Celkový katalog SALICRU
PRODUCT RANGE
CATALOGUE
APRIL 2014
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
Since its founding in 1965, Salicru, S.A. has designed,
manufactured and commercialised power electronics products
for the key sectors of the energy market.
Salicru’s mission is to provide innovative solutions and services
to increase our customers’ productivity through the provision
of high-quality power supplies that will be continuous, clean,
affordable, reliable and ecologically-friendly, in both alternating
and direct current.
Salicru has the broadest national coverage and 7 international
subsidiaries, with sales to over 40 countries worldwide, with
over 600,000 units operating and running. The company is
ISO-9001 and ISO 14001 certified, and its products are designed
and produced in full respect of the Environment.
In a technological firm such as ours, research and innovation
are essential to maintain our competitive edge and presence on
the market. Therefore, we dedicate 4% of our annual turnover
to R&D, which is well above the national average of 0.9% or
the European average of 1.4%.
The main product lines are:
- UPS (Uninterruptible Power Supplies): Electronic protection
with autonomy for all kinds of critical environments, ranging
from 400 VA to several MVA.
- Lighting flow dimmer-stabilisers: Energy and CO2 emission
saving for lighting installations.
- DC systems and inverters: Solutions for AC/DC and DC/AC
power supplies.
- Photovoltaic solar inverters: Generation of AC grid tied voltage
using solar energy.
- Voltage stabilisers: Regulating of the electrical supply.
Protection and continuity solutions
According to different studies, 40% of faults occurring in
computer systems are caused by disturbances in the electrical
power supply (far more than those caused by computer viruses)
also affecting productivity losses derived from inactivity and the
resources needed for restoring the damage caused.
Energy efficiency
Salicru is aware of the gradual fall in the availability of natural
resources used to produce energy and also of the growing need
to reduce energy consumption while maintaining the same energy
services without affecting comfort and quality of life and protecting
the Environment and assuring supply while encouraging sustainable
behaviour in its use.
Salicru’s investment in the Environment is longstanding: since the
first lighting flow dimmer-stabiliser (ILUEST+) came out in the early 1990s, to the photovoltaic solar inverters (EQUINOX), the will
of the company has always been to produce equipment that is not
only respectful of the Environment but also actively participates in
preserving it.
DELEGATIONS AND TECHNICAL SUPPORT & SERVICE (TSS)
BARCELONA
BILBAO
CORUNNA
GIJÓN
LAS PALMAS DE G. CANARIA
MADRID
MÁLAGA
MURCIA
PALMA DE MALLORCA
PAMPLONA
SAN SEBASTIÁN
SEVILLE
VALENCIA
VALLADOLID
ZARAGOZA
SUBSIDIARIES
CHINA
FRANCE
HUNGARY
MEXICO
MOROCCO
PORTUGAL
SINGAPORE
REST OF WORLD
Design adaptable to any
operating environment
Presentation in 1973 of
the first prototype of UPS
Solutions designed with eco-efficient
criteria
ISO 9001:
Quality management
ISO 14001:
Environmental management
ALGERIA
ARGENTINA
BELGIUM
BRAZIL
BULGARIA
CHILE
COLOMBIA
CUBA
CZECH REPUBLIC
ECUADOR
EGYPT
GERMANY
INDONESIA
IRELAND
JORDAN
KUWAIT
MALAYSIA
NETHERLANDS
PERU
PHILIPPINES
POLAND
RUSSIA
SAUDI ARABIA
SWEDEN
SWITZERLAND
THAILAND
TUNISIA
UAE
UNITED KINGDOM
UNITED STATES OF AMERICA
URUGUAY
VENEZUELA
VIETNAM
Follow us on:
@salicru_SA
www.linkedin.com/company/salicru
MARKETS + DISTURBANCES
DISTURBANCES
Burst
transients
Spikes
HOMES, OFFICES & SHOPS
Advanced and versatile protection of computer,
telecommunications and multimedia equipment
Sags & undervoltages
Dropouts & blackouts
SMES, LARGE CORPORATIONS AND
PUBLIC SECTOR BODIES
Surges & overvoltages
INDUSTRY
Maximum protection in the corporate environment
Tailor-made solutions to ensure the security of the power
supply and sensitive information
HOSPITAL
SOLUTIONS
SPS HOME
SPS SOHO+
SPS ADVANCE RT
SLC TWIN PRO
SLC TWIN RT
Off-line UPS 400 VA & 600 VA
Line-interactive UPS
from 400 VA to 2,000 VA
Sinewave Line-interactive
rack/tower UPS
from 750 VA to 3,000 VA
Single phase parallelable
On-line double conversion UPS
from 700 VA to 20 kVA
Single phase rack/tower
On-line double conversion UPS
from 700 VA to 10 kVA
DC POWER-S
OPTIMUS
FAC P
DC POWER-L
CS-IS/CS WAVE MDL
DC power systems
from 1 kW to 81 kW
Compact DC power systems
300 W & 700 W
DC power systems
from 1 kW to 170 kW
Thyristor rectifiers
from 25 A to 200 A
DC/AC inverters
from 1 kVA to 24 kVA
POWER SOLUTIONS
Harmonics
Notches
INFRASTRUCTURES & ENERGY
High-performance protection for large critical
applications
Noise waveform
distortions
Flickers
Frequency
variations
TELECOMMUNICATIONS
The best way to meet the expectations and needs of
telecom operators
ENERGY EFFICIENCY & RENEWABLES
Commitment to eco-efficiency and renewable energy
as a corporate value
SLC ADAPT
SLC CUBE3+
SLC XTRA
SICRES
SOFTWARES
Modular On-line UPS
from 10 kVA to 100 kVA
Three phase On-line UPS
from 7.5 kVA to 200 kVA
Three phase On-line UPS
from 100 kVA to 800 kVA
Telemaintenance service
Management & monitoring
RE3
EMI3
ILUEST+ CR
ILUEST+ MT
SICRES x ILUEST
Electronic voltage stabilisers
from 300 VA to 250 kVA
Servomotor voltage stabilisers
from 5 kVA to 330 kVA
Lighting flow dimmer-stabilisers
from 7.5 kVA to 45 kVA
Lighting flow dimmer-stabilisers
from 3.5 kVA to 120 kVA
Telemanagement to ILUEST+
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
HOMES, OFFICES & SHOPS
Advanced and versatile protection of computer, telecommunications and multimedia equipment
The computer systems of companies, regardless of the
size of the business, have become nerve centres for
information and management, and vital for optimum day-to-day
operation. The dependency that they create is proportional
to the uses and benefits that IT technologies provide, not to
mention their constant evolution, which helps to increase the
competitiveness of companies.
disturbances can also threaten the very integrity of computer,
multimedia and telecommunications equipment by reducing
their useful life and, in severe cases, resulting in the need for
replacement with the associated increase in costs.
The same occurs in the home environment: we live in a society
of digital information and technology. In our homes, we have
numerous computer and multimedia systems connected to
the Internet in which we also store large amounts of files and
documents containing personal data that are not in duplicate
hard-copy form.
Storms, lightning and excess demand are just some of the many
different causes of electrical disturbances (ranging from micro
power cuts to overvoltages, or voltage spikes, and electrical
interference) that can affect electrical equipment in the office
and home environments.
Numerous studies have shown that the main cause of data loss
in digital environments is not viruses but, in fact, disturbances
in the power supply, which account for almost half of all cases.
The economic impact of such loss on shops and SMEs can be
considerable and can have serious repercussions for clients,
suppliers and employees. Nor should we forget that these
For these two reasons, uninterruptible power supply (UPS)
systems have now become essential to ensure a continuous,
optimum and stable power supply. Salicru’s mission is to
ensure optimum energy availability and advanced and versatile
protection of computer and multimedia equipment in the home
and office environments. To achieve this, it offers a wide
range of UPS solutions using existing technologies - stand-by,
line- interactive and On-line double conversion - covering
power ratings that range from 300 VA to several MW with all
communication possibilities - SNMP, remote management, task
killers, and all options to suit the specific needs of each installation.
This range of solutions is complemented by protective power
strips that protect against overloads, overvoltages and lightning.
With their advanced technology and versatile design, it is
possible to protect, with a single device, the different components
of a computer network such as PCs and all associated peripherals
(monitor, printer, external hard drive, router, etc.), multimedia
systems (TV, decoder, DVD player, home cinema, HiFi, DTT,
etc.), IT systems and servers, and telephone/ADSL connections.
REF. JM849A01 CODE 401AB000672 ED. FEBRUARY 2014 HOMES, OFFICES & SHOPS
HOMES, OFFICES & SHOPS
Advanced and versatile protection of computer, telecommunications and multimedia equipment
Solutions
SPS AUTO
Disturbances
12 VDC to 230 VAC converter + USB charger
Salicru’s SPS AUTO units are converters that supply the necessary
Dropouts &
blackouts
Sags &
undervoltages
Surges &
overvoltages
Noise waveform
distortions
electrical power in 230 VAC and 5 VDC. The input connection using the car
(or ship) lighter socket and the 230 VAC schuko output has a power of 150
W, whereas the 5 VDC output is via USB port with a charge of 2 A.
SPS SAFE
SPS.SAFE 6+
Electric active protector
SPS.SAFE 7+
6 schuko mains with EMI/RFI.
7 schuko mains with EMI/RFI.
Overload + surge + phone protec- Cable wrap-organizer device.
tion..
SPS HOME
SPS.BOOK
SPS.MASTER
Folding design for connection Master / Slave intelligent elecease. USB 2.0 double charger tric protect. 6 schuko mains (1
(1A).
Master + 5 Slave)
Off-line UPS 400 VA & 600 VA
· Off-line technology.
. Multiple base design with 6 schuko sockets.
. 4 sockets with UPS protection; all sockets with overvoltage protection.
. USB port for monitoring and file closing software.
. Telephone / ADSL line protection by RJ-45 port.
. Batteries user replaceable.
SPS SOHO+
References
· AXA
· Banc de Sabadell
· Bank of China
· BBVA
· Carrefour
· Cepsa
· Credit Lyonnais
· El Corte Inglés
· Fnac
· Ikea
· La Caixa
· Mapfre
· Media Markt
· Mercadona
· Paradores de turismo
· Seguros Santa Lucía
Off-line UPS 400 VA - 2,000 VA
· Line-interactive UPS.
. Automatic voltage regulation AVR.
. LCD display with information on all parameters.
. UPS/PC communication via USB port.
. Monitoring software for Windows, Linux, Unix and Mac.
. Cold Start function to allow start-up without mains.
. Automatic restart when mains returns.
SPS ADVANCE RT Sine-wave Line-interactive UPS 750 VA - 3,000 VA
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
· Line-interactive UPS with sine-wave output.
. Output power factor = 0.9.
. Permanent stabilisation.
. Directable graphic screen.
· Power/rack convertible.
. Rack assembly height of 2U.
. Includes pedestal (tower) and ears (rack).
. Green-mode function.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
HOSPITAL
SMES, LARGE CORPORATIONS AND
PUBLIC SECTOR BODIES
Tailor-made solutions to ensure the security of the power supply and sensitive information
The business community is increasingly aware of the need
to have at its disposal equipment that enables more efficient
use of energy and it does not consider such equipment as
an expense, but as an investment for the protection of its
productive assets. This is particularly evident in large companies
because executives and businesspeople clearly understand
that an uninterruptible power supply (UPS) is synonymous with
efficiency and savings.
From both an economic and social responsibility perspective,
there is no doubt that organisations need to commit themselves
to security and energy efficiency, especially with regard to
critical and large-scale investments and infrastructures or in
the storage and processing of large amounts of information,
such as in hospitals, universities, public sector bodies and large
corporations.
Moreover, virtually all medium-sized and large companies have
some sort of data processing centre (DPC), while the largest
may even have several. One of the most important factors that
influences the creation of centres of this type is the need to
ensure continuity of service to clients, employees, citizens,
suppliers and business partners. In these areas, physical
protection by a UPS system of computer or communications
equipment, as well as database servers that can contain critical
and/or sensitive information, is essential.
A key factor to consider when making decisions that affect
energy security is the fact that the installation of a UPS, as
part of a complete installation of a new DPC, only represents
approximately 3 to 5% of the total investment, which is a
relatively small percentage considering the significant savings
it can provide in terms of preventing data loss, resulting in it
becoming a strategic advantage for the company.
Moreover, flexibility and scalability are two characteristics
that are becoming increasingly important in the ICT market,
as having equipment to suit the specific growth needs of a
company is a significant economic and operational advantage.
This is why innovation is key to Salicru’s strategy of offering
products that meet clients’ current requirements and providing
them with rack installation possibilities or the opportunity to
expand power capacities.
Salicru has the technology and know-how to offer clients
highly-versatile, tailor-made solutions for the protection of
these types of facilities in SMEs, public sector bodies and large
corporations. Its advanced technology enables monitoring,
remote management, modularity and growth in parallel.
Rigorous but, at the same time, flexible and agile production
processes make Salicru the perfect partner in the search for
tailor-made solutions.
REF. JM850A01 CODE 401AB000677 ED. FEBRUARY 2014 SMES, LARGE CORPORATIONS AND PUBLIC SECTOR BODIES
SMES, LARGE CORPORATIONS AND PUBLIC SECTOR BODIES
Tailor-made solutions to ensure the security of the power supply and sensitive information
Solutions
Disturbances
SPS ADVANCE RT
Dropouts &
blackouts
Sags &
undervoltages
Sine-wave Line-interactive UPS 750 VA - 3,000 VA
· Line-interactive UPS with sine-wave output.
. Output power factor = 0.9.
. Permanent stabilisation.
. Directable graphic screen.
Surges &
overvoltages
· Power/rack convertible.
. Rack assembly height of 2U.
. Includes pedestal (tower) and ears (rack).
Harmonics &
interharmonics
Frequency
variations
Flickers
SLC TWIN PRO
Double conversion On-line UPS from 700 VA to 20 kVA
· Double conversion On-line UPS.
· Output power factor = 0.9 (up to 3 kVA = 0.8).
· Input current Total Harmonic Distortion (THDi) <5%.
· Control panel with LCD display or graphic display and keyboard.
· Option of parallel up to 4 units.(1)
· Eco-mode operation.
· Tower format
(1) From 4 kVA
SLC TWIN RT
Rack/tower On-line UPS from 700 to 10.000VA
· Double conversion On-line UPS.
· Output power factor = 0.9.
· Input current Total Harmonic Distortion (THDi) <5%.
· Directable LCD display.
· Convertible between tower and rack.
· Up to 2 units in parallel.(1)
SLC ADAPT
Modular UPS from 10 to 100 kVA
· Double-conversion, On-line technology.
· Completely independent UPS module.
· Subracks of 50 kVA and 100 kVA with 10 kVA modules.
· Compact and light inverter/ondulator UPS format (9 kg x module).
· Power upgrading and redundant set up by adding modules.
· Possible three phase/single-phase configurations up to 40 kVA.
· System efficiency up to 96% (3-level inverter).
References
· Cisco Systems
· Fujitsu
· Hewlett Packard
· Hitachi
· IBM
· Iecisa
· Intel
· Panasonic
· SAP
· Siemens
· Sony
· Stanley
· Thomson
· Toshiba
(1) From 4 kVA
SLC CUBE3+
Uninterruptible power supply from 7.5 kVA to 200 kVA
· On-line double conversion (VFI) technology with DSP control.
· Input power factor 1, for better performance.
· Very low input current harmonic distortion (THDi as low as <1%).
· Total flexibility in input/output voltage. (1)
· Designed to withstand any type of load.
· Batt-Watch function for monitoring and battery care.
SLC X-TRA
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(1) Single/single, single/three and three/single configurations up to 60 kVA
Uninterruptible power supply from 100 kVA to 800 kVA
· On-line, double conversion, DSP control.
· Double input connection to increase the availability.
· Input power factor >0.99.
· Total harmonic distortion of input current (THDi) < 3%.
· High energy efficiency between 95% and 96%.
· Selectable operation inverter/Smart Eco-mode.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
INDUSTRY
Maximum protection in the corporate environment
Power supply in industry is basic and essential to ensure
maximum corporate profitability. For this reason, ensuring a
high-quality power supply in industrial environments is as
critical as it is vital.
The range of possible electrical problems that can affect
industrial processes - continuous manufacturing and
automated command and control systems, instrumentation and
measurement, process monitoring and control, safety systems,
critical applications, and many more - is extensive and requires
appropriate solutions for each type of problem or electrical
disturbance.
Voltage spikes, power outages, over/undervoltages, micro
power cuts, frequency variations, excess demand, etc., are
some of the electrical problems that commonly occur in the
industrial field. If any of these factors disturb the power supply
of industrial processes and affect productive capacity, economic
profitability will inevitably be affected.
voltage stabilisers, power supplies and, ultimately, thanks to its
know-how, tailor-made solutions for specific problems.
It is a set of solutions that provides maximum reliability in
electrical protection for production and control systems, and
for industrial processes that require the use of machinery that
is highly sensitive to variations in voltage, such as milling
machines, presses, trimming machines, lathes, polishing
machines, electrical discharge machines, as well as electric
drives and operations, numerical controls, electric furnaces,
lifts, graphic printing equipment, medical equipment and TV
repeater stations. This is also the case, for example, for the
most advanced technological processes such as ERP systems,
CRM platforms and business intelligence tools.
To ensure that these processes are not disturbed by these
external agents, it is necessary to have security mechanisms in
place to guarantee proper operation.
In the case of uninterruptible power supply (UPS) systems and
voltage stabilisers, Salicru’s solutions cover a wide range of
power ratings, extensive communication options via interface
and monitoring software, standard backup batteries and
expansion options, etc., that suit the qualitative and quantitative
growth needs of any type of industrial facility.
Salicru has several product lines that can solve the various
problems and electrical disturbances that can affect these
industrial processes: uninterruptible power supply systems,
Salicru’s experience in the industrial field is endorsed by its
long track record of service and effective operation of more than
600,000 devices currently installed worldwide.
.
REF. JM853A01 CODE 401AB000692 ED. FEBRUARY 2014 INDUSTRY
INDUSTRY
Maximum protection in the corporate environment
Solutions
SLC TWIN PRO
Disturbances
Dropouts &
blackouts
Sags &
undervoltages
Surges &
overvoltages
Notches
Frequency
variations
Flickers
Burst
transients
Double conversion On-line UPS from 700 VA to 20 kVA
· Double conversion On-line UPS.
· Output power factor = 0.9 (up to 3 kVA = 0.8).
· Input current Total Harmonic Distortion (THDi) <5%.
· Control panel with LCD display or graphic display and keyboard.
· Option of parallel up to 4 units.(1)
· Eco-mode operation.
(1) From 4 kVA
SLC CUBE 3+
Uninterruptible power supply from 7.5 kVA to 200 kVA
· On-line double conversion (VFI) technology with DSP control.
· Input power factor 1, for better performance.
· Very low input current harmonic distortion (THDi as low as <1%).
· Total flexibility in input/output voltage. (1)
· Designed to withstand any type of load.
· Batt-Watch function for monitoring and battery care.
Harmonics and
interharmonics
SLC X-TRA
(1) Single/single, single/three and three/single configurations up to 60 kVA
Uninterruptible power supply from 100 kVA to 800 kVA
· On-line, double conversion, DSP control.
· Double input connection to increase the availability.
· Input power factor >0.99.
· Total harmonic distortion of input current (THDi) < 3%.
· High energy efficiency between 95% and 96%.
· Selectable operation inverter/Smart Eco-mode.
EMI3
Servomotor voltage stabiliser from 5 kVA to 330 kVA
· Fast and efficient toroidal autotransformers for the entire power range.
· Output accuracy better than 1% (adjustable).
· In three-phase units, common or independent regulation per phase,
unaffected by imbalances.
· Input regulation range ±15% standard.
· High efficiency, up to 97.5%.
RE3
· Ultra-fast regulation: reply speed under 100 ms.
· Control and test of all parameters by one microprocessor per phase.
· Static bypass, loads always supplied.
· Entirely static structure, without moving elements, greater reliability.
· Output precision better than 2%.
· Efficiency > 97%.
References
· ABB
· Air Liquide
· ArcelorMittal
· BASF
· Bayer
· Boehringer Ingelheim
· Cepsa
· Dow Chemical
· EADS
· Gallina Blanca Star
· General Electric
· Honeywell
· Lafarge
· Nestle
· Otis
· Pepsico
· Renault
· Repsol
· Roche diagnostics
· Unilever
Electronic voltage stabiliser from 0.3 kVA to 250 kVA
DC POWER-L
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
Thyristor rectifier from 25 A to 200 A
· Microprocessor-controlled thyristor technology.
· Galvanic isolation between input and output via transformer.
· Ventilation by natural convection.
· Complete six-pulse bridge.
· Standard DC output earth fault detection.
· Electrolyte level detection for NiCd batteries (optional).
· Charging states: floating, fast and exceptional.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
INFRASTRUCTURES & ENERGY
High-performance protection for large critical applications
Airports, railways, ports and roads are essential infrastructures
for carrying out the activities of cities, companies and people.
The same is true of power (electricity and fuel networks) and
water (drinking water and drain networks) infrastructures.
These devices are very compact, which greatly facilitates their
installation, and made from over 60% recyclable materials.
Our professional and personal wellbeing largely depends on
their proper functioning. What would happen, for example, if
air traffic control radar, traffic lights or railway signalling lost
their power supply?
To prevent these kinds of situations from arising and affecting
our wellbeing and the competitiveness of our professional
work, uninterruptible power supply (UPS) systems exist. These
are devices that not only provide enough power to prevent
faults caused by power cuts, but also improve the quality of
mains voltage, thus extending the useful life of the electrical,
electronic and computer equipment connected to it.
Salicru, in line with its technological commitment, offers
various ranges of UPS whose features are ideal for large critical
applications such as transport, power and water infrastructures,
as they ensure the safeguarding of equipment and the proper
management of systems.
