Daikin | FTXS42J2V1BFTXS50J2V1B | Daikin Air Conditioner FTXS42J2V1BFTXS50J2V1B

Air Conditioners
Technical Data
Wall mounted unit
EEDEN12-100
FTX-GV
• Indoor Unit • Wall mounted unit • FTX-GV
TABLE OF CONTENTS
FTX-GV
1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
..................................................... 6
Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Piping Diagrams
6
............................................... 5
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Centre of Gravity
5
..................................................... 7
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Diagrams - Single Phase
7
4
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Drawings
4
3
.................................... 8
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sound Pressure Spectrum
• Split - Sky Air • Indoor Unit
........................................... 9
1
• Indoor Unit • Wall mounted unit • FTX-GV
1
Features
ekt tSi n uU - o mr tV o G i ol - l dl X pnaT •ISWF
3-D air flow combines vertical and horizontal auto swing to circulate
a stream of warm or cool air right to the corners of even large spaces
•
1
24 hour timer can be set to start heating or cooling anytime during a
24 hour period
•
1
Indoor unit silent operation: "silent" button on the remote control
lowers the operation sound of the indoor unit by 3dBA
•
Horizontal auto swing moves the discharge flaps left and right for
efficient air and temperature distribution throughout the room
•
Weekly timer can be set to start heating or cooling anytime on a daily
or weekly basis
•
Powerful mode can be selected for rapid heating or cooling; after the
powerful mode is turned off, the unit returns to the preset mode.
•
Titanium apatite photocatalytic air purification filter removes airborne
microscopic particles, powerfully decomposes odours and helps to
prevent the propagation of bacteria, viruses, microbes to ensure a
steady supply of clean air
•
Home leave operation maintains the indoor temperature at your
specified comfort level during absence, thus saving energy
•
Dry programme allows humdity levels to be reduced without
variations in room temperature
•
Movement sensor saves power consumption in unoccupied rooms:
when the room is empty, the unit switches to economy mode after 20
minutes and restarts when a person enters the room.
•
Auto-restart ensures that the unit restarts automatically at the original
settings after power failure
•
Night set mode saves energy by preventing overcooling or
overheating during night time
5 steps
5 steps
2
• Split - Sky Air • Indoor Unit
• Indoor Unit • Wall mounted unit • FTX-GV
2
Specifications
2-1 Technical Specifications
Power input
FTX50GV
FTX60GV
FTX71GV
0.040
0.045
0.045
0.060
Cooling
Nom.
kW
0.034
Heating
Nom.
kW
0.036
mm
290/1,050/238
1
mm
337/1,147/366
kg
12
2
Casing
Colour
White
Dimensions
Unit
Height/Width/Depth
Packed unit
Height/Width/Depth
Weight
Unit
Packed unit
kg
17
Heat exchanger
Length
mm
863
mm
1.4
Rows
Quantity
2
Fin pitch
Stages
Quantity
16
Tube type
ø7 Hi-XD
Fin
Fan
Type
Cross flow fan
Cooling High
Sound pressure level
Refrigerant
m³/min
14.7
16.2
cfm
519
572
614
Nom.
m³/min
12.4
13.6
14.6
cfm
438
480
516
Low
m³/min
10.3
11.4
11.6
cfm
364
403
410
Silent operation
m³/min
9.5
10.2
10.6
17.4
cfm
335
360
374
Heating High
m³/min
16.1
17.4
19.7
cfm
568
614
696
Nom.
