Q-Bic rgs-QB series Decorative 6, 12 and 24V,

Q-Bic  rgs-QB series Decorative 6, 12 and 24V,
Type:
Project/Location:
Q-BIC
RGS-QB Series
™
Contractor:
Prepared By:
Decorative 6, 12 and 24V,
Thermoplastic Cube Units
Features
•Impact-resistant steel center cabinet contains the battery and charger
•Frosted, thermoplastic light cubes protect light modules against
vandalism while providing visual masking and light diffusion
•Units can be wall or ceiling mounted
•Choice of lamps include mini tungsten wedge base, mini halogen quartz
bi-pin and halogen MR16
•Maintenance-free, sealed lead calcium battery
•120/347VAC standard input
•Fully automatic, solid-state charger with low voltage battery disconnect,
brownout protection, integral test switch and LED AC-On pilot lights
•Also available as a remote fixture; see Remote Fixtures
section of this catalogue
•CSA C22.2 No. 141 certified
Date:
Model No.:
typical specifications
Supply and install a complete emergency lighting system as described herein
and shown on the drawings.
The Lumacell® Smart Diagnostic micro-controller board shall supply the
rated load for a minimum of a 1/2 hour to 87.5% of the rated battery voltage.
The unit shall be rated 120V or 347V, 60 Hz and be CSA listed.
The unit shall have an output of
V.
The charger shall be fully computer tested and its charge voltage factory
set to ± 1% tolerance. Chargers with field-adjusted potentiometers are not
acceptable. A pulse-type charger shall be employed to promote long battery
life and reduce the potential for grid corrosion. The charger shall provide a
continuous high charge to recharge the battery, when the battery is at full
capacity, the charger will shut-off. Periodically the charger shall provide a pulse
of energy to keep the battery topped off. The charger shall be current limited,
temperature compensated, short-circuit proof and reverse polarity protected.
The unit shall be furnished with an electronic lockout circuit, which will connect
the battery when the AC circuit is activated, and an electronic brownout circuit,
which will activate the emergency heads when utility power dips below 75%
of nominal voltage. A low voltage battery protection circuit shall be provided
and will disconnect the battery from the fused output circuit at the end of
discharge. The unit shall self-test for 1 minute every 30 days, 10 minutes on
the 6th month and 30 minutes every 12 months. The unit shall be capable of
full recharge in compliance with CSA specifications. The unit shall be furnished
with a sealed, dust-tight relay, a test switch and diagnostic LED indicator
lights to continuously monitor the status of the unit: Battery Failure, Battery
Disconnected, Charger Failure, Lamp Failure, Service Alarm, AC -“ON”, Charger
High Rate. The unit shall come complete with fully adjustable 12V or 24V/12
W or 20 W quartz halogen lamps. Each lamp shall be housed in an impactresistant polycarbonate cube. The cube lens shall be frosted to diffuse light.
The unit shall be Lumacell® model:
.
Wire guards
460.0097-L
Wall Mount or Ceiling Mount
REPLACEMENT LAMPS
In the Same Family:
- RSQB/RSQBD/RSQB2 Series
Remote Fixtures
p. 133
102
www.lumacell.com
ordering code
type
570.0016-L
Mini tungsten
6V-9W
570.0025-L
Mini tungsten
12V-9W
570.0045-L
Mini tungsten
24V-9W
580.0097-L
MR16, LED
6V-4W
580.0093-L
MR16, LED
12V-4W
580.0104-L
MR16, LED
12V-5W
580.0098-L
MR16, LED
24V-4W
580.0100-L
MR16, LED
24V-6W
580.0095-L
MR16, LED
120V-4W
580.0106-L
MR16, LED
120V-4W
For the complete list, please see the lamp chart on page 144 to 146
voltage/ wattage
Type:
Project/Location:
Q-BIC™
RGS-QB Series
Contractor:
Prepared By:
Date:
Decorative 6, 12 and 24 V,
thermoplastic cube units
Model No.:
Dimensions
Dimensions are approximate and subject to change.
303/4” [78.1 cm]
43/4” [12.1 cm]
43/4” [12.1 cm]
41/2” [11.4 cm]
217/8” [55.6 cm]
POwer consumption and unit rating
model
wattage capacity
ac specs
1h30
2h00
RG36QB
0.10/0.04A
36
21
15
12
6
RG72QB
0.22/0.08A
72
42
30
24
12
RG108QB
0.22/0.08A
108
63
45
36
18
RG180QB
0.22/0.08A
180
105
75
60
30
RG1236QB
0.10/0.04A
36
21
15
12
6
0.15/0.06A
72
42
30
24
12
RG12144QB
0.41/0.14A
144
84
60
48
24
RG12200QB
0.41/0.14A
200
117
83
67
33
RG12288QB
0.41/0.14A
288
168
120
96
48
RG24144QB
0.55/0.20A
144
84
60
48
24
RG24288QB
0.67/0.23A
288
168
120
96
48
RG1272QB
120/347VAC
30min
1h00
4h00
ordering information
Series
capacity
housing
ac voltage
RG= 6V
36= 36W
72= 72W
108= 108W
144= 144W
180= 180W
QB= Q-Bic
Blank= 120/347
VAC input
ZC= 277VAC input
RG12= 12V
36= 36W
72= 72W
144= 144W
200= 200W
288= 288W
RG24= 24V
144= 144W
288= 288W
# of
lamps
2= two
lamps
lamp style/wattage
options
LD1= MR16 LED, 6V-4W
LD7= MR16 LED, 12V-4W
LD9= MR16 LED, 12V-5W
LD10= MR16 LED, 12V-6W
LD13= MR16 LED, 24V-4W
LD14= MR16 LED, 24V-6W
9W= mini tungsten, 6V, 12V, 24V-9W, wedge base
18W= mini tungsten, 12V, 24V-18W, wedge base
8W= mini halogen, 6V, 12V-8W, quartz bi-pin
12W= mini halogen, 6V, 12V-12W, quartz bi-pin
20W= mini halogen, 6V, 12V, 24V-20W,
quartz bi-pin
M6W= MR16 mini halogen, 6V-6W
M10W= MR16 mini halogen, 6V-10W
M12W= MR16 mini halogen, 12V-12W
M20W= MR16mini halogen, 12V, 24V-20W
M35W= MR16mini halogen, 12V, 24V-35W
M50W= M
R16 mini halogen, 12V, 24V-50W
TD= time delay
LC= line cord (120V only)
TL= twistlock plug (120V only)
LD= lamp disconnect
TMBD= DC terminal block
TP= tamper-proof screws
AT= auto-test
ATN= auto-test (non-audible)*
CT= cabtire
RR2= remote test receiver
(remote transmitter needed)
990.0119-L= tamper-proof bit (one bit per order)
TMBK= AC terminal bloc
HH2= remote test transmitter
NEX= NEXUS® system interface**
NEXRF= w
ireless NEXUS® system interface**
* Minimum lamp load required: 20% of unit capacity.
** Consult your sales representative for options available
with NEXUS® system.
EXAMPLE: RG36QB29W