Ensuring the functioning of all elements of these infrastructures
is essential for Salicru, and to achieve this, we also offer
products that ensure alternative power sources, such as our
DC/AC systems, which are designed to operate in harsh and
demanding operating environments such as: power stations,
electrical substations, oil and gas pipelines, petrochemical
plants, mines, railways, telecommunications facilities, hospitals
and industrial plants. DC systems are devices that convert
alternating current into direct current (rectifiers, chargers)
or direct current into alternating current (inverters). Such DC
systems can store power in an accumulator battery, enabling
an uninterrupted supply of DC or AC (through an inverter). They
also have a control and monitoring system that enables input
and output measurements, battery charging currents, control
of priority and non-priority loads and communication channels
with the outside to be managed.
An array of advanced technological solutions at the service of
highly-critical infrastructures.
REF. JM851A01 CODE 401AB000682 ED. FEBRUARY 2014 INFRAESTRUCTURES AND ENERGY
INFRASTRUCTURES AND ENERGY
High-performance protection for large critical applications
Solutions
SLC TWIN RT
Disturbances
Dropouts &
blackouts
Sags &
undervoltages
Surges &
overvoltages
Notches
Frequency
variations
Flickers
Spikes
Rack/tower On-line UPS from 700 to 10.000VA
· Double conversion On-line UPS.
· Output power factor = 0.9.
· Input current Total Harmonic Distortion (THDi) <5%.
· Directable LCD display.
· Convertible between tower and rack.
· Up to 2 units in parallel.(1)
· Selectable and priority loads control.(2)
SLC ADAPT
(1) From 4 kVA (2) Except 10 kVA
Modular UPS from 10 to 100 kVA
· Double-conversion, On-line technology.
· Completely independent UPS module.
· Subracks of 50 kVA and 100 kVA with 10 kVA modules.
· Compact and light inverter/ondulator UPS format (9 kg x module).
· Power upgrading and redundant set up by adding modules.
· Possible three phase/single-phase configurations up to 40 kVA.
· System efficiency up to 96% (3-level inverter).
Burst
transients
SLC CUBE 3+
Uninterruptible power supply from 7.5 kVA to 200 kVA
· On-line double conversion (VFI) technology with DSP control.
· Input power factor 1, for better performance.
· Very low input current harmonic distortion (THDi as low as <1%).
· Total flexibility in input/output voltage. (1)
· Designed to withstand any type of load.
· Batt-Watch function for monitoring and battery care.
SLC X-TRA
(1) Single/single, single/three and three/single configurations up to 60 kVA
Uninterruptible power supply from 100 kVA to 800 kVA
· On-line, double conversion, DSP control.
· Double input connection to increase the availability.
· Input power factor >0.99.
· Total harmonic distortion of input current (THDi) < 3%.
· High energy efficiency between 95% and 96%.
· Selectable operation inverter/Smart Eco-mode.
DC POWER-L
References
· AENA
· ADIF
· Alstom Power
· Bombardier
· CAF
· Dimetronic
· Dubai Natural Gas
· E.on
· Ecopetrol
· EDP
· Enagas
· Endesa
· Gas natural - Fenosa
· Gazprom
· Iberdrola
· Kuwait Oil Company
· Pemex
· REE
· Repsol
· Texaco
· Thales Rail
· Siemens
Thyristor rectifier from 25 A to 200 A
· Microprocessor-controlled thyristor technology.
· Galvanic isolation between input and output via transformer.
· Ventilation by natural convection.
· Complete six-pulse bridge.
· Standard DC output earth fault detection.
· Electrolyte level detection for NiCd batteries (optional).
· Charging states: floating, fast and exceptional.
DC POWER-S
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
DC power system
· Maximum power per system up to 81 kW.
· Flexible, scalable and N+n redundant systems, configurable for
current demand and future expansion.
· Option of single or three-phase power supply.
· DC systems with output voltages of 48, 110 or 125 Vdc.
· High power density in the modules, up to 27 W/in3.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
TELECOMMUNICATIONS
The best way to meet the expectations and needs of telecom operators
To talk about telecommunications is to talk about a strategic
and innovative sector. In fact, few sectors, like that of
telecommunications, better reflect the technological progress
of recent years and its contribution to the development of the
information society.
Because, to talk today about telecommunications is to talk about
the technology related to television, radio, landline telephones,
mobile telephones, voice and data networks and the Internet.
Salicru has a wide range of UPS systems whose features are
ideal for large critical applications, such as telecommunications
infrastructures, as they safeguard equipment and ensure
the proper management of systems. These devices are very
compact, which greatly facilitates their installation, and made
from over 60% recyclable materials.
Telecommunications have become a determining factor in the
development of the new digital society, which has also resulted
in significant technological dependence.
In order for operators and other telecom companies to be able to
offer their equipment and services on an industrial, professional
and domestic level, they need a constant and reliable electricity
supply without power cuts, disturbances and fluctuations
affecting normal operation.
In addition to a permanent power supply, current
telecommunication systems also need devices that store
energy as an alternative, as is the case of DC/AC systems or
battery chargers, which also meet the needs of a wide variety of
critical loads that have to be correctly powered and protected.
Particularly suited to the telecommunications sector are
rectifiers and inverters, which help to provide a high-quality AC
power supply from a DC power source.
This extensive product range includes high-performance
monitoring and remote-management devices that are essential
for the optimisation of infrastructures that are generally widely
dispersed.
To prevent this from happening and affecting our wellbeing
in our daily lives, and the competitiveness of our professional
work, uninterruptible power supply (UPS) systems exist. These
are devices that not only provide power to prevent faults caused
by power cuts, but also improve the quality of mains voltage,
thus extending the useful life of the technological equipment
connected to them.
This is Salicru’s way of meeting the expectations and needs
of a dynamic sector that is in constant technological evolution,
such as that of telecommunications.
REF. JM854A01 CODE 401AB000697 ED. FEBRUARY 2014 TELECOMMUNICATIONS
TELECOMMUNICATIONS
The best way to meet the expectations and needs of telecom operators
Solutions
DC POWER-L
Disturbances
Spikes
Burst
transients
Sags &
undervoltages
Surges &
overvoltages
· Microprocessor-controlled thyristor technology.
· Galvanic isolation between input and output via transformer.
· Ventilation by natural convection.
· Complete six-pulse bridge.
· Standard DC output earth fault detection.
· Electrolyte level detection for NiCd batteries (optional).
· Charging states: floating, fast and exceptional.
Dropouts &
blackouts
Harmonics &
interharmonics
Thyristor rectifiers from 25 A to 200 A
DC POWER-S
DC power systems
· Maximum power per system up to 81 kW.
· Flexible, scalable and N+n redundant systems, configurable for
current demand and future expansion.
· Option of single or three-phase power supply.
· DC systems with output voltages of 48, 110 or 125 Vdc.
· High power density in the modules, up to 27 W/in3.
CS IS
DC power converters
· Availability in a wide range of voltages and outgoing power.
· Broad range of input voltage variation.
· LCD display comes standard.
· Communication through relay interface or RS-232 / RS-485.
· Excellent dynamic behavior.
CS WAVE MDL
· DSP Design (Digital Signal Processor).
· Back-feed protection standard (in configurations with STS).
· Senoidal output.
· All Master technology for better reliability.
· Hot-Swap.
· High density power.
References
· Abertis
· Bouygues Telecom
· Cable & Wireless
· China Central TV
· Ericsson
· Indra
· Ikusi
· Lucent Technologies
· Motorola
· Nokia
· Nortel
· Orange
· Portugal Telecom
· Siemens
· Telefónica
· Vodafone
48 DC power converters
OPTIMUS
Compact DC power systems
· Suitable for single phase or three-phase supplies.
· Great power density.
· Easy installation and maintenance.
· High MTBF.
· High efficiency.
· Low cost operation and maintenance.
· Battery charging current limitation.
FAC-P
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
DC power systems
· Suitable for single phase or three-phase supplies.
· Great power density.
· Easy installation and maintenance.
· Low cost operation and maintenance.
· High MTBF.
· High efficiency.
· Battery charging current limitation.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
ENERGY EFFICIENCY
AND RENEWABLES
Commitment to eco-efficiency and renewable energy as a corporate value
Energy efficiency is defined as the reduction of energy
consumption while maintaining the same energy services,
ensuring continued comfort and quality of life, protecting the
environment, guaranteeing supply and promoting sustainable
behaviour in its use. Today, society demands equipment that, in
addition to responding to its business needs, saves energy and
costs, and is environmentally friendly.
In Spain,15,000 have been installed with total potential annual
energy savings of 558,000 MWh, reductions in CO2 emissions
of over 130,000 tons and cost savings of more than 50 million
euros.
Encouraging the development of new technologies that
contribute to more responsible energy consumption is, without
doubt, one of the cornerstones of Salicru’s corporate strategy.
For years, it has been firmly committed to renewable energy
and the most advanced technology applied to energy efficiency
through its SLC Greenergy Solutions line, which includes
stabilisers-step-down light dimmers and solar inverters.
The former have become the equipment of choice for street
lighting projects as they make it possible to achieve savings
of up to 40% on electricity bills. More than two decades ago,
Salicru pioneered a new way of accurately regulating street
lamps with its range of stabilisers-step-down light dimmers,
which make it possible to achieve significant energy and
maintenance savings.
Salicru’s solar inverters, which are designed for domestic
and commercial installation, convert direct current from solar
modules into the alternating current required for connection
to the low-voltage electricity distribution system. Their main
competitive advantage is that they make it possible to achieve
increases of up to 10% in production.
Their innovative technology, backed up by Salicru’s extensive
experience in the power electronics market, ensures high
performance in low and high-power solar photovoltaic facilities,
both indoors and outdoors. A wide range of communication
capabilities are also offered: all of the units feature an LCD and/
or graphic display screen to facilitate viewing of a facility’s data
and local or remote communication devices.
Since then, it has installed more than 27,000 devices in countries
like Spain, China, France, Poland, Tunisia and Morocco.
REF. JM852A01 CODE 401AB000687 ED. FEBRUARY 2014 ENERGY EFFICIENCY AND RENEWABLES
ENERGY EFFICIENCY AND RENEWABLES
Commitment to eco-efficiency and renewable energy as a corporate value
Solutions
ILUEST+ CR
Disturbances
Sags &
undervoltages
Spikes
· Stabilisation better than ± 1% + saving voltage periods = savings >
40%.
· Continuous regulation of the output voltage, no voltage steps;
higher lamp lifetime.
· Lineal and programming ramps.
· High response time.
· RS-232 port + MODBUS protocol, as standard.
Surges &
overvoltages
Noise waveform
distortions
Lighting flow dimmer-stabilisers from 7.5 to 45kVA
ILUEST+ MT
Lighting dimmer-flow stabilisers from 3.5 to 120 kVA
· Electronic lighting flow adjustment by static elements and
next generation microprocessor control.
. Entirely independent adjustment per phase.
. Automatic bypass per phase, independent operation, manually
operation and active by default.
. Protection with automatic programming rearm due to overload
and overtemperature.
ILUCOM
Remote management for street lighting
Salicru’s ILUCOM street lighting management system, which
operates in conjunction with the company’s ILUEST+ range of
lighting flow dimmer-stabilisers, enables powerful and effective, local
or remote, management of any type of control cabinet from any mobile
device connected to the Internet, without the need for any major
infrastructure and deployment.
SICRES
By incorporating the SICRES network card, Salicru offers a
telemaintenance service through an Internet connection, which enables
the state of the complete fleet of equipment (including cartography) to
be known at all times and failures in the equipment and/or the control
centres to the anticipated.
References
· Abu Dhabi (UAE)
· Barcelona (Spain)
· Beijing (China)
· Bydgoszcz (Poland)
· Cartago (Tunisia)
· Casablanca (Morocco)
· Gdansk (Poland)
· Guangzhou (China)
· Lyon (France)
· Madrid (Spain)
· Málaga (Spain)
· Rabat (Morocco)
· Reims (France)
· Rennes (France)
· Tunis (Tunisia)
· Shangai (China)
· Valencia (Spain)
Telemanagement to ILUEST
EQUINOX
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
Photovoltaic inverters 2.8 kW - 4 kW - 5 kW - 10 kW
· PWM technology with transformerless electronic insulation.
· Maximum Power Point Tracker system (MPPT).
· High conversion efficieny > 97%.
· Power factor > 0.99.
· Plug & Play connect.
· Multi-string connection choice: 1 to 3 MPPT.
· Indoor and outdoor versions.
· GFCI (Ground Fault Circuit Interruptor) so as to avail grounding leak
advanced control.
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SPS HOME
Off-line UPS 400 VA & 600 VA
SPS HOME: Full protection for office and domestic units
The numerous types of electrical disturbances (e.g. mains failures, power cuts, blackouts, over-voltages,…) arising from the various
causes (e.g. storms, lightning, excessive demand, natural disasters, accidents etc...) present problems to all electricity users, and a
constant challenge to all computer users who depend on a correct and stable power supply to be able to work safely and efficiently.
Electrical problems are responsible for the largest number of faults in computer systems, far more even than those caused by computer
viruses. The best solution is therefore to seek protection with an Uninterruptible Power Supply.
The Salicru SPS HOME series Uninterruptible Power Supply, with Off-line technology, come in power ratings of 400 VA and 600 VA
and are the best possible protection for both domestic and professional single-post computer environments.
Each UPS provides 6 output sockets with sufficient capacity for the central unit and all of the associated peripherals. In order to
achieve greater total protection, telephone/ADSL protection is provided, preventing the entry of overvoltages and/or electrical noise
through the telephone line. Completing the overall protection, the UPS units come complete with monitoring and file closing software
to facilitate orderly shutdowns in the event of extended power cuts.
Performance
· Off-line technology.
· Multiple base design with 6 schuko sockets.
· 4 sockets with UPS protection; all sockets with overvoltage
protection.
· On/Off multifunction pushbutton.
· Self-detection of 50 or 60 Hz frequency.
· LEDs indicating mains, battery mode and battery failure.
· USB port for monitoring and file closing software.
· Telephone / ADSL line protection by RJ-45 port.
· Batteries user replaceable.
· Cold Start function.
· Enabling self test at startup.
· Anchoring for wall fixture.
· Automatic restart after each power cut and at the end of
autonomy.
· Economic guarantee for connected units up to 70,000 €. (1)
SPS HOME
(1) Only European Union countries.
Applications: Versatile protection for single-post environments
Designed in multiple base format, the SPS HOME series UPS have 6 schuko bases duly turned to enable trafo connections and
with child protection by obturators, with a capacity in computer systems to protect both the PC and all of its associated peripherals
(screen, printer, external hard disk, router, …).
2
YEARS
WARRANTY
REF. JM773B01 CODE 401AB000563 ED. MARCH 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
ASK FOR LOCAL CONDITIONS
SPS HOME
Off-line UPS 400 VA & 600 VA
Description
TECHNICAL SPECIFICATIONS
9
MODEL
2
1
TECHNOLOGY
INPUT
3
SPS HOME
Off-line
Nominal voltage
Voltage range
230 V
Up to 170V – 265V
Nominal frequency
4
±10%
Frequency self-detection
OUTPUT
Yes
Voltage
230 V
±10%
Voltage precision (1)
8
50 or 60 Hz
Frequency (1)
6
4 x UPS sockets.
2 x overvoltage protection sockets.
On / Off multifunction pushbutton.
LED indicators.
AC input.
USB port.
RJ-45 telephone / ADSL protection.
Protection breaker.
Anchoring for wall fixture.
±1%
Frequency precision (1)
Wave form (1)
5
7
1.
2.
3.
4.
5.
6.
7.
8.
9.
50 or 60 Hz
Frequency range
Pseudo sinusoidal
Schuko
Socket type
4
No. sockets with autonomy + protection
2
No. sockets with protection
2/6 ms
Transfer time
PROTECTION
Input
Breaker, user-resettable
AC mode and battery mode
Overload
Immediate interruption
Short-circuit
Protection against peaks
480 joules, 2 ms
Tel / Fax, modem, ADSL internet + Ethernet 10/100 Mb
Data line
BATTERY
Type
Sealed, lead-calcium, free-maintenance,
useful life 3-5 years
8 hours
Recharging time
Autonomy
Up to 20 minutes
Replacement
Software WinPower
By the user
Against deep discharge
Protection
Fuse against short-circuit
Yes
Cold start
Autotest
At each starter
Automatic restart
INDICATIONS
Yes
Mains present
Green LED
Battery mode
Yellow LED
Battery failure
ALARMS
Red LED
Battery mode output
Audible alarm every 5 seconds
Low battery (end of autonomy)
Audible alarm every second
Inverter failure
· UPS monitoring and management software for
closing files/applications.
· Supports Windows, Linux, Unix and Mac.
COMMUNICATION
Port
GENERALS
Maximum altitude
· SPS HOME series UPS.
· UPS / PC USB connection wire.
· Quick start guide.
· Warranty certificate.
· Economic guarantee.
Salicru warranty
USB
Software
Monitoring and management for the Windows, Linux, Unix and Mac
3,500 m.a.s.l.
Up to 95% without condensing
Relative humidity
0°C ÷ +40°C
Temperature
Acoustic noise @ 1 metre
STANDARDS
Complete solution
Permanent alarm
<40 dB
Safety
EN-62040-1-1; EN-60950-1
Electromagnetic compatibility (EMC)
EN-62040-2
Quality and Environmental Management
ISO 9001 and ISO 14001
(1) Battery mode.
RANGE
MODEL
SPS.400.HOME
SPS.600.HOME
· On-line registry at www.salicru.com.
· 2-year warranty.
· Batteries covered by the warranty.
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
UPS POWER
TOTAL POWER
DIMENSIONS
WEIGHT
400 / 200
600 / 300
1,150 / 1,150
1,150 / 1,150
295 x 120 x 85
295 x 120 x 85
3.2
3.5
(VA / W)
(VA / W)
(D x W x H mm.)
(Kg)
Data may change without previous notice.
FUNCTIONS
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SPS SOHO+
Line-interactive UPS 400 VA - 2,000 VA
SPS.SOHO+: Full electric protection in office computer environments
Salicru’s SPS SOHO+ series is a Line-interactive UPS that incorporates an automatic voltage regulator (AVR), which attenuates all
possible fluctuations in the input voltage and at the same time causes smaller use of the batteries, extending their life and assuring
maximum autonomy if necessary.
For better integration in the office computer environment, the SPS SOHO+ series equipment has a full, rear-lit LCD display that gives
all information of the operating state of the units. It also has complete monitoring and management software through the USB
communication port, which enables continuous control of the system status and allows controlled computer shutdown in the event
of a long blackout when the system is left unattended.
Other outstanding functions include the Cold Start, which allows the system to be started in the absence of mains power; automatic
self test performed on the unit every time it is started, and the incorporation of schuko type socket to allow any kind of load to be
connected.
Performances
. Line-interactive UPS.
. Automatic voltage regulation AVR.
. LCD display with information on all parameters.
. UPS/PC communication via USB port.
. Monitoring software for Windows, Linux, Unix and Mac.
. Cold Start function to allow start-up without mains.
. Automatic restart when mains returns.
. Resettable input heat protection.
. Schuko type sockets.
. Data/modem line protection.
. Hot Swap function for changing batteries without shutting down.
. Automatic frequency detector 50/60 Hz.
. Self test on unit start-up.
. Protected against overloading, transient and short circuits.
. SLC Greenergy solution.
SPS SOHO+
Applications: Tranquillity and confidence in the power supply
The range of powers available covers 400, 600, 800, 1,000, 1,400 and 2,000 VA, with protection from single post stations to small
computer networks comprising a server plus several associated posts, the network electronics and the necessary peripherals.
The information stored in the computer systems is the most important value for any company’s operation. If it is lost or damaged, it
can cause serious harm so optimal protection is essential.
2
WARRANTY
YEARS
REF. JM818B01 CODE 401AB000607 ED. MARCH 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
ASK FOR LOCAL CONDITIONS
SPS SOHO+
Line-interactive UPS 400 VA - 2,000 VA
Description
TECHNICAL SPECIFICATIONS
MODEL
Line - interactive
Nominal voltage
Voltage range
220 V, 230 V, 240 V
Up to 162 V ÷ 290 V
Nominal frequency
50/60 Hz
Frequency auto-sensing
Yes
Stabilisation
OUTPUT
Buck/Boost
Voltage
230 V
±10%
Voltage accuracy (1)
Frequency
± 5% for load < 50% (2)
50/60 Hz
(1)
±1 Hz
Frequency accuracy (1)
Wave form (1)
Simulated sinewave
Schuko
Outlet type
2
Outlet quantity
400 / 600 / 800 VA
PROTECTION
1.
2.
3.
4.
5.
3
2 / 6 ms.
Transfer time
1000 / 1400 / 2000 VA
Input
Rearm thermal
AC and battery modes
Overload
AC input.
Output sockets.
USB communication port.
Data / ADSL line protection.
Thermal input protection.
Immediate shutdown
Short-circuit
Tel/fax, modem, ADSL internet + Ethernet network 10/100 Mb
Data line (RJ-45)
BATTERY
Sealed lead acid, AGM and free maintenance
Type
Recharge time
Autonomy (3)
6 - 10 hours up to 90%
Up to 20 minutes
Up to 40 minutes
Replacement
FUNCTIONS
By user
Protection
Against deep discharge against short-circuit through fuses
Cold Start
Yes
Yes, after end of autonomy
Automatic restart
Display
INDICATORS
LCD multifunction
Yes
Displayed values
Input voltage / output voltage
Levels
Connected load / overload / battery capacity
Operating modes
ALARMS
Normal / Battery / AVR (stabiliser)
Battery mode output
Beep every 10 seconds
Low battery (end of autonomy)
Beep every second
Battery replacement
Beep every 2 seconds
Fault
Beep continuously
Overload
6
1.
2.
3.
4.
5.
6.
Input voltage.
Output voltage.
Line mode (AVR stabilisation).
Load level.
Battery capacity.
Autonomy mode.
