RZQ-B
Pair/Twin/Triple/Double Twin
Application, Inverter
Controlled Unit
Split
Sky Air
air conditioning systems
technical data
Split - Sky Air
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the environment
Daikin units comply with the European
regulations that guarantee the safety of
the product.
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
Daikin Europe N.V. participates in the Eurovent Certification
Programme for Air Conditioners (AC), Liquid Chilling Packages
(LCP) and Fan Coil Units (FC); the certified data of certified
models are listed in the Eurovent Directory.
Zandvoordestraat 300
B - 8400 Ostend Belgium
www.daikineurope.com
EEDE05-1/3 • 05/2005
Prepared in Belgium by Goekint Graphics
Specifications are subject to change without prior notice.
• Outdoor Units • R410A • RZQ-B
TABLE OF CONTENTS
RZQ-B
1
2
Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3
Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6
Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Dimensional drawings and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
8
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
9
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Refnet pipe systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Service space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
11
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• Split Sky Air • Outdoor Units
1
• Outdoor Units • R410A • RZQ-B
o t o aB i d 0- l t 1Q pu4Z 1
SOR
Features
2
1
2
•
Outdoor units for pair application
•
The Sky Air Inverter is developed for use in shops, restaurants and small
offices. This innovative Daikin unit provides a more comfortable
environment and offers great savings in energy consumption to shop
and office owners.
•
During start up, the room can be cooled down or heated very quickly.
Once the temperature in the room has reached its set point, the low
power operation starts to save energy.
•
Daikin outdoor units are neat and sturdy and can be mounted easily on
a roof or terrace or simply placed against an outside wall.
•
The use of inverter type outdoor units results in an air conditioning
system with a high energy efficiency and very low sound level
•
Outdoor units are fitted with either a swing or scroll compressor,
renowned for low noise and high energy efficiency
•
An inverter driven compressor allows the capacity to be adjusted
precisely to match variations in room and outside temperatures.
•
A special acryl precoated fin for anti-corrosion treatment on the heat
exchanger ensures greater resistance against severe weather conditions
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
2
Specifications
2
2-1 TECHNICAL SPECIFICATIONS
Casing
Dimensions
Daikin white
Painted galvanized steel plate
Packing
Height
mm
900
1475
1475
1475
mm
980
980
980
980
Depth
mm
420
420
420
420
Height
mm
770
1345
1345
1345
Width
mm
900
900
900
900
Depth
mm
320
320
320
320
kg
68
106
106
106
kg
72
111
111
111
mm
857
857
857
857
2
2
2
2
mm
1.40
1.40
1.40
1.40
3
5
5
5
m2
0.641
1.131
1.131
1.131
34
60
60
60
Machine Weight
Dimensions
Length
Fin Pitch
Nr of Passes
Face Area
Nr of Stages
Tube type
Fin
Type
WF fin
Anti-corrosion treatment (PE)
Type
Propeller
Discharge direction
Horizontal
Quantity
1
2
2
2
Air Flow Rate
(nominal)
Cooling
m3/min
54.50
103.0
103.0
99.0
Heating
m3/min
48.10
101.0
101.0
100.0
Motor
Quantity
1
2
2
2
Model
Fan
Compressor
Speed (nominal
at 230V)
Motor
KFD-325-70-8A
Steps
8
8
8
8
Cooling
rpm
818
789
789
782
Heating
rpm
715
775
775
767
Output
W
70
70
70
70
Drive
direct drive
1
1
1
1
Model
2YC63BXD
JT100G-VD
JT1G-VDYR@T
JT100G-VD
Type
Hermetically sealed swing
compressor
Quantity
Motor
Motor
Output
W
Hermetically sealed scroll compressor
1800
2200
2200
2200
_
33
33
33
-15.0
Starting Method
Inverter driven
Crankcase
Heater
W
Min
°CDB
-15.0
-15.0
-15.0
Max
°CDB
50.0
50.0
50.0
50.0
Heating
Min
°CWB
-20.0
-20.0
-20.0
-20.0
Max
°CWB
15.5
15.5
15.5
15.5
Cooling
Sound
Power
dBA
63.0
65.0
65.0
66.0
Sound
Pressure
dBA
47.0
49.0
49.0
50.0
Heating
Sound
Pressure
dBA
49.0
51.0
51.0
52.0
Sound Level
(Night quiet)
Cooling
Sound
Pressure
dBA
43.0
45.0
45.0
45.0
Refrigerant
Type
kg
2.80
4.30
4.30
4.30
Operation Range Cooling
Sound Level
(nominal)
Charge
R-410A
Control
Nr of Circuits
2
Hi-XSS(8)
Treatment
Motor
RZQ125B8V3B
Width
Nr of Rows
Fan
RZQ100B7W1B
Colour
Gross Weight
Heat Exchanger
RZQ100B8V3B
Material
Unit
Weight
RZQ71B8V3B
Expansion valve (electronic type)
1
• Split Sky Air • Outdoor Units
1
1
1
3
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS
Refrigerant Oil
RZQ71B8V3B
Type
Charged Volume
2
Piping
connections
Liquid (OD)
RZQ100B8V3B
l
Quantity
0.8
1.0
1.0
1.0
1
1
1
1
9.52
9.52
1
1
Flare connection
Diameter
(OD)
Gas
mm
Quantity
9.52
9.52
1
1
Type
Flare connection
Diameter
(OD)
Drain
mm
Quantity
Type
Piping Length
RZQ125B8V3B
Daphne FVC68D
Type
2
RZQ100B7W1B
Daphne FVC50K
15.9
15.9
15.9
15.9
3
3
3
3
26
26
26
Hole
Diameter
(OD)
mm
26
Minimum
m
5
5
5
5
Maximum
m
50
75
75
75
Equivalent
m
70
95
95
95
Chargeless m
30
30
30
30
Additional Refrigerant Charge
kg/m
see installation manual 4PW21412-1
Installation
Maximum
height difference
m
30.0
30.0
Max. internunit level difference m
0.5
0.5
Heat Insulation
30.0
30.0
0.5
0.5
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Standard
Accessories
Item
Tie-wraps
Quantity
2
2
Item
Quantity
2-1 TECHNICAL SPECIFICATIONS
Casing
Dimensions
Colour
Material
Packing
Unit
Weight
Heat Exchanger
Machine Weight
Gross Weight
Dimensions
Tube type
Fin
Fan
4
2
2
Installation manual
Height
Width
Depth
Height
Width
Depth
mm
mm
mm
mm
mm
mm
kg
kg
mm
Length
Nr of Rows
Fin Pitch
mm
Nr of Passes
Face Area m2
Nr of Stages
Type
Treatment
Type
Discharge direction
Quantity
Air Flow Rate
Cooling
(nominal)
Heating
External static pressure (Max)
Motor
Quantity
Model
Position
m3/min
m3/min
1
1
1
1
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
RZQ250B7W1B
Daikin white
Painted galvanized steel plate
1475
1475
1753
1753
980
980
1055
1055
420
420
860
860
1345
1345
1600
1600
900
900
930
930
320
320
765
765
106
106
225
226
111
111
236
237
857
857
1640
1640
2
2
2
2
1.40
1.40
2.00
2.00
5
5
16
16
1.131
1.131
1.948
1.948
60
60
54
54
Hi-XSS(8)
WF fin
Non-symmetric waffle louvre
Anti-corrosion treatment (PE)
Corrosion resistant
Propeller
Horizontal
Vertical
2
2
1
1
99.0
99.0
175
175
100.0
100.0
175
175
60 Pa in high static pressure
2
2
1
1
KFD-325-70-8A
Brushless DC
Vertical
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS
Motor
Speed (nominal at Steps
230V)
Cooling
rpm
Heating
rpm
Fan
Motor
Output
W
Drive
Compressor
Quantity
Motor
Model
Type
Speed
rpm
Motor
W
Output
Starting Method
Crankcase W
Heater
Motor
Model
Type
Speed
rpm
Motor
W
Output
Starting Method
Crankcase W
Heater
Operation Range Cooling
Min
°CDB
Max
°CDB
Heating
Min
°CWB
Max
°CWB
Sound Level
Cooling
Sound
dBA
(nominal)
Power
Sound
dBA
Pressure
Heating
Sound
dBA
Power
Sound
dBA
Pressure
Sound Level
Cooling
Sound
dBA
(Night quiet)
Pressure
Refrigerant
Type
Charge
kg
Control
Nr of Circuits
Refrigerant Oil
Type
Charged Volume
l
Piping
Liquid (OD)
Quantity
connections
Type
Diameter
mm
(OD)
Gas
Quantity
Type
Diameter
mm
(OD)
Drain
Quantity
Type
Diameter
mm
(OD)
Piping Length
Minimum m
Maximum m
Equivalent m
Chargeless m
Additional Refrigerant Charge kg/m
Installation height Maximum m
difference
Max. internunit level difference m
Heat Insulation
Defrost Method
Defrost Control
Capacity Control Method
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
RZQ250B7W1B
8
782
767
70
8
782
767
70
8
760
825
750
8
760
825
750
Direct drive
1
JT1G-VDYR@T
1
2
JT1G-VDYR@T
Hermetically sealed scroll compressor
2200
2200
2200
2
2
2
Inverter
900~6480
2200
Direct on line
33
33
-
Hermetically sealed scroll compressor
-
-
33
33
ON - OFF
2900
4500
Direct on line
-
-
33
-15.0
50.0
-20.0
15.5
66.0
-15.0
50.0
-20.0
15.5
66.0
-5.0
46.0
-15.0
15.0
-
-5.0
46.0
-15.0
15.0
-
50.0
50.0
-
-
-
-
78.0
78.0
-
-
57.0
57.0
45.0
45.0
-
-
R-410A
4.30
8.00
Expansion valve (electronic type)
1
1
Daphne FVC68D
1.0
1.7 + 1.6
1
1
Flare connection
9.52
9.52
4.30
1
1.0
1
9.52
1
1
3
5
75
95
30
1.7 + 1.6
1
12.7
1
Braze connection
15.9
22.2
22.2
3
-
-
Hole
26
1
1
Flare connection
15.9
9.00
26
30.0
5
5
75
100
95
30
30
see installation manual 4PW21412-1
30.0
30.0
30.0
0.5
0.5
0.5
0.5
5
100
30
Both liquid and gas pipes
Pressure equalising
Sensor for outdoor heat exchanger temperature
Inverter controlled
• Split Sky Air • Outdoor Units
Reversed cycle
Sensor for outdoor heat exchanger temperature
Inverter controlled
5
• Outdoor Units • R410A • RZQ-B
2-1 TECHNICAL SPECIFICATIONS
RZQ125B7W1B
Safety Devices
2
2
Standard
Accessories
Item
Quantity
Item
Quantity
Item
Quantity
2
RZQ200B7W1B
2
1
1
Installation manual
1
1
RZQ250B7W1B
High pressure switch
Fan motor driver overload protector
Inverter overload protector
Overcurrent relay
PC board fuse
Installation manual
1
1
Additional refrigerant label
1
1
Connection pipes
4
4
Installation manual
2-2 ELECTRICAL SPECIFICATIONS
Power Supply
RZQ140B7W1B
High pressure switch
Fan motor thermal protector
Fuse
Tie-wraps
RZQ71B8V3B
RZQ100B8V3B
RZQ100B7W1B
RZQ125B8V3B
Name
V3
V3
W1B
V3
Phase
1
1
3N
1
Frequency
Hz
50
50
50
50
230
Voltage
V
230
230
400
Current
Recomended fuses
A
20
32
20
32
Voltage range
Minimum
V
207
207
360
207
Maximum
V
253
253
440
253
Wiring
connections
For Power Supply Remark
see installation manual 4PW21412-1
For connection
with indoor
see installation manual 4PW21412-1
Remark
Power Supply Intake
Outdoor unit only
2-2 ELECTRICAL SPECIFICATIONS
Power Supply
Current
RZQ125B7W1B
RZQ140B7W1B
RZQ200B7W1B
Name
W1B
W1B
W1
W1
Phase
3N
3N
3N~
3N~
Frequency
Hz
50
50
50
50
Voltage
V
400
400
400
400
Nominal running
current
Cooling
A
-
-
refer to electrical data indoor outdoor combination
Heating
A
-
-
refer to electrical data indoor outdoor combination
Starting current (cooling/heating)
Voltage range
Wiring
connections
RZQ250B7W1B
-
-
refer to electrical data indoor outdoor combination
Maximum running current
A
-
-
refer to electrical data indoor outdoor combination
Recomended
fuses
A
20
20
32
32
Minimum
V
360
360
360
360
Maximum
V
440
440
440
440
For Power Supply Quantity
Remark
For connection
with indoor
-
5
see installation manual 4PW21412-1
earth wire included
Quantity
-
4
Remark
see installation manual 4PW21412-1
earth wire included
Power Supply Intake
Outdoor unit only
Notes
See seperate drawings for electrical data
Power supply to the FDQ indoor unit is separate
NOTES
6
1
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
2
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2
RZQ71-125B7
Unit combination
Indoor unit
Outdoor unit
3
Power supply
Voltage range MCA
Hz-volts
TOCA
MFA
Comp.
