DS DALI USB en
luxCONTROL lighting control system
comfortDIM
DALI USB
PC interface module for DALI systems
Product description
•Interface module from USB to a DALI system
•For connecting Tridonic software tools
•Addressing, programming and parametrising DALI installations and
Tridonic devices
•Power supply via DALI line and USB interface
•5-year guarantee
È
Wiring diagrams and installation examples, page 3
Data sheet 01/16-CO058-5
Subject to change without notice.
www.tridonic.com
1
luxCONTROL lighting control system
comfortDIM
DALI USB
PC interface module for DALI systems
Technical data
Supply via
DALI cable and USB interface
Current draw
6 mA from DALI
Input
1 USB (Personal Computer)
Output
DALI
Ambient temperature ta
0 ... +50 °C
Type of protection
IP20
Ordering data
Type
Article number
Packaging, carton
DALI USB
24138923
50 pc(s).
Data sheet 01/16-CO058-5
Subject to change without notice.
www.tridonic.com
2
luxCONTROL lighting control system
comfortDIM
DALI standard
The DALI USB is designed to control control gear
with DALI standard IEC 60929 (DALI V0) and IEC
62386 (DALI V1).
Glow-wire test
according to EN 60598-1 passed.
The interface module DALI USB is used to connect
Personal Computers directly to the DALI network.
This means that complex DALI lighting control
solutions can be easily addressed and programmed
and that the parameters of the ballasts can be
changed.
Attention
The DALI USB cannot be used together
with winDIM.
Wiring
L
N
N L
PCA EXCEL
one4all
DALI
PS
PCA EXCEL
one4all
DA / D1
DA / D2
DA DA
DA / D1
DA / D2
DALI
DALI
GC
DALI
GC
DALI
SC
DALI
USB
DALI
TOUCHPANEL
DALI
DALI
DALI
DALI USB
Connection diagram
Note
The connection to the DALI-line is polarity free.
230 V on the DALI-line can destroy DALI USB!
Wiring type and cross section
The wiring can be in stranded wires with ferrules or solid. For perfect function
of the cage clamp terminals the strip length should be 4 – 5 mm for the input
terminal.
The max. torque at the clamping screw (M3) is 0.2 Nm.
To get a proper working strain relief it is recommended that the cable jacket
diameter of the side D2 is 2 mm bigger than the diameter of the side D1. (This
can vary if the used cable jacket material varies from side D2 to D1 in pinching
property).
Side D2
0,5 – 2,5
max. ∅ = 8,0 mm
min. ∅ = 4,0 mm
PRESS
4–5
max. ∅ = 6,0 mm
min. ∅ = 2,0 mm
4–5
Data sheet 01/16-CO058-5
Subject to change without notice.
D2
0,5 – 2,5
D1
Side D1
www.tridonic.com
3