Control Software
UPS monitoring and management software
enabling a controlled computer shutdown in the
event of prolonged blackout. Valid for Windows,
Unix, Linux and Mac.
Beep every 0.5 seconds
COMMUNICATION
Port
GENERALS
Maximum altitude
2400 m.a.s.l.
Relative humidity
Up to 95%, non-condensing
USB
Software
Monitoring and management for Windows, Unix, Linux and Mac
Temperature
0º C ÷ +40º C
Acoustic noise at 1 metre
STANDARDS
Safety
<40 dB
<45 dB
EN-62040-1-1; EN-60950-1
Electromagnetic Compatibility (EMC)
EN-62040-2
Operating
EN-62040-3
Quality and Environmental management
ISO 9001 and ISO 14001
(1) Battery mode
(2) ± 10% for SPS.1000.SOHO+
(3) PC + LCD 15”
RANGE
MODEL
SPS.400.SOHO+
SPS.600.SOHO+
SPS.800.SOHO+
SPS.1000.SOHO+
SPS.1400.SOHO+
SPS.2000.SOHO+
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
POWER
DIMENSIONS
WEIGHT
400 / 240
600 / 360
800 / 480
1,000 / 600
1,400 / 840
2,000 / 1,200
330 x 100 x 140
330 x 100 x 140
330 x 100 x 140
405 x 145 x 205
405 x 145 x 205
405 x 145 x 205
5
6
6.5
9
9.5
10
(VA / W)
(D x W x H mm.)
(Kg)
Data may change without previous notice.
TECHNOLOGY
INPUT
SPS 400 / 600 / 800 SOHO+ SPS 1000 / 1400 / 2000 SOHO+
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SPS ADVANCE RT
Sine-wave Line-interactive UPS 750 VA – 3,000 VA
SPS ADVANCE RT: Advanced protection for networks and IT servers
With sine-wave output Line-interactive technology, Salicru’s SPS ADVANCE RT series is a UPS which provides the best possible
performance on the market and comes in formats including the convertible tower/rack format (2U) with directable LCD display to be
integrated in any professional computer environment, with an output power factor of 0.9 which, along with sine-wave output form
waveform, makes it compatible with all current active PFC IT servers.
Furthermore, the possibilities of communication via RS-232 + USB + SNMP along with the different multiplatform management and
monitoring softwares enable the series to be adapted to any computer system. Also outstanding are the EPO (Emergency Power Off)
systems for emergency shutdowns, configurable and prioritisable output sockets, the Green-mode function for power saving and the
extended autonomy options for applications requiring longer back-up periods.
The powers available are: 750 VA, 1,000 VA, 1,500 VA, 2,000 VA and 3,000 VA.
Performances
· Line-interactive UPS with sine-wave output.
· Output power factor = 0.9.
· Permanent stabilisation.
· Directable graphic screen.
· Tower/rack convertible.
· Rack assembly height of 2U.
· Includes pedestal (tower) and ears (rack).
· Selectable and prioritisable load control.(1)
· Green-mode function.
· Series communication (RS-232) and USB interfaces.
· Monitoring software for Windows, Unix, Linux and
Mac.
· Smart slot for SNMP/relays.(1)
· Data/modem line protection.
· Extended autonomy available.(1)
· Automatic frequency detector.
· EPO – Emergency Power Off.(1)
· Cold Start function for starting from batteries.
· Self test on every start-up and/or manual.
· Battery replacement warning system.
· SLC Greenergy solution.
SPS ADVANCE RT
(1) For models ≥1,500 VA
Applications: Versatility and integration for computer environments
All of the described performances result in a UPS that is reliable, efficient, flexible and manageable, and is the best option for
protecting all kinds of servers, including those with an active PFC power supply. Redundant power solutions are also possible by installing
two SPS ADVANCE RT units along with a Salicru SPS.16.STS automatic transfer system.
Increased security for all IT applications, such as servers, VoIP telephony, network electronics and associated peripherals.
2
YEARS
WARRANTY
REF. JM819C01 CODE 401AB000611 ED. FEBRUARY 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
ASK FOR LOCAL CONDITIONS
SPS ADVANCE RT
Sine-wave Line-interactive UPS 750 VA – 3,000 VA
Connections
TECHNICAL SPECIFICATIONS
MODEL
750 VA 1000 VA 1500 VA 2000 VA 3000 VA
Line-interactive with pure sine-wave output
Voltage
220 / 230 / 240 V
Volatge range
±20% on Normal mode; -30% +20% on Generator mode (1)
Stabiliser
Buck-Boost
50 / 60 Hz ±5 Hz on Normal mode; 40÷70 Hz on Generator mode (1)
Frequency range
Transient absorption capacity
SPS.1500.ADV RT
OUTPUT
Active power (W)
6,5 kA
675
900
1350
0.9
Power factor
Voltage
±5% RMS
Total Harmonic Distortion (THDv)
IEC type AC outputs, configurable.
Modem/mains active protector.
SNMP/relays smart slot.
AC input.
RS-232 / opto coupler interface.
USB port.
Emergency Power Off (EPO).
<3%
Frequency
50 / 60 Hz
±0.1 Hz
Frequency accurancy (Bat. mode)
Wave form
Overload
Pure sine-wave
Line mode
Battery mode
110% shutdown after 3 minutes;150% shutdown after 200 ms
110% shutdown after 30 seconds;120% shutdown after 100 ms
Short-circuits
Output sockets
Yes
Type
Quantity
Display
Groups
TRANSFER TIME Inverter-mains
Type
BATTERY
8
8+1
4
Yes, two groups for priority and non-priority loads (2)
5 hours
Yes
Yes
Orientable LCD display
Autonomy mode
Beep every 4 seconds
Low battery
Beep every second
UPS fault
Continuous beep
Beep every second
Battery replacement
GENERALS
Continuous beep
Operating altitude
1500 m.a.s.l.
Relative humidity
Up to 95%, non-condensing
Operating temperature
0º C ÷ +40º C
Acoustic noise @ 1 metre
INTERFACE
<40 dB
Monitoring software
Yes
Opto couplers
No
Yes
USB
Apparent
power (VA)
Active
power (W)
SPS.750.ADV RT
750
675
SPS.1000.ADV RT
1,000
900
SPS.1500.ADV RT
1,500
1,350
SPS.2000.ADV RT
2,000
1,800
SPS.3000.ADV RT
3,000
2,700
Yes
SNMP
No
Emergency Power Off (E.P.O.)
No
Yes
Yes
Transient Protection modem/mains
Dry contacts
STANDARDS
<45 dB
For Windows, Unix, Linux and Mac
RS-232
Output FP = 0,9
Model
4 hours
Starting from batteries (Cold Start)
Green-mode
Overload
1. Available battery level.
2. Connected load level.
3. UPS status / user adjustments.
4. Voltage / frequency / input bases.
5. Voltage / frequency / output bases.
6. Warning / adjustment indicator.
IEC320 C13 +
IEC320 C19
2 ÷ 6 ms
Recharge time at 90%
INDICATORS
AUDIBLE
ALARMS
IEC320 C13
Sealed lead acid, AGM and free maintenance
10 minutes
Typical back up time (3)
FUNCTIONS
2700
220 / 230 / 240 V
Voltage accurancy (Bat. mode)
1.
2.
3.
4.
5.
6.
7.
1800
Yes
No
Safety
Optional
EN-62040-1-1; EN-60950-1
Electromagnetic Compatibility (EMC)
EN-62040-2
Operating
EN-62040-3
Quality and Environmental managament
ISO 9001 and ISO 14001
(1) Power reduction of 15%
(2) For models ≥1,500 VA
(3) At 75% of load
+30% of active power over other UPS with PF=0.7.
Salicru warranty
· Online registry at support.salicru.com.
· 2 year warranty, including batteries.
· Possibility of extending the warranty period.
@salicru_SA
RANGE
MODEL
SPS.750.ADV RT
SPS.1000.ADV RT
SPS.1500.ADV RT
SPS.2000.ADV RT
SPS.3000.ADV RT
Dimensions and weights for standar back up
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
POWER
DIMENSIONS
WEIGHT
750 / 675
1,000 / 900
1,500 / 1,350
2,000 / 1,800
3,000 / 2,700
436 x 438 x 89 (2U)
436 x 438 x 89 (2U)
436 x 438 x 89 (2U)
608 x 438 x 89 (2U)
608 x 438 x 89 (2U)
15
16
18.5
28
29
(VA / W)
(D x W x H mm.)
(Kg)
Data may change without previous notice.
TECHNOLOGY
INPUT
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SPS.16.STS
Automatic transfer system
SPS.16.STS: Redundancy in power supply sources
The Salicru SPS.16.STS is basically an automatic, single phase switch with two input AC lines, which uses two sine-wave power
supply sources to provide output voltage to load/s.
The SPS.16.STS is factory programmed with mains 1 as priority and mains 2 as reserve. Users can change this using the communication
software. Each time the SPS.16.STS is started, the system will start up with the criteria established the last time it was programmed.
It is possible to switch from mains 1 to mains 2 or vice versa using the BP2 pushbutton, and this change is recorded in the internal
memory. The power supply of the load/s is transfered from one mains to the other if the voltage and/or frequency of the priority source
is off-margins.
The LEDs on the control panel report the state of the equipment and operation at all times, and this panel is an easy-to-understand,
practical interface for any operator.
Performance
. Break Before Make.
. Automatic backfeed protection, as per standard EN 62310-1.
. Overloading and short-circuit protection in both mains (using
accessible fuses and 10A thermal relays).
. Redundant internal power supply (from mains 1 and 2).
. Alternating current detector (voltage and current detector).
. Output detector (current detector).
. Control panel with LED.
. Auxiliary contact for external RPO.
. IP30 protection index.
. The SPS.16.STS can transfer with P/N input wiring error.
. The two system inputs can be different phases of the same
three-phase N/R and N/S mains.
. Audible alarm silencer.
SPS.16.STS
Applications: A reliable, cheap and simple solution
Mains 1
Load/s
Mains 2
2
YEARS
WARRANTY
REF. JM809B01 CODE 401AB000624 ED. MARCH 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
ASK FOR LOCAL CONDITIONS
SPS.16.STS
Automatic transfer system
TECHNICAL SPECIFICATIONS
MODEL
INPUT
SPS.16.STS
Nominal voltage
230 V (220/230/240 V selectable)
Voltage range
160 ÷ 290 Vac
Acceptable voltage range
±12% ÷ ±20% (±12% as standard)
Nominal current
1.
2.
3.
4.
LED display.
RPO.
RS-232.
Dry contact interface.
OUTPUT
16 A
Nominal frequency
Frequency range
50/60 Hz (auto selectable)
±5% ÷ ±15% (±15% as standard)
Voltage
230 V (220/230/240 V selectable)
50/60 Hz (auto selectable)
Frequency
Transfer time
Overload capacity 101% ÷ 125% (20A)
16 A
<15 ms
12 s (input relay disconnection)
Overload capacity 126% ÷ 150% (24A)
8 s (input relay disconnection)
Overload capacity 151% ÷ 210% (33.6A)
4 s (input relay disconnection)
Overload capacity 211% ÷ 300% (48A)
2 s (input relay disconnection)
Current
Rear view
Fuse protection
Short-circuit
GENERALS
Operating temperature
0º C ÷ +40º C
Working relative humidity
20% ÷85%, non-condensing
Storage temperature
-20ºC ÷ 70ºC permanent
Storage relative humidity
10% ÷90%, non.condensing
Operating altitude
1.
2.
3.
4.
5.
≤1,000 m.s.n.m.
Acoustic noise @ 1 metre
<25 dB
Cooling
Natural
IP protection
IEC320-C20 type inputs.
IEC320-C19 type outputs.
10A output thermal protection.
IEC320-C13 type outputs.
Input protection fuses.
STANDARDS
IP 30
Safety
EN-62310-1
Electromagnetic Compatibility (EMC)
IEC-62310-2
Quality and Environmental managament
ISO 9001 and ISO 14001
RANGE
Display
MODEL
SPS.16.STS
8
1.
2.
3.
4.
5.
6.
7.
8.
9.
9
Load supplied from PS1 priority mains.
State of the PS1 mains.
PS1 mains selected.
PS1 or PS2 mains selector.
PS2 mains selected.
State of the PS2 mains.
Load supplied from PS2 secondary mains.
Alarm indication.
Alarm silencer.
Servicies
. Pre-sale and after sale advisory service.
. Telephone technical support.
. Maintenance contracts.
. Training courses.
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
CURRENT
DIMENSIONS
WEIGHT
16
315 x 430 x 44 (1U)
8
(A)
(D x W x H mm.)
(Kg)
Data may change without previous notice.
Previous view
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SLC TWIN PRO
Double conversion On-line UPS 700 VA - 20 kVA
SLC TWIN PRO: The solution for maximum On-line protection
Covering a wide range of powers from 700 VA to 20 kVA, Salicru’s SLC TWIN PRO series gives maximum reliability in electrical
protection for businesses and industry. With its double conversion On-line technology, the most reliable technology on the market,
the SLC TWIN PRO series is a single phase output UPS (with single phase input from 700 VA to 10 kVA and three-phase input
from 8 kVA to 20 kVA), with an output power factor of 0.9 (1), broad communication options via interface + monitoring/automatic file
closing shutdown software, batteries for standard autonomy integrated in the cabinet itself, option of extending back-up for processes
requiring greater available autonomy and options of parallel/redundant operation up to 4 units (1) for installations growing in qualitative
and quantitative demands.
Added performances include the standard static and maintenance bypasses (1), the low input current distortion (THDi) under 5%,
small footprint in both standard and extended autonomies, full information obtained from the LCD/graphic display or the possibility of
working in frequency converter mode.
Performances
· Double conversion On-line UPS.
· Output power factor = 0.9 (up to 3 kVA = 0.8).
· Input current Total Harmonic Distortion (THDi) <5%.
· Control panel with LCD display or graphic display and keyboard.
· Tower format.
· Option of parallel up to 4 units. (1)
· Eco-mode operation.
· Series communications (RS-232) (1) and USB interfaces.
· Monitoring software for Windows, Unix, Linux and Mac.
· Smart slot for SNMP/relays.
· Extended autonomy available.
· Automatic frequency detector.
· Frequency converter function.
· EPO – Emergency Power Off.
· Maintenance bypass. (1)
· Cold Start function for starting from batteries.
· SLC Greenergy solution.
(1) From 4 kVA
SLC TWIN PRO
Applications: Security and flexibility for single phase systems
The largest information losses from computer and telecommunications systems in more than 45% of cases are caused by
disturbances (blackouts, micro cuts, voltage variations, frequency variations,...) in the mains supply. To the information losses we
must add the losses caused by the user’s inactivity during the recovery time and the expense of restoring damaged equipment and
systems.
Salicru’s SLC TWIN PRO series UPS give the best protection for ERP systems, CRM platforms, Business Intelligence (BI), intranets/
extranets,...
2
YEARS
WARRANTY(*)
REF. JM821C01 CODE 401AB000619 ED. FEBRUARY 2014 UNINTERRUPTIBLE POWER SUPPLY (UPS)
ASK FOR LOCAL CONDITIONS
SLC TWIN PRO
(*) Units ≥ 4 kVA: 1 year warranty
Double conversion On-line UPS 700 VA - 20 kVA
Description
TECHNICAL SPECIFICATIONS
TWIN PRO
0,7 ÷ 3 kVA
MODEL
Tower
On-line, double conversion, PFC with double DC bus
Nominal voltage
Voltage range
200 / 208 / 220 / 230 / 240 V (1)
3 x 380 / 400 / 415 V
110 ÷ 276 V (2)
3 x 190÷478+N (2)
Frequency
50 / 60 Hz
Frequency range
±10%
Power factor
≥0.99
Total Harmonic Distortion (THDi)
OUTPUT
Power factor
<5%
0.8
Nominal voltage
0.9
200 / 208 / 220 / 230 / 240 V (1)
Voltage accuracy
±2%
±1%
Maximum slew rate
Frequency synchronisation
SLC-15000-TWIN/3 PRO
1.
2.
3.
4.
5.
6.
7.
8.
9.
SLC-3000-TWIN PRO
USB port.
Emergency Power Off (EPO).
RS-232 interface.
SNMP/AS-400 smart slot.
Parallel port.
Manual maintenance bypass.
AC input.
Schuko type AC outputs.
AC input/output connection terminals.
1 Hz/s
±0.2 Hz
±10%
±0.1 Hz
±0.05 Hz
>88%
92%
>93%
Total Harmonic Distortion (THDv) (2)
≤3% linear load;
≤5% non-linear load
(according to EN 62040-3)
Admissible overload
(normal mode)
Up to 110% during 1 min;
125% during 30 s
Crest factor
Parallel
≤2% linear load;
≤5% non-linear load
(according to EN 62040-3)
Up to 125% during
2 min;
150% during 30 s
3 to 1
No
Nominal voltage
Frequency range
MANUAL BYPASS
Type
BATTERY
Yes, up to 4 units
Yes (‘make before break’ type)
Sealed lead acid, AGM and free maintenance
Against overvoltages, under voltages and alternating current component
Charge type
I/U (Constant current/Constant voltage)
Recharging time
5 ÷ 8 hours at 90%
Temperature compensation
COMMUNICATION Ports
Yes
USB
Monitoring software
RS-232 and USB
For Windows, Unix, Linux and Mac.
FUNCTION MODES Eco-mode
Yes, until 98% efficiency
Green-mode
Yes
No
Frequency converter
Yes (3)
Starting from batteries (Cold Start)
GENERALS
Adaptability
· Extended autonomies.
· Single phase/3-phase input.
· Parallel-redundant system >3 kVA.
· Frequency converter.
· Eco-mode operation.
Services
· Pre-sale and after sale advisory service.
· Technical support by phone.
· Preventive/corrective interventions.
· Maintenance contracts.
· Multiple formulae for maintenance and
telemaintenance (SICRES).
@salicru_SA
www.linkedin.com/company/salicru
Operating altitude
Acoustic noise @ 1 metre
STANDARDS
Yes
0º C ÷ +45º C
Operating temperature
Relative humidity
1. Input voltage x phase and frequency.
2. Output voltage and frequency.
3. UPS status/user adjustments.
4. Connected load level.
5. Battery status.
Up to 110% during
5 min;
130% during 1 min
200 / 208 / 220 / 230 / 240 V (1)
50 / 60 Hz ±10 Hz
No
Protection
CHARGER
Display
mains present
free running
Efficiency
BYPASS
TWIN/3 PRO
8 ÷ 20 kVA
Safety
Up to 95%, non-condensing
1000 m.a.s.l. (with de-rating up to 5000 m.a.s.l.)
<50 dB (4)
<55 dB
EN-62040-1; EN-60950-1; EN-60529
Electromagnetic compatibility (EMC)
Operating
EN-62040-2
VFI according to EN-62040-3
ISO 9001 and ISO 14001
Quality and environmental
(1) Power reduction for 200 V and 208 V versions in single-single units and only for 200 V in three-single
(2) With load at 50%
(3) Power reduction of 40% in single-single models
(4) 8kVA & 10kVA < 55dB
RANGE
MODEL
SLC-700-TWIN PRO
SLC-1000-TWIN PRO
SLC-1500-TWIN PRO
SLC-2000-TWIN PRO
SLC-3000-TWIN PRO
SLC-4000-TWIN PRO
SLC-5000-TWIN PRO
SLC-6000-TWIN PRO
SLC-8000-TWIN PRO
SLC-8000-TWIN/3 PRO
SLC-10000-TWIN PRO
SLC-10000-TWIN/3 PRO
SLC-12000-TWIN/3 PRO
SLC-15000-TWIN/3 PRO
SLC-20000-TWIN/3 PRO
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
POWER
DIMENSIONS
WEIGHT
(Kg)
INPUT/
OUTPUT
700 / 560
1,000 / 800
1,500 / 1,200
2,000 / 1,600
3,000 / 2,400
4,000 / 3,600
5,000 / 4,500
6,000 / 5,400
8,000 / 7,200
8,000 / 7,200
10,000 / 9,000
10,000 / 9,000
12,000 / 10,800
15,000 / 12,000
20,000 / 18,000
400 x 145 x 220
400 x 145 x 220
460 x 192 x 347
460 x 192 x 347
460 x 192 x 347
560 x 260 x 708
560 x 260 x 708
560 x 260 x 708
560 x 260 x 708
560 x 260 x 708
560 x 260 x 708
560 x 260 x 708
650 x 350 x 890
650 x 350 x 890
650 x 350 x 890
13
14
30
31
32
84
85
86
92
92
93
93
181
182
183
II / II
II / II
II / II
II / II
II / II
II / II
II / II
II / II
II / II
III / II
II / II
III / II
III / II
III / II
III / II
(VA / W)
(D x W x H mm,)
Data may change without previous notice.
FORMAT
TECHNOLOGY
INPUT
TWIN PRO
4 ÷ 10 kVA
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SLC TWIN RT
Rack/tower On-line UPS 700 VA a 10,000 VA
SLC TWIN RT: Continuous protection for critical systems
Salicru’s SLC TWIN RT series is a double conversion On-line UPS with an output power factor of 0.9, which can be turned into tower
or rack format and can be set up in parallel (1). The powers range is from 700 VA to 10 kVA. The rack format is highly compact (with
batteries included) and comprises 2U of up to 3 kVA, 3U of 4 to 6 kVA and just 5U for powers of 8 and 10 kVA.
It comes with extensive communications options by graphic display, which can be positioned for the tower or rack formats, and
incorporates USB and RS-232 ports, as well as smart slot for SNMP/relays communication. For applications with broader back-up
requirements, there is the option of additional battery modules.
Above 4 kVA they include a rear plug-in module for electrical connections and a maintenance bypass to enable work to be done without
having to disconnect the loads.
Performances
· Double conversion On-line UPS.
· Output power factor = 0.9.
· Input current Total Harmonic Distortion (THDi) <5%.
· Directable LCD display.
· Convertible between tower and rack.