m³/min
13.9
15.1
16.9
cfm
491
533
597
Low
m³/min
11.5
12.7
14.3
cfm
406
448
505
Silent operation
m³/min
10.2
11.4
12.7
cfm
360
403
448
Model
ARW30W8P43DK
Speed
Sound power level
ML fin (Multi louver)
Type
Air flow rate
Fan motor
3
Steps
5 + silent, + auto
Cooling High/Medium/Low/
Silent operation
rpm
1,240/1,080/930/860
1,330/1,170/1,010/920
1,410/1,220/1,040/950
Heating High/Medium/Low/
Silent operation
rpm
1,270/1,110/960/870
1,360/1,200/1,040/950
1,520/1,330/1,150/1,040
Output
High
W
Cooling
High
dBA
59
61
Heating
High
dBA
58
60
62
Cooling
High/Nom./Low/Silent operation
dBA
43/39/34/31
45/41/36/33
46/42/37/34
Heating
Super high/High/Nom./Low/
Silent operation
dBA
-/42/38/33/30
-/44/40/35/32
-/46/42/37/34
Type
43
62
R-410A
Temperature control
Microcomputer control
Air direction control
Right, Left, Horizontal, Downward
Air filter
Type
Standard Accessories : Indoor unit fixing screws; Quantity : 2;
Removable / washable / mildew proof
Standard Accessories : Batteries; Quantity : 2;
Standard Accessories : Mounting plate; Quantity : 1;
Standard Accessories : Remote control holder; Quantity : 1;
Standard Accessories : Wireless remote control; Quantity : 1;
Standard Accessories : Installation manual; Quantity : 1;
Standard Accessories : Operation manual; Quantity : 1;
Standard Accessories : Titanium apatite photocatalytic air purification filter; Quantity : 2;
• Split - Sky Air • Indoor Unit
3
• Indoor Unit • Wall mounted unit • FTX-GV
2
Specifications
2-2 Electrical Specifications
Power supply
FTX50GV
FTX60GV
Name
V1
Phase
1
2
1~
Frequency
Hz
50
Voltage
V
220-240
Nominal running current Cooling
(RLA) - 50Hz
Heating
A
0.16 (2) / 0.15 (3) / 0.15 (4) 0.19 (2) / 0.18 (3) / 0.17 (4) 0.21 (2) / 0.20 (3) / 0.19 (4)
A
0.17 (2) / 0.16 (3) / 0.16 (4) 0.21 (2) / 0.20 (3) / 0.19 (4) 0.28 (2) / 0.27 (3) / 0.26 (4)
Current - 60Hz
Nominal running current
A
Wiring connections - 50Hz
For power supply
Current
-
Quantity
-
3
Remark
3 for power supply, 4 for interunit wiring (Earth wire included)
4 for interunit wiring (earth
wire included)
Notes
(1) SL: The silent fan level of the air flow rate setting
(2) 220V
(3) 230V
(4) 240V
4
FTX71GV
• Split - Sky Air • Indoor Unit
• Indoor Unit • Wall mounted unit • FTX-GV
3
Dimensional drawings
3-1
Dimensional Drawings
FTX50-60GV
Rear
Rear
Min. 30
Left
Right
(Space for
maintenance)
Min. 50
Min. 50
(Including
installation plate)
Operation lamp
Flaps
Signal
transmitter
Fan
Infrared
remote control
Drain hose for VP13
Gas pipe ø12.7 Cut
(connection part
(the lenght of pipe outside
I.D. 14.0, O.D. 18.0)
the unit: about 430)
(The hose length
of outside the unit:
Liquid pipe ø 6.4 Cut
about 530)
(the lenght of pipe outside the
unit: about 480)
BLADE ANGELS
Heating
3
Terminal block
with earth
terminal (inside)
Intelligent eye sensor
Timer lamp
Home leave lamp
Horizontal blade
(automatic)
Cooling
(Space for
maintenance)
REQUIRED SPACE
1
Model name
plate
Signal receiver
Indoor unit on/off
switch
Room temp. thermistor
(inside)
Front grille fixing screws
(inside)
3
Air flow (indoor)
(For performance and maintenance)
shows piping direction
(Space for
performance)
The mark
Dry
Wall hole
ø 80 hole
Vertical blade (automatic)
Wall hole for
embedded piping
ø 80 hole
STANDARD LOCATIONS OF WALL HOLES
3D055875A
FTX71GV
Rear
Rear
Min. 30
Left
Air flow (indoor)
(For performance and maintenance)
shows piping direction
Right
(Space for
maintenance)
Min. 50
Min. 50
(Including
installation plate)
Operation lamp
Signal receiver
Indoor unit on/off
switch
Room temp. thermistor
(inside)
Front grille fixing screws
(inside)
Flaps
Signal
transmitter
Infrared
remote control
REQUIRED SPACE
Terminal block
with earth
terminal (inside)
Intelligent eye sensor
Timer lamp
Home leave lamp
Fan
Heating
(Space for
maintenance)
Model name
plate
Drain hose for VP13
Gas pipe ø15.9 Cut
(connection part
(the lenght of pipe outside
I.D. 14.0, O.D. 18.0)
the unit: about 430)
(The hose length
of outside the unit:
Liquid pipe ø 6.4 Cut
about 530)
(the lenght of pipe outside the
unit: about 480)
BLADE ANGELS
Horizontal blade
(automatic)
Cooling
(Space for
performance)
The mark
Dry
Wall hole
ø 80 hole
Vertical blade (automatic)
Wall hole for
embedded piping
ø 80 hole
STANDARD LOCATIONS OF WALL HOLES
3D055876A
• Split - Sky Air • Indoor Unit
5
• Indoor Unit • Wall mounted unit • FTX-GV
4
Centre of gravity
4-1
Centre of Gravity
FTX50-71GV
1
4
4D065971B
B
%
6
• Split - Sky Air • Indoor Unit
• Indoor Unit • Wall mounted unit • FTX-GV
5
Piping diagrams
5-1
Piping Diagrams
FTXS50-60GV
3
Indoor unit
1
(7.9 CuT)
5
Heat exchanger
Thermistor on heat exch.