MSC RLA
OFM
kW
IFM
FLA
kW
FLA
3D048637A
SYMBOLS
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
FLA
kW
NOTES
: Min. Circuit Amps (A)
: Total Over Current Amps (A)
: Max. Fuse Amps (See note 7) (A)
: MSC means the max. current
during the starting of compressor.
(A)
: Rated Load Amps (A)
: Outdoor Fan Motor (A)
: Indoor Fan Motor
: Full Load Amps
: Fan Motor Rated Output (kW)
1
2
3
4
5
6
7
8
RLA is based on the following conditions:
Power supply: 50Hz 230V
Heating
Cooling
Indoor temperature 20.0°CDB
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 7.0°CDB/6.0°CWB
Outdoor temperature 35°CDB
TOCA means the total value of each OC set
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
Maximum allowable voltage unbalance between phases is 2%
MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop
down lists, click the search button. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
7
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2
3
RZQ71-125-140B7
Unit combination
Indoor unit
Outdoor unit
Hz-volts
Power supply
Comp.
Voltage range MCA TOCA MFA MSC RLA
OFM
kW
IFM
FLA
kW
FLA
3D048638A
SYMBOLS
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
FLA
kW
NOTES
: Min. Circuit Amps (A)
: Total Over Current Amps (A)
: Max. Fuse Amps (See note 7) (A)
: MSC means the max. current
during the starting of compressor.
(A)
: Rated Load Amps (A)
: Outdoor Fan Motor (A)
: Indoor Fan Motor
: Full Load Amps
: Fan Motor Rated Output (kW)
1
2
3
4
5
6
7
8
8
RLA is based on the following conditions:
Power supply: 50Hz 230V
Cooling
Heating
Indoor temperature 27°CDB/19°CWB
Indoor temperature 20.0°CDB
Outdoor temperature 35°CDB
Outdoor temperature 7.0°CDB/6.0°CWB
TOCA means the total value of each OC set
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
Maximum allowable voltage unbalance between phases is 2%
MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop
down lists, click the search button. Finally, click on the document title of your choice.
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
3
Electrical data
2
3
RZQ200-250B7
Indoor unit
Unit combination
Outdoor unit
Power supply
Voltage range
Hz-volts
MCA
TOCA
MFA
Comp.
MSC
RLA
OFM
kW
IFM
FLA
kW
FLA
Max. 50Hz 440V
Min. 50Hz 360V
Max. 50Hz 440V
Min. 50Hz 360V
3TW26561-4A
SYMBOLS
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
FLA
kW
NOTES
: Min. Circuit Amps (A)
: Total Over Current Amps (A)
: Max. Fuse Amps (A)
: MSC means the max. current
during the starting of compressor.
(A)
: Rated Load Amps (A)
: Outdoor Fan Motor
: Indoor Fan Motor
: Full Load Amps
: Fan Motor Rated Output (kW)
1
2
3
4
5
6
7
8
RLA is based on the following conditions:
Power supply: 50Hz - 400V
Heating
Cooling
Indoor temperature 20.0°CDB
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 7.0°CDB/6.0°CWB
Outdoor temperature 35°CDB
TOCA means the total value of each OC set
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
Maximum allowable voltage unbalance between phases is 2%
MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
Select wire size based on the larger value of MCA or TOCA
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select
’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the
document title of your choice.
• Split Sky Air • Outdoor Units
9
• Outdoor Units • R410A • RZQ-B
4
Options
2
4
RZQ71∼140B7V3B
Kit name
Name of option
RZQ71B7V3B
RZQ100B8V3B
RZQ125B8V3B
RZQ100B7W1B
Central drain plug
Refrigerant branch piping
RZQ125B7W1B
RZQ140B7W1B
KKPJ5F180
Twin
KHRQ22M20TA7
Triple
-
Double twin
-
Demand adapter kit
KHRQ127H7
-
KHRQ22M20TA7 (3x)
KRP58M51
3TW26739-1
Available options for RZQ200,250B7W1B
Name of option
Central drain pan kit
Refrigerant branch piping
Kit name
RZQ200B7W1B
RZQ250B7W1B
KWC26B280
Twin
Triple
Double twin
KHRQ22M20TA7
KHRQ250H7
KHRQ22M20TA7 (3x)
4TW26569-3
10
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-1
Combination table
2
5
Possible combinations and standard capacity for twin, triple and double twin application
Possible indoor combination
Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
In
In
Double twin
Out
In
In
In
In
RZQ71B8V3B
35-35
(KHRQ22M20TA7)
RZQ100B8V3B
RZQ100B7W1B
50-50
(KHRQ22M20TA7)
35-35-35
(KHRQ127H7)
RZQ125B8V3B
RZQ125B7W1B
60-60
(KHRQ22M20TA7)
50-50-50
(KHRQ127H7)
35-35-35-35
(3x KHRQ22M20TA7)
RZQ140B7W1B
71-71
(KHRQ22M20TA7)
50-50-50
(KHRQ127H7)
35-35-35-35
(3x KHRQ22M20TA7)
In
3TW26739-2
NOTES
1
Possible indoor units: FCQ35-71, FFQ35-60, FHQ35-71, FBQ35-71, FUQ71, FAQ71
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote control that is equipped with the most functions as the
main unit.
In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
Possible combinations and standard capacity for twin, triple and double twin operation
Possible indoor combination
Simultaneous operation
Outdoor models
Twin
Triple
Out
Out
In
In
In
In
Double twin
Out
In
In
In
In
RZQ200B7W1B
100-100
(KHRQ22M20TA7)
60-60-60
71-71-71
(KHRQ250H7)
50-50-50-50
(3x KHRQ22M20TA7)
RZQ250B7W1B
125-125
(KHRQ22M20TA7)
---
60-60-60-60
(3x KHRQ22M20TA7)
In
3TW26569-2
NOTES
1
Possible indoor units: FCQ50-125, FFQ50-60, FHQ50-125, FBQ50-125, FAQ71-100, FUQ71-125, FDQ125
2
Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room).
3
When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the
main unit.
In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ).
4
Between brackets are the required Refnet kits mentioned, that are necessary to install the combination.