· Up to 2 units in parallel. (1)
· Includes pedestal (tower) (2) and ears (rack).
· Selectable and priority loads control. (2)
· Eco-mode operation.
· Serial communication interfaces (RS-232) and USB.
· Monitoring software for Windows, Unix, Linux and
Mac.
· Smart slot for SNMP/relays.
· Data/modem line protection. (3)
· Extended back-up available.
· Automatic frequency detector.
· Frequency converter function.
· EPO – Emergency Power Off.
· Cold Start function for starting from batteries.
· Self test on every start up and/or manual.
· SLC Greenergy solution.
SLC TWIN RT
(1) From 4 kVA
(2) Except 10 kVA
(3) Up to 3 kVA (included)
Applications: Security and flexibility for single phase applications
The optimal solution for applications requiring the highest possible protection against all kinds of electrical disturbances (blackouts,
micro cuts, voltage and/or frequency variations, electric noise,...) in a compact unit with all necessary performances.
Secure power supply for all kinds of IT applications, such as voice and data networks, CAD/CAM, documentary management,
unified communications (UC) or video streaming.
2
YEARS
WARRANTY(*)
REF. JM820C01 CODE 401AB000615 ED. FEBRUARY 2014 UNINTERRUPTIBLE POWER SUPPLY (UPS)
ASK FOR LOCAL CONDITIONS
SLC TWIN RT
(*) Units ≥ 4 kVA: 1 year warranty
Rack/tower On-line UPS 700 VA - 10,000 VA
Connections
TECHNICAL SPECIFICATIONS
MODEL
SLC-1500-TWIN RT
Tower / Rack
On-line, double conversion, PFC, double DC bus
208 / 220 / 230 / 240 V (1)
Nominal voltage
Voltage range
120 ÷ 276 V (2)
Frequency
OUTPUT
50 / 60 Hz
Frequency range
±10%
Power factor
≥0.99
Total Harmonic Distortion (THDi)
<5%
Power factor
0.9
Nominal voltage
1.
2.
3.
4.
5.
6.
7.
8.
9.
±1%
Maximum slew rate
1 Hz/s
mains present
free running
Efficiency
Total Harmonic Distortion (THDv)
IEC type AC outputs.
Emergency Power Off (EPO).
USB port.
AC input.
Opto couplers.
SNMP/relays smart slot.
RS-232 interface.
Parallel port.
Maintenance bypass.
Admissible overload
(normal mode)
BYPASS
>93%
≤2% linear load; ≤5% non-linear load (according to EN 62040-3)
Up to 130% during 12 s;
150% during 1.5 s
3 to 1
Yes, up to 2 units
Nominal voltage
208 / 220 / 230 / 240 V (1)
50 / 60 Hz ±10 Hz
Independent bypass line
MANUAL BYPASS
BATTERY
Type
No
Yes
No
Yes (‘make before break’ type)
Sealed lead acid, AGM and free maintenance
Protection
CHARGER
Against overvoltages, under voltages and alternating current component
Charge type
I/U (Constant power/Constant voltage)
Recharging time
3 hours at 90%
Compensation voltage for temperature
SLC-700-TWIN RT
700
630
SLC-1000-TWIN RT
1,000
900
SLC-1500-TWIN RT
1,500
1,350
SLC-2000-TWIN RT
2,000
1,800
SLC-3000-TWIN RT
3,000
2,700
SLC-4000-TWIN RT
4,000
3,600
SLC-5000-TWIN RT
5,000
4,500
SLC-6000-TWIN RT
6,000
5,400
SLC-8000-TWIN RT
8,000
7,200
SLC-10000-TWIN RT
10,000
9,000
Power Factor (PF) = 0.9.
+30% of active power over other UPS with FP = 0.7.
+efficiency (98%) with Eco-mode function.
Communications
· RS-232 interface.
· USB interface.
· SNMP/relays smart slot.
· Monitoring and management software for Windows, Linux, Unix and Mac.
· SNMP/web adapter. (1)
· AS-400 card. (1)
· MODBUS protocol. (1)
· Temperature-humidity sensor. (1)
Yes
COMMUNICATION Ports
RS-232 and USB
Monitoring software
For Windows, Unix, Linux and Mac.
Emergency Power Off (E.P.O.)
FUNCTION MODES
Yes
Eco-mode
Yes, up to 98% efficiency
Starting free running (Cold Start)
Yes
Frequency converter
Yes (4)
INDICATORS
GENERALS
Directable LCD display
Operating temperature
0º C ÷ +40º C
1000 m.a.s.l. (degradation power up to 5000 m.a.s.l.)
<45 dB (5)
Safety
<55 dB
EN-62040-1; EN-60950-1; EN-60529
Electromagnetic compatibility (EMC)
EN-62040-2
Operating
VFI according to EN-62040-3
Quality and environmental
(1) Power reduction at 208 V for
units ≥ 4 kVA
0º C ÷ +45º C
Up to 95%, non-condensing
Relative humidity
Operating altitude
Acoustic noise @ 1 metre
STANDARDS
Up to 125% during 2 min;
150% during 30 s
No
Admissible frequency range
Active
power (W)
@salicru_SA
±0.1 Hz
>89% (3)
Parallel
Apparent
power (VA)
(1) Optional
±10%
±0.2 Hz
Crest factor
Higher output power
Model
Voltage accuracy
Frequency
synchronization
SLC-6000-TWIN RT
208 / 220 / 230 / 240 V (1)
ISO 9001 and ISO 14001
(2) With 50% of load
(3) For units of 700 and 1000 VA >87%
(4) Power reduction of 30%
(5) Models > 1500 VA is < 50 dB
RANGE
MODEL
SLC-700-TWIN RT
SLC-1000-TWIN RT
SLC-1500-TWIN RT
SLC-2000-TWIN RT
SLC-3000-TWIN RT
SLC-4000-TWIN RT
SLC-5000-TWIN RT
SLC-6000-TWIN RT
SLC-8000-TWIN RT
SLC-10000-TWIN RT
POWER
DIMENSIONS
WEIGHT
700 / 630
1,000 / 900
1,500 / 1,350
2,000 / 1,800
3,000 / 2,700
4,000 / 3,600
5,000 / 4,500
6,000 / 5,400
8,000 / 7,200
10,000 / 9,000
435 x 438 x 89 (2U)
435 x 438 x 89 (2U)
435 x 438 x 89 (2U)
435 x 438 x 89 (2U)
608 x 438 x 89 (2U)
630 x 438 x 133 (3U)
630 x 438 x 133 (3U)
630 x 438 x 133 (3U)
640 x 438 x 223 (5U)
640 x 438 x 223 (5U)
14
15
19
20
29
45
46
47
82
83
(VA / W)
Dimensions and weight for standard back-up models
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(D x W x H mm.)
(Kg)
Data may change without previous notice.
FORMAT
TECHNOLOGY
INPUT
SLC TWIN RT 0,7 - 3 kVA SLC TWIN RT 4 - 10 kVA
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SLC ADAPT
Modular UPS from 10 to 100 kVA
SLC ADAPT: Adaptable, scalable and modular protection
Modularity is something needed by applications (telecommunications, DPC, railway sector, calculation centres) that require availability,
growth and redundancy in addition to easy maintenance and lower ownership costs.
Salicru’s SLC ADAPT series starts with independent 10 kVA UPS modules to enable power extensions and n+n redundant
configurations thanks to the system’s full modularity, without disconnecting the system (hot-swappable) and no need for tools, in
configurations up to 100 kVA. A centralised control module is in charge of the communications, the configuration and monitoring the
system. The system is completed with a centralised bypass that charges the loads with the best power supply available.
The flexibility of the SLC ADAPT series allows its multiple formats to adapt to the environment thanks to its presentations in subracks
of 5 or 10 modules for integration in existing racks or in finished rack cabinets that include input/output switches, maintenance bypass
and back-up (the batteries can be housed in the same cabinet or in additional cabinets depending on the required power and autonomy
configurations).
Performances
. Double-conversion, On-line technology.
. Completely independent UPS module.
. Subracks of 50 kVA and 100 kVA with 10 kVA modules.
. Compact and light inverter/ondulator UPS format (9 kg x module).
. Power upgrading and redundant set up by adding modules.
. All options configured with just 3 references.
. Possible three phase/single-phase configurations up to 40 kVA.
. System efficiency up to 96% (3-level inverter).
. Unit input power factor (FP=1).
. Low input current distortion (THDi=3%).
. Modules extended and changed by the users themselves.
. Large variety of options available.
. Parallel/redundant capability by adding systems.
. Mean time to repair (MTTR) under 5 minutes.
. Inversion depending on growth or redundancy needs (pay as you
grow).
. SLC Greenergy solution.
SLC ADAPT 5
SLC ADAPT 10
SLC ADAPT control module
Applications: Redundant protection for critical applications
The modularity of these systems is used for different purposes:
- To increase the power simply, by adding modules as the installation grows. In this configuration, all of the installed modules are
used to give power.
- To achieve redundant systems, where there is always a number of modules prepared to take over in the event of any other failing
unexpectedly. A redundant n+1 system therefore has 1 module ready for this; in other words, when the system gives maximum
power, this is not taken into account. For example, a 3+2 system uses 3 modules to give power and 2 to make up for any problem
there might be in these 3.
REF. JM792B01 CODE 401AB000599 ED. MARCH 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
SLC ADAPT
Modularity
Modular UPS from 10 to 100 kVA
TECHNICAL SPECIFICATIONS
MODEL
On-line, double conversion, HF
Nominal voltage
Single phase 220 / 230 / 240 V
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph+ N)
Voltage range
+20% / -27 % (@ 3x400V / 230V Ph-N)
50 / 60 Hz
Frequency
3%
Total Harmonic Distortion (THDi)
Power factor
OUTPUT
Nominal voltage
Precision
Frequency
1
Single phase 220 / 230 / 240 V
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph+N)
Steady state
±1%
Dynamic state
±2% (load variations 100% - 0% - 100%)
Synchronised
50 / 60 Hz ±0.5 ±1 ±2 ±3 ±4 Hz (selectable)
Free running
50 / 60 Hz ±0.1%
1 Hz/s
Max. synchronisation speed
<2%
Total Harmonic Distortion (THDv)
110% during 10 min / 125% during 60 s
Admissible overload
3:1
Admissible crest factor
Total efficiency
STATIC BYPASS
96.0%
Hibrid control by microprocessor
Type and activation criteria
Voltage
Single phase 220 / 230 / 240 V
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph+N)
Frequency
50 / 60 Hz
Transfer time
Nil
MANUAL BYPASS Type
Without interruption
Voltage
1.
2.
3.
4.
5.
6.
7.
8.
UPS module.
Control module.
Bypass module.
Subrack.
Input, output, bypass and battery switches.
Battery protections.
Module’s input protections.
Input, output, bypass and battery terminals.
RECTIFIER
Frequency
50 / 60 Hz
Structure
Three-phase IGBT complete wave, soft start and PFC
Protection
BATTERIES
Against transitory over-voltages
Type
Lead acid, sealed, maintenance free
Recharging time
4-6 hours, to 80% of capacity
Protection
Against over-voltages and under-voltages
Charge voltage regulation
COMUNICATION
Batt-Watch
Ports
RS-232
Interface to relays
GENERALS
6 programmable
Operating temperature
0º C ÷ +40º C
Relative humidity
Operating altitude
Options
Up to 95%, non-condensing
2400 m.a.s.l.
Acoustic noise @ 1 metre
. Extended autonomies.
. Isolation transformer.
. External manual bypass.
. Web/SNMP or GPRS adapter.
. Monitoring, management and shutdown
softwares.
. 1 x additional RS-232/485 port.
. BACS II, monitoring, adjustment and battery
alarm.
Technical support and service
. Pre-sales and after-sales advice.
. Start-up.
. Technical support by telephone.
. Preventive/corrective services.
. Maintenance contracts.
. Telemaintenance contracts SICRES.
. Training courses.
@salicru_SA
Single phase 220 / 230 / 240 V
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph+N)
STANDARDS
Data may change without previous notice.
TECHNOLOGY
INPUT
SLC ADAPT
<52 dB (1)
Safety
EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC)
Operating
EN-62040-2
VFI-SS-111 according to EN-62040-3
Quality and Environmental Management
ISO 9001 and ISO 14001
(1) For a full loaded module.
RANGE
MODEL
1SLC-10-ADAPT/5
2SLC-10-ADAPT/5
3SLC-10-ADAPT/5
4SLC-10-ADAPT/5
5SLC-10-ADAPT/5
6SLC-10-ADAPT/10
7SLC-10-ADAPT/10
8SLC-10-ADAPT/10
9SLC-10-ADAPT/10
10SLC-10-ADAPT/10
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
POWER
(kVA)
10
20
30
40
50
60
70
80
90
100
SUBRACK VERSION
42U RACK CABINET VERSION
DIMENSIONS
WEIGHT
DIMENSIONS
WEIGHT
(D x W x H mm.)
(Kg)
(D x W x H mm.)
(Kg)
673 x 19” x 972
673 x 19” x 972
673 x 19” x 972
673 x 19” x 972
673 x 19” x 972
652 x 19” x 1416
652 x 19” x 1416
652 x 19” x 1416
652 x 19” x 1416
652 x 19” x 1416
43
52
61
70
79
64
73
82
91
100
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
1000 x 600 x 2020
231
240
249
258
267
299
308
317
326
335
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SLC CUBE3+
Uninterruptible
supply system from 7.5 to 200 kVA
SLC CUBE3+: Energy efficiency with superior
electricalpower
protection
Salicru’s SLC CUBE3+ series is a UPS range featuring high-performance, On-line double conversion (VFI) technology that provides a reliable, high-quality power supply and, at the same time, achieves significant energy and financial savings in terms of installation and operating
costs.
Particularly noteworthy is the unit’s input power factor (PF=1) and its extremely low distortion rate (THDi even lower than 1%), which help to
reduce installation and operating costs, and contribute to improving the quality of the electrical network.
The output power factor (PF=0.9) also stands out, providing optimum electrical protection for computer systems and low harmonic output
distortion (THDv even lower than 0.5%), enabling it to protect any type of load (inductive, resistive, capacitive or mixed). In addition, the
performance achieved (up to 95% in On-line mode and 98% in Smart Eco-mode) produces significant energy consumption savings and
reduces air conditioning needs.
For a full optimum solution, the SLC CUBE3+ provides maximum adaptability (even with the standard model), the possibility of
parallel redundant expansion and extensive communication options. Finally, also worth noting is the unit’s lightweight design and reduced
dimensions, enabling it to be easily installed and ensuring that footprint is minimal.
Performances
· On-line double conversion (VFI) technology with DSP control.
. Input power factor 1, for better performance.
. Very low input current harmonic distortion (THDi as low as <1%).
. Total flexibility in input/output voltage. (1)
. Designed to withstand any type of load.
. Batt-Watch function for monitoring and battery care.
. High output power factor (PF=0.9). (2)
. Very low output voltage distortion rate (THDv even lower than 0.5%).
. On-line mode efficiency of up to 95%.
. Smart Eco-mode efficiency of up to 98%.
. Very compact design with minimal footprint.
. Can be integrated into the most advanced IT environments.
. Parallel redundant configuration (N+1) for critical installations. (3)
. Built with 80% recyclable materials.
. Bluetooth application display for Android (up to 10 m).
. SLC Greenergy solution.
(1) Single/single, single/three and three/single configurations up to 60 kVA
(2) Up to 120 kVA
(3) Up to 4 units
SLC CUBE3 +
Applications: Designed to protect any type of environment
High-end design features plus great flexibility capacity (options, power upgrading, communications,…) make SLC CUBE3+ series the
best option to protect and secure a wide range of environments: data-centres, hosting, housing, IT-networks, server farms, voice and
data networks,…
REF. JM842A01 CODE 401AB000659 ED. OCTOBER 2013 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
SLC CUBE3+
High efficiency
High performance in On-line and
Smart Eco-mode operation.
Uninterruptible power supply system from 7.5 to 200 kVA
100%
99%
TECHNICAL SPECIFICATIONS
98%
MODEL
96%
95%
TECHNOLOGY
INPUT
94%
93%
92%
On-line, double conversion, HF, DSP control
Nominal voltage (1)
Single-phase 120 / 127 / 220 / 230 / 240 V
Three-phase 3 x 208 / 3 x 220 / 3 x 380 / 3 x 400 / 3 x 415 V (3P + N)
+15% / -20% (configurable)
Voltage margin
91%
50 / 60 Hz
Frequency
90%
20%
30%
40%
50%
60%
70%
80%
90%
Total Harmonic Distortion 7.5 ÷ 20 kVA
(THDi)
30 ÷ 80 kVA
100%
Load
CARGA
Load
Smart Eco-Mode
On-Line
100 ÷ 200 kVA
Low harmonic distortion
100% load: <1.5% / 50% load: <2.5% / 10% load: <6.0%
100% load: <1.0% / 50% load: <2.0% / 10% load: <5.0%
100% load: <2.0% / 50% load: <4.0% / 10% load: <8.0%
>0.99 from 10% load / 1 at 100% load
Power factor
The lowest harmonic distortion in the market.
THDi
THDi
SLC CUBE3+
Three-phase IGBT full wave, soft start, PFC, transformerless
Rectifier topology
OUTPUT
Nominal voltage (1)
Single-phase 120 / 127 / 220 / 230 / 240 V
Three-phase 3 x 208 / 3 x 220 / 3 x 380 / 3 x 400 / 3 x 415 V (3P + N)
12%
Accuracy
Frequency
8%
± 1% steady / ± 2% dynamic
State
10%
Response time
20 ms for load steps 0% ÷ 100% and voltage drop up to -5%
Synchronised
Free running
50/60 Hz ±4% (selectable)
6%
Maximum synchronisation speed
4%
Total Harmonic Distortion Linear load
(THDv)
Nonlinear load
2%
50/60 Hz ±0.05%
From 1 Hz/s to 10 Hz/s (programmable)
<0.5%
7.5 ÷ 80 kVA: <1.5% / 100 ÷ 200 kVA: <2% (EN-62040-3)
Output Power Factor (2)
0.9
Admissible overload
0%
0%
25%
Competitor
COMPETENCIA
50%
75%
SLC
CUBE3+
SLC CUBE3+
125% for 10 min / 150% for 60 s
Admissible crest factor
100%
Load
CARGA
>3:1
Total efficiency in On-line mode
7.5÷60 kVA: 92.0%÷93.0% / 80÷200 kVA: 94.0%÷95.0%
Efficiency in Smart Eco-mode
STATIC BYPASS
Options
Transfer time
· Ethernet/SNMP adapter or GPRS modem.
. SICRES adapter for remote management.
. Android wireless link.
. Monitoring, management and shutdown
software.
. 1 x additional RS-232/485 serial port.
. Extended backup times.
. Common battery set for parallel systems.
. BACS II, battery monitoring, regulation and
alarms.
. Dual-level charger for NiCd batteries.
. Separate bypass line.
. Single/single, single/three and three/single
configurations.(1)
. External manual bypass.
. Temperature and humidity sensors.
. External display.
. Frequency converter function.
(1) Up to 60 kVA
Solid state, controlled by microprocessor
On-line mode
Nil
4 ms (typical)
Smart Eco-mode
Transfer to bypass
Immediate, for overloads exceeding 150%
Retransfer
Automatic, after alarm deactivation
MANUAL BYPASS Type
Type (standard)
BATTERIES
Without interruption
Lead acid, sealed, maintenance free
Batt-Watch
Charge voltage regulation
COMMUNICATION Ports
1 x RS-232/485, with MODBUS protocol
Interface to relays
4 x AC failure, bypass, low battery and general
Free slots
1, for SNMP/SICRES
Parallel connection
GENERAL
2 x connectors
Operating temperature
0° C ÷ +40° C
Relative humidity
STANDARDS
Up to 95%, non-condensing
Operating altitude
2,400 masl
Acoustic noise at 1 metre
<52 dB(A) (3)
Safety
EN-62040-1-2; EN-60950-1
Electromagnetic Compatibility (EMC)
EN-62040-2
Operating
VFI-SS-111 according to EN 62040-3
Quality and Environmental Management
ISO 9001 and ISO 14001
(1) Single-phase 120 / 127 V available up to 30 kVA inclusive and three-phase 3 x 208 / 3 x 220 V available up to 100 kVA inclusive.
(2) Up to 120 kVA inclusive at three/three-phase configurations.
(3) <65 dB(A) for 80 to 120 kVA models / <70 dB(A) for 160 and 200 kVA models.
RANGE
Technical support and service
· Pre and post-sales advice.
. Start-up.
. Telephone technical support.
. Preventative/corrective intervention.
. Maintenance contracts.
. SICRES remote maintenance contracts.
. Training courses.
@salicru_SA
Up to 98%
Type and activation criteria
Data may change without previous notice.
Efficiency
EFICIENCIA
97%
www.linkedin.com/company/salicru
MODEL
SLC-7.5-CUBE3+
SLC-10-CUBE3+
SLC-15-CUBE3+
SLC-20-CUBE3+
SLC-30-CUBE3+
SLC-40-CUBE3+
SLC-50-CUBE3+
SLC-60-CUBE3+
SLC-80-CUBE3+
SLC-100-CUBE3+
SLC-120-CUBE3+
SLC-160-CUBE3+
SLC-200-CUBE3+
POWER
(kVA / kW)
Nº CABINETS
(UPS + BAT)
UPS DIMENSIONS
(D x W x H mm)
WEIGHT
(kg)
BAT DIMENSIONS
(D x W x H mm)
WEIGHT
(kg)
7.5 / 6.75
10 / 9
15 / 13.5
20 / 18
30 / 27
40 / 36
50 / 45
60 / 54
80 / 72
100 / 90
120 / 108
160 / 128
200 / 160
1+0
1+0
1+0
1+0
1+ 0
1+0
1+1
1+1
1+1
1+1
1+1
1+1
1+1
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
770 x 450 x 1100
880 x 590 x 1320
880 x 590 x 1320
880 x 590 x 1320
850 x 900 x 1900
850 x 900 x 1900
210
210
212
215
310
400
185
185
265
290
290
540
550
770 x 450 x 1100
770 x 450 x 1100
1050 x 650 x 1320
1050 x 650 x 1320
1050 x 650 x 1320
850 x 1300 x 1900
850 x 1300 x 1900
510
510
1020
1020
1020
1655
1690
Nomenclature, dimensions and weights for units with input voltage 3 x 400 V, output voltage 3 x 400 V and standard backup time.
