradition of the Wilkins 950XL, the 950XLV was created with the installer in
mind. Equipped with swivel union elbows, the 950XLV offers installation flexibility in non-health hazard
applications where other competitive double check valve assemblies fall short. The swivel union
elbows are perfect for those installations that demand either a vertical up-up or up-down configuration.
Saving the installer time equates to increasing the installers profit margin, and the 950XLV is designed
to accomplish this goal.
Features
Model 950XLV Series Double Check Valve With Elbows
Model 950XLVSH Supplied with stainless steel handles
Model 950XLVFT Supplied with fast-test test cocks


Thermal expansion tank (Model XT)
Quick test set (QT-SET)


Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest
edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and
a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be
made so that no part of the unit can be submerged.
Typical Installation
MODEL 950XLV
MODEL 950XLV
12" MIN.
30" MAX.
12" MIN.
30" MAX.
BASEMENT
FLOOR
Tech Support: 1-877-BACKFLO
www.zurn.com
®
25
a
®
company
Backflow Preventers
Applications
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Top entry double check valve assembly consisting of two independently
operated, spring-loaded center guided check valves
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• Both check valves and test cocks are designed at an inclined angle upward for easy access during repair, maintenance and testing
• Bronze body construction
• Test cocks are provided with threaded plugs
•
•
•
•
•
•
•
Model 950XLT
FNPT x FNPT end connections
Model 950XLTFT
Model 950LXLT
Less shut-off valves
Model 950XLTS
Supplied with bronze wye strainer
Model 950XLTU
Supplied with union connections between shut-off
valves and the device
Options
When double check valve assemblies are installed in valve boxes, it is advantageous to have top
access to the check valves and test cocks. The Wilkins 950XLT embodies these advantages. Both
check valve access covers and test cocks are angled upward for easy access during testing and
repair. Designed for backflow protection where a health hazard does not exist, the 950XLT is perfect for residential, commercial, and irrigation applications requiring a valve box installed double
check.
Features
Top Access Double Check Valve Assembly 950XLT Series
Accessories
11/4" – 2"
Noryl® replaceable seats and silicone rubber check discs
Entire unit serviceable in line
Temperature range 33°F – 180°F
Maximum pressure 175 psi
With BSP threaded connections
ASSE® Listed 1015, IAPMO® Listed, CSA® Certified.
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Test cocks have Integral male 45° flare SAE test
fittings with threaded caps
Model 950XLTSH Supplied with stainless steel handles
Model 950XLTUS Same as 950XLTU except supplied with bronze
wye strainer



3/4" – 1"
For Additional Information, reference WK-BPC catalog or visit
our web site.



Thermal expansion tank (Model XT)
Bronze wye strainer (Model S)
Stainless steel ball valve handles
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturer’s instructions and the latest edition of the
Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm)
above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be
submerged.
Typical Installation
PROTECTIVE
ENCLOSURE
MODEL 950XLTS
MODEL 950XLT
12" MIN.
30" MAX.
DIRECTION OF FLOW
DIRECTION OF FLOW
X Ref
OUTDOOR INSTALLATION
WILKINS
WATTS
950XLT
007QT, 719QT 950LXLT
PIT INSTALLATION
CONBRACO
FEBCO
AMES
HERSEY
40-100-T2
850
200B, 2000B
FDC
40-100-T1
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
26
Backflow Preventers
Applications
Double Check Valve 350A/350 Series Pat. No. 5,913,331
Building on Wilkins’ penchant for creating problem solving designs, the 350A / 350 series double check
valve assemblies step up to the plate. From their short, light weight ductile iron bodies to their patented
low head loss Compound Checks®, the 350A / 350 series offers the best features a modern double check
can offer. The 350A series utilize grooved couplings to attach the shut-off valves to the body whereas
the 350 utilizes flanges. Acceptable for use in any non-health hazard application, the 350A / 350 double
check valve assemblies are the valves that the fire, plumbing, and irrigation professionals view as the
zenith in backflow prevention assembly design.
• 350A 21/2”, 3”, 4”, 6”, 8”, 10”
350 21/2”, 3”, 4”, 6”, 8”, 10”, 12”
• Double check valve consisting of two independently operated springloaded center guided check valves
• Complete with two flange-ended non-rising stem resilient wedge gate
valves and four resilient seated ball valve test cocks
• Lightweight, thin wall, epoxy-coated ductile iron
• Check components are made from lead-free engineered plastics and
stainless steel
• No threads or taps in body or cover, eliminating exposure to corrosion
• Single access cover reduces maintenance down time
• Entire unit serviceable in-line
• Temperature range 33°F - 140°F
• Maximum pressure 175 psi
• ASSE® Listed 1015 (horizontal/vertical), AWWA Listed (horizontal/
vertical), IAPMO® Listed (350 only) (horizontal/vertical)
• CSA® Certified (horizontal/vertical), C-UL® Classified (horizontal/
vertical), UL® Classified (horizontal/vertical), FM® Approved
(horizontal/vertical) (21/2” – 10”)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
(horizontal/vertical) (21/2” – 10”)
• 12” UL Classified (horizontal)
• Contact Wilkins for approval updates
Model 350
Flanged body, NRS gate valves
Model 350FG
Model 350A
Grooved body, with grooved by flanged NRS
gate valves
Flanged body, with flanged inlet connection and
grooved outlet connection
Model 350AFG
Grooved body, with flanged inlet connection and
grooved outlet connection
Model 350L
Flanged body, less gate valves
Model 350AL
Grooved body, less gate valves
Model 350FSC
Model 350G
Flanged body, with flanged by grooved NRS
gate valves
Same as 350 except supplied with an epoxy
coated flanged wye strainer
Model 350AFSC
Model 350AG
Grooved body, with grooved by grooved NRS
gate valves
Same as 350A except supplied with an epoxy
coated wye strainer
Model 350PI
Flanged body supplied with Post Indicator Valve
Model 350API
Grooved body supplied with Post Indicator Valve
Model 350OSY
Flanged body, with flanged by flanged OS&Y
gate valves
Model 350AOSY
Grooved body, with grooved by flanged OS&Y
gate valves
Model 350OSYG
Flanged body, with flanged by grooved OS&Y
gate valves
Model 350AOSYG Grooved body, with grooved by grooved OS&Y
gate valves


To create a part number to fit your needs, see page 3 for an
example. For Additional Information, reference WK-BPC catalog
or visit our web site.

FSC wye strainer (non fire protection applications)
OS&Y gate valve tamper switch (OSY-40)
Local codes shall govern installation
requirements. Unless otherwise specified ,
the assembly shall be mounted at a minimum of 12” (305mm) and a maximum
of 30” (762mm) above adequate drains
with sufficient side clearance for testing
and maintenance. The installation shall be
made so that no part of the unit can be
submerged.
Test cock lock (Model TCL24)
PROTECTIVE
ENCLOSURE
12" MIN.
30" MAX.
12" MIN.
30" MAX.
DIRECTION OF FLOW
DIRECTION OF FLOW
INDOOR INSTALLATION
MODEL 350ABGVIC
X Ref
Model 350ABGVICGrooved body, with grooved by grooved,
tampered Victaulic® butterfly valves (21/2” – 8”)
DIRECTION OF FLOW
Typical Installation Accessories
Options
Features
(350ABGVIC shown)
WILKINS 350
INDOOR INSTALLATION
(VERT.) MODEL 350OSYG
WATTS
CONBRACO
FEBCO
774, 774X
4S-100
850, 857
775, 757a
OUTDOOR INSTALLATION
MODEL 350AFSC
AMES
2000SS, 200(a) Maxim & Colt
2001SS
Tech Support: 1-877-BACKFLO
www.zurn.com
®
27
a
®
company
Backflow Preventers
There are many instances where a double check valve assembly must be retrofitted into a system, but
there is inadequate room to install a traditional in-line, horizontal valve. The Wilkins 450 was designed
with this problem in mind. The 450, with its “N” pattern design, offers a compact double check that
lends itself well to cramped, retrofit locations. Constructed with light weight, ductile iron bodies, the 450
also utilizes the patented Compound Checks®, resulting in a light weight valve with extremely low head
loss. Providing protection where a health hazard does not exist, the Wilkins 450 is the “space saver” you
need on your retrofit job! Works well when an enclosure is specified, as the smaller footprint allows for a
smaller enclosure, reducing total installed costs. Check out the valve setter as well.
X Ref
(3" 450 Shown)
(450G Shown)
• 21/2”, 3”, 4”, 6”, 8”, 10”
• Double check valve assembly consisting of two independently operated
spring-loaded center guided check valves
• Standard with two flange-ended non-rising stem resilient wedge gate
valves and four resilient seated ball valve test cocks
• Lightweight, ductile iron construction with FDA approved fusion epoxy
coat inside and out
• Utilizes a patented center-stem guided Compound Checks® closure
(Pat. No. 5,913,331)
• Dual torsion springs bias the check in the closed position
• Modular poppet design; lead-free engineered plastic (Noryl®) and
stainless steel
• Replaceable seats and seat discs
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• ASSE® Listed 1015, IAPMO® Listed, CSA® Certified (21/2” – 8”), AWWA
Compliant, UL® Classified, C-UL® Classified, FM® Approved
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 450
Flange and NRS gate valves
Model 450OSYG Grooved end OS&Y gate valves
Model 450G
Grooved end gate valves
Model 450PI
Model 450FG
Flanged inlet gate connection and grooved outlet
NRS gate connection
Model 450L
Less gate valves (grooved end body connections)
Model 450OSY
Flanged end OS&Y (outside stem and yoke) gate
valves. For fire protection applications



Supplied with post indicator gate valve.
(4” – 8”) (ask for spec sheet GV-PI)
Model 450BGVIC With grooved by grooved Victaulic® tampered
butterfly shutoff (4”, 6" & 8”)
To create a part number to fit your needs, see page 3 for an
example. For Additional Information, reference WK-BPC catalog
or visit our web site.



