Eycon ™ Visual Supervisor Visual Supervisors

Add to my manuals
5 Pages

advertisement

Eycon ™ Visual Supervisor Visual Supervisors | Manualzz

SERIES

Colour touchscreen display

Peer to peer communications

Modbus master/slave

10/100Mbps

Ethernet

Continuous and sequential control

Multi-setpoint programmer

Batch control

Recipes

USB support

21 CFR Part 11

Data logging

Eycon10 and Eycon20

Visual Supervisors

Specification Sheet

Eycon™10 and Eycon™20 visual supervisors offer integrated colour

TFT LCD display panels and are capable of continuous, sequential and logic control. The open network architecture allows connection to the process interface (T2550) I/O modules, PLCs and other 3rd Party devices. Separating the processing and operator interface from the I/O allows for physical distribution of the modules resulting in reduced wiring costs.

The continuous control strategy is built by interconnecting function blocks, selected from an extensive library.

Sequential strategies are built using the powerful and intuitive

Sequential Function Chart (SFC) configurator.

Auditor

The Auditor option for the Eycon10 and Eycon20 visual supervisors have been designed specifically to aid compliance with FDA regulation

21 CFR part 11 for Electronic Records and Signatures. Tamper resistant electronic data, including time stamped Audit Trails can be viewed, analysed, and printed using the Eurotherm

®

Review software package.

Multi-setpoint program

The Setpoint Program feature enables an operator to select and run a pre-configured Setpoint Program. A preview facility allows the operator to view the program before running it. Once the program is running, the setpoint and achieved process values are plotted on the trend screen. Up to 8 setpoint programs can be run simultaneously.

Batch control

Batch Manager provides comprehensive batch control allowing an operator with suitable access permissions to load, start, hold, restart or abort a batch. The batch status can also be monitored from standard displays. Each batch being processed can be identified by a batch ID entered by the operator or a unique automatically generated batch number. The use of six customisable operator entry fields can be used to further identify the batch data.

• E U R O T H E R M

®

F L E X I B L E S O L U T I O N S •

SPECIFICATION

Environmental performance

Temperature limits Operation: 0 to +50°C

Humidity limits

Protection

Storage: –10 to +85°C

Operation: 5% to 85% RH (non condensing)

Storage: 5% to 95% RH (non condensing)

Bezel and display: IP65

Sleeve (rear of panel): IP20

Shock:

Vibration (10 to 150Hz):

Altitude:

BS EN61010

BS EN60873, Section 9,18

<2000 metres

Approvals

Electromagnetic compatibility CE, (EMC)

Emissions and immunity: BS EN61326

Electrical safety

(BS EN61010): Installation cat. II; pollution degree 2

INSTALLATION CATEGORY II

The rate impulse voltage for equipment on nominal 230V mains is 2500V.

POLLUTION DEGREE 2

Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected

Physical

Panel mounting:

Panel mounting angle:

Eycon10

DIN43700

Vertical

Bezel size: 144 x 144mm.

Panel cutout dimensions: 138 x 138mm (both –0/+1mm)

Depth behind panel: 87.7mm

Eycon20

Weight: 1.5kg

Bezel size: 288 x 288mm

Panel cutout dimensions: 282 x 282mm (both –0/+1.3mm)

Depth behind panel: 70.4mm

Weight: 3.7kg

Operator interface

Type:

Size and resoluion

Colour TFT LCD, with cold cathode backlight, fitted with resistive, analogue, touch panel

Eycon10: 1/4VGA (320 x 240 pixels) 5.5”

Eycon20: XGA (1024 x 768 pixels) 12.1”

Power requirements

Supply voltage:

Power consumed

Operating current:

Inrush current:

Fuse:

19.2 to 28.8V dc (24Vdc nominal)

Eycon10: 20W

Eycon20: 24W

1A max.

10A max.

No user replacable fuses

Ethernet communications

Ethernet port:

Protocols:

Cable

10/100Mbps auto sensing

TCP/IP, FTP, DHCP, BOOTP, MODBUS,

Telnet

Type: CAT5

Maximum length: 100 metres

Termination: RJ45

Serial communications

No. of ports:

Protocol:

Transmission standard:

2

Modbus RTU

Master and slave

EIA422 or EIA485

Back-up battery

Type:

Support time (RTC):

Replacement period:

Stored data:

Poly-carbonmonofluoride/lithium

(BR2330)

1 year min. with unit unpowered

3 years

Hot start parameters

Master I/O comms

Modbus TCP slave:

Modbus TCP master:

Used to talk through only

Slave connections 20 max

Modbus/Jbus (EIA422/485)Slave

Connectors:

Protocol:

Shielded RJ45 connector

MODBUS/JBUS RTU slave

Data rate:

Data format:

MODBUS:

Table length (max.):

Selectable between 1200 and 38,400 baud

8-bits, 1 or 2 stop bits, selectable parity

Data tables 16, configurable as registers or bits

200 registers or 999 bits

Memory allocated to tables: 20000 bytes

Isolation: Functional

Modbus TalkThru

TalkThru is a facility provided on the Eycon Series to enable use of Eurotherm iTools package to configure Modbus slave devices without having to disconnect them from the Eycon.

