Isolex7 Isolated Switch Modules

Isolex7 Isolated Switch Modules
Tempatron Tel: +44(0)1621 859500 Fax: +44(0)1621 855335
Isolex7TM Isolated Switch Modules
Models Available
ISOLEX7 Isolated Switch Module
The Tempatron Isolex7TM isolated switch modules offer a modern low
Product Features
Voltage free switch module
Alternative to air switch and tubing
Full galvanic isolation
Use with momentary or latching switch
16 Amp changeover relay output
110Vac, 230Vac or 24Vdc powered
Power up delay for diagnostic testing
Switch short circuit protection
Onboard LED or optional remote LED
solid state ferromagnetic technology. The devices can be used with a
cost alternative to air switching systems and tubing by using advanced
momentary or latching electrical switch, connected by up to 50 metres
of earthed cable. They are available in 110Vac and 230Vac versions (or
24Vdc to special order) with a 16 Amp changeover relay output.
The sensors pass near zero measurable current through the connected
switch and provide full galvanic isolation between the supply and the
inputs and outputs. These chassis mounting modules measure only
60mm x 30mm, have an integral 5 second power up delay for diagnostic
testing, and an inbuilt safety circuit to automatically de-energise the
output if the connected switch wiring is short circuited. An onboard (or
optional remote) LED indicates relay status and diagnostic conditions.
i
For isolated switching in electrical systems, as an alternative to air switching
Dimensions
Connections
Load Connection
N/O C N/C
30.0
40.0
17.0
60.0
M3
L
RCCB Protected
N
Power Supply
E
K
1 Wire Connection
XTLED
I2
5K6
SW
50m Maximum
I1
9.5
17.0
2 Wire Connection
5K6
SW
50m Maximum
I2
I1
The unit is set for onboard
LED indication
To select remote LED indication
‘spin cut’ the copper pad marked
LED OFF to disconnect the
onboard LED. Connect the remote
LED to the 2-pin XTLED Molex
header (ensuring LED cathode is
connected to pin K).
Link X
Leave in place for momentary (MOM) relay
operation (relay energises whilst the connected
switch is closed).
Cut out for toggle (TOG) relay operation (relay
alternately energises/de-energises each time
the connected switch is closed and opened).
Switch Wiring Diagnostic Test
Set the connected switch to off and switch on the power supply to the unit. The LED
will illuminate and blink for approximately 5 seconds if the length/capacitance of the
switch wiring is within acceptable limits.
All dimensions in mm
Tempatron Email: [email protected] Ordering information
Model
Code
ISOLEX7
Web: www.tempatron.co.uk
Description
Isolated Switch Module
uxiliary Power
A
Code
Description
110V
110Vac
230V
230Vac
24V24Vdc
Example
Continued...
ISOLEX7-230V
Specification
Power Supply Voltages:
110Vac (45-60Hz)
230Vac (45-60Hz)
24Vdc (to special order)
Supply Voltage Variation:
±15%
Burden:
2.5mA nominal (relay off)
10mA nominal (relay on)
Probe Circuit Power:
<30 microwatts
Output:
Single pole changeover relay contact
16A at 240Vac/30Vdc (resistive)
Re-activate Delay:
5 seconds nominal
De-activate Delay:
25ms nominal
Switch Type:
Switch and 5k6ohm 0.25W resistor
Switch Connection:
2 wire earthed or 1 wire double earthed
(see wiring connections)
Output Operation:
Momentary operation or latch on/off operation (selectable by link X)
LED Indication:
Onboard green LED
(2 pin molex connector for remote LED)
Blinking off: Power up test, switch
line signal OK
Blinking on: Relay de-energised
Continuous on: Relay energised
Electrical Connections:
Five screw terminals for power & probes
Three 6.3mm blades for relay output
Mounting:
Two M3 fixing pillars
(40mm vertical x 17mm horizontal)
Operating Temperature:
-20ºC to 65ºC
Enclosure Code:
Case IP00
Weight:
35g
Specification subject to change without notice.
Tempatron: Eltime House, Hall Road, Maldon, Essex, CM9 4NF UK.
Tempatron Industrial Controls is a division of Eltime Ltd.
© Eltime Ltd. Tempatron Isolex7 Isolated Switch Modules 05/2011