Thermal expansion tank (Model XT)
Valve setter (Model FLS or MJS or MJFS)
Flange by groove adapter (FLA)
OS&Y gate valve supervisory switch (OSY-40)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. To be installed in accordance
with the manufacturer’s instructions and the latest edition of the Uniform
Plumbing Code. Unless otherwise specified, the assembly shall be mounted at
a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate
drains with sufficient side clearance for testing and maintenance. The installation
shall be made so that no part of the unit can be submerged.
Typical Installation
Accessories
Options
Features
Applications
Double Check Valve 450 Series Pat. No. 5,913,331
PROTECTIVE
ENCLOSURE
MODEL 450G
12" MIN.
30" MAX.
DIRECTION OF FLOW
WILKINS VALVE SETTER
MODEL MJFS
WILKINS 450
WATTS
N775
FEBCO
AMES
870
2001SSN, 200(a) M&C “N”
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
28
Backflow Preventers
Designed to protect against backflow in residential and smaller commercial fire systems, the
Wilkins 950XLTDABF double check detector assembly offers an alternative to the larger flanged
detector assemblies that are typically used. Constructed around the 2” 950XLT, the 950XLTDA
utilizes a meter and ¾” 350 by-pass to detect the unauthorized use or leaking of water in a residential fire protection system. Available with either OS&Y (XLTDA) or butterfly (XLTDABF) shutoff valves, the 950XLTDA will satisfy the design criteria of any residential fire system that requires
a short, light-weight double check detector assembly where a health hazard does not exist.
• 2”
• Double check valve consisting of two independently operated springloaded center guided check valves
• Complete with two resilient wedge OS&Y gate valves and four resilient
seated ball valve test cocks
• The by-pass assembly consists of a water meter (gpm standard) in series
with a double check backflow preventer
• For use in fire line applications
• Entire unit serviceable in line
• Temperature range 33°F – 180°F
•
•
•
•
•
•
•
•
950XLTDABF
With butterfly shut-off valves
950XLTDALM
Less water meter
950XLTDABFSS
With butterfly shut-off valves and supervisory
switches
950XLTDACFM
With cu ft/min meter
950XLTDASCFM
Sensus cubic ft/min. meter
FNPT OS&Y x FNPT OS&Y end connections
For Additional Information, reference WK-BPC catalog or visit
our web site.
950XLTDA



Maximum pressure 175 psi
Bronze body construction
Maximum working water pressure 175 psi
Maximum working water temperature 180°F
Hydrostatic test pressure 350 psi
End connections (threaded) ANSI B1.20.1
Test cocks are provided with threaded plugs
ASSE® Listed 1040A, UL® Classified (horizontal/vertical), C-UL® Classified
(horizontal/vertical)
• Contact Wilkins for additional approval status
OS&Y gate valve supervisory switch (OSY-40)
Test cock lock (Model TCL24)
Quick test set (QT-SET)
Local codes shall govern installation requirements. To be installed in accordance with the
manufacturer’s instructions and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and
a maximum of 30” (762mm) above adequate drains with sufficient side clearance for
testing and maintenance. The installation shall be made so that no part of the unit can
be submerged.
MODEL 950XLTDABF
DIRECTION OF FLOW
Typical Installation
Accessories Options
Features
Applications
Double Check Detector 950XLTDABF
PROTECTIVE
ENCLOSURE
MODEL 950XLTDABF
12” MIN.
30” MAX.
DIRECTION OF FLOW
Tech Support: 1-877-BACKFLO
www.zurn.com
®
29
a
®
company
Backflow Preventers
Double Check Detector 350ADA/350DA Series
Applications
• 350ADA 21/2", 3", 4", 6", 8", 10"
350DA 21/2", 3", 4", 6", 8", 10”, 12"
• Double check valve consisting of two independently operated springloaded center guided check valves
• Complete with two flange-ended resilient wedge OS&Y gate valves and
four resilient seated ball valve test cocks
• The by-pass assembly consists of a water meter in series with a double
check backflow preventer
• For use in fire line applications
• Lightweight, thin wall, epoxy-coated ductile iron
• Modular check design utilizing lead-free engineered plastic (Noryl®) and
stainless steel
• No threads or taps in body or cover, eliminating exposure to corrosion
•
•
•
•
•
Model 350DA
Flanged body, flanged OS&Y gate valves
Model 350DAPI
Model 350ADA
Grooved body, with grooved by flanged
OS&Y gate valves
Flanged body supplied with Post Indicator
Valve (3” – 12”)
Model 350ADAPI
Model 350DAL
Flanged body, less gate valves
Grooved body supplied with Post Indicator
Valve (3” – 10”)
Model 350ADAL
Grooved body, less gate valves
Model 350DALM
Less water meter
Model 350DAG
Flanged body, with flanged by grooved
OS&Y gate valves
X Ref
Typical Installation
Accessories
Options
Fire protection systems, with their unmetered lines and unique need for ultra-low head loss, demand
a valve that can deal with this criteria. The Wilkins 350ADA / 350DA series double check detector
assemblies are ready to take on the challenge. Designed to detect water leakage or usage while
protecting against backpressure and backsiphonage, the 350ADA / 350DA series and their patented
Compound Checks® provide the low head loss that fire protection professionals demand. Providing
backflow protection where a health hazard does not exist, the 350ADA / 350DA is provided with
grooved or flanged body connections and the choice of grooved or flanged terminating ends.
Features
Pat. No. 5,913,331
Single access cover reduces maintenance down time
Entire unit serviceable in line
Temperature range 33°F – 140°F
Maximum pressure 175 psi
ASSE® Listed 1048 (horizontal/vertical),
UL® Classified (horizontal/vertical), C-UL® Classified (horizontal/vertical),
FM® Approved (horizontal/vertical), CSA® Classified (horizontal/vertical), AWWA Compliant (horizontal/vertical) (2" – 10")
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California (21/2" – 10")
• Available with CFM water meter (5/8" x 3/4")
• 12" UL classified (horizontal)
Model 350ADABGVIC Grooved body, with grooved by grooved,
tampered Victaulic® butterfly valves
(21/2” – 8”)
CFM
With cubic feet meter
SCFM
With Sensus cubic feet meter
Model 350ADAG
Grooved body, with grooved by grooved
OS&Y gate valves
Model 350DAFG
Flanged body, with flanged inlet connection
and grooved outlet connection
To create a part number to fit your needs, see page 3 for an
example
Model 350ADAFG
Grooved body, with flanged inlet connection
and grooved outlet connection
For Additional Information, reference WK-BPC catalog or visit
our web site.


OS&Y gate valve supervisory switch (OSY-40)
Test cock lock (Model TCL24)
Local codes shall govern installation
requirements. Unless otherwise specified, the assembly shall be mounted
at a minimum of 12” (305mm) and
a maximum of 30” (762mm) above
adequate drains with sufficient side
clearance for testing and maintenance. The installation shall be made
so that no part of the unit can be
submerged.
PROTECTIVE
ENCLOSURE
MODEL 350ADA
12" MIN.
30" MAX.
DIRECTION OF FLOW
WILKINS 350DA
350DA, 350DAG
350DA
WATTS
770DCDA
709DCDA
774DCDA
CONBRACO
FEBCO
AMES
HERSEY
40-600
806YD, 858
3000SS
DDC II
4S,4SG
856
3000DCDA
4S-60EC3
3001SS, 300(a) Maxim & Colt
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
30
Backflow Preventers
Applications
• 4”, 6”, 8”, 10”
• Double check valve consisting of two independently operated springloaded center guided check valves
• Standard with two flange-ended resilient wedge OS&Y (outside stem
and yoke) gate valves and four resilient seated ball valves and test cocks
• The bypass assembly consists of a 5/8” x 3/4” water meter in series with
a double check valve backflow preventer
• Lightweight, ductile iron construction with FDA approved fusion epoxy
coat inside and out
• Utilizes a patented center-stem guided Compound Check® closure
(Pat. No. 5,913,331)
• Modular check design utilizing lead-free engineered plastic (Noryl®)
and stainless steel
• For use in fire line services
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• ASSE® Listed 1048, UL® Classified, FM® Approved, C-UL® Classified,
AWWA Compliant, CSA® Certified (sizes 4” & 6”)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 450DA
Flanged end OS&Y gate valves
Model 450DAPI
Model 450DAL
Less end OS&Y gate valves, grooved
connections
Supplied with post indicator gate valve (ask
for spec sheet GV-PI)
Model 450CFM
With cubic feet meter
Model 450DAG
Grooved end OS&Y gate valves
Model 450SCFM
With Sensus cubic feet meter
Model 450DALM
Less water meter
Typical Installation
Accessories
Options
When space is tight, and a traditional horizontal valve just will not fit, the Wilkins 450DA is the space saver
that is needed. The 450DA is an “N” pattern double check detector assembly designed to prevent backpressure or backsiphonage of water from the fire system into the public potable supply. While protecting
against a non-health hazard backflow condition, the 450DA provides low head loss and excellent backflow
protection through the use of the center stem guided Compound Check®. As is true with all of Wilkins large
diameter backflow assemblies, the 450DA is available with grooved or flanged end connections via gate or
butterfly shut-off valves.
Features
Double Check Detector 450DA Series Pat. No. 5,913,331
(450DAG Shown)
Model 450DABGVIC Supplied with groove x groove tampered
Victaulic® butterfly valves (4” – 8”)
To create a part number to fit your needs, see page 3 for an
example
Model 450DAFG
For Additional Information, reference WK-BPC catalog or visit
our web site.