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SLC X-TRA
Uninterruptible Power Supplies from 100 to 800 kVA
SLC X-TRA: High performance protection for major critical applications
The SLC X-TRA series is one of the most reliable, high-performance three-phase Uninterruptible Power Supply system (UPS) on
the market, and provides protection and quality energy for a wide range of applications. Based on the Voltage and Frequency
Independent (VFI) mode of operation, it has been developed using double conversion IGBT technology with DSP control, which gives
considerable savings in the costs of operation and installation while it offers maximum protection for the connected loads. This
series has been conceived to offer the best guarantees in meeting customers’ requirements and needs and has been designed in full
respect of the most demanding environmental regulations.
The SLC X-TRA series features power range from 100 to 800 kVA in a very compact format for easier installation. Plus, the reliability
of the system can be increased with the installation of several redundant units or it can grow in parallel based on the needs of the
installation.
Performances
. On-line, double conversion, DSP control.
. Double input connection to increase the availability.
. Input power factor >0.99.
. Total harmonic distortion of input current (THDi) < 3%.
. High energy efficiency between 95% and 96%.
. Zig-zag transformer on the output inverter.
. Parallel for redundancy or increase the power capacity.
. Compatible with generating sets.
. Selectable operation inverter/Smart Eco-mode.
. Efficiency in Smart Eco-mode >98%.
. Prepared to bear loads with FP =0.9.
. Batt-Watch battery monitoring and care.
. Calculates available back-up time in a long-term failure.
. Compact format to save on installation space.
. Easy installation, operation and maintenance.
. A wide range of control and monitoring options.
. Large variety of options available.
. SLC Greenergy solution.
SLC X-TRA 100 kVA
Applications: Guaranteed energy for all environments
Data centres: Ensures the functionality of environments and prevents losses caused by mains failures.
IT-Networks: Prevent costs due to service interruptions or loss of information.
Financial services: Maintains online operability of financial transactions and operations.
Industrial processes: Protects productivity in electrically complicated environments.
Telecommunications: Prevents supply failures that can suspend communication between subscribers.
Infrastructures: Safeguards the instruments/equipment and ensures the proper management of the systems.
SLC X-TRA 600 kVA
REF. JM805C01 CODE 401AB000584 ED. MARCH 2014 UNINTERRUPTIBLE POWER SUPPLIES (UPS)
SLC X-TRA
Parallel growth
Rectifier connection
Bypass connection
UPS 1
Uninterruptible Power Supplies from 100 to 800 kVA
UPS 2
UPS 3
TECHNICAL SPECIFICATIONS
MODEL
Parallel diagram
The parallel UPS can be configured to achieve
redundancy or increase the power capacity of the
system. Parallel control is fully digital and works
for active as well as reactive power in each phase,
achieving an exact load distribution between the
UPS units in transitory conditions.
On-line, double conversion, DSP control
Nominal voltage
Three-phase 3 x 380 V / 3 x 400 V / 3 x 415 V
Voltage margin
+15% / -20% (@ 3 x 400 V)
50/60 Hz (45-65 Hz)
Frequency
OUTPUT
Total Harmonic Distortion (THDi)
<3%
Power factor
>0.99
Three-phase 3 x 380 V / 3 x 400 V / 3 x 415 V (3Ph+N)
Nominal voltage
Precision
±1% Steady state; ±5% Dynamic state (100% unbalanced) <20 ms recovery time
Frequency
50/60 Hz
<1%
Total Harmonic Distortion (THDv) Linerar load
<5%
Non-linear load
Efficiency
High energy efficiency
95% ÷ 96%
On-line
>98%
Smart Eco-mode
125% for 10 min. / 150% for 1 min.
Admisible overload
100,00
STATIC BYPASS
99,00
Independent
Input
98,00
Three-phase 3 x 380 / 3 x 400 / 3 x 415 V (3Ph + N)
Voltage
97,00
% Efficiency
Solid state, control by microprocessor
Type and activation criteria
50/60 Hz
Frequency
96,00
Nil
95,00
Transfer time
94,00
Transfer to bypass
Immediate for overloads of over 150%
93,00
Retransfer
Automatic after alarm disappearance
92,00
Admisible overload
91,00
90,00
20
30
40
Smart Eco-mode
50
60
70
80
90
100
% Load
On-line
High performance both On-line mode (between
95% and 96%) and Smart Eco-mode (>98%),
reducing operating costs, implementation costs
(no need to oversize the wiring), air conditioning
costs (without increasing cooling requirements)
and working costs (saving energy consumed).
Adaptability
. Parallel/redundant kit.
. Extended autonomies.
. BACS II.
. MODBUS protocol + RS-485 interface.
. SICRES platform for remote telemanagement.
. Ethernet / SNMP adapter or GPRS modem.
. Monitoring, management and shutdown software.
. Common input connection.
. Top cable input.
. External manual bypass.
. Auto-transformers to adapt the voltage.
Total availability
. Advisory service before and after the sale.
. Start up.
. Telephone technical support.
. Preventive / corrective interventions.
. Maintenance contracts.
. Telemaintenance contracts SICRES.
. Training courses.
1000% for 1 cycle
MANUAL
BYPASS
Type
RECTIFIER
Structure
Three-phase IGBT complete wave, soft start and PFC
Protection
Against transitory overvoltages
Lead acid, sealed, maintenance free
BATTERIES
Without interruption
As standard
100 – 300 kVA
Type (1)
Against overvoltages and undervoltages
Protection
4 hours, @ 80% of capacity
Charging time
Batt-Watch
Charge voltage regulation
Manual + Automatic
Test
COMMUNICATION Ports
RS-232, USB, Emergency Power Off (EPO),
Port for monitoring battery switch
LCD + LED block diagram
Display
GENERALS
0º C ÷ +40º C
Operating temperature
Relative humidity
Up to 95%, non-condensing
Operating altitude
<1,000 m.a.s.l.
<60 dB
Acoustic noise @ 1 metre
STANDARDS
EN-62040-1-2; EN-60950-1
Safety
EN-62040-2
Electromagnetic Compatibility (EMC)
VFI-SS-111 according to EN-62040-3
Operating
ISO 9001 and ISO 14001
Quality and Environmental Management
(1) Ni-Cd under request.
RANGE
POWER
MODEL
(kVA / kW)
SLC-100-XTRA
SLC-125-XTRA
SLC-160-XTRA
SLC-200-XTRA
SLC-250-XTRA
SLC-300-XTRA
SLC-400-XTRA
SLC-500-XTRA
SLC-600-XTRA
SLC-800-XTRA
100 / 90
125 / 112.5
160 / 144
200 / 180
250 / 225
300 / 270
400 / 360
500 / 450
600 / 540
800 / 720
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
Nº CABINETS UPS DIMENSIONS WEIGHT BAT. DIMENSIONS WEIGHT
(UPS + BAT)
(D x W x H mm)
(kg)
(D x W x H mm)
(kg)
1+1
1+1
1+1
1+1
1+1
1+2
1+2
1+2
1+2
1+3
865 x 815 x 1705
865 x 815 x 1705
865 x 815 x 1705
895 x 1220 x 1905
895 x 1220 x 1905
895 x 1220 x 1905
990 x 1990 x 1920
990 x 2440 x 2020
990 x 2440 x 2020
990 x 3640 x 1920
630
662
720
870
1020
1200
1820
2220
2400
3600
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
850 x 1300 x 1900
875
1370
1370
1550
1800
1370
1800
1800
2125
1925
Data may change without previous notice.
TECHNOLOGY
INPUT
Up to 8 UPS
Loads
SLC X-TRA
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
DC POWER-S
DC power systems
DC power-S: Compact, flexible and modular DC power supply systems
Salicru’s DC power-S energy systems feature the following components: DC-S rectifier modules, subracks, a control and monitoring
system, a communications module and a DC distribution unit, all situated in a closed cabinet with the possibility of including batteries.
DC power-S system rectifier modules are available in power ratings of 1000, 2000 and 2700 W and output voltages of 48, 110 and 125 Vdc.
Its modular design enables up to 4 modules to be installed in a 19” 2U subrack, achieving very high power density.
The control and monitoring system manages the entire system: input and output measurements, battery charging currents, control of priority
and non-priority loads and communication channels with the outside. The maximum number of rectifiers controlled by a control system is 30,
enabling systems to achieve power ratings of up to 81 kW with N+n redundant configuration options.
The basic version of the communications module has: three programmable relays, a battery temperature sensor and an RS-232/485 channel.
Extended version features a slot for an Ethernet/SNMP adapter, a NiCd electrolyte level detection input and six additional relays.
Performances
. Maximum power per system up to 81 kW.
. Flexible, scalable and N+n redundant systems, configurable for
current demand and future expansion.
. High power density in the modules, up to 27 W/in3.
. High efficiency, up to 95% even with low load.
. Option of single or three-phase power supply.
. DC systems with output voltages of 48, 110 or 125 Vdc.
. Wide operating temperature range from -20º C to +55º C.
. Wide input voltage range from 90 Vac to 290 Vac with power derating.
. Input power factor 1 for better performance.
. Modular design of the rectifiers and control system.
. Output current sharing between rectifiers.
. Front access for easy installation and maintenance.
. Hot-swap and hot-plug functions with automatic adjustment for
module connection/disconnection.
. LLVD and BLVD - disconnection of non-priority loads and for low
battery voltage.
. Full local control and monitoring system with LCD (4x40 characters).
. Communication unit for remote monitoring.
. Monitoring software via Ethernet/SNMP.
. Smart-mode to maximise MTBF (Mean Time Between Failures).
DC power-S
Applications: Redundant protection for critical applications
Salicru’s DC power-S energy systems provide a high-level power supply to always critical telecommunications systems,
ensuring excellent operation without unexpected outages. Because of its modular nature, it can also be expanded according to
needs, thereby optimising the investment. Typical applications include: fixed and mobile communications networks, broadband
access networks and data and telecommunications networks.
REF. JM840A01 CODE 401AB000649 ED. OCTOBER 2013 POWER SUPPLY
System description
DC POWER-S
DC power systems
1
2
TECHNICAL SPECIFICATIONS
MODEL
DC POWER- S
3
AC voltage
4
5
220 / 230 /240 V
3x380 / 400 / 415 V (3Ph+N)
Range (phase-neutral)
90 ÷ 290 Vac(1)
50/60 Hz
Frequency
6
OUTPUT
Power factor
THDi
>0.99 (PFC)
Efficiency
Up to 95.5%
DC voltage
48, 110, 125 V
<5% 0.1
Voltage adjustment range
±1%
Accuracy
7
9
Psophometric noise
10
Load sharing between modules
<2 mV
Active parallel
1000 / 2000 / 2700 W
Rectifier module power
8
30
Maximum number of parallel modules
30 / 60 / 81 kW
Maximum system power (depending on module)
BATTERIES
1. Rectifier module
2. Centralised control
3. Input protection
4. Output distribution
5. Batteries protection
6. Batteries
7. Extended communication
8. Surge protector
9. Input terminals
10. Output terminals
SMART mode
Type
PbCa or NiCd
Constant I/U in accordance with DIN 41773
Charge type
0.1C to 0.3C adjustable
Charging current
Recharge time
Up to 80% in 4 hours (0.2C)
Protection
Against overvoltage, undervoltage and overload
Voltage/temperature compensation
Yes, customisable (mV/°C)
Electrolyte level detection (NiCd battery)
PROTECTION
GENERAL
Load sharing in normal operation.
Optional
Input and output
Battery
Circuit breakers
Fuses
Dielectric strength
4000 V @1 minute
Information
subject to change
Degree of protection
Ventilation notice.
without
IP20
Forced
Acoustic noise at 1 metre
<55 dB(A)
Operating temperature
Storage temperature
Load sharing and cycling of rectifiers in Smartmode operation.
-40°C ÷ +70°C (3)
Relative humidity
Up to 95%, non-condensing
Maximum operating altitude
3,000 masl
Mean time between failures (MTBF)
Mean time to repair (MTTR)
SYNOPTIC
Extended communications
-20°C ÷ +55°C (2)
250,000 hours
15 minutes
LCD display
Indicators (LED)
Yes (4x40 characters)
5
COMMUNICATION Ports
RS-232/485
Dry contacts
3 relays (expandable to 9)
SNMP
Optional
Slot
STANDARDS
Yes, one
Safety
IEC/EN 61204-7, IEC/EN 60950-1
Electromagnetic compatibility (EMC)
IEC/EN 61204-3
Quality and environmental management
1. Slot for SICRES remote management or RS-232
interface.
2. RS-232 or RS-485 serial ports. MODBUS
communications protocol.
3. General alarm & programmable (x8) dry contact
interface.
4. Battery temperature measurement input.
5. NiCd electrolyte level detection input.(1)
. Surge protector.
. Output voltage dropping diodes.
. Positive, negative or isolated output voltages.
. Sealed or open PbCa batteries, NiCd, etc.
. Extended communications module.
. Other degrees of IP protection.
. Wireless-link communication.
. Non priority loads diconnector.
ISO 9001 and ISO 14001
(1) Power degradation for voltages lower than 190 Vac.
(3) Without batteries
(2) Power degradation for temperatures higher than 45°C.
RANGE
OUTPUT
VOLTAGE
(Vdc)
MODEL
POWER
CURRENT
CURRENT PER
SYSTEM
POWER PER
SYSTEM
DC-18-S
DC-36-S
DC-50-S
DC-8-S
DC-16-S
DC-22-S
DC-7-S
DC-16-S
DC-20-S
1000
2000
2700
1000
2000
2700
1000
2000
2700
18
36
50
8
16
22
7
15
20
Between 18 and 540
Between 36 and 1080
Between 50 and 1500
Between 8 and 240
Between 16 and 480
Between 22 and 660
Between 7 and 210
Between 15 and 450
Between 20 and 600
Between 1and 30
Between 2 and 60
Between 2.7 and 81
Between 1 and 30
Between 2 and 60
Between 2.7 and 81
Between 1 and 30
Between 2 and 60
Between 2.7 and 81
MODULE
48
(1) Only for extended version.
Options
Data may change without previous notice.
INPUT
110
125
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(W)
(A)
(A)
@salicru_SA
(kW)
www.linkedin.com/company/salicru
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
OPTIMUS
Compact DC power systems
OPTIMUS: Compact DC Power Systems for Telecommunications
The DC Power Systems Salicru OPTIMUS series are rectifiers especially designed for supplying small and medium power
telecommunications equipment. Produced in versions of 300 and 700 W per module, they can be configured both in the number of
rectifiers and battery breakers or distribution in order to adapt to the most varied power supply requirements.
They are conceived to be included in 19” racks or ETSI, and 2 sub-racks can be connected in parallel in applications with larger power
demands. The main sub-rack, in its maximum configuration, has 3 plug-in type rectifiers, monitoring and control unit MS-100, current
distribution unit with capacity for up to 8 breakers of different calibres, alarm card and 2 breakers for connecting 2 sets of batteries.
All of the system values and parameters, and the alarm category, may be modified by an LCD display or software for PC (optional).
Performances
OPTIMUS 300 W
. Suitable for single phase or three-phase supplies.
. Great power density.
. Easy installation and maintenance.
. High MTBF.
. High efficiency.
. Low cost operation and maintenance.
. Battery charging current limitation.
. Plug-in type output distribution unit (8 breakers).
. Plug-in type battery unit (2 breakers).
. Suitable for connecting any type of battery.
. Front input/output and connectors.
. Alarm card.
. Breaker calibre up to 30 A (Optimus 300) or 60 A (Optimus 700).
. Modularity: up to 3 plug-in type rectifiers per sub-rack.
. Power factor close to the unit.
OPTIMUS 700 W
MS-100 control
Supply and alarm unit
Applications: Telecommunications systems always operative
The Salicru OPTIMUS DC Power Systems provide high level supply to the always critical telecommunications systems,
guaranteeing their perfect operation without unexpected cuts. Due to their modular nature, they can also be expanded according
to needs, thus optimising the investment.
REF. JM585B01 CODE 401AB000366 ED. MARCH 2014 DC POWER SYSTEMS
OPTIMUS
Compact DC power systems
TECHNICAL SPECIFICATIONS
MODEL
INPUT
OPTIMUS 300
AC voltage
Voltage range
230 V
± 15%
Power factor
> 0.86
> 0.95
Nominal current
1.43 A
3.55 A
2.09 A
6.41 A
Maximum current
Efficiency
OUTPUT
> 85% (50% to 100% of the load) > 90% (10% to 100% of the load)
Frequency
50 / 60 Hz
Protection
Input fuse 10 A and overtemperature
DC voltage
- 48 V
- 48 V ÷ - 60 V
Volatge adjustment
OPTIMUS 300 W
± 0.1% (with battery full charged)
Accurancy
Nominal power
300 W
700 W
Maximum subrack power
900 W
2100 W
Nominal current (per module)
Response time
5.5 A
13 A
± 0.1% (10% a 100% load steps)
Output fuse 25 A
Protection
50 mVpp
Maximum ripple
STRUCTURE
Single or three phase
Active Power Factor Correction (PFC)
Against 5 kV transients (8 / 20 impulses µs)
Protection
GENERALS
Dielectric strenght
1500 Vac, 1 minute, input
800 Vac, 1 minute, output
Protection degree in a/ with standards
Isolation
OPTIMUS 700 W
< 2 mV
Acoustic noise @ 1 metre
< 40 dB
Cooling
Natural
- 10º C a + 45º C
Storage temperature
LCD display.
Monitoring software for Windows.
. RS-485 to TCP-IP converter.
.
.
- 20º C a + 70º C
Relative humidity
Up to 95%, non-condensing
Maximum operating altitude
Mean Time Between Failures (MTBF)
Mean Time To repair (MTTR)
Optical module indicators
INDICATORS &
COMMUNICATION Optical control MS-100 indicators
Communication ports
STANDARDS
2400 m.a.s.l.
250,000 hours
15 minutes
On / Rectifier fault
On, Alarm, Alarm A1, Alarm A2,
End of autonomy, Alarm 01, TX, RX
RS-485 or RS-232 through RJ45 connector
Protocol
MODBUS, as standard
Safety
EN 60950-1
Electromagnetic Compatibility (EMC)
Quality and Environmental management
ETS 300386-2
ISO 9001 and ISO 14001
RANGE
MODEL
Options
IP20
> 10 MΩ
Pshophometric noise
Operating temperature
1. RJ-45 connector for optional LCD display or PC.
2. 10 plug and play type connections (8 for output
distribution and 2 for batteries).
3. AC power supply connectors.
4. Urgent alarm outputs, not urgent and
informative.
5. Alarm outputs trigger distribution magnetic
thermal and trigger battery magnetic thermal.
6. Temperature probe.
7. Reading of maximum/minimum input voltage.
8. RS-232 and RS-485 ports.
9. Outputs 1 to 8.
10. Battery connectors.
OPTIMUS 700
OPTIMUS 300
OPTIMUS 700
(1) Complete subrack
Communications & services
MS-100 Monitoring and Control Unit.
and RS-485 serial ports.
. Pre-sale and after-sale advisory service.
. Multiple formulae for maintenance and
telemaintenance (SICRES).
.
. RS-232
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
POWER / MODULE
DIMENSIONS
WEIGHT
300
700
260 x 483 x 133
260 x 483 x 267
13
17
(W)
(D x W x H mm.)
(Kg)(1)
Data may change without previous notice.
Unit connectivity
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
FAC P
DC power systems
FAC P: DC Power Systems for medium and high powers
The Salicru FAC P series DC Power Systems are rectifiers especially designed to supply the most varied medium and high power
equipment in DC. Made in powers of 1000, 2000, 2700 and 5000 W, they can be connected in parallel and form part of 19” cabinets, where
each cabinet can also include the monitoring and control unit (MS-102), batteries and DC output distribution, and a load priority system.
Each rectifier module is also prepared for hot swapping, with all of the advantages that this involves for the system operation.
On the other hand, the large amount of rectifier modules that can be connected in a single system will allow a power concentration of
over 170 kW.
The Monitoring and Control Unit (MS-102) controls the whole system, stores and manages input, output and battery data and all of the
parameters are programmed here. Through the RS-485 port, there is communication with the rectifier modules, controlling at all times
the output voltage, the current spreads between modules, the battery loading current, the control of the priority and non-priority load
contactors, the ends of autonomy, etc. Exterior communication may be in local or remote mode (GSM / TCP-IP).
Performances
. Suitable for single phase or three-phase supplies.
FAC 1000 P
. Great power density.
. Easy installation and maintenance.
. Low cost operation and maintenance.
. High MTBF.
. High efficiency.
. Battery charging current limitation.
. Unit power factor.
. Hot swapping modules.
FAC 2000 P
FAC 2700 P
. Monitoring and Control Unit (MS-102).
MS-102
Applications: DC power systems always available
The Salicru FAC P series DC Power Systems provide high level supply to the always critical telecommunications systems,
guaranteeing their perfect operation without unexpected cuts. Due to their modular nature, they can also be expanded according
to needs, thus optimising the investment.