Cross flow fan
Field piping
(6.4 CuT)
Fan motor
Field piping
(12.7 CuT)
(12.7 CuT)
Refrigerant flow
Cooling
Heating
• Split - Sky Air • Indoor Unit
4D040081Y
7
• Indoor Unit • Wall mounted unit • FTX-GV
6
Wiring diagrams
6-1
Wiring Diagrams - Single Phase
FTX50-71GV
1
Field wiring
RECTIFIER
6
Outdoor
CAUTION
Note that operation will restart
automatically if the main power
supply is turned off and then back
on again.
Transmission
circuit
LED1 LED2 LED3
Intelligent eye
sensor
Indoor
Signal
receiver
infrared
remote
control
FG
FU
H1~H3
H1P~H3P
M1F
M1S, M2S
Frame ground
Fuse
Harness
Pilot lamp
Fan motor
Swing motor
PCB1~PCB5
R1T,R2T
S1~S38
S1W
X1M
Printed circuit board
Thermistor
Connector
Operation switch
Terminal strip
Protective earth
3D038530U
U
8
• Split - Sky Air • Indoor Unit
• Indoor Unit • Wall mounted unit • FTX-GV
7
Sound data
7-1
Sound Pressure Spectrum
3
1
7
FTX60GV
Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Approximate
threshold hearing
for continuous
noise
Octave band center frequency - IEC (Hz)
Octave band center frequency - IEC (Hz)
NOTES
H
45
50Hz
220-240V
Scale
L
36
0.8m
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
NOTES
50Hz
220-240V
Scale
1
Approximate
threshold hearing
for continuous
noise
1
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
H
44
L
35
0.8m
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Cooling
3D051227E
E
• Split - Sky Air • Indoor Unit
9
• Indoor Unit • Wall mounted unit • FTX-GV
7
Sound data
7-1
Sound Pressure Spectrum
FTX71GV
7
Approximate
threshold hearing
for continuous
noise
3D051225D
Octave band center frequency - IEC (Hz)
NOTES
1
NOTES
H
46
50Hz
220-240V
Scale
L
37
0.8m
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
3D051225D
Octave band center frequency - IEC (Hz)
50Hz
220-240V
Scale
Approximate
threshold hearing
for continuous
noise
1
2
3
4
Over All (dB):
(B,G,N is already rectified)
A
Measuring place: measure in anechoic room.
Operation noise differs with operation and ambient conditions.
Location of microphone.
1m
JISC9612
The operation noise
measuring method is in
accordance with JISC9612
H
46
L
37
0.8m
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
1
Heating
Octave band sound pressure level dB (0 dB = 0.0002μ bar)
Cooling
3D051225D
10
• Split - Sky Air • Indoor Unit
Please fill out the requested information
Please fill out the requested information
Daikin Europe N.V. participates in the Eurovent
Certification programme for Air conditioners (AC),
Liquid Chilling Packages (LCP), Air handling units
(AHU) and Fan coil units (FCU), Check ongoing validity
of certificate online: www.eurovent-certification.com
or using: www.certiflash.com”
Daikin products are distributed by:
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has
compiled the content of this leaflet to the best of its knowledge. No express
or implied warranty is given for the completeness, accuracy, reliability or fitness
for particular purpose of its content and the products and services presented
therein. Specifications are subject to change without prior notice. Daikin Europe
N.V. explicitly rejects any liability for any direct or indirect damage, in the
broadest sense, arising from or related to the use and/or interpretation of this
leaflet. All content is copyrighted by Daikin Europe N.V.
EEDEN1 2 - 1 0 0
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
EEDEN12-100 • 05/12 • Copyright © Daikin
The present publication supersedes EEDEN11-100
Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende
Daikin’s unique position as a manufacturer of air
conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This challenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.