P.O. Box 27
4300 AA Zierikzee
The Netherlands
Tel. +31 111 413656
Fax. +31 111 416919 www.deltapowersupplies.com
DELTA
ELEKTRONIKA B.V.
Euro Cas sette 6 HE high, 14
TE wide (front panel 16 TE).
Is sup plied incl. H15 mat ing con nec tor (faston ver sion),
CL15 and 2 pcs H155.
240S
- Se ries
240 W DC POWER SUP PLIES
Mod els
240 S 24
Volt age range
12 - 15 V
24 V
30 V
Cur rent range
12 A
10 A
8 A
• Output
• Input
• Safety
: Adjustable 12 - 30 V with a screwdriver
or analog programmable by 2 - 5 V.
Factory set at 24 V
: AC 195-265 V, 48-62 Hz, 1.8 Arms
: AC 100-132 V, 48-62 Hz, 3.2 Arms
For DC or operation at 400 Hz
contact factory.
Fuse 4 A T at 230 V, 6.3 A at 110 V
: EN 60950, EN 61010
SELV / PELV
• EMC
• Efficiency
: EN 61204-3 Low voltage DC power supplies
EN 61000-6-3 (EN55022B) Generic Emissions
EN 61000-6-2 Generic Immunity
: 87% at 240 W output.
(max. heat dissipation 36 W)
• Regulation
Load 0-100% : 50 mV (10 mV when using sense points)
Line 198-265V AC : 10 mV
• Ripple + Noise : 5 mV
RMS
, 15 mV pp
(BW=20MHZ)
• Recovery time
• Insulation
Input / output
Input / case
• Output / case
• Hold-up time
• Ambient temperature
Operating
Storage
• Series operation
• Parallel operation
• Alarm circuit
• Temp. coefficient : 5.10
-5
per °C
• Stability during 8 hrs : 3.10
-4
(after 1 hr warm up) • Current limit
• Output impedance : 0.1 Ohm up to 100 kHz
: 200 us after 50-100% load step
: 3750 Vrms (1 min.)
: 2500 Vrms (1 min.)
: 500 V DC
: 20 ms (24V / 10A, 230 V AC input )
: -10 to 50 °C. Above 50 °C derate
current linearly to 20% at 80 °C
: -40 to + 85 °C
: Up to 500 V total voltage
: At 90% of max. current
(Internal current limit switch at low).
The extra positive output terminal,
via build-in schottky diode, separates
the output circuits when units are
operated in parallel.
: A relay contacts changes when the
output drops 10% below the set
value. Gold contact, rating max.
100 mA / 30 V.
: Constant power limit from 30 to 22 V,
constant current below 22 V.
Current limit protects against
continuous overload and short circuit.
DELTA ELEKTRONIKA BV
• OVL
• Mounting
• Remote sensing
: Limits the maximum output voltage
at about 33 V.
: The 240S24 should be mounted
vertically for optimal cooling.
When mounted horizontally, put the
internal current limit switch at low
and keep the ambient temperature
below 40 C.
• Remote programming
• Voltage adjustment
with external potmeter
: The sense points (pin 8 and 10) are
internally connected to the + and -
output (pin 6 and 12), but these links
can be removed when remote sensing
is required.
The voltage drop across the leads plus
the load can never exceed the supply
maximum output rating. For example
at 24 V-8 A it is possible to
compensate 6 V (3V per lead)
because the unit can max. 30 V- 8A.
• MTBF
• Dimensions en weight
: 2 - 5 V between pin 14 an 10 gives
12 - 30 V output (internal switch in
position P).
Programming input is not isolated
(connected to - output).
240 S 24
: is possible if an internal link and a
resistor are removed.
: 1.000.000 hrs
: Height
Width
Depth
Weight
240 mm
71 mm
156 mm
2.0 kg
H 15 con nec tor
Page 1 - 2
Re dun dant par al lel op er a tion with un der volt age alarm.
Out puts are sep a rated by the built-in Schottky se ries di odes.
DATASHEET Rev. Sept. 2012
240 S 24 DELTA ELEKTRONIKA BV
240S24
Front panel F 19/2 for hor i zon tal 19" rack mount ing of one unit
Front panel F 16-6 rev. April 2008
240S24 with bench adapter BA 150
DATASHEET
Two ways of ver ti cal wall moun t ing. Mat ing con nec tor
(H15 with faston or screw con nec tions) can be fixed with sup plied clamp.
Page 1 - 3