- No category
advertisement
SERIES
●
Colour touchscreen display
●
Peer to peer communications
●
Modbus master/slave
●
10/100Mbps
Ethernet
●
Continuous and sequential control
●
Multi-setpoint programmer
●
Batch control
●
●
Recipes
USB support
●
21 CFR Part 11
●
Data logging
Eycon™10 and Eycon™20
Visual Supervisors
Specification Sheet
Eycon™10 and Eycon™20 visual supervisors offer integrated colour
TFT LCD display panels and are capable of continuous, sequential and logic control. The open network architecture allows connection to the process interface (T2550) I/O modules, PLCs and other 3rd Party devices. Separating the processing and operator interface from the I/O allows for physical distribution of the modules resulting in reduced wiring costs.
The continuous control strategy is built by interconnecting function blocks, selected from an extensive library.
Sequential strategies are built using the powerful and intuitive
Sequential Function Chart (SFC) configurator.
Auditor
The Auditor option for the Eycon10 and Eycon20 visual supervisors have been designed specifically to aid compliance with FDA regulation
21 CFR part 11 for Electronic Records and Signatures. Tamper resistant electronic data, including time stamped Audit Trails can be viewed, analysed, and printed using the Eurotherm
®
Review software package.
Multi-setpoint program
The Setpoint Program feature enables an operator to select and run a pre-configured Setpoint Program. A preview facility allows the operator to view the program before running it. Once the program is running, the setpoint and achieved process values are plotted on the trend screen. Up to 8 setpoint programs can be run simultaneously.
Batch control
Batch Manager provides comprehensive batch control allowing an operator with suitable access permissions to load, start, hold, restart or abort a batch. The batch status can also be monitored from standard displays. Each batch being processed can be identified by a batch ID entered by the operator or a unique automatically generated batch number. The use of six customisable operator entry fields can be used to further identify the batch data.
• E U R O T H E R M
®
F L E X I B L E S O L U T I O N S •
SPECIFICATION
Environmental performance
Temperature limits Operation: 0 to +50°C
Humidity limits
Protection
Storage: –10 to +85°C
Operation: 5% to 85% RH (non condensing)
Storage: 5% to 95% RH (non condensing)
Bezel and display: IP65
Sleeve (rear of panel): IP20
Shock:
Vibration (10 to 150Hz):
Altitude:
BS EN61010
BS EN60873, Section 9,18
<2000 metres
Approvals
Electromagnetic compatibility CE, (EMC)
Emissions and immunity: BS EN61326
Electrical safety
(BS EN61010): Installation cat. II; pollution degree 2
INSTALLATION CATEGORY II
The rate impulse voltage for equipment on nominal 230V mains is 2500V.
POLLUTION DEGREE 2
Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected
Physical
Panel mounting:
Panel mounting angle:
Eycon10
DIN43700
Vertical
Bezel size: 144 x 144mm.
Panel cutout dimensions: 138 x 138mm (both –0/+1mm)
Depth behind panel: 87.7mm
Eycon20
Weight: 1.5kg
Bezel size: 288 x 288mm
Panel cutout dimensions: 282 x 282mm (both –0/+1.3mm)
Depth behind panel: 70.4mm
Weight: 3.7kg
Operator interface
Type:
Size and resoluion
Colour TFT LCD, with cold cathode backlight, fitted with resistive, analogue, touch panel
Eycon10: 1/4VGA (320 x 240 pixels) 5.5”
Eycon20: XGA (1024 x 768 pixels) 12.1”
Power requirements
Supply voltage:
Power consumed
Operating current:
Inrush current:
Fuse:
19.2 to 28.8V dc (24Vdc nominal)
Eycon10: 20W
Eycon20: 24W
1A max.
10A max.
No user replacable fuses
Ethernet communications
Ethernet port:
Protocols:
Cable
10/100Mbps auto sensing
TCP/IP, FTP, DHCP, BOOTP, MODBUS,
Telnet
Type: CAT5
Maximum length: 100 metres
Termination: RJ45
Serial communications
No. of ports:
Protocol:
Transmission standard:
2
Modbus RTU
Master and slave
EIA422 or EIA485
Back-up battery
Type:
Support time (RTC):
Replacement period:
Stored data:
Poly-carbonmonofluoride/lithium
(BR2330)
1 year min. with unit unpowered
3 years
Hot start parameters
Master I/O comms
Modbus TCP slave:
Modbus TCP master:
Used to talk through only
Slave connections 20 max
Modbus/Jbus (EIA422/485)Slave
Connectors:
Protocol:
Shielded RJ45 connector
MODBUS/JBUS RTU slave
Data rate:
Data format:
MODBUS:
Table length (max.):
Selectable between 1200 and 38,400 baud
8-bits, 1 or 2 stop bits, selectable parity
Data tables 16, configurable as registers or bits
200 registers or 999 bits
Memory allocated to tables: 20000 bytes
Isolation: Functional
Modbus TalkThru
TalkThru is a facility provided on the Eycon Series to enable use of Eurotherm iTools package to configure Modbus slave devices without having to disconnect them from the Eycon.