Flanged inlet gate connection and grooved
outlet OS&Y gate connection


Valve setter (Model FLS or MJS or MJFS)
Flange by groove adapter (FLA)
OS&Y gate valve supervisory switch (OSY-40)
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be made so that no part of
the unit can be submerged.
Quick test set (QT-SET)
Test cock lock (Model TCL24)
PROTECTIVE
ENCLOSURE
MODEL 450DA
12" MIN.
30" MAX.
WILKINS VALVE
SETTER
MODEL MJFS
X Ref
DIRECTION OF FLOW
WILKINS WATTS
450DA
N775DCDA
FEBCO
AMES
876
3001SSN
876V 3001SSZ, 300(a) M&C “N”
Tech Support: 1-877-BACKFLO
www.zurn.com
®
31
a
®
company
Backflow Preventers
Applications
• 1/4”, 3/8”, 1/2”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• Bronze body construction
• Noryl® replaceable seats
•
•
•
•
•
•
•
Model 975XL
FNPT x FNPT end connections
Model 975XLTCU Supplied with test cocks up
Model 975LXL
Less shut-off valves
Model 975XLST
Model 975XFT
Supplied with fast-test test cocks
Model 975XLS
Supplied with wye strainer (1/2” only)
Model 975XLSH
Supplied with stainless steel handles
Typical Installation
Accessories Options
The 1/4” to 1/2” 975XL was designed for installation in very tight locations. Typically, high hazard
applications such as beverage machines require installation in small, inaccessible areas. With the
975XL’s top access to the checks, it is much easier to repair than “wye” pattern designs when in
difficult assembling areas. Designed to prevent backpressure and backsiphonage of contaminated water into the public potable supply, the1/4” to 1/2” 975XL is ready for the challenge.
Features
Reduced Pressure Principle 975XL Series



Silicone check valve discs standard
Entire unit serviceable in line
Temperature range 33°F – 180°F
Maximum pressure 175 psi
Available with stainless steel handles (optional)
ASSE® Listed 1013, IAPMO® Listed, CSA® Certified
Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California
Supplied with stainless steel body, test cocks,
and shut-off valves (3/8” and 1/2”). California
AB 1953 compliant
For Additional Information, reference WK-BPC catalog or visit
our web site.



Air gap (Model AG-8)
wye strainer (Model S)
Thermal expansion tank (Model XT)
Local codes shall govern installation requirements. To be installed
in accordance with the manufacturers’ instructions and the
latest edition of the Uniform Plumbing Code. Unless otherwise
specified, the assembly shall be mounted at a minimum of 12”
(305mm) and a maximum of 30” (762mm) above adequate
drains with sufficient side clearance for testing and maintenance.
The installation shall be made so that no part of the unit can be
submerged or where relief valve discharge could cause damage.
Test cock lock (Model TCL24)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
MODEL 975XL
AIR GAP
MODEL AG
12" MIN.
30" MAX.
DRAIN
X Ref
DIRECTION OF FLOW.
WILKINS
975XL
975LXL
975XLS
975XLST
WATTS
CONBRACO
FEBCO
AMES
HERSEY
009QT, 995, 909QT, 40-200-T2
825Y, 860
400B
FRPII
909M1QT, 919
009LF
40-200-T1
009QTS, 909QTS,
909M1QTS
SS009
40-200-T2S
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
32
Backflow Preventers
Features
Applications
Reduced Pressure Principle Assembly Model 375 Pat. No. 6,513,543
Wilkins has built a reputation of designing products that answer the need of the customer, and
the voice of the customer was the driving force behind the design of the 375. With its unique,
removable pressure vessel, the 375 is repaired easier and quicker than any other reduced pressure
principle assembly on the market. This unique design allows for rapid commissioning because the
entire pressure vessel can be removed for line flushing. The patented blow-out, flush fitting assists
in system start-ups and winterizations. When there is a need for simplicity and speed in repair, the
Wilkins 375 cannot be beat.
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Short lay length – fits in smaller area
• Top access to test cocks and shutoff valves and check assembly
Removable pressure vessel eliminates the need of union connections
Simple design for easy maintenance
Composite housing and check modules resist corrosion
ASSE® Listed 1013, (horizontal (3/4"-2") / vertical (3/4" & 1")), IAPMO®
Listed, CSA® Certified
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California (3/4” & 1”,
Contact Wilkins for 11/4” – 2” approvals)
– easy to test
cleaning or repair
• Easy to winterize by removing pressure vessel between shutoff
valves
Accessories Options
• Plastic pressure vessel is a theft deterrent





Model 375BOF
•
•
•
•
• Entire pressure vessel is removable to facilitate check access for
Model 375
Model 375L
Model 375S
Model 375FT
Model 375BOF
Model 375
With full port QT ball valves (standard)
Less ball valves – male pipe thread
With bronze wye strainer
Supplied with fast-test test cocks
Blow out flush housing for easy winterizing and
start up (bundled with the Model 375, 3/4" & 1")
Model 375SH
Stainless steel handles
Model 375SHFT
Stainless steel handles, Fast-test test cocks
Model 375XL
California AB 1953 compliant
Model 375P
Purple pressure vessel for reclaimed water
For Additional Information, reference WK-BPC catalog or visit
our web site.



Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Blow out / flush fitting (RK34-375BOF or RK1-375BOF)
Bronze wye strainer (Model S)
Typical Installation
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise
specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30”
(762mm) above adequate drains with sufficient side clearance for testing and maintenance. The
installation shall be made so that no part of the unit can be submerged.
MODEL 375SAG (3/4”- 1”)
75AG (1 1/4”- 2”)
4
375 RP
ZURN
/ WILKINS
175 PSIG 180° F
12" MIN.
30" MAX.
MODEL 375AG (1 1/4”- 2”)
3/4" 375 RP
ZURN
WILKINS
PROTECTIVE
ENCLOSURE
AIR GAP
/ WILKINS
175 PSIG 180° F
(1-1/4” - 2”) 8 1/8
(3/4” - 1”) 5 1/2
12" MIN.
30" MAX.
OPTIO
WATE
(1-1/4” - 2”) 3” PIPE
(3/4” - 1”) 2” PIPE
(DRAIN LINE CAN
BE ANY STANDARD
PIPING MATERIAL)
INLET SHUT OFF
LLATION
DIRECTION OF FLOW
WATTS
CONBRACO
009QT, 995, 909QT, 40-200-A2
909M1QT, 919
FLOOR DRAIN
INDOOR INSTALLATION
OUTDOOR INSTALLATION
WILKINS 375
12" MIN.
30" MAX.
FLOOR
DRAIN
DIRECTION OF FLOW
FLOOR DRAIN
X Ref
ZURN
1013
OPTIONAL
WATER METER
375 RP
B64.4
2
175 PSIG 180ß F
FEBCO
825Y,860
AMES
400B, 4000B
HERSEY
FRPII
Tech Support: 1-877-BACKFLO
www.zurn.com
®
33
a
®
company
Backflow Preventers
Applications
• 3/4", 1", 11/4", 11/2", 2"
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded wye type center guided check valves, wye pattern body
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• Bronze body construction
• Noryl® replaceable seats and silicone rubber check discs
• Entire unit serviceable in line
Temperature range 33°F – 180°F
Maximum pressure 175 psi
With BSP threaded connections
Available with stainless steel ball valve handles (optional)
ASSE® Listed 1013, IAPMO® Listed, CSA® Certified, AWWA, UL® Classified (Model 975LXL), C-UL® Classified (Model 975LXL)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 975XL
Model 975XLTCU
Model 975LXL
Model 975XLS
Model 975XLU
Model 975XLBMS Battery-powered integral supervisory switch
Model 975XLFDC Same as 2" size 975XL except supplied with
21/2" female swivel inlet hose connection and
21/2" male outlet hose connection, for temporary
water service from fire hydrant
Model 975XLFT
Supplied with fast-test test cocks
Model 975XLSH
Supplied with stainless steel handles
Typical Installation
Accessories
Options
Giving superior protection against both backpressure and backsiphonage in a high hazard application is exactly what the Backflow Prevention professional expects, and that is exactly what
the Wilkins 975XL offers. Built around the time honored “Wye pattern” design, the 975XL is
loaded with the features that demanding professionals ask for. From the individual access covers for the three main components, to the use of all silicone elastomers and Noryl® polymers,
the 975XL is the feature loaded valve that the professionals demanded. When your high hazard backflow installation demands the best RP available, you can rely on the Wilkins 975XL.
Features
Reduced Pressure Principle 975XL Series
Model 975XLUS
Model 975XLSE
Model 975XLP
Model 975XLMS




FNPT x FNPT end connections
Test cocks up
Less shut-off valves
Supplied with wye strainer
Supplied with union connections between shut-off
valves and the device
Same as 975XLU except supplied with wye strainer
Supplied with 90° elbows
Purple access covers for reclaimed water
Integral supervisory switch
•
•
•
•
•
For Additional Information, reference WK-BPC catalog or visit
our web site.




Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Ball valve handle locks (BVHL)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform
Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
MODEL 975XL
MODEL S
STRAINER
PROTECTIVE
ENCLOSURE
12" MIN
30" MAX
OPTIONAL
WATER METER
AIR GAP
DRAIN
DIRECTION OF FLOW
X Ref
INLET SHUT-OFF MODEL 850
WILKINS 975XL
WATTS
CONBRACO
FEBCO
AMES
HERSEY
009QT, 995,
40-200-A2
825Y,860
400B, 4000B
FRPII
909QT, 909M1QT,
40-200-A1
919 ,009LF
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
34
Backflow Preventers
Applications
Reduced Pressure Principle with Integral Relief Valve
Monitor Switch 975XLMS Series Pat. No. 5,425,393
Reduced pressure principle assemblies are designed to discharge water. Relief valve discharge can
result in severe property damage should the discharge go undetected. The Wilkins 975XLMS can
alleviate the potential damage. The relief valve is equipped with a monitor switch that when attached to the appropriate alarm, will notify the proper authorities that the relief valve is discharging.
Hence the discharge can be corrected before damage occurs. While still providing the superior
protection of the 975XL the 975XLMS can also be used in conjunction with the ZW106 and EST
allowing for a total shut-off of the water during relief valve discharge.
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Reduced pressure principle backflow preventer with patented integral
Accessories Options
Features
relief valve monitor switch
• When connected to a low voltage alarm circuit, the monitor switch
electrically supervises the relief valve in the closed position
• In the event of a backflow condition, the relief valve closes an electrical
•
•
•
•
•
circuit, signaling that a possible relief valve discharge may be occurring
Weather-resistant housing and wire leads
Switch contact rating 3A @ 24V
Bronze body and cover construction
Spring-loaded, center guided check valves
Noryl® replaceable seats
•
•
•
•
•
•
•
•
•
Entire unit serviceable in line
Temperature range 33°F – 180°F
Maximum pressure 175 psi
UL® recognized switch – supplied with normally open contacts
Switch is factory installed and ready for immediate installation to appropriate
electrical circuit
With BSP threaded connections
Self-contained monitor switch is also available as a kit to retrofit existing
975XL installations.
ASSE® Listed 1013, IAPMO® Listed, AWWA Compliant, CSA® Certified
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 975XLMSU Union connections between ball valves and the
device
Model 975LXLMS FNPT x FNPT end connections
Model 975LXLMS Less shut-off valves
Model 975XLMSS Supplied with wye Strainer
For Additional Information, reference WK-BPC catalog or visit
our web site.







Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Typical Installation
Local codes shall govern installation requirements. To be installed in accordance with the manufacturer’s instructions and the latest edition of the Uniform
Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
PROTECTIVE
ENCLOSURE
TO LOW VOLTAGE ELECTRICAL
CONTACT PANEL WITH ALARM,
LIGHT, HORN, ETC.
MODEL 975XLMS
MODEL 975XLMS
TO LOW VOLTAGE ELECTRICAL
CONTACT PANEL WITH ALARM,
HORN, LIGHT, ETC.
12" MIN.
30" MAX.
12" MIN.
30" MAX.
DIRECTION OF FLOW
OUTDOOR INSTALLATION
INDOOR INSTALLATION
Tech Support: 1-877-BACKFLO
www.zurn.com
®
35
a
®
company
Backflow Preventers
Applications
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Reduced pressure principle backflow preventer with self-contained
battery powered switch
• In the event of a backflow condition the 975XLBMS sounds an audible
alarm signaling that a possible relief valve discharge may be occurring
• Features manual on/off switch and LED indicating battery charge
• Built-in delay to prevent false signal due to intermediate pressure
fluctuations
• Bronze body and cover construction
• Spring-loaded, center guided check valves
• Noryl® replaceable seats
• Entire unit serviceable in line
•
•
•
•
Model 975XLBMS
Model BVMS
FNPT x FNPT end connections
•
•
•
•
Temperature range 33°F – 180°F
Maximum pressure 175 psi
UL® recognized switch – supplied with normally open contacts
Switch is factory installed and ready for immediate installation to appropriate
electrical circuit
With BSP threaded connections
Self-contained monitor switch is also available as a kit to retrofit existing
975XL installations
ASSE® Listed 1013, IAPMO® Listed, AWWA, CSA® Certified
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Supplied with ball valve monitor switch
Model 975LXLBMS Less shut-off valves
For Additional Information, reference WK-BPC catalog or visit
our web site.
Model 975XLBMSS Supplied with bronze wye strainer
Model 975XLBMSU Union connections between ball valves and
the device






Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. Note: If installed outdoors, a protective enclosure is recommended. The
installation shall be made so that no part of the unit can be submerged.
CENTRAL
STATION
ALARM
PANEL
Typical Installation
Accessories Options
Relief valve discharge from a reduced pressure principle assembly can lead to costly water
damage. The 975XLBMS is designed to sound an audible alarm should the relief valve begin
to discharge. The battery monitor switch used with the 975XLBMS is a stand-alone alarm that
does not require electrical power. When the relief valve discharge occurs, the BMS’s internal
timer will set off an audible alarm within 10 seconds, letting the appropriate people know that
discharge is occurring. In addition to this feature, the BMS also exhibits a phone port that can
be connected to an auto dialer or alarm panel.
Features
Reduced Pressure Principle with Integral Relief Valve Battery
Monitor Switch 975XLBMS Series Pat. No. 5,425,393
MODEL 975XLBMS
BATTERY
MONITOR
SWITCH
12" MIN.
30" MAX.
AIR GAP
FITTING
FLOOR
FLOOR DRAIN
DIRECTION OF FLOW
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
36
Backflow Preventers
Applications
Reduced Pressure Principle with Swivel Elbows 975XLV Series
Installation flexibility was the main focus when Wilkins created the 975XLV. In high hazard
applications, the 975XLV will protect against both backpressure and backsiphonage, while
allowing vertical up-up and up-down installation via the union connected elbows. The
sweeping elbows along with the superior design qualities of the 975XL, yield low head loss
and repeatability that Wilkins backflow preventers are known for.
Accessories Options
Features
• 3/4”, 1”
• Reduced pressure principle backflow preventer consisting of a pressure
•
•
•
•
•
differential relief valve located between two independently operated
spring-loaded center guided check valves, wye pattern body
Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
90° swivel union elbow on inlet and outlet allows for easy conversion to
different configurations
Compact design reduces space requirements for protective enclosures
Eliminates the need for pipe elbows, nipples and unions
Bronze body construction
Model 975XLV
FNPT x FNPT with swivel elbows
Model 975XLVS
Supplied with bronze wye strainer
•
•
•
•
•
•
•
Replaceable Noryl® check seats
Silicone check valve disc standard
Entire unit serviceable in line
Temperature range 33°F - 180°F
Maximum pressure 175 psi
Available with stainless steel handles (optional)
ASSE® Listed 1013, IAPMO® Listed, AWWA Compliant (horizontal/
vertical), CSA® Certified (horizontal/vertical)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
For Additional Information, reference WK-BPC catalog or visit
our web site.
Model 975XLVFT Supplied with fast-test test cocks







Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
MODEL 975XLV
Typical Installation
MODEL 975XLV
AIR GAP
MODEL AG
12" MIN.
30" MAX.
12" MIN.
30" MAX.
FLOOR DRAIN
X Ref
INDOOR VERTICAL INSTALLATION
WILKINS
975LXV
975XLVS
WATTS
U009AQT
U009AQTS
OUTDOOR HORIZONTAL INSTALLATION
CONBRACO
40-200-A2U (or Z)
Tech Support: 1-877-BACKFLO
www.zurn.com
®
37
a
®
company
Backflow Preventers
The 975XLSE provides the flexibility of allowing a vertical up-up and up-down installation,
while keeping the installation foot print small. The use of street elbows installed between
the valve body and the shut-off valves, yield the narrow footprint. The 975XLSE is a perfect
valve for use in high hazard backpressure or backsiphonage irrigation installations where a
large backflow enclosure would detract from the aesthetics of the landscape.
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves, wye pattern body
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• 90° street elbows allow for easy retrofit in space restrictive areas
• Short laying length
• Bronze body construction
• Replaceable Noryl® check seats
•
•
•
•
•
•
Model 975XLSE
For Additional Information, reference WK-BPC catalog or visit
our web site.
FNPT x FNPT with street elbows (3/4” & 1”)
Model 975XLSEU Full port quarter turn union ball valves
Silicone check valve disc standard
Entire unit serviceable in line
Temperature range 33°F – 180°F
Maximum pressure 175 psi
Available with stainless steel handles (optional)
ASSE® Listed (11/4” – 2”), AWWA Compliant, IAPMO® Listed,
CSA® Certified
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 975XLSEFT Supplied with fast-test test cocks







Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at
a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance
MODEL 975XLSE
for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
Typical Installation
Accessories Options
Features
Applications
Reduced Pressure Principle with 90° Elbows 975XLSE Series
DIRECTION OF FLOW
MODEL 975XLSE
X Ref
DIRECTION OF FLOW
WILKINS 375XLSE
FEBCO
825YA
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
38
Backflow Preventers
Accessories
Options
Features
Applications
Pre-Plumbed Backflow Station Pre-Set Series
The pre-set series of pre-plumbed backflow stations were created by Wilkins to reduce the time
necessary to install a backflow station. Typically, a backflow station will embody the backflow preventer,
wye strainer, pressure reducing valve and or check valve all plumbed together. Wilkins had a desire to
reduce the amount of labor the installer would spend by giving the installer a pre-plumbed, pre-tested
station. Available with either a 950XL or a 975XL, the appropriate strainer, pressure reducing valve, or
check valve is added to the station according to the needs of the installation.
(2" 975XLVSR Shown)
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Pre-plumbed backflow station. Assembly can be of the reduced
• Each unit is fully assembled with elbows, unions, and nipples, thereby
reducing time, effort and materials normally necessary in a backflow
installation
• Available with stainless steel handles (optional)
• ASSE® Listed 1013 (975XL), ASSE® Listed 1015 (950XL)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California (975XL)
pressure principle or of the double check type
• Includes a Model 975XL or 950XL backflow preventer and either
a wye strainer, in-line check valve, or pressure reducing valve in any
combination
• Each station is provided with unions between the backflow body &
shutoff valves
Model 950XLVSR/975XLVSR
Model YB wye strainer on inlet and
Model BR4 regulator on outlet
Model 950XLVSC/975XLVSC
Model YB wye strainer on inlet and
Model 40XL In-line Check Valve on
outlet
Model 950XLVRS/975XLVRS
Model BR4 regulator on inlet and
Model YB wye strainer on outlet
Model 950XLVCS/975XLVCS
Model 40XL in-line check valve on
inlet and Model YB wye strainer on
outlet
Model 950XLVCR/975XLVCR Model 40XL in-line check valve on
inlet and Model BR4 regulator on
outlet
Model 950XLVRC/975XLVRC Model BR4 Regulator on inlet and
Model 40XL in-line check valve on
outlet
For Additional Information, reference WK-BPC catalog or visit
our web site.







