Quick guide to Danvent DV

Quick guide to Danvent DV
Fans | Air Handling Units | Air Distribution Products | Air Conditioning | Fire Safety | Air Curtains and Heating Products | Tunnel Fans
Air Handling Units
Quick Guide to Danvent DV
Den Blå Planet, National Aquarium Denmark
Danvent DV Modular Air Handling Unit
Airflow 0,2-24 m3/s, 750-86.000 m3/h
Facts about Danvent DV
•1
4 sizes with airflows from 0,2-24 m3/s, 750-86.000 m3/h
•W
ith rotary heat exchanger, counter flow exchanger
or run-around coil exchangers
• With EC motor IE4, PM motor IE4 or AC motor IE2
• Plug fan
• With or without supply air, extract air, or mixing damper
• Filter classes: G4, M5, M6, F7, F8, F9 or F7 City-Flo
• With water heating coil, electric heating coil and/or cooling coil
• Can be supplied with integrated heat pump DVU-HP
• Can be supplied with humidifier/adiabatic cooling DVX
• With or without control system
• For indoor or outdoor installation
AHU No 07.02.339
DANVENT DV 10-240, TIME 10-40
Danvent DV is designed as a modular air
handling unit. The modular functions can
be configured for many different applications to make up the heart of any
ventilation system.
The flexibility makes it possible to
optimize the air handling unit for
each project.
Danvent DV is dimensioned in the design
programme SystemairCAD. SystemairCAD
makes it possible to combine air handling
unit functions as required very quickly
and easily.
4
|
Quick Guide to Danvent DV
1
2
4
5
7
6
3
The unit casing 1
The unit casing consists of a strong
frame construction with sound and
heat insulated panels. The frame
consists of a closed 1,3/1,5 mm
steel profile with surface of alu-zinc
AZ185 for corrosion protection. The
corners are die-cast and painted aluminum corners. The panels are also
corrosion protected with alu-zinc
AZ185 and consist of a sandwich
construction with two 0,8 mm steel
sheets and 50 mm mineral wool. The
unit sections are assembled with an
assembly bracket; Disc-Lock. Large
inspection doors provide easy access
for service and maintenance. It is
possible to lift off the doors, if needed. The doors are provided with lockable handles.
Plug fan DVE 2
The plug fan DVE has the impeller
fitted direct to the motor shaft and is
built into a soundproof unit casing.
The fan is a single inlet, free-blowing
fan where the unit casing acts as fan
housing. DVE has an efficiency of up
to 75% and a low noise level. On
large units, twin fans for parallel
operation are built-in. DVE can be
supplied with EC motor (IE4) in
Danvent DV 10-40, PM motor (IE4)
or AC motor (IE2). Fan impeller and
motor are statically and dynamically
balanced. Motor and fan are mounted on a sturdy frame, which is placed
on rubber vibration isolators, and the
fan inlet is connected to the unit with
a flexible connection.
Heat exchangers 3
The rotary heat exchanger DVC is
supplied in 3 types: Standard, enthalpy and sorption heat exchangers.
Generally, the rotary heat exchanger
has a high efficiency from 75% to
87% depending on operating conditions. It can recover moisture and is
the heat exchanger that requires the
least space. The enthalpy exchanger
recovers more moisture, and therefore contributes to the humidification
of the supply air. The sorption
exchanger dehumidifies the air more,
making it particularly suitable for
dehumidifying the outdoor air, for
example before cooling.
The plate heat exchanger DVQ is supplied in 3 types: Standard, high efficiency and counter flow heat
exchangers. Generally, the plate heat
exchanger has a high efficiency. It has
separated airflows, and thus the
transfer of odors to the supply air is
avoided. There is no transfer of moisture between the two airflows, and
so it can also be used for dehumidification. The standard cross flow
exchanger has an efficiency of up to
65%. The high efficiency cross flow
exchanger has an efficiency of up to
75%. These two types are supplied in
two variants: One made of aluminium
for comfort and one made of corrosion-resistant plastic-coated aluminium for aggressive environments. The
counter flow exchanger has an efficiency of up to 90% and is supplied
only in aluminium. The heat exchangers are fitted with by-pass for capacity control and have a built-in drip tray.