Continuous database resources
Resource
Continuous Control Database size 128 Kbytes
No. of TEATT’S (External Attachments) 128
No. of Connections 1024
Sequence control resorces
Resources
Sequence Memory Program Data
Sequence Memory SFC Resources
Independent sequence task simultaneously active
SFC actions, including root SFC’s
Steps
Action accociations
Actions
Transitions
112 Kbytes
76 Kbytes
10
100
320
1200
600
450
Setpoint program resources
Resources
Max. Profiled Analogs
Max. Profiled Digitals
Max. Segment per Program
16
32
250
A maximum of eight Setpoint Programs may run simultaneously. The table below shows how the resources are shared across multiple Setpoint Programs.
No. of
Programs
1 Program
2 Programs
4 Programs
8 Programs
No. of
Analogs (Max)
16
16
16
8
No. of
Digitals (Max)
32
32
16
8
No. of
Segments (Max)
250
125
80
40
Data logging
Selected data can be logged periodically (hourly, daily or on demand) to an internal history file. Process variables are placed into history at the configured recording interval. Additionally alarm messages, batch start/stop events are time stamped and placed in to history files when they occur. Archived data (either ASCII or tamper resistant) can then be transferred to a local/remote server via FTP, or a USB storage device. Alternatively archived data can be automatically transferred over the network using Eurotherm Review
Software package.
Data logging storage
Internal archive:
Data format:
Data compression:
Maximum log frequency:
45Mb flash memory
ASCII (.asc) or compressed data (UHH)
Proprietary
1Hz
Universal Serial Bus (USB)
Version:
Devices supported:
Isolation:
1.1 (2.0 devices are compatible)
USB bulk storage devices (‘Memory stick’)
No signal isolation
Eycon10 Visual Supervisor dimensional details
144.0 mm
6.7 mm
87.7 mm
Eycon20 Visual Supervisor dimensional details
288.0 mm
9.6 mm
70.4 mm
CL
Fixing Clip
(one each side)
F1
F4
F2
F5
F3
F6
Protective-conductor terminal (M4)
Panel thickness: Max = 22 mm; Min = 2 mm
Ethernet
Flash card
Serial comms
USB
– – + +
Power
137.5 mm
154.5 mm
170.5 mm
Panel cutout
138 mm x 138 mm
(both -0 + 1 mm)
PANEL MOUNTING DETAILS
Installed panel angle: Vertical panels only
Minimum inter-unit spacing: 50mm. vertical or horizontal
Note: Where multiple units are mounted in close proximity with one another, steps must be taken to ensure that the resulting ambient temperature does not exceed the specified maximum operating temperature of 50 degrees Celsius.
User configurable function keys
A unique feature of the Eycon series is the User definable keys which can be configured as required using the User Screen Editor Software package. As standard the Eycon10 visual supervisor has six (27 for the
Eycon20 visual supervisor) user definable function keys that can be configured to perform specific actions such as navigating between process screens.
CL
Fixing Clip
(one each side)
F1
F10
F19
F2
F11
F20
F3
F12
F21
F4
F13
F22
F5
F14
F23
F6
F15
F24
F7
F16
F25
F8
F17
F26
F9
F18
F27
Panel thickness: Max = 22 mm; Min = 2 mm
Ethernet
Serial
Comms Power
Flash card
– –++
USB
281.4 mm
298.4 mm
314.4 mm
PANEL MOUNTING DETAILS
Installed panel angle: Vertical panels only
Minimum inter-unit spacing: 50mm. vertical or horizontal
Note: Where multiple units are mounted in close proximity with one another, steps must be taken to ensure that the resulting ambient temperature does not exceed the specified maximum operating temperature of 50 degrees Celsius.
Protective-conductor terminal (M4)
Panel cutout = 282 mm x 282 mm
(both -0 + 1.3mm)
Additionally the size of the touch area, as well as the number of active keys required can also be customised by the user. The printed legend behind the touch screen area is also removable and can be customised and replaced as required, providing users with the ability to design their own, unique operator interface.
