OCS01-1.qxp
05.5.25 5:18 PM
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
May 2005
No. OCS01
TECHNICAL DATA BOOK R410A INVERTER
<Indoor unit>
[Model names]
PLA-RP·AA
PEAD-RP·EA
PEAD-RP·GA
PEA-RP·EA
PEH-RP·MYA
PKA-RP·GAL
PKA-RP·FAL
PCA-RP·GA
PCA-RP·HA
PSA-RP·GA
<Outdoor unit>
[Model names]
PUHZ-RP35/50/60/71/100/125/140VHA
PUHZ-RP100/125/140/200/250YHA
CONTENTS
1. REFERENCE SERVICE MANUAL·············································2
2. SPECIFICATIONS ······································································3
3. OUTLINES AND DIMENSIONS················································26
4. WIRING DIAGRAM···································································52
5. REFRIGERANT SYSTEM DIAGRAM ······································66
6. PERFORMANCE CURVES ······················································69
7. CORRECTION FACTORS ························································73
8. APPLICABLE EXTENSION PIPE FOR EACH MODEL ··········74
9. AIR FLOW DATA ······································································82
10. NOISE CRITERION CURVES ················································100
11. OPTIONAL PARTS···································································116
kW Model
OCS01-1.qxp
1
05.5.16 10:03 AM
Page 2
REFERENCE SERVICE MANUAL
For information on service, please refer to the service manual as follows.
1-1. INDOOR UNIT
Model name
Service Ref.
Service
Manual No.
OC335
PLA-RP35/50/60/71AA
PLA-RP100/125/140AA
PCA-RP50/60/71GA
PCA-RP100/125/140GA
PCA-RP71/125HA
PLA-RP35/50/60/71AA.UK
PLA-RP100/125/140AA.UK
PLA-RP35/50/60/71AA
PLA-RP100/125/140AA.UK
PCA-RP50/60/71GA
PCA-RP100/125/140GA
PCA-RP71/125HA
PKA-RP35/50GAL
PKA-RP35/50GAL
OC330
PKA-RP60/71/100FAL
PKA-RP60/71/100FAL
OC331
PSA-RP71/100/125/140GA
PSA-RP71/100/125/140GA
OC332
PEA-RP71/100/125/140EA
PEA-RP71/100/125/140EA.TH-A
OC326
PEAD-RP35/50/60/71EA
PEAD-RP100/125/140EA
PEAD-RP60/71/100GA
PEAD-RP35/50/60/71EA.UK
PEAD-RP100/125/140EA.UK
PEAD-RP60/71/100GA.UK
-
PEH-RP200/250MYA
PEH-RP200/250MYA
-
OC327
OC328
OC329
-
1-2. OUTDOOR UNIT
Model name
Service Ref.
PUHZ-RP35/50/60/71VHA
PUHZ-RP100/125/140VHA
PUHZ-RP100/125/140YHA
PUHZ-RP100/125/140VHA
PUHZ-RP35/50/60/71VHA
PUHZ-RP100/125/140VHA
PUHZ-RP100/125/140YHA
PUHZ-RP71/100/125/140VHA-A
PUHZ-RP200/250YHA
PUHZ-RP200/250YHA
OC338
PUHZ-RP200/250YHA-A
OC339
2
Service
Manual No.
OC334
OC337
OCS01-1.qxp
05.5.25 11:42 AM
Page 3
SPECIFICATIONS
2
2-1. CEILING CASSETTE TYPE
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
12,300
17,100
kW
3.6(1.6-4.5)
5.0(2.3-5.6)
kW
Energy label class
SHF
Capacity
Total input
A
A
0.89
0.86
14,000
20,500
4.1(1.6-5.2)
6.0(2.5-7.3)
kW
kW
1.12
1.62
3.66
3.70
A
A
-
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
1.55
3.23
kW
Energy label class
Power supply
1.07
3.36
Btu/h
COP
Booster heater
PLA-RP50AA
PUHZ-RP50VHA
Btu/h
EER
Heating
PLA-RP35AA
PUHZ-RP35VHA
1
A
16
Air flow
CMM
11-12-13-14
14-15-16-18
(Low-Medium2-Medium1-High)
CFM
390-425-460-495
495-530-565-635
External pressure
Sound level
Pa
0
0
dB(A)
27-28-29-31
28-29-31-33
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
White Munsell 0.70Y 8.59/0.97
W : mm
840 (950)
D : mm
840 (950)
H : mm
258 (30)
W : inch
33-1/16 (37-3/8)
D : inch
33-1/16 (37-3/8)
H : inch
10-3/16 (1-3/16)
Weight
Unit (Panel)
Unit drain pipe I.D.
Outdoor unit
Air flow
kg
24 (5)
lbs
53 (11)
mm
32
inch
1-1/4
CMM
35
CFM
1,240
Sound level at cooling
dB(A)
44
Sound level at heating
dB(A)
External finish
Dimension
W : mm
800
D : mm
330+23
H : mm
600
W : inch
31-1/2
D : inch
13 + 7/8
H : inch
23-5/8
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
kg
45
lbs
99
mm
12.7
inch
1/2
mm
6.35
inch
1/4
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
46
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
3
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 4
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
20,500
24,200
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
kW
Energy label class
SHF
Capacity
Total input
A
A
0.78
0.74
23,900
27,300
7.0(2.8-8.2)
8.0(3.5-10.2)
kW
kW
1.85
2.34
3.78
3.42
A
B
-
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
1.97
3.60
kW
Energy label class
Power supply
1.65
3.64
Btu/h
COP
Booster heater
PLA-RP71AA
PUHZ-RP71VHA
Btu/h
EER
Heating
PLA-RP60AA
PUHZ-RP60VHA
1
A
25
Air flow
CMM
14-15-16-18
15-16-18-20
(Low-Medium2-Medium1-High)
CFM
495-530-565-635
530-565-635-705
External pressure
Sound level
Pa
0
0
dB(A)
28-29-31-33
28-30-32-34
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Unit drain pipe I.D.
Outdoor unit
Air flow
White Munsell 0.70Y 8.59/0.97
W : mm
840 (950)
D : mm
840 (950)
H : mm
258 (30)
W : inch
33-1/16 (37-3/8)
D : inch
33-1/16 (37-3/8)
H : inch
10-3/16 (1-3/16)
kg
24 (5)
lbs
53 (11)
mm
32
inch
1-1/4
CMM
55
CFM
1,940
Sound level at cooling
dB(A)
47
Sound level at heating
dB(A)
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
kg
75
lbs
165
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
48
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
4
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 5
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
PLA-RP100AA
PLA-RP125AA
PLA-RP140AA
PUHZ-RP100VHA
PUHZ-RP125VHA
PUHZ-RP140VHA
Btu/h
34,100
42,700
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
EER
Energy label class
SHF
Heating
Capacity
Total input
A
A
C
0.77
0.74
0.70
38,200
47,800
54,600
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
kW
3.39
4.27
4.91
3.30
3.28
3.26
C
C
C
-
-
-
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
4.99
2.81
kW
Energy label class
Power supply
3.89
3.21
Btu/h
COP
Booster heater
3.03
3.30
1
A
32
40
Air flow
CMM
20-23-26-28
22-25-28-30
(Low-Medium2-Medium1-High)
CFM
705-810-920-990
775-880-990-1,060
Pa
0
0
dB(A)
33-36-39-41
37-40-43-45
External pressure
Sound level
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
White Munsell 0.70Y 8.59/0.97
W : mm
840 (950)
D : mm
840 (950)
H : mm
298 (30)
W : inch
33-1/16 (37-3/8)
D : inch
33-1/16 (37-3/8)
H : inch
Weight
Unit (Panel)
Unit drain pipe I.D.
Outdoor unit
Air flow
30 (5)
32 (5)
lbs
66 (11)
71 (11)
mm
32
inch
1-1/4
CMM
100
CFM
3,530
Sound level at cooling
dB(A)
49
Sound level at heating
dB(A)
51
External finish
Dimension
NOTE:
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
Gas side O.D.
kg
121
lbs
267
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
52
W : mm
Liquid side O.D.
Refrigerant pipe length
50
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe size
11-3/4 (1-3/16)
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
5
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 6
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
PLA-RP100AA
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
3.03
3.30
A
0.77
38,200
11.2(4.5-14.0)
3.39
3.30
C
-
20-23-26-28
705-810-920-990
0
33-36-39-41
PLA-RP125AA
PLA-RP140AA
PUHZ-RP125YHA
PUHZ-RP140YHA
42,700
47,800
12.5(5.5-14.0)
14.0(5.5-15.3)
3.89
4.99
3.21
2.81
A
C
0.74
0.70
47,800
54,600
14.0(5.0-16.0)
16.0(5.0-18.0)
4.27
4.91
3.28
3.26
C
C
3
50
400
16
22-25-28-30
775-880-990-1,060
0
37-40-43-45
(Low-Medium2-Medium1-High)
External finish (Panel)
Dimension
Unit (Panel)
Weight
Unit (Panel)
Unit drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
49
51
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
30 (5)
66 (11)
White Munsell 0.70Y 8.59/0.97
840 (950)
840 (950)
298 (30)
33-1/16 (37-3/8)
33-1/16 (37-3/8)
11-3/4 (1-3/16)
32 (5)
71 (11)
32
1-1/4
100
3,530
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
6
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Page 7
2-2. CEILING-CONCEALED TYPE
Model name
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
12,300
16,700
kW
3.6(1.6-4.5)
4.9(2.3-5.6)
kW
Energy label class
SHF
Capacity
Total input
A
A
0.88
0.82
14,000
20,500
4.1(1.6-5.2)
6.0(2.5-7.3)
kW
kW
1.26
1.65
3.25
3.64
C
A
-
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
1.52
3.22
kW
Energy label class
Power supply
1.12
3.21
Btu/h
COP
Booster heater
PEAD-RP50EA
PUHZ-RP50VHA
Btu/h
EER
Heating
PEAD-RP35EA
PUHZ-RP35VHA
1
A
16
Air flow
CMM
11-14
13.5-17
(Low-High)
CFM
388-494
476-600
External pressure
Pa
Sound level
dB(A)
(Low-High)
30(70)
34-38
36-40
(70Pa : 36-43)
(70Pa : 38-44)
External finish
Dimension
Galvanized sheets
W : mm
935
D : mm
700
H : mm
295
W : inch
36-13/16
D : inch
27-5/8
H : inch
Weight
33
35
lbs
73
77
Unit drain pipe
Outdoor unit
R1(External thread)
Air flow
CMM
35
CFM
1,240
Sound level at cooling
dB(A)
44
Sound level at heating
dB(A)
External finish
Dimension
W : mm
800
D : mm
330+23
H : mm
600
W : inch
31-1/2
D : inch
13 + 7/8
H : inch
23-5/8
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
kg
45
lbs
99
mm
12.7
inch
1/2
mm
6.35
inch
1/4
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
46
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe size
11-5/8
kg
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
7
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Page 8
Indoor unit
Outdoor unit
Capacity
Total input
20,500
24,200
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
kW
Energy label class
SHF
Total input
1.86
2.15
3.23
3.30
A
A
0.79
0.83
Btu/h
23,900
27,300
kW
7.0(2.8-8.2)
8.0(3.5-10.2)
kW
COP
Energy label class
Booster heater
PEAD-RP71EA
PUHZ-RP71VHA
Btu/h
EER
Capacity
PEAD-RP60EA
PUHZ-RP60VHA
kW
1.90
2.34
3.68
3.42
A
B
-
-
Phase
[
Cycle
Hz
50
V
230
Voltage
Breaker size
1
A
25
Air flow
CMM
17-21
20-25
(Low-High)
CFM
600-741
706-883
Pa
30(70)
70(130)
dB(A)
37-41
37-41
(70Pa : 39-46)
(130Pa : 40-45)
External pressure
Sound level
(Low-High)
External finish
Dimension
Galvanized sheets
W : mm
1175
D : mm
700
H : mm
295
W : inch
46-1/8
D : inch
27-5/8
H : inch
Weight
11-5/8
kg
42
44
lbs
92
97
Unit drain pipe
Air flow
R1(External thread)
CMM
55
55
CFM
1,940
1,940
Sound level at cooling
dB(A)
47
47
Sound level at heating
dB(A)
48
48
External finish
Dimension
Weight
Gas side O.D.
Liquid side O.D.
Ivory Munsell 3Y 7.8/1.1
W : mm
950
950
D : mm
330+30
330+30
H : mm
943
943
W : inch
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
37-1/8
kg
75
75
lbs
165
165
15.88
mm
15.88
inch
5/8
5/8
mm
9.52
9.52
inch
3/8
3/8
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 50
NOTE:
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
8
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 9
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
PEAD-RP100EA
PEAD-RP125EA
PEAD-RP140EA
PUHZ-RP100VHA
PUHZ-RP125VHA
PUHZ-RP140VHA
Btu/h
34,100
42,700
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
EER
Energy label class
SHF
Heating
Capacity
Total input
A
A
C
0.83
0.82
0.82
38,200
47,800
54,600
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
kW
3.48
4.11
4.76
3.22
3.41
3.36
C
B
C
-
-
-
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
4.91
2.85
kW
Energy label class
Power supply
3.69
3.39
Btu/h
COP
Booster heater
3.08
3.25
1
A
32
CMM
27-34
33.5-42
36.5-46
(Low-High)
CFM
953-1200
1183-1483
1288-1624
External pressure
Pa
Sound level
70(130)
dB(A)
(Low-High)
41-46
44-50
46-51
(130Pa : 42-48)
(130Pa : 46-52)
(130Pa : 47-53)
External finish
Dimension
Galvanized sheets
W : mm
1415
D : mm
700
H : mm
295
W : inch
H : inch
11-5/8
kg
62
65
70
lbs
136
143
154
100
CFM
3,530
dB(A)
49
Sound level at heating
dB(A)
51
50
52
Ivory Munsell 3Y 7.8/1.1
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
Gas side O.D.
Liquid side O.D.
kg
121
lbs
267
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
12-13/16
CMM
Sound level at cooling
Weight
NOTE:
29-1/8
R1(External thread)
External finish
Refrigerant pipe length
67-1/2
27-5/8
Air flow
Refrigerant pipe size
325
55-11/16
Unit drain pipe
Dimension
1715
740
D : inch
Weight
Outdoor unit
40
Air flow
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
9
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 10
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
Unit drain pipe
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Upper limit
Lower limit
Upper limit
Heating
Lower limit
PEAD-RP125EA
PEAD-RP140EA
PUHZ-RP125YHA
PUHZ-RP140YHA
42,700
47,800
12.5(5.5-14.0)
14.0(5.5-15.3)
3.69
4.91
3.39
2.85
A
C
0.82
0.82
47,800
54,600
14.0(5.0-16.0)
16.0(5.0-18.0)
4.11
4.76
3.41
3.36
B
C
3
50
400
16
27-34
33.5-42
36.5-46
953-1200
1183-1483
1288-1624
70(130)
41-46
44-50
46-51
(130Pa : 42-48)
(130Pa : 46-52)
(130Pa : 47-53)
Galvanized sheets
1415
1715
700
740
295
325
55-11/16
67-1/2
27-5/8
29-1/8
11-5/8
12-13/16
62
65
70
136
143
154
R1(External thread)
CMM
CFM
dB(A)
dB(A)
100
3,530
49
51
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PEAD-RP100EA
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
3.08
3.25
A
0.83
38,200
11.2(4.5-14.0)
3.48
3.22
C
-
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -20˚C, W.B. -20˚C
D.B. 17˚C
10
3. Guaranteed voltage
Indoor unit
198~264V, 50Hz
Outdoor unit
342~457V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
3 phase 400V 50Hz
w
If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 11
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
PEAD-RP71GA
PUHZ-RP71VHA
24,200
7.1(3.3-8.1)
2.15
3.30
A
0.83
27,300
8.0(3.5-10.2)
2.34
3.42
B
1
50
230
25
16.5-21
582-741
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
PEAD-RP60GA
PUHZ-RP60VHA
20,500
6.0(2.7-6.7)
1.68
3.57
A
0.88
23,900
7.0(2.8-8.2)
1.77
3.95
A
-
20-25
706-883
10/50/70
33-37/35-40/36-42
35-38/37-41/37-43
(10/50/70Pa)
(10/50/70Pa)
Galvanized sheets
1171
740
275
46-1/8
29-1/8
10-13/16
42
93
32
1-1/4
55
1,940
47
48
Ivory Munsell 3Y 7.8/1.1
950
330+30
943
37-3/8
13 + 1-3/16
37-1/8
75
165
15.88
5/8
9.52
3/8
Max. 30
Max. 50
PEAD-RP100GA
PUHZ-RP100VHA
34,100
10.0(4.9-11.4)
3.08
3.25
A
0.83
38,200
11.2(4.5-14.0)
3.48
3.22
C
-
32
26.5-33
935-1165
10/50/70
40-43/42-45/42-46
(10/50/70Pa)
1411
55-9/16
50
111
100
3,530
49
51
1350
53-1/8
121
267
Max. 30
Max. 75
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
11
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 12
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
PEAD-RP100GA
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
3.08
3.25
A
0.83
38,200
11.2(4.5-14.0)
3.48
3.22
C
3
50
400
16
26.5-33
935-1165
10/50/70
40-43/42-45/42-46
(10/50/70Pa)
Galvanized sheets
1411
740
275
55-9/16
29-1/8
10-13/16
50
111
32
1-1/4
100
3,530
49
51
Ivory Munsell 3Y 7.8/1.1
943
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
12
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Page 13
Model name
Indoor unit
PEA-RP71EA
Outdoor unit
Cooling
Capacity
PUHZ-RP71VHA
Btu/h
24,200
kW
7.1(3.3-8.1)
Total input
kW
2.86
SRI
3.87
SHF
Heating
Capacity
0.82
Btu/h
27,300
kW
8.0(3.5-10.2)
Total input
kW
COP
4.13
Booster heater
kW
-
Phase
[
1
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
2.47
3.24
SRI
Power supply
2.48
EER
A
25
Air flow
CMM
22-27
(Low-High)
CFM
780-955
External pressure
Sound level
Pa
125
dB(A)
52-55
(Low-High)
External finish
Dimension
Galvanized sheets
W : mm
785
D : mm
690
H : mm
428
W : inch
31
D : inch
27-1/16
H : inch
16-7/8
Weight
kg
46
lbs
101
Unit drain pipe
Outdoor unit
Air flow
R1(External thread)
CMM
55
CFM
1,940
Sound level at cooling
dB(A)
47
Sound level at heating
dB(A)
External finish
Dimension
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
Weight
Refrigerant pipe size
Gas side O.D.
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
75
lbs
165
mm
15.88
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
kg
inch
Liquid side O.D.
Refrigerant pipe length
48
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
13
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 14
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
Heating
PEA-RP100EA
PEA-RP125EA
PEA-RP140EA
PUHZ-RP100VHA
PUHZ-RP125VHA
PUHZ-RP140VHA
Btu/h
34,100
42,700
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
3.25
4.42
5.03
EER
kW
3.08
2.83
2.78
SRI
4.60
3.77
3.60
SHF
0.82
0.81
0.89
Btu/h
38,200
47,800
54,600
kW
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
3.2
4.30
4.73
3.50
3.26
3.38
5.00
4.20
4.60
-
-
-
Capacity
Total input
COP
SRI
Booster heater
Power supply
kW
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
1
A
32
40
Air flow
CMM
27-34
34-42
48-60
(Low-High)
CFM
955-1200
1200-1480
1695-2120
External pressure
Pa
Sound level
125
dB(A)
54-58
51-55
(Low-High)
External finish
Dimension
Galvanized sheets
W : mm
1055
1255
D : mm
H : mm
428
W : inch
41-1/2
D : inch
49-7/16
16-7/8
kg
58
72
73
lbs
128
159
161
Unit drain pipe
Outdoor unit
R1(External thread)
Air flow
CMM
100
CFM
3,530
Sound level at cooling
dB(A)
49
Sound level at heating
dB(A)
51
External finish
Dimension
NOTE:
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
Gas side O.D.
kg
121
lbs
267
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
52
W : mm
Liquid side O.D.