REF. JM581B01 CODE 401AB000392 ED. MARCH 2014 POWER SYSTEMS
FAC P
Unit connectivity
DC power systems
THECHNICAL SPECIFICATIONS
MODEL
Ac voltage
Volatge range
± 15%
> 0.99 (1)
Nominal current
5.0 A
10.7 A
13.5 A
Maximum current
5.9 A
12.6 A
15.8 A
Efficiency
> 87%
> 82%
50 / 60 Hz
Protection
Electronic
DC nominal volatge
12, 24, 36, 48, 60, 110,
125, 216, 220 V
25, 25, 24, 18, 14, 75, 75, 48, 36, 29,
8, 7, 4, 4 A
16, 14, 8, 8 A
49, 22, 20 A
5000 W (3)
181, 181, 121, 91,
72, 40, 36, 20, 20 A
< 3 mV
< 1 mV
< 3 mV
1000 W (2)
Nominal power
Nominal current
Psophometric noise
2000 W (3)
Power factor corrector (PFC)
Yes (1)
Against 5 kV peaks ( 8 / 20 µs )
Protection
Pb-Ca or Ni-Cd
Type
Charging curve
Charging current
I / U constant
0.1 a 0.3 C adjustable
Recharging time
Up to 80% in 4 hours (0.2 C)
Protections
Against over-voltages and under-voltages
Dielectric strenght
2000 V @ 1 minute
Protection degree ac. to standards
Output distribution.
Input protection.
MS-102.
FAC P modules.
Slots for increasing power.
Battery protection.
Batteries.
Cable input.
IP20
> 20 MΩ
Insulation
Acoustic noise @ 1 metre
< 50 dB
Cooling
Forced
Controlled and
forced
Operating temperature
0º C ÷ + 40º C
Storage temperature (4)
- 20º C ÷ + 70º C
Relative humidity
2400 m.a.s.l.
Mean Time Between Failures (MTBF)
. MS-102 Monitoring and Control Unit.
. Output distribution.
. Positive, negative or floating output
voltages.
. Ground failure detector.
. Any type of battery: Sealed, Ni-Cd,
open, etc.
. Atmospheric discharger.
. Output voltage reducer.
. Other IP.
Communications & services
. RS-232 and RS-485 serial ports.
. Relay interface.
. MODBUS communications protocol.
. Pre-sale and after-sale advisory service.
INDICATORS
Forced
Up to 95%, non-condensing
Maximum operating altitude
100,000 hours
Mean Time To Repair (MTTR)
Optional
2700 W
Active parallel
Load sharing
1.
2.
3.
4.
5.
6.
7.
8.
12, 24, 36, 48, 60,
110, 125, 216, 220 V
± 0.1% (with charged batteries)
Accurancy
GENERALS
48, 110, 125 V
- 15% + 25%
Voltage adjustment range
BATTERIES
24.8 A
29.2 A
> 90%
Frequency
STRUCTURE
FAC 5000P
230 V or 3 x 400 V
230 V
Power factor
OUTPUT
FAC 2700P
150,000 hours
100,000 hours
15 minutes
Display LCD
Yes
Yes
NA
General alarm
Yes
Equipment On
Yes
Batteries on discharge / float
COMMUNICATIONS Ports
Safety
STANDARDS
Yes
Yes
NA
RS-232 / RS-485 / relays
EN 60950-1
Electromagnetic Compatibility (EMC)
EN 61204-3; ETS 300 386-2
Quality and Environmental management
ISO 9001 and ISO 14001
(1) Single phase input only.
(2) Except 12 V and 24 V output voltages.
(3) Except 12 V output voltage.
(4) No batteries.
RANGE
RECTIFIER MODULE
FAC 1000P
FAC 2000P
FAC 2700P
FAC 5000P
(5) 2U for 48V models.
. Multiple formulae for maintenance and
telemaintenance.
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
DIMENSIONS (D x H x W mm.)
WEIGHT (Kg)
425 x 483 x 2U
525 x 483 x 3U (5)
450 x 73 x 6U
525 x 483 x 4U
12
15
6
28
Data may change without previous notice.
INPUT
FAC 1000P FAC 2000P
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
DC POWER-L
Thyristor rectifiers 25 A - 200 A
DC power-L: Charging systems for stationary batteries
Salicru’s DC power-L range of rectifiers/battery chargers, based on microprocessor-controlled thyristor technology, provides
high-quality and reliable protection for critical DC loads.
The DC power-L series covers the range between 25 A and 200 A with outputs from 110 to 220 Vdc. The output accuracy is better
than +/- 1% and the system is designed to charge open or sealed lead acid and nickel cadmium batteries.
All alarms, monitoring and status indicators (via display and LEDs) are managed through a digital control system. Each type of
battery requires special charging characteristics, which are managed by the controller. The systems are completely customisable to
the specific characteristics and needs of each client and application.
The robust design ensures that the installation requires low maintenance and can work for long periods without special attention.
Performances
. Microprocessor-controlled thyristor technology.
. Galvanic isolation between input and output via transformer.
. Complete six-pulse bridge.
. Ventilation by natural convection.
. Standard DC output earth fault detection.
. Electrolyte level detection for NiCd batteries (optional).
. Charging states: floating, fast and exceptional.
. Robust and compact design.
. High power density.
. Monitoring of all equipment parameters through LCD display.
. Possibility of redundant parallel operation.
. Operation with lead acid or nickel cadmium batteries.
. Temperature-compensated float voltage.
. Automatic disconnection in the event of minimum battery voltage
or temperature.
. Extensive configuration options.
. High MTBF and low MTTR.
. Easy installation, start-up and maintenance.
DC power-L
Applications: Efficient, reliable and robust solutions
DC power-L systems are designed to protect DC loads of maximum criticality and to operate with nickel cadmium or lead acid
batteries in harsh and demanding operating environments, such as power plants, electrical substations, oil and gas pipelines,
petrochemical plants, mines, railways, telecommunications facilities, hospitals, industrial plants, etc.
REF. JM837A01 CODE 401AB000643 ED. OCTOBER 2013 POWER SUPPLY
DC POWER-L
User interface
Thyristor rectifiers 25 A - 200 A
THECHNICAL SPECIFICATIONS
MODEL
AC voltage
Range
3 x 230 / 3 x 400 V (3 Ph + N)
±15%
Frequency
50/60 Hz
Frequency range
±5%
Power factor
0.85
Efficiency
1.
2.
3.
4.
5.
6.
Output voltage indicator.
Input voltage fault indicator.
Urgent alarm indicator (customisable).
Non-urgent alarm indicator (customisable).
LCD display with multiple languages.
Navigation keys.
OUTPUT
>85%
Rated DC voltage
110 V
Float voltage
120 V
125 V
2.28 V/cell (Pb) / 1.4 ÷ 1.45 V/el (NiCd)
Fast charging voltage
2.5 V/cell (Pb) / 1.5 V/el (NiCd)
Exceptional charging voltage/formation
2.7 V/cell (Pb) / 1.65 V/el (NiCd)
Accuracy (with batteries)
±1%
Ripple (with batteries)
<1%
Current
BATTERIES
25 / 50 / 75 / 100 / 150 / 200 A
Type
PbCa (sealed or open) or NiCd
No. of cells Pb
No. of elements NiCd
Extended communication
55
60
62
110
81 ÷ 86
88 ÷ 94
92 ÷ 96
161 ÷ 173
IU constant as per DIN 41773
Type of charge
Charging current
0.1 to 0.3 C adjustable
Recharging time
Protection
Up to 80% in 4 hours (0.2 C)
Against overvoltage and undervoltage
Voltage/temperature compensation
PROTECTION
Yes, customisable as per battery specifications (mV / °C)
Input protection / battery
Circuit breaker / fuses
Soft start
GENERAL
1. Slot for the SICRES telemagement or RS-232
interface.
2. RS-485 serial ports. MODBUS
communication protocol.
3. Programmable relay (x9) interface.
4. Battery temperature measurement input.
5. NiCd electrolyte level detection input. (1)
(1) Only extended version
Yes
Dielectric strength
2500 V @ 1 minute
Degree of protection
IP20
Cooling
Natural convection
Operating temperature
-10º C to +55º C (1)
Storage temperature
-20° C ÷ +70° C (2)
Relative humidity
Up to 95% non-condensing
Maximum operating altitude
SYNOPTIC
Up to 3000 m.a.s.l. (3)
LCD display
Yes
Indicators (LED)
4 (mains power failure, urgent alarm, non-urgent alarm, output OK)
COMMUNICATION Ports
Dry contacts
RS-232/485
3 Dry contacs (expandable to 9)
SNMP
Optional
Slots
Optional
· 12-pulse rectifier with isolation transformer.
. Voltage drop diodes.
. TCP/IP interface.
. Heater.
. Output diodes for parallel operation.
. Different types of batteries (SLA, lead acid,
nickel cadmium, etc.).
. Other degrees of protection.
. Other input voltages on request.
. Top cable entry.
Services
· Pre and post-sales advice.
. Multiple maintenance and telemaintenance
options.
@salicru_SA
www.linkedin.com/company/salicru
220 V
Yes, one
ALARMS
Urgent
Non-urgent
STANDARDS
Safety standard
Charger fault and DC output fault (customisable)
DC output earth fault and low electrolyte level (customisable)
IEC/EN 61204-7, IEC/EN 60950-1
Electromagnetic compatibility (EMC)
IEC/EN 61204-3 Class A
Environmental Quality Management
ISO 9001 and ISO 14001
(1) Power degradation from +40ºC
(2) Without batteries
(3) Power degradation from 1000 m.a.s.l.
RANGE
MODEL
DC-25-L 110
DC-50-L 110
DC-75-L 110
DC-100-L 110
DC-150-L 110
DC-200-L 110
DC-25-L 125
DC-50-L 125
DC-75-L 125
DC-100-L 125
DC-150-L 125
DC-200-L 125
DC-25-L 220
DC-50-L 220
DC-75-L 220
DC-100-L 220
DC-150-L 220
DC-200-L 220
OUTPUT
VOLTAGE
CURRENT
110
110
110
110
110
110
125
125
125
125
125
125
220
220
220
220
220
220
25
50
75
100
150
200
25
50
75
100
150
200
25
50
75
100
150
200
(Vdc)
(A)
BATT
(1)
DIMENSIONS (1) WEIGHT (1) DIMENSIONS
(1) WEIGHT
(D x W x H mm.)
(Kg)
(Kg)
(1) Dimensions and weights for units with standard back up time
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(D x W x H mm.)
640 x 605 x 1315
640 x 605 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 605 x 1315
640 x 605 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 605 x 2115
640 x 605 x 2115
640 x 805 x 2115
840 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
288
378
435
481
615
535
290
382
419
434
454
535
360
414
421
589
454
535
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
640 x 805 x 2115
258
216
273
366
438
Data may change without previous notice
INPUT
DC POWER-L
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
CS-IS
DC power converters
CS IS: High performance DC/AC industrial converters
Salicru’s CS IS series DC/AC converters are based on technically advanced solutions such as PWM technology and digitally controlled
servo systems so as to obtain: high performance, low distortion (THDv < 2%) and elevated stability. Moreover, they offer excellent
tolerance to short-circuits, polarity inversion protection and the possibility of operating in Eco-mode.
The line is available in power ranges between 1000 and 6000 VA,
with admissible continuous incoming voltage from 48 Vdc to 220 Vdc
nominal input.
Performances
CS 4000-IS
TECHNICAL SPECIFICATIONS
MODEL
CS IS
INPUT
DC nominal voltage
Voltage range
48 V, 110 V, 120 V, 125 V, 220 V
- 17%, + 20%
OUTPUT
AC nominal voltage
120 V, 220 V, 230 V, 240 V
. Isolation transformer on the bypass line.
. Psofometric filter.
. Anti-harmonic filter.
Services
Pre-sales and post-sales consultation service.
Several maintenance and remote maintenance methods.
Synchronized
0.1 Hz ÷ 9.9 Hz in increments of 0.1 Hz
± 0.05%
Synchronization speed
1 Hz/s
Admissible overload
150% for 30 seconds /
125% for 45 seconds
Efficiency
Up to 92%
Operating temperature
GENERALS
- 10º C ÷ + 40º C
Cooling
Forced
Relative humidity
Up to 95%, non-condensing
Maximum operating altitude
2400 m.a.s.l.
Safety
EN 60950-1
Electromagnetic Compatibility (EMC)
Optional
. EMI filters.
50 / 60 Hz
Unsynchronized
STANDARDS
. Static bypass.
± 2%
Frequency
Frequency range
Applications: Energy conversion
for industrial plants
Salicru’s CS IS series provides quality AC power from a
DC power source (normally batteries) for the most varied of
industrial applications such as cogeneration and biomass
plants, gas generators, water distributors, power stations
and substations, telecommunications, etc.
Accuracy
EN 61000-6-3; EN 61000-6-1
Quality and Environmental management
ISO 9001 and ISO 14001
RANGE
MODEL
CS 1000-IS
CS 2000-IS
CS 3000-IS
CS 4000-IS
CS 5000-IS
CS 6000-IS
POWER
(VA)
INPUT VOLTAGE
DIMENSIONS
(Vdc)
(D x W x H mm)
BOX
RACK
WEIGHT
(Kg)
48
110
120
125
220
1000
•
•
•
•
•
385 x 440 x 180 (1) 385 x 483 x 4U (1)
36
2000
•
•
•
•
•
385 x 440 x 180 (1) 385 x 483 x 4U (1)
49
3000
•
•
•
•
•
385 x 440 x 180 (1) 385 x 483 x 4U (1)
4000
•
•
•
•
600 x 440 x 270
600 x 483 x 6U
5000
•
•
•
•
600 x 440 x 270
600 x 483 x 6U
68
6000
•
•
•
•
725 x 440 x 270
-
84
57
63
Dimensions and weights for models without bypass nor filters. Ask for another power needs and/or configurations.
(1) For voltages ≥110 Vdc.
@salicru_SA
REF. JM673D01 CODE 401AB000466 ED. MARCH 2014 STATIC INVERTERS
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
www.linkedin.com/company/salicru
Data may change without previous notice
. Availability in a wide range of voltages and outgoing
power.
. Broad range of input voltage variation.
. LCD display comes standard.
. Communication through relay interface or RS-232 /
RS-485.
. Excellent dynamic behavior.
. Automatic restart to re-establish incoming power.
. Ramp start.
. 19” rack or box casing
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
CS WAVE MDL
48 VDC power converters
CS WAVE MDL: DC/AC converters for telecommunications
Today’s telecommunications systems include a large variety of critical loads that must be correctly powered and protected. Salicru’s
CS WAVE MDL is based on the modular architecture that can be adapted to any growth and/or redundancy needs.
The maximum configurations allows up to 24 kVA in models
with 1 or 1.5 kVA, which are supplemented by the modules:
static bypass (STS), LCD display, communications and/or
manual bypass with distribution.
Performances
. DSP
CS WAVE MDL
TECHNICAL SPECIFICATIONS
MODEL
INVERTER
Optional
Static bypass up to 12 kVA.
LCD display.
. Communications interface.
. Manual bypass with distribution.
Services
Pre-sales and post-sales consultation service.
Several maintenance and remote maintenance methods.
DSP; All Master
1000 VA / 800 W and 1500 VA / 1200 W
Maximum no. models x system
15 x 1500 VA or 24 x 1000 VA
Input voltage
40.5 Vdc ÷ 58 Vdc
Output voltage
230 Vac
Output frequency
50 / 60 Hz
Psofometric noise
# 1 mV
Efficiency
> 89%
Admissible overload
STATIC
BYPASS
(STS)
Power
MANUAL
BYPASS
Distribution
5 position selector
STANDARDS
Safety
150% for 20 seconds
12 kVA
Transfer time
< 5 ms
Synchronism
LCD DISPLAY Settings
INTERFACE Ports
Protocol
.
.
Technology
Modular power
Applications: AC power for Telecom
systems
Normally for mobile or land-line telecommunications
systems not able to connect to the mains, that need
autonomous solutions providing power from back-up
elements (batteries, fuel-cell,...).
CS WAVE MDL
± 2.5%
Input / Output / Alarms / General
RS-232, RS-485, USB and free contacts
CANBUS
2 x 20 A + 1 x 32 A + 1 x 50 A
Combined Inverter - STS - Manual bypass
EN 60950-1
Electromagnetic Compatibility (EMC)
EN 61000-6-3; EN 61000-6-1
Quality and Environmental management
ISO 9001 and ISO 14001
RANGE
MODEL
CS 1000-WAVE MDL 48/230
CS 1500-WAVE MDL 48/230
STS-WAVE MDL
LCD-WAVE MDL
COM-WAVE MDL
BM+DIS-WAVE MDL
DESCRIPTION
Inverter 1000 VA
Inverter 1500 VA
Static bypass (STS)
Display LCD
Communications
Manual bypass + distribution
@salicru_SA
REF. JM673D01 CODE 401AB000466 ED. MARCH 2014 STATIC INVERTERS
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
DIMENSIONS
WEIGHT
270 x 215 x 1U
2.5
270 x 215 x 1U
3
270 x 215 x 1U
3
(D x W x H mm)
(Kg)
270 x 90 x 1U
1
270 x 180 x 1U
0.5
270 x 483 x 2U
4
www.linkedin.com/company/salicru
Data may change without previous notice
Design (Digital Signal Processor).
protection standard (in configurations
with STS).
. All Master technology for better reliability.
. Senoidal output.
. Hot-Swap.
. High density power.
. Polarity inversion protection.
. Smart ventilation control.
. Back-feed
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SUPPLIES
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT AND SERVICE
RE3
Electronic voltage stabilisers from 300 VA to 250 kVA
RE: The fastest and the most accurate electronic regulation system of the market
In today’s electronic environment, saturated and highly unstable, where fluctuations in the power supply voltage are more than
frequent, voltage stabilisers play a very important role in guaranteeing stable voltage to loads more sensitive to such variations.
The Salicru RE series of electronic stabilisers, based on a completely static structure of high efficiency, fast reply speed and
excellent output precision, are made in single phase or three-phase configuration and in a range of powers from 300 VA to 250 kVA.
The three-phase units are conceived with a completely phase-independent regulation in order to avoid possible regulation problems
due to imbalance in the loads. Moreover, the units include a static bypass to guarantee the power supply in the event of a possible
fault.
Performances
. Power range, single and three-phase, up to 250 kVA.
. Ultra-fast regulation: reply speed under 100 ms.
. Digital control and parameters setting independent per phase.
. Entirely static structure, without moving elements, greater reliability.
. Static bypass, loads always supplied.
. In three-phase units, independent regulation per phase, immune to
imbalances.
. Output precision better than ±2%.
. ±15% input regulation margins standard.
. Efficiency > 97%.
. Isolation transformer or ultra-isolation on unit output. (1)
. LCD Display, as standard, from 6 kVA single-phase or 15 kVA
three-phase.
. Detection of voltage input or output (max/min) out of margins, as
standard. (2)
. SICRES comunication slot. (2)
. Overtemperature detection. (2)
. Do not introduce harmonics, or alter the power factor of the installation.
. Unaffected by line voltage harmonics; stabilisation based on true RMS.
. Stable operation in the event of load and/or voltage variations.
. Highly robust and reliable (high MTBF).
. More than 80% recyclable materials.
RE3
(1) Option
(2) For models with LCD display
Applications: Assured industrial processes
Many are the industrial processes where voltage stability is essential: from a wide range of applications where the numerical
control processors and automatons are entrusted with guaranteeing the final result, up to all kinds of calculation centres, computer
peripherals, transmission and communications equipment, laboratory equipment, etc.
REF. JM867A01 CODE 401AB000733 ED. MARCH 2014 VOLTAGE STABILISERS
RE3
Electronic voltage stabilisers from 300 VA to 250 kVA
Presentation
TECHNICAL SPECIFICATIONS
MODEL
Single phase voltage
Three-phase voltage
120 V, 220 V, 230 V, 240 V
3 x 208 V, 3 x 220 V, 3 x 380 V, 3 x 400 V, 3 x 415 V
Regulation range
± 15% (1)
Frequency
OUTPUT
48 ÷ 63 Hz
Single phase voltage
120 V, 220 V, 230 V, 240 V
Three-phase voltage
Accuracy
3 x 208 V, 3 x 220 V, 3 x 380 V, 3 x 400 V, 3 x 415 V
Better than ± 2%
48 ÷ 63 Hz
Frequency
Nil
Harmonic distortion
100 ms
Response time
> 97%
Efficiency
RE3 models
BYPASS
GENERALS
RE models
200% for 1 minute
Permissible overload
Type
Static
Ambient operating temperature
Relative humidity
RE3 models display
Up to 95%, non-condensing
Maximum operating altitude
2400 m.a.s.l.
Mean Time Between Failures (MTBF)
60,000 hours
Mean Time To Repair (MTTR)
30 minutes
Acoustic noise level at 1 metre
< 45 dB (A) (2)
Cooling
Natural or forced depending on power rate
Electrical noise attenuation on common mode
1
With isolation transformer > 40 dB
With ultra-isolation transformer > 120 dB
STANDARDS
Safety
IEC 62103
Electromagnetic Compatibility (EMC)
3
-10º C ÷ +45º C
2
Quality and Environmental management
EN-61000-6-4; EN-61000-6-2
ISO 9001 and ISO 14001
(1) Other ranges under request (2) <65 dB(A) for models with forced ventilation
RANGE (3)
1. LCD 2x16 characters.
2. Navigation keys.
3. LEDs (alarm, bypass, normal operation and
communications).
Options
Relay interface.
Manual maintenance bypass.
. Protection of high-low voltage with manual or
automatic reset (output voltage disconection
when out of range).
. Isolation transformer (T).
. Ultra-isolation transformer (NS).
. Current transformers for measures of current,
power (kVA / kW) and power factor.
. Overload protection. (1)
. Telemanagement SICRES card. (1)
. Extended communications module. (1)
.
.
(1) Models with display
Services
· Pre-sale and after sales advisory service.
· Numerous maintenance and remote maintenance
options (SICRES).