Air gap (Model AG)
Thermal expansion tank (Model XT)
Water hammer arrestor (Model 1250)
Quick test set (QT-SET)
Ball valve handle locks (BVHL)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Typical Installation
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in
accordance with manufacturer’s instructions and the latest edition of the Uniform Plumbing Code. If installed in
a pit or vault, specify the “SC” sealed cage option for the specified regulator. The assembly shall be installed with
sufficient side clearance for testing and maintenance. Multiple installations are recommended for wide demand
variations or where the desired pressure reduction is more than 4 to 1 (i.e.: 200 psi inlet reduced to 50 psi outlet).
CAUTION: Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct
pressure setting. Do not bottom adjustment bolt on bell housing.
OUTDOOR INSTALLATION
Tech Support: 1-877-BACKFLO
www.zurn.com
®
39
a
®
company
Backflow Preventers
The voice of the customer told Wilkins loud and clear that there was a need for lighter weight and lower
head loss when it came to reduced pressure principle assemblies. Wilkins answered the challenge with
the release of the 375A / 375 series reduced pressure principle assemblies. Ductile iron body construction
drastically reduced the weight that is normally associated with gray iron bodies, and the patented Compound Check® took head loss to lows not previously seen with a center-stem guided check. The 375A,
with its grooved body connections, and the 375, with is flanged body connection are available with gate
and butterfly shut-off valves. Designed to protect against backpressure and backsiphonage in a high
hazard application, both the 375A and 375 are available with flanged and grooved terminating ends.
• 375A 21/2”, 3”, 4”, 6”, 8”, 10”
375
21/2”, 3”, 4”, 6”, 8”, 10”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves
• Complete with two flange-ended non-rising stem resilient wedge gate
valves and four resilient seated ball valve test cocks
• Lightweight, thin wall, epoxy-coated ductile iron
• Check components are made from lead-free engineered plastics and
stainless steel
• No threads or taps in body or cover, eliminating exposure to corrosion
• Single access cover reduces down time
• Relief valve located on bottom of valve with test cocks facing up –
Allows for easy installation and repair
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• ASSE® Listed 1013, UL® Classified, FM® Approved, AWWA Compliant,
C-UL® Classified, CSA® Certified (21/2” – 8”), IAPMO® Listed (21/2” – 8”)
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
(375ABGVIC 21/2” to 8”)
Model 375
Flanged body, NRS gate valves
Model 375AFG
Model 375A
Grooved body, with grooved by flanged NRS gate valves
Grooved body, with flanged inlet connection and
grooved outlet connection, NRS gate valves
Model 375L
Flanged body, less gate valves
Model 375FSC
Model 375AL
Grooved body, less gate valves
Same as 375 except supplied with an epoxy coated
flanged wye strainer
Model 375G
Flanged body, with flanged by grooved NRS gate valves
Model 375AFSC
Same as 375A except supplied with an Epoxy coated
flanged wye strainer
Model 375AG
Grooved body, with grooved by grooved NRS gate valves
Model 375PI
Flanged body supplied with post indicator valve
Model 375OSY
Flanged body, with flanged by flanged OS&Y gate valves
Model 375API
Grooved body supplied with post indicator valve.
Model 375AOSY
Grooved body, with grooved by flanged OS&Y gate
valves
Model 375OSYG
Flanged body, with flanged by grooved OS&Y gate valves
Options
Applications
Pat. No. 5,913,331
Features
Reduced Pressure Principle 375A/375 Series Model 375ABGVIC Grooved body, with grooved by grooved, tampered
Victaulic® butterfly valves
Model 375AOSYG Grooved body, with grooved by grooved OS&Y gate
valves


Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of
the unit can be submerged.
Typical Installation
Accessories
For Additional Information, reference WK-BPC catalog or visit
Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
MODEL 375ABGVIC
MODEL 375ABGVIC
AIR GAP
W/DRAIN
12" MIN.
30" MAX.
MODEL 375AFSC
MODEL 375AFSC
PROTECTIVE
ENCLOSURE
PROTECTIVE
ENCLOSURE
AIR GAP
W/DRAIN
12" MIN.
30" MAX.
12" MIN.
30" MAX.
12" MIN.
30" MAX.
DIRECTION OF FLOW
DIRECTION OF FLOW
DIRECTION OF FLOW
INDOOR INSTALLATION
X Ref
To create a part number to fit your needs, see page 3 for an example.
Flanged body, with flanged inlet connection and grooved our web site.
outlet connection, NRS gate valves
Model 375FG



Model 375ABGVIC
WILKINS 375
WATTS
994, 957
375FSC
OUTDOOR
INDOOR INSTALLATION
CONBRACO
4D-200
®
company
INSTALLATION
OUTDOOR INSTALLATION
FEBCO
AMES
860, 867 4000SS, 400 Maxim & Colt
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
DIRECTION OF FLOW
40
Backflow Preventers
Accessories
Options
Features
Applications
Reduced Pressure Principle 375MS/375AMS Pat. No. 5,425,393 and 5,913,331
Building on the superior characteristics of the 375A / 375 reduced pressure principle series is the
375AMS and 375MS. Provided with a monitor switch in the relief valve, the MS series, when connected to the proper electrical circuit, will provide confirmation that the relief valve is in a discharging condition. This is a highly useful configuration where the assembly may be installed in a remote
location, and the discharge could cause catastrophic water damage. The 375AMS and 375MS are
designed for high hazard application where preventing backpressure or backsiphonage is required.
• 21/2”, 3”, 4”, 6”, 8”, 10”
• Reduced pressure principle backflow prevention valve assembly with
Model 375AMSBGVIC
• In the event of a backflow condition, the relief valve closes an electrical
circuit, signaling that a possible relief valve discharge may be occurring
integral relief valve monitor switch
• Same features as the 375A
• Completely sealed UL® recognized proximity switch factory installed –
Normally open contacts, weather resistant housing and wiring leads
ready for immediate installation to appropriate electrical circuit
• Approved by the Foundation for Cross Connection Control and
Model 375MS/375AMS
Flanged NRS x flanged NRS with
RV monitor switch
Model 375MSFSC/375AMSFSC With epoxy coated wye type
strainer (flanged only)
Model 375MSG/375AMSG
With groove end gate valves
Model 375AMSBGVIC
Supplied with groove x groove
body and grooved, tampered
Victaulic® butterfly valves
Model 375MSFG/375AMSFG







Air gap (Model AG)
Thermal expansion tank (Model XT)
OS&Y gate valve supervisory switch (OSY-40)
Electronic solenoid timer (Model EST)
Hydraulic Research at the University of Southern California, ASSE®,
CSA® (375AMSBGVIC 21/2” – 8”)
• UL® listed, C-UL® listed, FM® Approved
With flanged inlet gate connection
and grooved outlet gate connection.
Model 375MSL/375AMSL
Less shut-off valves
Model 375MSOSY/375AMSOSY With OS&Y gate valves
For Additional Information, reference WK-BPC catalog or visit our
web site.
To create a part number to fit your needs, see page 3 for an
example
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Solenoid control valve (ZW106)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of
the unit can be submerged.
MODEL EST
MODEL 375MSOSY
Typical Installation
Electric
S olenoid
Timer
MODEL ZW106
12" MIN.
30" MAX.
375MS with ZW106 Solenoid Control Valve and EST
Electronic Solenoid Timer
Tech Support: 1-877-BACKFLO
www.zurn.com
®
41
a
®
company
Backflow Preventers
Features
Applications
Hydrant Backflow and Meter Combination RPHBM
The Wilkins RPHBM was designed to help water purveyors increase income through the accurate
measurement of water while protecting the potable water supply at the same time. Designed to
measure the quantity of water used in temporary installations such as connection to a fire hydrant,
RPHBM allows for rapid refill of water trucks used for job site dust abatement and soil compaction.
Equipped with 2 – 1/2” fire hydrant inlet, and a 2 – 1/2” fire hose outlet, the RPHBM can hit intermittent flow rates as high as 650 gpm in a short, light-weight package. The RPHBM is designed to
provide backpressure and backsiphonage protection where a health hazard exists, while allowing
the water purveyor to accurately determine that amount of water used for proper billing.
• 21/2” brass inlet swivel fitting for fast installation
• 3”
• Consists of a 3” hydrant meter and 3” check valves allowing for increased • Class II turbine-type meter ensures accurate measurement
flow up to 650 gpm as compared to 2" check valves with a capacity of
• Straightening vanes for accurate meter measurement
250 gpm
• Meets the requirements of ANSI/AWWA C701-88 class II
• Single body construction. Water meter plus reduced pressure principle
(for meter only)
backflow preventer encased in a single body design
• Max flow rate 650 gpm
• Unitized a lightweight exterior epoxy powder-coated (blue) hard-anod- • Min flow rate 21/ gpm
2
ized aluminum body design results in a short lay length (261/2") and light
• Maximum working pressure 175 psi
weight (54 lbs) product ideal for temporary installations
• Max temperature 140°F
• Integral inlet screen to protect against damage by larger debris
Accessories Options
• Lifting handles allow for quick installation to fire hydrant
• Includes adjustable support stand for positive support
RPHBM
2 1/2" FNH Swivel x 2 1/2" MNH
Many other options available, consult Wilkins.
RPHBMGV
Outlet slow closing shutoff valve
For Additional Information, Ask For RPHBM or visit our web site.
RPHBMCFM With cubic foot meter



Breakaway hydrant lock for barrel lock (BHLB)*
Breakaway hydrant lock for padlock (BHLP)*
Test cock lock (Model TCL24)
*Locks not included
MODEL RPHBM
Typical Installation
OPTIONAL GATE VALVE
(MODEL RPHBMGV)
BREAKAWAY HYDRANT LOCK FOR BARREL LOCK
(MODEL BHLB)
BREAKAWAY HYDRANT LOCK FOR PADLOCK
(MODEL BHLP)
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
42
Backflow Preventers
Applications
•
•
•
•
•
Accessories Options
The Wilkins 975XLHBM is designed to provide measurement of potable water from a temporary
connection such as a fire hydrant. The 975XLHBM protects against both backpressure and backsiphonage of contaminants while accurately metering the volume for proper water billing. This will
ensure that the water purveyor has a protected potable supply while also generating income due
to accurate metering and assembly rental. The 975XLHBM is equipped with 2 – 1/2” fire hydrant
inlet and 2 – 1/2” fire hose outlet and is capable of a maximum intermittent flow rate of 250 gpm.
Features
Hydrant Backflow and Meter Valve 975XLHBM
975XLHBM
975XLHBMCFM 975XLHBMCMM
975XLHBMLM


• Outlet shutoff valve allows for easy flow adjustment
• NSFHT adapters allow for connection to 21/2” fire hydrant (inlet) and
2”
Maximum working water pressure 175 psi
Maximum working water temperature 180°F
Hydrostatic test pressure 350 psi
Maximum flow rate of 250 gpm
21/2” fire hose (outlet)
• Meets the design requirements of most national standards. Due to the
portability of the assembly, there are no national approvals available
975XLHBML With US gal. register (standard)
With cu. ft. register
With cu. meter register
Less water meter and inlet hose connection
Less inlet and outlet hose connections
For Additional Information, Ask For 975XLHBM or visit our web
site.

