Bosch | 583 DDC | Quick Start Guide

Quick Start Guide
560/583 DDC
8733914716(2014/02)
Please refer to the included Hardware User’s Guide and BACview Installation and
Operation Manual for more detailed information on setting up and using the controllers.
2|
8733914716 DDC (2014/02)
Quick Start Guide
Subject to change without prior notice
Quick Start Guide
Table of Contents | 3
Quick Start Guide
CONTENTS
Quick Start Guide – Hardware Setup. . . . . . . . . . . . . . . . . 4
Controller Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Jumper Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
DIP Switch Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Rotary Dial Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Quick Start Guide – Software Setup. . . . . . . . . . . . . . . . . .
Software Configuration Tools . . . . . . . . . . . . . . . . . . . .
Handheld BACview Module Features . . . . . . . . . . . . . .
Virtual BACview Module Features . . . . . . . . . . . . . . . . .
8
8
8
9
Getting Connected. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Configuring Application Parameters using BACview. . . . 11
Modifying Parameter Values Using BACview. . . . . . . . . . 11
Customizing Program Features Using BACview . . . . . . 12
Useful Shortcuts for Tweaking Program Features
Using BACview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Configurable I/O Port Assignments (SW 7.03.06). . . . . . 13
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Typical FHP560 Wiring Diagram. . . . . . . . . . . . . . . . . . . 14
Quick Start Guide
Subject to change without prior notice
8733914716 DDC (2014/02)
4 | Hardware Setup
Quick Start Guide
Quick Start Guide – Hardware Setup
Controller Features
Battery
24VAC
Network
LON Connector
Rotary Switch
DIP Switch
Bank
Jumper Bank
RNET
Connector
Analog
Outputs
(583 only)
Universal
Inputs
IN-1 to IN-6
Digital
Outputs
Part Number
Local Access Port
(see page 10)
FHP 560 Controller
8733914716 DDC (2014/02)
©Copyright 2014 Bosch, Inc All rights reserved
Subject to change without prior notice
Quick Start Guide
Getting Started | 5
Quick Start Guide
GETTING STARTED
JUMPER SETTINGS
Perform a quick visual inspection to ensure the
controller has no external damage and all connectors
are intact. Ensure wiring is per desired application
(see sample FHP 560 wiring diagram on page 14).
Refer to I/O port configuration (page 13) for further
details on wiring inputs and outputs.
Verify that hardware configuration for jumpers
match corresponding Heat Pump system
application. If the controller is networked, ensure
communications jumper is set to EIA-485, unless
the network protocol is BACnet over ARC156.
Input Selection Jumpers for IN-1 & IN-2
(e.g. for a 0-5V CO2 Sensor
connected to IN-1, the jumper
should be set in bottom position)
IN-1 & IN-2 Jumper
Settings Label
Communications Selection Jumper
(i.e. jumper in bottom position for
BACnet over ARC156, or, jumper in top
position for EIA-485 using BACnet over
MS/TP, LON, Modbus, or N2 protocols)
Communications Selection label
In the above diagram, IN-1 and IN-2 are set to Thermistor/Dry
Contact, and Communications is set to BACnet over ARC156.
Quick Start Guide
Subject to change without prior notice
8733914716 DDC (2014/02)
6 | DIP Switch Settings
Quick Start Guide
DIP SWITCH SETTINGS
Verify that hardware configuration for DIP switches
match corresponding network application per the
BAS Port Settings.
BAUD RATES
SW1
SW2
9600
Off
Off
19.2K
Off
On
38.4K
On
Off
76.8K
On
On
SW3
SW4
BACnet® MS/TP
Off
Off
N2
On
Off
Modbus
Off
On
LON Option
On
On
PROTOCOLS
DIP
Switch
Sample DIP switch settings for a
LON Talk Application.
Caution
8733914716 DDC (2014/02)
The LonTalk® card
must be installed
Subject to change without prior notice
Quick Start Guide
Rotary Dial Settings | 7
Quick Start Guide
ROTARY DIAL SETTINGS
Verify hardware configuration for rotary dials matches
corresponding application.
The rotary dials provide the controller address for
identification over a network.
The top dial represents the tens digit of the address,
and the bottom dial represents the ones digit for the
address. See example below:
In the example to the left,
the rotary dial is set to 69.
POWER UP
Apply power to the unit and verify via the power LED
that the controller is receiving 24VAC.
Quick Start Guide
Subject to change without prior notice
8733914716 DDC (2014/02)
8 | Software Setup
Quick Start Guide
Quick Start Guide – Software Setup
Software Configuration Tools
Handheld BACview Module Features
• Hot-keys: used for entering number values.
• Arrow keys: used for navigating the various
BACview screens.
• Soft- keys: four (4) buttons used to access
corresponding Soft-key Labels directly above them.
8733914716 DDC (2014/02)
• Link: an arrow next to a menu item implies
additional screen(s) can be accessed through
that menu. To access a screen navigate to the
menu item and hit the ENTER button. (Note:
selected fields have a bracket [...] around them).
• Contrast screw: used to adjust screen contrast.
Subject to change without prior notice
Quick Start Guide
Virtual BACview Features | 9
Quick Start Guide
Virtual BACview Features
Installation
Interface
• Download and install driver for USB cable (cable p/n
641-261 purchase required) from FHP website
(http://fhp-mfg.com/?p=controls_support).
• Use mouse to select keypad buttons (for
shortcut key combinations, FN = Ctrl on
keyboard e.g. FN+9 is Ctrl+9).
• Verify device is installed in Device Manager and take
note of COM port.
• Screen size (number of rows) can be adjusted
in Virtual BACview at startup.
• Download and install Virtual BACview from FHP
website (http://fhp-mfg.com/?p=controls_support).