Continuous database resources

Resource

Continuous Control Database size 128 Kbytes

No. of TEATT’S (External Attachments) 128

No. of Connections 1024

Sequence control resorces

Resources

Sequence Memory Program Data

Sequence Memory SFC Resources

Independent sequence task simultaneously active

SFC actions, including root SFC’s

Steps

Action accociations

Actions

Transitions

112 Kbytes

76 Kbytes

10

100

320

1200

600

450

Setpoint program resources

Resources

Max. Profiled Analogs

Max. Profiled Digitals

Max. Segment per Program

16

32

250

A maximum of eight Setpoint Programs may run simultaneously. The table below shows how the resources are shared across multiple Setpoint Programs.

No. of

Programs

1 Program

2 Programs

4 Programs

8 Programs

No. of

Analogs (Max)

16

16

16

8

No. of

Digitals (Max)

32

32

16

8

No. of

Segments (Max)

250

125

80

40

Data logging

Selected data can be logged periodically (hourly, daily or on demand) to an internal history file. Process variables are placed into history at the configured recording interval. Additionally alarm messages, batch start/stop events are time stamped and placed in to history files when they occur. Archived data (either ASCII or tamper resistant) can then be transferred to a local/remote server via FTP, or a USB storage device. Alternatively archived data can be automatically transferred over the network using Eurotherm Review

Software package.

Data logging storage

Internal archive:

Data format:

Data compression:

Maximum log frequency:

45Mb flash memory

ASCII (.asc) or compressed data (UHH)

Proprietary

1Hz

Universal Serial Bus (USB)

Version:

Devices supported:

Isolation:

1.1 (2.0 devices are compatible)

USB bulk storage devices (‘Memory stick’)

No signal isolation

Eycon10 Visual Supervisor dimensional details

144.0 mm

6.7 mm

87.7 mm

Eycon20 Visual Supervisor dimensional details

288.0 mm

9.6 mm

70.4 mm

CL

Fixing Clip

(one each side)

F1

F4

F2

F5

F3

F6

Protective-conductor terminal (M4)

Panel thickness: Max = 22 mm; Min = 2 mm

Ethernet

Flash card

Serial comms

USB

– – + +

Power

137.5 mm

154.5 mm

170.5 mm

Panel cutout

138 mm x 138 mm

(both -0 + 1 mm)

PANEL MOUNTING DETAILS

Installed panel angle: Vertical panels only

Minimum inter-unit spacing: 50mm. vertical or horizontal

Note: Where multiple units are mounted in close proximity with one another, steps must be taken to ensure that the resulting ambient temperature does not exceed the specified maximum operating temperature of 50 degrees Celsius.

User configurable function keys

A unique feature of the Eycon series is the User definable keys which can be configured as required using the User Screen Editor Software package. As standard the Eycon10 visual supervisor has six (27 for the

Eycon20 visual supervisor) user definable function keys that can be configured to perform specific actions such as navigating between process screens.

CL

Fixing Clip

(one each side)

F1

F10

F19

F2

F11

F20

F3

F12

F21

F4

F13

F22

F5

F14

F23

F6

F15

F24

F7

F16

F25

F8

F17

F26

F9

F18

F27

Panel thickness: Max = 22 mm; Min = 2 mm

Ethernet

Serial

Comms Power

Flash card

– –++

USB

281.4 mm

298.4 mm

314.4 mm

PANEL MOUNTING DETAILS

Installed panel angle: Vertical panels only

Minimum inter-unit spacing: 50mm. vertical or horizontal

Note: Where multiple units are mounted in close proximity with one another, steps must be taken to ensure that the resulting ambient temperature does not exceed the specified maximum operating temperature of 50 degrees Celsius.

Protective-conductor terminal (M4)

Panel cutout = 282 mm x 282 mm

(both -0 + 1.3mm)

Additionally the size of the touch area, as well as the number of active keys required can also be customised by the user. The printed legend behind the touch screen area is also removable and can be customised and replaced as required, providing users with the ability to design their own, unique operator interface.