• Split Sky Air • Outdoor Units
11
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ71B8V3B
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity
Cooling capacity
Indoor
EWB
230V [50Hz]
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
25
SHC
(kW)
4.39
4.82
4.80
4.79
4.73
4.66
TC
(kW)
6.47
7.43
7.58
7.66
8.05
8.37
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
6.46
7.20
7.35
7.43
7.81
8.12
30
SHC
(kW)
4.43
4.72
4.71
4.70
4.64
4.58
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
6.66
6.95
7.10
7.17
7.55
7.85
35
SHC
(kW)
4.62
4.61
4.60
4.59
4.54
4.48
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
6.39
6.67
6.82
6.89
7.26
7.55
40
SHC
(kW)
4.49
4.47
4.46
4.46
4.41
4.35
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048602
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB
(heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ71D
19
(0.10)
FCQ71B
18
(0.10)
FBQ71
19
(0.11)
FHQ71
17
(0.10)
FAQ71
19
(0.08)
FUQ71
19
(0.07)
Twin
Model
AFR
(BF)
FCQ35x2
14x2
(0.16x2)
FFQ35x2
10x2
(0.25x2)
FBQ35x2
11.5x2
(0.15x2)
FHQ35x2
13x2
(0.2x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ71D
1.98
1.97
FCQ71B
2.16
2.56
FBQ71
2.14
2.09
FHQ71
2.46
2.67
FAQ71
2.36
2.42
FUQ71
2.21
2.34
Twin
Model
Cooling
Heating
12
FCQ35x2
2.27
2.62
FFQ35x2
2.29
2.64
FBQ35x2
2.25
2.20
FHQ35x2
2.53
2.81
• Split Sky Air • Outdoor Units
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
Caution:
TC and SHC are shown by kW
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ100B8V3B (Pair + Twin/triple)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity
Cooling capacity
Indoor
EWB
230V [50Hz]
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
25
SHC
(kW)
6.19
6.78
6.76
6.75
6.66
6.57
TC
(kW)
9.12
10.5
10.7
10.8
11.3
11.8
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
9.10
10.1
10.4
10.5
11.0
11.4
30
SHC
(kW)
6.25
6.65
6.63
6.62
6.54
6.45
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
9.38
9.79
10.0
10.1
10.6
11.1
35
SHC
(kW)
6.51
6.49
6.48
6.47
6.39
6.30
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
9.00
9.40
9.60
9.71
10.2
10.6
40
SHC
(kW)
6.32
6.30
6.29
6.28
6.21
6.13
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048603
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ100D
30
(0.11)
FCQ100B
28
(0.16)
FBQ100
27
(0.20)
FHQ100
24
(0.14)
FAQ100
23
(0.10)
FUQ100
29
(0.07)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x3
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
FCQ35Bx3
2.78
3.31
FFQ35x3
2.79
3.21
FBQ35x3
3.01
3.16
FHQ35x3
3.32
3.79
Twin
Model
AFR
(BF)
FCQ50Bx2
15x2
(0.16x2)
FFQ50x2
12x2
(0.16x2)
FBQ50x2
14x2
(0.15x2)
FHQ50x2
13x2
(0.1x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ100D
2.44
2.56
FCQ100B
2.64
3.14
FBQ100
2.86
3.00
FHQ100
3.15
3.60
Triple
FAQ100
2.78
3.39
FUQ100
3.12
3.28
Model
Cooling
Heating
Twin
Model
Cooling
Heating
FCQ50Bx2
2.78
3.31
FFQ50x2
2.79
3.21
FBQ50x2
3.01
3.16
FHQ50x2
3.32
3.79
• Split Sky Air • Outdoor Units
13
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ100B7W1B (Pair + Twin/triple)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity
Cooling capacity
Indoor
EWB
400V [50Hz]
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
25
SHC
(kW)
6.19
6.78
6.76
6.75
6.66
6.57
TC
(kW)
9.12
10.5
10.7
10.8
11.3
11.8
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
9.10
10.1
10.4
10.5
11.0
11.4
30
SHC
(kW)
6.25
6.65
6.63
6.62
6.54
6.45
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
9.38
9.79
10.0
10.1
10.6
11.1
35
SHC
(kW)
6.51
6.49
6.48
6.47
6.39
6.30
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
9.00
9.40
9.60
9.71
10.2
10.6
40
SHC
(kW)
6.32
6.30
6.29
6.28
6.21
6.13
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048605
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ100D
30
(0.11)
FCQ100B
28
(0.16)
FBQ100
27
(0.20)
FHQ100
24
(0.14)
FAQ100
23
(0.10)
FUQ100
29
(0.07)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x3
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
FCQ35Bx3
2.78
3.31
FFQ35x3
2.79
3.21
FBQ35x3
3.01
3.16
FHQ35x3
3.32
3.79
Twin
Model
AFR
(BF)
FCQ50Bx2
15x2
(0.16x2)
FFQ50x2
12x2
(0.16x2)
FBQ50x2
14x2
(0.15x2)
FHQ50x2
13x2
(0.1x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ100D
2.44
2.56
FCQ100B
2.64
3.14
FBQ100
2.86
3.00
FHQ100
3.15
3.60
Triple
FAQ100
2.78
3.39
FUQ100
3.12
3.28
Twin
Model
Cooling
Heating
14
FCQ50Bx2
2.78
3.31
FFQ50x2
2.79
3.21
FBQ50x2
3.01
3.16
FHQ50x2
3.32
3.79
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ125B8V3B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
230V [50Hz]
TC
(kW)
11.4
13.1
13.3
13.5
14.2
14.7
25
SHC
(kW)
7.73
8.48
8.45
8.44
8.33
8.21
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
11.4
12.7
12.9
13.1
13.8
14.3
30
SHC
(kW)
7.81
8.32
8.29
8.28
8.18
8.06
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
11.7
12.2
12.5
12.6
13.3
13.8
35
SHC
(kW)
8.14
8.12
8.09
8.08
7.99
7.88
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
11.3
11.8
12.0
12.1
12.8
13.3
40
SHC
(kW)
7.90
7.88
7.86
7.85
7.76
7.67
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048604A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ125D
30
(0.13)
FCQ125B
31
(0.07)
FBQ125
35
(0.14)
FHQ125
30
(0.13)
Model
AFR
(BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
18x2
15x2
19x2
17x2
(0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125
32
(0.07)
FDQ125
45
(0.25)
Twin
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Model
AFR
(BF)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ125D
3.54
3.59
FCQ125B
3.88
4.36
FBQ125
3.98
3.99
Triple
FHQ125
4.45
4.50
FUQ125
4.05
4.36
FDQ125
4.15
3.69
Model
Cooling
Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
Double twin
Twin
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
15
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ125B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Rated point
Capacity range
Cooling capacity
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
400V [50Hz]
TC
(kW)
11.4
13.1
13.3
13.5
14.2
14.7
25
SHC
(kW)
7.73
8.48
8.45
8.44
8.33
8.21
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
11.4
12.7
12.9
13.1
13.8
14.3
30
SHC
(kW)
7.81
8.32
8.29
8.28
8.18
8.06
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
11.7
12.2
12.5
12.6
13.3
13.8
35
SHC
(kW)
8.14
8.12
8.09
8.08
7.99
7.88
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
11.3
11.8
12.0
12.1
12.8
13.3
40
SHC
(kW)
7.90
7.88
7.86
7.85
7.76
7.67
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048606A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ125D
30
(0.13)
FCQ125B
31
(0.07)
FBQ125
35
(0.14)
FHQ125
30
(0.13)
Model
AFR
(BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
18x2
15x2
19x2
17x2
(0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125
32
(0.07)
FDQ125
45
(0.25)
Twin
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Model
AFR
(BF)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ125D
3.54
3.59
FCQ125B
3.88
4.36
FBQ125
3.98
3.99
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
FHQ125
4.45
4.50
FUQ125
4.05
4.36
FDQ125
4.15
3.69
Model
Cooling
Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
Double twin
Twin
16
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ140B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Cooling
Capacity range
Rated point
Cooling capacity
Cooling capacity
Indoor
EWB
EDB
(°C)
(°C)
16.0
18.0
19.0
19.5
22.0
24.0
22
25
27
27
30
32
400V [50Hz]
TC
(kW)
12.8
14.6
15.0
15.1
15.9
16.5
25
SHC
(kW)
8.66
9.50
9.47
9.45
9.33
9.20
CPI
(-)
0.76
0.83
0.84
0.84
0.85
0.85
TC
(kW)
12.7
14.2
14.5
14.7
15.4
16.0
30
SHC
(kW)
8.74
9.31
9.29
9.27
9.16
9.03
Outdoor temp. (°CDB)
CPI
(-)
0.89
0.91
0.91
0.91
0.92
0.93
TC
(kW)
13.1
13.7
14.0
14.1
14.9
15.5
35
SHC
(kW)
9.12
9.09
9.07
9.05
8.95
8.83
CPI
(-)
0.99
1.00
1.00
1.00
1.01
1.02
TC
(kW)
12.6
13.2
13.4
13.6
14.3
14.9
40
SHC
(kW)
8.84
8.82
8.80
8.79
8.69
8.59
CPI
(-)
1.09
1.10
1.10
1.10
1.11
1.12
3D048607
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ140D
30
(0.07)
Model
AFR
(BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2
18x2
19x2
17x2
19x2
19x2
(0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
Twin
(m3/min)
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
Model
Cooling
Heating
FCQ140D
4.65
4.52
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.81
4.86
4.95
4.99
5.52
5.11
5.06
5.69
Double twin
Twin
Model
Cooling
Heating
Model
AFR
(BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2
4.81
4.95
4.99
4.99
4.92
5.52
5.06
5.69
5.05
5.22
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.81
4.86
4.95
4.99
5.52
5.11
5.06
5.69
17
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ200B7W1B (Pair / Twin / Triple / Double twin)
Coefficient of power input. (-)
Cooling
22.4
7.5
Cooling capacity (kW)
Cooling capacity
Indoor
TC
(kW)
20.2
21.3
21.8
22.3
23.4
24.4
°CWB
16
18
19
20
22
24
400V [50Hz]
25
SHC
(kW)
17.0
17.1
17.1
17.1
17.0
16.8
CPI
(-)
0.82
0.83
0.84
0.84
0.85
0.86
TC
(kW)
19.4
20.4
20.9
21.4
22.4
23.4
30
SHC
(kW)
16.3
16.4
16.4
16.4
16.3
16.1
Outdoor temperature (°CDB)
CPI
(-)
0.90
0.91
0.92
0.92
0.94
0.95
TC
(kW)
18.6
19.5
20.0
20.5
21.4
22.4
35
SHC
(kW)
15.5
15.7
15.6
15.6
15.6
15.4
CPI
(-)
0.98
0.99
1.00
1.01
1.02
1.03
TC
(kW)
17.7
18.6
19.1
19.6
20.5
21.4
40
SHC
(kW)
14.8
14.9
14.9
14.9
14.9
14.7
CPI
(-)
1.06
1.07
1.08
1.09
1.10
1.12
3TW26561-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark with * show the max. total capacity at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However, only rated capacity & CPI are guaranteed (maximal values NOT).
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. Rated values are guaranteed. Other values are accurate within an error of 5%.