Breakaway Hydrant Lock for barrel lock* (BHLB)
Breakaway Hydrant Lock for padlock* (BHLP)
Test cock lock (Model TCL24)
*Locks supplied by end user
Typical Installation
R
BREAKAWAY HYDRANT LOCK FOR BARREL LOCK
(MODEL BHLB)
TYPICAL INSTALLATION
MODEL 975XLHBM
HYDRANT BACKFLOW METER
BREAKAWAY HYDRANT LOCK FOR PADLOCK
(MODEL BHLP)
Tech Support: 1-877-BACKFLO
www.zurn.com
®
43
a
®
company
Need to Save Space, Reduce Costs & Save Time?
We’ve Got You Covered!
37.72
97
5
XL
W
IL
ZU KI
RN NS
Model 475
● Wilkins “N” pattern models reduce lay length by
as much as 80% and allow smaller enclosure
sizes saving additional dollars.
34.07
● When installed with a Valve Setter, Wilkins
“N” pattern models eliminate the need for two
elbows, two bolt packs, two valve support
stanchions, forms, cement, and labor for thrust
blocks and they use shorter spools.
12" MIN.
30" MAX.
(24" SHOWN)
GRADE
● With simplified installation, the “N” pattern is
easier to install, saving time & labor.
5'
● Like all Wilkins 300 & 400 Backflow Preventers,
the 400 “N” patterns allow better flow
characteristics and low maintenance costs.
● Models include Reduced Pressure (475),
RPDA (475DA), Double Check (450),
Double Check Detector (450DA)
Model 450DA
6
WILKINS
MJ X FLG
ZURN
Call a Wilkins Sales Representative Today!
18.70
Valve Setter
Customer Service Representatives available Monday through Friday 5:30 am to 5:00 pm PST.
Call: 877-222-5356 or 805-226-6297, [email protected] or visit us online at www.zurn.com
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
44
Backflow Preventers
The Wilkins 475 / 475V series reduced pressure principle assemblies are the perfect answer for cramped
installations that rule out a traditional horizontal valve. The 475, with its “N” pattern design, is the perfect
valve for use in retrofit applications where a horizontal valve will just not fit. The 475V allows for a vertical
up-up flows, and can be situated in very small closets or mechanical rooms. Both valves offer the low
head loss provided by the patented Wilkins Compound Check®, while providing high hazard protection
against both backsiphonage and backpressure. Using the valve setter, installation is simple and easy and
very cost-effective.
3” 475
• 21/2”, 3”, 4”, 6”, 8”, 10”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves
• Available in up/down (475) or up/up (475V) configuration
• Complete with two flange-ended non-rising stem full port grooved by
flanged end gate valves and four resilient seated ball valve test cocks
• Lightweight, ductile iron construction with FDA approved fusion epoxy
coat inside and out
• Utilizes a patented center-stem guided compound check™ closure
(Pat. No. 5,913,331)
475G
• Modular check design utilizing lead-free
engineered plastic (Noryl®) and stainless
steel
475VG
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• 21/2” and 3” sizes use 375 with 90° elbows
• ASSE® Listed 1013, UL® Classified, FM® Approved, C-UL® Classified,
IAPMO® Listed, CSA® Certified, AWWA Compliant
• Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California
Model 475
Flange x flange, NRS gate valves
Model 475VFG
Model 475L
Less gate valves (grooved body connections).
Model 475G
Grooved end NRS gate valves
Same as 475V except with flanged inlet NRS gate
connection and grooved outlet gate connection
(vertical configuration)
Model 475FG
Flanged inlet NRS gate connection and grooved
NRS outlet gate connection
Model 475VPI
Same as 475V except supplied with post
indicator gate valves
Model 475OSY
Flanged end OS&Y (outside stem and yoke) gate
valves. For fire protection applications
Model 475BGVIC
Supplied with groove x groove tampered
Victaulic® butterfly valve (4” – 8”)
Model 475OSYG
Grooved end OS&Y gate valves
Model 475PI
Supplied with post indicator gate valves
Model 475V
Vertical configuration (flow up)
Model 475VG
Same as 475V except with grooved end NRS gate
valves (vertical configuration)





Model 475VBGVIC Same as 475BGVIC except vertical configuration
(4” – 8”)
To create a part number to fit your needs, see page 3
For Additional Information, reference WK-BPC catalog or visit
our web site.




Air gap (Model AG)
Thermal expansion tank (Model XT)
Valve setter (Model FLS or MJS or MJFS)
OS&Y gate valve supervisory switch (OSY-40)
Soft seated check valve (Model 40XL)
Electronic Solenoid Timer (Model EST)
Solenoid control valve (ZW106)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a
minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for
testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
PROTECTIVE
ENCLOSURE
PROTECTIVE
ENCLOSURE
AIR GAP
12" MIN.
30" MAX.
12" MIN.
30" MAX.
WILKINS VALVE
SETTER
DIRECTION OF FLOW
Typical Installation
Accessories
Options
Features
Applications
Reduced Pressure Principle 475/475V Series Pat. No. 5,913,331
AIR GAP
DIRECTION OF FLOW
WILKINS VALVE
SETTER
AIR
GAP
DIRECTION OF FLOW
DRAIN
X Ref
MODEL 475G
WILKINS
475
475V
MODEL 475BGVIC
MODEL 475VG
FEBCO
880
880V
Tech Support: 1-877-BACKFLO
www.zurn.com
®
45
a
®
company
Backflow Preventers
Applications
Reduced Pressure Principle Detector Assembly
375ADA/375DA Series Pat. No. 5,913,331
When the fire protection professional demands a reduced pressure detection assembly with
low head loss and end connection flexibility, the Wilkins 375ADA / 375DA series RPDA's are
the preferred choice. Offered with either OS&Y or tamper switch equipped butterfly shut-off
valves, Wilkins make installation easier with the choice of grooved or flanged end connections. Designed to protect against high hazard backpressure or backsiphonage conditions in
unmetered fire lines, the 375ADA / 375DA Series provides low head loss with Wilkins patented
Compound Check®. In addition to low head loss, the ductile iron body provides low weight &
uncompromising strength for those challenging fire protection installations.
Typical Installation
Accessories
Options
Features
• 375ADA 4”, 6”, 8”, 10”
(375ADABGVIC shown)
375DA
21/2”, 3”, 4”, 6”, 8”, 10”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves, inlet and outlet flange-ended
OS&Y resilient wedge gate valves and four full port resilient seated test
cocks
• The by-pass assembly consists of a water meter in series with a reduced
pressure principle backflow preventer
• For use in fire line services
• Modular check design utilizing lead-free engineered plastic (Noryl®) and
stainless steel
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• Available with CFM water meter.
• ASSE® Listed 1047 375DA (4” – 8”), UL® Classified, FM® Approved,
C-UL® Classified
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
(375ADABGVIC 4” – 8”)
Model 375ADA
Flanged OS&Y x flanged OS&Y
Model 375DAL
Flanged body, less gate valves
Model 375ADAL
Grooved body, less gate valves
Model 375DAG
Model 375ADAG
Grooved body, with grooved X grooved
OS&Y gate valves
Flanged body, with flanged X grooved OS&Y
gate valves
Model 375DAPI
Model 375ADAFG
Grooved body, with flanged inlet OS&Y gate
valve and grooved outlet OS&Y gate valve
Flanged body supplied with post indicator
valve
CFM
With cubic feet meter
SCFM
With Sensus cubic feet meter
Model 375ADAPI
Grooved body supplied with Post Indicator
Valve
Model 375ADABGVIC Grooved body, with grooved by grooved
tampered Victaulic® butterfly valves
(21/2” – 8”)
To create a part number to fit your needs, see page 3.
For Additional Information, reference WK-BPC catalog or visit
our web site.
Model 375DA
Flanged OS&Y x flanged OS&Y gate valve
Model 375DAFG
Flanged body, with flanged inlet OS&Y gate
valve and grooved outlet OS&Y gate valve





Air gap (Model AG)
Thermal expansion tank (Model XT)
OS&Y gate valve supervisory switch (OSY-40)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturer’s instructions and the latest edition of the Uniform
Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
PROTECTIVE
ENCLOSURE
PROTECTIVE
ENCLOSURE
AIR GAP
W/DRAIN
12" MIN.
30" MAX.
12" MIN.
30" MAX.
AIR GAP
W/DRAIN
12" MIN.
30" MAX.
12" MIN.
30" MAX.
DIRECTION OF FLOW
DIRECTION OF FLOW
DIRECTION OF FLOW
DIRECTION OF FLOW
INDOOR
INSTALLATION
OUTDOOR
INSTALLATION
OUTDOOR
INSTALLATION
(MODEL
BGVIC
option)
INDOOR
INSTALLATION
(MODEL
375ADA with G option)
OUTDOOR INSTALLATION
(MODEL
375ADA with
BGVIC375ADA
option) with
INDOOR
INSTALLATION
(MODEL 375ADA
with
G option)
MODEL 375ADAG
X Ref
MODEL 375ADABGVIC
WILKINS 375DA
WATTS
994RPDA, 975RPDA
AMES
5000SS, 500 Maxim & Colt
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
46
Backflow Preventers
Reduced Pressure Principle Detector Assembly
475DA/DAV Series Pat. No. 5,913,331
Applications
• 4”, 6”, 8”, 10”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves
• Complete with two flange-ended OS&Y (grooved X flanged end) gate
valves (for fire protection applications) and four full port resilient seated
test cocks
• Available in up/down (475DA) or up/up (475DAV) configuration
• The by-pass assembly consists of a water meter in series with a reduced
pressure principle backflow preventer
• Lightweight, ductile iron construction with FDA approved fusion
epoxy coat inside and out
• Utilizes a patented center-stem-guided compound check™ closure
(Pat. No. 5,913,331)
• Modular check design utilizing lead-free engineered plastic (Noryl®)
and stainless steel
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• ASSE® Listed 1047 (4” – 8”), UL® Classified,
C-UL® Classified, FM approved (4” – 8”)
• Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California (sizes 4” – 8”)
Model 475DA
Flanged OS&Y x Flanged OS&Y
Model 475DAVFG
Model 475DABGVIC
Supplied with groove x groove, tampered
Victaulic® butterfly valves
Same as 475DAV except with flange by groove
inlet OS&Y gate valve and groove by groove
outlet OS&Y gate valve (vertical configuration)
Model 475DAFG
Flanged inlet OS&Y gate connections and
grooved outlet OS&Y gate connection
Model 475DAVG
Same as 475DAV except with groove by
groove OS&Y gate valves
Model 475DAG
Groove by groove OS&Y gate valves
Model 475DAVPI
Supplied with post indicator gate valves
Model 475DAL
Less OS&Y shutoffs (grooved body
connections)
CFM
With cubic feet meter
SCFM
With Sensus cubic feet meter
Options
Many fire suppression systems require their components to be installed in less than perfect locations.
Cramped closets and overflowing mechanical rooms do not leave much room for a traditional, horizontal
reduced pressure detector assembly. The 475DA and 475DAV were designed to solve this problem. The
475DA, with its “N” pattern design, and the 475DAV for vertical up-up flows provide compact backpressure
and backsiphonage protection in high hazard fire protection applications. The 475DA / 475DAV series
utilize the highly repeatable and low head loss generating Compound Check®, and are up to the challenge
that any high hazard fire suppression system may present.
Features
475DAG
Model 475DALM
Less water meter
Model 475DAPI
Supplied with post indicator gate valves
Model 475DAV
Same as 475DA but in vertical configuration
To create a part number to fit your needs, see page 3.
For Additional Information, reference WK-BPC catalog or visit
our web site.



Air gap (Model AG)
Thermal expansion tank (Model XT)
Valve setter (Model FLS or MJS or MJFS)
OS&Y gate valve supervisory switch (OSY-40)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
Typical Installation
Accessories
Model 475DAVBGVIC Same as 475DABGVIC but in vertical
configuration (4” – 8”)



475DAVG
AIR
GAP
AIR
GAP
AIR GAP
12" MIN.
30" MAX.
WILKINS VALVE
SETTER
MJFS
WILKINS VALVE
SETTER
MJFS
SUPPORT
SUPPORT
DRAIN
DRAIN
DIRECTION OF FLOW
MODEL 475DAV
12" MIN.
30" MAX.
AIR GAP
MODEL 475DAV
MODEL 475DA
DIRECTION OF FLOW
MODEL 475DA
Tech Support: 1-877-BACKFLO
www.zurn.com
®
47
a
®
company
Backflow Preventers
Accessories Options
Features
Applications
Dual Check Valve 700 Series
The Wilkins model 700 dual check is an economical way of providing backflow protection
against backpressure and backsiphonage in low hazard applications. The 700’s tubular design
houses two in-line checks and is available in several end connection configurations. The 700 is
perfectly suitable for providing isolation protection and is available in sizes of 1/4” to 1”.
• 1/4”, 3/8”, 1/2”, 3/4”, 1”
• Dual check valve backflow preventer consisting of two independently
•
•
•
•
•
operated in-line spring-loaded check valves
Bronze body construction
Corrosion-resistant internal parts
Includes two in-line cartridge check modules
Single union standard on inlet of all models
May be installed vertically or horizontally
Rough chrome finish available
BSP threads available on some models
Maximum temperature 180°F
Maximum pressure 175 psi
ASSE® Listed 1024, CSA® Certified
Consult your local Wilkins representative or factory for additional
configurations
700
FNPT (female) threaded union inlet connection (standard)
700FM FMTC (female) meter thread union inlet connection
700C
FC (female) copper sweat union inlet connection
700M
MNPT (male) threaded union inlet connection
700DU Union meter inlet and union outlet.
For Additional Information, reference WK-BPC catalog or visit
our web site.


700CM CM (male) copper sweat union inlet connection
Thermal expansion tank (Model XT)
Shut-off valve with integral thermal expansion relief valve
(Model BVEC)
FEMALE UNION "COPPER SWEAT" INLET X MALE
MALE UNION INLET X MALE OUTLET
FEMALE UNION INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
INLET (UNION)
OUTLET
PART NUMBER
INLET (UNION)
OUTLET
PART NUMBER
1" MNPT
1" MNPT
1UMX1M-700
3/4" FC
3/4" MNPT
34UFCX34M-700
1/4" FNPT
1/4" FNPT
14UFX14F-700
3/4" FC
1" MNPT
34UFCX1M-700
3/8" FNPT
3/8" FNPT
38UFX38F-700
1" FC
1" MNPT
1UFCX1M-700
1/2" FNPT
1/2" FNPT
12UFX12F-700
1/2" FC
1/2" FC
12UFCX12FC-700
FEMALE UNION INLET X MALE OUTLET
OUTLET
3/4" FNPT
3/4" MNPT
34UFX34M-700
3/4" FNPT
3/4" MMTC
34UFX34MM-700
3/4" FMTC
3/4" MNPT
34UFMX34M-700
3/4" FMTC
3/4" MMTC
34UFMX34MM-700
3/4" FNPT
1" MMTC
34UFX1MM-700
3/4" FMTC
1" MNPT
34UFMX1M-700
1" FNPT
1" MNPT
1UFX1M-700
1" FNPT
1" MMTC
1UFX1MM-700
1" FMTC
1" MNPT
1UFMX1M-700
1" FMTC
1" MMTC
1UFMX1MM-700
1" FNPT
3/4" MNPT
1UFX34M-700
1" FNPT
3/4" MMTC
1UFX34MM-700
Configurations
INLET (UNION)
PART NUMBER
1" FMTC
3/4" MNPT
1UFMX34M-700
1" FMTC
3/4" MMTC
1UFMX34MM-700
FEMALE UNION INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
3/4" FNPT
3/4" FNPT
34UFX34F-700
3/4" FMTC
3/4" FNPT
34UFMX34F-700
1" FNPT
1" FNPT
1UFX1F-700
1" FNPT
3/4" FNPT
1UFX34F-700
1" FMTC
1" FNPT
1UFMX1F-700
1" FMTC
3/4" FNPT
1UFMX34F-700
FEMALE UNION INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
1/4" FNPT
1/4" FNPT
14UFX14F-700
3/8" FNPT
3/8" FNPT
38UFX38F-700
1/2" FNPT
1/2" FNPT
12UFX12FC-700
1/2" FC
1/2" FC
12UFCX12FC-700
FEMALE UNION "COPPER SWEAT" INLET X FEMALE
FEMALE "METER UNION INLET X FEMALE UNION
INLET (UNION) OUTLET (UNION)
INLET (UNION)
OUTLET
PART NUMBER
PART NUMBER
3/4" FC
3/4" FNPT
34UFCX34F-700
34UFCX1F-700
FEMALE "METER" UNION INLET X MALE UNION
1" FMTC
3/4" FNPT
1UFMX34UF-700
3/4" FC
1" FNPT
INLET (UNION) OUTLET (UNION) PART NUMBER
1" FMTC
1" FNPT
1UFMX1UF-700
1" FC
1" FNPT
1UFCX1F-700
1" FMTC
1" FMTC
1UFMX1UFM-700
1" FC
3/4" FNPT
1UFCX34F-700
1" FMTC
X Ref
•
•
•
•
•
•
1" MNPT
WILKINS 700
1UFMX1UM-700
WATTS
7,7C, CU7
CONBRACO
40-300, 4N-300
FEBCO
510
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
AMES
20, CU20
48
Backflow Preventers
Configurations
Accessories Options
Features
Applications
Dual Check Valve 705 Series
The Wilkins model 705, with its lead free construction is the perfect valve to be used to protect against low hazard backpressure or backsiphonage in drinking water systems. Like the
model 700, the 705’s tubular design houses two in-line check valves and is a suitable valve
for providing isolation protection. The Wilkins 705 is one of the most economical ways of
preventing backflow.
• 3/4”, 1”
• Dual check valve backflow preventer consisting of two independently
operated in-line spring-loaded check valves
• Lead-free composite body construction
• Corrosion-resistant internal parts
• Includes two in-line cartridge check modules
• Single union standard on inlet of all models
•
•
•
•
•
•
•
705
FNPT (female) threaded union inlet connection (standard)
705FM FMTC (female) meter thread union inlet connection
705C
FC (female) copper sweat union inlet connection
705M
May be installed vertically or horizontally
BSP threads available on some models
Maximum temperature 180°F
Maximum pressure 175 psi
ASSE® Listed 1024, CSA® Certified
California AB 1953 compliant
Consult your local Wilkins representative or factory for additional configurations
MNPT (male) threaded union inlet connection
705CM CM (male) copper sweat union inlet connection
For Additional Information, reference WK-BPC catalog or visit
our web site.