Refrigerant pipe length
50
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe size
55-3/4
27-1/16
H : inch
Weight
1415
690
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
14
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 3:17 PM
Model name
Page 15
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
External pressure
Sound level
External finish
Dimension
Weight
PEH-RP200MYA
PUHZ-RP200YHA
64,800
19.0(10.0-22.4)
7.28
2.61
D
0.75
76,400
22.4(10.0-25.0)
6.98
3.21
C
-
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
3
50
400
32
60
2120
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
50/150
Upper limit
Lower limit
Upper limit
Heating
Lower limit
53
(50Pa)
Galvanizing
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
1380
1580
650
428
54-5/16
62-3/16
25-9/16
16-7/8
70
154
80
176
RC1
CMM
CFM
dB(A)
dB(A)
150
5,300
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
80
2825
49
(50Pa)
Unit drain pipe
Outdoor unit
PEH-RP250MYA
PUHZ-RP250YHA
75,000
22.0(12.5-28.0)
8.43
2.61
D
0.82
92,100
27.0(15.7-31.5)
8.41
3.21
C
-
55
58
56
58
Ivory Munsell 3Y 7.8/1.1
900
750
1798
35-7/16
29-17/32
70-25/32
198
436
25.4
28.58
1
1-1/8
9.52
12.7
3/8
1/2
Max. 40
Max. 120
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
15
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Page 16
2-3. WALL-MOUNTED TYPE
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
PKA-RP35GAL
PUHZ-RP35VHA
12,300
3.6(1.6-4.5)
1.03
3.50
A
0.84
14,000
4.1(1.6-5.2)
1.27
3.23
C
-
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
PKA-RP50GAL
PUHZ-RP50VHA
15,700
4.6(2.3-5.4)
1.63
2.82
C
0.74
15,400
4.5(2.5-6.2)
1.40
3.21
C
-
1
50
230
16
9-10-11-12
320-355-390-425
0
36-38-41-43
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
White Munsell 0.70Y 8.59/0.97
990
235
340
39
9-1/4
13-3/8
16
35
20
13/16
35
1,240
44
46
Ivory Munsell 3Y 7.8/1.1
800
330+23
600
31-1/2
13 + 7/8
23-5/8
45
99
12.7
1/2
6.35
1/4
Max. 30
Max. 50
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
16
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 17
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length Height difference
Length
NOTE:
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
PKA-RP100FAL
PUHZ-RP100VHA
34,100
10.0(4.9-11.4)
2.93
3.41
A
0.77
38,200
11.2(4.5-14.0)
3.25
3.45
B
-
32
22-28
780-990
0
39-45
Munsell 3.4Y 7.7/0.8
1400
235
340
55-1/8
9-1/4
13-3/8
24
53
20
13/16
55
1,940
47
48
Ivory Munsell 3Y 7.8/1.1
950
330+30
943
37-3/8
13 + 1-3/16
37-1/8
75
165
15.88
5/8
9.52
3/8
Max. 30
Max. 50
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
PKA-RP71FAL
PUHZ-RP71VHA
24,200
7.1(3.3-8.1)
1.98
3.59
A
0.77
27,300
8.0(3.5-10.2)
2.40
3.33
C
1
50
230
25
15-20
530-705
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PKA-RP60FAL
PUHZ-RP60VHA
20,500
6.0(2.7-6.7)
1.55
3.87
A
0.83
23,900
7.0(2.8-8.2)
2.01
3.48
B
-
41-46
1680
66-1/8
28
62
100
3,530
49
51
1350
53-1/8
121
267
Max. 30
Max. 75
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
17
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP100 D.B. -20:, W.B. -20:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 18
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length Height difference
Length
NOTE:
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
PKA-RP100FAL
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
2.93
3.41
A
0.77
38,200
11.2(4.5-14.0)
3.25
3.45
B
3
50
400
16
22-28
780-990
0
41-46
Munsell 3.4Y 7.7/0.8
1680
235
340
66-1/8
9-1/4
13-3/8
28
62
20
13/16
100
3,530
49
51
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
18
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Page 19
2-4. CEILING-SUSPENDED TYPE
Model name
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
PCA-RP50GA
PUHZ-RP50VHA
16,000
4.7(2.3-5.4)
1.67
2.81
C
0.76
18,800
5.5(2.5-6.6)
1.71
3.22
C
-
16
10-11-12-13
355-390-425-460
0
37-38-40-42
PCA-RP60GA
PUHZ-RP60VHA
20,500
6.0(2.7-6.7)
1.63
3.68
A
0.81
23,900
7.0(2.8-8.2)
2.03
3.45
B
1
50
230
PCA-RP71GA
PUHZ-RP71VHA
24,200
7.1(3.3-8.1)
2.14
3.32
A
0.74
27,300
8.0(3.5-10.2)
2.43
3.29
C
-
25
14-15-16-18
495-530-565-635
0
37-39-41-43
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Unit drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
39-3/8
27
60
35
1,240
44
46
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
1000
800
330+23
600
31-1/2
13 + 7/8
23-5/8
45
99
12.7
1/2
6.35
1/4
Max. 30
Max. 50
White Munsell 0.70Y 8.59/0.97
1310
680
210
51-9/16
26-3/4
8-1/4
34
75
26
1
55
1,940
47
48
Ivory Munsell 3Y 7.8/1.1
950
330+30
943
37-3/8
13 + 1-3/16
37-1/8
75
165
15.88
5/8
9.52
3/8
Max. 30
Max. 50
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
19
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 2:11 PM
Model name
Page 20
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
PCA-RP100GA
PUHZ-RP100VHA
34,100
10.0(4.9-11.4)
2.92
3.42
A
0.75
38,200
11.2(4.5-14.0)
3.26
3.44
B
-
PCA-RP125GA
PUHZ-RP125VHA
42,700
12.5(5.5-14.0)
3.89
3.21
A
0.77
47,800
14.0(5.0-16.0)
4.34
3.23
C
1
50
230
32
20-21-23-25
705-840-810-885
0
40-41-43-45
PCA-RP140GA
PUHZ-RP140VHA
47,800
14.0(5.5-15.3)
4.96
2.82
C
0.74
54,600
16.0(5.0-18.0)
4.60
3.48
B
-
40
27-30-32-34
955-1060-1130-1200
0
41-43-45-46
42-44-46-48
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Unit drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
51-9/16
37
82
49
51
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
1310
White Munsell 0.70Y 8.59/0.97
1620
680
270
63-3/4
26-3/4
10-5/8
43
95
26
1
100
3,530
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
121
267
15.88
5/8
9.52
3/8
Max. 30
Max. 75
45
99
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
20
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 21
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-Medium2-Medium1-High)
External pressure
Sound level
PCA-RP100GA
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
2.92
3.42
A
0.75
38,200
11.2(4.5-14.0)
3.26
3.44
B
-
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
20-21-23-25
705-840-810-885
0
40-41-43-45
PCA-RP125GA
PCA-RP140GA
PUHZ-RP125YHA
PUHZ-RP140YHA
42,700
47,800
12.5(5.5-14.0)
14.0(5.5-15.3)
3.89
4.96
3.21
2.82
A
C
0.77
0.74
47,800
54,600
14.0(5.0-16.0)
16.0(5.0-18.0)
4.34
4.60
3.23
3.48
C
B
3
50
400
16
27-30-32-34
955-1060-1130-1200
0
41-43-45-46
42-44-46-48
(Low-Medium2-Medium1-High)
External finish
Dimension
Weight
Unit drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
1310
51-9/16
37
82
49
51
White Munsell 0.70Y 8.59/0.97
1620
680
270
63-3/4
26-3/4
10-5/8
43
95
26
1
100
3,530
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
45
99
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
21
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 2:12 PM
Model name
Page 22
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe I.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length Height difference
Length
NOTE:
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
PCA-RP125HA
PUHZ-RP125VHA
42,700
12.5(5.5-14.0)
4.15
3.01
B
0.77
47,800
14.0(5.0-16.0)
4.25
3.29
C
1
50
230
25
17-19
600-670
0
34-38
32
PCA-RP125HA
PUHZ-RP125YHA
42,700
12.5(5.5-14.0)
4.15
3.01
B
0.77
47,800
14.0(5.0-16.0)
4.25
3.29
C
3
50
400
16
30-38
1060-1350
0
44-50
Stainless steel
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PCA-RP71HA
PUHZ-RP71VHA
24,200
7.1(3.3-8.1)
2.21
3.21
A
0.74
27,300
8.0(3.5-10.2)
2.49
3.21
C
-
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
1136
1520
650
280
44-3/4
59-7/8
25-5/8
11
41
90
56
124
26
1
55
1,940
47
48
950
330+30
943
37-3/8
13 + 1-3/16
37-1/8
75
165
15.88
5/8
9.52
3/8
Max. 30
Max. 50
100
3,530
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
121
267
15.88
5/8
9.52
3/8
Max. 30
Max. 75
135
298
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Outdoor
D.B. 46˚C
D.B. -5˚C
w1
D.B. 21˚C, W.B. 15˚C
D.B. -11˚C, W.B. -12˚C w2
22
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w1. If optional Air protect guide installed. D.B.-15:
w2. For RP125 D.B. -20:, W.B. -20:
OCS01-1.qxp
05.5.25 11:42 AM
Page 23
2-5. FLOOR STANDING TYPE
Model name
Indoor unit
PSA-RP71GA
Outdoor unit
Cooling
PUHZ-RP71VHA
Capacity
Btu/h
24,200
kW
7.1(3.3-8.1)
Total input
kW
2.20
EER
3.23
Energy label class
A
SHF
Heating
0.73
Capacity
Btu/h
27,300
kW
8.0(3.5-10.2)
Total input
kW
2.49
COP
3.21
Energy label class
C
Booster heater
Power supply
kW
-
Phase
[
1
Cycle
Hz
50
V
230
Voltage
Breaker size
Indoor unit
A
25
Air flow
CMM
15-18
(Low-High)
CFM
530-635
External pressure
Sound level
Pa
0
dB(A)
40-45
(Low-High)
External finish
White Munsell 0.70Y 8.59/0.97
Dimension
W : mm
600
D : mm
270
H : mm
1900
W : inch
23-5/8
D : inch
10-5/8
H : inch
74-13/16
kg
43
lbs
98
Weight
Unit drain pipeO.D.
Outdoor unit
Air flow
mm
20
inch
13/16
CMM
55
CFM
1,940
Sound level at cooling
dB(A)
47
Sound level at heating
dB(A)
External finish
Dimension
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Upper limit
Lower limit
Upper limit
Heating
Lower limit
kg
75
lbs
165
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 50
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
48
Ivory Munsell 3Y 7.8/1.1
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
D.B. 21˚C, W.B. 15˚C
D.B. 28˚C
D.B. -11˚C, W.B. -12˚C
D.B. 17˚C
23
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 24
Indoor unit
Outdoor unit
Cooling
Capacity
Total input
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
PUHZ-RP100VHA
PUHZ-RP125VHA
PUHZ-RP140VHA
Btu/h
34,100
42,700
47,800
kW
10.0(4.9-11.4)
12.5(5.5-14.0)
14.0(5.5-15.3)
kW
EER
Energy label class
SHF
Heating
Capacity
Total input
A
B
C
0.81
0.75
0.73
38,200
47,800
54,600
11.2(4.5-14.0)
14.0(5.0-16.0)
16.0(5.0-18.0)
kW
kW
3.28
4.36
4.98
3.41
3.21
3.21
B
C
C
-
-
-
Phase
[
Cycle
Hz
50
Voltage
V
230
Breaker size
Indoor unit
4.98
2.81
kW
Energy label class
Power supply
4.15
3.01
Btu/h
COP
Booster heater
2.99
3.34
1
A
32
40
Air flow
CMM
24-31
26-33
27-35
(Low-High)
CFM
850-1060
920-1165
955-1240
External pressure
Pa
Sound level
0
dB(A)
44-49
46-51
47-52
(Low-High)
External finish
Dimension
White Munsell 0.70Y 8.59/0.97
W : mm
600
D : mm
350
H : mm
1900
W : inch
23-5/8
D : inch
13-3/4
H : inch
74-13/16
Weight
Unit drain pipeO.D.
Outdoor unit
Air flow
kg
51
53
lbs
112
117
mm
20
inch
13/16
CMM
100
CFM
3,530
Sound level at cooling
dB(A)
49
Sound level at heating
dB(A)
51
External finish
Dimension
W : mm
950
D : mm
330+30
H : mm
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
53-1/8
kg
121
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
lbs
267
mm
15.88
inch
5/8
mm
9.52
inch
3/8
Height difference
m
Max. 30
Length
m
Max. 75
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Heating
Lower limit
Cooling
52
Ivory Munsell 3Y 7.8/1.1
Weight
Refrigerant pipe size
50
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
24
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
05.5.25 11:42 AM
Model name
Page 25
Cooling
Indoor unit
Outdoor unit
Capacity
Heating
Total input
EER
Energy label class
SHF
Capacity
Power supply
Indoor unit
Total input
COP
Energy label class
Booster heater
Phase
Cycle
Voltage
Breaker size
Air flow
(Low-High)
External pressure
Sound level
(Low-High)
External finish
Dimension
Weight
Unit drain pipe O.D.
Outdoor unit
Air flow
Sound level at cooling
Sound level at heating
External finish
Dimension
Weight
Refrigerant pipe size
Gas side O.D.
Liquid side O.D.
Refrigerant pipe length
NOTE:
Height difference
Length
Btu/h
kW
kW
Btu/h
kW
kW
kW
[
Hz
V
A
CMM
CFM
Pa
dB(A)
Upper limit
Lower limit
Upper limit
Heating
Lower limit
24-31
850-1060
44-49
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
CMM
CFM
dB(A)
dB(A)
W : mm
D : mm
H : mm
W : inch
D : inch
H : inch
kg
lbs
mm
inch
mm
inch
m
m
1. Rating conditions (ISO T1)
Cooling
Indoor : D.B. 27: (80˚F) W.B. 19: (66˚F)
Heating
Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Cooling
PSA-RP100GA
PUHZ-RP100YHA
34,100
10.0(4.9-11.4)
2.99
3.34
A
0.81
38,200
11.2(4.5-14.0)
3.28
3.41
B
-
51
112
49
51
PSA-RP125GA
PUHZ-RP125YHA
42,700
12.5(5.5-14.0)
4.15
3.01
B
0.75
47,800
14.0(5.0-16.0)
4.36
3.21
C
3
50
400
16
26-33
920-1165
0
46-51
PSA-RP140GA
PUHZ-RP140YHA
47,800
14.0(5.5-15.3)
4.98
2.81
C
0.73
54,600
16.0(5.0-18.0)
4.98
3.21
C
-
White Munsell 0.70Y 8.59/0.97
600
350
1900
23-5/8
13-3/4
74-13/16
51
112
20
13/16
100
3,530
50
52
Ivory Munsell 3Y 7.8/1.1
950
330+30
1350
37-3/8
13 + 1-3/16
53-1/8
135
298
15.88
5/8
9.52
3/8
Max. 30
Max. 75
27-35
955-1240
47-52
53
117
Outdoor : D.B. 35: (95˚F) W.B. 24: (75˚F)
Outdoor : D.B. 7: (45˚F) W.B. 6: (43˚F)
Indoor
Outdoor
D.B. 35˚C, W.B. 22.5˚C D.B. 46:
D.B. 19˚C, W.B. 15˚C
D.B. -5:
w
D.B. 21:, W.B. 15:
D.B. 28˚C
D.B. -20:, W.B. -20:
D.B. 17˚C
25
3. Guaranteed voltage
198~264V, 50Hz
4. Above data based on indicated voltage
Indoor unit
Single phase 230V 50Hz
Outdoor unit
Single phase 230V 50Hz
w If optional Air protect guide installed. D.B.-15:
OCS01-1.qxp
3
05.5.25 11:42 AM
Page 26
OUTLINES AND DIMENSIONS
Unit : mm
INDOOR UNIT
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
PLA-RP100AA PLA-RP125AA PLA-RP140AA
Ceiling hole
860 - 910
20 - 45
20 - 45
159
20 - 45
810
Suspension bolt pitch
Fresh air intake
197
{125
Burring hole pitch
120 _
158
20 - 45
3 - {2.8
Burring hole
120_
159
16
C
89
Detail drawing of fresh air intake
98
192
{150
159
840
{100
(Cut out hole)
Suspension bolt M10
or W3/8
1
Ceiling surface
Feeding hole
(Drain pump)
286
374
60
860 - 910
Ceiling hole
Terminal block
840
14 - {2.8
Burring hole
Suspension bolt pitch
605
Branch duct hole
350
{175
167
155
159
130
70_
100
90 100 100 90
Branch duct hole
(Cut out hole)
Drain pipe
VP-25connection
(O.D.{32)
Control wire entry
Power line entry
B
190
Ceiling surface
High efficiency filter
& Fresh air intake casement (option)
17 +50
135
Suspension bolt lower edge
17 +50
30
105
140
50 - 70
170
A
2
577
Air intake hole
Air intake grille
Grille
Drain hole
M
A
M
Emergency operation switch (cooling)
950
Emergency operation switch (heating)
Auto vane
577
Air intake hole
(WIRELESS PANEL)
411
Air outlet hole
A
DEFROST/STAND BY lamp
M
Receiver
77
Operation lamp
M
51
411
Air outlet hole
950
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
1 LIQUID SIDE
2 GAS SIDE
RP35, 50
RP60
RP71
RP100, 125, 140
[6.35
[6.35
—
—
[9.52
[9.52
[9.52
[9.52
[12.7
—
—
—
[15.88
[15.88
[15.88
[15.88
—
—
—
[19.05
Models
A
B
C
PLA-RP60,71AA
241
258
80
PLA-RP100,125,140AA
281
298
84
PLA-RP35,50AA
Factory flare nut attachment to the heat-exchanger.
26
Vane motor
77
51
Branch
duct hole
OCS01-1.qxp
05.5.25 11:42 AM
Page 27
Unit : mm
PEAD-RP35EA
PEAD-RP50EA
PEAD-RP60EA
Model
A
RP35,50 772
RP60
B
305
1012 280
w Setting at shipment
F
G
R410A Outdoor unit : 6.35 w R410A Outdoor unit : 12.7 w
R407C Outdoor unit : 9.52 R407C Outdoor unit : 15.88
Outdoor unit (SUZ) : 6.35
15.88
290 1070 1044
R407C Outdoor unit : 9.52 w
C
D
E
-
830
804
Service space:500 or more
50~150 29
Refrigerant piping flare connection (liquid [ F copper tube):HP
Refrigerant piping flare connection (gas [G copper tube):LP
Drain R1(External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP-25(I.D. [32)
Filter
55
Access door
81
C
B
81
197
450
Lifting bolt hole
(14×22)
C
13
13
30
277
45 80
85
282
288
256
176
Air inlet
E
6
40
24
10
179
227
2
35
1
243
109
3.5
21
10
10- [3 (RP35,50)
12- [3 (RP60)
D
30
61
4
In case of rear inlet
81
A
44 75
640
30
B
10
18
56
355
365~465
159
1
2
3
4
5
6
7
10- [3 (RP35,50)
12- [3 (RP60)
A
10
450
5
7
3.5
Air outlet
3
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
In case of bottom inlet
10- [3 (RP35,50)
12- [3 (RP60)
Air outlet
10
7
40
15
176
256
10
3.5
81
C
B
81
A
Air inlet
PEAD-RP71EA
PEAD-RP100EA
PEAD-RP125EA
PEAD-RP140EA
Service space:500 or more
Air inlet
375
44
243
6
5
7
Lifting bolt hole
(14x22)
12-[3
307
45 122
113
1
81
80
2
20
53
B
365~465
323
308
30
10
680
C
197
450
169
210
30
12-[3
A
81
81
35
7
140
6
282
5
3.5
30
4
40
3
Refrigerant piping flare connection (liquid [9.52 copper tube):HP
Refrigerant piping flare connection (gas [F copper tube):LP
Drain R1 (External thread)
Electrical parts box
Drain Pump (Option)
Set
Drain Pipe (Option) ... Flexible joint VP25(I.D.[32)
Filter
319
261
181
2
Air outlet
3.5
1
55
Access door
3
4
Keep duct-work length 850mm or more.
Be sure to apply the air filter
near the air inlet grille.
27
C
A
13
E
75
D
B
81
10
F
A
B
C
D
E
Model
15.88
RP71 1012 280 290 1070 1044
RP100,125 1252 360 370 1310 1284 R410A Outdoor unit : 15.88 w
RP140 1552 460 470 1610 1584 R407C outdoor unit : 19.05
w Setting at shipment
10
50~150 29
450
13
30
OCS01-1.qxp
05.5.25 11:42 AM
Page 28
Unit : mm
PEAD-RP60GA
PEAD-RP71GA
PEAD-RP100GA
Model
A
B
C
D
E
RP60 1125 1090 1050 1012 7
RP71 1125 1090 1050 1012 7
F
G
H
J
Outdoor unit(SUZ) : 6.35
Other outdoor unit : 9.52 w
840 8
9.52
840 8
RP100 1365 1330 1290 1252 9 1080 10
9.52
w Setting at shipment
28
15.88
15.88
R410A Outdoor unit : 15.88 w
R407C Outdoor unit : 19.05
05.5.16 10:03 AM
Page 29
Unit : mm
PEA-RP71EA
Service space
(opening)
in the ceiling
Drainage pan connection R1
672 (Drainage pan)
70 40
600
11
11
100
105
510
35
Service panel
Room temperature thermistor
(Room temperature thermistor)
Air intake
Air intake duct flange
22.5
24.5
25
40
125
125
650
25
25
40
Air outlet
Air outlet duct flange
730
Mounting plate
300
120
242
220
14
Heat insulator t10
29
(530)
175
250
200
15
70
4-12 ✕ 30
oblong
Suspension
bolt holes
145
(130)
12-[2.9 holes
For air outlet
duct connection
3.2
35
Heat insulator t10
200
Terminal
block
530
690
50
55
14-[2.9 holes
For air intake
duct connection
145
11
155
562 (Drainage
155
(10)
339
21
155
90
22.5
418
20
20
15
265
690
15
20
Air outlet
15
Service panel
(Condenser/evaporator
temperature thermistor)
20
Wiring entry(2-[22holes)
70
345
900
Electrical parts box
75 60
Air intake
300
Refrigerant-pipe flared
connection [15.88(5/8)
pan)
Refrigerant-pipe flared
connection [9.52(3/8)
45
OCS01-1.qxp
85 85
25
381
(10)
05.5.16 10:03 AM
Page 30
Unit : mm
PEA-RP100EA
Service space
(opening)
in the ceiling
(Drainage pan)
Drainage pan connection R1
942
Refrigerant-pipe flared
connection [9.52(3/8)
Refrigerant-pipe flared
connection [15.88(5/8)
600
40
11
100
70
(10)
11
21
70
15
Air outlet duct flange
65✕7=455
920
65
22.5
27.5
15
22.5
40
40
381
Air outlet
1000
Mounting plate
98
500
14
250
3.2
217
Heat insulator t10
30
65 65 65
27.5
(10)
pan)
90
250
200
(130)
24-[2.9 holes
For air outlet
duct connection
530
690
200
Terminal
block
Heat insulator t10
175
60
50
45
34-[2.9 holes
For air outlet
duct connection
35
(530)
345
40
65
4-12 ✕ 30
oblong
Suspension
bolt holes
418
339
65 65 65 65
20
39.5
20
15
40
960
65✕11=715
Air outlet
35
15
20
20
Wiring entry(2-[22holes)
Service panel
(Condenser/evaporator
temperature thermistor)
Room temperature thermistor
Service panel
90
795
(Room temperature thermistor)
Air intake duct flange
Air intake
245
900
Electrical parts box
70 70
Air intake
300
70
11
562 (Drainage
OCS01-1.qxp
Page 31
Unit : mm
PEA-RP125EA
Refrigerant-pipe flared
connection [9.52(3/8)
70
40
1142
11
Refrigerant-pipe flared
connection [15.88(5/8)
600
(Drainage pan)
11
Room temperature thermistor
90
Service panel
995
(Room temperature
Air
intake
thermistor)
Air intake duct flange
35
1160
20
65✕14=910
20
39.5
27.5
562(Drainage
21
27.5
40
Air outlet
1200
Mounting plate
900
84
117
65
11
175
690
70
Air outlet duct flange
65✕13=845
1120
15
27.5
40
250
14
Heat insulator t10
31
(10)
250
200
(130)
36-[2.9 holes
For air outlet
duct connection
3.2
Heat insulator t10
200
Terminal
block
530
50
60
40-[2.9 holes
For air outlet
duct connection
4-12✕30
oblong
Suspension
bolt holes
405
339
65 65 65 65
65
90
15
42.5
15
42.5
Air outlet
15
20
245
70
20
Service panel
(Condenser/evaporator
temperature thermistor)
(530)
900
345
Wiring entry(2-[22holes)
35
Air intake
300
100
Electrical parts box
70 70
Service space(opening)
in the ceiling
Drainage pan connection R1
pan)
05.5.16 10:05 AM
45
OCS01-2.qxp
65 65 65
381
27.5
(10)
OCS01-2.qxp
05.5.16 10:05 AM
Page 32
Unit : mm
PEA-RP140EA
Service space(opening)
in the ceiling
Drainage pan connection R1
1327
(Drainage pan)
600
11
40
100
Air intake
(530)
345
Electrical parts box
Wiring entry(2-[22holes)
900
300
70
90
Room temperature thermistor
Refrigerant-pipe flared
connection [15.88(5/8)
Air intake duct flange
Air intake
405
65✕16=1040
65 65 65 65
11
175
562
250
690
70
(130)
22-[3.1 holes
For air outlet
duct connection
530
200
200
44-[2.9 holes
For air outlet
duct connection
Service panel
(Room
temperature
thermistor)
15
130
4-12✕30
oblong
Suspension
bolt holes
15
35
Heat insulator t10
153 45
45
130✕7=910
1305
1415
40
40
1385
Mounting plate
14
250
98
3.2
160
25
100 100
381
Air outlet duct flange
Air outlet
1000
Heat insulator t10
32
(Drainage pan)
90
15
15
60
50
39.5
37.5
65
45
Terminal
block
(10)
339
(20)
1345
37.5
245
Air outlet
100
1115
20
70 70
20
Refrigerant-pipe flared connection
[9.52(3/8)
70
Service panel
(Condenser/evaporator
temperature thermistor)
(10)
05.5.16 10:05 AM
Page 33
Unit : mm
(C)
131 200
199
(A)
32
530
730
200
PEH-RP200MYA
20
(B)
1240
(B)
(D)
20
200
1280
1880
75
400
25
(1)
(2)
500
928
428
(3)
(A)
(1) When connecting air inlet
(2) When installing the suspension fixtures prior to installation of the indoor unit without inlet duct
(3) When hanging the indoor unit directly without inlet duct
(A) Service space
(B) Suspension bolt pitch
(C) Air inlet
(D) Air outlet
104
1102
130
130
130
130
130
34
130
130
130
31
24- [3.1 HOLES
40
AIR INLET DUCT FLANGE
199
100
31
20
200
1280
20
22- [3.1 HOLES
45
130
130
130
130
130
130
130
45
15
5
131
423
CONTROL BOX
4- [12 HOLES
(FOR HUNGING BOLT M10)
<FIELD SUPPLY>
AIR OUTLET DUCT FLANGE
AIR INLET SENSOR
REFRIGERANT PIPE [25.4
(1 BRAZE)
50
530
70
40
1240
120
1000
40
120
ACCESSORY PIPE
[9.52(3/8 BRAZE)
(USE FOR ONLY R410A)
562
DRAIN: Rc 1
REFRIGERANT PIPE [12.7
(1/2 BRAZE)
98
46
250
428
55 55 156
AIR OUTLET
CONNECT WIRE (PEH-PUH)
WIRING HOLE [27
(AIR INLET SIDE)
POWER SUPPLY
WIRING HOLE [27
(AIR INLET SIDE)
14
25
100 100
25
42
33
CONTROLLER
WIRING HOLE [27
(AIR INLET SIDE)
382
116
210
130
130
156
42
20
1320
15
15
152
344
AIR INLET
1380
650
95
OCS01-2.qxp
1264
DUCT EARTH POINT
(BOTH DUCT SIDE)
Note: When connecting duct to the inlet side, remove the air filter attached to the unit body, and mount
an air filter onto the inlet duct side separately.