Ordering code

1 2 3 4 5 6 7 8 9 10 11

Model

Eycon10 Eycon10 1/4 VGA Display with Touchscreen

Eycon20 Eycon20 Full XGA Display with Touchscreen

1

NONE

L01

L02

Software 1

Standard Display and software

Setpoint Program, Recipe & Report Capability

Batch Manager, Setpoint Program, Recipe & Report Capability

2

NONE

AUDIT

3

ELIN

MBMS

Software 2

No Auditor Feature

Auditor Feature - Electronic Records and Signatures

Comms Protocol

LIN Peer to Peer communications includes Modbus Slave

(RTU & TCP)

Modbus Master/Slave - RTU & TCP communicatios

(includes LIN)

4

Blank field not used

Battery

5

NONE

BATT

Battery not fitted

Battery fitted

6

SLV

GRN

BLK

SST

7

EUR

OEM

8

ENG

GER

FRA

CHI

Silver (Standard)

* Eurotherm Green

* Black

* Stainless Steel

Bezel Colour

Eurotherm

OEM

Keyboard

English

* German

* French

* Chinese

Installation Guide Language

9

XXXXX Eurotherm

Label Set

10

TS0

TS1

TS2

TS4

TS8

11

Technical Support

No support included

1 Hour Support

2 Hours Support

4 Hours Support

8 Hours Support

Warranty

XXXXX Standard Warranty

WL005 5 Years Extended Warranty

* Please consult factory

Eurotherm: International sales and service

Understanding and providing local support is a key part of Eurotherm's business. Complementing worldwide Eurotherm offices are a whole range of partners and a comprehensive technical support team… to ensure you get a service you will want to go back to.

AUSTRALIA Sydney

Eurotherm Pty. Ltd.

T (+61 2) 9838 0099

F (+61 2) 9838 9288

E [email protected]

AUSTRIA Vienna

Eurotherm GmbH

T (+43 1) 7987601

F (+43 1) 7987605

E [email protected]

BELGIUM & LUXEMBOURG Moha

Eurotherm S.A/N.V.

T (+32) 85 274080

F (+32) 85 274081

E [email protected]

BRAZIL Campinas-SP

Eurotherm Ltda.

T (+5519) 3707 5333

F (+5519) 3707 5345

E [email protected]

DENMARK Copenhagen

Eurotherm Danmark AS

T (+45 70) 234670

F (+45 70) 234660

E [email protected]

FINLAND Abo

Eurotherm Finland

T (+358) 22506030

F (+358) 22503201

E [email protected]

FRANCE Lyon

Eurotherm Automation SA

T (+33 478) 664500

F (+33 478) 352490

E info.

[email protected]

GERMANY Limburg

Eurotherm Deutschland GmbH

T (+49 6431) 2980

F (+49 6431) 298119

E [email protected]

HONG KONG & CHINA

Eurotherm Limited North Point

T (+85 2) 28733826

F (+85 2) 28700148

E [email protected]

Guangzhou Office

T (+86 20) 8755 5099

F (+86 20) 8755 5831

E [email protected]

Beijing Office

T (+86 10) 6567 8506

F (+86 10) 6567 8509

E [email protected]

Shanghai Office

T (+86 21) 6145 1188

F (+86 21) 6145 1187

E [email protected]

INDIA Chennai

Eurotherm India Limited

T (+91 44) 24961129

F (+91 44) 24961831

E [email protected]

IRELAND Dublin

Eurotherm Ireland Limited

T (+353 1) 4691800

F (+353 1) 4691300

E [email protected]

ITALY Como

Eurotherm S.r.l

T (+39 31) 975111

F (+39 31) 977512

E [email protected]

KOREA Seoul

Eurotherm Korea Limited

T (+82 31) 2738507

F (+82 31) 2738508

E [email protected]

NETHERLANDS Alphen a/d Rijn

Eurotherm B.V.

T (+31 172) 411752

F (+31 172) 417260

E [email protected]

NORWAY Oslo

Eurotherm A/S

T (+47 67) 592170

F (+47 67) 118301

E [email protected]

POLAND Katowice

Invensys Eurotherm Sp z o.o.

T (+48 32) 2185100

F (+48 32) 2177171

E [email protected]

SPAIN Madrid

Eurotherm España SA

T (+34 91) 6616001

F (+34 91) 6619093

E [email protected]

SWEDEN Malmo

Eurotherm AB

T (+46 40) 384500

F (+46 40) 384545

E [email protected]

SWITZERLAND Wollerau

Eurotherm Produkte (Schweiz) AG

T (+41 44) 7871040

F (+41 44) 7871044

E [email protected]

UNITED KINGDOM Worthing

Eurotherm Limited

T (+44 1903) 268500

F (+44 1903) 265982

E [email protected]

www.eurotherm.co.uk

U.S.A. Leesburg VA

Eurotherm Inc.

T (+1 703) 443 0000

F (+1 703) 669 1300

E [email protected]

www.eurotherm.com

ED53

© Copyright Eurotherm Limited 2007

Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.

All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited.

Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice.

The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.

Part No. HA029353 Issue 2 Eycon10, Eycon20 Specification Sheet Printed in England 01.07

Thank you for reading this data sheet.

For pricing or for further information, please contact us at our UK Office, using the details below.

UK Office

Keison Products,

P.O. Box 2124, Chelmsford, Essex, CM1 3UP, England.

Tel: +44 (0)1245 600560

Fax: +44 (0)1245 808399

Email:

[email protected]

Please note - Product designs and specifications are subject to change without notice. The user is responsible for determining the suitability of this product.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Download PDF

advertisement