Caution
Quick Start Guide
Subject to change without prior notice
All screen shots of BACview used in
this manual are from Virtual BACview
and may not represent the screen
viewed on an actual BACview module,
which is limited to four (4) rows of text.
8733914716 DDC (2014/02)
10 | Getting connected
Quick Start Guide
Getting Connected
Connect the BACview module (or laptop if using
Virtual BACview) to the FHP controller, or to an RS
Sensor connected to the controller.
8733914716 DDC (2014/02)
Subject to change without prior notice
Quick Start Guide
Configuring Application Parameters | 11
Quick Start Guide
CONFIGURING APPLICATION
PARAMETERS USING BACVIEW
Verify that the different parameters of the
controller program match the application of the
Heat Pump system.
3. A 4-character password is required to modify
the Unit Operation Set-point parameters. The
default administrative password for all FHP
controllers is 1111.
1. Maneuver from the Standby Screen to the
HOME screen by pressing any key on the
BACview.
2. Depending on the software version, either
select the ["SETUP] soft-key label (if available)
using the corresponding soft-key:
Sample screen shot from Virtual BACview. Actual screen may vary.
4. Maneuver through the different sub-menus and
change parameters to match your application
using the Arrow Keys and the Soft Keys.
Sample screen shot from Virtual BACview. Actual screen may vary.
or use the arrow-keys to highlight the
["UNIT OPERATION] menu and hit the
ENTER button to access the Unit Operation
screen, then select the ["Stpt] soft-key label:
Sample screen shot from Virtual BACview. Actual screen may vary.
MODIFYING PARAMETER VALUES
USING BACVIEW:
1. Scroll to the desired parameter to highlight it.
2. Hit the Enter button. The selected
parameter should begin to flash and the
modification soft-key labels should
appear at the bottom of the page.
3. Use the [ DECR ] and [ INCR ] soft-keys to
toggle through and select the preferred
parameter value.
Sample screen shot from Virtual BACview. Actual screen may vary.
Caution
Quick Start Guide
4. Use the [ OK ] or [ CANCEL ] soft-keys to save
or discard all changes respectively.
Based on the heat pump application chosen,
additional screens may need to be configured.
Consult the Bacview instruction manual for
detailed information.
Subject to change without prior notice
8733914716 DDC (2014/02)
12 | Customizing Program Features
Quick Start Guide
CUSTOMIZING PROGRAM FEATURES
USING BACVIEW
Verify that the various features of the controller
program match the application of the Heat Pump
system.
Useful Shortcuts for Tweaking Program
Features Using BACview:
8733914716 DDC (2014/02)
+
Change Temperature Offsets
+
Change BACnet ID
+
Modify Tuning Parameters
+
+
Change Inactivity Timeout
Access Alarms
+
Set the Time
Change the User Password
+
+
Access I/O Status & Overrides
Subject to change without prior notice
Quick Start Guide
Configurable I/O Port Assignments | 13
Quick Start Guide
CONFIGURABLE I/O PORT ASSIGNMENTS (SW 7.03.06)
PORT
INPUT PORTS
IN-1
Digital Input Enable
Humidity Sensor (0-5V output)
CO2 Sensor (0-5V output)
Static Pressure Sensor (0-5V output)
IN-2
Humidity Sensor (0-5V output)
Remote Temperature Sensor (OA or Zone)
IN-3*
Leaving Water Temperature Sensor
IN-4*
UPM Input
Filter Switch
Economizer Cooling (Entering Water Temperature Sensor)
Differential Pressure Switch
Secondary Condensate Pan
Boilerless (Entering Water Temperature Sensor)
INPUT EXPANSION MODULE (IEM) COMBINATIONS**
IN-5
IN-6*
EXPANSION PORT 1 (A)
EXPANSION PORT 2 (B)
EXPANSION PORT 3 (C)
Dirty Filter Switch
Fan Status Switch
Valve End Switch
Smoke Detector Switch
Fan Status Switch
Valve End Switch
Dirty Filter Switch
Fan Status Switch
Differential Pressure Switch
Smoke Detector Switch
Fan Status Switch
Dirty Filter Switch
Dirty Filter Switch
Fan Status Switch
Damper End Switch
Smoke Detector Switch
Fan Status Switch
Secondary Drain Pan
Discharge Air Temperature
DIGITAL OUTPUTS
DO-1*
Fan
DO-2*
Reversing Valve
DO-3*
Compressor Stage 1
DO-4*
Compressor Stage 2
DO-5**
Hot Gas Re-Heat (On/Off)
Fresh Air Damper (On/Off)
Heating Stage 1 (Aux Heat)
Boilerless Control (Aux Heat)
Economizer Cooling
Condenser Water Valve
ANALOG OUTPUTS (FHP 583 only)
AO-1
Variable Frequency Drive (Blower) ABB Drive or Equivalent
Mix Air Temperature SCR
AO-2
Modulating Hot Gas Re-Heat Valve
AO-3
Modulating Outside Air Damper
* Non-configurable, factory assigned I/O parameters
** Only one of six possible combinations per application
Quick Start Guide
Subject to change without prior notice
8733914716 DDC (2014/02)
14 | Wiring Diagram
Quick Start Guide
WIRING DIAGRAM
Typical FHP560 Wiring Diagram
8733914716 DDC (2014/02)
Subject to change without prior notice
Quick Start Guide
| 15
Quick Start Guide
Notes
Quick Start Guide
Subject to change without prior notice
8733914716 DDC (2014/02)
601 N.W. 65th Court
Ft. Lauderdale, FL
33309
Phone: 866-642-3198
Fax: 954-776-5529
www.fhp-mfg.com
8733914716
Revised 2014/02