33
OCS01-2.qxp
05.5.16 10:05 AM
Page 34
Unit : mm
(C)
131 200
199
(A)
32
530
730
200
PEH-RP250MYA
(D)
20
(B)
20
200
1440
(B)
1480
2080
75
400
25
(1)
(2)
500
928
428
(3)
(A)
(1) When connecting air inlet
(2) When installing the suspension fixtures prior to installation of the indoor unit without inlet duct
(3) When hanging the indoor unit directly without inlet duct
(A) Service space
(B) Suspension bolt pitch
(C) Air inlet
(D) Air outlet
104
1302
130
66
130
130
130
130
34
130
130
130
130
26-[3.1 HOLES
66
100
40
199
AIR INLET DUCT FLANGE
1480
200
20
20
5
131
423
CONTROL BOX
45
130
130
130
130
130
130
130
15
22- [3.1 HOLES
45
AIR OUTLET DUCT FLANGE
REFRIGERANT PIPE
[28.6 (1-1/8 BRAZE)
AIR INLET SENSOR
1580
650
50
530
1440
1000
220
REFRIGERANT PIPE [ 12.7
(1/2 BRAZE)
562
40
220
98
156
250
428
46
55 55
382
AIR OUTLET
CONNECT WIRE
(PEH-PUH)
WIRING HOLE [27
(AIR INLET SIDE)
14
100
100
25
42
33
CONTROLLER
WIRING HOLE [27
(AIR INLET SIDE)
25
116
210
130
130
156
152
344
40
15
95
AIR INLET
1520
70
42
20
15
4-[12 HOLES
(FOR HUNGING BOLT M10)
<FIELD SUPPLY>
1464
DRAIN: Rc 1
DUCT EARTH POINT
(BOTH DUCT SIDE)
POWER SUPPLY
WIRING HOLE [27
(AIR INLET SIDE)
Note: When connecting duct to the inlet side, remove the air filter attached to the unit body, and mount
an air filter onto the inlet duct side separately.
34
360
405
420
495
Sleeve w1
[90
MITSUBISHI ELECTRIC
150 or more
.SLI m
m r.S
Through hole
[90~[100
245
70 21
R52.5
Liquid pipe
Gas pipe
990
705 Air outlet
80
715 Air intake
400
12-Louvers(manual)
340 Air intake
ëOñ Å@ÇeÇqÇnÇmÇs
449
581
ÅrÇoÇoÅqÅ@
700 (Flexible hose total length800)
ÅrÇoÇoÅqÅ@
395
Auto vane
280 Air intake
225
40
86
54
70 35
MITSUBISHI ELECTRIC
.SLIm
mr.SLI
190
160
235
ON STAND COOL HEAT
OFF BY
233
153
(Right side piping
installation)
Terminal block for
power supply (Heater (PKH-P35, 50GALH only))
Terminal block to
outdoor unit
Service panel
(Power supply access)
—
[9.52
—
[9.52
[12.7
P35, 50
[6.35
RP35, 50
INDOOR UNIT
PKA-RP35GAL PKA-RP50GAL
[15.88
[15.88
: Factory flare nut attachment to the heat - exchanger.
GAS SIDE
LIQUID SIDE
Knock out hole for right piping
Refrigerant pipe.Drain pipe.
Wiring hole
Less than 15
Knock out hole for under piping
Refrigerant piping.Drain pipe.
Wiring hole
235
60
Right side
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
ëOñ Å@ÇeÇqÇnÇmÇs
Front view(to open the grille)
Filter grip
50
Lower side
(Left side piping
installation)
Unit drain pipe O.D.20
35
272
310
322
230
190
130
0
35
55
80
(Necessary clearance for
Unit installation)
Less than 130
Right side
60
340
w1 Sleeves are available on the market.
w2 This size shows the lower end of through hole.
Right-rear
piping hole
R52.5
Unit center
Installation plate
balance point hole
Knock out hole for
right-rear piping
5
Model
35, 50
2.
Knock out hole for
left-rear piping
300
R5
Left-rear
piping hole
49-[5hole
for tapping screw
245
Details of installation plate
190
230
210
HEAT
75
32
20
0
35
0
14-[14hole
for bolts
5
STAND COOL
BY
95
50 or more
135
2.
R5
ON
OFF
150
Allowing clearances
Front view
205
170
190
30 or more
180 or more
260
53
79
Knock out hole for left piping
Refrigerant pipe.Drain pipe.Wiring hole.
320
345
Front view
80
Left side
495
35
425
198 Air intake
60
280
05.5.16 10:05 AM
31
245
70 21
OCS01-2.qxp
Page 35
Unit : mm
OCS01-2.qxp
05.5.16 10:05 AM
Page 36
Unit : mm
PKA-RP60FAL
PKA-RP71FAL
Display section
62.5
Top
45
235
235
45
235
45
Defrosting Initial heating lamp
13
235
Power lamp
Front
Right side
1400
Left side
Emergency switch(Heat)
Emergency switch(Cool)
Receiving
section
235
Knock out hole for right piping
Refrigerant pipe. Drain pipe
340
A
197
1090 Air intake
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Knock out hole for
left piping
C
Gas pipe
25
Drain hose for
left-hand side piping
58
42
Bolt
Drain hose O.D.20
Drain hose
1110
183
55 (Gas pipe) 107
120
111
(Liquid pipe)
Lower side
Liquid pipe [9.52(3/8F)
Gas pipe [15.88(5/8F)
Auto vanes
1120
240
552 Air outlet
552 Air outlet
Louvers (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
B
Refrigerant pipe. Drain pipe
Unit center
990
245
455
Knock out hole for wiring
91
225
240
180
12-ø6 hole for
tapping screw
280
314
610
90
Rear piping opening
Range for left rear piping opening
36
C
30
100
B
37
74
39
98 32
39
37
74
4
32-ø12 hole for bolt
30
60
184
30
66-ø6 hole for
tapping screw
A
30
37
65
on left-hand side
Drainage range
on right-hand side
100
4 39
18
285
19
10
30
80
29
280
Wall fixture
10 91=(910)
900
18 Drainage range
OCS01-2.qxp
05.5.16 10:05 AM
Page 37
Unit : mm
PKA-RP100FAL
Top
62.5
Display section
45
235
45
235
45
235
235
45
13
235
Receiving
section
Emergency switch(Heat)
Emergency switch(Cool)
Defrosting Initial heating lamp
Power lamp
Front
Left side
Knock out hole for right piping
Right side
1680
235
1370 Air intake
340
197
A
Knock out hole for left piping
C
Terminal block for indoor/outdoor connecting line
15
Terminal block for heater (PKH only)
Liquid pipe
Gas pipe
25
Drain hose O.D.20
Drain hose
Drain hose for left-hand side piping
58
42
Bolt
1110 Drain hose
183
Lower side
1400
55 (Gas pipe) 102
120
111
(Liquid pipe)
240
694 Air outlet
Use the current nuts meeting the pipe size
of the outdoor unit.
Available pipe size
RP100
P100
694 Air outlet
LIQUID SIDE [9.52
[9.52
[15.88
[19.05
[19.05
: Factory flare nut attachment to the
heat-exchanger.
GAS SIDE
Louvers (manual)
B
Under panel
(Removable at left-hand side piping)
Auto vane
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Unit center
1270
Knock out hole for wiring
Drainage range
91
on right-hand side
60
295
225
Range for left rear piping opening
240
180
280
750
30
41-ø12 hole for bolt
314
90
Range for left rear piping opening
12-ø6 hole for tapping screw
37
Rear piping opening
A
30
B
C
30
100
Drainage range
on left-hand side
285
19
37
74
39
98 32
39
13 91=(1183)
900
37
74
4
18
37
65
18
184
30
84-ø6 hole for
tapping screw
245
595
10
30
80
29
280
Wall fixture
100
4 39
Unit out line
OCS01-2.qxp
05.5.16 10:05 AM
Page 38
Unit : mm
INDOOR UNIT
PCA-RP50GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
6
933 (suspension bolt pitch)
85
983
15
81 76
7
226
2
157
Electrical box
180
210
70
904
182
1000
gas
241
(Drainage)
254
506
680
56
Air outlet
liquid
201
Air intake
161
90
918
5
1 4
38
131
161
46 175
1
8
38 79
Ceiling
6~7
42
32
Electrical box [Front view]
179
3
2
1
2
3
4
5
6
7
8
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
352
525
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Available pipe size
RP50
P50
5 LIQUID SIDE [6.35
928
[9.52
4 GAS SIDE
When electrical
box is pulled
down
[9.52
[12.7
[15.88
[15.88
: Factory flare nut attachment to the heat-exchanger.
38
OCS01-2.qxp
05.5.16 10:05 AM
Page 39
Unit : mm
PCA-RP60GA
PCA-RP71GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
17
6
1240 (suspension bolt pitch)
85
1290
Electrical box
15
2
226
210
180
81 76
7
157
70
1214
182
(liquid)
1310
201
(5/8F gas)
241
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1228
38
131
161
525
1 4
46 175 1
Ceiling
5
8
3879
32
[ Front view ]
6~7
42
179
3
Electrical box
2
86
138
171
263
416
1235
1
2
3
4
5
6
7
8
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Use the current nuts meeting the pipe size of the outdoor unit.
Available pipe size
RP60
RP71,P60,P71
5 LIQUID SIDE [6.35
[9.52
[9.52
4 GAS SIDE
When electrical
box is pulled
down
[15.88
[15.88
: Factory flare nut attachment to the heat-exchanger.
39
OCS01-2.qxp
05.5.16 10:05 AM
Page 40
Unit : mm
PCA-RP100GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
18
6
1240 (suspension bolt pitch)
87
70
16
2
229
217
270
81 96
7
207
Electrical box
1214
182
(3/8F liquid)
1310
198
(5/8F, 3/4F gas)
245
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1228
Ceiling
8
5
1
4
6~7
38
192
45
42
236
38 140
1
93
[ Front view ]
160
239
3
Electrical box
2
1
2
3
4
5
6
7
8
525
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
Available pipe size
RP100
P100
5 LIQUID SIDE
687
1235
[9.52
[9.52
[15.88
[19.05
[19.05
4 GAS SIDE
When electrical
box is pulled
down
:Factory flare nut attachment to the heat-exchanger.
40
OCS01-2.qxp
05.5.25 11:45 AM
Page 41
Unit : mm
PCA-RP125GA
PCA-RP140GA
NOTES:
1. Use M10 or W3/8 screws for anchor bolt.
2. When optional drain lift-up mechanism is installed, always provide
upward piping for refrigerant piping.
140
70
320
150
80
18
6
1547(suspension bolt pitch)
87
70
16
229
2
217
270
81 96
7
207
Electrical box
1524
182
(3/8F liquid)
1620
198
(5/8F, 3/4F gas)
245
(Drainage)
254
506
680
56
Air outlet
Air intake
161
90
1535
[ Front view ]
Ceiling
8
5
1
4
192
236
Drainage pipe connection (26mm I.D.)
Drainage pipe connection (for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection (gas pipe side/flared connection)
Refrigerant-pipe connection (liquid pipe side/flared connection)
Knock out hole for upper drain pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
6~7
38
45
42
160
38 140
1
93
Electrical box
239
3
2
1
2
3
4
5
6
7
8
525
Use the current nuts meeting the pipe size of the outdoor unit.
86
138
171
263
Available pipe size
RP125,140 P125,140
5 LIQUID SIDE
[9.52
[9.52
4 GAS SIDE
[15.88
[19.05 [19.05
687
1545
When electrical
box is pulled
down
:Factory flare nut attachment to the heat-exchanger.
41
1224
<Air intake>
1098
1136
986 <Air
outlet>
bolt pitch>
75
21
1
<gas>
<liquid>
175
Suspension bolt
80
70
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
360
handle
3
or more
100
<Flexible hose(accessory)>
650
289
<Suspension bolt pitch>
320
495
<Filter contour dimension>
Filter (3-pieces)
Inspection port
(pipe sensor)
75
243
1
Rear wall
Adjustable part
85
45
1136
Ceiling
176
105
140
18
318
2
4
or more
100
366
6
8
7
0
90˚
Terminal block box
[2
22
[ 20
9
130
250
Less than
Allowing clearances
480
(122 )
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knock out hole for behind refrigerant-piping arrangement
Knock out hole for upper refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knock out hole (duct for fresh air intake): 2- [ 200
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pcs.)
43
110
<Air outlet>
1180 <Suspension
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
The half bottom of FAN CASING
can be separated.
Electrical box
75
2
15
102
110
258
254
295
197
<Air intake>
70~90
13
130
650
280
16
288
120
165
90
Less than
210
38
Terminal block box
300
1
2
3
4
5
6
7
8
9
Less than
5
500
42
or more
PCA-RP71HA
2~3
05.5.25 11:45 AM
(Gap to ceiling)
OCS01-2.qxp
Page 42
Unit : mm
Use the current nuts meeting the pipe size
of the outdoor unit.
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
The half bottom of FAN CASING
can be separated.
<Air intake>
1482
1520
outlet>
75
21
1 GAS SIDE
2 LIQUID SIDE
Available pipe size
<Suspension bolt pitch>
1370 <Air
1564
Suspension bolt
80
650
289
70
<Suspension bolt pitch>
320
495
[ 19.05
[ 15.88
[ 9.52
RP125
or more
18
45
85
140
2
4
Rear wall
298
176
105
Adjustable part
3
1
1520
Ceiling
246
6
440
(122)
7
440
or more
100
9
[2
22
0
[20
250
Less than
Allowing clearances
Terminal block box
8
: Factry flare nut attachment to the heat-exchanger
Filter element for the exchange
model:PAC-SG38KF-E (12pcs.)
360
handle
100
<Flexible hose(accessory)>
75
<Filter contour dimension>
Filter (4-pieces)
Inspection port
(pipe sensor)
75
1608
197
<liquid>
1
243
Electrical box
43
110
102
110
258
254
295
175
<Air outlet>
<Air intake>
70~90
13
120
90
<gas>
280
16
288
165
Refrigerant-pipe connection(gas pipe side/flared connection : 5/8F, 3/4F)
Refrigerant-pipe connection(liquid pipe side/flared connection : 3/8F)
Flexible hose(accessory) Drainage pipe connection(26mm I.D.)
Knock out hole for behind refrigerant-piping arrangement
Knock out hole for upper refrigerant-pipe arrangement
Knock out hole for wiring arrangement : 2- [ 27
Terminal block(indoor/outdoor connecting line)
Terminal block(remote controller)
Knock out hole (duct for fresh air intake) : 2- [ 200
Option parts:duct flange( [ 200). model: PAC-SF28OF-E(1 pcs.)
650
210
38
1
2
3
4
5
6
7
8
9
300
2
15
Less than
130
Less than
130
5
90˚
Terminal block box
500
43
or more
PCA-RP125HA
2~3
05.5.25 11:45 AM
(Gap to ceiling)
OCS01-2.qxp
Page 43
Unit : mm
10
10
38
controller
Front side
15
111
Metal fixture
against overturning
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
235
70
600
71
250
270
180
130
Knock out hole
for branch duct
132
530
520
260
240
370
340
125
240
100
130 130
Knock out hole for
under-piping(120 70 oval)
Terminal block for
heater power supply 22
(Only PSH-P•GAH)
Terminal block for
indoor/outdoor
connection.
Knock out hole
for bottom fixing
95
50
Knock out hole for
wiring.[27
(Provided on both sides)
Front side
Rear side
A
105
Knock out hole
for under-piping
Drain pipe
Gas pipe [15.88(5/8F)
Liquid pipe [ 9.52(3/8F)
Knock out hole for piping and wiring
(140 80 oval)
47
95
Electrical parts box
277
461
20
20
160
218
VIEW "A"
100
38
20
10
827
30
130
50
260
143
55
Rear side
115
40
1900
175
123
714
766
608
216
90
767
44
110
40
186
66
Front 1,000 or more
100 or more
1
2
300 or more
5 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
100 or more
PSA-RP71GA
590
05.5.25 11:45 AM
480
OCS01-2.qxp
Page 44
Unit : mm
controller
Knock out hole for refrigerant and drainage.
90 60 oval (Provided on both sides)
315
70
600
71
330
350
260
130
Metal fixture
against overturning
530
520
260
240
370
340
125
130 130
10
10
38
38
Front side
100
15
111
Knock out hole
for branch duct
130
50
260
20
132
40
1900
240
Knock out hole for
95
under-piping(120 70 oval)
Knock out hole for
wiring.[27 (Provided on both sides)
A
20
461
Front side
Rear side
105
[15.88(5/8F)
[19.05(3/4F)
Gas pipe
Drain pipe
[9.52(3/8F)
Liquid pipe
Knock out hole for piping and wiring
(140 80 oval)
47
95
—
[ 19.05
[ 19.05
[ 9.52
[ 15.88
[ 9.52
40
261
66
100 or more
Front 1,000 or more
1. Service access allows for
insertion of screw driver.
2. Adjustable
100 or more
RP100,125,140 P100,125,140
: Factry flare nut attachment to
the heat-exchanger
GAS SIDE
LIQUID SIDE
Available pipe size
Use the current nuts meeting the pipe size
of the outdoor unit.
Knock out hole
for under-piping
Electrical parts box
277
120
20
218
VIEW "A"
Knock out hole
for bottom fixing
Terminal block for
indoor/outdoor
connection.
Terminal block for
heater power supply
(Only PSH-P•GAH) 22
50
120
Rear side
115
10
827
30
255
123
714
766
608
216
140
767
201
77
110
45
590
05.5.25 11:45 AM
480
PSA-RP100GA
PSA-RP125GA
PSA-RP140GA
1
2
300 or more
5 or more
OCS01-2.qxp
Page 45
Unit : mm
OCS01-2.qxp
05.5.25 11:45 AM
Page 46
Unit : mm
OUTDOOR UNIT
PUHZ-RP35VHA
PUHZ-RP50VHA
400
[33 drain hole
347.5
330
300
Air intake
[33 drain hole
365
155
152
43.6
Air intake
45.4
40
18
23
32.5
4-10 o 21 oval hole
(M10 foundation bolt)
Service panel
Service panel
for charge plug
Air discharge
Handle for
moving
150
Connection for
gas pipe
90
10
155
300
43
35
600
Connection for
liquid pipe
183
69
287.5
Service port
Installation bolt pitch: 500
800
1. FOUNDATION BOLTS
2. PIPING-WIRING DIRECTION
Please secure the unit firmly Piping and wiring connection can
with 4 foundation (M10) bolts. be made from the rear direction only.
(Bolts, washer and nut must
be purchased locally.)
Free space around the outdoor unit
(basic example)
100
mm
w1
re
r mo
mo
m
100
18 or below
100 mm or more as long as
no obstacle is placed on the
rear and light-and-left sides
of the unit.
Basically open
3. ATTACHING THE CONDUIT
In order to attach the conduit, it is
necessary to fix the metal plate with
2 screws to the back panel. Procure
the metal plate and make screw holes
locally. It is recommended to use the
metal plate shown below. Align the
metal plate to the marks on the unit
and attach it.
<Foundation bolt height>
FOUNDATION
or m
ore
w1
w2
w The position and the size of
conduit hole depend on the
conduit to be used.
re
500
mm
o
or m
350
mm
40
20
or m
ore
2 sides should be open in
the right, left and rear side.
80
Minimum installation space for outdoor unit
60
w Conduit hole
w 1 In the place where short cycle tends to occur, cooling and heating
capacity and power consumption might get lowered 10%. Air outlet
guide (optional PAC-SG58SG) will help them improve.
w 2 If air discharges to the wall, the surface might get stained.
Holes for metal plate fixing screw
w The size of hole depends on the
screw to be used.
46
OCS01-2.qxp
05.5.16 10:05 AM
Page 47
Unit : mm
Ov
er
10
mm
m
0m
50
er
Ov
Ov
er
10
mm
F
R
E
E
m
0m
10
er
Ov
PUHZ-RP60VHA
PUHZ-RP71VHA
47
mm
50
r1
Ove
FREE
Ove
r1
0m
m
mm
50
r1
Ove
10
Service space
Over
Front piping hole
(Knock-Out)
92
[92
Front trunking hole 40
(Knock-Out)
65
45
Power supply wiring hole
(2-[27Knock-Out)
19
92
75
Right piping hole
(Knock-Out)
Piping Knock-Out Hole Details
55
[92
Air intake
Handle for moving
500
Over
100
Dimensions of space needed
for service access are
shown in the below diagram.
1 • • • Refrigerant GAS pipe connction (FLARE)[15.88 (5/8F)
2 • • • Refrigerant LIQUID pipe connection (FLARE)[ 9.52 (3/8F)
w1 • • • Indication of STOP VALVE connection location.
Example of Notes
Ove
r1
0m
m
55
27
Over
500
40
65
45
Right trunking hole
(Knock-Out)
92
[92
40
FOUNDATION
Rear piping hole
(Knock-Out)
Rear trunking hole
(Knock-Out)
Power supply wiring hole
(2-[27Knock-Out)
Handle for moving
Handle for moving
Side Air Intake
Rear Air Intake
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally.)
<Foundation bolt height>
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS
Power supply wiring hole
(2-[27Knock-Out)
Over
The diagram below shows a
basic example.
Explantion of particular details are
given in the installation manuals etc.
73 63
23
63
73
30
2 SERVICE SPACE
175
322
600
145
Air Discharge
Installation Feet
66
175
2-U Shaped notched holes
(Foundation Bolt M10)
Handle for moving
30
220
145
145
Earth terminal
950
42
Side Air Intake
1350
Rear Air Intake
Drain hole
(5-[33)
71
2
1
Handle for moving
Service panel
Terminal connection
Left • • • Power supply wiring
Right • • Indoor/Outdoor wiring
2-12o36 Oval holes
(Foundation Bolt M10)
71
635
371
417
1 FREE SPACE (Around the unit)
23 27 92
330
30
23
219
Less than
73 63
23
55
27
Front piping cover
RP·YHA
RP·VHA
Bottom piping hole
(Knock-Out)
A
930
1,076
Rear piping cover
PUHZ-RP100VHA PUHZ-RP100YHA
PUHZ-RP125VHA PUHZ-RP125YHA
PUHZ-RP140VHA PUHZ-RP140YHA
81
19
45
56
370
53
28
w1 443
48
A
05.5.16 10:05 AM
w1 447
OCS01-2.qxp
Page 48
Unit : mm
736
90
(780)
750
60
28
218
70
120
161
63
Wiring Hole([40 Knock-OUT)
Wiring Hole([27 Knock-OUT)
12
Front side
38
40
375
140
65
65
Drain Hole(4-[10)
Drain Hole
[
900
Wiring Hole([ 40 Knock-OUT)
Wiring Hole([ 27 Knock-OUT)
Power supply Wiring (Earth wiring)
Indoor/Outdoor Wiring
(Front Side)
Service panel
Piping Hole (Knock-OUT)
180
317
5
R1
1
[ 25.4
L
70
G
0
98
364
435
667
1457
1519
1798
2
Wiring Hole([ 27 Knock-OUT)
Wiring Hole([ 40 Knock-OUT)
Piping Hole([ 122 Knock-OUT)
150
MITSUBISHI
ELECTRIC
R1
5
AIR INTAKE
110
42 48
Piping Hole([ 122 Knock-OUT)
780
736
750
AIR FLOW
60
[ 12.7 (1/2F)
250YHA
200
O.D [ 28.58
2
O.D [ 25.4
1
[ 9.52 (3/8F)
200YHA
2 Refrigerant GAS PIPE connection (BRAZING)
1 Refrigerant LIQUID PIPE connection (FLARE)
380
Service panel
(Rear Side)
PUHZ-RP200YHA
PUHZ-RP250YHA
Wiring Hole([ 40 Knock-OUT)
Wiring Hole([ 27 Knock-OUT)
(22)
80
80
460
105
123
900
200
700~796
560
19
FOUNDATION BOLTS PITCH & DRAIN HOLES
48
152
94
49
191
0
70
58
05.5.16 10:05 AM
21
OCS01-2.qxp
Page 49
Unit : mm
OCS01-2.qxp
05.5.16 10:05 AM
Page 50
Unit : mm
WIRED REMOTE CONTROLLER
120
130
19
50
05.5.16 10:05 AM
Page 51
Unit : mm
WIRELESS REMOTE CONTROLLER
58
159.3
55
19
OCS01-2.qxp
51
OCS01-2.qxp
05.5.16 10:05 AM
Page 52
WIRING DIAGRAM
4
PLA-RP35AA PLA-RP50AA PLA-RP60AA PLA-RP71AA
PLA-RP100AA PLA-RP125AA PLA-RP140AA
[LEGEND]
SYMBOL
P.B
I.B
FUSE
ZNR
BCR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
SW1
SW2
SWE
C
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
FAN CONTROL ELEMENT
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
POWER SUPPLY(I.B)
POWER SUPPLY(I.B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
SWITCH(MODEL SELECTION) See table 1
SWITCH(CAPACITY CORD) See table 2
CONNECTOR(EMERGENCY OPERATION)
CAPACITOR(FAN MOTOR)
SYMBOL
MF
MV
H2
DP
DS
TB2
NAME
SYMBOL
FAN MOTOR
W.B
VANE MOTOR
RU
DEW PREVENTION HEATER
BZ
DRAIN-UP MACHINE
LED1
DRAIN SENSOR
LED2
TERMINAL BLOCK
SW1
(INDOOR UNIT POWER(OPTION))
SW2
TERMINAL BLOCK (INDOOR/
OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
COND./EVA. TEMP. THERMISTOR
(0˚C/15kΩ,25˚C/5.4kΩ DETECT)
WIRED REMOTE CONTROLLER BOARD
TB4
TB5, TB6
TH1
TH2
TH5
R.B
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
GRILLE
MV MV MV MV
5
5
5
5
H2
5
MF
3
2
1
DC
13.1V
2
1
1 2 3 6 7 4 8 9 5 10
1 2 3
CNSK P.B
(RED)
CN2S
(WHT)
TB4
YLW S1
ORN S2
ORN
S3
BRN
TO OUTDOOR UNIT
5
1 2 3
DP
FAN 1 3 5
(WHT)
X4 X1
BRN
ORN
BLK
WHT
YLW
ORN
RED
WHT
D.U.M 1 3 D.HEATER 1 3
1 3
CNC(RED)
CNP
POWER
(BLU)
CNDK
(RED)
X4
1 3 VANE
CND POWER INDOOR/OUTDOOR CN6V
(ORN) CN2D COMMUNICATION (GRN)
(WHT)
CN3C
(BLU)
CN51 CN41 CN2L
1 3 POWER 1 2
FUSE
BCR
YLW
YLW
X1
ZNR
CN32
SWE SW2
SW1
ON
OFF
LED3 LED2
HEATER D.SENSOR
CN24
CN31
(YLW)
(WHT)
DS
Refer to tables 1
and 2.
BLU
BLU
1 2 3
LED1
INTAKE LIQUID PIPE REMOCON
CN20
CN21 CN29
CN22 WIRELESS
(RED) (WHT) (BLK)
(BLU) CN90
1 2 1 2 1 2
1 2 (WHT)
TH1
2
1
W.B
BZ
9
LED1
SW1
SW2
RU
R.B
TB5
TRANSMISSION WIRES
DC12V
TH2
1 2
TB6
TB2
RED
BLU
GRN/YLW
1 (Fig.1)
TH3
NOTES:
1.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor
unit electric wiring for servicing.
4.This dlagram shows the wiring of Indoor and Outdoor connecting wires
(specification of 230V), adopting superimposed system of power and signal.
I.B
1 3
1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label located near this diagram.
Table 2
Table 1
SW1
MODELS
Service board
PLA-RP. AA
LED2
CNB
1 2 3 4 5
ON
OFF
MODELS
PLA-RP35AA
PLA-RP50AA
PLA-RP60AA
PLA-RP71AA
SW2
Service board MODELS
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
PLA-RP100AA
ON
OFF
PLA-RP125AA
ON
OFF
PLA-RP140AA
Service board
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
ON
OFF
ON
OFF
ON
OFF
ON
OFF
52
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
I.B
YLW
YLW
RED
WHT
BLK
C
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
Please set the voltage using the
remote controller.
For the setting method. please refer to
the indoor unit Installation Manual.
OCS01-2.qxp
05.5.31 10:51 AM
Page 53
PEAD-RP35EA PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA
PEAD-RP100EA PEAD-RP125EA PEAD-RP140EA
53
OCS01-2.qxp
05.5.31 10:51 AM
PEAD-RP60GA
Page 54
PEAD-RP71GA
PEAD-RP100GA
54
OCS01-2.qxp
05.5.31 10:51 AM
PEA-RP71EA
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
Page 55
PEA-RP100EA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH))
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSOION(INDOOR • OUTDOOR)
PEA-RP125EA
SYMBOL
I.B SW1
SW2
SWE
X4
X5
X6
R.B
TB6
PEA-RP140EA
SYMBOL
NAME
TERMINAL BLOCK(INDOOR UNIT POWER(OPTION))
TB2
TERMINAL BLOCK
TB4
NAME
SWITCH(MODEL SELECTION)wSee table 1
SWITCH(CAPACITY CODE)wSee table 2
(INDOOR/OUTDOOR CONNECTING LINE)
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
REMOTE CONTROLLER BOARD
TERMINAL BLOCK(REMOTE CONTROLLER
TB5
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
TH1
ROOM TEMPERATURE THERMISTOR
(0;/15K', 25;/5.4K' DETECT)
TH2
PIPE TEMPERATURE THERMISTOR/LIQUID
TRANSMISSON LINE)
(0;/15K', 25;/5.4K' DETECT)
CAPACITOR(FAN MOTOR)
FAN MOTOR
C
MF
TH5
COND./EVA. TEMPERATURE THERMISTOR
(0;/15K', 25;/5.4K' DETECT)
w1(Fig.1)
INDOOR UNIT
P.B
CN2S
(WHT)
2
DC13.1V
1
TB4
YLW
ORN
CNSK
(RED)
3
2
1
MF
TB2
BLU
TO
OUTDOOR
UNIT
S1
S2
S3
RED
RED
TB4
BLU
L
N
POWER SUPPLY
~ (1PHASE) Table 1
230V 50Hz
S1
S2
S3
TO
OUTDOOR
UNIT
BLK
WHT
BRN
ORN
1 3 5 7
POWER 1 3
CND
(ORN)
1 2
1 3
ZNR
X6 X5 X4
X6
X5
SW2
Refer to tables
1 and 2
SW1
CN24
TH1
TH5
2
1
BLU
BLU
TB5
CN2L
CN41
CN32
1
2
BLU
R.B
TH2
REMOCON
CN22
(BLU)
1 2
BLU
TRANSMISSION
WIRE DC12V
TB6
1 3
POWER
CND
(ORN)
WIRELESS
CN90
(WHT)
2 LIQUID
CN21
1 (WHT)
2 INTAKE
CN20
1 (RED)
PIPE
2 CN29
1 (BLK)
X4
LED3 LED2 LED1
SWE
ON
OFF
I.B
POWER INDOOR/OUTDOOR
CN2D COMMUNICATION
CN3C
(WHT)
(BLU)
FUSE
FAN
(WHT)
BRN
ORN
YLW
ORN
POWER 1 3
CNDK
(RED)
C
YLW
ORN
RED
WHT
I.B
ORN
BLK
BLU
BRN
WHT
RED
2 3 4 1 5 6
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
w1;When work to supply power separately
to Indoor and Outdoor unit was applled,
refer to Fig 1.
w2;For power supply system of this unit,
refer to the caution label located
near this diagram.
Please set the voltage using
the remote controller.
For the setting method,please
refer to the indoor unit
installation Manual.
Table 2
MODELS
SW1
Manufacture/Service
MODELS
1 2 3 4 5
PEA-RP.EA
SW2
Manufacture/Service
1 2 3 4 5
ON
OFF
PEA-RP71EA
ON
OFF
1 2 3 4 5
PEA-RP100EA
ON
OFF
1 2 3 4 5
PEA-RP125EA
ON
OFF
1 2 3 4 5
PEA-RP140EA
ON
OFF
55
[NOTES]
1.Symbols used in wiring diagram above are,
:Connector,
:Terminal(block).
2.Indoor and outdoor connecting wires are made with polarities,
make wiring matching terminal numbers(S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
4.This diagram shows the wiring of Indoor and Outdoor
connecting wires(speclfication of 230V), adopting
superimposed system of power and signal.
OCS01-2.qxp
05.5.31 10:51 AM
PEH-RP200MYA
Page 56
PEH-RP250MYA
REMOTE CONTROLLER
REMOTE CONTROLLER
BOARD
TB6
CIRCUIT BREAKER
(FIELD SUPPLY)
PEH-RP200,250MYA:15A
POWER SUPPLY
3N~PE
380/400/415V
50Hz
LCD
TB2
RED
WHITE
BLACK
L1
L2
L3
N
PE
52F
51F
C01
(WHITE)
(50Pa)
C02
(RED)
(150Pa)
PE
1
2
3
2
3
1
MF1
TH1
PE
PE
TH2
TH5
1
2
TB5
RETURN AIR
DUCT
SUPPLY AIR
DUCT
5 4 3 2 1
1 CN2L
2
1
2 CN31
3
1 CN22
2
1
2
3
4
5 CN90
6
7
8
9
PE
PE
2 1
1
2 CN41
3
INDOOR
4 CONTROLLER BOARD
CN51
5 4 3 2 1
ON
OFF
SW1
5 4 3 2 1
ON
OFF
1 CN29
2
1
2 CN32
3
1 CN21
2
LED1
1 CN20
2
(*1)SW2
SWE
ON
OFF
X4 X5 X6
LED2
LED3
X4 X5 X6
FUSE
CN3C
3 1
CN2D
DC13.1V
ZNR
3
1
CND
3 1
CNDK
7
5
3
FB
1
C12
1
49F
INDOOR
POWER BOARD
CN2S
1 DC
2 13.1V
FAN
3
CNSK
51F
1
3
CR
TAB1
52F
S1
S2
S3
TB4
TO OUTDOOR UNIT
CONNECTING WIRES
(POLAR)
OUTDOOR UNIT
S1
S2
S3
TB3
INDOOR UNIT CONTROL BOX
INDOOR UNIT
SYMBOL
MF1
51F
52F
49F
TB2,4,5
TH1
TH2
TH5
CR
FB
INDOOR
FUSE
CONTROLLER ZNR
BOARD
X4-6
SW1
SW2
SWE
LED1
LED2
LED3
NAME
FAN MOTOR (INDOOR)
OVER CURRENT RELAY (INDOOR FAN MOTOR)
MAGNETIC CONTACTOR (INDOOR FAN MOTOR)
INTERNAL THERMOSTAT (INDOOR FAN MOTOR)
TERMINAL BLOCK
ROOM TEMP
THERMISTOR LIQUID PIPE TEMP
COND/EVA TEMP
SURGE KILLER
FERRITE CORE
FUSE (T6.3AL250V)
VARISTOR
AUXILIARY RELAY
SWITCH(MODEL SELECTION)
SWITCH(CAPACITY CORD)
SWITCH(EMERGENCY OPERATION)
LED (POWER SUPPLY)
LED (POWER SUPPLY<REMOTE CONTROLLER>)
LED (TRANSMISSION<INDOOR•OUTDOOR>)
OUTDOOR UNIT
SYMBOL
TB3
TERMINAL BLOCK
NAME
Note:1. The dotted lines show field wiring.
2. Color of earth wire is yellow and green twisting.
3. Specification subject to change without notice.
4. Indoor and outdoor connecting wires are made with polarities,
make sure matching wiring and terminal.
5. Emergency operation
If a trouble occurs with either the remote controller or the indoor microcomputer and no other trouble exists, emergency operation for cooling or heating
can be performed by changing the setting of switch (SWE) "ON" on the
indoor controller board.
6. SW2(*1) shows PEH-RP250MYA setting.
In case of PEH-RP200MYA setting is shown as below.
5 4 3 2 1
ON
OFF
(*1)SW2
7.
mark is connector.
Caution,
1. To protect fan motor from abnormal current,over current relays is installed.
Therefore, do not change factory set value of over current relays.
REMOTE CONTROLLER
SYMBOL
NAME
TB6
TERMINAL BLOCK
56
05.5.16 10:05 AM
Page 57
PKA-RP35GAL
PKA-RP50GAL
P.B CNDK
(RED)
CN2S
(WHT)
1
2 DC13.1V
3
MF
w1 (Fig.1)
1
2
TB2
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
1 2 3
BLK
WHT
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(RED)
(ORN)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
X4
BCR
ZNR
X4
CN41
CN2L
CN51
CN32
TO
OUTDOOR
UNIT
I.B
6
FUSE
FAN 1 3 5
(WHT)
YLW
ORN
I.B
RED
WHT
RED
WHT
BLK
C
RED
BLU
GRN/YLW
MV
POWER
SUPPLY
~(1PHASE)
230V 50Hz
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
OCS01-2.qxp
1 3
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
WIRELESS
CN90
(WHT)
LED3 LED2 LED1
SW2
SWE
ON
OFF
SW1
INTAKE
CN20
(RED)
LIQUID PIPE
CN21
CN29
(WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
R.B
2
1
TH2
TH1
TH5
TRANSMISSION WIRES DC12V
1
TB6
2
TB5
PKH-P35,50GALH models only
1 2
H1
YLW
YLW
I.B
HEATER
CN24
(YLW)
6
RED
88H
1
GRY
6
5 RED
SW1
Service board
1 2 3 4 5
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
ON
OFF
FS1
FS2
26H
88H
RED
WHT
1
2
RED 5
TB2
L
3 RED
N
BLU
GRN/YLW
MODELS
PKA-RP35GAL
PKH-P35GALH
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR <LOSSNAY>
CONNECTOR <REMOTE SWITCH>
CONNECTOR <HA TERMINAL-A>
CONNECTOR <CENTRALLY CONTROL>
SWITCH <MODEL SELECTION>wSee Table 1.
SWITCH <CAPACITY CODE>wSee Table 2.
SWITCH <EMERGENCY OPERATION>
RELAY <FAN MOTOR>
FAN CONTROL ELEMENT
POWER SUPPLY <I.B>
POWER SUPPLY <R.B>
TRANSMISSION <INDOOR-OUTDOOR>
Please set the voltage using the
remote controller.
For the setting method,please refer to
the indoor unit Installation Manual.
POWER SUPPLY
~(1PHASE)
230V 50Hz
SW2
Service board
MODELS
Service board
1 2 3 4 5
1 2 3 4 5
SYMBOL
C
MF
MV
TB2
TB4
TB5,TB6
TH1
TH2
TH5
ON
OFF
PKA-RP50GAL
PKH-P50GALH
NAME
CAPACITOR <FAN MOTOR>
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) wPKH-P.GALH
models only or option for PKA-RP.GAL models.
TERMINAL BLOCK <INDOOR/ OUTDOOR
CONNECTING LINE>
TERMINAL BLOCK <REMOTE CONTROLLER
TRANSMISSION LINE> <OPTION>
ROOM TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
PIPE TEMP.THERMISTOR/ LIQUID
<0:/ 15k", 25:/ 5.4k" DETECT>
COND./ EVA.TEMP.THERMISTOR
<0:/ 15k", 25:/ 5.4k" DETECT>
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
HEATER
FS1
FS2
H1
26H
88H
ON
OFF
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED <RUN INDICATOR>
LED <HOT ADJUST>
SWITCH (HEATING ON/ OFF>
SWITCH (COOLING ON/ OFF>
WIRED REMOTE CONTROLLER BOARD
THERMAL FUSE <104:10A>
THERMAL FUSE <84:10A>
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
w1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
w2. For power supply system of this unit, refer to the caution label located near this diagram.
57
05.5.16 10:05 AM
PKA-RP60FAL
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X4
BCR
LED1
LED2
LED3
Page 58
PKA-RP71FAL
SYMBOL
C
MF
MV
TB2
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE(T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) wSee Table 1.
SWITCH (CAPACITY CODE) wSee Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
NAME
CAPACITOR(FAN MOTOR)
FAN MOTOR
VANE MOTOR
TERMINAL BLOCK (HEATER) wPKH-P.FALH
models only or option for PKA-RP.FAL models.
TERMINAL BLOCK(INDOOR/OUTDOOR
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )(OPTION)
ROOM TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0;/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
TB4
TB5
TH1
TH2
TH5
P.B CNDK
(RED)
1
2
TB4
YLW
S1
S2
ORN
S3
ORN
BRN
1 2 3
FAN 1 3 5
X4
BCR
BLK
WHT
POWER
POWER
1 2
1 3 VANE
CNDK 1 3 CND 1 3
CN6V
INDOOR/OUTDOOR (GRN)
(RED)
(ORN)
POWER
CN2D(WHT) COMMUNICATION
CN3C(BLU)
ZNR
X4
CN41
CN2L
CN51
CN32
NAME
WIRELESS REMOTE CONTROLLER BOARD
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR )
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
WIREDREMOTE CONTROLLER BOARD(OPTION)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
HEATER
FS1,2 THERMAL FUSE(117; 10A:60,71FALH/
117; 16A:100FALH)
HEATER
H1
26H HEATER THERMAL SWITCH
88H HEATER CONTACTOR
w1 (Fig.1)
TB2
RED
BLU
GRN/YLW
TO
OUTDOOR
UNIT
I.B
6
FUSE
(WHT)
YLW
ORN
RED
WHT
RED
WHT
BLK
C
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
R.B
TB6
Please set the voltage
using the remote controller.
For the setting method,
please refer to the indoor
unit Installation Manual
CN2S
(WHT)
1
2 DC13.1V
3
MF
PKA-RP100FAL
1 3
MV
L
N
POWER
SUPPLY
(1PHASE)
230V 50Hz
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
OCS01-2.qxp
TO
OUTDOOR
UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
9
WIRELESS
CN90
(WHT)
LED3 LED2 LED1
SWE
ON
OFF
SW2
SW1
INTAKE LIQUID PIPE
CN20 CN21
CN29
(RED) (WHT) (BLK)
1 2
1 2
1 2
CNB
BZ
REMOCON
CN22
(BLU)
RU
RECEIVER LED1 LED2 SW2 SW1
1 2
W.B
Refer to tables 1
and 2 for service PCB.
R.B
2
1
TH2
TH1
Table 1
SW1
Service board
1 2 3 4 5
ON
OFF
Service board
MODELS
1 2 3 4 5
PKA-RP60FAL
PKH-P60FALH
HEATER
PKA-RP71FAL
ON
OFF PKH-P71FALH
YLW
YLW
RED
1
1 2 3 4 5
MODELS
PKA-RP100FAL
ON
OFF PKH-P100FALH
Service board
1 2 3 4 5
ON
OFF
P100FALH models only
FS1
88H
SW2
Service board
MODELS
H1
CN24
1 2 (YLW)
6
1
TB6
2
TRANSMISSION WIRES DC12V
TB5
Table 2
PKH-P60
I.B
TH5
6
GRY
5 RED
26H
FS2
88H
RED
WHT
1
2
RED 5
TB2
L
3 RED
N
BLU
GRN/YLW
NOTES:
1. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
w1. When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig 1.
w2. For power supply system of this unit, refer to the caution label located near this diagram.
58
POWER SUPPLY
(1PHASE)
230V 50Hz
05.5.16 10:05 AM
Page 59
PCA-RP50GA PCA-RP60GA
PCA-RP71GA
PCA-RP100GA PCA-RP125GA PCA-RP140GA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR(LOSSNAY)
CONNECTOR(REMOTE SWITCH)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(CENTRALLY CONTROL)
SWITCH (MODEL SELECTION) WSee Table 1.
SWITCH (CAPACITY CODE) WSee Table 2.
SWITCH(EMERGENCY OPERATION)
RELAY(DRAIN PUMP)
RELAY(FAN MOTOR)
FAN CONTROL ELEMENT
POWER SUPPLY(I.B)
POWER SUPPLY(R.B)
TRANSMISSION(INDOOR-OUTDOOR)
CAPACITOR(FAN MOTOR)
SYMBOL
MF
MV
DP
DS
TB2
TB4
TB5,TB6
TH1
TH2
TH5
R.B
P.B CNDK
(RED)
C
BRN
ORN
YLW
ORN
RED
WHT
FUSE
D.SENSOR INTAKE LIQUID PIPE
CN31
CN20 CN21
CN29
(WHT)
(RED) (WHT) (BLK)
SW1
1 2
1 2
1 2
BLK
BLK
1 2 3
Refer to tables 1
and 2 for service PCB.
REMOCON
CN22
(BLU)
TB4
S1
S2
S3
MV
MV
9
100~140 TYPE
5
5
MV
CNB
Please set the voltage using the remote
controller.
For the setting method, please refer to
the indoor unit Installation Manual.
RU
RECEIVER LED1 LED2 SW2 SW1
W.B
2
1
TO OUTDOOR UNIT
50~71 TYPE
6
6
6
BZ
1 2
BLU
BLU
SW2
THERMAL FUSE(98;10A:50GAH/117;16A:100GAH
110;16A:60,71,125,140GAH)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
YLW
ORN
ORN
BRN
D.U.M 1 3 POWER 1 3 POWER 1 3
1 2
1 3 VANE
CND
CNDK
CNP
6
INDOOR/OUTDOOR (CN6V)
POWER
(ORN)
(RED)
(BLU)
CN2D(WHT) COMMUNICATION GRN
CN3C(BLU)
X4
X1
CN41
CN2L WIRELESS
ZNR
CN90
CN51
CN32 (WHT)
X4
X1
LED3 LED2 LED1
BLK
BLK
BCR
NAME
WIRELESS REMOTE CONTROLLER BOARD(OPTION)
RECEIVING UNIT
BUZZER
LED(RUN INDICATOR)
LED(HOT ADJUST)
SWITCH(HEATING ON/OFF)
SWITCH(COOLING ON/OFF)
1
2
DP
FAN 1 3 5
(WHT)
SWE
ON
OFF
H1
26H
88H
(OPTION)
1 2 3
I.B
SYMBOL
W.B
RU
BZ
LED1
LED2
SW1
SW2
HEATER
FS1,2
CN2S
(WHT)
1
2 DC13.1V
3
MF
NAME
FAN MOTOR
VANE MOTOR
DRAIN-UP MACHINE (OPTION)
DRAIN SENSOR (OPTION)
TERMINAL BLOCK (HEATER) WPCH-P.GAH
models only or option for PCA RP.GA models.
TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE )
ROOM TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
PIPE TEMP.THERMISTOR/LIQUID
(0;/15k', 25;/5.4k' DETECT)
COND./EVA.TEMP.THERMISTOR
(0;/15k', 25;/5.4k' DETECT)
WIRED REMOTE CONTROLLER BOARD
BLK
WHT
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
SW1
SW2
SWE
X1
X4
BCR
LED1
LED2
LED3
C
RED
WHT
BLK
TRANSMISSION WIRES DC12V
1 2
1 2
WWhen installing optional
TB5
drain-up machine disconnect
R.B
the CN31 jumper connector
1 2
and
replace
it
with
the
CN31
TB6
TH2
TH1
TH5
DRAIN SENSOR drain sensor (DS).
[Servicing]
(WHT) 1 2 3
When installing drain-up
Fasten terminal of the terminal board "TB4"equips lock system.
machine (Optional part).
To remove the fastened terminal, pull it while pressing the protruding
DS
portion (locking lever) of the terminal. The fastened terminal protruding
portion should face upward.
H1
FS1
FS2
88H
RED
WHT
1
2
RED 5
W1 (Fig.1)
TB2
L
3 RED
N
BLU
POWER SUPPLY
~(1PHASE)
230V 50Hz
GRN/YLW
W1. When work to supply power separately to
Indoor and Outdoor unit was applied, refer to Fig 1.
W2. For power supply system of this unit,
refer to the caution label located near this diagram.
I.B
1 2
HEATER
CN24
(YLW)
I.B
RED
6
6
1 GRY
5 RED
88H
Table 2
SW2
Table 1
MODELS
PCA-RP.GA
PCH-P.GAH
SW1
Service board
1 2 3 4 5
ON
OFF
MODELS
Service board
PCA-RP50GA
PCH-P50GAH
1 2 3 4 5
PCA-RP60GA
PCH-P60GAH
1 2 3 4 5
PCA-RP71GA
PCH-P71GAH
1 2 3 4 5
MODELS
Service board
PCA-RP100GA
1 2 3 4 5
PCA-RP125GA
1 2 3 4 5
PCA-RP140GA
1 2 3 4 5
ON
OFF PCH-P100GAH
ON
OFF PCH-P125GAH
ON
OFF PCH-P140GAH
TB2
RED
BLU
GRN/YLW
59
ON
OFF
ON
OFF
ON
OFF
26H
1 3
L
N
YLW TB4S1
ORN
S2
ORN
S3
BRN
YLW
ORN
PCH-P50~P140GAH
models only
YLW
YLW
OCS01-2.qxp
POWER SUPPLY
~(1PHASE)
230V 50Hz
TO OUTDOOR UNIT
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
NOTES:
1. Since the outdoor side electric wiring may change be sure to
check the outdoor unit electric wiring for servicing.
2. Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1, S2, S3).
3. Make sure that the main power supply of the booster heater is
independent.
4. Symbols used in wiring diagram above are,
: Connector,
: Terminal (block).
OCS01-2.qxp
05.5.16 10:05 AM
PCA-RP71HA
Page 60
PCA-RP125HA
[ LEGEND ]
SYMBOL
P. B
I. B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
X1
X4
X5
X6
SW1
SW2
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROLL)
POWER SUPPLY (I. B)
POWER SUPPLY (R. B)
TRANSMISSION(INDOOR-OUTDOOR)
RELAY (DEW PREVENTION HEATER)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH (MODEL SELECTION) See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SYMBOL
MF1, MF2
C1, C2
H2
TB2
NAME
FAN MOTOR
CAPACITOR(FAN MOTOR)
DEW PREVENTION HEATER
TERMINAL BLOCK(INDOOR UNIT
POWER (OPTION))
TB4
TERMINAL BLOCK(INDOOR/OUTDOOR
TB5,TB6
CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER
TRANSMISSION LINE)
ROOM TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH1
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH5
COND./ EVA.TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
R. B
WIRED REMOTE CONTROLLER BOARD
SWITCH (EMERGENCY OPERATION)
SWE
For PCA-RP125HA
1
1
I.B
FAN 1 3 5 7
(WHT)
DC13.1V
TB4
S1
S2
S3
YLW
ORN
ORN
BRN
FUSE
CN41
ZNR
TH1
1 2
1 2
1 2
BLK
BLK
Refer to tables 1
and 2 for service PCB.
PIPE REMOCON
CN29
CN22
(BLK)
(BLU)
BLU
BLU
LED3 LED2 LED1 INTAKE LIQUID
CN20
CN21
(RED) (WHT)
WHT
WHT
SW1
1 2
ON
OFF
YLW
ORN
ORN
CN2L
1 2
1 3
TH2
TH5
I.B
YLW
ORN
CN51 CN32
ON
OFF
Table 1
SW1
Service board
1 2 3 4 5
w1 (Fig.1)
D.HEATER 1 3 ROWER 1 3 ROWER 1 3
1 2
1 3
CNC
CNDK
CND
ROWER INDOOR/OUTDOOR
COMMUNICATION
(RED)
(RED)
(ORN)
CN2D(WHT) CN3C(BLU)
X6 X5 X4
SW2
TO
OUTDOOR
UNIT
RED
BLU
GRN/YLW
X6 X5 X4
SWE
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
1
2
BLK
WHT
H2
1
2
3
YLW
ORN
BRN
C2
GRY
CN2S
(WHT)
(RED)
YLW
YLW
ORN
C1
RED
P.B CNDK
RED
WHT
6 5 4 3 2 1
BLK
BLU
YLW
WHT
6 5 4 3 2 1
BLK
BLU
YLW
WHT
ORN
RED
BLK
BLU
YLW
WHT
MF2
ORN
RED
BLK
BLU
YLW
WHT
MF1
1 3
BRN
PCA-RP71HA
TB5
2
TRANSMISSION WIRES DC12V
1
SW2
MODELS
Service board
Service board
1 2 3 4 5
1 2 3 4 5
ON PCA-RP125HA
ON
OFF
OFF
NOTES:
1.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S1,S2,S3).
3.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
1 ; When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label located near this diagram.
60
POWER
SUPPLY
~(1PHASE)
230V 50Hz
TB4
S1
S2
S3
1 3
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
Table 2
MODELS
TB2
L
N
R.B
1
TB6
2
TO
OUTDOOR
UNIT
OCS01-3.qxp
05.5.16 10:08 AM
PSA-RP71GA
SYMBOL
P.B
I.B
FUSE
ZNR
CN2L
CN32
CN41
CN51
LED1
LED2
LED3
Page 61
PSA-RP100GA
NAME
INDOOR POWER BOARD
INDOOR CONTROLLER BOARD
FUSE (T6.3AL250V)
VARISTOR
CONNECTOR (LOSSNAY)
CONNECTOR (REMOTE SWITCH)
CONNECTOR (HA TERMINAL-A)
CONNECTOR (CENTRALLY CONTROL)
POWER SUPPLY (I.B)
POWER SUPPLY (R.B)
TRANSMISSION (INDOOR-OUTDOOR)
SYMBOL
I.B SW1
SW2
SWE
X2
X4
X5
X6
R.B
TB6
HEATER
FS1,2
H
26H
88H
PSA-RP125GA
NAME
SWITCH (MODEL SELECTION) See Table 1.
SWITCH (CAPACITY CODE) See Table 2.
SWITCH (EMERGENCY OPERATION)
RELAY (LOUVER)
RELAY (FAN MOTOR)
RELAY (FAN MOTOR)
RELAY (FAN MOTOR)
WIRED REMOTE CONTROLLER BOARD
TERMINAL BLOCK (REMOTE CONTROLLER
TRANSMISSION LINE)
THERMAL FUSE (110˚C16A)
HEATER
HEATER THERMAL SWITCH
HEATER CONTACTOR
PSA-RP140GA
SYMBOL
C
MF
ML
NAME
CAPACITOR (FAN MOTOR)
FAN MOTOR
LOUVER MOTOR
TB2
TERMINAL BLOCK (HEATER) PSH-P.GAH
models only or option for PSA-RP.GA models.
TB4
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TH1
ROOM TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
TH5
COND./EVA.TEMP.THERMISTOR
(0˚C/15kΩ, 25˚C/5.4kΩ DETECT)
INDOOR UNIT
TB4
YLW
S1
P.B
CNSK
(RED)
CN2S
(WHT)
2
1
ORN
S2
3
2
1
DC13.1V
S3
Please set the voltage using the
remote controller.
For the setting method, please refer to
the indoor unit Installation Manual.
TO
OUTDOOR
UNIT
TB2
1 (Fig.1)
ORN
MF
RED
BLU
GRY/YLW
ML
C
2
1
2
1
2
1
X2
X6 X5 X4
LED3 LED2 LED1
SW2
SWE
ON
SW1
OFF
CN24
TH2
Refer to tables 1
and 2 for service PCB.
R.B
2
1
I.B
YLW
YLW
1
TB6
TH5
88H 6YLW
FS2
6
5
RED 26H
RED
FS1
RED
WHT
H
1
2
TB4
S1
S2
S3
I.B
POWER SUPPLY
~(1PHASE)
230V 50Hz
1 3
1 3
TO
OUTDOOR
UNIT
POWER INDOOR/OUTDOOR
CND COMMUNICATION
(ORN)
CN3C
(BLU)
BLU
2
HEATER
CN24
(YLW)
RED
BLU
LIQUID WIRELESS
CN21
CN90
(WHT)
(WHT)
INTAKE
CN20 REMOCON 2
(RED)
CN22
(BLU) 1
PIPE
CN29
(BLK)
CN2L
CN41 CN32
1
TH1
PSH -P.GAH
models only
1 3
INDOOR/OUTDOOR
COMMUNICATION
CN3C
(BLU)
BRN
ORN
X6 X5 X4
CN51
ZNR
1 2
POWER
CN2D
(WHT)
YLW
ORN
X2
POWER 1 3
CND
(ORN)
L
N
BRN
ORN
POWER 1 3
CNDK
(RED)
BLK
WHT
RED
WHT
LOUVER 1 3
CNL
(YLW)
YLW
ORN
YLW
YLW
FAN 1 3 5 7
(WHT)
I.B
FUSE
BLK
BLU
YLW
WHT
RED
BLU
TRANSMISSION
WIRES DC12V
RED 5
88H
TB2
3 RED L
BLU N
GRN/YLW
POWER SUPPLY
~(1 PHASE)
230V 50Hz
Table 1
SW2
Service board
1
2 3 4 5
PSA-RP.GA
ON
PSH-P.GAH
OFF
MODELS
Table 2
SW2
Service board
1
2 3 4 5
PSA-RP71GA
ON
PSH-P71GAH
OFF
MODELS
PSA-RP100GA
PSH-P100GAH
1 2 3 4 5
PSA-RP125GA
PSH-P125GAH
1 2 3 4 5
PSA-RP140GA
PSH-P140GAH
1 2 3 4 5
1 ; When work to supply power separately to Indoor and Outdoor unit
was applied, refer to Fig1.
2 ; For power supply system of this unit, refer to the caution label
located near this diagram.
[NOTES]
1.Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (S1,S2,S3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor
unit electric wiring for servicing.
4.This diagram shows the wiring of Indoor and Outdoor connecting wires
(specification of 230V), adopting superimposed system of power and signal.
ON
OFF
ON
OFF
ON
OFF
61
OCS01-3.qxp
05.5.16 10:08 AM
PUHZ-RP35VHA
SYMBOL
TB1
MC
MF1
21S4
63H
SV
TH3
TH4
TH6
TH7
TH8
LEV(A),LEV(B)
ACL
P.B.
R/S
U/V/W
CN2~5
PFC
IPM
CB1~CB3
Page 62
PUHZ-RP50VHA
NAME
Terminal Block (Power Supply, Indoor/Outdoor)
Motor for Compressor
Fan Motors
Solenoid Valve (Four-Way Valve)
High Pressure Switch
Solenoid Valve (Bypass Valve)
Thermistor (Outdoor Pipe)
Thermistor (Discharge)
Thermistor (Outdoor 2-Phase Pipe)
Thermistor (Outdoor)
Thermistor (Radiator Panel)
Electronic Expansion Valve
Reactor
Power Circuit Board
Connection Terminal (L/N-Phase)
Connection Terminal (U/V/W-Phase)
Connector
Converter
Inverter
Main Smoothing Capacitor
PUHZ-RP60VHA
SYMBOL
N.F.
LI/LO
NI/NO
E
CNAC1/2
CN5
CN52C
52C
C.B.
SW1
PUHZ-RP71VHA
NAME
Noise Filter Circuit Board
Connection Terminal (L-Phase)
Connection Terminal (N-Phase)
Connection Terminal (Ground)
Connector
Connector
Connector
52C Relay
Controller Circuit Board
Switch (Forced Defrost, Defect History
Record Reset, Refrigerant Address)
Switch (Test Operation)
Switch (Function Switch)
Switch (Model Select)
Switch (Function Setup)
Switch
Switch
Switch (Model Select)
Light Emitting Diodes
(Operation Inspection Indicators)
SW4
SW5
SW6
SW7
SW8
SW9
SW10
LED1,LED2
SYMBOL
F1~4
SWP
CN31
CNAC
CNDC
CNS
CNF1
SS
SV2
CNM
CNMNT
NAME
Fuse (6.3 A)
Switch (Pump Down)
Connector (Emergency Operation)
Connector
Connector
Connector
Connector
Connector (Connection for Option)
Connector
Connector (A-Control Service Inspection Kit)
Connector
(Connected to Optional M-NET Adapter Board)
Connector
CNVMNT
(Connected to Optional M-NET Adapter Board)
Connector
CNDM
( Connected for Option (Contact Input))
X51,X52,X55 Reray
TH3
TH4
LEV-A
C.B.
LEV-B
SW11
SW1
LED2
SW7
LED1
12
CN2M
(WHT)
LED5
SW9
CN31
123
CNDM
(WHT)
CN52C
(RED)
12
A
12
34
CNAC
(WHT)
F4
21S4
1 (GRN)
3
21S4
SV2
1 (BLU)
3
B
S
TB7
M-NET
X51
F3
X52
F2
X55
CN51
(WHT)
CN4
(WHT)
21
12345
1
CN2
(WHT)
1234567
123
3
TRANS
F1
M-NET SUBSTRATE
1
CNDC
(PNK)
CNS
(WHT) 3 2 1
LED4
SW10
SW5
SW6
SW1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
CNM
(WHT)
SW4 SWP SW8
63H
(YLW)
F5
123456 123 12345
LEV-B
CNVMNT CNMNT
(RED)
(WHT)
(WHT)
LED1
MF1
123456
LEV-A
(WHT)
12 12
TH3 TH4
(WHT) (WHT)
LED2
1234
TH7/6
(RED)
SW12
LED3
1
CNF1
(WHT)
1
4567
3
1
CND
(WHT)
TH7 TH6
12345
CN5
(WHT)
When M-NET adaptor is connected
3
SS
1 (WHT)
SV
ACL
1 2
LO
NO
N.F.
2
W
CN3
(WHT)
CN2
(WHT)
CB3
3
1
CB2
21
S
CNAC2
(RED)
TH8
7 6 54 3 2 1
V
3
12
CN4
(WHT)
U
R
CN5
(RED)
1
I PM
21
PFC
CB1
52C
CN52C
(BLK)
MC
P.B.
CNAC1
(WHT)
1 MODEL SELECT
SW10
ON
OFF
50V
ON
OFF
ON
OFF
1 2 3 4 5 6
60V
ON
OFF
1 2
ON
OFF
1 2
ON
OFF
1 2 3 4 5 6
TB1
L
ON
OFF
1 2 3 4 5 6
71V
(RED)
CN5
1 2
1 2
N
S1 S2 S3
NO FUSE
BREAKER
POWER SUPPLY
~/N
230V 50Hz
INDOOR
UNIT
2 RP60/71V only
62
NI
1 2 3 4 5 6
E
35V
SW6
ON
OFF
LI
MODEL
1 2
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Terminal Block (M-net connection)
Connector (Transmission)
Connector (Power Supply)
Connector (M-NET communication)
Switch (Status of communication)
Switch (Address setting : 1st digit)
Switch (Address setting : 2nd digit)
LED (Power Supply : DC5V)
LED (Connection to Outdoor Unit)
LED (Transmission : Sending)
LED (Transmission : Recelving)
LED (Power Supply : DC12V)
OCS01-3.qxp
05.5.16 10:08 AM
Page 63
PUHZ-RP100VHA
SYMBOL
TB1
MC
MF1,MF2
21S4
SV
63H
63L
TH3
TH4
TH6
TH7
TH8
LEV-A,B
DCL
52C
RS
ACTM
CB
P.B.
TABU/V/W
TABS/T
PUHZ-RP125VHA
NAME
Terminal Block (Power Supply, Indoor/Outdoor )
Motor for Compressor
Fan Motors
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Low Pressure Switch
Thermistor (Outdoor Pipe)
Thermistor (Discharge)
Thermistor (Outdoor 2-Phase Pipe)
Thermistor (Outdoor)
Thermistor (Heat Sink)
Electronic Expansion Valve
Reactor
52C Relay
Rush Current Protect Resistor
Active Filter Module
Main Smoothing Capacitor
Power Circuit Board
Connection Terminal (U/V/W-Phase)
Connection Terminal (L/N-Phase)
SYMBOL
TABP1/P2/P
TABN1/N2/N
CN2~5
CNDC
CNAF
DS2,3
IPM
N.F.
LI/LO
NI/NO
EI
CNAC1/2
CN5
C.B.
F1~4
SW1
PUHZ-RP140VHA
NAME
Connection Terminal (DC Voltage)
Connection Terminal (DC Voltage)
Connector
Connector
Connector
Diode Bridge
Power Module
Noise Filter Circuit Board
Connection Lead (L-Phase)
Connection Lead (N-Phase)
Connection Terminal (Ground)
Connector
Connector
Controller Circuit Board
Fuse (6.3 A)
Switch (Forced Defrost, Defect History Record
Reset, Refrigerant Address)
Switch (Test Operation)
Switch (Function Switch)
Switch (Model Select)
Switch (Function Setup)
SW4
SW5
SW6
SW7
SYMBOL
SW8
SW9
SW10
SWP
CN31
LED1,LED2
NAME
Switch
Switch
Switch (Model Select)
Switch (Pump Down)
Connector (Emergency Operation)
Light Emitting Diodes
(Operation Inspection Indicators)
Connector
Connector
Connector
Connector
Connector
Connector
Connector
Connector
Connector (Connection for Option)
Connector
Connector (A-Control Service Inspection Kit)
Connector (Connected to Optional M-NET Adapter Board)
Connector (Connected to Optional M-NET Adapter Board)
Connector ( Connected for Option (Contact Input))
CN2
CNAC
CNDC
CNS
CNF1
CNF2
52C
21S4
SS
SV2
CNM
CNMNT
CNVMNT
CNDM
LEV-A
LEV-B
123456
123456
C.B.
SW11
SW1
LED2
SW7
SW9
SW6
CN31
3
F1
12
34
F4
3
52C
21S4
1 (BLK) 3
1 (GRN) 3
21S4
123
CN51
(WHT)
12345
A B S
TB7
M-NET
X51
X52
F3
CNAC
(WHT)
X53
F2
21
123
1
CNDM
(WHT)
CN4
(WHT)
X55
1
CN2
(WHT)
1234567
LED1
CNM
(WHT)
M-NET SUBSTRATE
12
CN2M
LED5 (WHT)
1 2 3 4 5 6 7 8 9 10 111213 14
LED4
SW10
63L
(RED)
SW1
LEV-B CNVMNT CNMNT
(RED) (WHT) (WHT)
SW4 SWP SW8 SW5
12345
TRANS
CNDC
(PNK)
CNS
(WHT) 3 2 1
123
123
LED1
63H
(YLW)
MF2
F5
LEV-A
(WHT)
TH3 TH4
(WHT) (WHT)
TH7/6
(RED)
MF1
12
LED2
1
4 5 6 7 CNF2
(WHT)
12
SW12
LED3
1
1234
(WHT)
1
4 5 6 7 CNF1
3
1
CND
(WHT)
TH7 TH6 TH3 TH4
12345
CN5
(WHT)
When M-NET adaptor is connected
SV2
3
1 (BLU)
SS
1 (WHT)
1MODEL SELECT
MODEL
SV
SW6
ON
100V OFF
SW10
ON
OFF
1 2 3 4 5 6
ON
125V OFF
1 2
ON
OFF
1 2 3 4 5 6
ON
140V OFF
P.B.
12
12
12
CN3
(WHT)
CN5
(RED)
CN4
(WHT)
TABN
TABP
IPM
~
~
1 2
N.F.
DS3
TABS
+
~
~
LO
NO
1 2
CN5
(RED)
NI
EI
DS2
TABP1
-
+
(RED)
CNAC2
3 1
TABN1
(WHT)
CNAC1
3 1
LI
+
TABV
TABP2
+
U
V
TABW
CN2
(WHT)
TABU
1234567
+
CB
1 2 3 4 5 6
TABT
CNAF
(WHT)
CNDC 1 3
(PNK)
123456
TH8
1 2
ON
OFF
TABN2
W
MC
M-NET ADAPTER
TB1 L
DCL
N
S1 S2 S3
RS
L2
L1
52C
123456
+
P
-
N1
N2
I
ACTM
NO FUSE
BREAKER
INDOOR
UNIT
POWER SUPPLY
~/N
230V 50Hz
63
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Terminal Block (M-net connection)
Connector (Transmission)
Connector (Power Supply)
Connector (M-NET communication)
Switch (Status of communication)
Switch (Address setting : 1st digit)
Switch (Address setting : 2nd digit)
LED (Power Supply : DC5V)
LED (Connection to Outdoor Unit)
LED (Transmission : Sending)
LED (Transmission : Recelving)
LED (Power Supply : DC12V)
PUHZ-RP125YHA
63H
63L
TH4
3
12345
CN5
(WHT)
M-NET
SV
(
1 MODEL SELECT)
SW6
MODELS
P.B.
123
CN7
(WHT)
1234567
CN2
(WHT)
CT2
+
TB-W
BLK
TB-V
WHT W
RED V
12
12
CN5 CN4
(RED) (WHT)
+
125Y
ON
OFF
140Y
ON
OFF
BLK
TB-L2
WHT
TB-L1
RED
TB-C1
TB-N1
CB2
CK
S3
CB1
CNAC1 1
(WHT)
N.F.
TB1
L1
L2
L3
BLK
N
BLU
1 2
1 2 3 4 5 6
ON
OFF
1 2
1 2 3 4 5 6
ON
OFF
1 2
L1-A1
S2
NO FUSE
BREAKER
ON
OFF
123
CN7
(WHT)
TB-P2
SW10
1 2 3 4 5 6
L3-OU
TB-L3
RS
TB2
S1
INDOOR
UNIT
-
MC
ON
OFF
U
TB-U
CT1
100Y
CNCT 1 2
(RED)
3
1
3 CNAC2
(RED)
L1-A2
21S4
3
TB7
A B S
SS
1 (WHT)
CK-OU
SV2
1 (BLU)
L2-A2
3
21S4
1 (GRN)
L1-OU
CNS
(WHT) 3 2 1
F4
N-IN
F1
123
L2-OU
F3
CNAC
(WHT)
12
34
X55
F2
1
CONV.B.
L1-IN
CNDC
(PNK)
CN4
(WHT)
21
L3-A2
1
CN2
(WHT)
1234567
X51
TRANS
SW12
LED3
LED4
CND
(WHT)
CN31
LED2
LED1
1
SW11
SW1
12
CN2M
LED5 (WHT)
1 2 3 4 5 6 7 8 9 10 11121314
CNM
SW6
123456 123 12345
LEV-B CNVMNT CNMNT
(RED)
(WHT) (WHT)
3
F5
1 3
63L
(RED)
123456
LEV-A
(WHT)
M-NET ADAPTER (OPTION)
SW9 SW7
4 5 6 7 CNF2
(WHT)
12 12
TH3 TH4
(WHT) (WHT)
LED1
1
MF2
1234
TH7/6
(RED)
LED2
4 5 6 7 CNF1 1 2 3
(WHT) CN3N
63H
(YLW)
3 1
1
MF1
LEV
LEV
SW1
TH3
C.B.
SW10
TH7 TH6
PUHZ-RP140YHA
CN51 CNDM CN3S
(WHT) (WHT) (WHT)
12345 123 123
PUHZ-RP100YHA
Page 64
SW4 SWP SW8 SW5
05.5.25 11:48 AM
X52
OCS01-3.qxp
ACL1
RED
LI1
LO1
RED
WHT
LI2
LO2
WHT
LI3
LO3
BLK
NI
NO
ACL2
POWER SUPPLY
3N~
400V
50Hz
ACL3
GD1
SYMBOL
TB1
TB2
MC
MF1,MF2
21S4
SV
63H
63L
TH3
TH4
TH6
TH7
LEV
ACL1~ACL4
CB1,CB2
CK
RS
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P2
TB-C1
TB-N1
CT1, CT2
CN2
CN4
CN5
CN7
NAME
Terminal Block (Power Supply )
Terminal Block (Indoor/Outdoor )
Motor for Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Low Pressure Switch
Thermistor (Outdoor Pipe)
Thermistor (Discharge)
Thermistor (Outdoor 2-Phase Pipe)
Thermistor (Outdoor)
Linear Expansion Valve
Reactor
Main Smoothing Capacitor
Capacitor
Rush Current Protect Resistor
Power Circuit Board
Connection Terminal (U/V/W-Phase)
Connection Terminal (L1/L2/L3-Power Supply)
Connection Terminal
Connection Terminal
Connection Terminal
Current Trans
Connector
Connector
Connector
Connector
SYMBOL
N.F.
LI1/LI2/LI3/NI
LO1/LO2/LO3/NO
CNAC1
CNAC2
CNCT
CNDC
CNL
GD1
CONV.B
L1-A1/IN
L1-A2/OU
L2-A2/OU
L3-A2/OU
N-IN
CK-OU
CN7
C.B.
F1,F2
F3,F4
SW1
SW4
SW5
SW6
SW7
SW8
SW9
GD2
CNDC 1
(PNK)
NAME
Noise Filter Circuit Board
Connection Terminal (L1/L2/L3/N-Power Supply)
Connection Terminal (L1/L2/L3/N-Power Supply)
Connector
Connector
Connector
Connector
Connector
Connection Terminal (Ground)
Converter Circuit Board
Connection Terminal (L1-Power Supply)
Connection Terminal (L1-Power Supply)
Connection Terminal (L2-Power Supply)
Connection Terminal (L3-Power Supply)
Connector
Connector
Connector
Controller Circuit Board
FUSE (6.3 A)
FUSE (6.3 A)
Switch (Forced Defrost, Defect History Record
Reset, Refrigerant Adress)
Switch (Test Operation)
Switch (Function Switch)
Switch (Model Select)
Switch (Function Switch)
Switch (Function Switch)
Switch (Function Switch)
M-NET ADAPTER
TB7
CN5
CND
CN2M
SW1
SW11
Terminal Block (M-NET connection )
Connector (Transmission)
Connector (Power Supply)
Connector (M-NET communication)
Switch (Status of communication)
Switch (Address setting: 1st digit)
SW12
LED1
LED2
LED3
LED4
LED5
3
Switch (Address setting. 2nd digit )
LED (Power Supply: DC5V)
LED (Connection to Outdoor Unit)
LED (Transmission: Sending)
LED (Transmission: Receiving)
LED (Power Supply: DC12V)
64
3
1 CNL
(BLU)
SYMBOL
SW10
SWP
CN31
CNAC
CNS
CNDC
21S4
SV2
SS
CN2
CN4
LEV-A/LEV-B
63H
63L
TH3
TH4
TH7/6
CNF1/CNF2
LED1/LED2
CNM
CNVMNT
CNMNT
CN3S
CNDM
CN51
BLU
ACL4
NAME
Switch (Model Select)
Switch (Pump Down)
Connector (Emergency Operation)
Connector
Connector
Connector
Connector (Four-Way Valve)
Connector (Bypass Valve)
Connector (Connection for Option)
Connector
Connector
Connector (LEV)
Connector (High Pressure Switch)
Connector (Low Pressure Switch)
Connector (Thermistor)
Connector (Thermistor)
Connector (Thermistor)
Connector (Fan Motor Operation)
LED (Operatiion Inspection Indicators)
Connector (A-Control Service Inspection Kit)
Connector (Connect to Optional M-NET Adapter Board)
Connector (Connect to Optional M-NET Adapter Board)
Connector ( Connection for Option)
Connector ( Connection for Option)
Connector ( Connection for Option)
Page 65
PUHZ-RP250YHA
1 MODEL SELECT
SW6
MODEL
SYMBOL
TB1
TB2
MC
MF
21S4
SV
63H
63L
TH3
TH32
TH4
TH6
TH7
LEV
DCL
CB1,CB2
RS
FUSE1,FUSE2
P.B.
TB-U/V/W
TB-L1/L2/L3
TB-P1
TB-P2
TB-C1
TB-N1
CT1,CT2
CN1
CN2
CN4
CN5
N.F.
LI1/LI2/L13/NI
LO1/LO2/LO3/NO
CNAC1
CNAC2
CNCT
CNDC
F.C.
U/V/W
CN2
CN5
CN6
LED1
C.B.
F3, F4
SW1
NAME
Terminal Block (Power Supply)
Terminal Block (Indoor/Outdoor)
Motor Compressor
Fan Motor
Solenoid Valve (Four-Way Valve)
Solenoid Valve (Bypass Valve)
High Pressure Switch
Low Pressure Switch
Thermistor (Outdoor Pipe)
Thermistor (Outdoor Pipe)
Thermistor (Discharge)
Thermistor (Outdoor 2-Phase Pipe)
Thermistor (Outdoor)
Linear Expansion Valve
Reactor
Main Smoothing Capacitor
Rush Current Protect Resistor
FUSE (15 A)
Power Circuit Board
Connection Terminal (U/V/W-Phase)
Connection Terminal (Ll /L2/L3-Power Supply)
Connection Terminal
Connection Terminal
Connection Terminal
Connection Terminal
Current Trans
Connector
Connector
Connector
Connector
Noise Filter Circuit Board
Connection Terminal (L1/L2/L3/N-Power Supply)
Connection Terminal (L1/L2/L3/N-Power Supply)
Connector
Connector
Connector
Connector
Fan Controller Circuit Board
Connection Terminal (U/V/W-Phase)
Connector
Connector
Connector
LED (MF Operation Status Indicators)
Controller Circuit Board
FUSE (6.3 A)
Switch (Forced Defrost, Defect History Record
Reset, Refrigerant Address)
Switch (Test Operation)
SW4
Switch (Function Switch)
SW5
Switch (Model Select)
SW6
SW7
Switch (Function Switch)
Switch (Function Switch, Model Select)
SW8
Switch (Function Switch)
SW9
Switch (Model Select)
SW10
SWP
Switch (Pump Down)
Connector (Emergency Operation)
CN31
CNAC
Connector
CNS
Connector
CNDC
Connector
21S4
Connector
SV2
Connector
Connector (Connection for Option)
SS
CN2
Connector
Connector
CN4
Connector
CN331
Connector
CN332
LEV-A
Connector
63H
Connector
63L
Connector
TH3
Connector
Connector
TH4
Connector
TH7/6
TH32
Connector
Connector (A-Control Service Inspection Kit)
CNM
CNVMNT Connector (Connect to Optional M-NET Adapter Board)
Connector (Connect to Optional M-NET Adapter Board)
CNMNT
CN3S
Connector ( Connection for Option)
CNDM
Connector ( Connection for Option)
Connector ( Connection for Option)
CN51
LED1,LED2 LED (Operation Inspection Indicators)
ON
RP200Y OFF
ON
RP250Y OFF
SW8
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
SW10
ON
OFF
1 2 3
1 2
ON
OFF
1 2 3
1 2
M-NET ADAPTER
SYMBOL
TB7
CN5
CND
CN2M
SW1
SW11
SW12
LED1
LED2
LED3
LED4
LED5
NAME
Terminal Block(M-NET connection)
Connector (Transmission)
Connector (Power Supply)
Connector (M-NET communication)
Switch (Status of communication)
Switch (Address setting:1st digit)
Switch (Address setting:2nd digit)
LED (Power Supply:DC5V)
LED (Connection to Outdoor Unit)
LED (Transmission:Sending)
LED (Transmission:Receiving)
LED (Power Supply:DC12V)
SW1
OFF
ON
LED2
SW12
LED3
LEV
1 2 3 4 1 2
1 2
1 2 3 4 5 6
1 2
TH4
TH7/6
(RED)
TH3 TH4
(WHT) (WHT)
CNMNT
(WHT)
1 2
LED2
1
3
63H
(YLW)
63L
(RED)
CNVMNT
(WHT)
CN331 LEV-A
(GRN) (WHT)
1 2 3
1
1 2 3 4 5 6 7 8 9 10 11121314
CNM
ON
OFF
ON
OFF
SW6
TH32
(BLK)
1 2 3 4 5
1
SW1
CN3N
(RED)
1 2 3
CN31
SW10 SW9 SW7
1 2
LED1
1 2 3
SW4 SWP SW8 SW5
ON
OFF
C.B.
1
A
B
CN4
(WHT)
1 2
2 1
CN51
(WHT)
CN2
(WHT)
1 2 3 4 5 6 7
F3
21S4
(GRN)
SV2
(BLU)
SS
(WHT)
F4
3
3
3
1
1
1 2 3
1
3 5
CN5
(WHT)
1 2
3 4
SV
1 2
CN2
(GRN)
21S4
1 2
CN6
(BLU)
P.B.
1 2 3 4 5 6 7
CN2
(WHT)
CT2
+
TB-W
--
1 2
CN5
CN4
(RED) (WHT)
1 2
CT1
+
TB-L3
TB-L2
TB-L1
--
RS
CN1(WHT)
S1
1
+
+
CB1
N.F.
LI 2
LO 2
L3
LI 3
LO 3
N
NI
GD2
65
3
CNDC
(PNK)
1
1
3
LO 1
CNAC2
(RED)
3
1
CNAC1
(WHT)
1 2
LI 1
L2
CNCT
(RED)
TB1
L1
GD1
5
TB-C1
TB-P2
DCL
NO FUSE
BREAKER
3
TB-P1
+
CB2
TB-N1
TB-U
F.C.
W
V
TB-V
INDOOR S2
UNIT
S3
U
1
CNAC
(WHT)
CNS
(WHT)
3 2 1
1 2 3
CN332
(BLU)
1 2 3 4 5
CN3S
(WHT)
12V
5V
GND
1 CNDC
(PNK)
M-NET
CNDM
(WHT)
3
CND
(WHT)
1 2 3
TB7
S
CN32
LED1
63L
TH3
CN2M
LED5 (WHT)
LED4
U
V
LED1
63H
TH32 TH7 TH6
TB2
POWER SUPPLY
3N~
400V 50Hz
SW11
CN5
(WHT)
1 2 3 4 5
M-NET ADAPTER(OPTION)
FUSE2
PUHZ-RP200YHA
GND
5V
GND2
18V
05.5.16 10:08 AM
FUSE1
OCS01-3.qxp
W
1 2 3
1 2 3
MC
MF
OCS01-3.qxp
5
05.5.16 10:08 AM
Page 66
REFRIGERANT SYSTEM DIAGRAM
5-1. INDOOR UNIT
PLA-RP·AA
PKA-RP·GAL
PEAD-RP·EA
PCA-RP·GA
PKA-RP·FAL
PEAD-RP·GA
PCA-RP·HA
PSA-RP·GA
PEA-RP·EA
PEH-RP·MYA
Strainer(#50)
Heat exchanger
Thermistor TH5
(Cond./Eva. temperature)
Refrigerant GAS pipe connection
(Flare)
(PEH brazing)
Refrigerant flow in cooling
Refrigerant flow in heating
Distributor
with strainer(#50)
Thermistor TH1
(Room temperature)
Thermistor TH2
Pipe temperature (Liquid)
Refrigerant LIQUID pipe connection
(Flare)
(PEH brazing)
Strainer(#50)
66
OCS01-3.qxp
05.5.16 10:08 AM
Page 67
5-2. OUTDOOR UNIT
PUHZ-RP35VHA
PUHZ-RP50VHA
Heat exchanger
Stop valve
(with service port)
Refrigerant GAS pipe
connection(1/2F)
Thermistor TH6
(Outdoor 2-phase pipe)
Charge plug
Solenoid valve
(Four-way valve)
Thermistor TH7
(Outdoor)
Strainer
#50
Thermistor TH3
(Outdoor pipe)
Muffler
Distributor
High pressure
switch 63H
Thermistor TH4
(Discharge)
Muffler
Linear
expansion valve B
Compressor
Power
receiver
Linear expansion valve A
Stop valve
Refrigerant LIQUID pipe
connection(1/4F)
Strainer
#100
Strainer
#100
PUHZ-RP60VHA
PUHZ-RP71VHA
Heat exchanger
Ball valve
Refrigerant GAS pipe
connection(5/8F)
Strainer
#50
Thermistor TH7
(Outdoor)
Thermistor TH6
(Outdoor 2-phase pipe)
4-way valve
Oil separator
Bypass valve
Charge plug
(Low pressure)
Charge plug
(High pressure)
Capillary tube
O.D.4.0OI.D.2.4OL500
Capillary tube
O.D.2.5OI.D.0.6OL1000
Thermistor TH3
(Outdoor pipe)
Distributor
High pressure
switch 63H
Strainer
#100
Thermistor TH4
(Discharge)
Strainer
#100
Stop valve
(with service port)
Refrigerant LIQUID pipe
connection(3/8F)
Strainer
#100
Power
receiver
Linear
expansion
valve B
Muffler Compressor
Linear expansion valve A
Strainer
#100
Refrigerant flow in cooling
Refrigerant flow in heating
67
OCS01-3.qxp
05.5.16 10:08 AM
Page 68
PUHZ-RP100VHA
PUHZ-RP125VHA
PUHZ-RP140VHA
PUHZ-RP100YHA
PUHZ-RP125YHA
PUHZ-RP140YHA
Heat exchanger
Refrigerant GAS pipe
connection(5/8F)
Ball valve Strainer
#50
Thermistor TH6
(Outdoor 2-phase pipe)
Solenoid valve
(Four-way valve)
Thermistor TH3
(Outdoor pipe)
Charge plug
(High pressure)
Muffler
Charge plug
(Low pressure)
Distributor
Low pressure
switch 63L
Strainer
#100
High pressure
switch 63H
Thermistor TH4
(Discharge)
Strainer
#100
Linear
expansion valve B
Stop valve
(with service port)
Refrigerant LIQUID pipe
connection(3/8F)
Thermistor TH7
(Outdoor)
Strainer
#100
Power
receiver
Compressor
Linear expansion valve A
Restrictor
valve
Strainer
#100
Strainer
#100
Strainer
#100
Solenoid valve
(Bypass valve)
Replace filter
PUHZ-RP200YHA
PUHZ-RP250YHA
High pressure switch 63H
Charge plug
(High pressure)
4-way valve
Stop valve
(with service port)
Refrigerant GAS pipe
connection
(RP200:1, RP250:1-1/8)
Strainer
#50
Strainer
#100
Capillary tube2
Replace
Bypass valve
filter
Oil
separator
Heat exchanger
Thermistor TH7
(Outdoor)
Strainer
#100
Charge plug
(Low pressure)
Accumulator
Thermistor TH6
(Outdoor 2-phase pipe)
Strainer
#100
Thermistor TH3
(Outdoor pipe)
Capillary tube1
Thermistor TH4
(Discharge)
Oil-back hole
Strainer#40
Refrigerant LIQUID pipe
connection
(RP200:3/8F, RP250:1/2F)
Low pressure switch 63L
Compressor
Stop valve
(with service port)
Strainer
#50
Linear expansion valve
Strainer
#100
Thermistor TH32
(Outdoor pipe)
Strainer
#100
Refrigerant flow in cooling
Refrigerant flow in heating
68
OCS01-3.qxp
05.5.16 10:08 AM
6
Page 69
PERFORMANCE CURVES
6-1. FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-RP•VHA, PUHZ-RP100~140YHA
Cooling performance curve(50Hz)
CAPACITY (RATIO)
1.4
INDOOR
W.B.(°C)
1.2
22
1.0
20
18
0.8
16
22
20
18
16
TOTAL INPUT (RATIO)
1.2
1.0
0.8
0.6
0.4
-5
0
10
20
30
40
46
OUTDOOR D.B.(°C)
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
69
INDOOR
W.B.(°C)
OCS01-3.qxp
05.5.16 10:08 AM
Page 70
Heating performance curve(50Hz)
Correcting the capacity line influenced by frosting
Not correcting the capacity line influenced by frosting
CAPACITY (RATIO)
1.4
1.2
In some cases, heating operation
cannot be conducted with the maximum
frequency in the area below the slanting line.
15
20
25
INDOOR
D.B.(°C)
25
20
INDOOR
D.B.(°C)
1.0
0.8
0.6
0.4
TOTAL INPUT (RATIO)
1.4
1.2
In some cases, heating operation
cannot be conducted with the maximum
frequency in the area above the slanting line.
15
1.0
0.8
0.6
0.4
-12 -10
-5
0
5
10
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
70
15
OCS01-3.qxp
05.5.16 10:08 AM
Page 71
6-2. FOR THE COMBINATION OF OUTDOOR UNIT PUHZ-RP200 / 250YHA
Cooling capacity
1.4
Cooling capacity ratio
Indoor intake air wet-bulb temperature <W.B. :>
1.2
22
1
20
18
0.8
0.6
16
-5
0
5
10
15
20
25
30
35
40
46
Outdoor intake air dry-bulb temperature <D.B. :>
Cooling input
22 20
18
16
Cooling input ratio
1.2
1.0
0.8
0.6
Indoor intake air wet-bulb temperature <W.B. :>
0.4
-5
0
5
10
15
20
25
30
35
40
Outdoor intake air dry-bulb temperature <D.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
71
46
OCS01-3.qxp
05.5.16 10:09 AM
Page 72
Heating capacity
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Heating input
Indoor intake air dry-bulb temperature <D.B. :>
Outdoor intake air wet-bulb temperature <W.B. :>
Note : This diagrams show the case where the operation frequency of a compressor is fixed.
72
OCS01-3.qxp
05.5.16 10:09 AM
7
Page 73
CORRECTION FACTORS
7-1. PUHZ-RP·VHA, PUHZ-RP100~140YHA
Cooling capacity correction factors
Outdoor unit
Refrigerant piping length (one way)
30m
40m
50m
55m
5m
10m
20m
PUHZ-RP35VHA
1.00
0.992
0.976
0.962
0.949
0.936
PUHZ-RP50VHA
1.00
0.985
0.957
0.931
0.908
PUHZ-RP60VHA
1.00
0.992
0.976
0.962
PUHZ-RP71VHA
1.00
0.988
0.966
1.00
0.985
1.00
1.00
PUHZ-RP100VHA
PUHZ-RP100YHA
PUHZ-RP125VHA
PUHZ-RP125YHA
PUHZ-RP140VHA
PUHZ-RP140YHA
60m
70m
80m
0.930
—
—
—
0.886
0.876
—
—
—
0.949
0.936
0.930
—
—
—
0.946
0.929
0.913
0.905
—
—
—
0.957
0.931
0.908
0.886
0.876
0.865
0.846
0.829
0.981
0.946
0.914
0.885
0.858
0.845
0.834
0.812
0.792
0.976
0.931
0.893
0.858
0.827
0.813
0.800
0.775
0.753
60m
70m
80m
Heating capacity correction factors
5m
10m
20m
Refrigerant piping length (one way)
30m
40m
50m
55m
PUHZ-RP35VHA
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP50VHA
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP60VHA
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
PUHZ-RP71VHA
1.00
0.997
0.991
0.985
0.979
0.973
0.970
—
—
—
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
1.00
0.997
0.991
0.985
0.979
0.973
0.970
0.967
0.961
0.955
Outdoor unit
PUHZ-RP100VHA
PUHZ-RP100YHA
PUHZ-RP125VHA
PUHZ-RP125YHA
PUHZ-RP140VHA
PUHZ-RP140YHA
7-2. PUHZ-RP200·250YHA
Cooling capacity correction factors
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
5m
10m
15m
20m
25m
30m
35m
40m
1.00
0.985
0.971
0.958
0.943
0.931
0.919
0.908
45m
50m
55m
60m
65m
70m
75m
80m
0.898
0.887
0.876
0.865
0.855
0.847
0.838
0.829
85m
90m
95m
100m
105m
110m
115m
120m
125m
0.823
0.815
0.808
0.800
0.797
0.790
0.785
0.780
0.778
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
Heaing capacity correction factors
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
5m
10m
15m
20m
25m
30m
35m
40m
1.00
0.997
0.994
0.991
0.988
0.985
0.982
0.979
45m
50m
55m
60m
65m
70m
75m
80m
0.976
0.973
0.970
0.967
0.964
0.961
0.958
0.955
85m
90m
95m
100m
105m
110m
115m
120m
125m
0.952
0.949
0.946
0.943
0.940
0.937
0.934
0.931
0.928
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
Refrigerent piping length (one way)
Outdoor unit
PUHZ-RP200/250YHA
73
OCS01-3.qxp
05.5.16 10:09 AM
Page 74
APPLICABLE EXTENSION PIPE FOR EACH MODEL
8
8-1. PUHZ-RP·VHA, PUHZ-RP100~140YHA
The height difference between indoor and outdoor unit should be kept within 30 m for all models.
(1) 1:1 system
(a) Maximum pipe length
<Table 1> Pipe length for 1:1 system
Liquid OD
[6.35
pipe
t0.8
(mm) Thickness
Gas OD
[9.52
[12.7
pipe
t0.8
t0.8
(mm) Thickness
RP35
RP50
RP60
RP71
RP100
RP125
RP140
30m
10m
50m
50m
10m
10m
[9.52
[12.7
t0.8
[15.88
[12.7
t1.0
t0.8
30m
30m
10m
10m
30m
30m
30m
30m
t0.8
[15.88
[19.05
[15.88
[19.05
t1.0
t1.0
t1.0
t1.0
30m (*1)
30m (*1)
50m
50m
75m (*2)
75m (*2)
75m (*2)
50m (*1)
50m (*1)
50m (*1)
30m
30m
50m
50m
50m
50m (*1)
50m (*1)
50m (*1)
*1: Set DIP SW8-1 on outdoor unit controller board to ON.
*2: The maximum length is 50 m in case of using existing pipes.
[Marks in the table above]
: Standard piping
: It can be used, however, additional refrigerant charge is required when the pipe length exceeds 20m.
: It cannot be used.
: It can be used.
: It can be used, however, the capacity is lowered.
Refer to (c) Capacity correction.
Refer to <table 4>.
(b) Adjusting the amount of refrigerant
• Additional refrigerant charge is not necessary for the pipe length up to 30 m. When the pipe length exceeds 30 m or service
(refrigerant replacement) is performed, charge proper amount of refrigerant for each pipe length referring to table below.
Use refrigerant R410A. Use charge hose exclusive for R410A.
• When charging additional refrigerant, charge the refrigerant from low-pressure side of the port valve using a safety charger.
• Make sure that air purge for this unit at refrigerant replacement is performed from both high-pressure check valve and service port. If air purge is performed only from one of them, air in not purged enough.
• When replacing refrigerant, charge the refrigerant from service port. When charged refrigerant is less than specified amount,
charge the refrigerant again from low pressure side of the port valve using a safety charger.
• Tighten the service port cap (nut) of stop valve firmly. The tightening torque is 12 to 16 N·m. (to prevent slow-leak)
• Check additional refrigerant charging amount referring to table 4 when liquid pipe is one size larger than standard diameter,
and table 2 when the pipe is standard diameter.
<Table 2> Additional refrigerant charging amount for pipe of standard diameter
Additional refrigerant charging amount for pipe
Permitted
Height
Number of
length exceeding 30 m (kg)
Outdoor unit
pipe length
difference
bends
31 — 40m 41 — 50m 51 — 60m 61 — 75m
PUHZ-RP35, 50VHA
50m or less
0.2kg
0.4kg
—
—
PUHZ-RP60, 71VHA
50m or less
0.6Kg
1.2Kg
—
—
PUHZ-RP100-140VHA, RP100-140YHA 75m or less
0.6kg
1.2kg
1.8kg
2.4kg
15
30m or
above
<Table 3>
Outdoor unit
PUHZ-RP35, 50VHA
PUHZ-RP60, 71VHA
PUHZ-RP100-140VHA
PUHZ-RP100-140YHA
Recharge refrigerant amount or additional amount in parentheses
Permitted
pipe length 10m or below 11 — 20m 21 — 30m 31 — 40m 41 — 50m 51 — 60m 61 — 75m
50m or less
50m or less
75m or less
2.1
3.1
4.6
2.3
3.3
4.8
2.5
3.5
5.0
2.7
2.9
—
—
(0.2)
(0.4)
—
—
4.1
4.7
—
—
(0.6)
(1.2)
—
—
5.6
6.2
6.8
7.4
(0.6)
(1.2)
(1.8)
(2.4)
<Table 4> Required additional charge when the pipe size is larger than the standard diameter
Liquid pipe dia Chargeless Max. pipe length Refrigerant amount to be added
RP35, 50
[9.52
20m
30m
60 g per 1 m longer than 20 m
RP60, 71
[12.7
20m
30m
100 g per 1 m longer than 20 m
RP100-140
[12.7
20m
50m
100 g per 1 m longer than 20 m
74
05.5.16 10:09 AM
Page 75
(c) Capacity correction
Cooling and heating capacity is lowered according to pipe length. Capacity can be obtained by referring to the capacity
curves below. When the diameter of gas pipe is one size smaller than standard diameter, cooling capacity is lowered comparing to the standard diameter. The lowered capacity can be obtained by referring to capacity curves for gas pipe which is
one size smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends x 0.3 (m)
1 Capacity curves for PUHZ-RP • HA model <Standard size>
Cooling
100
Heating
95
Heating RP35, 50, 60,
71, 100, 125 and 140
models
(Up to 55m for RP35,
50, 60, 71 model)
Capacity ratio [%]
Cooling RP35, 60 models
Cooling RP71 model
90
85
Cooling RP50, 100 models
80
Cooling RP125 model
75
Cooling RP140 model
Note: The permitted pipe length is up to 55m for RP35, 50, 60, 71 model.
70
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Corrected pipe length
2 Capacity curve for PUHZ-RP35, 50 models
<When gas pipe is one size smaller than standard size>
100
Heating RP35, RP50
95
Capacity ratio [%]
OCS01-3.qxp
90
Cooling RP50
85
Cooling RP35
80
5
10
15
20
25
30
35
Corrected pipe length
75
40
45
50
55
OCS01-3.qxp
05.5.16 10:09 AM
Page 76
3 Capacity curve for PUHZ-RP60, 71 models
<When gas pipe is one size smaller than standard size>
100
Heating RP60, RP71
Capacity ratio [%]
95
90
Cooling RP60
85
80
Cooling RP71
5
10
15
20
25
30
35
40
45
50
55
Corrected pipe length
4 When gas pipe is one size larger than standard size for PUHZ-RP100, 125 and 140.
1 Capacity can be obtained by referring to capacity curves of standard size.
76
OCS01-3.qxp
05.5.16 10:09 AM
Page 77
8-2. PUHZ-RP200·250YHA
8-2-1. 1:1 SYSTEM
(1) Pipe length
<Table 1> Maximum pipe length (RP200·RP250)
Liquid
pipe
(mm)
gas
pipe
(mm)
OD
Thickness
OD
Thickness
[9.52
[12.7
[15.88
t0.8
t0.8
t1.0
[19.05
[22.2
[25.4
[28.58
[19.05
[22.2
[25.4
[28.58
[22.2
[25.4
[28.58
[31.75
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
t1.0
20m
[20m]
50m
[30m]
70mw1
[30m]
70m
[30m]
20m
[20m]
50m
[30m]
70m
[30m]
70m
[30m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[30m]
70m
[30m]
70m
[30m]
20m
[20m]
50m
[30m]
70m
[30m]
50m
[20m]
50m
[20m]
50m
[20m]
50m
[20m]
Normal piping
RP200
SW
SW
SW
w2
Nomal piping
20m
[20m]
RP250
70mw1
[30m]
SW
w2
Note : The maximum pipe length is 80m in case of new piping.
w1 Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
<Marks in the table above>
SW : When the outdoor unit is located lower than
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
: It can be used.
: Cooling capacity is lowered. Refer to <Table6>
: Additional refrigerant charge is required when
the pipe length exceeds 20m. Refer to <Table7>
SW
The maximum pipe length
Charge-less pipe length
70m
[30m]
(2) Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to table 7 when the liquid pipe diameter is larger than
the standard size, and table 2 when the pipe of the standard diameter is used.
<Table 2>
permitted
pipe length
Outdoor unit
RP200
At time of shipping
(kg)
120m or less
10.5
No additional
charge necessary
10.5
RP250
Amount of additional refrigerant charge (kg)
30 m and less
31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less
The additional charge
0.9 kg
1.8 kg
2.7 kg
3.6 kg
1.2 kg
2.4 kg
3.6 kg
4.8 kg
amount is obtained by
the following formula.
Calculate the additional charge amount based on the following procedure.
If the calculation results in an amount that is smaller than the "Additional charge amount for 70m," perform the additional charge using the amount shown
in "Additional charge amount for 70m."
Amount of additional
charge [kg]
=
Main piping:
Liquid line size
[12.7 over all length [m]
o 0.12 [kg/m]
+
Main piping:
Liquid line size
[9.52 overall length [m]
o 0.09 [kg/m]
+
Branch piping: Liquid
line size
[9.52 overall length [m]
o 0.06 [kg/m]
+
Branch piping: Liquid
line size
[6.35 overall length [m]
o 0.02 [kg/m]
–
3.6 (kg)
Additional charge amount RP200 3.6 kg
for 70 m
RP250 4.8 kg
•If the wiring connecting the indoor and outdoor units is longer than 80m. use separate indoor /outdoor unit
power supplies.
77
OCS01-3.qxp
05.5.16 10:09 AM
Page 78
(3) Capacity correction
Cooling and heating capacity is lowered according to the piping length. Capacity can be obtained by referring
to the following capacity curves.
When the diameter of the gas pipe is smaller than the standard size, cooling capacity is lowered comparing to
the operation using the standard diameter pipe.
The lowered capacity can be obtained by referring to the capacity curves for gas pipe which is one or two size
smaller than standard size.
Corrected pipe length (m) = actual pipe length (m) + number of bends o 0.3 (m)
1. Capacity curves 1 <Standard size>
Cooling
Heating
100
Capacity ratio [%]
95
RP200,250
90
85
80
RP200,250
75
70
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110 115 120 125
Corrected pipe length [m]
2. Capacity curves 2 <When the gas pipe's diameter is one-size-smaller than the standard size>
100
Heating RP200([22.2), RP250([25.4)
Capacity ratio [%]
95
Cooling RP250([25.4)
90
85
80
Cooling RP200([22.2)
75
70
5
10
15
20
25
30
35
40
45
50
55
Corrected pipe length [m]
3. Capacity curves 3 <When the gas pipe's diameter is two-size-smaller than the standard size>
100
Cpacity ratio [%]
95
Heating RP200([19.05), RP250([22.2)
90
85
Cooling RP250([22.2)
80
Cooling RP200([19.05)
75
70
5
10
15
20
25
Corrected pipe length [m]
78
OCS01-3.qxp
05.5.16 10:09 AM
Page 79
8-2-2. SYNCHRONIZED TWIN, TRIPLE AND QUADRUPLE SYSTEM
(1) Synchronized twin
Maximum pipe length (Main pipe[A]+Branch pipe diameter [ B and C ])
Main pipe
(mm)[A]
Branch
pipe
[mm]
[B, C]
RP200 twin (RP100O2)
RP250 twin (RP125O2)
[9.52
[12.7
[15.88
[9.52
[12.7
[15.88
[19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75
Liquid pipe
Gas pipe
Liquid pipe
[6.35
Gas pipe
[12.7
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Normal
Normal
sw w2 sw
w2
sw
sw
piping
piping
20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70mw1 50m 50m 50m 50m
[15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[9.52
[9.52
w2
sw
sw
sw w2 sw
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[12.7
sw
sw
w2
sw w2 sw
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
(2) Synchronized triple
Maximum pipe length (Main pipe [A] + Branch pipe [ B, C and D ])
Main pipe
(mm)[A]
RP200 triple (RP60O3)
RP250 triple (RP71O3)
[9.52
[12.7
[15.88
[9.52
[12.7
[15.88
[19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75
Liquid pipe
Gas pipe
Liquid pipe
[6.35
Gas pipe
[12.7
Liquid pipe
Branch
pipe Gas pipe
[mm]
Liquid pipe
[B, C, D]
Gas pipe
Liquid pipe
Gas pipe
Normal
Normal
sw w2 sw
w2
sw
sw
piping
piping
20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70mw1 50m 50m 50m 50m
[15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[9.52
[9.52
w2
sw
sw
sw w2 sw
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[12.7
sw
sw
w2
sw w2 sw
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
(3) Synchronized quadruple
Maximum pipe length (Main pipe[A]+Branch pipe [ B, C, D and E ])
Main pipe
(mm)[A]
RP200 quadruple (RP50O4)
RP250 quadruple (RP60O4)
[9.52
[12.7
[15.88
[9.52
[12.7
[15.88
[19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75 [19.05 [22.2 [25.4 [28.58 [19.05 [22.2 [25.4 [28.58 [22.2 [25.4 [28.58 [31.75
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Branch
pipe Gas pipe
[mm]
Liquid pipe
[B, C, D, E]
Gas pipe
Liquid pipe
Gas pipe
Normal
sw w2 sw
sw
sw
piping
20m 50m 70mw1 70m 20m 50m 70m 70m 50m 50m 50m 50m
[12.7 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[6.35
Normal
w2
sw
sw
sw w2 sw
piping
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70mw1 50m 50m 50m 50m
[15.88 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[9.52
[9.52
sw
sw
w2
sw w2 sw
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m 20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[19.05 [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m] [20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
w2
20m 50m 70m 70m 20m 50m 70m 70m 50m 50m 50m 50m
[20m] [30m] [30m] [30m] [20m] [30m] [30m] [30m] [20m] [20m] [20m] [20m]
[12.7
[19.05
w1 The maximum pipe length is 80m in case of new pipping.
w2 When using [31.75 pipe, the outdoor temperature range (dry-bulb temperature) for heating operation is -11 to +21:.
<Marks in the table above>
SW : When the outdoor unit is located lower than
the indoor unit, set DIP SW8-1 on the outdoor
unit controller board to ON.
SW
70m
[30m]
: It can be used.
: Cooling capacity is lowered. Refer to <Table6>
: Additional refrigerant charge is required when
the pipe length exceeds 20m. Refer to <Table7>
The maximum pipe length
Charge-less pipe length
79
OCS01-3.qxp
05.5.16 10:09 AM
Page 80
Pipe diameter and thickness
OD
(mm) [6.35
Thickness
0.8
(mm)
[9.52
[12.7
0.8
0.8
[15.88 [19.05
1.0
[22.2
1.0
[25.4 [28.58
1.0
1.0
[31.75
1.0
1.1
Be sure to use hard (tempered) one for pipe over [22.2.(Do not use soft (annealed) one.)
4
B
4
D
4
E
1
Indoor unit
Outdoor unit
Main piping
Branch piping
Multi disttibution
pipe (option)
1 Height difference (Indoor unitOutdoor unit) Max. 40 m
2 Height difference (Indoor unitIndoor unit) Max. 8 m
3 Distance between indoor and indoor units
pipe length. Max. 8m
1
1
1
2
3
4
5
1
2
1
4
C
B—C B—D B—E
C—D C—E D—E
5
3
A
4 Number of pipe bends
Within 15
points8 points between main pipe A and
each branch pipe (B, C, D, E).
2
<Table 6> Lowered cooling capacity by the smaller gas pipe diameter
RP200 Cooling capacity ratio
gas pipe [22.2
gas pipe [19.05
100%
100%
100~96%
100~91%
96~91%
91~81%
91~86%
86~83%
83~80%
Pipe length
5m and less
6~10m
11~20m
21~30m
31~40m
41~50m
RP250 Cooling capacity ratio
gas pipe [25.4
gas pipe [22.2
100%
100%
100~98%
100~95%
98~94%
95~88%
94~91%
91~88%
88~86%
<Table 7> Additional refrigerant amount when the liquid pipe of the larger diameter is used.
(Single /Simultaneous Twin / Simultaneous Triple / Simultaneous Quadruple)
Capacity
When the extension pipe length (main piping + branch piping) exceeds 20m
Additional refrigerant amount W(g)=(180oL1)+(120oL2) (90oL3)+(30oL4)-3000
RP200, RP250
L1 : [15.88 liquid pipe (m)
L3 : [9.52 liquid pipe (m)
L2 : [12.7 liquid pipe (m)
L4 : [6.35 liquid pipe (m)
If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary.
( W [ 0)
<Table 8>
Outdoor unit
Permissible total
piping length
A+B+C+D+E
A+B or A+C
or
A+D or A+E
Charge-less
piping length
A+B+C+D+E
RP200
PR250
120 m and less
100 m and less
30 m and less
<Table 9>
Outdoor unit
B-C or B-D or
B-E or C-D or
C-E or D-E
RP200
RP250
8 m and less
Number of
pipe bends
Within 15
80
OCS01-3.qxp
05.5.16 10:09 AM
Page 81
<Table 10>
Outdoor unit
RP200
RP250
permitted
pipe length
120m or less
At time of shipping
(kg)
10.5
A+B+C+D
30 m and less
No additional
charge necessary
10.5
Amount of additional refrigerant charge (kg)
31-40 m and less 41-50 m and less 51-60 m and less 61-70 m and less 71-120 m and less
The additional charge
0.9 kg
1.8 kg
2.7 kg
3.6 kg
1.2 kg
2.4 kg
3.6 kg
4.8 kg
amount is obtained by
the following formula.
When length exceeds 70 m
When the total length of the piping exceeds 70 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the
“Additional charge amount for 70 m,”perform the additional charge using the amount shown in “Additional charge amount for 70 m.”
Amount of additional
charge
Main piping:
= Liquid line size
[12.7 overall length
0.12
+
Main piping:
Liquid line size
[9.52 overall length
0.09 (Gas line:[28.58)
Branch piping: Liquid
Branch piping: Liquid
+ line size
+ line size
[9.52 overall length
[6.35 overall length
0.06 (Gas line: [15.88)
0.02 (Gas line: [15.88)
–
3.6 (kg)
Additional charge amount RP200 3.6 kg
for 70 m
RP250 4.8 kg
1. Perform refrigerant piping connections for the indoor / outdoor unit while the outdoor unit's stopvalve is completely
closed (factory setting), and then vacuumize the refrigerant lines through the service port of the outdoor unit.
2. Open the stop valves of the outdoor unit completely.
This will completely connects the refrigerant lines of the indoor and outdoor units.
Handling of the stop valve is shown on the outdoor unit.
Note :
· Apply refrigerating machine oil over the flare seat surface. Do not apply to the threaded portion.
(It will cause the flare nut to loosen.)
· Use two wrenches to tighten piping connection.
· Use leak detector or soapy water to check for gas leaks after connections are completed.
· For the insulation of the connection at the indoor side, make sure to use the attached insulation materials and
thoroughly follow the instruction shown in the manual.
· Always use a non-oxidizing brazing material when brazing the pipes.
Adjusting the amount of refrigerant
Check additional refrigerant charging amount referring to the procedure 2 below when the liquid pipe diameter of the main
piping A is larger than the standard size.
1 When the standard diameter pipe is used for the main piping A, calculate the additional refrigerant amount by
referring to <Table 2> as well as the 1:1 system.
2 When the liquid pipe diameter of the main piping A is one size larger than the standard size:
· When the extension pipe length (main piping + branch piping) does not exceeds 20m, adjustment of the
refrigerant is not necessary (charge-less).
· When the extension pipe length (main piping + branch piping) exceeds 20m, charge the amount of refrigerant
that is obtained by the formula shown in <Table 7>.
If the calculation produces a negative number (i.e. a "minus" charge), additional charging is not necessary.
Note: Apply 0 to L1 to L3 corresponding to the piping that are not used.
Correcting the capacity value
When calculating the lowered capacity by the extension pipe length, use the longest length between the indoor and the outdoor
units.
81
OCS01-3.qxp
9
05.5.16 10:09 AM
Page 82
AIR FLOW DATA
9-1. OUTLET AIR SPEED AND COVERAGE RANGE
Air flow
Air speed
Coverage range
m3/min.
m/sec.
m
PLA-RP35AA
14
2.8
4.0
Air flow
Air speed
Coverage range
m3/min
m/sec
m
Air flow
Air speed
Coverage range
m3/min
Air flow m3/min
Air speed m/sec
Coverage range m (ft)
Air flow m3/min
Air speed m/sec
Coverage range m (ft)
Air flow
Air speed
Coverage range
m/sec
m
PLA-RP50AA
18
3.6
5.2
PLA-RP60AA
18
3.6
5.2
PLA-RP71AA
20
4.0
5.7
PLA-RP125AA
30
6.6
8.9
PLA-RP140AA
30
6.6
8.9
PCA-RP50GA PCA-RP60GA PCA-RP71GA PCA-RP100GA PCA-RP125GA PCA-RP140GA
34
34
18
13
25
18
4.4
4.4
3.8
3.7
4.1
3.8
15.2
15.2
10.4
8.8
12.6
10.4
PCA-RP71HA PCA-RP125HA
38
19
4.2
2.9
7.9
13.2
PKA-RP35GAL
PKA-RP50GAL
12
12
5.3
5.3
10(32.8)
10(32.8)
PKA-RP60FAL
PKA-RP71FAL
PKA-RP100FAL
20
20
28
4.9
4.9
5.4
12.4(40.7)
12.4(40.7)
15.3(50.2)
m3/min
m/sec
m
PLA-RP100AA
28
4.9
7.4
PSA-RP71GA
18
2.6
8.3
PSA-RP100GA
31
4.5
14.3
PSA-RP125GA
33
4.8
15.2
PSA-RP140GA
35
4.9
16.1
The air coverage range is the value up to the position where the air speed is 0.25m/sec. when air is blown out horizontally from
the unit at the Hi notch position.
The coverage range should be used only as a general guideline since it varies according to the size of the room and the furniture inside the room.
82
OCS01-3.qxp
05.5.16 10:09 AM
Page 83
9-2. PLA-RP·AA
9-2-1. FRESH AIR INTAKE AMOUNT
83
OCS01-3.qxp
05.5.16 10:09 AM
Page 84
84
OCS01-3.qxp
05.5.16 10:09 AM
Page 85
9-2-2. BRANCH DUCT (Installation at site)
85
OCS01-3.qxp
05.5.16 10:09 AM
Page 86
Branch duct air flow rate/static pressure characteristics
PLA-RP35AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
86
OCS01-3.qxp
05.5.16 10:09 AM
Page 87
PLA-RP50AA
PLA-RP60AA
4-way air flow (horizontal vane) Rectangular duct
4-way air flow (horizontal vane) Round duct
3-way air flow (horizontal vane) Rectangular duct
3-way air flow (horizontal vane) Round duct
2-way air flow (horizontal vane) Rectangular duct
2-way air flow (horizontal vane) Round duct
87
OCS01-3.qxp
05.5.16 10:09 AM
Page 88
PLA-RP71AA
4-way air flow (horizontal vane) Round duct
Static pressure [Pa]
30
20
High
10
Low
0
1
2
3
4
5
6
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
30
20
High
10
Low
0
1
2
3
Air flow rate [m3/min]
3-way air flow (horizontal vane) Rectangular duct
6
60
50
Static pressure [Pa]
Static pressure [Pa]
5
3-way air flow (horizontal vane) Round duct
60
40
High
30
20
Low
10
50
40
1
2
3
4
5
6
7
8
9
High
30
20
Low
10
0
0
1
2
3
4
Air flow rate [m /min]
2-way air flow (horizontal vane) Rectangular duct
5
6
7
2-way air flow (horizontal vane) Round duct
100
100
90
90
80
Static pressure [Pa]
80
70
60
High
50
40
Low
30
20
10
70
60
50
High
40
Low
30
20
10
0
1
2
3
4
5
6
7
8
9
10
8
Air flow rate [m3/min]
3
Static pressure [Pa]
4
Air flow rate [m3/min]
11
0
Air flow rate [m3/min]
1
2
3
4
5
6
Air flow rate [m3/min]
88
7
9
05.5.16 10:09 AM
Page 89
PLA-RP100AA
4-way air flow (horizontal vane) Round duct
50
Static pressure [Pa]
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
40
30
High
20
Low
10
0
1
2
3
4
5
6
7
8
9
50
40
30
High
20
Low
10
0
10
1
2
3
4
5
Air flow rate [m /min]
3
7
8
9
10
3-way air flow (horizontal vane) Round duct
100
100
90
90
Static pressure [Pa]
Static pressure [Pa]
6
Air flow rate [m3/min]
3-way air flow (horizontal vane) Rectangular duct
80
70
60
High
50
40
30
Low
20
10
80
70
60
50
High
40
30
Low
20
10
0
1
2
3
4
5
6
7
8
9
10
11
12
13
0
14
1
Air flow rate [m3/min]
110
100
100
90
90
Static pressure
120
110
80
High
60
50
Low
40
30
50
4
5
6
7
8
9
10
11
12
13
14
15
7
8
9
10
11
12
13
14
High
40
Low
30
10
3
6
60
10
2
5
70
20
1
4
80
20
0
3
2-way air flow (horizontal vane) Round duct
120
70
2
Air flow rate [m3/min]
2-way air flow (horizontal vane) Rectangular duct
Static pressure [Pa]
OCS01-3.qxp
0
16
1
Air flow rate [m /min]
3
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Air flow rate [m3/min]
89
16
OCS01-3.qxp
05.5.16 10:09 AM
Page 90
PLA-RP125AA
PLA-RP140AA
4-way air flow (horizontal vane) Round duct
50
50
40
30
High
20
Low
10
0
1
2
3
4
5
6
7
8
9
10
Static pressure [Pa]
Static pressure [Pa]
4-way air flow (horizontal vane) Rectangular duct
40
30
High
20
10
Low
0
1
2
3
4
5
100
100
90
90
80
70
60
High
40
Low
20
10
0
9
10
80
70
60
50
High
40
30
Low
20
10
1
2
3
4
5
6
7
8
9
10
11
12
13
0
14
1
2
3
4
5
6
Air flow rate [m /min]
3
2-way air flow (horizontal vane) Rectangular duct
120
110
110
100
100
90
80
70
High
50
40
Low
30
8
9
10
11
12
13
14
2-way air flow (horizontal vane) Round duct
120
60
7
Air flow rate [m3/min]
Static pressure[Pa]
Static pressure [Pa]
8
3-way air flow (horizontal vane) Round duct
Static pressure [Pa]
Static pressure [Pa]
3-way air flow (horizontal vane) Rectangular duct
30
7
Air flow rate [m /min]
Air flow rate [m /min]
50
6
3
3
20
10
90
80
70
60
50
High
40
Low
30
20
10
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
16
1
Air flow rate [m3/min]
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Air flow rate [m3/min]
90
16
05.5.16 10:13 AM
Page 91
9-2. PEAD-RP·EA, GA
9-2-1. FAN PERFORMANCE AND CORRECTED AIR FLOW
Fan Performance <30Pa>
100
Corrected Air Flow
80
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
PEAD-RP35EA
60
40
20
6
8 10 12 14 16
Air Flow (CMM)
1.0
0.9
0.8
10
Fan Performance <70Pa>
12 14 16 18
Air flow (CMM)
20
Heating
1.3
120
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
Capacity
input
Cooling
1.1
140
100
80
60
40
1.2
1.1
1.0
0.9
0.8
20
6
8
10 12 14 16 18
Air flow (CMM)
8 10 12 14 16 18
Air Flow (CMM)
PEAD-RP50EA
Fan Performance <30Pa>
Corrected Air Flow
120
Correction factor
100
80
60
40
20
1.1
6
160
8
1.0
0.9
0.8
10
10 12 14 16 18 20
Air Flow (CMM)
Fan Performance <70Pa>
12 14 16 18
Air flow (CMM)
20
22
12 14 16 18
Air flow (CMM)
20
22
Heating
1.3
140
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
20
8
Capacity
input
Cooling
8
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
140
External static pressure (Pa)
(1Pa 0.1mmAq)
OCS01-4.qxp
10 12 14 16 18 20 22
Air Flow (CMM)
91
8
10
05.5.16 10:13 AM
Page 92
Fan Performance <30Pa>
120
100
80
60
40
20
8
Capacity
input
Corrected Air Flow
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
PEAD-RP60EA
1.1
Cooling
1.0
0.9
0.8
12 14 16 18 20 22
Air flow (CMM)
24 26
10 12 14 16 18 20 22 24
Air Flow (CMM)
Heating
Fan Performance <70Pa>
1.3
Correction factor
External static pressure (Pa)
(1Pa 0.1mmAq)
140
120
100
80
60
40
1.2
1.1
1.0
0.9
0.8
12 14 16 18 20 22 24
Air flow (CMM)
20
10 12 14 16 18 20 22 24 26
Air Flow (CMM)
PEAD-RP71EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
Hi
Lo
120
100
80
60
40
20
180
160
140
120
Hi
Lo
100
80
60
40
20
12 16 20 24 28 32
12 16 20 24 28 32
A i r fl ow (C MM)
A i r fl o w (C M M )
Corrected Air Flow
Capacity
Input
Cooling
Heating
1.3
1.1
Correction factor
1.2
Correction factor
OCS01-4.qxp
1.0
0.9
0.8
12
16
20
24
28
1.1
1.0
0.9
32
Air flow (CMM)
0.8
12
16
20
24
28
Air flow (CMM)
92
32
26
05.5.16 10:13 AM
Page 93
PEAD-RP100EA
Fan performance <70Pa>
Recommended range
Fan performance <130Pa>
220
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
120
Hi
100
80
60
Lo
40
20
200
180
160
140
120
80
60
Lo
40
20
24 26 28 30 32 34 36 38
A i r fl o w (C MM)
A i r fl ow (C MM )
Corrected Air Flow
Cooling
1.0
0.9
Heating
1.2
Correction factor
Capacity
Input
1.1
Correction factor
Hi
100
26 28 30 32 34 36 38 40
1.1
1.0
0.9
0.8
0.8
24
26
28
30
32
34
36
38
24
40
26
28
30
32
34
36
38
40
Air flow (CMM)
Air flow (CMM)
PEAD-RP125EA
Fan performance <70Pa>
Fan performance <130Pa>
Recommended range
220
External static pressure (Pa)
(1Pa = 0.1mmAq)
External static pressure (Pa)
(1Pa = 0.1mmAq)
Recommended range
200
180
160
140
120
100
Hi
80
60
Lo
40
20
220
200
180
160
140
120
100
32 34 36 38 40 42 44 46 48
60
40
A i r fl ow (C MM )
Heating
1.2
Correction factor
Capacity
Input
Cooling
1.1
1.0
0.9
34
36
Lo
20
32 34 36 38 40 42 44 46
Corrected Air Flow
0.8
32
Hi
80
A i r fl o w (C M M )
Correction factor
OCS01-4.qxp
38
40
42
44
46
48
Air flow (CMM)
1.1
1.0
0.9
0.8
32
34
36
38
40
42
44
Air flow (CMM)
93
46
48
05.5.16 10:13 AM
Page 94
PEAD-RP140EA
Fan performance <70Pa>
Recommended range
External static pressure (Pa)
220
(1Pa = 0.1mmAq)
External static pressure (Pa)
Recommended range
200
180
160
140
120
100
80
60
40
Hi
Lo
200
(1Pa = 0.1mmAq)
Fan performance <130Pa>
180
160
140
120
100
80
Hi
60
Lo
40
20
20
36 38 40 42 44 46 48 50 52
36 38 40 42 44 46 48 50
Ai r fl o w (C M M )
A i r fl ow (C MM)
Heating
Corrected Air Flow
1.2
Capacity
Input
Cooling
1.1
Correction factor
Correction factor
OCS01-4.qxp
1.0
0.9
0.8
36
38
40
42
44
46
48
50
52
1.1
1.0
0.9
0.8
36
38
40
42
44
46
Air flow (CMM)
Air flow (CMM)
94
48
50
52
OCS01-4.qxp
05.5.16 10:13 AM
Page 95
PEAD-RP60GA
PEAD-RP71GA
95
OCS01-4.qxp
05.5.16 10:13 AM
Page 96
PEAD-RP100GA
96
05.5.16 10:13 AM
Page 97
9-3.PEA-RP·EA
FAN PERFORMANCE AND CORRECTED AIR FLOW
(1) PEA-RP71EA
Corrected Air flow
Capacity
Input
Cooling
1.05
Correction factor
Fan Performance
Recommended range
Hi
150
1.0
0.95
0.9
17 20
1.2
100
50
0
15 17 20
25
30
Air flow (CMM)
Lo
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
200
25
30
35
Heating
1.15
1.1
1.05
1.0
Air flow (CMM)
0.95
17 20
25
30
Air flow (CMM)
(2) PEA-RP100EA
Corrected Airflow
Cooling
Fan Performance
Correction factor
1.05
Recommended range
200
Hi
150
1.0
0.95
0.9
20 23 25
30
35
40
Air flow (CMM)
100
Lo
1.15
0
Capacity
Input
Heating
1.1
50
20 23 25
30
35
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
OCS01-4.qxp
40
Air flow (CMM)
1.05
1.0
0.95
20 23 25
30
Air flow (CMM)
97
35
40
OCS01-4.qxp
05.5.16 10:13 AM
Page 98
From the previous page.
(3) PEA-RP125EA
Corrected Air flow
Cooling
1.05
Correction factor
Fan Performance
Recommended range
Hi
150
1.0
0.95
0.9
28 30
100
25 28 30
40
45
35
40
45
50
Air flow (CMM)
1.1
1.05
1.0
0.95
28 30
35
40
45
Air flow (CMM)
(4) PEA-RP140EA
Corrected Air flow
Cooling
Correction factor
Fan Performance
150
Lo
Hi
100
Air flow (CMM)
50
Capacity
input
Heating
44 45
55
65
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
Recommended range
200
0
35
50
Capacity
Input
Heating
1.15
50
0
35
Air flow (CMM)
Lo
Correction factor
External static pressure(Pa)
(1Pa = 0.1mmAq)
200
75
Air flow (CMM)
Air flow (CMM)
98
50
05.5.16 10:13 AM
Page 99
9-4.PEH-RP·MYA
[1] Capacity/Input Ratio against Changes in Room Airflow Rate
•Model
PEH-RP200MYA
Heating
Cooling
1.05
1.05
Capacity/Input ratio
Capacity/Input ratio
Input
1.0
1.0
Input
Capacity
Capacity
0.95
50
55
•Model
60
Airflow rate (m3/min)
65
70
0.95
50
55
60
Airflow rate (m3/min)
65
70
PEH-RP250MYA
Heating
Cooling
1.05
1.05
Capacity/Input ratio
Capacity/Input ratio
Input
1.0
Input
Capacity
0.95
70
75
80
Airflow rate (m3 /min)
85
90
1.0
Capacity
0.95
70
75
80
Airflow rate (m3 /min)
85
90
[2] Airflow Characteristic Curves
PEH-RP250MYA
PEH-RP200MYA
Operating airflow range
Operating airflow range
220
220
200
200
External static pressure (Pa)
External static pressure (Pa)
OCS01-4.qxp
150
100
50
0
40
50
60
Airflow rate (m3/min)
70
80
99
150
100
50
0
60
70
80
Airflow rate (m3/min)
90
100
OCS01-4.qxp
10
05.5.26 10:48 AM
Page 100
NOISE CRITERION CURVES
NOTCH SPL(dB)
High
31
Medium1
29
Medium2
28
Low
27
PLA-RP35AA
LINE
PLA-RP50AA
PLA-RP60AA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
250
500
1000
2000
4000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
500
LINE
1000
2000
4000
NOTCH SPL(dB)
High
41
Medium1
39
Medium2
36
Low
33
PLA-RP100AA
90
8000
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
250
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
34
Medium1
32
Medium2
30
Low
28
PLA-RP71AA
NC-20
10
8000
BAND CENTER FREQUENCIES, Hz
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
20
NOTCH SPL(dB)
High
33
Medium1
31
Medium2
29
Low
28
250
500
1000
2000
4000
8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
BAND CENTER FREQUENCIES, Hz
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
100
4000
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 101
NOTCH SPL(dB)
45
High
43
Medium1
40
Medium2
37
Low
PLA-RP125AA
LINE
PLA-RP140AA
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
20
NOTCH SPL(dB)
45
High
43
Medium1
40
Medium2
37
Low
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
63
125
250
BAND CENTER FREQUENCIES, Hz
500
1000
2000
BAND CENTER FREQUENCIES, Hz
UNIT
CEILING
1.5m
MICROPHONE
101
4000
8000
05.5.16 10:13 AM
Page 102
(External static
pressure 30Pa)
PEAD-RP35EA
70
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
PEAD-RP35EA
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
63
125
250
500
1000
2000
4000
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
8000
63
(External static
pressure 30Pa)
High
Low
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
63
125
250
500
1000
2000
4000
(External static
pressure 30Pa)
NC60
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
250
500
1000
2000
4000
8000
(External static
pressure 70Pa)
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
125
250
500
PEAD-RP60EA
50
125
4000
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES (Hz)
High
Low
63
2000
High
Low
63
60
0
1000
60
8000
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
PEAD-RP60EA
500
70
OCTAVE BAND CENTER FREQUENCIES (Hz)
70
250
PEAD-RP50EA
60
0
125
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
PEAD-RP50EA
70
(External static
pressure 70Pa)
70
OCTAVE BAND CENTER FREQUENCIES (Hz)
OCTAVE BAND PRESSURE LEVEL (dB) 0dB = 20µPa
OCS01-4.qxp
8000
70
High
Low
60
NC60
50
NC50
40
NC40
30
NC30
20
NC20
10
Approximate minimum
audible limit on
continuous noise
0
63
OCTAVE BAND CENTER FREQUENCIES (Hz)
(External static
pressure 70Pa)
125
250
500
1000
2000
4000
OCTAVE BAND CENTER FREQUENCIES (Hz)
102
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 103
103
OCS01-4.qxp
05.5.16 10:13 AM
PEA-RP71EA
Page 104
NOTCH SPL(dB)
High
55
Low
52
LINE
PEA-RP100EA
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
NC-20
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
PEA-RP125EA
NOTCH SPL(dB)
High
58
Low
54
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
8000
63
NC-20
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
90
80
70
NC-70
UNIT
1m
60
NC-60
1m
50
NC-50
MICROPHONE
40
NC-40
30
NC-30
20
10
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
90
NOTCH SPL(dB)
High
58
Low
54
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
NC-20
8000
104
External static
pressure 125Pa
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 105
PEA-RP140EA
NOTCH SPL(dB)
High
55
Low
51
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROTIMATE
TERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
UNIT
CEILING
1.5m
MICROPHON
105
OCS01-4.qxp
05.5.16 10:13 AM
Page 106
PEH-RP200MYA
70
Measurement condition
Aux. duct
2m
1.5m
1m
Measured point
OCTAVE BAND PRESSURE LEVEL <dB> 0dB = 20µPa
External static pressure: 50Pa
External static pressure: 150Pa
60
NC60
50
NC50
40
NC40
30
NC30
20
Approximate minimum
audible limit on
continuous noise
10
63
125
250
NC20
500
1000
2000
4000
8000
OCTAVE BAND CENTER FREQUENCIES <Hz>
PEH-RP250MYA
70
Measurement condition
Aux. duct
2m
1.5m
1m
Measured point
OCTAVE BAND PRESSURE LEVEL <dB> 0dB = 20µPa
External static pressure: 50Pa
External static pressure: 150Pa
60
NC60
50
NC50
40
NC40
30
NC30
20
Approximate minimum
audible limit on
continuous noise
10
63
125
250
NC20
500
1000
2000
OCTAVE BAND CENTER FREQUENCIES <Hz>
106
4000
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 107
PKA-RP35GAL
PKA-RP50GAL
NOTCH SPL(dB)
High
43
Medium1
41
38
Medium2
Low
36
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0dB=0.0002 µbar)
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
UNIT
WALL
1m
1m
MICROPHONE
107
OCS01-4.qxp
05.5.16 10:13 AM
PKA-RP60FAL
PKA-RP71FAL
Page 108
NOTCH SPL(dB)
High
45
Low
39
PKA-RP100FAL
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB(0dB=0.0002 µ bar)
LINE
90
90
20
NOTCH SPL(dB)
High
46
Low
41
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
10
63
125
250
500
1000
2000
4000
63
8000
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
UNIT
WALL
1m
1m
MICROPHONE
108
4000
8000
05.5.16 10:13 AM
Page 109
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PCA-RP50GA
NOTCH SPL(dB)
42
High
40
Medium1
38
Medium2
37
Low
PCA-RP60GA
PCA-RP71GA
LINE
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCS01-4.qxp
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
NC-20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
250
500
1000
2000
4000
63
8000
125
PCA-RP100GA
NOTCH SPL(dB)
High
45
Medium1
43
Medium2
41
Low
40
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
500
1000
2000
2000
4000
8000
4000
NOTCH SPL(dB)
High
46
Medium1
45
Medium2
43
Low
41
LINE
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
250
1000
70
NC-20
10
125
500
PCA-RP125GA
LINE
90
63
250
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NC-20
10
10
20
LINE
70
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NOTCH SPL(dB)
High
43
Medium1
41
Medium2
39
Low
37
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
8000
63
BAND CENTER FREQUENCIES, Hz
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
109
4000
8000
OCS01-4.qxp
05.5.16 10:13 AM
PCA-RP140GA
Page 110
NOTCH SPL(dB)
High
48
Medium1
46
Medium2
44
Low
42
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
ceiling
1m
1m
about 1.4m
unit
MICROPHONE
110
05.5.16 10:13 AM
Page 111
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
PCA-RP71HA
NOTCH SPL(dB)
High
38
Low
34
PCA-RP125HA
LINE
90
90
80
80
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
OCS01-4.qxp
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
NC-20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
10
63
125
250
500
1000
2000
4000
63
8000
ceiling
1m
about 1.4m
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
1m
LINE
70
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NOTCH SPL(dB)
High
50
Low
44
unit
MICROPHONE
111
4000
8000
OCS01-4.qxp
05.5.16 10:13 AM
NOTCH SPL(dB)
45
High
40
Low
LINE
PSA-RP100GA
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
PSA-RP71GA
Page 112
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
125
250
500
1000
2000
4000
8000
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
PSA-RP125GA
NC-20
NOTCH SPL(dB)
High
51
Low
46
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
125
250
500
1000
2000
BAND CENTER FREQUENCIES, Hz
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
NC-70
10
63
20
LINE
70
NC-20
10
NOTCH SPL(dB)
High
49
Low
44
4000
8000
BAND CENTER FREQUENCIES, Hz
112
4000
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 113
PSA-RP140GA
NOTCH SPL(dB)
High
52
Low
47
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 µBAR
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
HERESHOLD OF
REARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
MICROPHONE
1m
1m
about 1.4m
unit
floor
113
OCS01-4.qxp
05.5.16 10:13 AM
Page 114
MICROPHONE
1m
UNIT
1.5m
GROUND
MODE SPL(dB)
COOLING
44
HEATING
46
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
PUHZ-RP60VHA
PUHZ-RP71VHA
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PUHZ-RP35VHA
PUHZ-RP50VHA
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
125
NC-20
250
500
1000
2000
4000
8000
BAND CENTER FREQUENCIES, Hz
PUHZ-RP125VHA
PUHZ-RP140VHA
PUHZ-RP125YHA
PUHZ-RP140YHA
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MODE SPL(dB)
COOLING
49
HEATING
51
LINE
90
BAND CENTER FREQUENCIES, Hz
PUHZ-RP100VHA
PUHZ-RP100YHA
MODE SPL(dB)
COOLING
47
HEATING
48
8000
BAND CENTER FREQUENCIES, Hz
MODE SPL(dB)
COOLING
50
HEATING
52
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
114
LINE
8000
OCS01-4.qxp
05.5.16 10:13 AM
Page 115
MICROPHONE
UNIT
1m
1m
GROUND
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
MODE SPL(dB)
COOLING 58.0
HEATING 58.0
PUHZ-RP250YHA
8000
BAND CENTER FREQUENCIES, Hz
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
MODE SPL(dB)
COOLING 55.0
HEATING 56.0
PUHZ-RP200YHA
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
115
LINE
8000
OCS01-4.qxp
11
05.5.16 10:13 AM
Page 116
OPTIONAL PARTS
11-1. INDOOR UNIT
Part Name
Model Name
Remote sensor
Remote operation adapter
Remote on/off adapter
Power supply terminal kit
L/N/Earth
PAC-SE41TS-E
PAC-SF40RM-E
PAC-SE55RA-E
PAC-SG96HR-E
L/N
PAC-SG97HR-E
Multi-functional casement
High-efficiency filter element
(PAC-SG03TM-E is needed.)
Grille + Wireless remote controller
Grille + Wired remote controller
Air outlet shutter plate
(20 set, 2pcs/set)
Wireless remote controller + Wireless Adapter
Drain lift up mechanism
High-efficiency filter
Duct flange for fresh air
Filter element
Decoration cover
(Front + Suspending bracket cover)
Wired remote controller
(with terminal bed)
Drain lift up mechanism
Motor
(for high external static pressure)
Drain lift up mechanism
Insulation kit
Wiring kit
Applicable model
All models
All models
except PCA-RP·HA,
PEAD-RP·GA, PEH-RP·MYA
PCA-RP·HA
PEAD-RP·GA
PAC-SG03TM-E
PAC-SG01KF
PLP-6AALM
PLP-6AAMD
PAC-SG06SP-E
PLA-RP·AA
PAR-SL99B-E
PAC-SH20DM-E
PAC-SH21DM-E
PAC-SH22DM-E
PAC-SE80KF-E
PAC-SE81KF-E
PAC-SE82KF-E
PAC-SF28OF-E
PAC-SG38KF-E
PAC-SF81KC-E
PAC-SF82KC-E
PAR-21MAAT-E
PCA-RP·GA
PCA-RP50,60GA
PCA-RP71GA
PCA-RP100,125,140GA
PCA-RP50GA
PCA-RP60,71,100GA
PCA-RP125,140GA
PCA-RP·HA
PAC-SE90DM-E
PAC-SK005MT-F
PAC-SK004MT-F
PAC-SK003MT-F
PAC-KE03DM-F
PAC-SK010DK
PAC-SK020EC
116
PCA-RP71HA
PCA-RP125HA
PKA-RP·GAL
PKA-RP·FAL
PKA-RP·FAL
PEAD-RP71EA
PEAD-RP100EA
PEAD-RP125,140EA
PEAD-RP·EA
PEAD-RP·GA
OCS01-4.qxp
05.5.16 10:13 AM
Page 117
11-2. OUTDOOR UNIT
Part Name
Model Name
Applicable model
M-NET adapter
PAC-SF70MA-E
All models
A-control service tool
PAC-SK52ST
Drain socket
PAC-SG61DS-E
PUHZ-RP35-140
Air outlet guide
PAC-SG58SG-E
PUHZ-RP35, 50
(RP100,125,140 needs two piece.)
PAC-SG59SG-E
PUHZ-RP60-140
Air protect guide
PAC-SG56AG-E
PUHZ-RP35, 50
PAC-SG57AG-E
PUHZ-RP60-140
Front, Rear
PAC-SG86AG-E
PUHZ-RP200, 250
Left, Right
PAC-SG87AG-E
Drain pan
Filter dryer
Distribution pipe
Joint pipe
(Unit
Extension pipe)
PAC-SG63DP-E
PUHZ-RP35, 50
PAC-SG64DP-E
PUHZ-RP60-140
PAC-SF60MA-E
PUHZ-RP200, 250
( [6.35)
PAC-SG81DR-E
PUHZ-RP35, 50
( [9.52)
PAC-SG82DR-E
PUHZ-RP60-200
( [12.7)
PAC-SG85DR-E
PUHZ-RP250
(Twin)
MSDD-50SR-E
PUHZ-RP100-140
MSDD-50WR-E
PUHZ-RP200, 250
(Triple)
MSDT-111R-E
PUHZ-RP140-250
(Quadruple)
MSDF-1111R-E
PUHZ-RP200, 250
( [6.35
[9.52)
PAC-SG72RJ-E
PUHZ-RP35, 50
( [9.52
[12.7)
PAC-SG73RJ-E
PUHZ-RP35, 50, 200
PAC-SG75RJ-E
PUHZ-RP60-140
PAC-SG92DS-E
PUHZ-RP200, 250
( [15.88
Centralized drain kit
[19.05)
117
OCS01-4.qxp
05.5.16 10:13 AM
Page 118
TM
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
CCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in May 2005 No.OCS01 PDF8
Made in Japan.
New publication, effective May 2005.
Specifications subject to change without notice.