Ordering code
1 2 3 4 5 6 7 8 9 10 11
Model
Eycon10 Eycon10 1/4 VGA Display with Touchscreen
Eycon20 Eycon20 Full XGA Display with Touchscreen
1
NONE
L01
L02
Software 1
Standard Display and software
Setpoint Program, Recipe & Report Capability
Batch Manager, Setpoint Program, Recipe & Report Capability
2
NONE
AUDIT
3
ELIN
MBMS
Software 2
No Auditor Feature
Auditor Feature - Electronic Records and Signatures
Comms Protocol
LIN Peer to Peer communications includes Modbus Slave
(RTU & TCP)
Modbus Master/Slave - RTU & TCP communicatios
(includes LIN)
4
Blank field not used
Battery
5
NONE
BATT
Battery not fitted
Battery fitted
6
SLV
GRN
BLK
SST
7
EUR
OEM
8
ENG
GER
FRA
CHI
Silver (Standard)
* Eurotherm Green
* Black
* Stainless Steel
Bezel Colour
Eurotherm
OEM
Keyboard
English
* German
* French
* Chinese
Installation Guide Language
9
XXXXX Eurotherm
Label Set
10
TS0
TS1
TS2
TS4
TS8
11
Technical Support
No support included
1 Hour Support
2 Hours Support
4 Hours Support
8 Hours Support
Warranty
XXXXX Standard Warranty
WL005 5 Years Extended Warranty
* Please consult factory
Eurotherm: International sales and service
Understanding and providing local support is a key part of Eurotherm's business. Complementing worldwide Eurotherm offices are a whole range of partners and a comprehensive technical support team… to ensure you get a service you will want to go back to.
AUSTRALIA Sydney
Eurotherm Pty. Ltd.
T (+61 2) 9838 0099
F (+61 2) 9838 9288
AUSTRIA Vienna
Eurotherm GmbH
T (+43 1) 7987601
F (+43 1) 7987605
BELGIUM & LUXEMBOURG Moha
Eurotherm S.A/N.V.
T (+32) 85 274080
F (+32) 85 274081
BRAZIL Campinas-SP
Eurotherm Ltda.
T (+5519) 3707 5333
F (+5519) 3707 5345
DENMARK Copenhagen
Eurotherm Danmark AS
T (+45 70) 234670
F (+45 70) 234660
FINLAND Abo
Eurotherm Finland
T (+358) 22506030
F (+358) 22503201
FRANCE Lyon
Eurotherm Automation SA
T (+33 478) 664500
F (+33 478) 352490
E info.
GERMANY Limburg
Eurotherm Deutschland GmbH
T (+49 6431) 2980
F (+49 6431) 298119
HONG KONG & CHINA
Eurotherm Limited North Point
T (+85 2) 28733826
F (+85 2) 28700148
Guangzhou Office
T (+86 20) 8755 5099
F (+86 20) 8755 5831
Beijing Office
T (+86 10) 6567 8506
F (+86 10) 6567 8509
Shanghai Office
T (+86 21) 6145 1188
F (+86 21) 6145 1187
INDIA Chennai
Eurotherm India Limited
T (+91 44) 24961129
F (+91 44) 24961831
IRELAND Dublin
Eurotherm Ireland Limited
T (+353 1) 4691800
F (+353 1) 4691300
ITALY Como
Eurotherm S.r.l
T (+39 31) 975111
F (+39 31) 977512
KOREA Seoul
Eurotherm Korea Limited
T (+82 31) 2738507
F (+82 31) 2738508
NETHERLANDS Alphen a/d Rijn
Eurotherm B.V.
T (+31 172) 411752
F (+31 172) 417260
NORWAY Oslo
Eurotherm A/S
T (+47 67) 592170
F (+47 67) 118301
POLAND Katowice
Invensys Eurotherm Sp z o.o.
T (+48 32) 2185100
F (+48 32) 2177171
SPAIN Madrid
Eurotherm España SA
T (+34 91) 6616001
F (+34 91) 6619093
SWEDEN Malmo
Eurotherm AB
T (+46 40) 384500
F (+46 40) 384545
SWITZERLAND Wollerau
Eurotherm Produkte (Schweiz) AG
T (+41 44) 7871040
F (+41 44) 7871044
UNITED KINGDOM Worthing
Eurotherm Limited
T (+44 1903) 268500
F (+44 1903) 265982
www.eurotherm.co.uk
U.S.A. Leesburg VA
Eurotherm Inc.
T (+1 703) 443 0000
F (+1 703) 669 1300
www.eurotherm.com
ED53
© Copyright Eurotherm Limited 2007
Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris and Wonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the prior written permission of Eurotherm limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore be changed without notice.
The information in this document is given in good faith, but is intended for guidance only. Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
Part No. HA029353 Issue 2 Eycon10, Eycon20 Specification Sheet Printed in England 01.07
Thank you for reading this data sheet.
For pricing or for further information, please contact us at our UK Office, using the details below.
UK Office
Keison Products,
P.O. Box 2124, Chelmsford, Essex, CM1 3UP, England.
Tel: +44 (0)1245 600560
Fax: +44 (0)1245 808399
Email:
[email protected]
Please note - Product designs and specifications are subject to change without notice. The user is responsible for determining the suitability of this product.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project