Quick Guide to Danvent DV |
Functions
The run-around coil heat exchanger
DVR has an efficiency of up to 70%
and is used, where the two airflows
must be kept completely separate, or
where the airflows are at a distance
from each other. For example on 2
different storeys. The DVR is a heat
exchanger system with circulating
water-glycol brine between the supply air heating coil and extract air
cooling coil. The transfer of energy is
done through a pipe system. Capacity
regulation is done through a shunt
system and a motor valve or by controlling the circulation pump.
Coils 4
The heating coil DVH is used for heating the supply air. The heating can be
effected by hot water or condensation of refrigerant. These coils consist
of copper tubes and aluminum fins.
Heating can also be affected with
electricity. These coils consist of heating elements of stainless steel and
have built-in safety control system. In
the standard version the coils are
built into the unit. More variants and
options are possible.
The cooling coil DVK is used for cooling the supply air. It can be effected
by cold water or direct evaporative
refrigerant. A cooling coil for evaporation has the liquid distributor
placed in the unit. These coils consist
of copper tubes and aluminum fins.
In the standard version, the coils are
built into the unit. More variants and
options are possible.
The change-over battery DVHK is
basically a cooling coil for cold water,
which can also be used for heating by
changing the water temperature from
cold to warm as required. Typically
used in connection with heat pumps.
Heat pump DVU-HP 5
The DVU-HP is an integrated reversible heat pump system built into a
unit section. The system consists of a
reversible heat pump and a rotary
heat exchanger that enables both
heating and cooling. The DVU-HP can
be supplied for Danvent DV 10 to 80.
The unit is equipped with 2 scroll
compressors (1 compressor for the
two smallest sizes DV 10 and DV 15),
and cooling/heating capacity is stepless variable in the range 5-100%.
The heat pump is based on R-410A
refrigerant. The DVU-HP is equipped
with a complete control system
which can communicate both with
Systemair Corrigo control system and
other control systems. Tested and
ready for operation from the factory.
Humidifier DVX
The humidifier is made as a complete
unit, which includes humidification
elements, tray and frame made of
stainless steel AISI 304, circulation
pump, irrigation regulation valves,
overflow, bleed-off regulation valve,
float valve for controlling the water
supply to the tray and valve for emptying the tray. The HU-CELL humidification elements are stainless steel
frames which contains corrugated
fiberglass plates arranged in crosschannel configuration. The function
of the humidifier is based on the
natural process that water evaporates when air passes a wet surface.
The humidifier can either be placed
in the supply air after a heating coil
or used as indirect adiabatic cooling
by placing it in the extract air before
a heat exchanger.
Damper 6
The dampers comply with tightness
class 3 according to EN 1751:2014.
The dampers have counter rotating
aerodynamically shaped damper
blades made of aluminium, which
ensures a low pressure loss when
open. The blades are equipped with
tight-fitting, rubber sealings, and are
mounted on sturdy, square shafts and
service-free, synthetic bearings. The
connection between the blades is a
rod drive located outside the airflow.
The bearings in the pivoting system
are made of brass. The blades can be
supplied insulated and/or anodized.
The following types of dampers can
be supplied: DVA shutoff damper with
horizontal connection, DVB shutoff
damper with vertical connection, DVM
mixing damper with 2 built-in dampers, DVP mixing damper with 3 builtin dampers. All dampers are equipped
with position indicator and are prepared for internal damper motor.
Filter 7
The compact filter DVG is a basic filter
class G4 according to EN779:2012 with
a short building length. It is designed
on pleated filter principle. The DVG can
be used as pre-filter and thereby
extend the life of the main filter.
5
6
|
Quick Guide to Danvent DV
Functions
The bag filter DVF is a bag filter,
whose design provides a large filter
area. DVF has a long lifetime and
thus good overall economy. DVF can
be supplied in the filter classes G4,
M5, M6, F7, F8, F9 og F7 City-Flo
according to EN 779:2012. F7 CityFlo is a filter with particle and molecular filtration specially designed for
use in urban areas and areas with
heavy traffic. The filter cells are fixed
with a simple but effective fixing
system of transverse locking rails
which can easily be activated using a
large handle. This ensures that the
filter cells are tight and meet tightness requirement according to
EN 1886:2008.
Sound attenuator DVD
The sound attenuator DVD is an
absorption attenuator with baffles.
DVD is used to reduce the sound
power level from the air handling unit
to the duct system. The baffles have
a surface coating which prevents the
entrainment of the sound absorbing
material. The surface coating is available in two variants: A standard lining, which is a hard wear-resistant
material where the baffles can be
cleaned by dry cleaning. As well as a
variant with a synthetic lining suitable
for wet cleaning. This variant is
selected for hygienic reasons.
Roof unit DV
Danvent DV 10-150 can be supplied
as a roof unit for outdoor installation.
In this version, the unit is supplied
assembled on a base frame. You can
select between 2 different roof
coverings: Bitumen roof, which consists of strong polyester reinforced
bitumen material. Supplied finished
from the factory. Steel profile roof,
which consists of trapezoidal alu-zinc
coated steel sheets, as well as profiles for the attachment and termination of the roof panels. Supplied for
on-site installation. Air intake and
exhaust can be supplied with louvers.
Inspection and empty
section DVI and DVO
Installation of an inspection and an
empty section DVI and DVO is possible.
Outdoor air section DVY allows for
exhaust of extract air at the rear of
the unit.
Danvent DV airflows
1000
1500
2000
3000
5000
10000
20000
30000
50000
90000 m3/h
240
190
150
120
100
80
60
50
40
30
25
20
15
10
0,2
0,4
0,7
1
2
3
Indicates airflow range at the shown combination examples with heat recovery and by
specific fan power 2,1 kW/(m3/s). The exact values are calculated by SystemairCAD.
Indicates airflow range for the unit size.
5
10
Kombination C1E
Combination
C1E
15
20
25 m3/s
Kombination Q1E
Combination
Q1E
Automatik
Control
System Corrigo
Danvent DV can be supplied with a pre-assembled and fully tested control
system. The control system is a user-friendly system, where functions
and parameters are selected from the external control panel. The control
panel can be positioned freely and used as a remote control. The most
important operating data are continuously displayed on the control panel
display, including alarms, operating values, operating status and time
settings. Commissioning is simplified, as the control system is preloaded
with temperatures, time settings and control sequences. The settings can
easily be changed if desired.
Functions:
• Weekly clock.
• Select between:
• T emperature control: Cascade room control, fixed supply air temperature, outdoor compensated supply air temperature, outdoor temperature dependent change between room control and supply air control.
•A
irflow control: 2 fixed airflows, constant duct pressure (VAV),
constant duct pressure with extract air as slave.
• Extended operation.
• Free night cooling.
• Cooling recovery.
• Filter guard for supply and extract air.
• Alarm and safety functions.
• Readout of fan data: Airflow and pressure.
• Water heating coil, control and frost protection.
•E
lectric heating coil, modulating with protection
against overheating as well as control.
• Cooling coil, control.
• Run-around coil heat exchangers, control.
• Recirculation.
• Heating and cooling valves incl. actuator.
• Control/communication of DVU-HP heat pump.
• Supply air and extract air dampers as well as damper motors.
• External fire signal.
• Co2/temperature control.
• Humidity control.
BMS communication configured via the control panel:
• Integrated BACnet IP or MS/TP.
• Integrated Modbus RTU via RS485 or TCP/IP.
• Updated WEB master standard.
• LON is possible.
8
|
Quick Guide to Danvent DV
Combination Examples
Unit size
Rotary heat exchanger
10
15
20
25
30
40
50
60
80
100
120
150
190
240
Unit
Width
970
1120
1270
1420
1570
1720
2020
2170
2170
2370
2590
2890
3190
3490
Rotary heat exchanger section
Width
-
-
-
-
-
-
-
-
2320
2520
2890
3040
3720
4020
Unit
Height*
970
1120
1270
1420
1570
1720
2020
2240
2540
2840
3140
3440
4340
4940
C1E
Length
2160
2160
2460
2460
2760
3060
2910
3280
3210
3960
4260
4560
5010
5530
430
520
660
760
920
1100
1470
1980
2140
2630
3250
3990
6290
7610
2910
2910
3210
3210
3510
3810
3660
4030
4030
4930
5230
5530
5980
6430
500
610
770
870
1080
1270
1690
2250
2470
3050
3890
4690
7220
8600
2680
2680
3130
3130
3430
3880
4030
4400
4400
5450
5900
6200
6430
7100
480
580
730
810
1010
1220
1700
2230
2480
3160
3870
4660
6870
8280
3430
3430
3880
3880
4180
4630
4780
5220
5220
6420
7020
7170
7400
8000
Weight kg
C2E
Length
Weight kg
C3E
Length
Weight kg
C4E
Length
C5E
Length
Weight kg
Weight kg
C6E
Length
Weight kg
560
660
840
930
1180
1390
1930
2560
2830
3610
4560
5320
7790
9180
2680
2680
3130
3130
3430
3880
3730
4100
4100
5080
5380
5680
6430
7100
480
570
720
800
1010
1220
1630
2120
2330
2970
3620
4390
6860
8280
3430
3430
3880
3880
4180
4630
4480
4850
4850
6050
6350
6650
7400
8000
550
660
840
920
1180
1380
1850
2410
2670
3370
4280
5060
7790
9170
The above dimensions and weights are a guideline only. Accurate values and combinations are calculated in SystemairCAD.
* Height excl. legs/base frame. The heights of DV 190 and 240 are incl. base frames.
Unit size
Plate heat exchanger
Counter flow heat exchanger
10
15
20
25
30
40
50
970
1120
1270
1420
1570
1720
2020
Height*
970
1120
1270
1420
1570
1720
2020
Length
3280
3430
3880
3880
4480
4780
4930
570
700
874
1003
1296
1508
2084
3890
4180
4630
4630
5230
5530
5680
660
790
1000
1140
1470
1680
2310
3730
3950
4550
4550
5150
5600
5750
650
760
970
1020
1400
1630
2270
4480
4700
5300
5300
5900
6350
6500
720
840
1080
1190
1560
1800
2510
3730
3950
4550
4550
5150
5600
5750
640
750
960
1050
1410
1450
2250
4480
4700
5300
5300
5900
6350
6500
720
840
1080
1180
1550
1790
2490
Unit
Width
Unit
Q1E
Weight kg
Q2E
Length
Weight kg
Q3E
Length
Weight kg
Q4E
Length
Weight kg
Q5E
Length
Weight kg
Q6E
Length
Weight kg
The above dimensions and weights are a guideline only. Accurate values and combinations are
calculated in SystemairCAD.* Height excl. legs/base frame.
Quick Guide to Danvent DV |
Unit size
Plate heat exchanger
Cross-flow exchanger
10
15
20
25
30
40
50
60
80
100
120
150
Unit
Width
970
1120
1270
1420
1570
1720
2020
2170
2170
2370
2590
2890
Unit
Height*
970
1120
1270
1420
1570
1720
2020
2240
2540
2840
3140
3440
Q1E
Length
3210
3580
4030
4330
4780
5080
5230
5460
5230
5910
6960
7260
570
760
940
1130
1370
1640
2300
2550
2610
3210
4200
5130
3960
4330
4780
5080
5530
5830
5980
6210
5980
6880
7930
8230
Weight kg
Q2E
Length
Q3E
Length
Weight kg
Weight kg
Q4E
Length
Weight kg
Q5E
Length
Weight kg
Q6E
Length
Weight kg
660
850
1060
1260
1540
1810
2520
2880
2910
3660
4870
5790
3800
4100
4700
5000
5450
5900
6050
6280
6280
7330
8380
8680
650
820
1030
1140
1470
1760
2480
2720
2840
3620
4600
5550
4550
4850
5450
5750
6200
6650
6800
7030
6800
8000
9050
9350
720
900
1140
1310
1630
1930
2720
3030
3130
3980
5150
6130
3800
4100
4700
5000
5450
5900
6050
6280
6130
7030
8080
8680
640
810
1020
1170
1480
1750
2460
2700
2890
3690
4690
5840
4550
4850
5450
5750
6200
6650
6800
7100
6800
8000
9050
9350
720
900
1140
1300
1620
1920
2700
3030
3200
4120
5320
6380
The above dimensions and weights are a guideline only. Accurate values and combinations are calculated in SystemairCAD.
* Height excl. legs/base frame.
Unit size
Run-around coil heat exchangers
Unit
Width
10
15
20
25
30
40
50
60
80
100
120
150
190
240
970
1120
1270
1420
1570
1720
2020
2170
2170
2370
2590
2890
3190
3490
Single height unit
Height*
520
595
670
745
820
895
1045
1120
1270
1420
1570
1720
2170
2470
Double height unit
Height*
1040
1190
1340
1490
1640
1790
2090
2240
2540
2840
3140
3440
4340
4940
R1E
Length
2540
2540
2690
2690
2840
2990
2990
3140
3140
3590
3890
4110
5010
5230
580
700
840
990
1170
1420
1980
2240
2460
2990
3800
4580
6290
7420
3360
3360
3510
3510
3360
3810
3810
3960
3960
4560
4860
5010
5910
6060
680
820
980
1150
1360
1620
2220
2550
2790
3510
4340
5170
7050
8270
Weight kg
R2E
Length
Weight kg
The above dimensions and weights are a guideline only. Accurate values and combinations are calculated in SystemairCAD.
* Height excl. legs/base frame. The heights of DV 190 and 240 are incl. base frames.
Select combination and add or remove functions
Danvent DV contains countless combination options. To
ease the process of designing a unit, the most popular
combinations are illustrated above. See more combination
examples in the DV catalogue on www.systemair.dk.
Key to symbols
Exhaust air
Outdoor air
Extract air
Supply air
9
10
|
Quick Guide to Danvent DV
Certificates
Systemair strives constantly to
improve the energy saving, technical
and mechanical quality of Danvent
DV. The unit is certified and approved
on a number of important points.
Eurovent certification
Danvent DV air handling units are
Eurovent certified. This ensures the
conformity between the calculated
performance in SystemairCAD design
programme, and the measured performance at independent test laboratories. Certificate 07.02.339.
Machinery directive
Danvent DV air handling units are
manufactured according to the safety
demands of the EU Machinery
Directive 2006/42/EF. This is confirmed through the issurance of corresponding Declaration of
Incorporation for units without
control system, and corresponding
Declaration of Conformity and CE
label for units with factory installed
control system.
ISO 9001:2008 certification
Danvent DV air handling units are
developed and manufactured in
Denmark. The factory’s quality
management system is certified
according to the standard EN ISO
9001:2008 by Bureau Veritas
Certification.
Eurovent energy classification
Danvent DV air handling units are
energy classified according to
Eurovent’s guidelines for air handling
units RS 6/C/005–2015. The energy
class expresses the unit’s total energy consumption. The energy class is
calculated by the design programme
SystemairCAD based on the actual
data of the designed unit.
Mechanical strength
Class D2
Casing air leakage
Negative pressure: - 400 Pa: Klasse L2
Positive pressure:
+ 700 Pa: Klasse L2
Filter by-pass leakage
Negative pressure:
- 400 Pa: Klasse F9
Positive pressure:
+ 400 Pa: Klasse F9
Thermal transmittance
Class T2
Thermal bridging factor
Class TB3
Classifications
The performance of the air handling
unit casing corresponds with the following classifications according to
the European standard EN 1886,
2. edition 2008.
ENERGY EFFICIENCY
339
2014
AHU No 07.02.339
DANVENT DV 10-240, TIME 10-40
Report to performance data 2014
Quick Guide to Danvent DV |
SystemairCAD
Danvent DV units are designed in
SystemairCAD. It is an advanced
design programme which ensures an
optimal dimensioning of the unit’s
functions. The programme is free and
can be downloaded from
www.systemair.com. SystemairCAD is
very user-friendly and allows a simple and quick way to combine the
unit functions as required. When the
unit design is finished, SystemairCAD
makes a technical calculation and
automatically generates a complete
technical documentation in pdf format for the selected unit.
The documentation includes the
following highlights:
• Frontpage with a summary of the
most important technical data of
the selected unit: Airflow, external
pressure drop, motor data, overall
dimensions, weight, efficiency of
the heat exchanger, SFP, performance of the heating coil and
sound power level.
•D
etailed drawing of the unit’s construction, dimensions and duct
connections.
• Sound power level divided into
frequency bands.
• Technical specifications of all components included in the unit such as
pressure loss, dimensions, electric
data, efficiencies, air temperatures,
COP, EER, description of materials,
ErP, power input, etc.
• Shipping, dimensions and weights
of all parts.
• The control system including flowchart, external electrical components, description of control functions, alarms, and safety functions,
as well as communication options.
•M
olliere diagram with summer
and winter conditions.
• SystemairCAD includes a feature
that can automatically generate a
complete consultant text adapted
to the selected unit.
The drawn to scale drawings from
SystemairCAD can be exported to
other CAD software. There are the
following options:
• Export of DXF files 2D and 3D
• Export of DMR files to
Autodesk Revit.
• SystemairCAD project files can be
opened directly in AutoCAD via
MagiCAD plugin and in Autodesk
Revit via Revit plugin.
11
Avedøreholmen 50
DK-2650 Hvidovre
Tel. +45 87 38 75 00
[email protected]
www.systemair.dk
Systemair DK • May 2015 • V4-90934201