@salicru_SA
www.linkedin.com/company/salicru
MODEL
RE-309-2
RE-609-2
RE-1009-2
RE-2009-2
RE-3009-2
RE-4509-2
RE3 M 6-2
RE3 M 9-2
RE3 M 12-2
RE3 M 15-2
RE3 M 20-2
RE3 M 25-2
RE3 M 30-2
RE3 M 40-2
RE3 M 50-2
POWER
DIMENSION
WEIGHT
0.3
0.6
1
2
3
4.5
6
9
12
15
20
25
30
40
50
280 x 210 x 185
280 x 210 x 185
280 x 210 x 185
390 x 250 x 195
390 x 250 x 195
460 x 300 x 220
540 x 330 x 500
540 x 330 x 500
540 x 330 x 500
540 x 330 x 500
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
6
6
9
19
22
35
44
58
67
69
103
127
154
170
186
(kVA / kW)
(D x W x H mm)
(Kg)
Nomenclature, dimensions and weight for models: 230 V 50 Hz input / 230 V 50 Hz output and ± 15% input range
MODEL
RET 3-4
RET 6-4
RET 9-4
RE3 T 15-4
RE3 T 20-4
RE3 T 30-4
RE3 T 45-4
RE3 T 60-4
RE3 T 75-4
RE3 T 100-4
RE3 T 125-4
RE3 T 150-4
RE3 T 200-4
RE3 T 250-4
POWER
DIMENSION
WEIGHT
3
6
9
15
20
30
45
60
75
100
125
150
200
250
680 x 340 x 240
680 x 340 x 240
630 x 390 x 520
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
840 x 450 x 620
838 x 616 x 1318
838 x 616 x 1318
838 x 616 x 1318
838 x 616 x 1318
816 x 816 x 2118
816 x 816 x 2118
32
61
68
80
117
164
225
260
317
343
438
650
850
925
(kVA / kW)
(D x W x H mm)
Nomenclature, dimensions and weight for models: 3 x 400 V 50 Hz input / 3 x 400 V 50 Hz output and ± 15% input range
(3) For models with isolation transformer and other configurations, consult
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(Kg)
Data may change without previous notice
INPUT
RE3
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SUPPLIES
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT AND SERVICE
EMi3
Servomotor voltage stabiliser 5 kVA - 330 kVA
EMi3: Constant stabilisation and savings in overvoltages
Issues such as the constant variation of loads connected to the mains, interference generated by the loads themselves, possible failures
in distribution lines, voltage drops due to the length of the lines and problems caused by lightning make it impossible to have an electricity
supply with a stable voltage. Salicru’s EMi3 servomotor voltage stabilisers are the ideal solution to protect sensitive equipment from
constant voltage fluctuations in the power supply.
Moreover, in the event of drops in the total consumption of a power line, voltage tends to rise, causing overconsumption in the equipment
that remains connected. By using a stabiliser, overconsumption can be eliminated, thereby producing significant cost savings and ensuring
that connected loads function within the voltage range for which they were designed.
Salicru’s EMi3 servomotor voltage stabilisers are the culmination of 45 years of experience and development, in which the company has
manufactured and installed over 100,000 units worldwide.
The operating principle is based on regulation, by means of a control circuit, of the variable autotransformer that supplies the voltage for the
booster transformer in series, either in phase or in phase opposition, to achieve the rated value of the output voltage.
Features
· Power range, single and three-phase, up to 330 kVA.
. Fast and efficient toroidal autotransformers for the entire power range.
. Output accuracy better than 1% (adjustable).
. In three-phase units, common or independent regulation per phase, unaffected by imbalances.
. Input regulation range ±15% standard.
. High efficiency, up to 97.5%.
. High speed regulation, up to 70 V/s.
. Full LCD display for stabiliser control and monitoring.
. Guaranteed output stability through a MosFET servo control.
. Unaffected by line voltage harmonics; stabilisation based on true RMS.
. Stable operation in the event of load and/or voltage variations.
. Wide operating temperature range (-10°C to +55°C).
. Dry contact interface (2 standard and up to 11 optional).
. No harmonics injection.
. Mechanically-optimised design, easier maintenance.
. Transient overloads of up to 1000% of the rated
admissible.
. Highly robust and reliable (high MTBF).
. Quiet operation.
. More than 80% recyclable materials.
EMi3
Applications: Effective protection for all types of critical load
Actions and operations in electrical substations, electric ovens, numerical controls, lifts, graphic printing equipment, production
lines, medical equipment, TV repeater stations, machine tools (milling machines, trimming machines, presses, lathes, polishing
machines, electrical discharge machines, etc.) are some of the applications, because of their power, extremely reactive nature and
high sensitivity to voltage variations.
REF. JM841A01 CODE 401AB000654 ED. OCTOBER 2013 VOLTAGE STABILISERS
EMi3
Description
Servomotor voltage stabiliser 5 kVA - 330 kVA
11
22
33
TECHNICAL SPECIFICATIONS
MODEL
INPUT
EMi3
Voltage
Single-phase 220 / 230 / 240 V
Three-phase 3x380 / 3x400 / 3x415 V (3Ph + N)
Range
55
±15 (1)
48 ÷ 63 Hz
Frequency
OUTPUT
Voltage
66
Accuracy
77
Frequency
Single-phase 220 / 230 / 240 V
Three-phase 3x380 / 3x400 / 3x415 V (3Ph + N)
± 1% (adjustable between 1% ÷ 5%)
± 5%
Output voltage setting
48 ÷ 63 Hz
Up to 70 V/s
Regulation speed
Between 96.5% and 97.5%
Performance
Injection of voltage harmonic distortion
<0.2%
Adjustable
Voltage disconnection value (2)
1.
2.
3.
4.
5.
6.
7.
8.
Display LCD
Variable autotransformer
Control PCB
Input protection
Input and output terminals
Surge protection
Motor supply transformer
Booster transformer
Options
· Output current, power and overload
measurement.
. Maximum and minimum output voltage
protection.
. Manual bypass.
. Overload contactor.
. Communications and relay module.
. Other regulation ranges.
. Galvanic isolation transformer.
Extended communications
Up to 200% for 20 s
Admissible overload
88
0 ÷ 100%
Possible load variation
Power factor influence
INDICATORS
COMMUNICATION
GENERAL
Front panel
Independent
LCD display (2x16 characters) + 4 status LEDs
Standard
RS-232 (3)
Standard
One
-10° C ÷ +55° C
2 Dry contacts
Free slot (3)
Operating temperature
Storage temperature
-20° C ÷ +85° C
Ventilation
Natural convection (4)
Level of acoustic noise at 1 metre
<45 dB(A) (5)
Relative humidity
STANDARDS
Data may change without previous notice
44
Up to 95%, non-condensing
Maximum operating altitude
2,400 m.a.s.l.
Mean time between failures (MTBF)
Mean time to repair (MTTR)
60,000 hours
30 minutes
Safety
IEC-62103
Electromagnetic compatibility (EMC)
EN-61000-6-4; EN-61000-6-2
Quality and environmental management
ISO 9001 and ISO 14001
(1) Other ranges available on request
(2) With optional voltage maximum-minimum
(4) Forced from 20 kVA for single phase and 55 kVA for three-phase
(3) Mutually exclusive ports
(5) <65 dB(A) for models with forced ventilation
RANGE
MODEL
EMi3 M 5-2
EMi3 M 7.5-2
EMi3 M 10-2
EMi3 M 15-2
EMi3 M 20-2
EMI3 M 25-2
EMi3 M 30-2
POWER
DIMENSION
WEIGHT
5
7.5
10
15
20
25
30
540 x 328 x 500
540 x 328 x 500
540 x 328 x 500
839 x 450 x 620
839 x 450 x 620
839 x 450 x 620
839 x 450 x 620
45
59
60
115
119
196
209
(kVA / kW)
(D x W x H mm)
(Kg)
Nomenclature, dimensions and weights for models: Input 230 V 50 Hz / Output 230 V 50 Hz and input range +/-15%.
MODEL
1. Slot for SICRES remote management or RS-232
interface.
2. RS-485 serial ports. MODBUS
communications protocol.
3. Programmable dry contact interface (x5).
4. Digital input.
Services
· Numerous maintenance and remote
maintenance options (SICRES).
@salicru_SA
EMi3 T 15-4
EMi3 T 20-4
EMi3 T 35-4
EMi3 T 55-4
EMi3 T 70-4
EMi3 T 90-4
EMi3 T 110-4
EMi3 T 140-4F
EMi3 T 175-4F
EMi3 T 220-4F
EMi3 T 275-4F
EMi3 T 330-4F
POWER
DIMENSION
WEIGHT
15
20
35
55
70
90
110
140
175
220
275
330
839 x 450 x 620
839 x 450 x 620
839 x 450 x 620
640 x 605 x 2110
640 x 605 x 2110
840 x 605 x 2110
840 x 605 x 2110
840 x 1605 x 2110
840 x 1605 x 2110
840 x 1605 x 2110
840 x 1605 x 2110
840 x 1605 x 2110
126
169
224
374
495
533
577
857
1159
1227
1298
1450
(kVA / kW)
(D x W x H mm)
(Kg)
Nomenclature, dimensions and weights for models:
- From 15 kVA to 110 kVA: Input 3x400 V 50 Hz / Output 3x400 V 50 Hz, input range +/-15% and common regulation. (Independent regulation per
phase available on request).
- From 140 kVA to 330 kVA: Input 3x400 V 50 Hz / Output 3x400 V 50 Hz, input range +/-15% and independent regulation per phase.
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
ILUEST+CR
Lighting flow dimmer-stabiliser
ILUEST+CR: Regulation + Telemanagement = Saving
With today’s modern street lighting systems, it’s not enough to reduce the voltage to supply the lamps to obtain energy savings. The
criteria are different nowadays and the requirements have increased in accordance with the growth of street lighting. Applying the
most advanced technology possible is needed as well as telemanagement, monitoring and parameterisation of the complete block
of units in order to guarantee the sustainability of the lighting system.
The ILUEST+CR series of advanced lighting flow dimmer-stabilisers from Salicru, takes over from its highly successful and fieldtested predecessor, has vast improvements in critical aspects of modularity, power density, protection and telemanagement. As a
result, greater flexibility in areas of power growth, maintenance, commissioning and equipment integration can be better realized
along with superior reliability and shorter payback periods.
The ILUEST+CR series is available in a wide range of powers, has 3 implementation variants - indoor, outdoor and OEM Kit - and
several possibilities of monitoring. Used in conjunction with our powerful telemanagement SICRES technology, the ILUEST+CR is
now the state-of-the-art reference in lighting regulation and control.
Performances
. Bi-directional ‘Buck’ converter with IGBTs, electronic, static and transformerless.
. Continuous regulation of the output voltage, no voltage steps; higher lamp lifetime.
. Lineal and programming ramps.
. High response time.
. Stabilisation better than ± 1% + saving voltage periods = savings > 40%.
. LCD display, as standard.
. Protections with automatic programming rearm due to overload and overtemperature.
. Protections with fuses (1) and against lightning arrestors.(2)
. Automatic bypass per phase, independent operating, manual operating (3),
active by default and break before make.
. RS-232 port + MODBUS protocol, as standard.
. SICRES telemanagement card built in completely.(4)
. Duty cycle adapted to the warm up curve of the lamp.
. Programming of two saving levels and start voltage via LCD display.
. Average payback of the investment between 6 and 24 months.(5)
. Low weight and dimensions, higher power density.
. No harmonic injection to mains.
. SLC Greenergy solution.
ILUEST+ CR
ILUEST+CR module
Applications: Lighting savings and management
The ILUEST+CR is suitable for use in many areas, both industrial and commercial e.g. roads and highways, road bridges &
tunnels, airports, hospitals, commercial centres, ports, railroads, car parks and many more. The superior supervisory and remote
control capability of the ILUEST+CR will result in the better and more efficient management of lightings, regardless of their
applications.
As an example, our studies have shown that a town of 10,000 inhabitants with 1,700 public lighting points would consume an
average of 1,210 MW of electricity per year. By using just 13 units of the ILUEST+CR rated 30 kVA each, potential annual savings
of 490 MW can be realized, translated to 270 Tm less CO2 to the atmosphere.
(1) In the equipment.
(2) MOV (Metal Oxid Vasistor).
(3) Through stated input or keypad.
(4) In frontal slot provided for this purpose.
(5) Estimated 0.09 €/kWh rate.
REF. JM806B01 CODE 401AB000589 ED. MARCH 2014 LIGHTING FLOW DIMMER STABILISER
ILUEST+CR
Monitoring
Lighting flow dimmer-stabiliser
TECHNICAL SPECIFICATIONS
MODEL
ILUEST+CR
TECHNOLOGY
View of the SICRES card slot
INPUT
and PC connection
Single phase: 230 V / Three-phase: 3 x 400 V + N
+ 25% / - 7% nominal voltage
+ 25% / - 17% saving voltage HPSV
+ 25% / - 10% saving voltage MV/MH
48 ÷ 65 Hz
Voltage
Voltage range
All of the units, regardless of the format, include
synoptic panel as standard, comprised of:
LCD panel: It provides input / output voltages,
frequency, load and saving percentage levels,
output currents, active power, apparent power,
power factor, load type and temperature. It
includes timer, astronomical clock and event data
logger.
Frequency
Module protection
Input/output fuses / electronic for temperature, overload
Fuse
Equipment protection per phase
OUTPUT
Voltage
Adjustable 215 V to 230 V (220 V as standard)
Better than ± 1%
Accuracy inside voltage range
Preselectable (1) and adjustable
Soft start voltage
Adjustable 180 V to 210 V
Saving voltage
From 1 V/minute to 6 V/minute
Speed ramp setting
< 40 ms.
Response time
Linear and independent per phase
Regulation
96% ÷ 98%
Efficiency
Communication ports: RS-232 via RJ-45
connector for local PC monitoring.
Through LCD panel or via SICRES communication
Selectable saving voltage
150% for 30 seconds; 120% for > 1 minute
Permissible overload
BYPASS
MODBUS protocol.
100% permissible
Phase unbalancing
No break
Type
Features
Automatic, reversible, independent per phase, independent
operating, input for manual activation
Overtemperature, overload, fault, output fault, manual activation
Activation criteria
Implementations
Rearm
Automatic by alarm cancelling.
Quantity of retries: 5; time between retries: 2 minutes
RS-232 and RS-485 (2)
SICRES system (2)
COMMUNICATION Ports
Monitoring
GENERALS
– 20º C ÷ + 55º C (3)
Operating temperature
Relative humidity
Up to 95%, non-condensing
Maximum altitude
2,400 m.a.s.l.
Mean Time Between Failures (MTBF)
60,000 hours
30 minutes
Mean Time To Repair (MTTR)
<48 dBA (with typical load)
Acoustic noise @ 1 metre
IMPLEMENTATIONS Indoor
Indoor version
Outdoor version
STANDARDS
Modules built in assembling base (chassis of sheeted steel at carbon
cold) with drills to fix to the wall
Outdoor
Indoor built in a poylester cabinet
OEM kit
Modules + Supports + Control wiring + Power Supply
Safety
EN-60950-1
Electromagnetic compatibility (EMC)
IEC 62041
Quality and Environmental management
ISO 9001 and ISO 14001
(1) Depending on type of lamp
(2) Optional
(3) 4% power derating per each degree over 45ºC
RANGE
KIT OEM
Available options
. External or internal manual bypass.
. GSM/GPRS modem.
. SICRES card.
. Digital I/O card (digital inputs and outputs).
. Atmospheric gas discharger.
Services
. Customized studies and simulations of the saving
and payback.
. Extended warranties (under request).
. Multiple formulae of maintenance and
telemaintenance (SICRES).
@salicru_SA
www.linkedin.com/company/salicru
MODEL
POWER
KIT NET+7.5-4-LCD
KIT NET+10-4-LCD
KIT NET+15-4-LCD
KIT NET+20-4-LCD
KIT NET+25-4-LCD
KIT NET+30-4-LCD
KIT NET+45-4-LCD
MODEL
(kVA)
MODULES
NO.
7.5
10
15
20
25
30
45
3
3
3
3
3
3
3
POWER
NET+ 7.5-4
NET+ 10-4
NET+ 15-4
NET+ 20-4
NET+ 25-4
NET+ 30-4
NET+ 45-4
(kVA)
7.5
10
15
20
25
30
45
KIT OEM
DIMENSIONS PER MODULE
WEIGHT
200 x 172 x 310
200 x 172 x 310
200 x 172 x 310
200 x 172 x 310
200 x 172 x 470
200 x 172 x 470
200 x 172 x 470
11
11
12
12
19
20
20
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
(Kg)
INDOOR IMPLEMENTATION
OUTDOOR IMPLEMENTATION
WEIGHT
DIMENSIONS
WEIGHT
DIMENSIONS
(D x W x H mm.)
(Kg)
(D x W x H mm.)
(Kg)
240 x 520 x 610
240 x 520 x 610
240 x 520 x 610
240 x 520 x 610
240 x 520 x 770
240 x 520 x 770
240 x 520 x 770
29
30
31
33
55
56
57
320 x 750 x 1105
320 x 750 x 1105
320 x 750 x 1105
320 x 750 x 1105
320 x 750 x 1105
320 x 750 x 1105
320 x 750 x 1105
64
65
66
68
89
90
91
Nomenclature, dimensions and weight for models: 3x400 V / 50 Hz input/output.
(*) Spain only (**) Rest of the world
(D x W x H mm.)
Data may change without previous notice.
LCD Display, LED synoptic panel
Bidirectional ‘Buck’ converter with IGBTs, electronic, static and
transformerless
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
ILUEST+MT
Lighting flow dimmer-stabilisers
ILUEST+MT: Savings as always with extra control
It is undeniable that regulating street lighting is a common practice for most city governments and the entities responsible for their
maintenance as, without a doubt, it leads to obvious significant financial benefits. Moreover, the monitoring and control requirements
related to the systems have notably increased in recent times with a demand for more and better remote maintenance and monitoring
tools for the units and lighting panels that produce tangible improvements in terms of the quality and optimised management.
The Salicru ILUEST+MT series is a next generation lighting flow dimmer-stabiliser designed to optimise the control and management
of today’s street lighting systems, taking communication capability to a higher level: 1) lighting control via an astronomical clock built
into the LCD panel, as a standard, and lighting control in the feeder pillar, and 2) complete telemanagement of a block of units via web
interface using an optional SICRES card and a GSM/GRPS model, all governed by the SICRES control software.
Performances
. Electronic lighting flow adjustment by static elements and next
generation microprocessor control.
. Entirely independent adjustment per phase.
. Automatic bypass per phase, independent operation, manually
operation and active by default.
. Protection with automatic programming rearm due to overload and
overtemperature.
. LCD display with astronomical clock, time programmer and relay to
control lighting line head, as standard.
. SICRES (1) card for total control of a block of units using
GSM / GPRS (1) modems and Web interface.
. Efficiency > 97%.
. No harmonic injection to mains or alter the power factor of the
installation.
. Instantaneous stabilisation in all operating states.
. Duty cycle adapted to the warm up curve of the lamps.
. Suitable for all kinds of discharge lamps (including metal halide).
. Soft transitions between the nominal and reduced flow states.
. Fine adjustments of all voltage levels and output precision
improved by ± 2%.
. Selectable start-up voltage.
. Two levels of saving adjustable via LCD display.
. Easy installation alongside the feeder pillar or inside it.
. Savings of over 40%.
(1) Option
ILUEST+MT
. Additional energy savings through the complete elimination of
the night-time overvoltage.
. Significant increase in the life span of the lamps.
. Average payback of the investment between 6 and 24 months.(2)
. Optimised maintenance of the unit.
. SLC Greenergy solution.
(2) Estimated 0.09 €/kWh rate
Applications: Affordable energy efficiency for lighting
All of these, from urban street lighting (avenues, streets, roads, ring roads, roundabouts, bridges, etc.) to lighting in industrial
areas, shopping centres, car parks, hospitals, ports, railway stations or airports, can benefit from the advantages given by the
ILUEST+MT in such important aspects as rationality in light levels, maintenance and telemaintenance of the installations and
electrical consumption.
REF. JM807B01 CODE 401AB000588 ED. MARCH 2014 LIGHTING FLOW DIMMER STABILISER
ILUEST+MT
SICRES: lighting control
Lighting flow dimmer-stabilisers
TECHNICAL SPECIFICATIONS
MODEL
SICRES is an electronic card of communication that
makes possible the telemaintenance service trough
Internet connection.
The functions of the system include:
· Interface for Ethernet networks with TCP-IP and
SNMP protocols and GSM/GPRS and RTC modems.
. 10 digital and 17 analogue measurements for the
ILUEST+ family.
. Multiple measurements are available: Active and
apparent power, power factor, load level, etc.
. Multiple programming and setting parameters: Time,
current day and month, voltage level types of lamp,
start voltage, nominal and saving.
. Calibrations.
. Programming and automatic SMS and e-mail sending.
. 7 week days + 10 special days time scheduler.
. Astronomical clock selection and programming is
included.
ILUEST+MT
Static and electronic regulation by microprocessor control
Voltage
Single phase
120 V, 220 V, 230 V, 240 V
Three-phase
3 x 208 V, 3 x 220 V, 3 x 380 V, 3 x 400 V, 3 x 415 V (+N)
Voltage range
+ 33% / - 8% nominal voltage
+ 4% / - 29% saving voltage HPSV
+ 10% / - 24% saving voltage MV/MH
48 ÷ 63 Hz
Frequency
Single pole MCB
Equipment protection per phase
OUTPUT
Voltage
Single phase
120 V, 220 V, 230 V, 240 V
Three-phase
3 x 208 V, 3 x 220 V, 3 x 380 V, 3 x 400 V, 3 x 415 V
Better than ± 2%
Accuracy inside voltage range
Preselectable (1) and adjustable
Soft start voltage
180 V (phase to neutral) adjustable MV, HPSV, MH and fluorescence
Saving voltage
From 1 V/minute to 6 V/minute
Speed ramp setting
< 100 ms.
Response time
Independent per phase
Regulation
100% permissible
Phase unbalancing
> 97%
Efficiency
Through LCD panel or via SICRES communication
Selectable saving voltage
150% for 30 seconds; 120% for > 1 minute
Permissible overload
BYPASS
Static
Type
Automatic and independent per phase.