Thermal expansion tank (Model XT)
FEMALE UNION INLET X FEMALE OUTLET
Shut-off valve with integral thermal expansion relief valve
(Model BVEC)
FEMALE UNION "COPPER SWEAT" INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
INLET (UNION)
OUTLET
PART NUMBER
3/4" FNPT
3/4" FNPT
34UFX34F-705
3/4" FC
3/4" FNPT
34UFCX34F-705
3/4" FMTC
3/4" FNPT
34UFMX34F-705
3/4" FC
1" FNPT
34UFCX1F-705
1" FNPT
1" FNPT
1UFX1F-705
1" FC
1" FNPT
1UFCX1F-705
1" FNPT
3/4" FNPT
1UFX34F-705
1" FC
3/4" FNPT
1UFCX34F-705
1" FMTC
1" FNPT
1UFMX1F-705
1" FMTC
3/4" FNPT
1UFMX34F-705
MALE UNION INLET X FEMALE OUTLET
INLET (UNION)
OUTLET
PART NUMBER
1" MNPT
1" FNPT
1UMX1F-705
Local codes shall govern installation requirements. To be installed in accordance with the manufacturer’s instructions and the latest edition of the
Uniform Plumbing Code. Unless otherwise specified, the Model 705 shall be mounted with sufficient side clearance for maintenance.
Typical Installation
WATER METER
MODEL 705
WATER METER
METER SETTER
MODEL 705
METER SETTER INSTALLATION
PIT INSTALLATION
Tech Support: 1-877-BACKFLO
www.zurn.com
®
49
a
®
company
Backflow Preventers
Accessories Options
Features
Applications
Dual Check Valve 950LF Series
In order to answer the need of the fire sprinkler installer, Wilkins introduced the 950LF dual check
for use in residential and commercial, small scale fire protection systems. Equipped with female
end connections, the 950LF lends itself to rapid, easy installation. All of the internal components
are the same used in the 950XL, so you are assured that the 950LF will provide excellent low hazard protection against both backpressure and backsiphonage.
• 3/4”, 1”, 11/4”, 11/2”, 2”
• Dual check valve backflow preventer consisting of two independently
•
•
•
•
•
operated spring-loaded center guided check valves in wye pattern
Designed for fire sprinkler systems
Bronze body construction
Female NPT inlet and outlet connections
Complete with three resilient seated ball valve test cocks
Entire unit serviceable in line
Model 950LF
FNPT x FNPT end connections
Model 950LLF
Less test cocks

•
•
•
•
Temperature range 33°F – 180°F
Maximum pressure 175 psi
Shut-off valve option available
ASSE® Listed 1024 (horizontal/vertical), CSA® Certified (horizontal/vertical), UL® Classified as to friction loss and body strength only, C-UL® Classified (horizontal)
• Complies with NFPA 13D for flow requirements to residential fire sprinklers (3 heads)
For Additional Information, reference WK-BPC catalog or visit
our web site.
Quick test set (QT-SET)
DIRECTION OF FLOW
Typical Installation
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform
Plumbing Code. Unless otherwise specified, shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drain and
sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
BALL VALVE
MODEL BVMS
MODEL 950LF
MODEL 950LF
BALL VALVE
MODEL BVMS
DIRECTION OF FLOW
TYPICAL VERTICAL INSTALLATION
TYPICAL HORIZONTAL INSTALLATION
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
50
Backflow Preventers
Accessories Options
Features
Applications
Dual Check with Atmospheric Vent 760 Series
Designed for installation on boiler fill water lines to protect against both backsiphonage
and backpressure of polluted water into the potable water supply. Assembly shall provide
protection where a potential health hazard does not exist.
• 1/2”, 3/4”
• Continuous pressure type backflow preventer with threaded
atmospheric vent drain
• Consists of two independently operated spring-loaded check valves with
intermediate atmospheric vent
• Brass body construction
• Integral stainless steel screen
• Corrosion-resistant internal parts
• Union connections both ends; available with FNPT or copper connections
• Temperature range 33°F – 210°F
• Maximum pressure 175 psi
• ASSE® Listed 1012, CSA® Certified
Model 760
Model 760C
FNPT x FNPT end connections
Same as 760 except with female copper sweat
connection
Model 876CI Model 876
Model 80BR fast fill regulator combined with
Model 760 dual check backflow preventer with
atmospheric vent
For Additional Information, reference WK-BPC catalog or visit
our web site.



Fast fill regulator (80CI & 80BR)
Hydronic expansion tank (HXT)
Model 80CI (cast iron) fast fill regulator combined
with Model 760 dual check backflow preventer
with atmospheric vent
Pressure relief valve (P1000A or P300BR)
Under certain conditions, the Model 760 will spill water from the vent port. WARNING: Provisions must be made to collect this spillage through an
air gap or other means. The vent port should never be directly piped into a drainage ditch, sewer or pump. Under no circumstances should the vent
port or drain line be plugged. Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. The installation shall be made so that no part of the unit can be submerged.
MODEL 80CI or 80BR
FAST FILL VALVE
MODEL P1000A
PRESSURE RELIEF VALVE
MODEL 760
Typical Installation
OUTLET
INLET SHUT-OFF
MODEL 850
WILKINS
BOILER
RETURN
DRAIN
X Ref
DIRECTION OF FLOW
WILKINS WATTS
760
9D
CONBRACO
40-400
FEBCO
815
CASH-ACME
BFP
Tech Support: 1-877-BACKFLO
www.zurn.com
®
51
a
®
company
Backflow Preventers
Features
Applications
Backflow Preventer for Vending Machine Water Supply
Model 740
Designed for installation on carbonated beverage dispensing systems, as well as non-carbonated systems, to prevent carbon dioxide (CO ) gas or carbonated water from coming in contact
with copper potable water supply line. The 740’s stainless steel construction ensures superior
corrosion resistance for increased longevity.
• 3/4”
• SAE J513 flare fitting threads inlet and outlet
• Designed for installation in vending machine water supply lines to prevent backflow of carbon dioxide and carbonated water into the potable
supply
• Pressure rated to 150 psi
• Maximum temperature 130°F
• Consists of two spring loaded check valves with an atmospheric vent
located between the two checks
• Quick acting check valves prevent unnecessary vent discharge
The Model Model
740 can
740be installed in the horizontal or
vertical position.
Under
certain conditions the Model
Backflow
Preventer
740 may discharge water from the vent port. Provisions
must be made to ensure that discharge will not damage
surrounding property or equipment. Copper tubing shall
not be used downstream of the Model 740.
•
•
•
•
Manufactured with 300 series stainless steel
Silicon rubber check valve discs
Stainless steel springs
Stainless steel strainer screen provided on the inlet to prevent check
fouling due to debris in the supply water line
• ASSE® Listed 1022
• California AB 1953 compliant
For Additional Information, reference WK-BPC catalog or visit
our web site.
Model 740
Backflow Preventer
Water
Supply
Filter
Carbonator
Pump
Beverage
Carbonated
Beverage
Dispenser
CO2
Gas
Typical Installation
Dispenser
Safe DrainModel
740
Backflow Preventer
Model 740
Backflow Preventer
Safe Drain
CarbonatedWater
Beverage System
Carbonated Beverage System
Supply
Water
Supply
Filter
Pump
Beverage
Carbonator
CO2
Gas
Dispenser
Safe Drain
Safe Drain
X Ref
Non-Carbonated Beverage System
WILKINS 740
WATTS
SD-3, 9BD
Carbonated Beverage System
CONBRACO
4C-100
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
®
company
52
Carb
Beve
Disp
Backflow Preventers
Typical Installation
Accessories Options Features
Applications
Stainless Steel Reduced Pressure Principle 975XLST
Designed for installation on potable water lines to protect against both backsiphonage and
backpressure of contaminated water into the potable water supply. The Model 975XLST
provides protection where a potential health hazard exists. The valve’s stainless steel
construction is ideal in those systems that utilize liquids corrosive to copper alloys. Potential
applications include: medical diagnostic equipment, food processing, distilleries and breweries. Additionally, the 975XLST is ideal for applications requiring valves that are lead free.
3/8”, 1/2”
Stainless steel reduced pressure principle backflow prevention assembly
Ideal for systems that use liquids that are corrosive to copper alloys
Check components are made from lead-free engineered plastics (Noryl®)
and stainless steel
• Full port ball valves (standard)
•
•
•
•
Model 975XLST
Model 975XLSTL
For Additional Information, reference WK-BPC catalog or visit
our web site.
•
•
•
•


FNPT x FNPT end connections
Less shut-off valves
Maximum working water pressure 175 psi
Maximum working water temperature 180°F
ASSE® Listed 1013
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
• California AB 1953 compliant


Air gap (Model AG)
Quick test set (QT-SET)
Local codes shall govern installation requirements. To be installed
in accordance with the manufacturers’ instructions and the
latest edition of the Uniform Plumbing Code. Unless otherwise
specified, the assembly shall be mounted at a minimum of 12”
(305mm) and a maximum of 30” (762mm) above adequate
drains with sufficient side clearance for testing and maintenance.
The installation shall be made so that no part of the unit can be
submerged or where relief valve discharge could cause damage.
Test cock lock (Model TCL24)
Thermal expansion tank (Model XT)
MODEL 975XLST
AIR GAP
MODEL AG
12" MIN.
30" MAX.
DRAIN
X Ref
DIRECTION OF FLOW.
WILKINS 975XLST
WATTS
SS009
CONBRACO
40-200-T2S
Tech Support: 1-877-BACKFLO
www.zurn.com
®
53
a
®
company
Backflow Preventers
Options
Features
Applications
In-Line Single Check Valve 40XL Series
Designed for installation on potable domestic and commercial water systems such as well pump
systems and applications requiring tight seating. For use as a positive backstop to eliminate reduced
pressure principle backflow preventer discharge caused by pressure fluctuations or water hammer.
Its low-lead design makes the model 40XL perfectly suitable for drinking water applications.
• 1/4”, 3/8", 1/2", 3/4", 1", 11/4”, 11/2”, 2”, 21/2”, 3", 4”
• Can be used to help eliminate reduced pressure backflow preventer
supply pressure fluctuations or downstream water hammer conditions
• Soft seated slow closing check design
• Brass body construction
• Polyetherimide poppet and NBR rubber seat gasket
Model 40XL
FNPT x FNPT end connections
Model 40XLHT
with Viton® seal, 125 PSI steam rating,
Temperature: 366°F
®
company
Female NPT inlet and outlet connections
Stainless steel spring
May be installed in any position
Rated at 200 psi, [email protected]°F
• NFS® Standard 61 Certified
• California AB 1953 compliant
For Additional Information, reference WK-BPC catalog or visit
our web site.
Tech Support: 1-877-BACKFLO
www.zurn.com
®
a
•
•
•
•
54
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project