8. Heating capacity includes capacity drop due to defrost operation.
9. Air flow rate and BF are tabulated below.
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Pair
Model
AFR
(BF)
Triple
FDQ200
69
0.31
Model
AFR
(BF)
Twin
Model
AFR
(BF)
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2
28x2
27x2
24x2
29x2
23x2
(0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)
10. Rated power input of each model is tabulated below.
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3
18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3
(0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)
Double twin
Model
AFR
(BF)
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4
15x4
12x4
14x4
13x4
(0.16x4) (0.16x4) (0.15x4) (0.1x4)
Pair
Model
Cooling
Heating
Triple
FDQ200
6.43
7.54
Model
Cooling
Heating
Twin
Model
Cooling
Heating
18
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2
5.87
6.36
7.00
6.93
6.18
7.16
6.85
8.21
7.48
7.74
• Split Sky Air • Outdoor Units
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3
6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50
7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14
Double twin
Model
Cooling
Heating
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4
6.18
6.20
6.69
7.37
7.54
7.32
7.21
8.65
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-2
Cooling capacity tables
2
5
RZQ250B7W1B (Pair / Twin / Double twin)
Coefficient of power input. (-)
Cooling
28
9.1
Cooling capacity (kW)
Cooling capacity
Indoor
TC
(kW)
25.4
26.6
27.2
27.8
29.0
30.2
°CWB
16
18
19
20
22
24
400V [50Hz]
25
SHC
(kW)
21.5
21.5
21.5
21.4
21.2
20.9
CPI
(-)
0.79
0.80
0.80
0.81
0.81
0.82
TC
(kW)
24.4
25.5
26.1
26.7
27.8
29.0
30
SHC
(kW)
20.7
20.6
20.6
20.5
20.3
20.1
Outdoor temperature (°CDB)
CPI
(-)
0.88
0.89
0.90
0.91
0.92
0.93
TC
(kW)
23.4
24.5
25.0
25.5
26.6
27.7
35
SHC
(kW)
19.8
19.8
19.8
19.7
19.5
19.3
CPI
(-)
0.98
0.99
1.00
1.01
1.02
1.03
TC
(kW)
22.3
23.4
23.9
24.4
25.5
26.5
40
SHC
(kW)
19.0
18.9
19.0
18.9
18.7
18.4
CPI
(-)
1.08
1.09
1.10
1.11
1.12
1.13
3TW26571-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark with * show the max. total capacity at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However, only rated capacity & CPI are guaranteed (maximal values NOT).
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. Rated values are guaranteed. Other values are accurate within an error of 5%.
8. Heating capacity includes capacity drop due to defrost operation.
9. Air flow rate and BF are tabulated below.
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Pair
Model
AFR
(BF)
Double twin
FDQ250
89
0.34
Model
AFR
(BF)
Twin
Model
AFR
(BF)
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4
18x4
15x4
19x4
17x4
(0.1x4) (0.11x4) (0.11x4) (0.2x4)
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2
31x2
35x2
30x2
32x2
45x2
(0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
Double twin
FDQ250
8.30
8.85
Model
Cooling
Heating
Twin
Model
Cooling
Heating
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4
9.08
9.18
9.31
10.41
9.83
9.13
9.00
10.15
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2
8.62
8.84
9.89
9.00
9.22
9.34
8.55
9.64
9.34
7.91
• Split Sky Air • Outdoor Units
19
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ71B8V3B (Pair + Twin)
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity
Heating capacity
Indoor
EDB
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
TC
(kW)
5.14
5.14
5.13
5.13
5.12
5.12
230V [50Hz]
−15
CPI
(-)
1.06
1.10
1.15
1.17
1.19
1.23
TC
(kW)
5.68
5.67
5.67
5.66
5.66
5.65
−10
CPI
(-)
1.12
1.16
1.21
1.23
1.25
1.30
TC
(kW)
6.22
6.21
6.20
6.20
6.19
6.19
−5
Outdoor temp. (°CWB)
CPI
(-)
1.17
1.22
1.27
1.29
1.32
1.36
TC
(kW)
6.75
6.74
6.74
6.73
6.73
6.72
0
CPI
(-)
1.23
1.28
1.33
1.35
1.38
1.43
TC
(kW)
8.02
8.01
8.00
8.00
7.99
7.98
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
8.64
8.62
8.61
8.61
8.60
8.59
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048602
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of
power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is
7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined
as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ71D
19
(0.10)
FCQ71B
18
(0.10)
FBQ71
19
(0.11)
FHQ71
17
(0.10)
FAQ71
19
(0.08)
FUQ71
19
(0.07)
Twin
Model
AFR
(BF)
FCQ35x2
14x2
(0.16x2)
FFQ35x2
10x2
(0.25x2)
FBQ35x2
11.5x2
(0.15x2)
FHQ35x2
13x2
(0.2x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ71D
1.98
1.97
FCQ71B
2.16
2.56
FBQ71
2.14
2.09
FHQ71
2.46
2.67
FAQ71
2.36
2.42
FUQ71
2.21
2.34
Twin
Model
Cooling
Heating
20
FCQ35x2
2.27
2.62
FFQ35x2
2.29
2.64
FBQ35x2
2.25
2.20
FHQ35x2
2.53
2.81
• Split Sky Air • Outdoor Units
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
Caution:
TC and SHC are shown by kW
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ100B8V3B (Pair + Twin/triple)
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity
Heating capacity
Indoor
EDB
230V [50Hz]
−15
TC
(kW)
7.16
7.15
7.15
7.14
7.14
7.13
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
CPI
(-)
1.01
1.05
1.09
1.12
1.14
1.18
TC
(kW)
7.91
7.90
7.89
7.89
7.88
7.87
−10
CPI
(-)
1.07
1.11
1.15
1.17
1.20
1.24
TC
(kW)
8.66
8.65
8.64
8.63
8.63
8.62
−5
Outdoor temp. (°CWB)
CPI
(-)
1.12
1.16
1.21
1.23
1.26
1.30
TC
(kW)
9.41
9.39
9.38
9.38
9.37
9.36
0
CPI
(-)
1.17
1.22
1.27
1.29
1.32
1.36
TC
(kW)
11.2
11.2
11.2
11.2
11.2
11.2
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
12.1
12.1
12.1
12.1
12.0
12.0
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048603
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ100D
30
(0.11)
FCQ100B
28
(0.16)
FBQ100
27
(0.20)
FHQ100
24
(0.14)
FAQ100
23
(0.10)
FUQ100
29
(0.07)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x3
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
FCQ35Bx3
2.78
3.31
FFQ35x3
2.79
3.21
FBQ35x3
3.01
3.16
FHQ35x3
3.32
3.79
Twin
Model
AFR
(BF)
FCQ50Bx2
15x2
(0.16x2)
FFQ50x2
12x2
(0.16x2)
FBQ50x2
14x2
(0.15x2)
FHQ50x2
13x2
(0.1x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ100D
2.44
2.56
FCQ100B
2.64
3.14
FBQ100
2.86
3.00
FHQ100
3.15
3.60
Triple
FAQ100
2.78
3.39
FUQ100
3.12
3.28
Model
Cooling
Heating
Twin
Model
Cooling
Heating
FCQ50Bx2
2.78
3.31
FFQ50x2
2.79
3.21
FBQ50x2
3.01
3.16
FHQ50x2
3.32
3.79
• Split Sky Air • Outdoor Units
21
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ100B7W1B (Pair + Twin/triple)
Coefficient of power input. (-)
Heating
Capacity range
Rated point
Heating capacity
Heating capacity
Indoor
EDB
400V [50Hz]
−15
TC
(kW)
7.16
7.15
7.15
7.14
7.14
7.13
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
CPI
(-)
1.01
1.05
1.09
1.12
1.14
1.18
TC
(kW)
7.91
7.90
7.89
7.89
7.88
7.87
−10
CPI
(-)
1.07
1.11
1.15
1.17
1.20
1.24
TC
(kW)
8.66
8.65
8.64
8.63
8.63
8.62
−5
Outdoor temp. (°CWB)
CPI
(-)
1.12
1.16
1.21
1.23
1.26
1.30
TC
(kW)
9.41
9.39
9.38
9.38
9.37
9.36
0
CPI
(-)
1.17
1.22
1.27
1.29
1.32
1.36
TC
(kW)
11.2
11.2
11.2
11.2
11.2
11.2
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
12.1
12.1
12.1
12.1
12.0
12.0
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048605
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ100D
30
(0.11)
FCQ100B
28
(0.16)
FBQ100
27
(0.20)
FHQ100
24
(0.14)
FAQ100
23
(0.10)
FUQ100
29
(0.07)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
(m3/min)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ35Bx3
14x3
(0.16x3)
FFQ35x3
10x3
(0.25x3)
FBQ35x3
11.5x3
(0.15x3)
FHQ35x3
13x3
(0.2x3)
FCQ35Bx3
2.78
3.31
FFQ35x3
2.79
3.21
FBQ35x3
3.01
3.16
FHQ35x3
3.32
3.79
Twin
Model
AFR
(BF)
FCQ50Bx2
15x2
(0.16x2)
FFQ50x2
12x2
(0.16x2)
FBQ50x2
14x2
(0.15x2)
FHQ50x2
13x2
(0.1x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ100D
2.44
2.56
FCQ100B
2.64
3.14
FBQ100
2.86
3.00
FHQ100
3.15
3.60
Triple
FAQ100
2.78
3.39
FUQ100
3.12
3.28
Twin
Model
Cooling
Heating
22
FCQ50Bx2
2.78
3.31
FFQ50x2
2.79
3.21
FBQ50x2
3.01
3.16
FHQ50x2
3.32
3.79
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ125B8V3B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Capacity range
Heating capacity
Heating capacity
Indoor
EDB
TC
(kW)
8.83
8.82
8.81
8.81
8.80
8.79
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
Rated point
−15
CPI
(-)
1.05
1.10
1.14
1.16
1.18
1.22
TC
(kW)
9.76
9.74
9.73
9.73
9.72
9.71
−10
230V [50Hz]
CPI
(-)
1.11
1.15
1.20
1.22
1.24
1.29
TC
(kW)
10.7
10.7
10.7
10.6
10.6
10.6
−5
Outdoor temp. (°CWB)
CPI
(-)
1.16
1.21
1.26
1.28
1.31
1.35
TC
(kW)
11.6
11.6
11.6
11.6
11.6
11.5
0
CPI
(-)
1.22
1.27
1.32
1.34
1.37
1.42
TC
(kW)
14.0
14.0
14.0
14.0
14.0
14.0
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
15.1
15.1
15.1
15.1
15.1
15.0
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048604A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ125D
30
(0.13)
FCQ125B
31
(0.07)
FBQ125
35
(0.14)
FHQ125
30
(0.13)
Model
AFR
(BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
18x2
15x2
19x2
17x2
(0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125
32
(0.07)
FDQ125
45
(0.25)
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
Model
AFR
(BF)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ125D
3.54
3.59
FCQ125B
3.88
4.36
FBQ125
3.98
3.99
Triple
FHQ125
4.45
4.50
FUQ125
4.05
4.36
FDQ125
4.15
3.69
Model
Cooling
Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
Double twin
Twin
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
23
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ125B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Capacity range
Heating capacity
Heating capacity
Indoor
EDB
TC
(kW)
8.83
8.82
8.81
8.81
8.80
8.79
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
Rated point
−15
CPI
(-)
1.05
1.10
1.14
1.16
1.18
1.22
TC
(kW)
9.76
9.74
9.73
9.73
9.72
9.71
−10
400V [50Hz]
CPI
(-)
1.11
1.15
1.20
1.22
1.24
1.29
TC
(kW)
10.7
10.7
10.7
10.6
10.6
10.6
−5
Outdoor temp. (°CWB)
CPI
(-)
1.16
1.21
1.26
1.28
1.31
1.35
TC
(kW)
11.6
11.6
11.6
11.6
11.6
11.5
0
CPI
(-)
1.22
1.27
1.32
1.34
1.37
1.42
TC
(kW)
14.0
14.0
14.0
14.0
14.0
14.0
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
15.1
15.1
15.1
15.1
15.1
15.0
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048606A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
Model
AFR
(BF)
FCQ125D
30
(0.13)
FCQ125B
31
(0.07)
FBQ125
35
(0.14)
FHQ125
30
(0.13)
Model
AFR
(BF)
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
18x2
15x2
19x2
17x2
(0.1x2) (0.11x2) (0.11x2) (0.2x2)
FUQ125
32
(0.07)
FDQ125
45
(0.25)
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
FCQ50Bx3 FFQ50x3 FBQ35x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
Model
AFR
(BF)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ125D
3.54
3.59
FCQ125B
3.88
4.36
FBQ125
3.98
3.99
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
FHQ125
4.45
4.50
FUQ125
4.05
4.36
FDQ125
4.15
3.69
Model
Cooling
Heating
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
Double twin
Twin
24
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
FCQ60Bx2 FFQ60x2 FBQ60x2 FHQ60x2
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.08
4.13
4.19
4.45
4.59
4.26
4.20
4.74
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ140B7W1B (Pair + Twin / triple / double twin)
Coefficient of power input. (-)
Heating
Rated point
Capacity range
Heating capacity
Heating capacity
Indoor
EDB
TC
(kW)
9.82
9.80
9.79
9.79
9.78
9.77
(°C)
16.O
18.O
20.0
21.O
22.O
24.0
−15
CPI
(-)
1.05
1.10
1.14
1.16
1.18
1.22
TC
(kW)
9.80
10.8
10.8
10.8
10.8
10.8
−10
400V [50Hz]
CPI
(-)
1.11
1.15
1.20
1.22
1.24
1.29
TC
(kW)
11.9
11.8
11.8
11.8
11.8
11.8
−5
Outdoor temp. (°CWB)
CPI
(-)
1.16
1.21
1.26
1.28
1.31
1.35
TC
(kW)
12.9
12.9
12.9
12.8
12.8
12.8
0
CPI
(-)
1.22
1.27
1.32
1.34
1.37
1.42
TC
(kW)
16.0
16.0
16.0
16.0
16.0
16.0
6
CPI
(-)
0.92
0.96
1.00
1.02
1.04
1.08
TC
(kW)
17.3
17.2
17.2
17.2
17.2
17.2
10
CPI
(-)
0.97
1.01
1.05
1.07
1.09
1.13
3D048607
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark j show the max. at standard conditions.
On the figure the mark Q show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. The value contains less than 5% error acording to indoor unit type.
8. Heating capacity include the drop of frost formation.
9. Air flow rate and BF are tabulated below.
Pair
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
FCQ140D
30
(0.07)
Model
AFR
(BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2
18x2
19x2
17x2
19x2
19x2
(0.1x2) (0.11x2) (0.1x2) (0.07x2) (0.08x2)
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Triple
Model
AFR
(BF)
Model
AFR
(BF)
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
15x3
12x3
14x3
13x3
(0.16x3) (0.16x3) (0.15x3) (0.1x3)
Double twin
Twin
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
14x4
10x4
11.5x4
13x4
(0.16x4) (0.25x4) (0.15x4) (0.2x4)
Triple
Model
Cooling
Heating
FCQ140D
4.65
4.52
FCQ50Bx3 FFQ50x3 FBQ50x3 FHQ50x3
4.81
4.86
4.95
4.99
5.52
5.11
5.06
5.69
Double twin
Twin
Model
Cooling
Heating
Model
AFR
(BF)
FCQ71Bx2 FBQ71x2 FHQ71x2 FUQ71x2 FAQ71x2
4.81
4.95
4.99
4.99
4.92
5.52
5.06
5.69
5.05
5.22
• Split Sky Air • Outdoor Units
Model
Cooling
Heating
FCQ35Bx4 FFQ35x4 FBQ35x4 FHQ35x4
4.81
4.86
4.95
4.99
5.52
5.11
5.06
5.69
25
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ200B7W1B (Pair / Twin / Triple / Double twin)
Coefficient of power input. (-)
Heating
8.5
23
23.0
25
30
Heating capacity (kW)
Heating capacity
Indoor
TC
(kW)
14.5
14.4
14.3
14.2
14.1
°CDB
16
18
20
22
24
400V [50Hz]
-15
CPI
(-)
1.17
1.19
1.21
1.23
1.25
TC
(kW)
17.3
17.2
17.1
17.0
16.8
-10
CPI
(-)
1.22
1.25
1.27
1.29
1.31
TC
(kW)
16.9
16.8
16.7
16.6
16.4
-5
Outdoor temperature (°CWB)
CPI
(-)
1.21
1.23
1.25
1.28
1.30
TC
(kW)
18.1
18.0
17.9
17.8
17.6
0
CPI
(-)
1.24
1.26
1.28
1.31
1.33
TC
(kW)
23.3
23.2
23.0
22.8
22.7
6
CPI
(-)
0.97
0.98
1.00
1.02
1.03
TC
(kW)
25.4
25.3
25.1
24.9
24.7
10
CPI
(-)
1.01
1.02
1.04
1.06
1.08
3TW26561-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark with * show the max. total capacity at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However, only rated capacity & CPI are guaranteed (maximal values NOT).
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. Rated values are guaranteed. Other values are accurate within an error of 5%.
8. Heating capacity includes capacity drop due to defrost operation.
9. Air flow rate and BF are tabulated below.
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Pair
Model
AFR
(BF)
Triple
FDQ200
69
0.31
Model
AFR
(BF)
Twin
Model
AFR
(BF)
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2
28x2
27x2
24x2
29x2
23x2
(0.16x2) (0.2x2) (0.14x2) (0.07x2) (0.1x2)
10. Rated power input of each model is tabulated below.
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3
18x3 18x3 15x3 19x3 19x3 17x3 17x3 19x3 19x3
(0.1x3) (0.1x3) (0.11x3) (0.11x3) (0.11x3) (0.2x3) (0.1x3) (0.07x3) (0.08x3)
Double twin
Model
AFR
(BF)
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4
15x4
12x4
14x4
13x4
(0.16x4) (0.16x4) (0.15x4) (0.1x4)
Pair
Model
Cooling
Heating
Triple
FDQ200
6.43
7.54
Model
Cooling
Heating
Twin
Model
Cooling
Heating
26
FCQ100x2 FBQ100x2 FHQ100x2 FUQ100x2 FAQ100x2
5.87
6.36
7.00
6.93
6.18
7.16
6.85
8.21
7.48
7.74
• Split Sky Air • Outdoor Units
FCQ60x3 FCQ71x3 FFQ60x3 FBQ60x3 FBQ71x3 FHQ60x3 FHQ71x3 FUQ71x3 FAQ71x3
6.18 6.18 6.20 6.69 6.69 7.37 7.37 7.30 6.50
7.54 7.54 7.32 7.21 7.21 8.65 8.65 7.88 8.14
Double twin
Model
Cooling
Heating
FCQ50x4 FFQ50x4 FBQ50x4 FHQ50x4
6.18
6.20
6.69
7.37
7.54
7.32
7.21
8.65
• Outdoor Units • R410A • RZQ-B
5
Capacity tables
5-3
Heating capacity tables
2
5
RZQ250B7W1B (Pair / Twin / Double twin)
Coefficient of power input. (-)
Heating
9.1
31. 5
27.0
Heating capacity (kW)
Heating capacity
Indoor
TC
(kW)
16.5
16.4
16.2
16.1
15.9
°CDB
16
18
20
22
24
400V [50Hz]
-15
CPI
(-)
1.04
1.08
1.12
1.16
1.20
TC
(kW)
19.4
19.2
19.0
18.8
18.7
-10
CPI
(-)
1.09
1.14
1.18
1.23
1.27
TC
(kW)
18.7
18.5
18.4
18.2
18.0
-5
Outdoor temperature (°CWB)
CPI
(-)
1.09
1.13
1.18
1.22
1.26
TC
(kW)
19.9
19.7
19.5
19.3
19.2
0
CPI
(-)
1.12
1.17
1.22
1.26
1.31
TC
(kW)
27.5
27.2
27.0
26.8
26.5
6
CPI
(-)
0.92
0.96
1.00
1.04
1.08
TC
(kW)
29.9
29.6
29.3
29.1
28.8
10
CPI
(-)
0.98
1.02
1.06
1.10
1.14
3TW26571-2A
NOTES
SYMBOLS
1. Ratings shown are net capacities which include a deduction for indoor fan motor heat
2. On the figure the mark with * show the max. total capacity at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However, only rated capacity & CPI are guaranteed (maximal values NOT).
3. On the tables Q show rated capacity and rated coefficient of power input.
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB)
Add SHC* to SHC.
5. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
:0m
6. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
7. Rated values are guaranteed. Other values are accurate within an error of 5%.
8. Heating capacity includes capacity drop due to defrost operation.
9. Air flow rate and BF are tabulated below.
AFR:
BF:
EWB:
EDB:
TC:
SHC:
PI:
CPI:
Air flow rate
Bypass factor
Entering wet bulb temp.
Entering dry bulb temp.
Total cooling/heating capacity
Sensible heating capacity
Power input
(comp.+indoor+outdoor fan motor)
Coefficient of power input.
(m3/min)
(°CWB)
(°CDB)
(kW)
(kW)
(kW)
(-)
Caution:
TC and SHC are shown by kW
Pair
Model
AFR
(BF)
Double twin
FDQ250
89
0.34
Model
AFR
(BF)
Twin
Model
AFR
(BF)
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4
18x4
15x4
19x4
17x4
(0.1x4) (0.11x4) (0.11x4) (0.2x4)
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2
31x2
35x2
30x2
32x2
45x2
(0.07x2) (0.14x2) (0.13x2) (0.07x2) (0.25x2)
10. Rated power input of each model is tabulated below.
Pair
Model
Cooling
Heating
Double twin
FDQ250
8.30
8.85
Model
Cooling
Heating
Twin
Model
Cooling
Heating
FCQ60x4 FFQ60x4 FBQ60x4 FHQ60x4
9.08
9.18
9.31
10.41
9.83
9.13
9.00
10.15
FCQ125x2 FBQ125x2 FHQ125x2 FUQ125x2 FDQ125x2
8.62
8.84
9.89
9.00
9.22
9.34
8.55
9.64
9.34
7.91
• Split Sky Air • Outdoor Units
27
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
2
6
RZQ71B7V3B
unit (mm)
Hole for anchor bolt
4-M12
1
2
3
4
5
6
7
8
Gas pipe connection J15.9 flare
Liquid pipe connection - J9.5 flare
Service port (in the unit)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock hole J34)
Control wiring intake (knock hole J27)
Drain outlet
3TW25144-1A
unit (mm)
RZQ100-125-140B7V3B
Hole for anchor bolt
4-M12
1
2
3
4
5
6
7
8
Gas pipe connection J15.9 flare
Liquid pipe connection - J9.5 flare
Service port (in the unit) (2x)
Grounding terminal M5 (in switch box)
Refrigerant piping intake
Power supply wiring intake (knock hole J34)
Control wiring intake (knock hole J27)
Drain outlet
3TW26071-1
28
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
2
6
RZQ200B7
4 - 15 x 22.5 mm Oblong holes
(foundation bolt hole)
(Pitch of foundation bolt holes)
(Pitch of foundation bolt holes)
(Knock out hole)
(Knock out hole)
(for side-routed pipe)
Notes:
1 The dimensions marked with (a) are those with the
installation of the provided pipes.
2 Refer to the installation instructions when the pipes
are routed through the bottom of the unit.
1
2
3
4
5
6
7
8
9
(for front-routed
pipe)
Liquid pipe connection port 9.52 flare connection
Gas pipe connection port 22.2 braze connection
Grounding terminal inside of switch box
Power cord routing hole (side) - J 65
Power cord routing hole (front) - J 45
Power cord routing hole (bottom) - J 60
Power cord routing hole (front) - J 27
Pipe routing hole (front)
Pipe routing hole (bottom) - see note 2
(Knock out hole)
(Knock out hole)
RZQ250B7
3TW26564-2
4 - 15 x 22.5 mm Oblong holes
(foundation bolt hole)
(Pitch of foundation bolt holes)
(Pitch of foundation bolt holes)
(Knock out hole)
(Knock out hole)
(for side-routed pipe)
Notes:
1 The dimensions marked with (a) are those with the
installation of the provided pipes.
2 Refer to the installation instructions when the pipes
are routed through the bottom of the unit.
1
2
3
4
5
6
7
8
9
(for front-routed
pipe)
Liquid pipe connection port 12.7 flare connection
Gas pipe connection port 22.2 braze connection
Grounding terminal inside of switch box
Power cord routing hole (side) - J 65
Power cord routing hole (front) - J 45
Power cord routing hole (bottom) - J 60
Power cord routing hole (front) - J 27
Pipe routing hole (front)
Pipe routing hole (bottom) - see note 2
(Knock out hole)
(Knock out hole)
• Split Sky Air • Outdoor Units
3TW26574-2
29
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-2
Dimensional drawings and accessories
2
6
RZQ200-250B7
3D041017C
30
• Split Sky Air • Outdoor Units
• Outdoor Units • R410A • RZQ-B
6
Dimensional drawing & centre of gravity
6-3
Centre of gravity
2
6
RZQ200-250B7
Center of foundation bolt hole
Center of foundation bolt hole
(oblong hole)
• Split Sky Air • Outdoor Units
Center of foundation bolt hole
Center of foundation bolt
hole (oblong hole)
4TW26569-1
31
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2
7
RZQ71B (Pair)
Electronic expansion
valve
One way valve
One way valve
Filter
One way valve
Service port
5/16″
One way valve
Heat exchanger
Capillary tube
Solenoid valve
Receiver
Strainer
Heat exchanger
4-way valve
Muffler
Low pressure
sensor
Muffler
One way
valve
Field piping J9.5 C1220T-0
Service port
5/16″
Filter
Field piping J15.9 C1220T-0
Compressor
High pressure
switch
Indoor unit
Outdoor unit
Heating
Cooling
Stop valve
(with service port 5/16’ flare)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
3TW26735-1
RZQ100-125-140B (Pair)
One way valve
One way
valve
One way
valve
Heat exchanger
Filter
Solenoid
valve
One way
valve
One way
valve
Capillary
tube
Electronic
expansion
valve
Capillary
tube
Receiver
Strainer
Capillary tube
Service port
5/16″
Heat exchanger
4-way valve
Filter
Low pressure
switch
High pressure
switch
Muffler
Field piping J9.5 C1220T-0
Service port
5/16″
Filter
Field piping J15.9 C1220T-0
Compressor
Indoor unit
Outdoor unit
Stop valve
(with service port 5/16’ flare)
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
32
• Split Sky Air • Outdoor Units
Heating
Cooling
3TW26745-1
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2
7
RZQ200-250B (Pair)
Filter
Capillary
tube
Receiver
Solenoid
valve
Model
RZQ200B
RZQ250B
Check
valve
Check
valve
Filter
Fan
Check Check
valve valve
Electronic expansion
valve
Electronic expansion
valve
Filter
A
9.52
12.70
Heat exchanger pipe
Solenoid
valve
Heat exchanger
4-way valve
High pressure sensor
Pressure
regulating
valve
Filter
Filter
Filter
Compressor
Field piping J A
Compressor
Filter
Capillary
tube
Capillary tube
Indoor heat
exchanger
High pressure
switch
Oil separator
Oil separator
Filter
High pressure switch
Check valve
Low pressure sensor
Solenoid
valve
Field piping J22.20
Fan
Stop valve (with service port on field piping
side J 7.9mm flare connection)
Indoor unit
Outdoor unit
Note: The pipes between the branch and the
indoor units should have the same size as the
indoor connections.
3TW26565-1
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ71B (Twin)
Electronic expansion
valve
One way valve
One way valve
Heat exchanger
Filter
One way valve
Service port
5/16″
Heat exchanger
Capillary
tube
Solenoid valve
Field piping
Filter
One way valve
Receiver
Field piping
Strainer
Indoor unit
4-way valve
Muffler
Low pressure
sensor
Muffler
Heat exchanger
One way
valve
Field piping J9.5
Branch duct
connection
Option
Service port
5/16″
Field piping J15.9
Compressor
Outdoor unit
Field piping
Filter
Indoor unit
Field piping
High pressure
switch
Stop valve
(with service port 5/16’ flare)
Note: 1. The pipes between the branch and the indoor units should have the same
size as the indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
Heating
Cooling
3TW26735-2
33
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2
7
RZQ100-125-140B (Twin)
One way valve
One way
valve
One way
valve
One way
valve
One way
valve
Heat exchanger
Filter
Capillary
tube
Solenoid
valve
Electronic
expansion
valve
Capillary
tube
Receiver
Field piping
Filter
Heat exchanger
Strainer
Capillary tube
Field piping
Service port
5/16″
Indoor unit
4-way valve
Low pressure
switch
Filter
High pressure
switch
Muffler
Heat exchanger
Field piping J9.5
Branch duct
connection
Service port
5/16″
C1220T-0
Option
Field piping J15.9
Compressor
C1220T-0
Outdoor unit
Field piping
Filter
Heating
Cooling
Field piping
Note: 1. The pipes between the branch and the indoor units should have the
same size as the indoor connections.
Stop valve
(with service port 5/16’ flare)
Indoor unit
3TW26745-2
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Twin)
Filter
Capillary
tube
Receiver
Solenoid
valve
Filter
Model
RZQ200B
RZQ250B
Check
valve
Check
valve
Fan
Check Check
valve valve
Electronic expansion
valve
Electronic expansion
valve
Filter
A
9.52
12.70
Heat exchanger pipe
Solenoid
valve
Heat exchanger
4-way valve
High pressure sensor
Pressure
regulating
valve
Filter
Filter
Fan
Capillary
tube
Field piping
Filter
Capillary tube
Compressor
Field piping
High pressure
switch
Oil separator
Filter
High pressure switch
Oil separator
Indoor heat
exchanger
Check valve
Compressor
Option
Indoor heat
exchanger
Low pressure sensor
Field piping J22.20
Stop valve (with service port on
field piping side J 7.9mm flare
connection)
Filter
Field piping J A
Branch pipe
Indoor unit
Solenoid
valve
Outdoor unit
Field piping
Fan
Field piping
Note: The pipes between the branch and the
indoor units should have the same size as the
indoor connections.
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
34
• Split Sky Air • Outdoor Units
3TW26565-2
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2
7
RZQ100-125-140B (Triple)
Indoor unit
Heat exchanger
One way valve
One way
valve
Stop valve
(with service port 5/16’ flare)
Filter
Field piping
Filter
Capillary
tube
Solenoid
valve
Field piping
One way
valve
Heat exchanger
One way
valve
One way
valve
Electronic
expansion
valve
Capillary
tube
Indoor unit
Receiver
Heat exchanger
Strainer
Capillary tube
Service port
5/16″
4-way valve
Field piping J9.5
C1220T-0
Field piping
Filter
Field piping
Indoor unit
Heat exchanger
Filter
Low pressure
switch
High pressure
switch
Muffler
Field piping J15.9
C1220T-0
Service port
5/16″
Branch duct
connection
Option
Compressor
Outdoor unit
Field piping
Filter
Field piping
Heating
Cooling
Note: 1. The pipes between the branch and
the indoor units should have the same size
as the indoor connections.
3TW26745-3
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Triple)
Filter
Model
RZQ200B
RZQ250B
Filter
Heat exchanger pipe
Solenoid
valve
Check
valve
Check
valve
Fan
Check Check
valve valve
Electronic expansion
valve
Electronic expansion
valve
Indoor
heat
exchanger
Filter
A
9.52
12.70
Capillary
tube
Receiver
Solenoid
valve
Heat exchanger
4-way valve
Field piping
High pressure sensor
Pressure
regulating
valve
Check valve
Field piping J A
Field piping
Fan
Field piping
Branch pipe
Indoor unit
Option
Indoor heat
exchanger
Compressor
Capillary
tube
Field piping J22.20
Stop valve (with service port on
field piping side J 7.9mm flare
connection)
Filter
Capillary tube
Filter
High pressure switch
High pressure
switch
Low pressure sensor
Compressor
Filter
Indoor
heat
exchanger
Oil separator
Indoor unit
Filter
Filter
Field piping
Oil separator
Fan
Solenoid
valve
Outdoor unit
Field piping
Fan
Field piping
Indoor unit
Note: The pipes between the branch and the
indoor units should have the same size as the
indoor connections.
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Outdoor Units
3TW26565-3
35
• Outdoor Units • R410A • RZQ-B
7
Piping diagram
2
7
RZQ100-125-140B (Double twin)
Heat
exchanger
Indoor unit
One way
valve
One
way
valve
One way
valve
One
way
Capillary
valve
tube
One way
valve
Field piping
Field piping
Filter
Heat
exchanger
Indoor unit
Filter
Solenoid
valve
Field piping
J9.5
Service port
5/16″
Field piping
Filter
Electronic
expansion
valve
Strainer
Capillary tube
Capillary
tube
Receiver
Field piping
J15.9
Heat exchanger
4-way valve
Field piping
Heat
exchanger
Indoor unit
Field piping J9.5
Branch duct
connection
Filter
C1220T-0
Low
pressure
sensor
High pressure
switch
Option
Service
port
5/16″
Field piping J15.9
Muffler
C1220T-0
Compressor
Field piping
Filter
Field piping
Heat
exchanger
Outdoor unit
Heating
Cooling
Field piping
J9.5
Stop valve
(with service port 5/16’ flare)
Field piping
J15.9
Note: 1. The pipes between the branch and the
indoor units should have the same size as the
indoor connections.
Field piping
Field piping
Filter
3TW26755-4
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
RZQ200-250B (Double twin)
Filter
Solenoid
valve
Field piping
Filter
Check
valve
Check
valve
Fan
Check Check
valve valve
Electronic expansion
valve
Electronic expansion
valve
Indoor unit
Field piping J 9.52
Indoor
heat
exchanger
Heat exchanger pipe
Solenoid
valve
Filter
Field piping
Fan
Model
RZQ200B
RZQ250B
Capillary
tube
A
9.52
12.70
Receiver
Indoor
heat
exchanger
Heat exchanger
Field piping J15.90
4-way valve
Field piping
High pressure sensor
Pressure
regulating
valve
Field piping J A
Compressor
Field piping
Fan
Field piping J22.20
Field piping
Indoor unit
Field piping
J 9.52
Indoor heat
exchanger
Field piping
J15.90
Capillary
tube
Capillary tube
Filter
Option
Low pressure sensor
Stop valve (with service
port on field piping side J
7.9mm flare connection)
Compressor
Filter
High pressure switch
Branch pipe
High pressure
switch
Oil separator
Indoor
heat
exchanger
Oil separator
Indoor unit
Filter
Filter
Check valve
Filter
Field piping
Fan
Solenoid
valve
Outdoor unit
Field piping
Fan
Field piping
Note: The pipes between the branch and the
indoor units should have the same size as the
indoor connections.
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
36
• Split Sky Air • Outdoor Units
3TW26565-4A
• Outdoor Units • R410A • RZQ-B
8
Wiring diagram
2
8
RZQ71B8V3B
Indoor
: Live
: Neutral
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
NOTE 1.
L
N
Outdoor
: Relay connector
Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow /
BRN: Brown / GRN: Green
ON
OFF
NOTES:
1. Refer to the optional manual, for connection
wiring to X6A.
2. Confirm the method of setting the selector
switches (DS1) by service manual. When the
unit is shipped by factory all switches are set
to be off.
El. comp. assy front
A1P
A2P
BS1
C1-C2-C3
DS1
F1U
HAP (A1P)
HAP (A2P)
H1P (A1P)
Printed circuit board
Printed circuit board (INV)
Push button switch (forced defrost / pump down)
Capacitor
Dip switch
Fuse (T6, 3A/250V)
Light emitting diode (service monitor green)
Light emitting diode (service monitor green)
Light emitting diode (service monitor red)
K1M(A2P)
K1R(A1P)
K2R(A1P)
K2R(A2P)
L1R
M1C
M1F
PS
Q1DI
R1-R2
R1T
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay (Y2S)
Magnetic relay
Reactor
Motor compressor
Motor fan
Power circuit
Earth leakage breaker (30mA)
Resistor
Thermistor (air)
R2T
R3T
R4T
R5T
S1PH
S1NPL
RC
TC
V1R
Thermistor (coil)
Thermistor (discharge pipe)
Thermistor (suction pipe)
Thermistor (power module)
Pressure switch (high)
Pressure sensor (low)
Signal receiver circuit
Signal transmission circuit
Power module
V2R-V3R
V1T
X6A
X1M
Y1E
Y1S
Y2S
Z1C, Z2C
Z3C, Z4C
Z1F
View A
Diode module
IGBT
Connector (Option)
Terminal strip
Expansion valve
4-way valve
Solenoid valve
Noise filter
2TW26736-1A
Noise filter (with surge absorber)
RZQ100-125B8V3B
Indoor
: Live
: Neutral
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
NOTE 1.
L
N
Outdoor
: Relay connector
Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow /
BRN: Brown / GRN: Green
ON
OFF
NOTES:
1. Refer to the optional manual, for connection
wiring to X6A.
2. Confirm the method of setting the selector
switches (DS1) by service manual. When the
unit is shipped by factory all switches are set
to be off.
A1P
A2P
BS1
C1-C2-C3
DS1
E1HC
F1U
F2U
F3U
HAP (A1P)
HAP (A2P)
H1P (A1P)
Printed circuit board
Printed circuit board (INV)
Push button switch (forced defrost / pump down)
Capacitor
Dip switch
Crankcase heater
Fuse (T 6,3A/250V)
Fuse
Fuse (B 5A/250V)
Light emitting diode (service monitor green)
Light emitting diode (service monitor green)
Light emitting diode (service monitor red)
K1M(A2P)
K1R(A1P)
K2R(A1P)
K3R(A1P)
K4R (A1P)
L1R
M1C
M1F
PS
Q1DI
R1-R2
R1T
El. comp. assy front
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay
Magnetic relay (E1HC)
Magnetic relay (Y2S)
Reactor
Motor compressor
Motor fan
Power circuit
Earth leakage breaker (30mA)
Resistor
Thermistor (air)
R2T
R3T
R4T
R5T
S1PH
S1NPL
TC
V1R
Thermistor (coil)
Thermistor (discharge pipe)
Thermistor (suction pipe)
Thermistor (power module)
Pressure switch (high)
Pressure sensor (low)
Signal transmission circuit
Power module
• Split Sky Air • Outdoor Units
V2R-V3R
V1T
X6A
X1M
Y1E
Y1S
Y2S
Z1C, Z2C
Z3C, Z4C
Z1F
Z1F
View A
Reactor box
Diode module
IGBT
Connector (Option)
Terminal strip
Expansion valve
4-way valve
Solenoid valve
Noise filter
Noise filter
Noise filter (with surge absorber)
2TW26746-1
37
• Outdoor Units • R410A • RZQ-B
8
Wiring diagram
2
8
RZQ100-125-140B7W1B
Indoor
: Live
: Neutral
: Field wiring
: Protective earth (screw)
: Wire clamp
: Terminal
: Connector
NOTE 1.
L
N
Outdoor
: Relay connector
Colours
BLK: Black / ORG: Orange / BLU: Blue /
WHT: White / RED: Red / YLW:Yellow /
BRN: Brown / GRN: Green
ON
OFF
NOTES:
1. Refer to the optional manual, for connection
wiring to X6A.
2. Confirm the method of setting the selector
switches (DS1) by service manual. When the
unit is shipped by factory all switches are set
to be off.
A1P
A2P
BS1
C1-C2-C3
DS1
F1U (A2P)
F2U
F3U
F4U
HAP (A1P)
HAP (A2P)
H1P (A1P)
Printed circuit board
Printed circuit board (INV)
Push button switch (forced defrost / pump down)
Capacitor
Dip switch
Fuse (T 6,3A/250V)
Fuse (T 6,3A/250V)
Fuse (B 10A/250V)
Fuse (B 10A/250V)
Light emitting diode (service monitor green)
Light emitting diode (service monitor green)
Light emitting diode (service monitor red)
K1M(A2P)
K1R(A1P)
K2R(A1P)
K3R(A1P)
K4R, K5R
L1R
M1C
M1F
PS
Q1DI
R1-R2
RZQ200-250B7
Reactor box
El. comp. assy front
Magnetic contactor
Magnetic relay (Y1S)
Magnetic relay (Y2S)
Magnetic relay (E1HC)
Magnetic relay
Reactor
Motor compressor
Motor fan
Power circuit
Earth leakage breaker (30mA)
Resistor
Power supply
R1T
R2T
R3T
R4T
R5T
S1PH
S1NPL
RC
TC
V1R
Thermistor (air)
Thermistor (coil)
Thermistor (discharge pipe)
Thermistor (suction pipe)
Thermistor (power module)
Pressure switch (high)
Pressure sensor (low)
Signal receiver circuit
Signal transmission circuit
Power module
V2R-V3R
V1T
X6A
X1M
Y1E
Y1S
Y2S
Z1C, Z2C
Z3C, Z4C
Z1F
Z1F
View A
Diode module
IGBT
Connector (Option)
Terminal strip
Expansion valve
4-way valve
Solenoid valve
Noise filter
2TW26766-1
Noise filter
Noise filter (with surge absorber)
Indoor
400V 3N ∼50Hz
Printed circuit board
Main
Inverter
Fan motor
Noise filter
current sensor
Push button switch
Mode, set, return, test, forced defrost
C2-C5,C63,C65 Capacitor
DS1
Dip switch
E1HC, E2HC
Crankcase heater
B ) (A4P)
F1U
Fuse (250V, 5A j
B ) (A1P)
F1U, F2U
Fuse (250V, 10Aj
F5U
Field fuse
H1P-H7P
Pilot lamp (Pilotlamp service monitor - orange)
Prepare test--------Flickering
[H2P] Malfunction detection---Light up
HAP
Pilot lamp (Pilotlamp service monitor - green)
K1
Magnetic relay
K2S
Magnetic relay (M2C)
K2
Magnetic contactor (M1C)
K2M
Magnetic contactor (M2C)
K1R-K7R
Magnetic relay
K1R
K2M (A1P)
K2R
Y1S
K3R
E1HC (A1P)
K4R
E2HC (A1P)
K5R
Y2S
K6R
Y3S
K7R
Y4S
L1R
Reactor
M1C, M2C
Motor compressor
M1F
Motor fan
PS
Power circuit
Q1DI
Earth leakage breaker (max. 30mA)
Q1RP
Phase reversal detect circuit
R10
Resistor (current sensor)
R50, R59
Resistor
R95
Resistor (current limiting)
R1T, R32T
Thermistor
R1T
Air (A1P)
R32T
M2C Discharge
R1T
Fin type (A2P)
R4T
Coil-deicer
R2T
Suction
R5T
Coil-outlet
R31T
M1C Discharge
S1NPH
Pressure sensor (high)
(NOTE 4)
A1P-A5P
A1P
A2P
A3P
A4P
A5P
BS1-BS5
38
ON
XXX = Color of PCB connector
YYY = (Marked) color of wire connector
ZZZ = Color of wire
OFF
(NOTE 4)
(NOTE 4)
Notes:
1. This wiring diagram only applies to the outdoor unit
: Field wiring
2.
3.
: Terminal strip
: Connector
: Terminal
: Protective earth (screw)
4. For use of the option adaptor, how to use BS1 ∼ BS5 and
DS1 switch and connection to X1M(A1P) or X3M refer to
the installation manual.
5. Do not operate the unit by short-circuiting protection
device S1PH, S2PH
6. BLK: Black / WHT: White / RED: Red / BLU: Blue
GRY: Grey / BRN: brown / GRN: Green / YLW: Yellow /
PNK: Pink
Detail of M1C, M2C
S1NPL
S1PH, S2PH
T1A
T1R
V1CP, V2CP
V1R, V2R
V1R
X1M
X2M
X3M
X4M
Pressure sensor (low)
Pressure switch (high)
current sensor
Transformer(230V/20V)
Safety devices input
Power module (A2P)
Power module (A3P)
Terminal strip (Control) (A1P)
Terminal (Power supply indoor)
Terminal (Control)
Terminal strip (Power supply)
Y1E
Electronic expansion valve (Main)
Y2E
Electronic expansion valve (Subcool)
Y1S-Y4S Solenoid valve
Y1S
4-way valve
Y2S
Hot gas
Y3S
Receiver gas purge
Y4S
Liquid pipe
Z1C, Z5C Noise filter (ferrite core)
Z1F
Noise filter (with surge absorber)
Option connectors
X36A
Connector adaptor power supply
• Split Sky Air • Outdoor Units
Front layer
Rear layer
Position in
switch box
2TW26566-1
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2
RZQ71B8V3B - Cooling
Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
3TW26737-1
3TW26737-2
Octave band center frequency (Hz)
NOTES
1
2
3
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
1
2
3
4
Measuring location
(discharge side)
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
Measuring location
(discharge side)
RZQ100B8V3B - Heating
RZQ100B7W1B
Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
3TW26747-1
Octave band center frequency (Hz)
3TW26747-2
NOTES
4
Octave band center frequency (Hz)
NOTES
RZQ100B8V3B - Cooling
RZQ100B7W1B
1
2
3
9
RZQ71B8V3B - Heating
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
1
2
3
Measuring location
(discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
Measuring location
(discharge side)
39
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2
9
RZQ125B8V3B - Heating
RZQ125B7W1B
Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
RZQ125B8V3B - Cooling
RZQ125B7W1B
3TW26757-1
3TW26757-2
Octave band center frequency (Hz)
NOTES
1
2
3
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
1
2
3
Measuring location
(discharge side)
4
3TW26787-2
Octave band center frequency (Hz)
NOTES
40
Measuring location
(discharge side)
Sound pressure level [dB(A)]
3TW26787-1
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
RZQ140B8V3B - Heating
Sound pressure level [dB(A)]
RZQ140B8V3B - Cooling
1
2
3
Octave band center frequency (Hz)
NOTES
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
1
2
3
Measuring location
(discharge side)
• Split Sky Air • Outdoor Units
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
Measuring location
(discharge side)
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-1
Sound pressure spectrum
2
9
Sound pressure level [dB(A)]
RZQ250B7
Sound pressure level [dB(A)]
RZQ200B7
3TW26567-1
3TW26577-1
Octave band center frequency (Hz)
NOTES
1
2
3
4
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition (measured in a
semi-anachoic room)
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Coil
Microphone
1
2
Switchbox
Location of microphone
• Split Sky Air • Outdoor Units
3
4
Data is valid at free field condition (measured in a
semi-anachoic room)
dB(A) = A-weighted sound pressure level (A-scale
according to IEC)
Reference acoustic pressure 0dB = 20μPa
If sound is measured under actual installation
conditions, the measured value will be higher due to
environmental noise and sound reflections.
Coil
Microphone
Switchbox
Location of microphone
41
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-2
Sound power spectrum
2
9
RZQ100B8V3B - Cooling
RZQ100B7W1B
Sound pressure level [dB(A)]
Sound pressure level [dB(A)]
RZQ71B7V3B - Cooling
3TW26737-3
3TW26747-3
Octave band center frequency (Hz)
NOTES
1
2
3
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
1
2
3
4
RZQ125B8V3B - Cooling
RZQ125B7W1B
Sound pressure level [dB(A)]
3TW26787-3
Octave band center frequency (Hz)
NOTES
42
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
RZQ140B8V3B - Cooling
Sound pressure level [dB(A)]
3TW26757-3
1
2
3
4
Octave band center frequency (Hz)
NOTES
Octave band center frequency (Hz)
NOTES
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
• Split Sky Air • Outdoor Units
1
2
3
4
Data is valid at free field condition
Data is valid at nominal conditions.
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic pressure 0dB = 20μPa
• Outdoor Units • R410A • RZQ-B
9
Sound data
9-2
Sound power spectrum
2
Sound power level (dB)
3TW26567-2
3TW26577-2
Octave band center frequency (Hz)
NOTES
1
2
3
9
RZQ250B7
Sound power level (dB)
RZQ200B7
Octave band center frequency (Hz)
NOTES
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic intensity 0dB = 10E-6μW/m2.
Measured according to ISO 3744
• Split Sky Air • Outdoor Units
1
2
3
dB(A) = A-weighted sound pressure level (A-scale according to IEC)
Reference acoustic intensity 0dB = 10E-6μW/m2.
Measured according to ISO 3744
43
Liquid side junction
Suction gas side junction
Liquid side header
Discharge gas side header
10
44
1TW25799-1E
Liquid side junction
10
Closed pipes
Discharge gas side junction
• Outdoor Units • R410A • RZQ-B
Installation
10 - 1 Refnet pipe systems
2
• Split Sky Air • Outdoor Units
Reducers - Expanders
• Outdoor Units • R410A • RZQ-B
10
Installation
10 - 2 Service space
2
10
RZQ71∼140B
A. Non stacked installation
Legend
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the
bottom of the installation
frame to prevent discharged
air from being bypassed.
In these cases, only 2 units can
be installed.
This situation is not allowed.
Figures between ( ) indicate the
dimensions only for the 100-125-140
class models.
B. Stacked installation
2. Obstacles exist in front of the air inlet
1. Obstacles exist in front of the outlet side
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
C. Multiple-row installation
1. Installation of one unit per row
2. Installing multiple units (2 units or more) in
lateral connection per row
Relation of dimensions of H, A, and L are shown in the
table below.
L≤H
H<L
L
0 < L ≤ 1/2 H
1/2 H < L
Installation impossible
A
150 (250)
200 (300)
3TW26739-4
• Split Sky Air • Outdoor Units
45
• Outdoor Units • R410A • RZQ-B
11
Operation range
2
Cooling
RZQ100B7W1B
RZQ100B8V3B
RZQ125B7W1B
RZQ125B8V3B
RZQ140B7W1B
Heating
Allowable range of operation
(warming-up)
Outdoor temp. (°CWB)
Operation range
Allowable range of operation (pull-down)
Model name
RZQ71B8V3B
Indoor temp. (°CWB)
Operation range
RZQ71-100-125-140B
Outdoor temp. (°CDB)
11
Indoor temp. (°CDB)
Notes:
- Depending on operation and installation conditions, the indoor unit can change over to
freeze-up operation (indoor de-icing).
- To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install
the outdoor unit in a location not exposed to wind.
RZQ200-250B7
• Split Sky Air • Outdoor Units
Operation range
Allowable range of operation
(warming-up)
Heating
Outdoor temp. (°CWB)
Allowable range of operation (pull-down)
Operation range
Outdoor temp. (°CDB)
Cooling
Indoor temp. (°CWB)
46
3TW26733-1
Indoor temp. (°CDB)
4TW26566-1
Download PDF