Features
Overtemperature, overload, fault, output fault, manual activation
Automatic by alarm cancelling.
Quantity of retries: 5; time between retries: 2 minutes
Activation criteria
Rearm
COMMUNICATION Ports
RS-232 and RS-485 (2)
SICRES system (2)
Monitoring
GENERALS
– 40º C ÷ + 55º C (3)
Operating temperature
Relative humidity
Up to 95%, non-condensing
Maximum altitude
2,400 m.a.s.l.
Mean Time Between Failures (MTBF)
60,000 hours
30 minutes
Mean Time To Repair (MTTR)
< 35 dBA
Acoustic noise @ 1 metre
IMPLEMENTATIONS Indoor
Modules built in assembling base (chassis of sheeted steel at carbon
cold) with drills to fix to the floor
Indoor built in a poylester cabinet
Outdoor
1. Lighting Control Centre: ILUEST+ with a SICRES
card and GSM/GPRS modem.
2. Bidirectional transmission.
3. Control Centre (email)/mobile (SMS).
4. Internet. (1)
5. Internet Server. (2)
6. Technical Assistence Service.
(1) Other communication options: PLC, Ethernet, optical fiber, etc.
(2) Salicru web server or another owned by the customer.
Available options
. SICRES card.
. GSM/GPRS modem.
. Manual bypass to electrically isolate the unit during
maintenance work.
. Automatic bypass by contactors, per phase or common.
. Atmospheric gas discharger.
. Digital I/O card.
Services
· Customized studies and simulations of the saving
and payback.
. Extended warranties (under request).
@salicru_SA
www.linkedin.com/company/salicru
STANDARDS
EN-60950-1
Safety
Electromagnetic compatibility (EMC)
EN 61000-6-2; EN 61000-6-3
Quality and Environmental management
ISO 9001 and ISO 14001
(1) Depending on type of lamp
(2) Optional
RANGE
MODEL
POWER
(kVA)
NA+ 3.5-2
NA+ 5-2
NA+ 7,5-2
NA+ 10-2
NA+ 15-2
NA+ 20-2
3.5
5
7.5
10
15
20
(3) 4% power derating per each degree over 45ºC
INDOOR IMPLEMENTATION
WEIGHT
DIMENSIONS
(D x W x H mm.)
(Kg)
245 x 350 x 380
245 x 350 x 380
245 x 350 x 380
245 x 350 x 380
245 x 350 x 380
245 x 350 x 380
42
43
45
46
50
67
OUTDOOR IMPLEMENTATION
DIMENSIONS
WEIGHT
(D x W x H mm.)
(Kg)
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
72
73
75
76
80
105
Nomenclature, dimensions and weight for models: 230 V / 50 Hz input/output.
MODEL
POWER
(kVA)
NAT+ 7.5-4
NAT+ 10-4
NAT+ 15-4
NAT+ 20-4
NAT+ 25-4
NAT+ 30-4
NAT+ 45-4
NAT+ 60-4
NAT+ 80-4
NAT+ 100-4
NAT+ 120-4
7.5
10
15
20
25
30
45
60
80
100
120
INDOOR IMPLEMENTATION
WEIGHT
DIMENSIONS
(D x W x H mm.)
(Kg)
245 x 350 x 800
245 x 350 x 800
245 x 350 x 800
245 x 350 x 800
245 x 350 x 800
245 x 350 x 800
245 x 350 x 800
355 x 350 x 1100
355 x 350 x 1100
350 x 800 x 1070
350 x 800 x 1070
60
80
81
82
90
95
139
181
204
214
225
Nomenclature, dimensions and weight for models: 3x400V / 50 Hz output.
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
OUTDOOR IMPLEMENTATION
DIMENSIONS
WEIGHT
(D x W x H mm.)
(Kg)
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
320 x 520 x 1348
420 x 520 x 1348
420 x 520 x 1348
420 x 1020 x 1348
420 x 1020 x 1348
94
116
117
118
125
130
173
221
244
254
265
Data may change without previous notice.
Cartographic map of a park of equipments with SICRES system.
TECHNOLOGY
INPUT
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SICRES
Telemanagement to ILUEST+
SICRES: Complete lighting telemanagement
In any municipality, the lighting control centres are located in the street and away from the technical services, something which makes
maintenance enormously more difficult. The cost of lighting maintenance therefore increases significantly and obliges municipalities
to have brigades or subcontractors who, even without carrying out any corrective action, make periodic rounds of the streets in order
to detect problems. In the best of cases, the installations will be in an operative state and it will not be possible to obtain statistics of
faults, graphs on consumption, line quality, etc.
By incorporating the SICRES network card, Salicru offers a telemaintenance service through an Internet connection, which enables
the state of the complete fleet of equipment (including cartography) to be known at all times and failures in the equipment and/or the
control centres to the anticipated. Amongst the many services offered by the system, we might mention: sending of unattended alarms
by SMS and/or e-mail, full monitoring of the equipment, control and programming of the different parameters such as the adjustments
of the astronomic clock, transitions between states (nominal and economy), the different voltage levels, the types of lamp and a long
etc, giving an overall view of the installation at all times and providing all kinds of graphs and statistics.
1
1
1 Lighting Control Centre: ILUEST+ with
1
SICRES card and GSM/GPRS modem.
2 Two-way transmission.
3 Internet.(1)
4 Internet Server.(2)
2
5 Control Centre (e-mail) / mobile (SMS).
6
5
3
4
6 Technical Assistance Service.
(1) Other communication options: PLC, Ethernet, optical
fiber, etc.
(2) Salicru Web server or one owned by the customer.
Flow of data through remote connection SICRES
Advantages & performances
The SICRES telemaintenance system provides monitoring, analysis and technical support in real-time 24/7, thus reducing the
MTTR in the event of any unexpected incident. While the monitoring is under way, an incident and alarm log is created to enable
exhaustive analysis of the equipment, which provides valuable information on the operating tendency and identifies potential
future problems. For more important incidents and/or alarms, SICRES sends e-mails and SMS to instantly report the incident and
to enable suitable corrective action to be taken. SICRES facilitates overall lighting maintenance by including cartographic maps
with the exact location of the units. By clicking on any of them, we can find out their main parameters and enable their monitoring,
control and programming.
REF. JM808B01 CODE 401AB000587 ED. MARCH 2014 LIGTHING FLOW DIMMER-STABILISERS
SICRES
Monitoring & control
Telemanagement to ILUEST+
TECHNICAL SPECIFICATIONS
MODEL
SICRES MODULE & CONTROL CENTRE
HARDWARE PLATFORM FEATURES
“Low Power ARM9” microprocessors
128 Mb RAM
RS232 / RS485 communications and Ethernet
Storage supports: E2PROM, SPI and SD/MMC
Location map of the park equipment
S.O. in real-time WCE 5.0
MODBUS/TCP
SICRES MODULE
Functions
Data compilation and incorporation of advanced alarm
management functions and logs
Remote control and communications via RTC/GSM/GPRS/RS485,
LAN/ETHERNET, WIFI/WIMAX and protocols
Equipment
telemaintenance
E-mail automatic
sending
Configurable SMS
depending on the incident
Inclusion of native SNMP control
Consultation and remote control of the unit values by a Web interface:
sending of commands, consultations, alarm management, remote updates, etc.
Data table
Web explorer monitoring
Performances
Telnet/Web/FTP configuration
Accessed via Ethernet or serial connection
Optional access by GPRS, Wifi, Wimax
Possibility of third party system connection
SNMP protocol support for integration with network administration tools
Functions
Monitoring of different ILUEST+ equipment: information centralisation
and resending of commands from/to the different SICRES control cards
General map of the CC with display of the state of the equipment
General screen of a unit
Graphs of voltage, output intensity, power and % charge
Chart of the different parameters
Web user interface
Performances
Consultation of ILUEST+units location geographic maps
Personalised screens for perfect equipment
location, monitoring, control and programming.
Consultation/programming of specific information concerning
the different SICRES control cards
Sending of alarm notification by SMS and e-mail
Consultation of real-time data
Display of the state of the equipment in real-time: alarms, MODBUS table, ...
Versions
Generation of statistics and consultation of data log
MEASUREMENT
ALARMS
Input voltage by phase
INPUT
Output voltage by phase
SICRES Card
SICRES Box
Voltage down alarm by phase
Protections alarm
Charge level by phase
Output current by phase
In order to perfectly integrate the SICRES system
throughout the ILUEST+ range, both in present
and previous equipment, we have two versions of
the card:
Apparent power by phase
. SICRES CARD: For equipment with a slot to
insert the SICRES card. This avoids having small
devices around the unit.
Inducer temperature by phase
OUTPUT
Output protections alarm
BYPASS
Manual bypass alarm
Bypass alarm by phase
GENERAL
Overheating alarm sensors 1 and 2
Total apparent power
Cos by phase
Temperature 1 and 2 of the dissipater by phase
Frequency
Percentage saving
Overloading alarm by phase
Off-margin alarm by phase
Active power by phase
Total active power
Overloading alarm by phase
Intrusion alarm
ILUEST+ communication failure alarm
N MODULES
Overloading alarm
Bypass alarm
High and low input voltages alarm
High and low output voltages alarm
. SICRES BOX: When the equipment has no slot,
as in the case of the OEM Kits, the SICRES can
be installed externally.
High temperatures 1 and 2 (dissipater) alarm
High current in serial and parallel IGBT alarm
Bypass failure alarm
Fan failure alarm
Equipment blocked alarm
Manual bypass alarm
General alarm
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
Data may change without previous notice.
CONTROL CENTRE
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SICRES
Telemaintenance service
SICRES: Complete surveillance of your equipment
The units for protecting and controlling critical loads are normally installed in locations away from the passing or working areas,
which prevents information from being obtained on the state and alarms without sending a technician to the place of the installation.
Sometimes this lack of information means not having the protection equipment in the best state, causing considerable losses of data,
production line downtimes, etc.
To be informed at all times of the state and even anticipate possible faults in the equipment, Salicru offers the SICRES solution; the
internet telemaintenance service with different forms: BASIC, MEDIUM, PREMIUM and PREMIUM PLUS, which will allow the
customer to be advised in the event of a fault, the equipment to be monitored via web and to be accessed for control, amongst other
things, thus avoiding the unnecessary movement of maintenance personnel and reporting and solving problems before the user notices
them.
Normal status
NON urgent alarm
2
SICRES operating flow
1 Alarm location.
1
1
URGENT alarm
2
2
3
4
2 Sending/reception of information.
3 Analysis/diagnosis of information.
4 In-situ intervention of our STS
(Service & Technical Support).
5
5 Report sending.
Advantages & services
With the SICRES system, you can concentrate entirely on your business and forget about the surveillance and management of your
Salicru protection systems. Leave this responsibility in our hands, and work peacefully.
The SICRES telemaintenance allows monitoring, analysis and technical support in real time, 24/7 by Salicru professionals, thus
reducing the MTTR (mean time to repair) in any unexpected event.
During the monitoring, an events and alarms log is created that allows exhaustive analysis of the equipment, providing valuable
information on the operating tendency and thus identifying potential future problems. Likewise, every month a detailed report is
sent on the state of the customer’s equipment.
For events and/or alarms that the customer considers more important SICRES will send electronic mails and SMS messages to
instantly report the incident and start the suitable corrective action at the same time.
REF. JM658B01 CODE 401AB000456 ED. MARCH 2014 TECHNICAL SUPPORT & SERVICE
SICRES
Telemaintenance service
MODEL
BASIC
MEDIUM
PREMIUM
PREMIUM+
Monitoring from SALICRU
•
•
•
-
Web Monitoring
-
•
•
•
Telephone support
•
•
•
•
Monthly reports
•
•
•
•
Equipment location
Remote access to the unit
-
-
•
•
Personalised screens for perfect unit localisation.
Customer-owned system
-
-
-
•
SMS sending
•
•
•
•
Electronic mail
•
•
•
•
Technical support on location
•
•
•
•
Maintenance contract
•(1)
•(1)
•(1)
-
Unit parameter adjustment
-
-
•
•
(•) Included (-) Not Included
(1) Consulting procedures for maintenance contracts.
Equipment data
Unit alarms and measurements in real time.
Have a maintenance contract.
SICRES SNMP/WEB ADAPTER compatible with the unit.
Internet connection.
Versions
To perfectly integrate SICRES in all products of
the Salicru range, both current equipment and the
previous series, there are two versions:
. SICRES CARD: For product ranges with a slot for
the SICRES card. This avoids having small units
around the equipment.
. SICRES BOX: When the unit does not have a slot,
the SICRES adapter can be installed externally.
SICRES CARD
REQUIREMENTS
SICRES BOX
COMPATIBILITY
SERIES
SPS.ADVANCE
SPS.ADVANCE RT
SLC LINK
SLC TWIN
SLC TWIN PRO
SLC TWIN RT
UPS DL
SLC CUBE
SLC CUBE STR
SLC CUBE 3
SLC CUBE 3 +
SLC ELITE
(2) Equipos ≥ 1500 VA
SLC ELITE MAX
SLC X-TRA
CS IS
OPTIMUS
DC power-L
DC power-S
EMi3
RE3
(•) Compatible (-) Not compatible
(2) Equipment ≥ 1500 VA
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
SICRES CARD
SICRES BOX
SICRES+SNMP TH GX
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
-
•
•
•
•
•
-
(2)
(2)
Data may change without previous notice
FORMS
Monitoring & control
UNINTERRUPTIBLE POWER
SUPPLIES (UPS)
LIGTHING FLOW DIMMERSTABILISERS
DC POWER SYSTEMS
STATIC INVERTERS
PHOTOVOLTAIC INVERTERS
VOLTAGE STABILISERS
TECHNICAL SUPPORT & SERVICE
SOFTWARE - ADAPTERS
Management & monitoring
SOFTWARE - ADAPTERS: The best complements for a full protected installation
An Uninterruptible Power Supply (UPS) is needed to protect electrical installations from disturbance and avoid damage to the loads or
losse of data. However, this protection will not be complete until the user has a completely autonomous system that informs them of the
status of the UPS and proceeds to perform preconfigured actions.
This system consists of the management and monitoring of the UPS in real time, to allow full remote control of it all times by means of
software installed in a PC/Server and/or Ethernet/SNMP Web adapter. Salicru offers this complete solution with the: UNMS II,
RCCMD, WINPOWER and VIEWPOWER softwares and the different Ethernet/SNMP Web adapter available for each of the UPS
series.
Ethernet/SNMP: IP network integration
RCCMD: Remote shutdown application
For the perfect integration of the UPS in the computer network, the
best thing is not to depend exclusively on a computer, which is why
the Ethernet/SNMP Web adapter (Single Network Management
Protocol) enables the UPS to be completely independent without
any need to have a PC or server associated.
BOX and CARD versions: Allowing the UPS to be integrated in
the computer network. Available in box and insertable card version
for the intelligent slots of the Salicru equipment. There is also the
possibility of connecting temperature and humidity sensors and TCP,
RS-232 and RS-485 communication with MODBUS protocol.
It becomes virtually impossible to manage and monitor a UPS
in heterogeneous computer networks where different system
converge, for the less common operating system on the market do
not have this software. The RCCMD is an application that allows
the simultaneous and secure shutdown of the different servers or
Workstations of 95% of the existing platforms.
Like the most complete monitoring softwares, the RCCMD is
capable of launching messages or commands to the diferent clients
of the network.
Different actions are
executed by customized
scripts, when the order from
the SNMP Web adapter
is received. Compatible
with all operating systems,
even with virtual systems
(vmware, citrix and hyperv).
Highlighted functionalities
UNMS II: Unlimited UPS management
. Web monitoring of main parameters and status of each
equipment (mains failure, mains restored , inverter fault, bypass
transference,...).
. Warning electronic mail or SMS sending (depending on the
availability of the IT environment).
. Capacity to be integrated in SNMP platforms (Nagios).
. Closing files and servers arranging by means of RCCMD software.
. MODBUS protocol included to be integrated in industrial
applications; available by means of TCP, RS-232 or RS-485.
For networks with more than one UPS to feed the and which require
monitoring concentration from a single control post, the UNMS II
(UPS Network Managament System) software is the ideal solution.
The UNMS II allows the management of multiple installations of
all devices that have an Ethernet/SNMP Web adapter and/or
sensors.
The UNMS II has different levels or licences, which depend on the
number of UPS to be managed. Except for the basic level, when the
UNMS II licence is acquired, a screen can be personalised to make
the management of all
the UPS much easier and
intuitive.
REF. JM653C01 CODE 401AB000457 ED. MARCH 2014 TECHNICAL SUPPORT & SERVICE
SOFTWARE - ADAPTERS
Management & monitoring
TECHNICAL SPECIFICATIONS
ETHERNET/SNMP ADAPTERS
SOFTWARE
RCCMD
WINPOWER
The WINPOWER and VIEWPOWER softwares
allow shutdowns to be monitored and controlled
in the PCs where they are installed, and electronic
mails, SMS messages or broadcasts to be sent,
amongst other functions.
Options
· SENSORS: For cases where it is essential to
have all the environmental data of the room
where the UPS is located, there is a temperature
and humidity sensor that allows these data
to be included from the monitoring software
without resorting to a totally external system.
The sensor includes communication cable with
the Ethernet/SNMP Web adapter.
. DISPLAY: The perfect view of the parameters of
the UPS from a distance by means of a display
that shows any parameter from the Ethernet/
SNMP Web adapter or RCCMD software.
BOX GX5
CARD GX5
-
-
-
-
•
•
•
•
-
-
-
-
-
-
-
-
•
•
•
•
•
•
•
•
•
•
•
-
-
•
•
•
Web Browser viewing
-
-
RS-232 Communication port
-
USB Communication port
-
•
•
•
•
•
•
Ethernet TCP/IP Port
-
-
-
Ordened shutdown of the PC /server
•
Sending electronic mails
-
•
•
•
•
MODBUS Protocol (RS-232 port)
-
-
-
MODBUS Protocol (TCP)
-
-
-
•
•
•
•
•
Software UPS shutdown
-
•
•
-
-
-
-
Location in UPS slot
-
-
-
-
-
•
•
•
•
•
•
•
-
-
-
-
Different user/administrator levels
-
•
•
•
•
•
-
Monitoring of the main parameters of
the UPS
Broadcast (window) of warning in the
event of alarm
-
Time synchronisation
-
-
-
Event log
-
Value log
-
•
•
•
•
•
•
•
•
-
-
-
•
•
•
•
•
•
•
•
•
Temperature and humidity sensor
connection
•
•
•
•
•
-
-
COMPATIBILITY
ETHERNET/SNMP ADAPTERS
SOFTWARE
RCCMD
SPS.HOME
SPS.HOME 2011
SPS.ONE
SPS.SOHO
SPS.SOHO+
SPS.ADVANCE
SPS.ADVANCE RT
SLC LINK
SLC TWIN
SLC TWIN PRO
UPS DL
SLC CUBE
SLC CUBE STR
SLC CUBE3
SLC CUBE3+
SLC ELITE
SLC ELITE MAX
Display size 1300 mm x 110 mm.
TH CARD
GX5
-
SLC TWIN RT
Display size 400 mm x 110 mm.
TH BOX
GX5
Monitoring (software installed in PC)
VIEWPOWER
When you have a single work station of a small
computer network, the UPS used for their
protection are single phase low or medium power,
which means they have to be implemented in the
system management.
SNMP/WEB ADAPTER
WINPOWER VIEWPOWER
Data may change without previous notice.
WINPOWER & VIEWPOWER:
The best UPS control
SLC X-TRA
(1) Equipments ≥ 1500VA
@salicru_SA
www.linkedin.com/company/salicru
(*) Spain only (**) Rest of the world
902 48 24 00* +34 93 848 24 00** WWW.SALICRU.COM
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · [email protected]
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
SNMP/WEB ADAPTER
WINPOWER VIEWPOWER UPSMON
-
•
-
•
•
•
•
-
•
•
•
-
-
•
-
•
-
•
-
TH BOX
GX5
TH CARD
GX5
BOX GX5
CARD GX5
-
-
-
-
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
-
•
•
•
•
•
•
(1)
(1)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
(1)
(1)
-
•
•
•
•
•
•
REF. JM639I01 CODE 401AB000418 ED. APRIL 2014 PRODUCT RANGE CATALOGUE
Avda. de la Serra 100
08460 Palautordera
BARCELONA - Spain
Tel. +34 93 848 24 00
Fax +34 93 848 11 51
[email protected]
SALICRU.COM
@salicru_SA
www.linkedin.com/company/salicru
SUBSIDIARIES
CHINA
FRANCE
HUNGARY
MEXICO
REST OF WORLD
ALGERIA
ARGENTINA
BELGIUM
BRAZIL
BULGARIA
CHILE
COLOMBIA
CUBA
CZECH REPUBLIC
ECUADOR
EGYPT
MOROCCO
PORTUGAL
SINGAPORE
GERMANY
INDONESIA
IRELAND
JORDAN
KUWAIT
MALAYSIA
NETHERLANDS
PERU
PHILIPPINES
POLAND
RUSSIA
Product Range
Uninterruptible Power Supplies (UPS)
Lighting Flow Dimmer-Stabilisers
DC Power Systems
Static Inverters
Photovoltaic Inverters
Voltage stabilisers
SAUDI ARABIA
SWEDEN
SWITZERLAND
THAILAND
TUNISIA
UAE
UNITED KINGDOM
UNITED STATES OF AMERICA
URUGUAY
VENEZUELA
VIETNAM
NB: Salicru can offer other power electronics solutions depending on the specifications of the application or the technical requests
DELEGATIONS AND TECHNICAL SUPPORT & SERVICE (TSS)
BARCELONA
PALMA DE MALLORCA
BILBAO
PAMPLONA
CORUNNA
SAN SEBASTIÁN
GIJÓN
SEVILLE
LAS PALMAS DE G. CANARIA
VALENCIA
MADRID
VALLADOLID
MÁLAGA
ZARAGOZA
MURCIA
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement