D192D Indicating Circuit Supervision
Module
Features
• Compatible with 12 or 24 V DC
Control/Communicators
• Supervises 12 or 24 V DC Class A, Style Z or
Class B, Style Y indicating circuits
• Supervised signal silencing switch
• Signaling circuit rated at 3 Amps
• Multiple module configurations
• Mounts in panel enclosure
Description
The D192D is an accessory Indicating Circuit
Supervision Module that supervises the wiring to remote signaling devices for open circuit, short circuit, or grounded circuit faults in compliance with UL 864 and NFPA 72.
A silence switch on the D192D disconnects power to the signaling circuit during system tests. With the switch in the OFF (silence) position, the D192D shorts the Control
Panel’s supervisory zone or point, which the panel reports as a trouble condition
The D192D supervises alarm circuits powered by either a Fire Alarm Control Panel (FACP) or an auxiliary power supply. It allows the use of 12 V or 24 V DC signaling devices, depending on the power supply selected.
Several D192D modules can connect to the same supervisory zone or point of the FACP.
Application
The 192D Module provides a supervised connection point between an alarm indicating circuit and the FACP. It supervises the indicating circuit for open, short, and ground condition, any of which the FACP will report as a trouble condition.
In an alarm situation, the FACP signals the D192D to power the indicating circuit, either from the
FACP battery or from an auxiliary power supply.
The D192D uses a DC-DC converter to isolate the signaling circuit from earth ground. A Class B two-wire signaling circuit annunciates with a single ground fault. A Class A four-wire signaling circuit annunciates with simultaneous single open and single ground faults.
Alarm signaling devices used with the D192D must:
• be polarized (DC)
• match the power supply voltage rating
• not have a circuit current in excess of 3 Amps per module
Installation
The D192D mounts inside the FACP enclosure.
Depending on the configuration of the panel, it may attach using existing mounting holes or on a mounting bracket.
Install according to the Radionics Installation
Instructions. Test and maintain equipment according to the Instruction manual, NFPA 72,
Local Codes, and the Authority Having
Jurisdiction. Failure to follow these instructions may result in a failure to initiate an alarm condition. Radionics is not responsible for improperly installed, tested, or maintained products.
1996 Radionics All rights reserved
The Radionics logo is a registered trademark of Radionics,
1800 Abbott Street, Salinas, CA 93901, USA
75-07667-000-A 9/96
D192D Specifications
Page 1 of 2
Specifications
D192D
Input Voltage
(Auxiliary or
External)
Auxiliary Power
Idle Current
Auxiliary Power
Alarm Current
External Power
Input Current
Signaling
Circuit Current
Compatible
External Power
Supplies
12 V
10.0 - 14.0 V DC
1 mA
70 mA
1.25 x Signaling
Circuit Current
0.1 A Minimum
3.0 A Maximum
Alarm-SAF AS-
PS5-BFS-12-UL
•
24 V
17.0 - 28.0 V DC
2 mA
70 mA
1.25 x Signaling
Circuit Current
0.1 A Minimum
3.0 A Maximum
Radionics D9142F
Alarm-SAF AS-
PS5-BFS-24-UL
Dimensions
• Width
• Height
• Depth
3”
5”
2”
Ordering Information
Model
D192D
Description
Indicating Circuit Supervision Module
Class A +
Class B +
Class B -
Class A -
Class A -
Class A +
•
• Class A Circuit Connections
Class B Circuit Connections
The Class B Circuit must have a 33k End of
Line resistor installed in the circuit after the last signaling device..
1996 Radionics All rights reserved
The Radionics logo is a registered trademark of Radionics,
1800 Abbott Street, Salinas, CA 93901, USA
75-07667-000-A 9/96